3333333 STANDARD SAVINGS ESTIMATION PROTOCOL FOR PUMP VARIABLE FREQUENCY DRIVES REGIONAL TECHNICAL FORUM Release Date: June 10, 2013 Standard Savings Estimation Protocol - Pump VFD TABLE OF CONTENTS 1. PURPOSE............................................................................................................ 1 2. SUNSET DATE ...................................................................................................... 1 3. DEFINITION OF KEY TERMS ..................................................................................... 1 4. ELIGIBLE PROJECTS ............................................................................................... 2 5. REQUIRED KNOWLEDGE AND SKILLS OF PRACTITIONER ................................................... 3 6. DELIVERY VERIFICATION ......................................................................................... 3 7. DATA COLLECTION REQUIREMENTS ........................................................................... 3 7.1. Pump and Pump Motor Specifications .............................................................................. 3 7.2. Pump Operations ............................................................................................................... 4 7.3. Post-Period Electrical Measurements................................................................................ 4 7.4. Facility Control System Post-Period Trend Logs ................................................................ 5 7.5. Baseline Operation............................................................................................................. 5 8. PROVISIONAL DATA REQUIREMENTS ......................................................................... 7 9. SAVINGS ESTIMATION STEPS ................................................................................... 7 9.1. Derive Flow vs. Power Relationship for Post Period.......................................................... 8 9.2. Derive Flow vs. Power Relationship for Baseline Period ................................................... 8 9.3. Compute Savings for Trend Log Intervals .......................................................................... 8 9.4. Annualized Savings: Pump Speed Determined by OAT and Facility Operations Schedule .................................................................................................................................... 9 9.4.1. Systems with On-Off Valve in the Baseline Period ............................................................. 9 9.4.2. Systems Without On/Off in Baseline Period..................................................................... 10 9.5. Annualized Savings: Pump Speed Determined by Facility Operations Schedule ............ 10 9.5.1. Systems with On-Off Valve in the Baseline Period ........................................................... 10 9.5.2. Systems Without On/Off in Baseline Period..................................................................... 11 10. SAMPLING PROCEDURE ...................................................................................... 11 11. RELATIONSHIP TO OTHER PROTOCOLS AND GUIDELINES ............................................. 11 12. TYPICAL COST OF APPLYING THIS PROTOCOL ........................................................... 12 13. USER’S GUIDE TO THE SAVINGS CALCULATOR .......................................................... 13 13.1. Information Tab ............................................................................................................. 13 13.2. Pump Operating Conditions Tab .................................................................................... 14 13.2.1. Motor Information.......................................................................................................... 14 13.2.2. Machine Curve ................................................................................................................ 15 13.2.3. Recirculation Inputs ........................................................................................................ 16 13.2.4. Baseline Period Control Strategy .................................................................................... 17 Regional Technical Forum i Standard Savings Estimation Protocol - Pump VFD 13.2.5. System Curve Information .............................................................................................. 17 13.2.6. One Time Electrical Data ................................................................................................ 18 13.3. Pump Operating Schedule Tab ..................................................................................... 19 13.4. Trend Data (Pre) and Trend Data (Post) Tabs ................................................................ 20 13.5. Results Tab ..................................................................................................................... 20 Regional Technical Forum ii Standard Savings Estimation Protocol - Pump VFD 1. PURPOSE This protocol establishes a method by which annual electrical energy savings (kWh) can be estimated for a pump that has been upgraded by the addition of a Variable Frequency Drive (VFD). VFDs reduce electric use by adjusting the pump motor’s speed to match the required load. Many pumps do not need to run at full capacity all of the time, and VFDs are more efficient than other flow control methods, such as throttling valves, at regulating pump flow rates. This protocol specifies minimum acceptable data collection requirements and the method by which these data are to be used in computing savings through two methods, (1) a best practices method (BPM)1 and (2) the simplest reliable method2 (SRM). For some data elements, alternative sources of data, considered to be of equal or superior quality, are also defined and are allowed. Savings are computed using the Protocol Calculator that accompanies this document to ensure standardized application of the savings estimation methods. 2. SUNSET DATE This protocol is approved for use until June 30, 2015. 3. DEFINITION OF KEY TERMS Project. A VFD installed to control one pump unit and baseline control mechanism (e.g. throttling valve) is either removed or disabled and set to the maximum flow condition. Baseline. This modifier; as in baseline control strategy has one of two meanings. (1) For pump units upgraded in existing facilities, it refers to the period prior to the upgrade. (2) For pump units in new construction, there is no such period. In these instances, the term baseline refers to the design specification for the pump unit without the efficiency upgrade. Post. This modifier; as in post current trend log, refers to the period after the pump unit VFD upgrade is installed and fully commissioned. 1 The BPM is the ideal method to calculate energy savings for a measure. Data required to compute savings using the best practices method are described in Section 8 2 The SRM is intended to yield similar results to the best practices method using minimum possible data collection. The data required to compute savings using the simplest reliable method are described in Section 7 Regional Technical Forum 1 Standard Savings Estimation Protocol - Pump VFD Qualified Electrical Worker. As defined in OSHA 29 CFR Part 1910.3993 or NFPA 70E4. Machine Curve. The pump performance curve, obtained on site or from the manufacturer, showing the flow vs. head relationship, along with efficiencies. 4. ELIGIBLE PROJECTS Eligible pumps must follow the affinity laws. Centrifugal pumps and vertical and horizontal turbine pumps are eligible. Positive displacement pumps are not eligible. The methodology employed in calculating energy usage restricts what control strategies are eligible under this protocol. The methodology requires a constant system curve in the post configuration. Systems which incorporate operating valves in the post configuration are thus excluded. This excludes many constant-pressure-controlled HVAC systems. Applications where this protocol might be suitable include industrial transfer pumps, feedwater pumps, and water or wastewater pumps. The following criteria define eligible projects. The primary determinants of pump speed are either facility operations schedule or outside air temperature combined with operations schedule. The baseline control strategy must rely on throttling valves, with or without recirculation. The protocol is limited to a single pump. The flow profile must be the same for baseline and post periods. The system curve remains constant in the post period; all control valves have been removed or are non-operational. This excludes many HVAC pump systems, in which operational valves continue to be part of the system after VFD installation. Pump motors must be single speed motors. Pumps must not be subject to a local energy code requirement for variable speed drive. This excludes many new construction HVAC pumps. The cost of implementing this protocol must not make the project economically unattractive. 3 “One who has received training in and has demonstrated skills and knowledge in the construction and operation of electric equipment and installations and the hazards involved” 4 “One who has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved” Regional Technical Forum 2 Standard Savings Estimation Protocol - Pump VFD 5. REQUIRED KNOWLEDGE AND SKILLS OF PRACTITIONER The practitioner who has lead responsibility for applying this protocol must have at a full understanding of the following: Appropriate safety procedures for work involving pumps and the measurement equipment required by this protocol This protocol and the accompanying savings calculator. The practitioner must also be able to successfully perform the following tasks: Identify the determinants of pump operation: (1) facility operations schedule or, (2) outside air temperature combined with facility operations schedule. Supervise a qualified electrical worker in taking a series of spot measurements of true power and other required parameters for the pump unit circuit. Install and operate a current logger and obtain necessary trend logs from facility control systems. 6. DELIVERY VERIFICATION This protocol may only be used for pump units that pass the following delivery verification tests: The baseline control mechanism is either removed or disabled and set to the maximum flow condition in the post case. 7. DATA COLLECTION REQUIREMENTS This section describes the data collection requirements for the SRM to estimate energy savings. The details of the SRM energy savings methodology are presented in Section 9. The minimum acceptable procedure for obtaining the data is specified. In some cases, alternative procedures are allowed which would provide data of equal or better quality. 7.1. Pump and Pump Motor Specifications Machine Curve. Obtained on site or from the pump manufacturer. Data points from the manufacturer’s performance curve are required. Flow, pressure, and efficiency points must be read from the appropriate machine curve and must match the conditions at the site in terms of impeller size and speed (RPM). This is also sometimes referred to as the pump curve by practitioners. Pump Motor HP. Obtained from the motor name plate. Pump Motor RPM. Obtained from the motor name plate. Pump Motor Enclosure type. Obtained from the motor name plate. Regional Technical Forum 3 Standard Savings Estimation Protocol - Pump VFD 7.2. Pump Operations Determinants of Pump Speed. Obtained from facility operator. Possible determinants are: (1) facility operations schedule, or (2) Outside air temperature combined with operations schedule. Facility Operations Schedule. Obtained from facility operator. If the pump unit has different operation modes determined by the facility’s operations schedule, e.g., setback of flow during night and weekend hours, determine the period for each mode, defined as needed by hour of day, day of week, and season. This method requires that all schedule modes are metered. Typical Outside Air Temperature (OAT). Determine whether OAT is a significant determinant by discussion with the facility operator and consideration of the types of load being served by the pump. Weather Station. If OAT is a significant determinant, identify the TMY (Typical Meteorological Year) weather station which is closest to the project site. Static Head. The head at zero flow – the net static head including elevation head – must be known. Site personnel should be able to provide this value, or describe the means to acquire it. Pump Operating Point. This (flow, pressure) operating point must be with all valves removed or wide open. The point may be taken from the equipment schedule on the facility’s mechanical plan. Alternatively, this value may be determined by: (1) inspecting facility control system trend logs of pump flow rate, if the system has a calibrated flow sensor and the log contains values at or near 100% speed; or (2) based on a pair of values – measured kW along with corresponding VFD speed. On/Off Valve Presence. The implementer needs to ask the customer if the pump operated with an on/off valve prior to VFD installation. 7.3. Post-Period Electrical Measurements One-Time Electrical Measurements. Taken by a qualified electrical worker under the on-site supervision of the practitioner. Power meter is attached as needed to record true RMS poly-phase power and current on one leg of the circuit supplying power to the VFD. These measurements are recorded while the VFD is set to a series of at least 3 levels of speed, including one at 100% speed. Measurements should aim to capture VFD operation at low and medium speed as well. Trend Log of VFD Current. A data logger is installed to measure 15-minute interval true RMS current on the same leg of the circuit as was used in the one-time measurements. If the pump unit speed is primarily determined by OAT, the measurement period must be at least two months and must start between August 15th and October 15th or between March 15th and May 15th in order to capture measurements for a sufficient range of OAT values. If the pump unit speed is primarily Regional Technical Forum 4 Standard Savings Estimation Protocol - Pump VFD determined by facility operating schedule the period must be at least one month long, include all modes of operation as dictated by the operating schedule, and can start at any time of the year. Alternative Measurements. True Power. In lieu of the one-time electrical measurements and current trend log this protocol allows for a trend log of true poly-phase RMS power for the circuit powering the VFD. The same measurement interval, period and timing requirements apply as described for the current measurement above. 7.4. Facility Control System Post-Period Trend Logs Trend Log of VFD Facility OAT These data may be obtained from the facility’s control system if it can be programmed to record OAT at 15-minute intervals. Data must be collected for the same period as the VFD current trend log. These data are required only if pump speed is primarily a function of OAT (such as for a heating or cooling units). If OAT is not available from the facility’s control system or appears unreliable, an OAT data recorder should be installed to create this trend log. Alternatively, OAT can be obtained from an applicable weather station. 7.5. Baseline Operation If end-use demand in the baseline restricts flow, the flow may drop below the pump minimum requirement. Recirculation of flow will likely be employed to counteract this. The recirculation would not necessarily be required in the post period because lower speed operation is available. The flow profile derived from the post period can be modified to include the baseline recirculation flow that is over and above the post recirculation flow. Two types of recirculation can be defined: Minimum flow. The baseline flow never drops below a given value. When applying the post flow to the baseline period, all flows below this value are set to the minimum flow. Constant recirculation flow. A constant amount is always recirculated. This flow is added to the flow values derived in the post period when applied to the baseline. This value must be the flow over and above any recirculation flow in the post period. Data collection required to define recirculation can be achieved in one of three ways: 1. Fixed orifice or similar device. Constant flow through the device is specified in one of four ways: Flow capacity (CV). Taken from device cut sheet, AND Pressure drop across valve. Observed during the baseline or found in records from the baseline period, OR Regional Technical Forum 5 Standard Savings Estimation Protocol - Pump VFD Orifice diameter, AND Recirculation pipe diameter, AND Pressure drop across valve. Observed during the baseline or found in records from the baseline period, OR Engineering design documents. Design documents which specify the bypass flow rate. OR Measured flow. Observed or recorded flow through the bypass line during the baseline period. 2. Automatic recirculating valve (ARV). Minimum flow is specified in one of two ways: Observed minimum flow rate. The minimum total pump discharge flow observed during the baseline or found in records from the baseline period, if those observations show a clear lower limit, OR Engineering design documents. Design documents, especially ARV manufacturer documents, which specify the minimum flow rate of the installed device. 3. Instrument controlled recirculating valve. Minimum flow is specified in one of three ways: Observed minimum flow rate. The minimum total pump discharge flow observed during the baseline or found in records from the baseline period, if those observations show a clear lower limit, OR Engineering design documents. Design documents which specify the minimum flow rate of the control valve. OR Controller setpoint. Controller minimum flow setpoint, observed during the baseline period. An alternative data collection method utilizes baseline electrical measurements: Alternative Measurements. In lieu of the baseline performance curves, pump motor current or power can be measured during the baseline period. The same measurement interval, period and timing requirements apply as described under Trend Log of VFD Current in section7.3. This Regional Technical Forum 6 Standard Savings Estimation Protocol - Pump VFD alternate method should be used only when operating conditions are reasonably similar between baseline and post measurement conditions. The practitioner should use his best judgment to discern whether the operating conditions are reasonably similar or not. 8. PROVISIONAL DATA REQUIREMENTS This section outlines the data requirements for the BPM. During the period that the RTF classifies this protocol as Provisional, the following data requirements will be in force: Baseline Electrical Measurements. Trend log true poly-phase RMS power for the circuit powering the pump unit. The same measurement interval, period and timing requirements apply as described under Trend Log of VFD Current in section 7.3. Post-Period Electrical Measurements. Trend log true poly-phase RMS power for the circuit powering the pump unit. Trend log amperage of at least one leg with the same time stamp signatures as the true poly-phase RMS power trend logs for verification. The same measurement interval, period and timing requirements apply as described under Trend Log of VFD Current in section 7.3. 9. SAVINGS ESTIMATION STEPS This protocol defines a method to derive energy savings based on power (or current) measurements taken post-VFD-installation, together with pump performance specifications and site operating characteristics. The basis for the calculation is that the post power trend, combined with site system specification, allows the derivation of the post flow trend. This flow trend is assumed to apply in the baseline case (with exceptions in the case of recirculation), where it is used to derive the baseline power trend from the pump performance curve. The post operating curve (system curve) is assumed to not vary. All valves have either been removed or are fixed. The system curve is specified with two points – the static head and an operating point. Baseline power is derived from the flow profile. Flow, head, and efficiency points from the performance curve are used to develop a flow-to-power relationship. To account for cases where a recirculation flow exists in the baseline that does not exist in the post period, the user can specify a minimum flow or a constant circulation flow that will be used to modify the flow profile. Savings from the period of measurement are annualized based on annual facility operations schedules or a correlation with outside air temperature. Savings are estimated using the savings calculator that accompanies this protocol. Regional Technical Forum 7 Standard Savings Estimation Protocol - Pump VFD 9.1. Derive Flow vs. Power Relationship for Post Period System Curve. The full-flow operating point is used to derive an equation for the system curve (flow vs. pressure) as the parabola (or lower order equation) from the static head value through the point on the machine curve matching the operating point collected as described in Section 7.1. Flow vs. Power Curve. The pump will operate along the system curve as the VFD changes pump speed. Pump efficiency may vary along this curve, and is included in the flow vs. power calculations. The calculator derives an equation for flow as a function of power (kW) along this curve. Motor efficiency and VFD efficiency are based on default relationships (DOE tables5) according to motor percent load. 9.2. Derive Flow vs. Power Relationship for Baseline Period Flow vs. Power Curve. Assuming constant speed, the pump will operate along the machine curve. Using the machine curve data points entered, the calculator derives an equation for power as a function of flow along the machine curve. Recirculation Flow. Recirculation flow, if present in the system, is accounted for in the calculator as either a constant or minimum recirculation flow. Constant recirculation is taken into account at each calculated flow value (calculated via the Flow vs. Power curve) to determine flow with recirculation. Minimum recirculation flow is taken into account only when calculated flow falls below the minimum specified amount; in this case, the calculated flow is set to minimum circulation flow. 9.3. Compute Savings for Trend Log Intervals Data Synchronization. Start times for all trend log intervals are synchronized by moving each to the closest standard sub-hourly interval start times, e.g. 0, 15, 30 and 45 minutes after the start of each hour. Power and Current Curve Fit. Spot measurements of true power and current (taken at least for 3 levels of speed, including 100%) are fit to a second order equation. Post kW. Calculate kW from fitted equation for each current (amps) value. Post flow. Calculate flow as a function of kW using the equation derived from the system curve. 5 Motor efficiencies are taken from MotorMaster+ International version 1.1.5, August, 2011. https://www1.eere.energy.gov/manufacturing/tech_assistance/software_motormaster.html. VFD efficiencies were obtained from DOE Motor Tip Sheet 11, June 2008. https://www1.eere.energy.gov/manufacturing/tech_assistance/pdfs/motor_tip_sheet11.pdf. Regional Technical Forum 8 Standard Savings Estimation Protocol - Pump VFD Baseline flow. The assumption is that the baseline flow profile is identical to the post flow profile, with the exception of recirculation adjustments to the baseline flow. Baseline kW. Calculate kW as a function of flow using the equation derived from the machine curve. Savings for Trend Log Period. Calculate the kW savings profile as the difference between baseline kW and post kW. 9.4. Annualized Savings: Pump Speed Determined by OAT and Facility Operations Schedule This method for annualizing savings assumes the load can be characterized by outside air temperature changes combined with a facility operations schedule. In BPA terminology, this is also a VLVS (Variable Load Variable Schedule) case. The methods used are essentially the same as those described in the BPA guidelines, except that baseline kW is modeled rather than metered. 9.4.1. Systems with On-Off Valve in the Baseline Period This method makes the assumption that in the baseline period, there is no control valve installed, only an on/off valve. Implying that in the baseline period, the pump either operates at the operating point and at 100% speed or is off. In this case, the annual energy savings will be calculated in the following manner: Calculate Total Consumption for Post Period. Using post period trended data, first calculate consumption at each logged interval during the trending period. Establish Relationship between Calculated Flow, OAT, and Facility Operating Schedule: Using the calculated consumption at each logged interval, the OAT at each interval and data on facility operating schedule (during trending period), a relationship between the three variables is established. Annualize Post Period Consumption: Using the relationship derived above, post period consumption should then be annualized applying the derived relationship to the annual facility schedule, and annual OAT data. Calculate Total Annual Flow Volume through Pump. Using the power-flow relationship derived from the post period and annuialized post period consumption data, calculate total annual flow through pump in the post period. Calculate Total Annual Energy Consumption in Baseline Period. As the total annual volume moved through the pump is now known, use the power – flow relationship at the operating point to calculate the total annual baseline energy consumption. Regional Technical Forum 9 Standard Savings Estimation Protocol - Pump VFD Calculate Total Annual Energy Savings. This is the difference between the annualized energy consumption in the baseline and the post period. 9.4.2. Systems Without On/Off in Baseline Period Average Savings by Trend Log Bin. Average kW savings by two degree temperature bins for all trend log intervals during operating hours, as defined by facility operations schedules (Section 7.2). If the facility has more than one operation mode (that determines pump speed), temperature bin averages are separately computed for each operation mode. Operating Hours by TMY Bin. Divide the 8,760 TMY OAT data into two degree bins and compute frequency of annual operating hours for each bin, as defined by facility operations schedules (Section 7.2). Average Savings by TMY Bin. TMY bin average bin savings equal trend log average bin savings for each matching bin. Extrapolate average savings for TMY bins that do not have trend log data. Higher temperature bins are extrapolated by a linear equation fit to the trend log bins above 57 degrees and lower temperature bins by a linear equation fit to the bins below 57 degrees. No bin value is allowed to exceed the rated pump motor kW. Saving by Bin. For each TMY bin, multiply the average bin savings by the number of operating hours in each bin, to get kWh savings in each bin. Annual Savings. Sum the kWh values across TMY bins. 9.5. Annualized Savings: Pump Speed Determined by Facility Operations Schedule This method makes two assumptions: 1) There is a strong correlation between schedule periods and savings; and 2) Power trends for the post period are available for all schedule periods. In BPA terminology, this is a Variable Load Timed Schedule (VLTS) case. The methods used are essentially as described in the BPA guidelines, except that baseline kW is modeled rather than measured. 9.5.1. Systems with On-Off Valve in the Baseline Period This method makes the same assumption stated in Section 9.4.1, The annual energy savings will be calculated in the following manner: Calculate Total Consumption for Post Period. Using post period trended data, first calculate consumption at each logged interval during the trending period. Establish Relationship between Calculated Flow, and Facility Operating Schedule: Using the calculated consumption at each logged interval, and data on facility operating schedule (during trending period), a relationship between the two variables is established. Regional Technical Forum 10 Standard Savings Estimation Protocol - Pump VFD Annualize Post Period Consumption: Using the relationship derived above, post period consumption should then be annualized by applying the derived relationship to the annual facility schedule. Calculate Total Annual Flow Volume through Pump. Using the power-flow relationship derived from the post period and annuialized post period consumption data, calculate total annual flow through pump in the post period. Calculate Total Annual Energy Consumption in Baseline Period. As the total annual volume moved through the pump is now known, use the power – flow relationship at the operating point to calculate the total annual baseline energy consumption. Calculate Total Annual Energy Savings. This is the difference between the annualized energy consumption in the baseline and the post period. 9.5.2. Systems Without On/Off in Baseline Period Average Savings for Trend Period. For the trend log period, average the savings for each operation mode, as determined by facility operations schedule (Section 7.2). Annual Operating Hours. Determine the number of operating hours for each operating mode in a year. Savings by Operating Mode. Multiply the number of annual operating hours times the average saving for each operating mode. Annual Savings. Sum savings across operating modes. 10. SAMPLING PROCEDURE No sampling is permitted by this protocol. Data collection and savings estimation is required for each upgraded pump unit regard less of the number of such units that may be upgraded at a facility. 11. RELATIONSHIP TO OTHER PROTOCOLS AND GUIDELINES The relationship between this protocol and other relevant protocols and guidelines is as follows: International Performance Measurement and Verification Protocol – 2007 (IPMVP), Efficiency Valuation Organization. This protocol is consistent with Option A - Retrofit Isolation: Key Parameter Measurement described in the IPMVP, as a number of key parameters are measured (VFD current, VFD %speed and OAT). The use of default pump performance curves is consistent with this option. M&V Guidelines: Measurement and Verification for Federal Energy Projects Version 3.0, U.S. Department of Energy Federal Energy Management Program. The relevant part of this guideline is Regional Technical Forum 11 Standard Savings Estimation Protocol - Pump VFD Section 11.4 Variable Speed Motors. This guideline requires both baseline and post measurements, which is not consistent with this protocol. Verification by Equipment or End-Use Metering Protocol, 2011, Bonneville Power Administration. This BPA guideline, based on ASHRAE Guideline 14-2002, in general requires both baseline and post metering. The protocol described herein is based on post-only metering, although its provisional form calls for pre- and post- metering. The BPA guideline End-Use Metering Absent Baseline Measurement is aimed at new construction projects, and does not provide additional guidance for VFD retrofit projects where baseline measurements are not taken. The BPA guidelines emphasize measurements of the load, which in this case would be the fluid flow, together with spot measurements of power, rather than requiring a trend of just power. In BPA terminology, the eligible VFD pump projects described herein are either Variable Load Timed Schedule (VLTS) or Variable Load Variable Schedule (VLVS), in which neither the load nor the schedule changes between baseline and post. Sampling Reference Guide, BPA. It is unlikely that more than 20 pump units would be upgraded as part of any one project. It is difficult to obtain reliable sample estimates from populations this small, especially given the likely variation in savings between units. Therefore no sampling is allowed. This is consistent with the BPA guide. Regression Reference Guide, BPA. This protocol uses regression techniques to fit a linear equation to the measurements of true power and current for the VFD and to extrapolate savings to temperatures beyond those observed in the trend logging period (for pump units whose speed is primarily determined by OAT). The application of these regression techniques is consistent with the BPA guide. 12. TYPICAL COST OF APPLYING THIS PROTOCOL Shown below is an estimate of typical cost of applying this protocol for a single pump unit. Projects that involve more than one pump unit at the same facility are likely to see lower cost per unit. Expenses for alternative measurements, allowed by this protocol, are not included in this estimate of typical cost. Item Quantity $ / Hour Rental Total Cost ($) Equipment Power Meter 1 100 100 Current Logger 1 200 200 Labor Practitioner Travel 3 110 330 Scheduling 1 110 110 Facility Operator Interview 2 110 220 0.5 110 55 VFD Inspection Regional Technical Forum 12 Standard Savings Estimation Protocol - Pump VFD Item Quantity $ / Hour Rental Total Cost ($) Electrical Measurements 0.5 110 55 Install/Remove Current Logger 2 110 220 Savings Estimate 5 110 550 Travel 2 90 180 Electrical Measurements 1 90 90 2 150 300 Electrician Controls Specialist Setup and Export Trend Logs Total $2,410 13. USER’S GUIDE TO THE SAVINGS CALCULATOR This section is a step by step guide for using the Pump VFD Excel Savings Calculator (Savings Calculator). The Savings Calculator is an Excel-based, tool that implements the savings calculation methodology outlined in this protocol document. The Savings Calculator is organized by tabs, with each tab containing a related set of inputs required by the protocol to calculate energy savings. The Savings Calculator contains the following tabs: Information PumpOperatingConditions PumpOperatingSchedule Trend Data (Pre) Trend Data (Post) Results The following subsections explain the intent of each tab, the data inputs required by each tab, and instructions on how to interpret results. 13.1. Information Tab The user enters descriptive information regarding the project being analyzed in this tab. This descriptive information consists of the customer information, project location and the properties of the fluid that is being pumped. Figure 1 presents a screenshot of the data input required in this tab. Regional Technical Forum 13 Standard Savings Estimation Protocol - Pump VFD Figure 1 Customer and Project Information Section in the Savings Calculator Customer Information Facility Site Contact Name: Phone: Email: Fax: Address: Facility Type: Please choose a specific gravity fluid Pump Fluid Type: Water @ 70 F Calculated Specific Gravity: 0.999 Custom Specific Gravity (optional): Please choose nearest TMY city State: City: ID Idaho Falls Fanning Field The customer and project information are descriptive fields that the user can enter in any format. The primary purpose of these inputs is documentation; these descriptive inputs are not required for energy savings calculations. The user can choose fluid properties by using a prepopulated dropdown list, or by entering custom values for fluid properties. To enter custom values, the user must choose the option “Other” from the dropdown list. Care should be taken while selecting fluid properties; unlike the project detail fields on this tab, fluid properties are used to calculate energy savings. 13.2. Pump Operating Conditions Tab Inputs that define the pump, motor and system characteristics are entered in this tab. These inputs are used to calculate energy savings through the SRM; therefore, the energy savings results are sensitive to the inputs in this tab. The inputs required by this tab are subdivided into six categories, presented below. 13.2.1. Motor Information The user shall enter motor nameplate data including motor size, type, and efficiency. These inputs and their format required by the calculator are presented in Figure 2. Regional Technical Forum 14 Standard Savings Estimation Protocol - Pump VFD Figure 2 Motor Name Plate and Manufacturer's Information The user needs to enter the motor size in horsepower (HP) based on motor nameplate information; this is entered using a prepopulated dropdown list. The mechanical converter efficiency can be set to any valid number the user chooses; however, the calculator indicates typical values of 97% for belt-driven applications and 100% for direct-drive. The minimum allowable flow speed for the system must also be specified. While this input does not directly impact savings, care must be taken when specifying this parameter in relation to the other pump inputs, particularly static head. For example, if the minimum allowable flow speed is set too low, such that the system cannot meet the static head requirement, the calculator will not be able to generate a flow versus power relationship. The user has the option to either enter the motor full load efficiency manually, or let the calculator look up the efficiency value based on motor nameplate information. The calculator requires the user to enter motor speed (rpm), and motor enclosure type in addition to the motor size (entered previously) for the calculator to estimate motor full load efficiency. Motor speed and enclosure type are standardized inputs; the user can select a value for these fields via a prepopulated dropdown list. 13.2.2. Machine Curve The Machine Curve (also often referred to as the pump curve) is a set of flow rates (gpm), and corresponding pressure (ft) at which the pump operates. For each flow rate and pressure combination, the pump operates at a different efficiency level and power (Brake Horse Power, expressed as BHP). The Savings Calculator requires the user to enter ten points to describe the machine curve. These points on the machine curve are entered by specifying a flow (gpm), pressure (ft) and corresponding efficiency (%) or BHP. The user can use a dropdown menu to enter either the efficiency or BHP for each point (as shown in Figure 3). Machine curve input format as required by the calculator is presented in Figure 3. Regional Technical Forum 15 Standard Savings Estimation Protocol - Pump VFD Figure 3 Machine (Pump) Curve Inputs Required by the Calculator If the user does not have all ten points required to define a machine curve, the user can repeat the last point a few times; however, it is strongly advised to enter at least six distinct points to accurately define a machine curve. 13.2.3. Recirculation Inputs The user can specify in the Savings Calculator if the system in consideration has recirculation. If the user selects the “with recirculation” option, a “Enter Recirculation Inputs” button will appear, as shown in Figure 4. Figure 4 Recirculation Input Options & Recirculation Input Screen 3. Recirculation If the system includes recirculation please indicate so and enter information regarding recirc Enter Recirculation Inputs Regional Technical Forum 16 Standard Savings Estimation Protocol - Pump VFD Also presented in Figure 4 is a detailed recirculation input screen, which appears once the user clicks on the “Enter Recirculation Inputs” button. In this screen, the user can choose the type of recirculation flow present in the system and state the amount of recirculation flow. The input options presented in this screen are aligned with Section 7 of this standard protocol. 13.2.4. Baseline Period Control Strategy The user can specify if the baseline system relies on a throttling valve or an on/off valve. This can be entered using a simple button as shown in Figure 5. Figure 5 Baseline Period Control Strategy 4. Baseline Period Control Strategy Did the baseline system rely on a throttling valve or an on/off valve in the baseline period? 13.2.5. System Curve Information The Savings Calculator plots a quadratic system curve using the static head value (ft.) and the operating point of the system. The operating point can be specified in two ways, (1) through the system flow (gpm) and the system pressure (ft.), or (2) by specifying the VFD speed (in percentage) and measured Regional Technical Forum 17 Standard Savings Estimation Protocol - Pump VFD power (kW). Figure 6 presents the Standard Calculator input cells used to enter the system curve information. Figure 6 Inputs Required to Plot System Curve 5. System Curve Information Please enter information for system curve. Value 10 Static head Units ft. Operating point Please enter system operating point either by specifying system flow and pressure (Option 1) OR measured power and VFD speed (Option 2). Please select: Option 1 Option 1 System Flow (Q) System Pressure (H) Option 2 VFD Speed Measured Power 3250 135 gpm ft. kW Update Pump Operating Conditions The user should note that either Option 1 (system flow and pressure) or Option 2 (VFD speed and measured power) can be entered, not both. The user can select the option being used to input the system operating point using a dropdown menu. Once the operating point has been entered, the user should click on the “Update Pump Operating Conditions” button (bottom of Figure 6). 13.2.6. One Time Electrical Data The user has the option of either logging the power or the current of the system being studied. If the user is logging current, the user is required to take three measurements of power (kW) and current (amps) at different VFD speeds. It is required to have one measurement at 100 % speed. The input section for one time electrical data is presented in Figure 7. Figure 7 One-Time Electrical Data Input 6. One-Time Electrical Data (Optional) Enter electrical data measurements in lieu of trended data VFD Speed kW Amp 100% 132.2 200 70% 109.1 150 60% 76.6 100 Regional Technical Forum 18 Standard Savings Estimation Protocol - Pump VFD 13.3. Pump Operating Schedule Tab A detailed annual operating schedule of the pump is entered in this tab. As per the Standard Protocol, the user can specify pump operating schedule using one of two options, (1) “Operations Schedule Only” or (2) “Outside Air Temperature and Operations Schedule”. Once the user selects one of these two options, the user should click on the “Enter Operations Schedule” button to enter operating schedule details, as presented in Figure 8. Figure 8 Pump Operating Schedule Input Screen INPUT - Pump Operating Schedule Pump speed and hours of operation are determined by the following two options. Please choose one. If Outside Air Temperature is chosen please enter operations schedule by pressing the button "Enter Operations Schedule" Enter Operations Schedule As shown in Figure 8, once the user presses the “Enter Operations Schedule” button, a detailed operations schedule input screen will appear. This screen allows users to specify the hour, day, and month the pump is operational for up to three different schedules. The screen contains instructions on how to assign hours, days and months to each schedule. The user will then indicate shutdown periods for the pump using the boxes shown in Figure 9. Shutdown periods are defined as atypical times during which the pump is shut completely down, such as holidays and maintenance periods. Here the user shall record the total number of shutdown days per year which are not already captured in the trend data/ logging period. Regional Technical Forum 19 Standard Savings Estimation Protocol - Pump VFD Figure 9 Pump Shutdown Period Input Screen Annual Days of Shutdown (excluding those already captured in trend data): Days per Year Schedule 1: Notes (indicate reason for shutdown) Schedule 2: Schedule 3: Total: Estimated Annual Operating Hours (calculated result): 0 days 8,760 (based on typical operating schedule and shutdown periods entered above) 13.4. Trend Data (Pre) and Trend Data (Post) Tabs Both the Trend Data (Pre) and Trend Data (Post) tabs have the same layout. In these tabs, the user can paste data logged at the site. The data logged can be in either kW or amps; the user can specify this before pasting in the trend data. Power (kW) or current (amp) data MUST be all non-negative, numeric values (i.e. not text). The time stamp for the trend data must be in the form "mm/dd/yyyy hh:mm:ss" in order for the calculator to function properly. Time stamp and power data which does not follow these specifications may result in calculator errors. If pump operation depends on Outside Air Temperature (OAT), OAT trend data must also be provided. The trend data input screen is presented in Figure 10. Figure 10 Trend Data Input Screen Trend Data Please select whether power (kW) or current (amp) was logged in the pre-period: OAT Time Stamp kW 6/2/2006 17:53 127.49 52.0 6/2/2006 17:58 127.54 73.0 6/2/2006 18:03 127.49 24.0 6/2/2006 18:08 127.39 68.0 kW Once all the data has been entered, the user should press the "Update Logged Data" button. 13.5. Results Tab Once all the inputs have been entered, the user can go to the Results tab and view the energy savings estimates for both the BP and the SRM. The calculator presents the results for both BP and SRM in tabular and graphical form. This is presented in Figure 11. Regional Technical Forum 20 Standard Savings Estimation Protocol - Pump VFD Figure 11 Savings Calculations Results Screen Results: Simplest Reliable Method 130.3 80.3 Savings 347,977 49.9 Baseline vs. Proposed kW/kWh Using Simplest Reliable Method kWh/yr 1,200,000 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.0 1,000,000 kW 800,000 kWh Avg Power Proposed 703,580 600,000 400,000 200,000 Results: Best Practice Method Annual Energy Baseline 1,088,210 Proposed 703,580 Savings 384,630 0 Baseline kWh/yr Proposed kWh Avg Power 124.2 80.3 43.9 kW Annual Energy Baseline 1,051,558 kW kW kW Savings % Difference, Simplest Reliable Savings vs. Best Practice: -9.5% 13.7% kWh kWh Savings % Difference, Simplest Reliable Savings vs. Best Practice: 500,000 60.0 400,000 50.0 40.0 300,000 30.0 200,000 20.0 100,000 10.0 0 0.0 Simplest Reliable kWh Regional Technical Forum kW Simplest Reliable vs. Best Practice Method: kW/kWh Savings Best Practice kW 21