AutroSafe SelfVerify Interactive Fire & Gas Detection System ID: ASAFE_intro_Eng, 2007-09 ID: 1 Overview and a brief introduction of; Reference to traditional systems The AutroSafe system Background for development – IEC EN54 AutroSafe terminology Features introduction SelfVerify System Integrity (SIL) Reliability Communication Software Tools ID: 2 Traditional Analogue Addressable Fire-Alarm Systems BU-100 5th Deck BU-70 4th Deck BU-100 3rd Deck BU-70 2nd Deck BU-100 BRANN LER CCR 1st Deck Utility Deck DYNAMIC FILTER PROCESS ID: 3 AutroSafe SelfVerify Interactive Fire-& Gas Detection System Corridor 5th deck LER Corridor 4th deck LER Corridor 3rd deck LER Corridor 2nd deck LER CCR LER 1st deck Utility-deck ID: AUTROLON 4 Traditional F & G System AutroSafe DCS system Operator Station Standard Loop Units Node 1 Redundant Network Node 2 Node 3 Node 4 Node 5 Node 6 EX Loop Units AutroPoint AutroFlame Third party detectors Third party detectors Simrad ID: AutroPath HC600 RX AutroPath HC600 TX Kidde Fenwal Analaser II AutroFlame CCTV 5 AutroSafe Panel (TCP/IP) AutroSafe IFG AutroOS AutroSafe Panel ModBus To Process Control System AutroSafe Controller Al_Com loop AutroLON Standard AutroSafe loop units Information/ Repeater panel Barrier unit BZ-500 BSD-340 AutroFieldBus AutroSafe EX loop units BSD-321 AutroFlame X33/1 PL PowerLoop Video BN-342 (4-20mA) Third-party Detector Third-party Detector Kidde Fenwal Analaser II AutroPath HC600 AutroFlame CCTV ID: 6 AutroSafe and EN 54 AutroSafe: Developed and approved in accordance with EN 54-2 and EN 54-4 AutroSafe: Considers the demands of future EN 54 norms AutroSafe: Exploits all the possibilities of EN 54 (American equivalent is NFPA 72 – AutroSafe is also FM approved – thus tested and approved against NFPA 72) ID: 7 Features, Performance, Functionality.. A u tro n i c a A u tro n i c a A u tro n i c a ID: Interactive loop Communication Automatic addressing Intelligent field devices Increased reliability – key terms: SelfVerify TM DYFI+ (Dynamic Filter Process) Built-in Short circuit isolators Loop topology Fail-safe loop communication Roughed loop communication 8 Terminology – mostly based on EN54 Some examples: DECK 3, CORRIDOR Heat Detector DECK 3, LER SOUTH Smoke Detector A u tro n i c a Operator panel DZ-2 DZ-1 F A A F W K K A R 2 1 R E E DZ-3 A u tro n i c a OZ-1 K NU S TRYK K HER B REAK G LA S SE T P RE S S H ER E G LA S S A u tro n i c a AZ-2 = DZ: Detection zone = AZ: Alarm zone CCR Optical Smoke Detector AZ-1 DZ-4 WORKSHOP Multi-sensor Detector AZ-3 = OZ: Operation zone ID: 9 AutroSafe SelfVerify System Panels Maximum flexibility: Easy to read, understand and operate Fire & Gas Alarm panel Operator Panel Repeater Panel Information Panel Controller ID: 10 AutroLON AutroLON AutroSafe panels in a Ring loop Short-circuit isolators in every panel – all panels will continue to operate even with a single break or short circuit on the AutroLON Maximum 32 panels in one LONring (but needs a Booster for each 8th panel) Fibre-optic modems available (3000 meters between two panels) Back to main page ID: 11 AutroSafe Panel A complete fire and gas control panel with full operator capabilities Supports up to 6 fire detection loops and 1 AutroFieldBus 2 AutroCom Serial, 1 AutroCom Ethernet (TCP/IP) Outputs and inputs, monitored or unmonitored Back to main page ID: 12 AutroSafe Controller Serves as a connection unit for detection loops (maximum 6) 1 AutroFieldBus 2 AutroCom Serial, 1 AutroCom Ethernet Outputs and inputs, monitored or unmonitored Communicates with other system units on AUTROLON Back to main page ID: 13 AutroSafe Information/ Repeater Panel Information Panel Serves as an indication device only Provides information related to the defined operation zone(s). Repeater Panel Displays alarms and allows operation of alarms and receipt of additional information related to the relevant operation zone Back to main page ID: 14 AutroSafe SelfVerify, a Modular System A variety of DIN rail mounted I/O modules available.. •Loop drivers •Digital output modules •24V alarm output modules •Digital input modules ID: 15 A Wide Range of Products for All Applications Series Units Heat detectors Optical smoke detectors High-sensitivity Multisensor smoke smoke detectors detectors Manual Call-points Interface/ address units Sounder Series 200 Standard InteractiveAddressable units Series 300 With SelfVerify® functions Series 500 With special protection for marine, offshore, Exi applications ID: 16 AL_Com Loop AL_Com Loop Ring loop-topology with detectors, I/O interfaces and sounders Short-circuit isolators in every loop unit – all detectors and interfaces will continue to operate even with a single break or short circuit on the AL_Com Loop One branch between two units on the main loop All ‘decisions’ made by loop unit, event messages sent to panel Fail-safe operation if communication fails. Back to main page ID: 17 Standard AutroSafe Loop Units The detection loop is connected directly to the Loop Driver Module All types and series of AutroSafe detectors, manual call-points and I/O units can be connected to the same detection loop (99 det/mcp + 27 I/O) Back to main page ID: 18 AutroSafe EX Loop Connected to one barrier (branch) between two units on the main loop Maximum 20 EX-units on one branch Most Autronica-detectors and I/Ounits are produced in EX-versions Back to main page ID: 19 Large Assortment of I/O Units A number of loop controls and Interface units are available Disablement input-units Interface units for alarm and faults Door control and monitoring units Output control unit General monitoring and control units Sprinkler monitoring units ID: 20 BSL-330/X Interfaces on-site third-party systems The following messages can be transmitted (from/to an AutroSafe fire-alarm panel): fire alarms pre-alarms faults technical alarms from I/O units and event handling from thirdparty devices Four different versions Version Modbus Port 2 BSL-330/1 Slave RS-422/RS-485 BSL-330/2 Master RS-422/RS-485 BSL-330/3 Slave RS-232 BSL-330/4 Master RS-232 Back to main page ID: 33 AutroCom directly to DCS ABB AC400 ABB AC800 Siemens Kongsberg Emerson Hima Advantages of direct communication and propriatary protocol: Fuctionality and SIL! ID: 34 AutroOS A remote monitoring and control system that enables full operation of the AutroSafe fire-alarm panels All alarms, faults, inhibits, overrides and outputs can be monitored and controlled from the AutroOS stations Video from CCTV flame cameras Microsoft Windows platform Back to main page ID: 35 AutroSafe Sys. & Utility Software Package AS Configuration Tool Merge Tool Power Calculators Import/Export Tools Download Tools AS I/O Simulator Tool The perfect Application Software verification Tool Loop Diagnostics Tool WAS-2000 and AS-2000 ID: 36 What is SelfVerify®? SelfVerify® function: The detectors are tested once every 24 hours with a calibrated signal ID: 37 Standard Analogue Addressable Fire-Alarm System Supply Power supply Detector Loop Communication Communication interface interface Monitored parts NonCalibrated test Smoke detector Fault Warning warning Fault Fault Signal signal Fault ALARM! Fire Alarm signal Fire Alarm Signal STOP! Operation Alarm Alarm signal signal ID: Detector test with test gas Detector smoke chamber 39 SelfVerify® Fail-safe detectors give increased reliability, and reduce maintenance costs dramatically Power supply Communicationinterface SVcontrol Smoke detector Fault warning Fault signal ALARM! Fire Alarm Fire Alarm Signal STOP! Operating SelfVerify® stimulator Alarmsignal Calibrated test Detector smoke chamber Monitored part ID: 40 Why SelfVerify®? SelfVerify® – Reduces the need for manual testing is significantly ID: 41 System Integrity R&D target for System Integrity: No single fault shall degrade system performance SIL 2 (Safety Integrity Level2) in accordance with IEC-61508 (By TÛV and NEMCO) ID: 42 SIL 2 Certificates by TÛV and NEMCO ID: 43 Comprehensive list of Approvals American Bureau of Shipping ATEX (NEMCO) Bosec BUREAU VERITAS AND AUTORITES MARITIMÈS FRANCAISES China Compulsory Certification China Classification Society China National Quality Supervision and test centre for explosion protected electrical products Dansk brand- og Sikringsteknisk Institut Det Norske Veritas (DNV) Forsikringsselskapenes Godkjenningsnevnd FM APPROVALS Germanischer Lloyd Japanese Government Lloyd's Register of Shipping ID: Maritime and Coastguard Agency Nonprofit Independent Research Organisation “Certification Centre of Explosion-proof and Mine Electrical Equipment" - Nanio “CCVE" Nippon Kaiji Kyokai Polski rejestr Statków Registro Italiano Navale Russian Maritime register of Shipping Svensk Brand- och Säkerhets Certifiering ab United States Coast Guard Vniipo/Gost 44