SAMSUNG Electronics HVAC SAMSUNG 4-WAY CASSETTE SINGLE ZONE SPLIT SYSTEMS HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: www.Quietside.com www.SamsungDVM-S.com Single zone heat pump systems. Samsung Electronics Single Zone 4-Way Cassette Model Numbers: Model Indoor Unit Outdoor Unit CH070CAV1 CH070CAV1 UH070CAV1 CH105CAV CH105CAV UH105CAV CH140CAV CH140CAV UH140CAV Part 1 – General 1.01 SYSTEM DESCRIPTION The variable capacity, heat pump air conditioning system shall be a Samsung Electronics System. The systems shall be (cool/heat) split system heat pump. The heat pump system shall consist of a single outdoor condensing unit, single indoor unit, and wired controller. The condensing shall be a horizontal discharge, 208/230V, 1Ph, 60Hz unit. The evaporator shall be recessed, ceiling cassette type. 1.02 A. B. C. QUALITY ASSURANCE The units shall be listed by Electrical Laboratories (ETL) and bear the ETL label. All wiring shall be in accordance with the National Electrical Code (N.E.C.). The units shall be manufactured in a facility registered to ISO 9001 and ISO14001 which is a set of standards applying to environmental protection set by the International Standard Organization (ISO). D. A full charge of R-410A for the condensing unit only shall be provided in the condensing unit. Additional refrigerant is required based on lengths of system liquid refrigerant lines. DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 1 SAMSUNG Electronics HVAC Part 2 – Warranty LIMITED WARRANTY SAMSUNG Air Conditioning Mini-Split Heat Pumps manufactured after 1/2006 1. LIMITED WARRANTY – SAMSUNG Air Conditioning warrants to the original end-user (“you”) of SAMSUNG Mini-Split Heat Pumps, the “Product” as follows: (a) If within Five (5) years after initial installation of the Product, the compressor ONLY in the Product shall prove to be defective in material or workmanship, SAMSUNG will replace the defective compressor at no charge. (b) If within Three (3) years after initial installation of the Product, ANY OTHER component/part of the Product shall prove to be defective in material or workmanship, SAMSUNG will at SAMSUNG’s option, repair or replace the defective part at no charge for the part. (c) If you are unable to prove the date of initial installation of the Product to the satisfaction of SAMSUNG, the th warranty period shall be deemed to commence on the 30 day after the date of manufacture of the Product. (d) The warranty on the replacement compressor and replacement parts will be limited to the unexpired term of the original warranty for the Product. 1. CONDITIONS – The warranty applies only if the Product: (a) was initially installed within the continental United States, Hawaii or Canada and remains at the site of its original installation (except for mobile home installations); and (b) was installed and operated and maintained in accordance with all written instructions, all applicable local installation and building codes, and good industry practices. 2. LIMITED LABOR WARRANTY: The above warranty applies with respect to parts only and NOT labor. Accordingly, subject to the conditions and limitations set forth herein, the above warranty entitles the Customer only to receive a repaired or replacement part, shipped via SAMSUNG’s choice of carrier and way and not to the installation of said part. However for a period of 120 (One Hundred & Twenty) Days from proven date of installation in the above warranty period SAMSUNG will provide labor services to repair a product or install repair or replacement parts at its designated repair facilities, or at its option, compensate its authorized dealers and contractors at SAMSUNG standard fixed rates in effect (irrespective of charges actually imposed and time actually expended) to provide such services. This limited labor warranty covers only the installation of parts or repair of the unit, not diagnosis of fault, time taken to obtain such parts or travel time to and from the jobsite. This warranty also does not cover costs for parts (such as filters or belts) incurred in connection with normal maintenance or owner-required maintenance of the Product. Consult the instructions enclosed with the Product for information regarding recommended maintenance. 4. THIS WARRANTY DOES NOT COVER damages caused by: (a) accident, abuse, negligence or misuse; (b) operating the Product in a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals; (c) modification, alteration, repair service by any person other than an authorized SAMSUNG dealer or HVAC contractor; (d) improper matching or application of the Product or components or loss of refrigerant; (e) failure to provide proper maintenance or service to the Product according to manufacturer’s instructions; (f) if the Product is not applied, installed, and operated in compliance with SAMSUNG’s written instructions, training seminars and recommendations; (g) fluctuations in electrical power;(h) lightning, flood, fire or other acts of God; or (i) if the product has not been paid for in full 1. TO OBTAIN WARRANTY PERFORMANCE or replacement parts you must notify an authorized SAMSUNG dealer or your HVAC contractor in writing of any claimed defect within the applicable warranty period. Any defective part to be replaced must be made available to SAMSUNG in exchange for the replacement part. To obtain the name of the nearest authorized SAMSUNG dealer or information on warranty performance, you may contact: QUIETSIDE, 8750 PIONEER BLVD, SANTA FE SPRINGS CA 90670, Tel : 1-562-6996066 2. Any and all implied warranties, including without limitation, any warranties of merchantability and fitness for a particular purpose, are limited in duration to the lessor of: (a) the applicable warranty period specified in DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 2 SAMSUNG Electronics HVAC paragraph 1 above, or (b) the warranty period provided by law for such implied warranty. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. 3. In no event shall SAMSUNG be liable to the owner of the Product or any other person for any special incidental or consequential damages in connection with the Product, whether arising out of breach of warranty, breach of contract, or otherwise. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. 4. This warranty contains the sole express warranty made by SAMSUNG in connection with the Product. No SAMSUNG dealer or contractor or other person is authorized to make any other warranties or representations on behalf of SAMSUNG in connection with the Product. 5. This warranty gives you specific rights, and you may also have other rights which vary from state to state. SAM-WAR-002 May 2006 DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 3 SAMSUNG Electronics HVAC Part 3 – Outdoor Unit Performance 3.01 The outdoor unit shall perform as indicated below (nominal capacity): Outdoor Unit UH070CAV1 UH105CAV UH140CAV Cooling Capacity* (Btu/h) 24,000 36,000 48,000 Heating Capacity* (Btu/h) 27,000 38,000 54,500 *Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB. *Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F. Part 4 – Products 4.01 UH070CAV1 / UH1**CAV Condensing Unit A. General The outdoor unit shall be equipped with multiple circuit boards that shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory. 1. Outdoor unit shall have a sound rating no higher than the following: Model dB UH070CAV1 60 UH105CAV 66 UH140CAV 66 2. Both refrigerant lines from the outdoor unit to indoor unit shall be insulated. 3. The outdoor unit shall have an accumulator. 4. The outdoor unit shall have a high pressure safety switch, fuse, over-current protection and crank case heater. 5. The outdoor unit shall have the ability to operate with a maximum height difference and total length noted in table below. Model UH070CAV1 UH105CAV UH140CAV Maximum Vertical Separation (feet) 98 98 98 Maximum Line Set Length (feet) 162 246 246 6. The outdoor unit shall be capable of operating in outside ambient temperatures between 14⁰F to 115⁰F in cooling mode without additional low ambient controls. DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 4 SAMSUNG Electronics HVAC 7. The outdoor unit shall be capable of operating in outside ambient temperatures between 0⁰F to 115⁰F in cooling mode with optional wind baffle accessory (see “accessories” section). 8. The outdoor unit shall be capable of operating in outside ambient temperatures between 5⁰F and 75⁰F in heating mode without additional low ambient controls. 9. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system. B. Unit Cabinet 1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a powder coated baked enamel. C. Fan 1. The UH070CAV1 outdoor unit shall be furnished with one (1) direct drive, variable speed propeller type fan. 2. The UH105CAV and UH140CAV outdoor unit shall be furnished with two (2) direct drive, variable speed propeller type fans 3. All fan motors shall be BLDC type. 4. The fan motor shall have inherent protection, have permanently lubricated bearings, and be completely variable speed. 5. The fan motor shall be mounted for quiet operation. 6. The fan shall be provided with a raised guard to prevent contact with moving parts. 7. The outdoor unit shall have horizontal discharge airflow. D. Refrigerant 1. The condensing unit shall require R410A refrigerant. 2. The condensing unit come charged for system line set lengths up to 25 feet. Additional refrigerant is required if the system line set length is over 25 feet. 3. The condensing unit shall contain a single EEV (electronic expansion valve) with 480 positions each to control refrigerant flow to the indoor unit. E. Coil 1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate fins on copper tubing. 2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce corrosion and promote moisture shedding. 3. The coil shall be protected with an integral guard. 4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity modulation capable, inverter driven, twin BLDC rotary compressor. F. Compressor 1. The compressor shall be an inverter driven, DC voltage, twin BLDC rotary compressor made by Samsung. 2. A crankcase heater shall be factory mounted in/on the compressor. DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 5 SAMSUNG Electronics HVAC 3. The outdoor unit compressor shall have a variable modulation technology to modulate capacity. The capacity shall be completely variable as noted in the table below: Model UH070CAV1 UH105CAV UH140CAV Cooling Capacity Range (Btu/h)* 7,500 – 28,500 11,000 – 41,000 13,800 – 52,600 Heating Capacity Range (Btu/h)* 6,800 – 37,000 9,200 – 50,000 11,500 – 59,000 *Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB. *Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F. 4. The compressor shall be equipped with an internal thermal overload. 5. The compressor shall be mounted to avoid the transmission of vibration. G. Electrical 1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The outdoor unit shall be controlled by integral microprocessors. 4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC 7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. 5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to indoor unit. 4.02 CH070CAV1/CH1**CAV (4-WAY CASSETTE) INDOOR UNIT A. General The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. The indoor unit shall have an internal condensate pump with maximum 28 inch vertical lift and internal condensate float switch. The indoor unit shall have the ability to use optional wireless controllers without installing a separately purchased IR receiver. Indoor unit and refrigerant pipes shall be charged with dehydrated nitrogen gas before shipment from the factory. B. Unit Cabinet 1. The cabinet shall be space-saving ceiling-recessed cassette. 2. Each corner portion of the panel cabinet shall be detachable, to provide easy access to adjust the unit height. DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 6 SAMSUNG Electronics HVAC 3. The cabinet shall have provisions for a field installed, filtered, outside air intake. A booster fan is necessary. A 208/230V AC relay terminal is available to control the booster fan (max 1A). 4. Branch ducting shall be allowed from cabinet, available on 2 sides to condition an adjacent space. 5. The indoor unit shall ship with a fascia panel as standard. The panel shall have 4 auto-swing louvers, IR receiver, and LED status lights. C. Fan 1. The indoor fan assembly shall be a turbo fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (4) speeds, Low, Mid, High, and Turbo 4. The auto air swing vanes (4) shall be capable of automatically swinging up and down for uniform air distribution. Model Number CH070CAV1 CH105CAV CH140CAV Fan Speed Setting (UL) - Low – Mid – High - Turbo B. Filter 1. Return air shall be filtered by means of an easily removable, electro-static, pleated, washable filter. C. Coil 1. The indoor coil shall be of nonferrous construction with Slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce corrosion and promote moisture shedding. 4. All tube joints shall be brazed with phos-copper or silver alloy. 5. The coils shall be pressure tested at the factory. 6. A condensate pan and drain shall be provided under the coil. 7. Both refrigerant lines to the indoor unit shall be insulated. D. Electrical 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz supplied from the condensing unit. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) 3. The indoor unit PCB contains a time-lag fuse. 4. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system. DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 7 SAMSUNG Electronics HVAC 4.03 Wired Controller (MWR-WE10) 1. Connection: Can control up to 16 Samsung indoor units (defined and controlled as one group). 2. Dimensions: 4 5/8” x 4 7/8” in size and white in color 3. Easy indoor unit control a. Indoor unit operation ON/OFF b. Indoor unit operation mode, set temperature, air flow direction, fan speed c. Quiet and sleep modes d. Error display e. Filter replacement alarm display and reset f. Single indoor unit control or multiple unit control (maximum 16 units) g. Upper/lower temperature setting h. Automatic operation stop function i. Daily/weekly operating schedule setting Premium Wired Controller Description Run and stop operation for a single group Switches between Auto/Cool/Dry/ Fan/Heat Set the temperature for a single group. Temperature Range of temperature setting Setting o Auto/Cool/Dry: 65°F-86°F o Heat: 61°F-86°F Models with 3 air flow speed settings: Fan Speed Setting o High /Mid/Low/Auto Air flow 2-step direction (Swing/Stop) Air Flow Direction Direct setting at a specific angle. Setting Air flow operation varies depending on the model. ON/OFF, temperature, fan speed, and mode settings can be specified Weekly Schedule Maximum 6 schedules may be set for each day. Real-time clock function: current time, day display function Button permission level setting (On/Off / Temperature setting / Mode button / Fan speed) Button lock Temperature limit setting After power reset, setting value is restored Various restriction capabilities Automatic stop setting Specified Function o Setting time range : 0-12 hours Setting/Viewing indoor unit option code Viewing indoor unit RMC address Viewing indoor unit cycle data Service Mode Setting/Viewing temperature sensor compensation of the wired remote controller(-9°~ +9°) Viewing the RPM compensation Viewing the filter time (1,000 hours or 2,000 hours) DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. Item ON/OFF Operation Mode Operation Display Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group 8 SAMSUNG Electronics HVAC Item Error Permit / Prohibit Local Operation Quiet Mode Room Temperature Premium Wired Controller Description Viewing indoor unit temperature sensor compensation under Heating (+2 or +5°) Viewing the H/W option setting Viewing the wired remote controller software version When an error is currently occurring on an air conditioner unit, the afflicted unit and the error code are displayed Setting/releasing of simplified locking for remote control buttons can be performed Select the Quiet mode to run the indoor unit to the set mode to lower the fan noise level. Actual room temperature display (or set temperature display) Operation Display Each Group Each Group Each Group N/A Each Group N/A Each Group Each Group 4. Other Premium Controller features a. Different button permission levels b. Partial button lock option (on/off, selection, temperature setting, fan speed, and schedule setting buttons can be locked individually) c. Backlight d. Daylight savings clock advance option e. Temperature limit setting option f. Real-time clock function; current time/day display function g. Built-in room temperature sensor h. Indoor unit operation state display i. Service mode support (indoor unit cycle data monitoring, option code monitoring and setting, and dip switch state monitoring) 5. Specifications a. 4 wire connection b. DC 12V (V1/V2) power supplied by indoor unit c. RS485 communication (F3/F4) d. Can sense temperature via internal sensor, temperature sensor inside the air handler, or use the average temperature between controller and air indoor unit sensors e. The Premium Controller shall require no addressing. f. The Premium Controller shall connect using four-wire (2 wires for power supply and the other two for communication), untwisted, shielded. The Premium Controller shall require cross-over wiring for grouping across indoor units. g. 16 AWG shielded cable is necessary for proper operation 4.04 OPTIONAL ACCESSORIES A. Wireless controller (MR-BH01U) DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 9 SAMSUNG Electronics HVAC 1. The wireless controller shall have the following control capabilities: a. Unit operation ON/OFF b. Can control: unit operation mode, set temperature, louver position, and fan speed c. Filter replacement alarm reset d. Louver position control e. Simple ON/OFF timer f. Low battery indicator g. Indoor unit option code setting (24 segment) 2. The indoor unit shall have the ability to use a wireless controller without adding additional IR receivers. 3. The wireless controller shall include a holder to secure the controller to a wall, etc. 4. The wireless controller shall include batteries from the factory B. Wind baffles for low ambient cooling 1. Front wind baffle (WBMF) a. WBMF-9/12/18 wind shield/baffle is compatible with: UH070CAV1, UH105CAV (requires 2), and UH140CAV (requires 2) outdoor units. b. Designed to be placed on fan discharge side (front). c. Only a front shield is required for applications where the mini split is adjacent to a structure that would protect the intake side from prevailing wind. Applications without this protection would require a back shield (ex: roof top). d. The wind baffle material shall be clear plastic. 2. Back wind baffle (WBMB) a. WBMB-9/12/18/36 wind shield/baffle compatible with UH105CAV (requires 2) and UH140CAV (requires 2) outdoor units. b. WBMB-24 wind shield/baffle is compatible with UH070CAV1 outdoor units. c. Designed to be placed on the coil intake side of the unit (back). d. Note: This back shield is only required for applications where the mini split is not adjacent to a structure that would protect the intake side from prevailing wind (ex: roof top). e. The wind baffle material shall be clear plastic. C. MIM-N01 Central control, communication converter, interface module. 1. Specifications a. Allows connection of DVM Plus III and Samsung single zone and multizone split systems to DVM S system NASA communication protocol central control options: MIM-D00AN (Data Management Server 2), MIMB17N (BACnet gateway), MIM-B18N (LONWORKS gateway), MCMA202DN (ON/OFF controller), MCM-A300N (touchscreen controller). b. 12VDC c. One per system DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 10 SAMSUNG Electronics HVAC 2. Connection a. Installs in outdoor unit b. Includes connection wires and installation box for simple installation. D. External remote room sensor (MRW-TA) 1. Connection a. The external room sensor shall be capable of connection up to 1 indoor unit. 2. Function a. The external room sensor shall be used to measure the exact room temperature. b. The external room sensor shall support wire length of maximum 39 feet. E. External contact control – individual unit on/off control and monitoring (MIM-B14) 1. Function a. Control options to enable/disable and monitor individual indoor units b. Direct indoor unit control by external contact, 0 volts signal c. Emergency control with simple contact input d. Indoor unit operation (thermo or operation) and error state output through relay contacts 2. Installation a. The external contact controller shall mount inside indoor unit b. Connection to PCB with included wire harnesses DRAFT: 6/26/2014 www.Quietside.com Specifications are subject to change without notice. 11