Procurement Section Tender 2014/254 Online Smart UPS (100 ,60 , 30 ) KVA 100 KVA Online Smart UPS with the following Specifications: Qty:1 Item Technology Capacity Phase Input Voltage Input Frequency Output Voltage Output Frequency Output Wave Form Overload Capacity Short Circuit Transfer Time Battery Backup Time (@Full Load) Battery recharge rate Management Interface Software Front panel LED Audible Alarm Audible Noise Operating Temperature Installation Warranty Specifications Online Smart UPS 100 KVA 3 Phase in – 3 Phase out 380V line to line 10% 50Hz 5% 220V Line-to-Neutral, 380V Line-to-Line 3% 50Hz 0.5% Pure Sine-Wave 105% ~ 150% for 30 seconds Auto cut off output no transferring to bypass Zero-cross transfer, <4ms. UPS to bypass or reverse 10 minutes Less than 4 hours to 90% Ethernet (& Optional RS232 ) with support for SNMP V1, V2 Licensed management and monitoring software (using Ethernet and RS-232) System operating status display, input / output voltage and current, frequency, output load %, battery voltage and temperature Utility power fail, low battery, fault, over Charge, overload,… < 55 db 0 °C to 40 °C Onsite installation included 3 years warranty on UPS and batteries Preferred delivery time: Immediatly Procurement Section Tender 2014/254 Online Smart UPS (100 ,60 , 30 ) KVA 60 KVA Online Smart UPS with the following Specifications: Qty:1 Item Technology Capacity Phase Input Voltage Input Frequency Output Voltage Output Frequency Output Wave Form Overload Capacity Short Circuit Transfer Time Battery Backup Time (@Full Load) Battery recharge rate Management Interface Software Front panel LED Audible Alarm Audible Noise Operating Temperature Installation Warranty Specifications Online Smart UPS 60 KVA 3 Phase in – 3 Phase out 380V line to line 10% 50Hz 5% 220V Line-to-Neutral, 380V Line-to-Line 3% 50Hz 0.5% Pure Sine-Wave 105% ~ 150% for 30 seconds Auto cut off output no transferring to bypass Zero-cross transfer, <4ms. UPS to bypass or reverse 10 minutes Less than 4 hours to 90% Ethernet (& Optional RS232 ) with support for SNMP V1, V2 Licensed management and monitoring software (using Ethernet and RS-232) System operating status display, input / output voltage and current, frequency, output load %, battery voltage and temperature Utility power fail, low battery, fault, over Charge, overload,… < 55 db 0 °C to 40 °C Onsite installation included 3 years warranty on UPS and batteries Preferred delivery time: Immediatly Procurement Section Tender 2014/254 Online Smart UPS (100 ,60 , 30 ) KVA 40 KVA Online Smart UPS with the following Specifications: Qty:1 Item Technology Capacity Phase Input Voltage Input Frequency Output Voltage Output Frequency Output Wave Form Overload Capacity Short Circuit Transfer Time Battery Backup Time (@Full Load) Battery recharge rate Management Interface Software Front panel LED Audible Alarm Audible Noise Operating Temperature Installation Warranty Specifications Online Smart UPS 40 KVA 3 Phase in – 3 Phase out 380V line to line 10% 50Hz 5% 220V Line-to-Neutral, 380V Line-to-Line 3% 50Hz 0.5% Pure Sine-Wave 105% ~ 150% for 30 seconds Auto cut off output no transferring to bypass Zero-cross transfer, <4ms. UPS to bypass or reverse 10 minutes Less than 4 hours to 90% Ethernet (& Optional RS232 ) with support for SNMP V1, V2 Licensed management and monitoring software (using Ethernet and RS-232) System operating status display, input / output voltage and current, frequency, output load %, battery voltage and temperature Utility power fail, low battery, fault, over Charge, overload,… < 55 db 0 °C to 40 °C Onsite installation included 3 years warranty on UPS and batteries Preferred delivery time: Immediatly Procurement Section Tender 2014/254 Online Smart UPS (100 ,60 , 30 ) KVA 30 KVA Online Smart UPS with the following Specifications: Qty:1 Item Technology Capacity Phase Input Voltage Input Frequency Output Voltage Output Frequency Output Wave Form Overload Capacity Short Circuit Transfer Time Battery Backup Time (@Full Load) Battery recharge rate Management Interface Software Front panel LED Audible Alarm Audible Noise Operating Temperature Installation Warranty Specifications Online Smart UPS 30 KVA 3 Phase in – 3 Phase out 380V line to line 10% 50Hz 5% 220V Line-to-Neutral, 380V Line-to-Line 3% 50Hz 0.5% Pure Sine-Wave 105% ~ 150% for 30 seconds Auto cut off output no transferring to bypass Zero-cross transfer, <4ms. UPS to bypass or reverse 10 minutes Less than 4 hours to 90% Ethernet (& Optional RS232 ) with support for SNMP V1, V2 Licensed management and monitoring software (using Ethernet and RS-232) System operating status display, input / output voltage and current, frequency, output load %, battery voltage and temperature Utility power fail, low battery, fault, over Charge, overload,… < 55 db 0 °C to 40 °C Onsite installation included 3 years warranty on UPS and batteries Preferred delivery time: Immediatly