Scope-Building-412-a.. - Associated Builders Inc.

advertisement
Demolition Buildings 412 and 413
REF: WO 3297
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD
Revised May 21, 2015
Statement of Work
Revised May 21, 2015
Demolition of Buildings (Trailers) 412 and 413 and remaining infrastructure
Background: Trailers (Buildings) 412 and 413 at NIST Gaithersburg, MD have been determined to be
excess by Governmental authorities. NIST has been directed to dispose of the trailers by those authorities.
The contractor shall provide all labor, material, and other services required to mechanically demolish
buildings (trailers) 412 and 413, remove utilities, remove existing asphalt and provide new asphalt /
parking area. All debris shall be removed from the NIST campus.
Contractor shall field verify all dimensions noted herein and on all contract documents. The word trailer
and building are used interchangeably in this SOW.
1. Location
The project and modular trailers identified as Buildings 412 and 413 at located on the National Institute
of Standards and Technology (NIST) Campus at 100 Bureau Drive, Gaithersburg, MD, 20899.
On campus these buildings are further located to the east of the Building 224 / 226 parking lot in the
Building 224 / 226 loading dock driveway area.
2. General Information






Eight 12’ x 60’ modular / portable trailers configured end to end and side to side to produce two
separate buildings (blocks) with a 24’ x 120’ foot print.
Each 24’ x 120’ section is supported on 16” x 16” masonry piers.
The main steel beams under the trailer are 10” x3” x 3/16 I beam.
Cross members and other associated framing was not identified.
The trailers hitches lay under the edges of the trailers and are made from the same above 10” I
beam.
The trailer axels are lying unattached under the trailers without any wheels or tires.
Wheels and tires are lying underneath trailers.
Page

1
2. a Buildings 412 and 413 consist of
Demolition Buildings 412 and 413
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD









REF: WO 3297
Revised May 21, 2015
Both buildings have aluminum siding and a metal roofing.
Each trailer section has an exterior wall mounted Bard air conditioner.
Each interior room /office has a window and a pressed wood hollow core door.
The walls are lightweight gypsum board with a decorative wallpaper covering.
Flooring is carpeting or tile.
On the south side of the building is a pressure treated wood walkway and ramp.
The walkway is 50’ x 7’ and the ramp facing to the south is 25’ long x 5’ wide.
All electrical and plumbing services have been disconnected from the buildings.
Air conditioner units are NOT empty of refrigerant and oil.
2.b Contractor to Salvage for Government:


The contractor shall salvage and turn over to the Government two of the four Bard air
conditioning units. The COR will identify the two (2) units to the contractor.
The contractor on the other two units NOT to be salvaged shall be disposed of by the contractor.
The contractor shall retrieve the refrigerant from the two units NOT to be salvaged. The
contractor shall submit proof the refrigerant has been recovered by a CFC licensed technician.
3. Standards of demolition and related activity
3-a. General
3-a-1 The demolition of Buildings 412 and 413 involves removal of all of the following: all metal,
wood, tires, and support components, building service infrastructure, and existing asphalt and curb
under the existing buildings.
3-a-2 Contractor is not permitted to burn or explode with dynamite or other similar chemicals to
demolish facilities within this contract.
3-a-4 Contractor is not permitted to remove the structure in whole or in sections off the NIST campus
due to the coordination requirements to coordinate road closures on the NIST property.
3-a-5 Contractor is not permitted to conduct sales or other salvage operations where the general
public would remove materials from the construction area.
The stone drip edge shall be removed and replaced with soil and planted with grass seed.
3-a-8
New asphalt and concrete curb shall be provided after building demolition.
3-a-9
See NIST Specifications attached to this document:

CONCRETE PAVING
Page
3-a-7
2
3-a-6 The existing asphalt and curb shall be removed after building demolition.
Demolition Buildings 412 and 413
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD



REF: WO 3297
Revised May 21, 2015
ASPHALT PAVING
EARTH MOVING
LAWNS, GRASSES
4. Safety
4-a-1

In addition to all other aspects and safety requirements of the contract, the contractor shall:
Prior to any demolition starting the contractor shall independently access the buildings to
ensure all electrical hazards, other services, HVAC units, and plumbing services are rendered
safe, removed and or severed. Any and all Utility outages shall be on a Saturday from 6 AM to 2
PM. Contractor shall request any utility outage 14 days in advance.
5. Scope of Work
5-a
General
5-a-1 The contractor shall have four consecutive days during Monday to Friday to complete the
demolition and removal of all building / trailer complex and wood walkway and ramp known as Buildings
412 and 413.
The four days does not include the asphalt and curb removal. The four consecutive days start after the
first element of the trailer is removed. Interior demolition activities are not counted within the four
consecutive days.
5-a-2 After trailer demolition the asphalt, curb, pipe, and electrical work can commence. The
contractor shall remove all asphalt and curbing in one calendar day.
5-a-3 The contractor assumes all responsibility and ownership of and for buildings 412 and 413,
removed asphalt, and all other debris once any demolition or disassembly of any kind begins.
Page
5-a-5 The contractor shall maintain a clean demolition area actively collecting and disposing of paper,
insulation, or other item that “blow” away from the area as work progresses. Further, the contractor
shall comply with the dust control regulation see paragraph 7.
3
5-a-4 The contractor shall obtain all required permits and authorization to operate his trucks, trailers,
roll off dumpsters, or other transportation / load carrying equipment, or that of others he contracts, on
the city, county, state, and federal roads operated over in the performance of this contract. Contractor
is solely responsible for load covering and any damages to others property during any demolition or
transport of debris.
Demolition Buildings 412 and 413
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD
REF: WO 3297
Revised May 21, 2015
5-a-6 The contractor shall coordinate the start date of demolition with COR and NIST Police to restrict
all access to the demolition area and to coordinate delivery of equipment and traffic control items. The
contractor shall erect a chain link temporary fence (at least 5 feet tall) to keep non-contractor personnel
out of the space.
5-a-7 The contractor, with coordination with NIST police, shall be responsible for demolition area
access and egress control, maintain an accessible area for both Buildings 224 and 226 loading docks,
maintain the driveway area to the area parking lot and loading docks free of metal or other debris.
Contractor shall mechanically sweep the entire demolition area between buildings 224, 226, and the
concourse between buildings 225 and 226 after all building 412 and 413 have been removed and prior
to opening the driveway area to foot or vehicular traffic.
5-a-8 The contractor shall supply all industry standard and recognized mechanical demolition
equipment, trucks, roll-offs, and additional equipment to demolish buildings 412 and 413. The
contractor shall supply trained and experience operators for all project equipment.
5-a-9 The contractor shall haul all demolished material off site for disposal, reclamation activity, or
other disposal or recycling activity. Proceeds from recycling or re-purposing building components
salvaged belong to the contractor. All disposal locations shall be licensed by a town or county within
Maryland.
5-a-10 The contractor shall demolish the trailers with recognized standard construction demolition
heavy equipment utilizing buckets, booms, hooks, and or jaws. Demolition by hand unless in direct
support of the mechanized demolition is not authorized. Any wrecking balls are not permitted.
5-a-11 The contractor shall haul all demolition debris away on his trucks or trucks contracted by him to
the proper final disposal area. The contractor shall provide COR trip or landfill / disposal tip tickets from
the final county or state approved disposal location.
5-a-12 The contractor shall remove and dispose of the masonry piers, trailer tie downs, tie down
anchors, metal framing, axels, wheels and tires, trailer tongues and any other trailer related debris.
5-a-13 As part of the building demolition and two day demolition time frame, the pressure treated
walkway and ramp shall be demolished and disposed of by contractor including posts and concrete post
anchors buried in the ground. Holes shall be filled with organic material and leveled.
Page
5-a-15 Contractor shall dispose of all trash, insulation, wire, or any trash left in the project area.
4
5-a-14 Any ruts made by contractors’ equipment in the grass area south of the buildings, and the area
under the removed wooden walkway / ramp shall be leveled, filled and seeded with a NIST specified
grass seed as and applied provided by contractor. Final acceptance of contract requires successful
growth of grass as specified in Demolition Buildings 412 and 413 LAWNS, GRASSES.
Demolition Buildings 412 and 413
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD
REF: WO 3297
Revised May 21, 2015
5-a-16 Contractor shall mechanically sweep the entire demolition area between buildings 224, 226, and
the concourse between buildings 225 and 226 after building 412 and 413 has been removed and prior to
opening the driveway area to foot or vehicular traffic.
6. Scope of Work Major Elements
6-a-1 Electrical : The contractor shall modify, alter, or remove the following electrical items and other
electrical conditions formally supplying buildings 412 & 413 rendering the former electrical service and
components safe, code compliant, and weather tight for the long term.
6-a-2
Outage schedule – must provide 14 days’ notice











Coordinate with COR and building occupants for outage to for building 224, north side,
east and west 208 V Buss. Secure power using LOTO to prepare to remove buss plugs
that supplied power to the trailer electrical panel.
Remove wire from bus plugs; remove buss plugs and close access blanks on buss duct.
Demolish the four 2” conduits on each side of the cross over to the junction boxes at 4”
conduit on the center cross over chase.
Use knock out blanks to fill holes left by demolished conduits.
Pull and scrap wire from attic to outside trailer panel board cutoff electrical enclosures.
Cut off panel board angle posts at pad level and scrape the aluminum panel board posts.
Cut off the 4” conduit at a uniform height (4-6”) above concrete pad and remove the
electrical panel board and scrap.
Seal conduit openings weather tight with expandable foam 4” deep. Trim excess foam
when dry and paint with enamel paint – silver.
Cut off the 4” galvanized pipe on the east side of the concrete pad and fill pipe to 4”
with expandable foam. Trim excess foam when dry and paint with enamel paint – silver
Cut and remove any conduit left from ground level to point of disconnect (cut) near /
under trailer framing / floor. Seal conduit going underground with expandable foam.
Remove the electrical box at the southwest end of building 413 and cut off at ground
level and seal conduit with foam.
Electrical conduit removal from bus plugs to junction box on each side of the cross-over
consists of eight total conduits each 10 to 12” long.
6-a-4
Knock out blanks on both junction boxes at the attic crosswalk: Cooper, Thomas &
Betts, Eaton or other manufacture, snap in.
6-a-5
Expandable Foam: GREAT STUFF Gaps and Cracks Insulating Foam Sealant or
other similar commercial product.
6-a-6
Silver paint: Rustoleum or similar enamel silver spray paint.
Page
5
6-a-3
Demolition Buildings 412 and 413
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD
REF: WO 3297
Revised May 21, 2015
6-b-1 Piping: The contractor shall modify, alter, or remove the plumbing or piping and other plumbing
or piping conditions formally serving buildings 412 & 413 rendering the former plumbing or piping and
components safe, code compliant, and weather tight for the long term.



On the south side of the trailers (buildings 412 and 413) cut off, cap, and abandon or
remove to pit by electrical pad the below ground piping formerly used to provide water
or drain services to trailers. If removed to pit by electrical pad, cap or plug pipes with
the appropriate PVC or other same pipe material type fitting.
The 4” black poly gutter and condensate drain lines around the trailer perimeter shall be
removed during asphalt removal.
Replace, a field fabricated valve box level to ground level on the City Water south of the
Building 412 location. See sketch.
6-b-2
Expandable Foam: GREAT STUFF Gaps and Cracks Insulating Foam Sealant or other
similar commercial product.
6-b-3
City water valve box: Field fabricated from 6” schedule 40 PVC pipe, 6” soc x thd
schedule 40 PVC adapter, and 6" Brass countersunk threaded plug (MPT) (Sioux Chief or
similar) painted blue with Rustoleum or similar enamel blue spray paint.
6-c-1 Asphalt and Curb: The contractor shall remove the existing asphalt and concrete curb from
under and around buildings 412 and 413:
6-c-2 Starting from the southeast corner of the project parking area, closest to building 225,
measuring west 267 feet, more or less, to within two feet of the storm drain where the curb starts an
arch to the loading dock of Building 224 and 34 feet north: remove the asphalt and curb.
6-c-3
Remove the stone formerly used as drip edge just south of the existing curb.
6-c-4 The contractor responsibilities as found in section 5. Scope of Work, 5-a General apply to
asphalt removal.
6-c-5 See NIST detail drawings STD0160 and STD-154 and the NIST Asphalt and Concrete specification
for new asphalt and curb installation.
Fill level and seed any disturbed area from the City Water valve box work.
Page
6-d-2
6
6-d1 Earthmoving and Lawn: The contractor shall remove the existing stone formerly used as drip
edge just south of the existing curb and replace with satisfactory soil from off NIST campus.
Demolition Buildings 412 and 413
REF: WO 3297
National Institute of Standards and Technology
NIST Campus, Gaithersburg, MD
Revised May 21, 2015
6-d-3 Fill, level, and seed any area rutted by Contractor’s equipment, dug, or otherwise requiring
reseeding to grow grass.
6-d-4
See NIST specification for Earthmoving and Lawn and Grasses.
7. Dust Control
7.1
Contractor shall submit a dust control plan in accordance with Maryland Department of the
Environment “2011 Maryland Standards and Specifications for Soil Erosion and Sediment Control” H-5.
8. SUBMITTALS
8.1
A. Dust Control Plan
B. Outage Request
C. Asphalt Product Data
D. Asphalt Material Certificates
E. Grass Seed Product Data
F. Grass Seed certification of Seed
G. Grass Seed – Installer qualification
H. Concrete Paving – Product Data
I. Concrete Paving – Design Mixtures
8.2
All Submittals shall be submitted to the COR four (4) days after the NTP. The COR will review
and return submittals to the contractor within five (5) days.
9. Performance Period:
9.1
The buildings and area are available for contractual work once the Notice to Proceed is issued.
The contractor shall be finished within 21 days of starting field work. Task order period of performance
is 50 days.
10. Materials and Labor:
10.1
Government will provide no material or labor
Specifications:
Specifications start on the next page.
7
CONCRETE PAVING
ASPHALT PAVING
EARTH MOVING
LAWNS, GRASSES
End of Statement of Work