Reheat steam temperature control concept in Once-through boilers - A Review Dr. Joachim Franke, SIEMENS AG, Germany Ponnusami K Gounder, CETHAR VESSELS LTD V.Balarathinam, CETHAR VESSELS LTD SYNOPSIS In once through boilers, superheated steam temperature is controlled by means of coordinated feed water flow and spray attemperation. For reheat (RH) steam temperature control, many methods are being adopted namely burner tilt, gas recirculation, divided back pass dampers, excess air and steam bypass as primary control and feed water attemperation is envisaged as emergency control. When the boiler is operated in sliding pressure mode the cold reheat steam temperature is higher compared to constant pressure operation. The adjustment required for maintaining constant reheat outlet temperature is larger in constant pressure operation mode. In general spray is not used for RH steam temperature control for boilers designed for constant pressure operation since the spray quantity required will be large and its impact on plant heat rate. In Europe utility boilers are operated under sliding pressure mode and hence RH steam temperature control by spray is a common practice especially for once-through boilers. This paper deals with the benefits and losses of using spray for RH steam temperature control in lieu of other control mechanisms. Introduction: pressure operation as it affects plant heat rate. In utility boilers, it is important to achieve best However, in case of once through boilers which possible heat rate to reduce the fuel cost and are generally operated in sliding pressure mode, hence the operators try to maintain superheat quantum of RH spray is expected to be lower. In and reheat steam temperatures at rated value to this case RH spray attemperation is preferred as the extent possible. In once through boilers, SH it will result in simpler design and operation of steam temperature is maintained by means of the boiler and also less maintenance as systems coordinated spray like burner tilt, GR fans, divided back pass attemperation. There are many methods to dampers are eliminated. Above aspects are control RH steam temperature: like burner tilt, discussed in detail in this paper. feed water flow and gas recirculation (GR), divided back pass dampers (gas biasing), excess air and steam Need for steam temperature control: bypass. an Superheat and reheat steam temperatures emergency control, is not preferred as a means should not be allowed to increase beyond the of RH steam temperature control in constant rated value as it will result in metallurgical Spray, though envisaged as problems in superheater and reheater tubes and Burner tilt: also turbine components. On the other hand, Tilting burners are provided in corner or steam temperature lower than rated value will tangential fired boilers. The burners can be tilted result in higher cycle heat rate. Typically a up or down in unison in all the four corners to temperature reduction of 10 deg C in large move the fire ball inside the furnace either capacity power plant will result in about 0.3 % upward or downward to change the furnace increase in plant heat rate. Hence it is essential absorption. When RH temperature is lower than to reheat the rated value, burners are tilted up to reduce temperatures within a narrow range around the the furnace absorption and increase the furnace rated values. outlet temperature. As more heat is now maintain the superheat and available for RH pick up, RH temperature can be Steam temperature control methods: maintained. When RH temperature is more than In a coal fired boiler, super heat and reheat pick the rated value, the burners are tilted down. up are influenced by many variables like coal Refer Figure-1. quality, cleanliness / dirtiness of the furnace, fouling of heat transfer sections, etc,. When the furnace is cleaner compared to the design condition, the furnace absorption is more resulting in lower furnace outlet temperature (FOT) and hence lower SH and RH temperatures. On the other hand, when slagging / fouling occurs due to deterioration in coal quality, furnace absorption will be lower resulting in higher furnace outlet temperature and hence higher SH and RH outlet temperatures. Normally superheat steam temperature is maintained over the load range by means of coordinated feed Fig. 1 Burner Tilt water flow and spray attemperation. Various methods are employed to maintain the reheat steam temperature at rated value over the control load range. The after effect of reheat temperature control on superheat temperature increase or decrease is regulated by feed water attemperation. The methods employed for reheat temperature control are discussed below. Divided back pass dampers: The divided back pass arrangement is used in wall fired boilers with fixed burners. In wall fired boilers, the convective back pass is divided into two gas passes. On one side, Low Temperature Reheat (LTRH) section is located and on the other side Low Temperature Superheat (LTSH) section is located. These two sections are dampers are positioned both upstream and divided by steam cooled wall or a baffle plate. A downstream of the fan. Refer Figure-3 for a common economiser heat transfer section is typical arrangement of gas recirculation. As the located across both the LTRH and LTSH quantity of re-circulated gas is changed, the sections outlet. The gas mass flow through quantity of heat absorbed in the furnace and the LTRH side can be increased or decreased (gas heat at furnace outlet are changed. When RH biasing) by the multi louver dampers positioned outlet temperature is lower than rated value, GR at the outlet of each pass (generally at the outlet quantity is increased to increase the heat of economizer section in lower gas temperature available for RH pick up. In this case power region). Refer Figure-2 for a typical arrangement consumed by the GR fan is additional loss and of dived back pass with control damper. By will increase the net plant heat rate. opening the dampers on LTRH side, the heat transfer in LTRH section which is predominantly convective is increased due to the increase in gas mass flow thereby increasing the RH steam temperature. In this type of control, draft loss through the dampers will increase the power consumed by induced draft fans. Fig. 3 RH Steam Temp. Control By Gas Recirculation Excess air: Excess air by itself is not used as a means of Fig. 2 Divided Back Pass Damper control RH steam temperature control as an increase in excess air will increase the stack loss and Gas recirculation: reduces the boiler efficiency. Typically 0.3 to 0.4 Flue gas at economizer outlet or ID fan outlet is % of boiler efficiency will be lost for every 10 % drawn and reintroduced into the furnace by a increase in excess air. In some cases especially Gas Recirculation (GR) fan. Tight shut off when the control load is very low, in addition to burner tilt or gas biasing, excess air is also to be the rated temperature can be achieved at increased to achieve the RH steam temperature. control load (70%) with zero spray. Even at loads below control load the reheat steam Effect of RH spray: temperature deviation is small compared to The reheat spray is done in a reheat de- constant pressure operation and hence the superheater located in the cold reheat piping at impact on turbine metal temperature and heat the inlet of low temperature reheat (LTRH) rate are minimal. Figure 4 gives typical reheat section or in between stages in a two stage steam temperatures over the load range for reheater. Due to the lower operating pressure constant for reheat cycle, RH spray is normally taken pressure operation. Reheat steam temperature from boiler feed pump inter stage. When tapped control by spray is a common practice in at this location, the spray water is not passing Europe for once through boilers. Attached table through the HP feed water heaters. Hence this (Table 1) gives few supercritical boilers built in amount of spray quantity is less regenerative. Europe where spray attemperation is the Further this spray quantity bypasses HP turbine normal and expands only in IP / LP turbines doing less temperature control. pressure control operation means for and variable reheat steam work. Because of these reasons, the cycle efficiency reduces and heat rate increases. The reduction in efficiency (or increase in heat rate) is a function of the quantity of spray water used. RHO CP Rated temp 568 deg c RHO SP Since the spray water required under sliding pressure operating mode is less, its impact on heat rate is minimal. Typically the cycle efficiency decreases by about 0.08 % for every 1% RH spray. RHI SP RH spray as the primary control method in RHI CP once through boilers: In once through boilers which are generally operated in sliding pressure mode, the temperature of steam entering RH at all loads is higher than it would be in constant pressure RHO CP – RH outlet temp, constant pressure operation. This helps in achieving the rated RH RHO SP – RH outlet temp, sliding pressure outlet temperature easily even at part loads. RHI CP – RH inlet temp, constant pressure When designed with 1 to 2% spray at full load, RHI SP – RH inlet temp, sliding pressure Table 1 Reference List of European supercritical boilers with reheat temperature control by spray attemperation Name of plant Maasvlakte Walsum 10 Neurath F&G (BOA1&2) Nordjyllandsvaerket 3 Iskenderun 1&2 Country Netherlands Germany Germany Denmark Germany Name of Customer E.ON Evonik RWE Vattenfall Year of order Power Output, gross ( MW ) Steam pressure (barg) Main steam temperature (°C) RH steam temperature (°C) 2008 1100 284 600 620 2006 710 290 603 621 2005 1100 272 580 605 1993 415 290 582 580/580 Turkey Evonik/Ste ag 2000 660 210 541 539 Boiler type Pulverised coal Pulverised coal Pulverised coal Pulverised coal Pulverised coal Pulverised coal Type of coal Bituminous Bituminous Lignite Bituminous Bituminous Bituminous Rostock E.ON 1991 550 265 545 562 Design simplification: Generally for coal fired boilers either "Burner Tilt" or "Divided Backpass" is used for reheat steam temperature control. The control response is slow due to the large inertia involved with these control mechanisms. So emergency spray is provided in addition to either of these control methods. In many operating plants, the operators resort to spray for control flexibility though other control mechanism is provided in the design. As a result the real heat rate advantage is not realized in day to day operation. The design can be simplified if "Burner Tilt" or "Divided Backpass" is not considered for control. Elimination of the control mechanisms with their associated Controls & Instrumentation will also result in reduced capital cost and operating cost. Conclusion: In view of the marginal effect on heat rate, elimination of maintenance prone control mechanisms, design simplification, RH steam temperature control by spray attemperation in once through boilers is good for both boiler suppliers and plant owners. The consultants and owners who are in the process of making the specification for once through boilers should seriously consider adopting spray as the normal control means for reheat steam temperature control. Reference: 1. Power plant Engineering – Black and Veatch 2. J.C. Peeraer , "Gegenüberstellung unterschiedlicher Zwischenüberhitzer temperaturregelungen", Diploma Thesis Delft University of Technology, Netherlands, 1996