Experiment No : 02 FAULT STUDY Instructed By: Name Group Members: : Weerasinghe W.M.S.C. Weranga K.S.K. - 060529 Index No : 060526V Wickramasinghe V.B. - 060531 Group : 12 Yasaranga H.B.D. - 060562 Dept : EE Abeygoonasekara -060567 Date : 14/06/2007 CALCULATION For this experiment following simplified power system was used. Fault calculations were done with respect to this system. x1= 0.3 x2= 0.2 x0= 0.05 x = 0.09 x1= 0.1 POLPITIYA Z=0 . x0= 0 002+j0.00 5 .02 ANURADHAPURA 4 0 0. .8 7+j0 0.34 Z = 2.5 x0= j 7+ 01 0. 15 = 0. Z 0= x Z = 0.058+j0.102 x0= 0.4 Z= x0= 0.156 1.1 +j0.3 4 1 Z = 0.19+j0.44 x0= 2.0 Z = 0.057+j0.13 x0= 0.45 BOLAWATTA LAXAPANA x = 0.02 x1= 0.05 x2= 0.04 x0= 0.01 xp = 0.051 xt = 0.055 xs = 0.045 KOLONNAWA x = 0.08 Practical Calculation 1. Single Line to Earth Fault (L-G Fault) Supply Side Ia Va = 0 Ib Vb Ic Vc The fault impedance is zero. So, Va 0 Ib 0 Ic 0 (a) the fault currents could be calculated as follows, I a 1 I 1 b I c 1 1 I a0 I a1 2 I a2 1 2 1 I a0 1 I 1 a1 3 1 I a2 1 2 I a0 I a1 I a2 1 I a 2 I b 0 I c 0 Ia 3 Therefore Fault current, I f = I a a b c I f 3I a0 I f 3 46mA I f 138mA Actual current in the circuit, I f 138 10 3 4000 2640 A I f 1457.284kA (b) fault voltages can be calculated as follows, Va 1 V 1 b Vc 1 1 Va0 Va1 2 Va2 1 2 Va 0 1 V 1 b Vc 1 1 2 1 - 18 32 2 - 14 Vb Va0 2 Va1 Va2 Vb -18 32240 0 14120 0 Vb 48.1248 124.1278 0 kV Actual voltage, Vb 48.1248 2640 - 124.1278 Vb 127.0495 - 124.1278 kV Vc Va0 Va1 2 Va2 Vc -18 32120 0 14240 0 Vc 48.1248124.1278 0 V Actual voltage, Vc 48.1248 26404.1278 Vc 127.0495124.1278 kV 2. Double Line to Earth Fault (LL-G Fault) Ia Va Ib Vb=0 Ic Vc=0 Supply Side Fault impedance is zero. So Ia 0 Vb 0 Vc 0 (a) the fault currents could be calculated as follows, I a 1 I 1 b I c 1 1 2 I a 0 1 I 1 b I c 1 1 I a0 I a1 I a2 1 2 1 - 39 92 - 53 a b c I b I a0 2 I a1 I a2 I b 39 92240 0 53120 0 I b 138.5316 114.979 0 mA Actual current in the circuit I b 138.5316 10 3 4000 2640 114.979 0 I b 1462.8937 114.979 0 kA I c I a0 I a1 2 I a2 I c 39 92120 0 53240 0 I c 138.5316114.979 0 mA Actual current in the circuit I c 138.5316 10 3 4000 2640114.979 A I c 1462.8936114.979 kA (c) fault voltages can be calculated as follows, Va 1 V 1 b Vc 1 1 Va0 Va1 Va2 1 2 Va 1 V 0 1 b Vc 0 1 1 2 Va Va0 Va1 Va2 Va 15 15 15 Va 45 V Actual voltage in the circuit Va 45 2640 Va 118.8 kV 1 15 15 15 3. Line to Line Fault (L-L Fault) Supply Side Ia Va Ib Vb Ic Vc Fault impedance is zero. So Ia 0 Vb Vc I b I c (a) Calculating fault currents 1 1 I a0 I a 1 I 1 2 I a1 b I c 1 I a2 1 1 0 I a 0 1 I 1 2 75 b I c I b 1 - 75 I b I a0 2 I a1 I a2 I b 0 75240 0 75120 0 I b 129.9038 90 0 mA a b c Actual current in the circuit I b 129.9038 10 3 4000 2640 90 0 A I b 1371.7842 90 0 kA I c I a0 I a1 2 I a2 I c 0 75120 0 75240 0 I c 129.903890 0 mA Actual current in the circuit I c 129.9038 10 3 4000 264090 0 A I c 1371.784290 0 kA (d) fault voltages can be calculated as follows, Va 1 V 1 b Vc 1 1 2 Va 0 1 V 1 b Vc Vb 1 1 Va0 Va1 Va2 1 2 1 0 22 22 Vb Va0 2 Va1 Va2 Vb 0 22240 0 22120 0 Vb 22180 0 V Actual voltage in the circuit Vb 22 2640180 0 Vb 58.08180 0 kV Vc 58.08180 kV Theoretical Calculation Single Line to Earth Fault (L-G Fault) Va 0 , I b 0 , Ic 0 Since Z1 =0.208, Z2 = 0.1915, Z3 = 0.4495 Fault Current can be given as, 3E f If Z1 Z2 Z0 If 3 132 0.208 0.1915 0.4495 I f 466.43 kA Fault Voltages from the diagram Va0 Z 0 I a0 - 0.4495 155.48 kA -69.89 kV Va1 E f Z1 I a1 132 kV - 0.208 155.48 kA 99.46 kV Va2 Z 2 I a2 - 0.1915 155.48 kA - 29.77kV Vb Vb0 Vb1 Vb2 Vb -69.89 2 99.46 29.77 Vb -69.89 99.46240 29.77120 Vb 153.28 - 133.10 0 kV Vc Vc0 Vc1 Vc2 Vc -69.89 99.46 2 29.77 Vc -69.89 99.46120 29.77240 Vc 153.28133.10 0 kV Double Line to Earth Fault (LL-G Fault) Ia 0, Vb 0, Vc 0 Since Z1 =0.208, Z2 = 0.1915, Z3 = 0.4495 Z1 =832, Z2 = 766, Z3 = 1796 I a1 132 /( 0.208 0.1915 // 0.4495) I a1 385.64kA I a 2 (132 385.64 0.208) / 0.1915 I a 2 270.42kA I a 0 (132 385.64 0.208) / 0.4495 I a 0 115.21kA Va 3 Va1 Va 3 132 0.208 385.64 Va 155.36 kV I b I b0 I b1 I b2 I b I a0 2 I a1 I a2 I b 115.21 385.64240 115.21120 I b 500.85 120 0 kA I c I c0 I c1 I c2 I c I a0 I a1 2 I a2 I c 115.21 385.64120 115.21240 I c 500.85120 0 kA Line to Line Fault (L-L Fault) I a 0, Vb Vc , I b Ic Since Z1 =0.208, Z2 = 0.1915, Z3 = 0.4495 I a1 Ef Z1 Z 2 I a1 132 kV 0.208 0.1915 I a1 132 kV 0.461 I a1 330.41 kA I a2 330.41 kA Va1 Va2 63.556kV Vb Vb0 Vb1 Vb2 Vb Va0 2 Va1 Va2 Vb 0 63.556240 63.556120 Vb 63.556180 0 kV Vc 63.556180 0 kV I b I b0 I b1 I b2 I b I a0 2 I a1 I a2 I b 0 330.41240 330.41120 I b 572.29 90 0 kA I c I b I c 572.2990 0 Practical Values Faul t Typ e Fault Currents kA Fault Voltages kV Va Ia Ib Ic L-G 1457.2 84 0 0 0 L-L 0 1371.7842 90 0 1371.784290 0 0 LL-G 0 Vc Vb 48.1248 - 124.1278 48.1248124.1278 58.08180 0 58.08180 0 0 1462.8937 114.979 0 1462.8937 114.979 0 45 Theoretical Values Fault Type Fault Currents kA Fault Voltages kV Ia Ib Ic Va Vb Vc L-G 466.43 0 0 0 153.28 133.10 0 153.28133.10 0 L-L 0 572.29 90 0 572.2990 0 0 63.5561800 63.5561800 L-LG 0 500.85 120 0 500.85120 0 155.36 0 0 DISCUSSION 1. Importance of Fault Study Fault of a power system is required in order to provide information for the selection of switchgear, setting of relays and stability of system operation. The power system which is given is not a static one. So that system changes during operation (Switching on or off of generators and transmission lines) and during planning (addition of generators and transmission lines). So fault study need to be routinely performed by utility engineers. 2. Assumptions made in Fault Study To simplify the calculations following assumptions are usually made in fault study of the power systems. They are as follows, All sources are balanced and equal in magnitude and phase. Sources represented by the Thevenin’s voltage prior to fault at the fault point. Large systems may be represented by infinite bus-bars. Transformers are on nominal tap position. Resistances are negligible compared to reactance. Transmission lines are assumed fully transposed and all three phase have same Z. Loads currents are negligible compared to the fault currents. Line charging currents can be completely neglected. 3. DC Network Analyzer The DC network analyzer is design to analyze the fault currents in power system. The symmetrical andunsymmetrical fault analysis can be done with help of analyzer. The unit comprises with variable power supply sources, variable resistance, Milliammeter and ohmmeter. The unit is design with number of sections in power system. The sections are considered for general case. The unit will have two sections of alternators, two sections of sending end transformers with busbars, four sections of transmission lines, four sections of receiving end transformers with busbars and four load sections. The fault impedance diagram can be prepared on per phase basis for symmetrical faults and currents are calculated. The same can be analyzed with dc network analyzer panel. For the unsymmetrical faults, the sequence reactance diagrams are prepared and the positive, negative & zero sequence reactance diagrams are connected in series or parallel according to type of fault for fault current analysis. The DC network analyzer will give the simulated fault current in agnitude but the exact phase can not be found. The assumption is made that fault resistance is very small than the reactance. (i.e. Rf <<< XF) So the fault current is pure reactive & logging behind the phase voltage by 90. For analyzing currents with its phase and magnitude the AC network analyzer is required. The DC network analyzer is simple to operate, easy to understand and full proof with protections. The power supply units in analyzer can be independently used for other applications also. The power supply manual is enclosed separately. The DC network analyzer unit is totally enclosed, free standing, dustproof. The unit powder coated and screen printed for different section parameters. 4. Importance of using Sequence Components Considering the power system the analyzing procedure is easy if the power system is balanced. But the systems are not balance in every time. To analyze the unbalanced systems the method of sequence components is using. In this method the unbalanced system splits in to three balanced components. They are, Positive sequence networks (balanced & same phase sequence as unbalanced system), Negative sequence (balanced & opposite phase sequence to the unbalanced system) networks and Zero sequence (balanced & having same phase) networks. Because of this decomposition of the unbalanced system removes the complex parts of the system properties. So the analyzing matrix calculation will be easy. 5. Relationships between the sequence impedance for generators, transformers and transmission lines Depending on the component used in the power system impedance of the components used for fault calculation may changed for various sequences. Some detail about the relationship between the sequential impedance for generators, transformers and transmission lines are given below. Generator The generator has an inherent direction of rotation and the sequence considered may either have the same direction (no relative motion) or the opposite direction (relative motion at twice the speed). Thus the rotational emf generated for the positive sequence and the negative sequence would also be different. So that the generator has different values for positive sequence, negative sequence and zero sequence impedances. Transformer Transformer is also passive and stationary. So it does not have an inherent direction of rotation. So it always has the same positive sequence impedance and negative sequence impedance and even zero sequence impedances. But the zero sequence paths across the windings of a transformer depend on the winding connection and even grounding impedance. Transmission Lines Likes a transformer, the conductors of the transmission lines are passive and stationary. So they do not have an inherent direction. Thus, they have the same positive sequence and negative sequence impedances. But the zero sequence paths involve the earth wire and or the earth return path. The result is higher the zero sequence impedance. References o EE 423 – Power System Analysis study notes