EMS Lead Checklist template - Alberta Ministry of Infrastructure

advertisement
Lead Checklist
Project ID: ID
Official Project Title:
LOCATION - BUILDING NAME AND CONTRACT TITLE
Project ID:
Project Manager:
Phone Number:
Date:
ID
Name
xxx-xxx-xxxx
Click to select date.
1.0
Lead
Lead in landfills has the potential to leach into groundwater systems. Lead waste accumulates in the
environment and can cause harmful effects to humans, plants and animals. The Occupational Exposure Limit
(OEL) for elemental and inorganic lead compounds is 0.05 mg/ m3 on 8 hours of exposure. For the purpose of
this checklist, sources of lead include lead acid batteries, paint scrapings, lead plumbing, lead flashings,
obsolete computers, and other lead containing equipment (i.e, Cathode Ray Tubes (CRT) in viewing screens).
Alberta Infrastructure disposes of any quantities of lead waste as regulated waste.
2.0
Emergency Response
2.1
The Contractor has submitted a site-specific
emergency preparedness and response plan
(EPRP).
2.2
The EPRP should include provisions for spills/
releases and fire.
2.3
Local authority may have further requirements.
3.0
Handling
3.1
Contractor personnel are familiar with hazards:
 the use of protective equipment
and
 clothing procedures when handling waste
containing lead.
3.2
A code of practice for the storage, handling and
disposal of lead waste that is:
a. a pure substance in an amount
exceeding 10kg or
b. a mixture in which the amount of the
substance is more than 10kg at a
concentration of 0.1 percent by weight
or more.
3.3
Workers are trained in accordance with the
Dangerous Goods Transportation and Handling
Act.
Rev: 2013 01 31
Filename: Document1
Resource ID: CA_T_
Notes:
Notes:
Page 1 of 3
Lead Checklist
Project ID: ID
4.0
Packaging
4.1
All lead containing waste is appropriately
packaged for the waste category. For example,
corrosive waste should be stored in nonmetallic containers.
4.2
All liquid waste containing lead must be stored
in leak proof containers with a screw- top or
other secure lid. Snap caps, mis-sized caps,
parafilm and other loose fitting lids are not
acceptable.
4.3
Lead waste that is classified under the
Transportation of Dangerous Goods (TDG) is
not mixed with other classified lead containing
wastes.
4.4
Lead waste is not mixed with any solid or liquid
for the purpose of dilution.
5.0
Temporary Waste Storage
5.1
Signage is posted in temporary lead storage
areas. Temporary lead storage areas are
secured and only accessible to authorized
personnel.
5.2
All lead wastes that are stored in such a
manner that incompatible wastes will have no
contact, even in the event of a release.
6.0
Transportation
6.1
Persons transporting or handling dangerous
goods have valid and current TDG certification.
6.2
Contractor transporting hazardous waste has
correct TDG placarding on vehicles.
6.3
Contractor responsible to provide required
manifests. Project Manager to provide
generator number.
6.4
Emergency response kit required on
transportation vehicle.
Rev: 2013 01 31
Filename: Document1
Resource ID: CA_T_
Notes:
Notes:
Notes:
Page 2 of 3
Lead Checklist
Project ID: ID
7.0
Disposal or Recycling
7.1
Lead waste has been disposed of by a licensed
waste disposal facility (to be verified by copy
of manifest) or recycled (if greater than 205
litres or 205 kilograms) by a licenced recyling
facility.
7.2
Liquid hazardous waste containing up to
500mg per kg of lead are deposited to class
1(a) landfill only.
8.0
Records
8.1
Records of all inspections conducted on site.
8.2
Copy of Shipping documents and manifests for
transportation of waste.
8.3
Copy of disposal certificate from disposal
facility.
8.4
Copy of EPRP.
8.5
Copy of fire protection plan.
9.0
Reportable limits
9.1
Contractor reports all spills or releases of any
quantities to Alberta Infrastructure.
9.2
Lead waste can be classed as an oxidizing
substance (Class 5.1), and is reportable if a spill
or release, from the transport exceeds 50 kg or
50 L. Lead waste can also be classed as a toxic
substance (Class 6.1), reportable at a spill or
release of 1kg or 1 L, or as an environmentally
hazardous substance (Class 9.2), reportable at
1kg or more. If considered a corrosive
substance (Class 8), a spill or release that
exceeds 5 kg or 5 L, is reportable. All of the
above mentioned quantities, depending on
their class is reportable to Alberta
Transportation and the local police.
Rev: 2013 01 31
Filename: Document1
Resource ID: CA_T_
Notes:
Notes:
Notes:
Page 3 of 3