Value pricing of surface coatings for mitigating heat exchanger fouling L. Gomes da Cruz1,2, E.M. Ishiyama3, C. Boxler4, W. Augustin4, S. Scholl4 and D.I. Wilson1,* 1 Department of Chemical Engineering & Biotechnology, University of Cambridge, New Museums Site, Pembroke Street, Cambridge CB2 3RA, UK 2 Department of Chemical Engineering, Polytechnic School, University of São Paulo, Av. Prof. Luciano Gualberto, 380, trav. 3, 05508-010, São Paulo, SP, Brazil 3 IHS Downstream Research, 133 Houndsditch, London EC3A 7BX, UK 4 Institute for Chemical and Thermal Engineering, Technische Universität Braunschweig, Langer Kamp 7, 38106 Braunschweig D, Germany *Corresponding author: diw11@cam.ac.uk ABSTRACT Surface modification has been proposed as an attractive mitigation strategy for combatting heat exchanger fouling in the food industry and other sectors. Antifouling coatings manipulate the interactions between the surface and fouling precursors or fouling deposit to either extend the induction period before appreciable fouling starts and/or reduce the rate of deposition. A successful surface treatment should extend the time between cleaning operations, thereby reducing the operating cost of the system. A modified exchanger will, however, incur additional capital costs for replacement and this needs to be compared to the anticipated savings during operation. This paper considers the economic attractiveness of replacing existing exchangers by units with modified surfaces in a retrofit. Three cases are considered, which are modelled using fouling rates taken from studies in the literature. Antifouling performance is expressed in terms of (i) extended induction period before fouling starts, and/or (ii) reduced fouling rate. The annualised total cost (operating + annualised capital spend) is mapped for different combinations of these parameters to establish the economically favourable region for a coating at different coating prices. This allows the value pricing margin to be identified, where the expected benefits have to be split between the cost of the coating and the benefit to the manufacturer and operator. The case studies are (a) DLC-related surface modification to reduce aqueous crystallization fouling; (b) fluorocarbon-based coatings which offer antifouling performance but can reduce heat transfer, for crystallization fouling; and (c) fluorocarbonbased coatings in a dairy pasteurizer application. A novel strategy, of replacing stainless steel with fluorocarbon coated carbon steel, is also considered for case (b). Key words: heat exchanger, fouling mitigation, cleaning, coating, techno-economic analysis 1 1. Introduction Fouling is a widespread problem in process heat transfer systems and necessitates regular cleaning and/or costly mitigation measures. It is a challenge for sustainable manufacturing as it incurs additional equipment, energy, treatment chemicals and downtime with associated costs as well as increasing the environmental impact of the process. Fouling can be mitigated (see Müller-Steinhagen et al., 2011) by modifying the process streams (e.g. softening hard water), manipulating process conditions (e.g. temperatures and flow rates/shear stresses, using alternative apparatus such as fluidised bed heat exchangers), and by modifying the heat transfer surface to reduce (or eliminate) fouling and/or enhance cleaning. The latter strategy, which may be labelled as the search for the ‘Holy Grail’ or antifouling surface, has attracted a considerable amount of research effort in recent years (Santos et al., 2013). Coating a surface to reduce fouling or other deposition processes involves modifying the interaction between the surface and the process fluid and thus the attachment, adhesion, retention and removal of depositing species. These interactions determine the strength of adhesion of any fouling layer and the cleanability of the surface. An ideal coating would prolong the fouling induction period, improving the plant operating efficiency. If deposition did occur, it would also require less effort for cleaning (lower concentration and temperature of cleaning solutions, shorter cleaning times), increasing the plant productivity and reducing the consumption of natural resources. Coatings There is a wide variety of processes available for coating metal substrates, including electrochemical deposition, thermal spraying, contact welding, plating, ion implantation or sputtering, physical and/or chemical vapour deposition, and hybrid methods. These differ in the deposition options (e.g. coating devices, coating species and precursors, coating rate), film properties (tribological and energetic properties, thickness and surface topography) and cost (equipment purchase and maintenance price, power consumption, space and personnel requirements). The choice of coating material and method will depend on the nature of the surface to be coated as well as the nature of the species causing fouling. Tables 1 and 2 summarise the results of recent experimental studies on the effect of surface coatings on heat exchanger fouling in water scaling and milk-related liquids, respectively. These tables do not provide a comprehensive account of each study, as their purpose is to illustrate the breadth of types of coating tested, the range of fouling fluids (usually solutions), and the variety of outcomes. Details such as the method of manufacture, mode of heat transfer, and testing conditions can all be found in the original paper(s). The studies vary in terms of characterisation of the coatings (e.g. roughness, surface energy, thickness and uniformity), so comparing coatings is not always straightforward. A recent review of the effectiveness of different antifouling coatings has been published by Banerjee et al. (2011). 2 Some of the contradictory results in Tables 1 and 2 can be attributed to the diversity in experimental conditions, differences in methods for preparing coatings, composition of fouling solutions and monitoring/analytical methods. It is noteworthy that many workers have reported surface coatings to have a stronger effect on cleaning than on fouling. This indicates that assessments of surface coating performance should consider their contribution to the whole fouling-cleaning cycle. Coatings in practice A key aspect of surface coatings is the durability, stability and cost effectiveness of the coating over repeated operating (fouling and cleaning) cycles. Al-Janabi et al. (2010), Bani Kananeh et al. (2010) and Mauermann et al., (2009) reported that the coatings studied were not suited for the continuous thermal and mechanical stress which would be experienced during extended operation. This aspect is not addressed in many studies. Some, such as Barish and Goddard (2013), have reported the coating performance over several fouling and cleaning cycles. If the coating loses integrity, this limits the asset lifetime and this will be shown to determine the economic attractiveness of this mitigation option. In order to be acceptable for process applications, antifouling surfaces – whether imparted by coatings or new materials of fabrication – have to function effectively under normal process conditions as well as other ancillary scenarios (such as cleaning, sanitisation, processing different products), consistently over the lifetime of the unit. There has been considerable interest in their application in the food and drinking water sectors, as the ability to modify the feedstock, flow rates and temperatures are limited as these may be set by separate criteria such as consumer/legal requirements or pasteurisation kinetics. Furthermore, the substances being processed are usually low margin products so there is limited scope for capital to replace existing equipment. The dairy sector is an important example in the food manufacturing area where fouling and cleaning present significant challenges for manufacturing and need to be addressed to improve the sustainability of milk processing operations (Xu and Flapper 2009; Carbon Trust, 2011). Plate heat exchangers (PHX) are standard items for pasteurisation and high temperature sterilisation applications: these units are often subject to acute fouling and require cleaning on a daily basis. Additional energy is needed to counter heat transfer inefficiencies caused by fouling, and to heat cleaning solutions. The latter requires volumes of clean water and cleaning chemicals, the treatment of which adds to the environmental impact burden of the plant (Guignard et al., 2009). This has prompted the investigation of surface coatings and antifouling treatments for stainless steel PHX plates since the mid 1980s, and Table 2 summarises some of the key studies in this area related to dairy processing. The EU-funded MODSTEEL project (Beuf et al., 2004; Rosmaninho et al., 2008; Santos et al., 2006) considered a range of coating methods for stainless steel PHX plates and reported mixed results for fouling performance but noticeable reductions in cleaning time. A noticeable feature 3 of recent studies is the extended testing of surface coatings over several fouling and cleaning cycles (e.g. Barish and Goddard, 2014), replicating standard practice in membrane research (e.g. Weis and Bird, 2001) where it is recognised that surfaces age noticeably over the first few operating cycles. 4 The innovation gap Antifouling coatings, like other inventions, must cross the ‘innovation gap’ in order to become adopted in manufacturing practice. The new coating (or replacement material) must demonstrate a suitably large advantage in performance, and incremental return on investment, in order to justify the capital expenditure and risk associated with its implementation. This requires a techno-economic analysis of the process subject to fouling and cleaning before and after implementation, which has not, to the authors’ knowledge, been considered by researchers in this area. This is particularly important for coatings based on fluorocarbons as the coating introduces an extra insulating layer into the heat transfer considerations, so that more PHX plates are needed for a given heat duty. These calculations also allow vendors of coating technologies to conduct value pricing analyses, i.e. to establish the profit margin (based on savings) achievable with a given coating and thus the maximum price that an operator would be prepared to pay. In this paper, a general techno-economic model is described and then applied to three case studies. The case studies are taken from the water and food sectors, with stainless steel as the standard material of construction. Three coating scenarios are considered, illustrated by three case studies: (i) where the coating has negligible impact on heat transfer, typical of surface modifications such as diamond like carbon (DLC) (Case Study I); (ii) where the coating introduces an insulation effect, reducing the rate of heat transfer while mitigating fouling (Case Studies II and III); (iii) as (ii), but where the coating provides complete corrosion protection, so the substrate can be substituted with carbon steel, offsetting the heat transfer penalty associated with the coating (Case Study II). Scenario (iii) is suitable for fluorocarbon-based coatings which provide good corrosion protection (Ebnesajjad and Khaladkar, 2005) and adhere to carbon steel more readily than stainless steels. 5 2. Model formulation The techno-economic model requires a quantitative description of the effect of fouling on the performance of a heat exchanger, which includes the effect of a coating on heat transfer, fouling and cleaning. Its outputs are fed into a cost model which allows optimal operating strategies to be developed, and compared. Lumped parameter models are used to predict heat exchanger performance, to illustrate the concepts. More complex, distributed models could be used (e.g. Coletti et al., 2010), but the aim of this paper is to establish the nature of the solution landscape and this is best achieved without detailed models (which may in turn be difficult to parameterise). Similarly, the cost models do not consider the time value of money nor inflation. 2.1. Heat exchanger performance with fouling Fouling of heat transfer surfaces leads to increased pressure drop and reduced heat transfer. Only the latter effect is considered here: pressure drop (and changing flow rate) considerations, as discussed by Ishiyama et al. (2009) could be added as required. The thermal impact of fouling is quantified via the fouling resistance, Rf, which is related to the thickness of the deposit, δf, and its thermal conductivity, λf. Assuming that the thin-slab approximation holds gives π π = πΏπ ⁄ππ (1) As the deposit layer grows, π π increases and the temperature at the deposit/process stream interface will change. This will affect the rate of deposit formation, as discussed by Ishiyama et al. (2008). The sensitivity to temperature is determined by the species and mechanisms involved in deposition. For the purposes of this paper, the rate of change in Rf with time (the fouling rate) is taken to be constant, at π Μπ . Deposit ageing, which also complicates the effect and rate of deposition over time (see Ishiyama et al., 2011) was not considered here: ππ is also assumed to remain constant over time, giving ππ π 1 πδπ ≡ π πΜ = ππ‘ ππ ππ‘ (2) For some processes and surfaces, there may be a delay before there is a discernible increase in π π . This induction period, π‘πππ , may be extended by the use of a coating and is modelled as an initial lag, giving 0, π π (π‘) = { Μ π π × (π‘ − π‘πππ ), π‘ < π‘πππ π‘ ≥ π‘πππ (3) The heat exchanger is modelled using a lumped parameter approach, where the rate of heat transfer is calculated using an average temperature driving force and an overall heat transfer coefficient, π. As deposition proceeds, U is related to its deposit-free (clean) value, πππ , by 6 1 1 = + π π π πππ (4) The overall heat transfer coefficient for a clean heat exchanger can be calculated from 1 1 πΏπππ‘ππ 1 = + + π ππππ‘ + πππ ββ ππππ‘ππ βπ (5) where ββ and βπ are the hot and cold stream film heat transfer coefficients, respectively, πΏπππ‘ππ is the thickness of the heat transfer surface , ππππ‘ππ is its thermal conductivity, and π ππππ‘ is the thermal resistance of the coating. In Eqn [5] the internal and external heat transfer areas are assumed to be equal. π ππππ‘ is calculated from the coating thickness, πΏππππ‘ , and its thermal conductivity, πππππ‘ , using π ππππ‘ = πΏππππ‘ ⁄πππππ‘ (6) Differences in surface roughness between a coated and standard surface are assumed to be negligible. The following assumptions are made in the calculation of heat exchanger unit performance: i. The thermal and physical properties of both the hot and cold process streams remain constant within the heat exchanger. Each value corresponds to the arithmetic average of the stream inlet and outlet temperatures; ii. Cleaning actions remove all deposit material, so Rf is reset to zero after cleaning; iii. The coating layer is homogeneous, durable, free of defects and its fouling mitigation properties do not change over its lifetime; iv. The thickness of the deposit is small compared to the duct dimension, so there is no change in flow area, average velocity and film heat transfer coefficients of both streams during operation; v. Fouling deposits are uniformly distributed. The heat duty, Q, is evaluated using the effectiveness-NTU method (Kays and London, 1964), where the effectiveness, ε, is defined by π= π ππππ₯ = π (7) (πΜπΆπ )πππ (πβ,ππ − ππ,ππ ) where ππππ₯ is the maximum heat duty achievable from the process, (πΜπΆπ )πππ is the minimum heat capacity flow rate, πΜ is the mass flow rate and πΆπ is the specific heat of a given stream. Stream temperature π is labelled with subscripts ‘in’ and ‘out’ referring to the inlet and outlet location, while ‘h’ and ‘c’ refer to the hot and cold stream, respectively. The case studies consider examples of single phase (liquid-liquid) heat transfer. The change in temperature of each stream is related to the heat duty by 7 π={ πΜβ πΆπ,β (πβ,ππ − πβ,ππ’π‘ ), for the hot stream (8) πΜ π πΆπ,π (ππ,ππ’π‘ − ππ,ππ ), for the cold stream (9) The effectiveness, π, depends on the number of transfer units, πππ, πππ = π. π΄ (10) (πΜπΆπ )πππ and the heat capacity flow ratio, πΆπ , πΆπ = (11) (πΜπΆπ )πππ (πΜπΆπ )πππ₯ where π΄ is the effective heat transfer surface area and (πΜπΆπ )πππ₯ is the larger of the two streams’ heat capacity flow rates. The functional relationship, ο₯ = f(NTU, Cr) depends on the type and contacting configuration of the exchanger. The performance of the exchanger is evaluated over time, t (see Figure 1). At each time instant, Rf is evaluated, giving U (via Eqn [4]) and Q (via Eqn [8]). Figure 1 shows that as Rf increases, U and Q both decrease. Eventually it will be more profitable to take the exchanger off-line for a period of time of length ο΄ for cleaning, resulting in U being restored to its clean value, Ucl. There will be an optimal operating period before cleaning, the evaluation of which is described below. It should be noted that the presence of a coating will change the overall heat transfer resistance (via Eqn [4]), usually reducing U, and NTU (Eqn [10]). If the clean heat duty is to be maintained at a target level, this reduction in U is usually countered by increasing the heat transfer area, A. Coating the heat transfer surface is therefore likely to require a larger heat exchanger in the absence of ‘fouling factors’. This has an effect on the response of the exchanger to fouling, as NTU includes the product UA: the extra heat transfer surface reduces the impact of a given Rf value and appears to mitigate fouling. This is one of the benefits of the ‘fouling factor’ approach in designing heat exchangers for fouling service, where the exchanger is oversized based on a presumed amount of deposition occurring at some point in the future. In practice, such exchangers tend to foul more quickly owing to inappropriate operating protocols, as expressed in Bott’s ‘self-fulfilling fouling prophecy’ (Bott, 1995), quantified by Ishiyama et al. (2008). Oversizing exchangers based on fouling factors is not included in the process models here, and could be readily added as desired. 2.2. Cost model and economic optimisation In considering any process improvement, the capital cost for implementing the change must be compared with the expected improvement in operating costs. For heat exchangers subject to fouling, 8 the operating cost needs to be evaluated over the fouling-cleaning cycle shown in Figure 1. Fouling is assumed to repeat itself with similar rates over each cycle. The approach presented by Ma and Epstein (1981) is used to identify the optimal cleaning cycle (OCC), with a processing period of length tp, and down-time for cleaning, π. The influence of ageing, discussed by Ishiyama et al. (2011) and choice of cleaning methods (see Pogiatzis et al., 2012) are not considered here. The costs due to fouling incurred over the cycle are: i. Compensation for reduced heat transfer, e.g. additional heating/cooling cost of the process stream to achieve temperature target(s), CH, discussed below. ii. Heating/cooling during the time the heat exchanger is off-line for cleaning, with cost = cE Qclο΄, where cE is the cost per unit energy. iii. Cost of a cleaning operation, Ccl, including disposal of cleaning chemicals etc. iv. (For completeness, but not considered here) increased pumping costs or penalties associated with loss of throughput Additional heating or cooling, CH The reduced rate of heat transfer caused by fouling can be compensated for in different ways, depending on the design and operation of the exchanger. For example, an overdesigned heat exchanger (one with excess area) can be operated with a flow bypass in order to achieve the desired outlet temperatures, and fouling only has a marked effect when the bypass is fully closed. This mode is not considered here. The two modes considered are: I Providing additional heating/cooling to adjust the process stream from its exit ππ temperature, Ti,out, to the desired value, obtained when the unit was clean, ππ,ππ’π‘ . In this case, (12) πΆπ» (π‘π ) = ππΈ ∫π‘π(πππ − π(π‘))ππ‘ 0 where tp is the duration of the processing period. II Adjusting the heating/cooling utility inlet temperature, ππ,ππ , from its value when the ππ exchanger is clean, ππ,ππ , in order to maintain the process stream outlet temperature at its target value. In this case (13) πΆπ» (π‘π ) = ππΈ ∫π‘π ππππ (π‘)ππ‘ 0 where ππππ is the additional heat duty required to pre-heat or cool the utility stream, given by (14) 9 ππππ (π‘π ) = { π ππ πΜβ πΆπ,β (πβ,ππ (π‘π ) − πβ,ππ ), πππππ‘πππππ βπππ‘πππ ππ ππππ’ππππ ππ π πΜ π πΆπ,π (ππ,ππ − ππ,ππ (π‘π )), (15) πππππ‘πππππ πππππππ ππ ππππ’ππππ Optimal operating period The optimal operating cost (and OCC length) is found by minimising the time-averaged operating cost, πππ , which is the sum of the above three costs divided by the total cycle time, tcyc, which is the sum of tp and ο΄ο¬ viz. πππ (π‘π ) = πΆπ» (π‘π )+ πΆπΈ πππ π+ πΆππ (16) π‘π + π Since ο΄ is here assumed constant and not time dependent, Eqn [16] can be differentiated with respect to tp. The optimal operating period, π‘π,πππ‘ , is when ππππ π2 πππ = 0: >0 ππ‘π ππ‘π 2 (17) The annual total energy loss, πΈπππ π , due to fouling can then be calculated, from: π‘ πΈπππ π = { π [∫0 π,πππ‘(πππ − π(π‘))ππ‘ + πππ π] , πππ (πΌ) π‘ π [∫0 π,πππ‘ ππππ (π‘)ππ‘ + πππ π] , πππ (πΌπΌ) (18) (19) where n is the number of cleaning cycles in a year. When comparing a mitigation strategy such as coating with the performance of existing equipment, the capital cost of replacing an existing plant asset has to be considered. The annualised capital cost, ππππ , is calculated from ππππ = πΌπΆπππ’ππ (π΄) π‘πΏπΉ (20) where πΆπππ’ππ is the installed price of an uncoated unit with area A, πΌ is the cost multiplier associated with the coating, and tLF is the asset lifetime for accounting purposes. The coating must remain effective over this period. In the techno-economic analysis the annual operating cost of an existing, uncoated heat exchanger subject to fouling, πππ,π’ππ , is compared with the cost of a new coated unit, π π,ππππ‘ , which includes the annual operating cost, πππ,ππππ‘ , (which is expected to be lower than πππ,π’ππ ) and the capital costs associated with replacement, ππππ,ππππ‘ . The alternative scenario, of applying a coating to an existing unit, is not considered here. This may not be possible in practice. Considerations of the time dependency 10 of money, e.g. net present value and inflation, are not included in the calculations but could be added as desired. All calculations were performed using MATLAB® on a desktop PC. The calculation sequence is summarised in the Appendix. 3. Case studies 3.1 Case Study I. DLC coating of a shell and tube heat exchanger to combat water scaling Crystallisation fouling caused by hard water, or scaling, is a common industrial problem where the water contains significant amounts of ions of inverse solubility salts such as calcium and magnesium sulphates and carbonates. Scaling mitigation techniques have been studied widely (Kho et al., 1997; Naik et al., 2010; Tijing et al., 2011) and antifouling coatings have been shown to be quite effective in reducing water scaling, as summarised in Table 1. Geddert et al. (2009) reported an improvement in the performance of a heat transfer mini-plant treating synthetic hard water using surfaces with thin diamond-like carbon (DLC) coatings prepared by plasma enhanced chemical vapour deposition (PECVD), including DLC, Si-DLC, SICAN and SICON®. The modified surfaces gave negligible differences in clean heat transfer performance and affected crystal adhesion, prolonging the induction period and reducing any subsequent rate of fouling. The economic attractiveness of such coatings is considered in this case study. It is assumed that the coatings retain their effectiveness over the financial lifetime, tLF. Geddert et al. (2011) subsequently reported that some of the coatings exhibited changes in composition following several cleaning cycles using different cleaning agents. The effect of tLF is considered in this case study as it can be manipulated to represent the durability of the coating, and quantify how long a coating must remain effective in order to justify replacement of an uncoated unit. The performance of two shell-and-tube heat exchangers are compared here based on the Rf-t data reported by Geddert et al. (2009). The units have identical design, with one shell pass and two tube passes. Rcoat is set at zero, as the 3 µm thick DLC coating had negligible effect on heat transfer. Both are fabricated from stainless steel (SS304), one with no coating and the other having SICON®-coated heat transfer surfaces. Both process streams are aqueous liquids, and one is prone to fouling. For the SICON® unit the fouling stream will have to be on the shell-side as coating techniques for tube internals are not commercially available at present. Fouling streams are usually put on the tube-side in order to facilitate cleaning. The choice of shell- or tube-side is not considered further here: it is assumed that there is no difference in fouling behaviour or heat transfer. 11 Equation [12] is used to evaluate the additional operating cost due to fouling, assuming that the streams can be heated elsewhere in the process. The effectiveness is given by Incropera et al. ( 2001): π = 2 {1 + πΆπ + (1 + πΆπ2 )1/2 1 + ππ₯π[−πππ(1 + πΆπ2 )1/2 ] × } 1 − ππ₯π[−πππ(1 + πΆπ2 )1/2 ] −1 (21) Table 3 summarises the unit design and performance parameters. They represent an industrial unit operating at conditions similar to those in Geddert et al. (2009)’s experiments. In the latter study the SICON® surface extended the fouling induction period from 5 h to 72 h and the fouling rate was reduced to less than a third of the uncoated value. In this case study the time taken to clean the exchanger is fixed, at 4 days. The timescale associated with fouling can be gauged by the time taken for U to fall to half its clean value, Ucl/2, corresponding to a fouling Biot number (= Ucl×Rf) of 1, is 62 days for the uncoated heat exchanger and 235 days for the SICON®-coated unit. The plot of overall operating cost in Figure 2 shows that there is an optimal processing time which gives a minimum in ο¦op. The optimum is not symmetric and is shallow, particularly at higher tp. The optimal processing time before cleaning for the uncoated exchanger is 40 days whilst that for the SICON®coated unit is 71 days, representing a 77% extension to the operation period. The effectiveness values decreased from 0.30 to 0.20 and 0.25 for the uncoated and coated surfaces, respectively, indicating that the optimal operating condition does not correspond to a common value of U. The coating reduces the optimal annualised operating cost by 43%, from 235.4 to 133.5 US$ day-1. The capital cost of a new heat exchanger, given in Table 3, was obtained from data in Peters et al. (1990) adjusted to December 2012 using a chemical engineering plant cost index of 572.7. The cost of the SICON® coating is not considered here, so πΌ = 1. The life-time, tLF, is set at 5 years. This gives an annualised capital cost for the replacement unit, ππππ , of 38.7 US$/day, i.e. 16% of the operating cost of the uncoated HEX. ‘Value pricing’ The summary of the costs in Table 4 shows that the total annualised cost of the coated unit is 62.8 kUS$/yr, which is 23.1 kUS$/yr less than the uncoated unit. This difference represents the maximum return on investment for the coating and can be used in either (i) assessing the economic attractiveness of a coating by the operator, or (ii) establishing the costing space in a ‘value pricing’ calculation for the coating by its vendor. As an example of the latter, the 23.1 k$/yr difference in total annualised costs is 1.65× the capital cost, indicating that the maximum value of ο‘ at which the coating can be sold is close to 2.5. This in turn can be compared with the cost of manufacturing the coated unit. The values will be determined by the inputs to the calculation: size of unit, material of construction, duty, impact on 12 fouling, and costing parameters (particularly tLF). These will vary from sector to sector. The remainder of this case study compares the impact of different fouling parameters on the attractiveness of replacing an existing unit with a coated surface. Fouling parameter sensitivity When comparing the effect of fouling parameters on the performance and costs of coated and uncoated units, it is helpful to present the results in terms of ratios based on the uncoated (i.e. base case) exchanger. The dimensionless performance indices are: [i] ∗ π‘ππ¦π = π‘ππ¦π,ππππ‘ ⁄π‘ππ¦π,π’ππ Ratio of the optimal cycle times [ ii ] π ∗ = π π,ππππ‘ ⁄πππ,π’ππ Ratio of the total annualised cost for the coated unit divided by the operating cost for the uncoated one [ iii ] ∗ πΈπππ π = πΈπππ π ,ππππ‘ ⁄πΈπππ π ,π’ππ Ratio of the energy losses due to fouling Table 4 shows that π ∗ = 0.73 for the example in Figure 2, representing a 27% reduction in total cost. In terms of energy consumption, which may attract tax benefits, the coating delivers a 44% reduction in energy losses due to fouling. The results of parametric sweeps are now presented. The ranges considered are (a) Fouling rate, π πΜ , varying from near 0.1× to 1.5× the uncoated rate. The latter values represent a poor coating in terms of fouling rate, but this could be offset by extending the induction period and/or increasing the cleaning rate. (b) Induction period, tind, ranging from 0 to 5 days. tind for the uncoated HEX is set as 5 hours. (c) Cleaning times, ο΄, of 2, 4 or 5 days, representing possible improvements or extension of cleaning time as a result of the coating. ο΄ο for the uncoated heat exchanger is fixed, at 4 days. No assumptions are made about the nature of the coating beyond it not affecting the overall heat transfer resistance. The coated and uncoated exchangers in this instance have the same area and the results apply to any coatings with these characteristics. The calculation outputs are summarised in 3-D plots in Figure 3, where the fouling rate is presented as the fraction of the rate in the uncoated case. The horizontal plane in each plot corresponds to the performance of the uncoated exchanger for its original values of π ΜπΉ , tind and ο΄. The calculated optimal cycle times in Figure 3(a) shows that increasing the induction period over the range of values considered shortens tcyc* slightly, while a lower fouling rate results in a longer operating period and cycle length. tcyc* is more sensitive to fouling rate: for example, the point where tcyc* 13 approaches 1 is most sensitive to fouling rate, followed by cleaning time and then induction period. Finally, a shorter cleaning period also gives shorter cycle times. Figure 3(b) shows families of results for different cleaning times plotted as planes of total annualised cost. Some general trends are evident, namely (i) reducing the cleaning time reduces π π , particularly when tcyc is short; (ii) increasing tind reduces π π , albeit relatively weakly, and (iii) π π is most sensitive to the fouling rate, with a lower fouling rate than the uncoated case required to give π π < 1. The capital cost contribution to π π means that the fouling rate required to give ο¦* = 1 is lower (i.e. better mitigation performance) than that required to give tcyc* = 1. Reducing the cleaning time, ο΄, to 2 days also has a significant effect. The effect of the coating on energy losses in Figure 3(c) shows benefits for all cases where the fouling rate is reduced from the base case, and also where the induction period is extended. Reducing the cleaning time also gives noticeable improvement in Eloss*. Comparing the region where Eloss* < 1 in Figure 3(c) with that for ο¦* < 1 (Figure 3(b)) indicates that the latter requires better antifouling performance (lower fouling rate, longer induction period and/or shorter cleaning time) in order to be economically favourable. Figure 3(b) suggests that the fouling rate should be reduced to less than 40% of that in the uncoated unit in order for coating to be economically attractive to the operator with this costing (ο‘ = 1). This is a sizeable reduction and arises from the cost of installing a new unit: it illustrates the balance between capital costs and energy prices. Significantly better performance will be required if the coating is expensive to manufacture or the vendor wishes to negotiate a mutually attractive price for the coating. 3.2 Case Study II. Fluorocarbon coating of a shell and tube heat exchanger to combat hard water scaling This case considers a fluorocarbon or similar coating which can introduce a noticeable thermal resistance. Oldani et al. (2013) reported a 40% reduction in linear fouling rate for water-based fouling with a perfluoropolyether (PFPE) film on tubes in a shell-and-tube heat exchanger. This performance is subjected to the above techno-economic analysis and further factors considered. Although the coating reduced the rate of scale deposition, its relatively low thermal conductivity, of around 0.1 W m-1K-1, gives a lower Ucl value. In order to achieve the same heat duty as the uncoated heat exchanger with the same temperature driving force, the existing unit would have to be replaced by one with larger area, given by π΄ππππ‘ = πππ,π’ππ × π΄π’ππ πππ,ππππ‘ (22) 14 This increase in area is assumed to be small enough that installing the replacement unit does not require major structural changes, e.g. supports, space and associated expense. The increase in area will be accompanied by higher capital cost. Table 5 summarises the parameters for this case study. Two stainless steel shell-and-tube heat exchangers are considered, again with one shell pass and two tube passes each. Oldani et al. (2013) used a liquid phase coating process so that the tubes could be coated internally and externally. They did not report whether deposition was limited to one side of the tubes. The design and performance parameters were taken from Oldani et al. (2013) and typical industry values. Equation [21] was used to calculate the effectiveness. πΆπ» was calculated using Equation [13], as in Case Study I. The effect of coating thickness on heat exchanger area and capital cost for the base case design is illustrated in Figure 4. Increasing the coating thickness reduces U, and the increase in ο¦cap and Acoat becomes significant when ο€coat > 10 µm for this example. A 100 µm thick layer is unlikely to be considered for practical use but is included here to convey the impact of such layers on heat transfer performance. While Figure 4 indicates that coating thicknesses of order 10 µm are desirable for this application, durability criteria as well as resistance to cleaning agents may require use of thicker layers. Oldani et al. (2013) did not indicate any effect of the coating on the induction period so tind is set at zero for both surfaces. The cleaning time for the units is similarly taken to be the same. A tLF value of 10 years is used in the base case calculation. The time taken fouling to cause U to fall to half of its clean state, Ucl/2, is 157 days for the uncoated heat exchanger and 269 days for the PFPE-coated unit. The results for the base case, with a coating thickness of 10 µm, are shown in Figure 5 and Table 6. The coated stainless steel heat exchanger gives an 18% reduction in the operation cost and extends the ∗ operating period by 27%. There is a 17% reduction in energy losses (πΈπππ π = 0.83). However, this level of improved performance is not sufficient to offset the cost of the new exchanger. Even in the absence of coating costs (ο‘ set to 1), the total amortised cost for operating and capital costs is comparable to the existing unit, with π ∗ = 1.01 for tLF =10 yr. This indicates that replacement of the unit with a PFPEcoated one is not economically attractive for this set of input parameters and cost structure. Extending tLF (requiring the coating to be effective for longer times), higher energy costs etc., could all be explored in a search of the costing parameter space for economically attractive combinations. Coating carbon steel? The scenarios considered to this point have all assumed that the coating is used to improve the fouling performance of stainless steel surfaces. Stainless steel surfaces are frequently used to avoid corrosion and contamination problems. Fluorocarbon coatings offer good corrosion resistance (McKeen, 2006). If the coating is durable and prevents corrosion as well as mitigating fouling, it may be possible to use 15 a cheaper material of construction, such as carbon steel, to provide the mechanical strength needed for the unit. Carbon steel (CS) also has a thermal conductivity three times that of SS, so the heat transfer penalty associated with a thick coating can be offset by improved conduction through the steel. CS units are also considerably cheaper, as shown in Figure 6. The option of using a coated CS unit is investigated in this scenario. Results for a coated CS unit for the base case are given in Table 6. The U value for the unit is comparable to the uncoated SS exchanger and the additional area is small. The time taken to reach a fouling Biot number of 1 is 262 days for the coated CS unit, representing a reduction of 7 days compared to the SS unit. The tcyc* and πππ values differ slightly from the SS unit owing to the difference in UA. The capital cost is 13.3 US$ day-1, which is about a third of the cost of the coated SS unit, at 43.6 US$ day-1. This reduces π ∗ to 0.89, at which point the coated exchanger is economically attractive. The maximum cost of coating can also be calculated, at 101.5k US$ for a 10-year lifetime, representing a maximum ο‘ value of 3.1. This concept is not considered further here: it is presented to promote discussion and research. Coating performance The results reported by Oldani et al. (2013) are now extended in a parameter sweep to establish the economic attractiveness of a theoretical fluorocarbon coating. The thickness of the coating is varied from 0.1 to 100 µm, and the associated fouling rate is assumed to vary from 0.1 to 1.5 times that reported by Oldani et al. (2013) for the uncoated SS unit. A deterministic model of the effect of coating thickness on fouling behaviour is not offered here: this would be a useful tool as it would guide coating development into economically feasible regions. The results for coated SS and coated CS units are presented as 3-D plots in Figures 7 and 8. Figure 7 shows the effect of fouling parameters for a fixed coating thickness of 10 µm, as in the base case discussed above. The fouling induction period is varied from 0 to 10 days and two cleaning times are considered, namely 2 and 4 days. The plots of tcyc* in Figure 7(a) indicate little influence of tind, but high sensitivity to the fouling rate, as in Case Study I. This is expected as the induction period is relatively short compared to the operating times. The cleaning time has a significant effect, however, indicating that the heat lost during the period when the unit is off-line for cleaning is appreciable. This aspect highlights another target for coatings in fouling service, to promote rapid cleaning, as reported for dairy pasteuriser units by Beuf et al. (2004) and heat pump systems processing treated sewage water (Yang et al., 2014). 16 The sensitivity to fouling rate and cleaning period is emphasised in the total annualised cost in Figure 7(b). The influence of material of construction is now evident, with the CS units always lower than the SS equivalent, and the plane for the CS unit with a 4 day cleaning time comparable to that for a SS unit with a 2 day cleaning time. The desirability of improved cleaning performance is very evident in this plot. The fouling induction period does have some effect on Ο*, evident from where the planes cut the Ο* = 1 plane, at higher fouling rates where the optimal operating periods are shorter. When the coating gives a reduction in fouling rate of 50% or greater, there is little influence of tind. The Eloss* plots in Figure 7(c) all show a positive benefit of the coating. Reducing the fouling rate has the strongest effect, followed by shortening the cleaning time. The induction period has a noticeable effect where the fouling rate is high and close to that of the uncoated exchanger: this is, however, unlikely to be considered satisfactory for an ‘antifouling’ coating. Figure 8 shows the effect of coating thickness for a SS and a CS exchanger with fouling induction periods of 0 days and 5 days. There is little effect of fouling induction period on tcyc* across the parameter space in Figure 8(a), as expected from Figure 7(a). There is little difference between the two coating options over the parameter space. The planes for tcyc* are curved, with larger tcyc* values for thicker layers, indicating improved performance under these conditions. This is the effect of the extra heat transfer area added to match Qcl as the coating thickness increases. There is a noticeable col in the 3-D plot where tcyc* = 1 for thicknesses in the range of 1-10 µm. It is an interesting feature, but only applies to cases where there is little reduction in the fouling rate as a result of the coating so is not considered further here. For coatings which give reduction in fouling rate, the increase in tcyc* occurs when coatings are more than 10 µm thick. Figure 8(b) shows that coating is economically attractive, i.e. π ∗ < 1, when the fouling rate is reduced. There is some sensitivity in π ∗ to the fouling induction period at high fouling rates, which are associated with shorter operating times and hence induction period length. At lower fouling rates (good antifouling performance) there is negligible sensitivity to tind. The point at which π ∗ = 1 is insensitive to coating thickness, which is attributed to the balance between extra capital cost and improved operating performance. At low fouling rates there is no effect of ο€coat on π ∗ for the CS unit and for the SS unit for thicknesses less than 50 µm. This suggests that coatings on stainless steel should not exceed this thickness (for the case study parameters, i.e. heat transfer conditions, costs, etc. considered here). The plot of energy losses in Figure 8(c) shows that the coatings are attractive for all cases where the fouling rate is reduced, which is expected. There is a relatively small effect of fouling induction period as discussed above. The influence of coating thickness on Eloss* is relatively weak for a given extent of fouling rate reduction until ‘thick’ coatings are used, at which point the cost of the coating on SS 17 outweighs the energy saving to give an increase in Ο* in Figure 8(b) but for the CS unit the difference in costs is small and Ο* is uniformly attractive for good antifouling performance. 3.3 Case Study III. Fouling and cleaning a Ni-PTFE-coated dairy plate heat exchanger Fouling is a major problem in food and beverage manufacturing operations, not only in terms of heat transfer and obstruction to flow, but also in affecting product quality and hygiene. Milk pasteurisation and sterilisation units in dairy processing require cleaning, often on a daily basis (Jun and Puri, 2005), due to the high rates of protein and mineral deposition on heat transfer surfaces and the associated risk of microbial contamination. Frequent interruption and the large volumes of cleaning agents required incur significant productivity losses and cleaning costs. Fouling mitigation in milk processing has been investigated at some length, and ‘antifouling’ coatings have been found to be effective on reducing unwanted deposition in heat exchangers, as shown in Table 2. Surface modifications must also be durable as well as resistant to frequent contact with acid, alkali and oxidising cleaning and disinfection agents. The latter agents may be used for periodic cleaning of the whole system or switchover to other product streams. Barish and Goddard (2013) studied the performance of a model plate and gasket heat exchanger (PHX) with Ni-P-PTFE (nickel-phosphorus-polytetrafluoroethylene) coated plates operating under simulated pasteurisation conditions and showed a significant reduction in fouling levels. The (anti-) fouling performance of the coating was similar over several repeated fouling and cleaning actions, indicating a durable character. This is one of the few studies of repeated cycle PHX performance in the literature and their data are used here in an evaluation of the performance of such coatings. It should be noted that many types of fluorocarbon coatings exist and their performance will be determined by the method of assembly and quality of manufacturing as well as their chemistry (McKeen, 2006). The results presented here should be interpreted as representing all fluorocarbon coatings. Consider two stainless steel plate and gasket heat exchangers, one of which has a 10 µm fluorocarbon layer on the product side. The PHX configuration is a 1-1 pass counterflow arrangement, with raw milk as the cold stream and water as the hot stream. The effectiveness is given by Kandlikar and Shah (1989): π= 1 − ππ₯π[−πππ(1 − πΆπ )] 1 − πΆπ ππ₯π[−πππ(1 − πΆπ )] (23) As the outlet temperature of the process stream is critical for pasteurisation, it must be maintained at its target value. The milk flow rate is also held constant to maintain the mean residence time. As deposition proceeds, the inlet temperature of the heating water stream is raised in order to achieve the desired duty, and equations 13 and 14 are used in the model for this Case Study. 18 The parameters used in the simulations are presented in Table 7. Barish and Goddard (2013) reported a 90% reduction in fouling rate for their Ni-P-PTFE-coated surfaces, but it was not possible to extract reliable values of induction periods from their data, so the uncoated and coated surfaces are both allocated a π‘πππ value of 2 hours. The cleaning-in-place operation was initially considered to be unaffected by coating, so πππππ‘ = ο΄ = 4 hours. The characteristic time scale for fouling is noticeably faster in this Case Study as the both the fouling rate and Uc are large (Ucl = 7500 W m-2 K-1). The time taken for the fouling Biot number to reach 1 is 5.5 hours for the uncoated unit and 53 hours for the coated unit. Figure 9 shows that the fluorocarbon coating would give a 70 % reduction in operating costs and extend the processing cycle by more than 3.5 times. The coated CS scenario described in Case Study II was not considered in this Case Study. Hygiene restrictions Food manufacturing processes are subject to regular cleaning and disinfection cycles to ensure product hygiene. The optimised PHX operating cycle length afforded by coating could be longer than the maximum hygienic operating period, denoted thyg. The hygiene constraint would then require the unit to be cleaned before topt, such that the benefit of the improved heat transfer performance is limited by the need to guarantee product quality and safety. Figure 9 illustrates this for the base case scenario with thyg set at 48 h (2 days), which is longer than topt for the uncoated unit so that its optimal ο¦op value of is not affected. The thyg constraint reduces the cycle ∗ time for the coated exchanger by 30 % but the effect on performance (see π ∗ and πΈπππ π in Table 8) is not large as the locus is locally quite shallow: the coating still yields around 70 % savings in costs and a 60 % reduction in energy losses. Figure 9 suggests that if thyg was shortened to 24 h the difference between the optimal and the limited performance for the coated unit would be significant. The summary of performance in Table 8 includes the results for this case: ο¦* increases from 0.34 (for thyg = 48 h) to 0.51 (for thyg = 24 h). Table 8 shows that the contributions to the total annualised cost are dominated by operating costs due to regular process interruption and cleaning, at appreciable cost. The capital contribution (calculated with ο‘ = 1) constitutes around 2 % of the total annualised cost, so replacing the existing unit with a coated one would be attractive. The maximum value of ο‘ for thyg = 48 h is 78, indicating a wide margin for the coating cost (which would be divided between manufacturing cost, vendor profit and incentive for the purchaser). This margin is reduced to around 55 for thyg =24 h. Microbiological factors, which set the value of thyg on the basis of anticipated microbial growth, are clearly important. It is quite likely 19 that the value of thyg would differ for a coated unit as the surface coating is likely to affect the adhesion and growth of micro-organisms. However, the extent to which thyg would be increased is not currently estimable, and a rigorous microbiological testing regime on an installed unit would be required to validate a different thyg value in practice. Fouling parameter sensitivity The effect of different fouling parameters, i.e. the antifouling performance of the coating, was investigated for the base case 10 µm thick coating. Figure 10 shows that the coated cycle length is not significantly affected by an increase in induction period and cleaning time. There is little effect of tind and τ on total annualised cost, Ο*, at low fouling rates, whereas there are noticeable differences at high fouling rates. A decrease in fouling rate will cause an extension of cycle length and will imply cheaper costs. As the capital cost contribution in this case is small (less than 3% Ο* for the scenarios in Table 8) due to the high costs of cleaning, a small improvement in fouling performance makes unit replacement economically attractive. Eloss* values are then similar to Ο* and are not plotted, for brevity. Figure 11 demonstrates the impact of the hygiene constraint, thyg, on tcyc* and Ο* for different coating thicknesses and fouling rates. As noted above, a deterministic relationship between the coating thickness and fouling rate would be a valuable addition to this analysis. In the absence of hygiene limitations, lower fouling rates and thicker coatings give rise to longer cycles and tcyc* approaches 20× the uncoated value. Figure 11 shows the results for thyg = 1 and 2 days. In Figure 11(a) the thyg limit truncates the rise in tcyc*, giving rise to a larger value of Ο*. The cost savings are still favourable for both thyg scenarios, but thyg = 24 h limits Ο* to values > 0.5. Microbiological considerations are therefore critical and may ultimately determine the attractiveness of coatings. Figure 12 presents the performance for a coated exchanger subject to a maximum cycle length of 48 h (i.e. without significant microbiological impacts) for different fouling rates, induction periods and cleaning times. tcyc* is longer and Ο* is reduced with lower fouling rates and a higher value of tind, as expected from the results above. There is a noticeable truncation in tcyc* at lower fouling rates owing to the thyg constraint becoming active but the effect on Ο* is small. The down-time required for cleaning, taken as 2, 4 or 5 hours (cf. 4 hours for the uncoated case), causes a shift in tcyc* but the maximum topt value is the same for all cases. Cleaning downtime only affects Ο* at high fouling rates. Figure 12(b) also shows that coating is economically attractive across the range of fouling parameters considered. Splitting savings: Value pricing and operation cost reduction 20 Table 8 shows that the coated heat exchanger with a 10 µm thick coating subject to thyg = 2 days gives Ο* = 0.34, representing a 66 % reduction in costs, if no expenses related to coating are considered in the capital costs (α = 1). A coated unit will only be manufactured and adopted if it is attractive to both producers and operators. It follows that α > 1 and Ο* < 1 so each party can benefit from exchanger replacement. The increased performance of the coated exchanger in Table 8 provides cost savings of 82.2 k$/year, which represents an αmax value of 79 for Ο* = 1, albeit with no benefit to the operator. Given that there must be an incentive for the operator to adopt the technology, a saving based on reduction in operating costs is employed here. For example, for a 25 % reduction in operating costs, the maximum cost associated with manufacturing this PHX is 51.9 k$/year, giving αmax = 49, and the operator would save 31.3 k$/year. For Ο* = 0.5, the maximum annualised capital cost falls to 20.6 k$/year and the maximum cost multiplier αmax is then 20. These values will in turn depend on the lifetime of the coating or the accounting period, whichever is shorter. Figure 13 presents the calculated maximum values of α for different fouling rates and induction periods with set saving fractions. The horizontal plane at the base of the plot represents α =1 and is included to mark where there is no extra cost or benefit derived by the manufacturer. The uppermost plane shows the results for Ο* = 1, where the cost of the new, coated unit matches the savings generated by its introduction. This represents the maximum price that the manufacturer could expect to market the coated devices at, albeit with no savings for the customer. The intermediary planes describe αmax values where the operator gains a prescribed benefit from installing the coated exchanger. At Ο* = 0.75, the operator has set a target of 25% improvement in annualised operating costs, and at Ο* = 0.5 the saving is twice this. As the operator demands a larger share of the savings (lower Ο*) the manufacturer is compelled to manufacture the surfaces more cheaply (or accept a lower profit) and to achieve lower fouling rates. There is relatively little effect of induction period for this scenario. Note on application Several parameters have been set at arbitrary or typical values in order to generate Figure 13, and these would be replaced by more reliable values based on local experience when modelling particular applications. The cost factors are particularly important in these techno-economic analyses and will vary between industrial sector and location, as will the timescales. Figure 13 nevertheless summarises the key finding from this study, in demonstrating that surfaces for mitigating fouling in processes subject to repeated fouling and cleaning cycles will require guaranteed long term antifouling effectiveness (here, with fouling rate reduction by a factor of at least 5× for the ο¦* = 0.50 case) in order to be considered for industrial application. 21 4. Conclusions The economics of mitigation of fouling by coating heat exchanger surfaces has been investigated using quantitative models which included both the capital cost of replacing existing units and optimised operating costs of repeated fouling and cleaning cycles. The effect of the coating on heat transfer and the surface area of the exchanger for constant duty applications was considered. The increase in robustness towards fouling resulting from increased exchanger surface area was evident and noted. For most of the case studies considered here, the annualised costs associated with adding an antifouling surface were smaller than the benefit (savings in operation costs) resulting from enhanced performance, in which case replacement of the unit is economically attractive as long as the improved fouling behaviour lasts the lifetime of the heat exchanger. Coating also extends the length of equipment operating periods in fouling and cleaning cycles and reduces the additional energy required to compensate heat transfer inefficiencies. One Case Study considered the scenario where the coating is able to prevent corrosion completely so that a stainless steel unit could be replaced by a coated carbon steel one. This both compensated for the reduction in heat transfer associated with a coating of finite thickness and also reduced the capital cost of the unit. Another Case Study considered a food processing application wherein the fouling and cleaning cycle is subject to hygiene-driven cycle length limits. The latter can dominate the financial attractiveness of such coatings. The calculations allowed the cost saving benefits and the maximum increase in installed price that a coated unit could be sold for. This information allows the value pricing margin to be identified and the associated levels of fouling mitigation effectiveness to be quantified. Data for the performance of coatings were based on studies in the open literature. The modelling framework presented here can be used to assess the economic attractiveness of coatings once such data become available. Alternatively, a deterministic model relating fouling behaviour to coating nature and thickness could be used to identify performance targets for such coatings and guide coating development. Acknowledgements Funding for CB’s doctoral studies by the Friedrich-Ebert-Stiftung and Max-Buchner- Forschungsstiftung is gratefully acknowledged, as a scholarship for LG from the University of São Paulo Innovation Agency. 22 5. Nomenclature Roman A Heat transfer area, m2 Ccl Cost of cleaning, US$ unit-1 cE Energy cost, US$ J-1 Cequip Cost of the uncoated equipment, US$ CH Cost of additional heating, US$ Cp Specific heat capacity, J kg-1 K-1 Cr Heat capacity flow ratio, - Eloss Annual total energy loss, J ∗ πΈπππ π Ratio of energy losses due to fouling, - h Film transfer coefficient, W m-2K-1 πΜ Mass flow rate, kg s-1 n number of cleaning cycles per year, - NTU Number of transfer units, - Q Heat duty, W Rcoat Thermal resistance of the coating, m2K W-1 Rf Thermal resistance of the fouling layer, m2K W-1 π Μf Fouling rate, m2K J-1 Rmetal Thermal resistance of the tube metal, m2K W-1 t Time, day π‘ππ¦π Optimum cycle time, day ∗ π‘ππ¦π Ratio of optimum cycle times, - T temperature, K U Overall heat transfer coefficient, W m-2K-1 Greek ο‘ Equipment cost multipilication factor due to coating, - ο€coat Thickness of coating, m ο€f Thickness of foulant, m ο€metal Thickness of tube, m ο₯ Effectiveness, - ο¬coat Thermal conductivity of coating, W m-1K-1 ο¬f Thermal conductivity of deposit, W m-1K-1 ο¬metal Thermal conductivity of tube, W m-1K-1 ο¦*ο Ratio of the total annualised cost for the coated unit over the uncoarted unit, 23 ο¦capο Time averaged capital cost, US$ day-1 ο¦opο Time averaged operation cost, US$ day-1 ο¦Tο Time averaged total annualised cost, US$ day-1 ο΄ Time taken to clean a unit, days Subscript add Additional c Cold stream cl Clean coat Coated h Hot stream hyg Hygienic constraint in Inlet ind Induction LF Life time of the heat exchanger max Maximum min Minimum opt Operating out Outlet p Processing period unc Uncoated Superscript cl Clean state r Required condition to achieve the same amount of heat as the clean state 24 Appendix Calculation sequence of economic performance parameters of uncoated and coated heat exchangers Step Equation 1. Initialization. Selection of reference heat exchanger without coating: surface area, Aunc, clean overall heat transfer coefficient, Ucl,unc, clean heat duty, Qcl with an induction period of tind,unc, constant fouling rate, π Μπ,π’ππ and a cleaning period of ο΄. 0, π‘ < π‘πππ π π (π‘) = { Μ π π × (π‘ − π‘πππ ), π‘ ≥ π‘πππ 2. At a given time instance, t, calculate fouling resistance, Rf 1 3. Calculate overall heat transfer coefficient, U π = 1 πππ + π π Eq. (3) Eq. (4) Ucl is the clean overall heat transfer coefficient 4. Calculate exchanger effectiveness, ο₯ π = π(πππ, πΆπππ , πΆπππ₯ ) Here Cmin and Cmax are the minimum and maximum heat capacity flow rates, respectively. NTU is given by πππ = ππ΄ Eq. (10) πΆπππ π = πππππ₯ 5. Calculate operating heat duty based on Eq. (7) Here Qmax is the maximum heat duty given by ππππ₯ = πΆπππ (πβ,ππ − ππ,ππ ) Th,in and Tc,in are the hot stream and cold stream inlet temperatures. 6. Calculate the additional energy cost, Ch(tp) during an operating period of tp, due to fouling. If the process achieves the target operating conditions by (a) supplying additional heating, integrate steps 2 to 5 (a) πΆπ» (π‘π ) = ππΈ ∫π‘π(πππ − π(π‘))ππ‘ Eq. (12) (b) πΆπ» (π‘π ) = ππΈ ∫π‘π ππππ (π‘)ππ‘ Eq. (13) 0 0 Here, CE is the energy cost. (b) modifying inlet temperature ππππ (π‘π ) = π ππ πΜ β πΆπ,β (πβ,ππ (π‘π ) − πβ,ππ ), πππππ‘πππππ βπππ‘πππ ππ ππππ’ππππ ππ π πΜ π πΆπ,π (ππ,ππ − ππ,ππ (π‘π )) , {πππππ‘πππππ πππππππ ππ ππππ’ππππ 7. Calculate the time averaged operating cost, πππ 25 πππ (π‘π ) = πΆπ» (π‘π )+ πΆπΈ πππ π+ πΆππ π‘π + π Eq. (16) 8. Evaluate optimum operating time, tp,opt tp,opt is when: ππππ ππ‘π = 0: π 2 πππ ππ‘π 2 >0 Eq. (17) This gives an optimum cycle, tcyc of: tcyc = tp,opt + π 9. Calculate the optimum averaged operating cost πππ (π‘π,πππ‘ ) (from step 7) 10. Calculate the time averaged capital cost ππππ = πΌπΆπππ’ππ (π΄) Eq. (20) π‘πΏπΉ ο‘ is a cost multiplier associated with coating. If no coating is applied, ο‘ = 1. tLF is the asset lifetime. 11. Calculate the total time averaged cost, π π π π = ππππ + πππ Calculate annual total energy loss, Eloss (a) πΈπππ π = π [∫0 π,πππ‘(πππ − π(π‘))ππ‘ + πππ π] Eq. (18) π‘ π‘ (b) πΈπππ π = π [∫0 π,πππ‘ ππππ (π‘)ππ‘ + πππ π] Eq. (19) 12. Follow steps 2 to 11 for uncoated heat exchanger to obtain tcyc,unc, πππ,π’ππ , πΈπππ π ,π’ππ . 13. Calculate new area for the coated unit, Acoat, to give the same operating condition with a coating thickness of ο€coat and a coating thermal conductivity of ο¬coat. The coating gives an induction period of tind,coat, constant fouling rate, π Μπ,ππππ‘ and a cleaning period of ο΄. π΄ππππ‘ = πππ,π’ππ πππ,ππππ‘ × π΄π’ππ Here Ucl,coat is the clean overall heat transfer coefficient of the coated unit given by 1 πππ,ππππ‘ = 1 ββ + πΏπππ‘ππ ππππ‘ππ + π ππππ‘ + π ππππ‘ = πΏππππ‘ ⁄πππππ‘ 14. Follow steps 2 to 11 for the coated heat exchanger to obtain tcyc,coat, πππ,ππππ‘ , πΈπππ π ,ππππ‘ . 15. Calculate dimensionless performance indices ∗ π‘ππ¦π = π‘ππ¦π,ππππ‘ ⁄π‘ππ¦π,π’ππ π ∗ = π π,ππππ‘ ⁄πππ,π’ππ ∗ πΈπππ π = πΈπππ π ,ππππ‘ ⁄πΈπππ π ,π’ππ 26 Eq. (22) 1 βπ Eq. (5) Eq. (6) References AlβJanabi A., Malayeri M.R., MüllerβSteinhagen H. (2010). Experimental Fouling investigation with electroless NiβP coatings. International Journal of Thermal Science, 49, 1063–1071. Balasubramanian S., Puri V.M. (2008). Fouling mitigation during product processing using a modified plate heat exchanger surface. Transactions of ASABE, 51 (2), 629–639. Balasubramanian S., Puri, V.M. (2009). Reduction of milk fouling in a plate heat exchanger system using food-grade surface coating. Transactions of the ASABE, 52 (5), 1603-1610. Banerjee I., Pangule R.C., Kane R.S. (2011). Antifouling coatings: Recent developments in the design of surfaces that prevent fouling by proteins, bacteria, and marine organisms. Advanced Materials, 23 (6), 690–718. Bani Kananeh A.B., Scharnbeck E., Kück U.D., Räbiger N. (2010). Reduction of milk fouling inside gasketed plate heat exchanger using nano-coatings. Food and Bioproducts Processing, 88 (4), 349–356. Barish J.A., Goddard J.M. (2013). Anti-fouling surface modified stainless steel for food processing, Food and Bioproducts Processing, doi:10.1016/j.fbp.2013.01.003 Barish J.A., Goddard J.M., (2014). Stability of nonfouling stainless steel heat exchanger plates against commercial cleaning agents, Journal of Food Engineering, 124, 143-151. Beuf M., Rizzo G., Leuliet J. C., Müller-Steinhagen H., Yiantsios S., Karabelas A. Benezech T. (2004). Fouling and cleaning of modified stainless steel plate heat exchangers processing milk products. In: Proceedings of International Conference Heat Exchanger Fouling and Cleaning (pp. 99–106). Santa Fé, USA Bott T.R. (1995) Fouling in Heat Exchangers, publ. Elsevier, Amsterdam. Boxler C., Augustin W., Scholl S. (2013a). Cleaning of whey protein and milk salts soiled on DLC coated surfaces at high-temperature. Journal of Food Engineering, 114 (1), 29–38. Boxler C., Augustin W., Scholl S. (2013b). Fouling of milk components on DLC coated surfaces at pasteurization and UHT temperatures. Food and Bioproducts Processing, 91, 336–347. Boxler C., Augustin W., Scholl S. (2013c). Influence of surface modification on the composition of a calcium phosphate-rich whey protein deposit in a plate heat exchanger. Dairy Science & Technology, doi: 10.1007/s13594-013-0142-5. Britten M., Gree M. L., Boulet M., Paquin P. (1998). Deposit formation on heated surfaces – effect of interface energetics. Journal of Dairy Research, 55 (4), 551–562. Carbon Trust (2011) Industrial Energy Efficiency Accelerator. Guide to the Dairy Sector, Report CTG033, Carbon Trust, UK Coletti F., Ishiyama E.M., Machietto S., Paterson W.R., Wilson D.I. (2010). Impact of deposit ageing and surface roughness on thermal fouling: distributed model, AIChEJ, 56(12), 3257-3273. 27 Dowling D.P., Nwankire C.E., Riihimäki M., Keiski R., Nylén U. (2010). Evaluation of the antifouling properties of nm thick atmospheric plasma deposited coatings. Surface and Coatings Technology, 205 (5), 1544–1551. Dupeyrat M., Labbé J.-P., Michel F., Billoudet F., Daufin G. (1987). Mouillabilité et interactions solide-liquide dans l'encrassement de divers matériaux par du lactosérum et du lait. Le Lait, 67 (4), 465–486. Ebnesajjad S. and Khaladkar P.R. 2005, Flouropolymers Applications in Chemical Processing Industries, publ. William Andrew, Norwich NY. Förster M., Bohnet M. (2000). Modification of molecular interactions at the interface crystal/heat transfer surface to minimize heat exchanger fouling, International Journal of Thermal Sciences, 39 (7), 697–708. Geddert T., Bialuch I., Augustin W., Scholl S. (2009). Extending the induction period of crystallization fouling through surface coating. Heat Transfer Engineering, 30 (10–11), 868– 875. Geddert T., Augustin W., Scholl S. (2011). Influence of surface defects and aging of coated surfaces on fouling behavior. Heat Transfer Engineering, 32, 300–306. Gordon K.P., Hankinson D.J., Carver C.E. (1968). Deposition of milk solids on heated surfaces. Journal of Dairy Science, 51 (4), 520–526. Guignard C., Verones F., Loerincik Y., Jolliet O. (2009). Environmental/Ecological impact of the dairy sector. Bulletin of the International Dairy Federation, 436, 1-60. Incropera F.P., DeWitt D.P., Bergman T.L., Lavine A.S. (2001). Fundamentals of Heat and Mass Transfer, 5th Edition. ed. Wiley. Ishiyama E.M., Paterson W.R., Wilson D.I. (2008). Thermo-hydraulic channelling in parallel heat exchangers subject to fouling, Chemical Engineering Science, 63(13), 3400-3410. Ishiyama E.M., Paterson W.R., Wilson D.I. (2009). The effect of fouling on heat transfer, pressure drop and throughput in refinery preheat trains: Optimisation of cleaning schedules, Heat Transfer Engineering, 30(10-11), 1-10. Ishiyama E.M., Paterson W.R., Wilson, D.I. (2011). Optimum cleaning cycles for heat transfer equipment undergoing fouling and ageing. Chemical Engineering Science, 66, 604–612. Jun S. and Puri V.M. (2004). Fouling models for heat exchangers in dairy processing: a review, J. Food Process Engineering, 28, 1-34. Kandlikar S.G., Shah R.K. (1989). Asymptotic effectiveness-NTU formulas for multipass plate heat exchangers. Journal of Heat Transfer, 111(2), 314-321. Karlsson C.A.-C., Wahlgren M.C., Trägårdh A.C. (1996). β-Lactoglobulin fouling and its removal upon rinsing and by SDS as influenced by surface characteristics, temperature and adsorption time. Journal of Food Engineering, 30, 43–60. Kays W.M., London A.L. (1964). Compact Heat Exchangers, Second Edition. ed. McGraw-Hill Book Company. 28 Kho T., Zettler H.U., Müller-Steinhagen H., Hughes D. (1997). Effect of flow distribution on scale formation in plate and frame heat exchangers. Chem. Eng. Res. Des. 75, 635–640. Ma R.S.T. and Epstein N. (1981) Optimum cycles for falling rate processes, Can. J. Chem. Eng, 59, 631–633. Mauermann M., Eschenhagen U., Bley T., Majschak J. (2009). Surface modifications - Application potential for the reduction of cleaning costs in the food processing industry. Trends in Food and Science & Technology, 20, 8–15. McGuire J., Swartzel K.R. (1989). The influence of solid surface energetics on macromolecular adsorption from milk. Journal of Food Processing and Preservation, 13, 145–160. McKeen, L.W. (2006). Fluorinated Coatings and Finishes Handbook, publ. William Andrew, Norwich NY. Müller-Steinhagen H., Zhao Q. (1997). Investigation of low fouling surface alloys made by ion implantation technology, Chemical Engineering Science, 52 (19), 3321–3332. Müller-Steinhagen, H., Malayeri, M.R. and Watkinson, A.P. (2011) Heat exchanger fouling: cleaning and mitigation techniques, Heat Transfer Eng., 32(3-4), 189-196. Naik J.B., Mishra S., Deore D. (2010). Investigation of scale mitigation and sequestering properties of some polyelectrolytes. Polym. - Plast. Technol. Eng. 49, 69–73. Oldani V., Bianchi C.L.M., Biella S., Pirola C., Cattaneo G. (2013). Use of perfluoropolyether coatings to prevent fouling on heat exchanger metal surfaces. Proc. Heat exchanger fouling and cleaning conference, Budapest, Hungary, http://www.heatexchangerfouling.com/papers/papers2013/45_Oldani_F.pdf Patel J.S., Bansal B., Jones M. I., Hyland M. (2013). Fouling behaviour of milk and whey protein isolate solution on doped diamond-like carbon modified surfaces. Journal of Food Engineering, 116 (2), 413–421. Peters M.S., Timmerhaus K.D., West R.E. (1990). Plant Design and Economics for Chemical Engineers, Fourth Edition. ed. McGraw-Hill Education. Pogiatzis T., Ishiyama E.M., Paterson W.R., Vassiliadis V.S., Wilson D.I. (2012). Identifying optimal cleaning cycles for heat exchangers subject to fouling and ageing, Applied Energy, 8(1), 6066. Premathilaka S.S., Hyland M.M., Chen X.D., Watkins L.R., Bansal B. (2007). Interaction of whey protein with modified stainless steel surfaces. In: Hans Müller-Steinhagen, M. Reza Malayeri, and A. Paul Watkinson (Eds.), Proceedings of 7th International Conference on Heat Exchanger Fouling and Cleaning - Challenges and Opportunities (pp. 150–161). The Berkeley Electronic Press, Tomar, Portugal. Rosmaninho R., Melo L.F. (2006). Calcium phosphate deposition from simulated milk ultrafiltrate on different stainless steel-based surfaces. International Dairy Journal, 16 (1), 81–87. Rosmaninho R., Melo L.F. (2008). Protein-calcium phosphate interactions in fouling of modified stainless-steel surfaces by simulated milk. International Dairy Journal, 18, 78–80. 29 Rosmaninho R., Rizzo G., Müller-Steinhagen H., Melo L.F. (2008). Deposition from a milk mineral solution on novel heat transfer surfaces under turbulent flow conditions. Journal of Food Engineering, 85 (1), 29–41. Rungraeng N., Cho Y.-C., Yoon S.H., Jun S. (2012). Carbon nanotube-polytetrafluoroethylene nanocomposite coating for milk fouling reduction in plate heat exchanger. Journal of Food Engineering, 111 (2), 218–224. Santos O., Nylander T., Schillen K., Paulsson M., Trägårdh C. (2006). Effect of surface and bulk solution properties on the adsorption of whey protein onto steel surfaces at high temperature. Journal of Food Engineering, 73 (2), 174–189. Santos O., Anehamre J., Wictor C., Tornqvist A., Nilsson M. (2013). Minimizing crude oil fouling by modifying the surface of heat exchangers with a flexible ceramic coating, Proc. Heat Exchanger Fouling & Cleaning X, http://heatexchangerfouling.com/papers/papers2013/12_Santos_F.pdf Tijing L.D., Yu M.-H., Kim C.-H., Amarjargal A., Lee Y.C., Lee D.-H., Kim D.-W., Kim C.S. (2011). Mitigation of scaling in heat exchangers by physical water treatment using zinc and tourmaline. Applied Thermal Engineering 31, 2025–2031. Weis A., Bird M.R. (2001). The influence of multiple fouling and cleaning cycles upon the membrane processing of lignosulphonates. Food Bioproducts Processing, Part C 79, 184–187. Xu T., Flapper J. (2009). Energy use and implications for efficiency strategies in global fluid-milk processing industry. Energy Policy 37, 5334–5341. Yang Q., Wilson D.I., Chang S. and Shi L. (2014) A new approach for mitigating heat exchanger biofouling by promoting online cleaning using a sacrificial paraffin coating, Heat Transfer Engineering, in press. Yoon J., Lund D.B. (1994). Comparison of two operating methods of a plate heat exchanger under constant heat flux condition and their effect on the temperature profile during milk fouling, Journal of Food Process Engineering, 17(3), 243-262. Zettler H.U., Weiß M., Zhao Q., Müller-Steinhagen H. (2005). Influence of surface properties and characteristics on fouling in plate heat exchangers. Heat Transfer Engineering, 26 (2), 3–17. Zhao Q., Liu Y., Müller-Steinhagen H., Liu G. (2002). Graded Ni–P–PTFE coatings and their potential applications. Surface Coatings Technology, 155, 279–284. Zhao Q., Liu Y., Wang S. (2005a). Surface modification of water treatment equipment for reducing CaSO4 scale formation. Desalination, 180 (1–3), 133–138. Zhao Q., Liu Y., Wang C., Wang S., Müller-Steinhagen, H. (2005b). Effect of surface free energy on the adhesion of biofouling and crystalline fouling. Chemical Engineering Science, 60 (17), 4858–4865. 30 Tables Table captions Table 1: Experimental studies of the effect of surface coatings on stainless steels for mitigation of aqueous crystallization fouling (scaling). Table 2: Experimental studies of the effect of surface coatings on stainless steels for mitigation of fouling, or enhancement of cleaning, of milk-related deposits. Table 3: Input parameters for Case Study I (DLC coating, water scaling). Shell-and-tube heat exchanger, one shell pass, two tube passes. Table 4: Case study I. Comparison of optimal cleaning times, annualised costs and annual energy losses for uncoated and SICON®-coated heat exchanger unit. Fouling parameters in Table 3. Table 5: Input parameters for Case Scenario II. Fluorocarbon coating, water scaling. Shell-and-tube heat exchanger, one shell pass, two tube passes. Table 6: Case study II. Comparison of optimal performance indices and process parameters for base case (values in Table 5) Table 7: Input parameters for Case Scenario III for fluorocarbon coating in milk pasteurization PHX Table 8: Case study III. Comparison of optimal performance indices and process parameters for base case (operating parameters in Table 5). Fluorocarbon coating thickness 10 µm. 31 Table 1: Experimental studies of the effect of surface coatings on stainless steels for mitigation of aqueous crystallization fouling (scaling). Coating type Coating CaSO4 Influence on fouling 0 CaSO4 - Zettler et al. (2005) CaSO4 - Zhao et al. (2002); Zhao et al. (2005a,b) Ca3(PO4)2 - Rosmaninho and Melo (2006) Ni-P, Ni-P-BN CaSO4 - AlβJanabi et al. (2010) FEP CaSO4 - Förster and Bohnet (2000) FA, FP, FS, TC, TC/TF CaCO3 - for FA, TC &TC/FS DLC CaSO4 - Förster and Bohnet (2000) DLC CaSO4 - Zettler et al. (2005) DLC, Si-DLC, Si-O-DLC (prepared by PECVD) CaSO4 - Geddert et al. (2009) CaPh - Boxler et al. (2013b) SiOx CaPh + TaC sputtered CaSO4 + Zettler et al. (2005) CrN CaSO4 - Geddert et al. (2009) Si+, F+, H+, SiF+, SiF4+ CaSO4 except H+ MoS2, SiF3+ CaPh - C, N CaSO4 - PTFE PTFE-based Electroless nickel film Polymer-based CVD PVD Ion-implanted Carbon nitriding Ni-P-PTFE Foulant Influence on cleaning Source(s) Förster and Bohnet (2000) Dowling et al. (2010) + Rosmaninho and Melo (2006) Müller-Steinhagen and Zhao (1997); Zettler et al. (2005) - Rosmaninho and Melo (2006) Zettler et al. (2005) +, increase; -, reduction deposition or cleaning effort compared with non-coated surface; 0, no influence. Null entry indicates data not available. Acronyms: CaPh: calcium phosphate; CVD – chemical vapour deposition; DLC – diamond-like carbon; FA – Fluoroalkene; FEP – perfluorethylenpropylen FP – Fluoropolymer; FS – Fluorosiloxane; Ni-P-BN – Nickel phosphorous boron-nitride; PECVD – plasma enhanced chemical vapour deposition; PVD – physical vapour deposition; TC – Tomcats (tetramethylcyclotetrasiloxane); TC/FP – Tomcats + fluoropolymer: 32 Table 2: Experimental studies of the effect of surface coatings on stainless steels for mitigation of fouling, or enhancement of cleaning, of milk-related deposits. Coating type Coating material PTFE PTFE-based Ni-P-PTFE CNT-PTFE Excalibur® and Xylan® Polymer-based polyethylene as well as silicone and fluorine resins nylon, PMMA, PS, cellulose acetate (CA) and agarose polysiloxane silica sol-gel LectrofluorTM and AMC148-18 FEP, PEEK + fluoropolymer and nanocomposite epoxy-resin & polyurethanebased coatings CVD DLC (prepared by PECVD) DLC and Si-O-DLC Foulant raw milk whey milk raw whole milk WPC pasteurised milk dairy dessert model fluid skim milk WPI in SMUF raw milk pasteurised milk dairy dessert model fluid whey raw whole milk raw whole milk WPI skim milk WPI WPC dairy dessert model fluid WPI Influence on fouling + + + + + + Influence on cleaning - - - 0 - - (Xylan®) - - (PMMA) Britten et al. (1988) Kananeh et al. (2010) Beuf et al. (2004) + 33 Balasubramanian and Puri (2008, 2009) Rosmaninho and Melo (2008) Barish and Goddard (2013) Rungraeng et al. (2012) Beuf et al. (2004) Yoon and Lund (1994) Santos et al. (2006) Balasubramanian and Puri (2008, 2009) Mauermann et al. (2009) - - (at pH 6.7) Gordon et al. (1968) Dupeyrat et al. (1987) McGuire and Swartzel (1989) Yoon and Lund (1994) Kananeh et al. (2010) Rungraeng et al. (2012) Beuf et al. (2004) Dupeyrat et al. (1987) 0 - (PMMA, CA) + + + - except PEEK + fluoropolymer Source(s) 0 Santos et al. (2006) DLC PVD Ion- implanted Ceramic-based WPI + (at pH 7.8) - (85 °C) - Premathilaka et al. (2007) Rosmaninho and Melo (2008) Mauermann et al. (2009) Patel et al. (2013) Si-O-DLC (prepared by PECVD) WPI in SMUF Si-O-DLC (prepared by PECVD) doped DLC (prepared by PECVD) WPI + - milk, whey 0 0 -, 0 DLC, Si-DLC, WPI, SMUF and for batch-wise Si-O-DLC (prepared by PECVD) WPI in SMUF deposition at 120 °C dairy dessert model fluid SiOx WPI in SMUF - (at pH 6.7) DLC WPI + (at pH 7.8) WPI + TiN WPI in SMUF + Ti-DLC WPI dairy dessert silica, SiF+ and MoS2 model fluid - at pH 6.7, silica, SiF3, MoS2 and TiC WPI except MoS2 silica and MoS2 WPI in SMUF + at 85 °C alumino-silicate whole milk chromium oxide and methylated β-lactoglubulin + silica Boxler et al. (2013a, 2013b, 2013c) - + 0 + 0 except SiF3 (-) 0 or + Beuf et al. (2004) Rosmaninho and Melo (2008) Santos et al. (2006) Premathilaka et al. (2007) Rosmaninho and Melo (2007) Mauermann et al. (2009) Beuf et al. (2004) Santos et al. (2006) Rosmaninho and Melo (2008) McGuire and Swartzel (1989) Karlsson et al. (1996) +, increase; -, reduction deposition or cleaning effort compared with non-coated surface, 0, no influence. Null entry indicates data not available. Acronyms: CVD – chemical vapour deposition; DLC – diamond-like carbon; FEP – perfluorethylenpropylen; PECVD – plasma enhanced chemical vapour deposition; PEEK – polyethyletherketone; PMMA – polymethylmethacrylate; PS – polystyrene; PTFE – polytetrafluoroethene; SMUF – simulated milk ultrafiltrate; WPC – whey protein concentrate; WPI – whey protein isolate. 34 Table 3: Input parameters for Case Study I (DLC coating, water scaling). Shell-and-tube heat exchanger, one shell pass, two tube passes. Description Operation Design Thermal properties Fouling performance† Costs Parameter Value πΜπ Cold stream mass flow 30 kg s-1 πΜβ Hot stream mass flow 50 kg s-1 ππ,ππ Cold stream inlet temperaturea 42 oC πβ,ππ Hot stream inlet temperature 80 oC π΄ Heat transfer surface area 200 m2 πππ Clean overall heat transfer coefficienta 250 W m-2 K-1 πππ Clean heat duty 1.42 MW π ππππ‘ Coating thermal resistanceb 0 m2 K W-1 πΆπ,π Cold stream heat capacity 4180 J kg-1 K-1 πΆπ,β Hot stream heat capacity 4180 J kg-1 K-1 π Μπ,π’ππ Linear fouling rate, uncoated HEXa 7.5×10-10 m2 K J-1 π Μπ,ππππ‘ Linear fouling rate, SICON®-coated HEXa 2.0×10-10 m2 K J-1 π‘πππ,π’ππ Induction period, uncoated HEXa 5h π‘πππ,ππππ‘ Induction period, SICON®-coated HEXa 72 h π Cleaning period 4 days ππΈ Energy cost 0.0057 US$ MJ-1 (6×10-6 US$ Btu-1) πΆππ Cost of cleaning a unit 2,000 US$ unit-1 πΆπππ’ππ Unit capital costc 70,600 US$ π‘πΏπΉ Asset lifetime 5 years ππππ (from eq. 20) Unit annualised capital costd 38.7 US$ day-1 a Obtained from Geddert et al. (2009) b Thermal resistance of the SICON®-coating is considered negligible c Obtained from Peters et al. (1990) and corrected using Chemical Engineering Plant Cost Index (CEPCI) of December 2012. d No additional capital cost for the coating (πΌ = 1) 35 Table 4: Case study I. Comparison of optimal cleaning times, annualised costs and annual energy losses for uncoated and SICON®-coated heat exchanger unit. Fouling parameters in Table 3. Optimal cleaning times Annualised costs Uncoated HEX SICON®-coated HEX π‘π,πππ‘ + π 40 + 4 days 71 + 4 days ∗ π‘ππ¦π - 1.73 πππ (from eqs. 17, 18) 235.4 US$ day-1 133.4 US$ day-1 ππππ (from eq. 20) -a 38.7 US$ day-1 b ππ 235.4 US$ day-1 172.1 US$ day-1 π∗ - 0.73 Total annualised cost Energy losses 85,930 US$ yr -1 Energy loss per cycle 1.47 TJ cycle-1 πΈπππ π (from eq. 19) 12.2 TJ yr-1 ∗ πΈπππ π - a considering no additional capital costs for the current uncoated heat exchanger. b as described in Table 3. 36 62,830 US$ yr-1 1.41 TJ cycle-1 6.86 TJ yr-1 0.56 Table 5: Input parameters for Case Scenario II. Fluorocarbon coating, water scaling. Shell-and-tube heat exchanger, one shell pass, two tube passes. Description Operation Design Thermal properties Fouling performance* Costs Parameter Value πΜπ Cold stream mass flow 25 kg s-1 πΜβ Hot stream mass flow 85 kg s-1 ππ,ππ Cold stream inlet temperature† 20 oC πβ,ππ Hot stream inlet temperature† 50 oC π΄ Heat transfer surface area 500 m2 βπΆ Cold side heat transfer coefficient† 500 W m-2 K-1 βπ» Hot side heat transfer coefficient† 800 W m-2 K-1 πΏπππ‘ππ Metal tube thickness 2 mm πΏππππ‘ Coating thickness 10 μm πππ Clean heat duty 2.12 MW πΆπ,π Cold stream heat capacity 4180 J kg-1 K-1 πΆπ,β Hot stream heat capacity 4180 J kg-1 K-1 πππ Stainless steel thermal conductivity 16 W m-1 K-1 ππΆπ Carbon steel thermal conductivity 54 W m-1 K-1 πππππ‘ PFPE thermal conductivity 0.1 W m-1 K-1 π Μπ,π’ππ Linear fouling rate, uncoated HEXa 2.5 × 10-10 m2 K J-1 π Μπ,ππππ‘ Linear fouling rate, PFPE-coated HEXa 1.5 × 10-10 m2 K J-1 π‘πππ,π’ππ Induction period, uncoated HEXb 0 days π‘πππ,ππππ‘ Induction period, PFPE-coated HEXb 0 days π Cleaning period 4 days ππΈ Energy cost 0.0057 US$ MJ-1 (6×10-6 US$ Btu-1) πΆππ Cost of cleaning a unit 4,200 US$ unit-1 a taken from Oldani et al. (2013). b induction period is set at zero for both surfaces as no effect on the induction period was reported. 37 Table 6: Case study II. Comparison of optimal performance indices and process parameters for base case (values in Table 5) Operation parameters Optimum cleaning times Annualised cost Energy losses a Uncoated HEX PFPE-coated SS HEX PFPE-coated CS HEX πππ 296.3 W m-2K-1 287.8 W m-2K-1 295.2 W m-2K-1 π΄ 500 m2 514.8 m2 501.8 m2 π‘πππ‘ + π 84 + 4 days 108 + 4 days 106 + 4 days ∗ π‘πππ‘ - 1.29 1.26 πππ (from eq. 16) 243.6 US$ day-1 200.7 US$ day-1 202.5 US$ day-1 ππππ (from eq. 20) - a 43.6 US$ day-1 †13.3 US$ day-1 ππ 243.6 US$ day-1 244.3 US$ day-1 215.8 US$ day-1 π∗ - 1.01 0.89 Annualised total cost 88,900 US$ yr-1 89,170 US$ yr-1 78,770 US$ yr-1 Energy loss per cycle 3.02 TJ cycle-1 3.21 TJ cycle-1 3.17 TJ cycle-1 πΈπππ π (from eqs. 18, 19) 12.5 TJ yr-1 10.4 TJ yr-1 10.5 TJ yr-1 ∗ πΈπππ π - 0.83 0.84 Taken from Figure 4 with no additional capital cost for the coating (πΌ = 1) and a unit lifetime of 10 years. 38 Table 7: Input parameters for Case Scenario III for fluorocarbon coating in milk pasteurization PHX Description Operation Design Thermal properties Fouling Performance b Costs Parameter Value πΜπ Cold stream mass flow 7 kg s-1 πΜβ Hot stream mass flow 13 kg s-1 πβ,ππ Hold stream inlet temperature 74 oC ππ,ππ Cold stream inlet temperature a 63 oC ππ,ππ’π‘ Cold stream outlet temperature a 73 oC π΄ Heat transfer surface area 15 m2 πππ Clean overall heat transfer coefficient 7500 W m-2 K-1 πππ Clean heat duty 275.8 kW πΏππππ‘ Coating thickness b 10.5 μm πΆπ,π Cold stream heat capacity 3940 J kg-1 K-1 πΆπ,β Hot stream heat capacity 4200 J kg-1K-1 πππππ‘ Coating thermal conductivity 0.2 W m-1 K-1 π Μπ,π’ππ Linear fouling rate, uncoated HEX b 10 × 10-9 m2 K J-1 π Μπ,ππππ‘ Linear fouling rate, Ni-P-PTFE-coated HEX b 1 × 10-9 m2 K J-1 π‘πππ,π’ππ Induction period, uncoated HEX b 2h π‘πππ,ππππ‘ Induction period, Ni-P-PTFE-coated HEX b 2h π Cleaning period 4h ππΈ Energy cost 0.0083 US$ MJ-1 (0.03 US$ kWh-1) πΆππ Cost of cleaning a unit 150 US$ unit-1 a Typical inlet and outlet temperatures for the hot section of a milk pasteuriser. b Taken from Barish and Goddard (2013). 39 Table 8: Case study III. Comparison of optimal performance indices and process parameters for base case (operating parameters in Table 5). Fluorocarbon coating thickness 10 µm. Uncoated HEX Operation parameters Optimum cleaning times Annualised costs Energy losses a coated HEX coated HEX, with hygiene constraint coated HEX, with hygiene constraint 0 < tp < ∞ 0 < tp < 24 h 0 < tp < 48 h πππ 7500 5380 5380 5380 π΄ 15 m2 21 m2 21 m2 21 m2 π‘πππ‘ + π 16 + 4 hours 69 + 4 hours 24 + 4 hours 48 + 4 hours ∗ π‘ππ¦π - 3.65 1.40 2.60 πππ (from eqs. 16) 14.30 US$ hour-1 4.50 US$ hour -1 7.10 US$ hour -1 4.80 US$ hour -1 ππππ (from eq. 20) - ππ 14.30 US$ hour -1 4.62 US$ hour -1 7.22US$ hour -1 4.92 US$ hour -1 π∗ - 0.32 0.51 0.34 Annualised total cost 125,270 US$ yr-1 40,470 US$ yr-1 Energy loss per cycle 1.2× 1010 J cycle-1 1.8 × 1010 J cycle-1 πΈπππ π (from eq. 19) 5.3 × 1012 J yr-1 2.2× 1012 J yr-1 0.6× 1012 J yr-1 1.4× 1012 J yr-1 ∗ πΈπππ π - 0.41 0.11 0.26 a 0.12 US$ hour -1 Calculated with no additional capital costs for the coating (πΌ = 1) and a unit lifetime of 5 years. 40 a 0.12 US$ hour 1 63,250US$ yr-1 a 0.12 US$ hour -1 43,100 US$ yr-1 0.2 × 1010 J cycle-1 0.8 × 1010 J cycle-1 Figures List of figure captions Figure 1: Heat exchanger performance profiles during operation time. Variation of (a) fouling resistance; (b) overall heat transfer coefficient; (c) heat duty over an operating cycle. Figure 2: Case Study I. Effect of tp on annualised operation cost, πππ , showing optimal cleaning times, ππππ , for both uncoated and SICON®-coated heat exchangers. Figure 3: Case Study I. Comparison of the performances of uncoated and SICON®-coated heat exchanger for different induction periods, fouling rates and cleaning periods of coated-HEX. (a) optimal cleaning time; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). Figure 4: Case Study II. Effect of PFPE film thickness on the heat transfer area required for fixed duty and the capital cost of the coated heat exchanger. Figure 5: Case Study II. Annualised operation cost and optimal operating time for cleaning, ππππ , for uncoated and PFPE-coated stainless steel heat exchangers. Figure 6: Case Study II. Estimated capital cost for installed stainless and carbon steel shell-and-tube heat exchangers. Values obtained from Peters et al. (1990), corrected using the Chemical Engineering Plant Cost Index (CEPCI) of December 2012. Figure 7: Comparison of the performance of uncoated and 10 µm thick fluorocarbon coated heat exchangers made of stainless or carbon steel for different induction periods, fouling rates and cleaning periods on the coated units. (a) ratio of optimal cleaning times; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). Figure 8: Case Study II. Comparison of the performance of uncoated and fluorocarbon-coated heat exchangers made of stainless or carbon steel for different induction periods, fouling rates and coating thicknesses. (a) ratio of optimal cleaning times; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). Figure 9: Case Study III. Annualised operation cost profile and optimal cleaning times, ππππ, for uncoated and fluorocarbon coated stainless steel dairy PHX, with a hygiene operating constraint at 2 days (48 h). Figure 10: Case Study III. Comparison of the performance of an uncoated and a coated dairy PHX for different induction periods, fouling rates and cleaning periods. 10 µm thick fluorocarbon coating. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. Note different base axes. Figure 11: Case Study III. Relative performance of a coated dairy PHX unit for different fouling rates, coating thickness and hygiene constraint. tind = 2 hours. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. Figure 12: Case Study III. Relative performance of a dairy PHX unit with 10 µm thick fluorocarbon coating and thyg = 48 h for different induction periods, fouling rates and cleaning periods. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. Note change in base axes. Figure 13: Case Study III. Maximum capital cost factor, ο‘, for different fouling rates and induction periods and for selected cost saving ratios. 41 Figure 1: Heat exchanger performance profiles during operation time. Variation of (a) fouling resistance; (b) overall heat transfer coefficient; (c) heat duty over an operating cycle. 42 Figure 2: Case Study I. Effect of tp on annualised operation cost, πππ , showing optimal cleaning times, ππππ , for both uncoated and SICON®-coated heat exchangers. 43 Figure 3: Case Study I. Comparison of the performances of uncoated and SICON®-coated heat exchanger for different induction periods, fouling rates and cleaning periods of coated-HEX. (a) optimal cleaning time; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). 44 Figure 4: Case Study II. Effect of PFPE film thickness on the heat transfer area required for fixed duty and the capital cost of the coated heat exchanger. 45 Figure 5: Case Study II. Annualised operation cost and optimal operating time for cleaning, ππππ , for uncoated and PFPE-coated stainless steel heat exchangers. 46 Figure 6: Case Study II. Estimated capital cost for installed stainless and carbon steel shell-and-tube heat exchangers. Values obtained from Peters et al. (1990), corrected using the Chemical Engineering Plant Cost Index (CEPCI) of December 2012. 47 Figure 7: Comparison of the performance of uncoated and 10 µm thick fluorocarbon coated heat exchangers made of stainless or carbon steel for different induction periods, fouling rates and cleaning periods on the coated units. (a) ratio of optimal cleaning times; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). 48 Figure 8: Case Study II. Comparison of the performance of uncoated and fluorocarbon-coated heat exchangers made of stainless or carbon steel for different induction periods, fouling rates and coating thicknesses. (a) ratio of optimal cleaning times; (b) ratio of annualised costs; (c) ratio of energy losses. Note change in base axes between (a) and (b). 49 Figure 9: Case Study III. Annualised operation cost profile and optimal cleaning times, ππππ, for uncoated and fluorocarbon coated stainless steel dairy PHX, with a hygiene operating constraint at 2 days (48 h). 50 Figure 10: Case Study III. Comparison of the performance of an uncoated and a coated dairy PHX for different induction periods, fouling rates and cleaning periods. 10 µm thick fluorocarbon coating. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. Note different base axes. 51 Figure 11: Case Study III. Relative performance of a coated dairy PHX unit for different fouling rates, coating thickness and hygiene constraint. tind = 2 hours. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. 52 53 Figure 12: Case Study III. Relative performance of a dairy PHX unit with 10 µm thick fluorocarbon coating and thyg = 48 h for different induction periods, fouling rates and cleaning periods. (a) ratio of optimal cleaning times; (b) ratio of annualised costs. Note change in base axes. Figure 13: Case Study III. Maximum capital cost factor, ο‘, for different fouling rates and induction periods and for selected cost saving ratios. 54