Distributed Generation and Power Quality-Continued 1 Siting Distributed Generation # Distributed Generation provides some capacity relief on the substation. # Distributed Generator should be sited away from the substation. # Distributed Generator (diesel genset) might be sited near the tie-point between two feeders. 2 Typical interconnection requirements for customer-owned DG • No voltage regulation while interconnected unless by special agreement • Anti-islanding frequency and voltage control (IEEE Standard 929-2000) • Relaying to detect resonant conditions in susceptible applications • Fault detection: relaying to detect faults on utility system and disconnect after delay. • Direct transfer trip (costly) 3 Typical requirement to detect faults on utility system and disconnect after delay (60 Hz system): Condition Max delay V 50% 10 cycles 50% < V 88% 2.0 sec 110% < V 120% 1.0 sec V > 120% 10 cycles f < 59.3 Hz 10 cycles f > 60.5 Hz 10 cycles 4 ANSI C37-2 Device Numbers 21 Distance Relay 25 Synchronizing Device 27 Undervoltage Relay 32 Directional Power Relay 49 Thermal Relay 50 Instantaneous Overcurrent Relay 51 AC Time Overcurrent Relay 52 AC Circuit Breaker 5 ANSI C37-2 Device Numbers 59 67 Overvoltage Relay AC Directional Overcurrent 72 76 79 DC Circuit Breaker DC Overcurrent Relay AC Reclosing Relay 81 Frequency Relay 86 87 Lockout Relay Differential Relay 6 Small DG: Relays added to normal protection (overcurrent, etc.) for interconnection 81 OU load DG 27/59 27: undervoltage 59: overvoltage 81: frequency (O=over, U=under) 7 Small DG: Relays would trip DG breaker if not used for backup. Relays would trip main breaker if used for backup, so that continued operation is possible (must coordinate with controls on DG) 8 50/51 46 27/59 81 47 O/U 25 46 87 51G 32R DG 59I 59N 50/51 40 resistance grounded to limit ground fault current 1-10 MW DG showing typical protection 9 25: synchronizing device 27: undervoltage 32R: reverse power 40: loss of field 46: negative sequence current 47: negative phase sequence 50: instantaneous overcurrent 51: time overcurrent 51G: ground overcurrent 59I: inst. overvoltage (if resonance is problem) 59N: overvoltage (on corner of broken delta) 87: differential (main generator overcurrent) 10