ERV Plus

advertisement
INSTALLER
ERV
VER. 01- Jan. 2011
ENERGY RECOVERY VENTILATION
[ERV Plus]
SAMSUNG ELECTRONICS Co. LTD.
HQ SE
1
Trainer Profile
• Name :
• E-mail :
SAMSUNG ELECTRONICS CO.LTD
2
Contents
■ ERV + Basics
SAMSUNG
ERV
■ Key Technology
■ Controls & Solution
■ Case Study
■ ERV Line-up
■ Duct design
SAMSUNG ELECTRONICS CO.LTD
3
ERV Plus Introduction
ERV +
ERV Plus introduction
ERV Plus = ERV(Ventilator) + DX Coil + Humidifier(Option)
5
ERV+ USP
High efficiency of motor
■ Power consumption comparison by models
500 CMH
255%
1000 CMH
131%
100% 100%
Samsung
Company D
Capacity
Samsung
Company D
500 CMH
220W
560W
1000 CMH
510W
670W
6
ERV+ USP
The Slimmest Height & Light Weight
- The slim height makes installation, maintenance
and repair very easy
270mm
Div
D Company
M Company
X Company
Samsung
387mm
317mm
365mm
270mm
100%
82%
97%
71%
96kg
57kg
98kg
62kg
100%
59%
102%
64%
Product
Image
Height
Weight
7
ERV + USP
Simple line up
- ERV PLUS = ERV (Ventilator) + Dx-Coil (Air conditioner) + Humidifier(Optional)
=> Install humidifier to ERV Plus at any time.
+
ERV Plus
Line
Up
Humidifier
Kit
D Company
M Company
X Company
Samsung
Humidifier Model
Non-Humidifier
Model
(Separated Model)
Humidifier Model
Non-Humidifier
Model
(Separated Model)
Humidifier Model
Non-Humidifier
Model
(Separated Model)
Non-Humidifier Model
+
Optional Humidifier Kit
8
ERV+ USP
Filter high efficiency
Samsung
High Efficiency Medium-filter
D company
Pre-filter
■ Classified as high efficiency Medium-filter, while the other is defined as pre-filter
■ Dust spot efficiency is over 70% (based on ASHRAE Std 52.1)
■ Fractional efficiency is over 60% (based on MIL,STD-282)
Composition
Filter media
Frame
Hot melt
Spec.
Media
PP + PET Spun bond
Composition
PP + PET Nonwoven
Weight
120g/㎡ ± 10%
Material
PET
Weight
260g/㎡ ± 20%
Material
Nylon
Softening point
139 ~ 149 ℃
9
ERV+ USP
Class
Standard 52.2
Min. Efficiency
Reporting Value
(MERV)
1
2
3
Pre filter
4
5
6
7
8
9
10
Medium
Filter
HEPA
ULPA
Pre/Medium
(EN 779)
HEPA/ULPA
(EN1822)
G1
D company
Panel Type
Compact Pocket Type
G2
G 35
MP 35
F 40 / F 45
G3
G4
Samsung
Compact Pocket Type
Compact ECO Pocket Type
F5
11
F6
12
F7
13
F8
14
F9
15
H 10
16
H 11
17
H 12
18
H 13
19
H 14
20
U 15
F 50
EP Series
MF Series
HEPA
ULPA
SF Series
U 16
U 17
10
ERV + Basic
Structure of ERV Plus
Total heat
exchanger element
Humidifier (Option)
Exhaust Air
Outdoor Air
Return Air
Supply Air
Access panel
Filter
PCB
DX Coil
Damper
11
ERV + Basic
Schematic diagram of ERV Plus
< DX Coil specification>
Return air temp. sensor
Suction air temp. sensor
ERV Plus
Eva out temp.
sensor
Total
heat exchanger
OA temp. sensor
DX Coil
RHF050KHEA
RHF100KHEA
L : 340 mm
2Row x 12 step
L : 644 mm
3Row x 14 step
Fin
1.5 FP, Slit
DX coil
Eva in temp.
sensor
Humidifier
Gas pipe
< EDM type EEV>
EEV
Liquid pipe
Water feed pipe
EEV
RHF050KHEA
RHF100KHEA
DPF(Q) 1.3
DPF(Q) 2.0
- Max. 1400 step
12
ERV + Basic
The specification of RHF050KHEA
Classification
Air flow rate
Unit
Samsung (RHF050KHEA)
D (VKM500GAMV1)
Air flow rate
(㎥/h)
500
500
Static pressure
(Pa)
160
180/*160
(W)
220
560
cooling
(%)
70
76
heating
(%)
75
76
cooling
(%)
60
64
heating
(%)
73
67
cooling
(KW)
5.1
(ERV:1.5)
4.71
(ERV:1.91)
heating
(KW)
6.5
(ERV:2.5)
5.58
(ERV:2.38)
(kg/h)
2.7
2.7
(dB)
38.5/* 37.5
38.5/* 37.5
(kg)
61 / * 63
96 /* 102
(mm)
1553*270*1000
1764*387*1214
Power input
Ventilation
performance
Temp. exchange
efficiency
Enthalpy
exchange
efficiency
Outdoor air processing capacity
Humidifying capacity
Sound level
Set size
extra high
* Including humidifier
13
13
ERV + Basic
The specification of RHF100KHEA
Classification
Air flow rate
Ventilation
performance
Unit
Samsung (RHF100KHEA)
D (VKM100GAMV1)
Air flow rate
(㎥/h)
1000
950
Static pressure
(Pa)
150
150 / *110
(W)
510
670
cooling
(%)
70
74
heating
(%)
75
74
cooling
(%)
62
62
heating
(%)
75
65
cooling
(KW)
heating
(KW)
10.5
(ERV:3.4)
13.2
(ERV:5.2)
9.12
(ERV:3.52)
10.69
(ERV:4.39)
(kg/h)
5.4
5.4
(dB)
40.5/* 39.5
40.5/* 39.5
(kg)
90 / * 93
114 / * 125
(mm)
1763*340*1135
1764*387*1214
Power input
Temp. exchange
efficiency
Enthalpy
exchange
efficiency
Outdoor air processing capacity
Humidifying capacity
Sound level
Set size
extra high
* Including humidifier
14
14
ERV + Basic
Psychrometric chart plotting with cooling operation
100
< Example>
80
60
71.7 kJ/Kg
62.82 kJ/Kg
Total
heat exchanger
Heat recovery
DX
Coil
40
53.77 kJ/Kg
ERV Plus
cooling
performance
Cooling
SA
Cooling
Cooling
35℃
RH 40%
20
RA
27℃
RH 47%
-5
0
5
10
Absolute Humidity (kg/kg’)
OA
15
20
25
30
35
40
Dry bulb (℃)
29.5℃
RH 50.2%
32.4℃
RH 38%
Temperature Efficiency
13.3℃
RH 80%

t(OA)  t( SA)
 100
t(OA)  t( RA)
Enthalpy efficiency ratio 
Enthalpy Efficiency

h(OA)  h( SA)
 100
h(OA)  h( RA)
71.7  62.82
100
71.7  53.77
= 49.5 %
15
ERV + Basic
Psychrometric chart plotting with heating operation
100
< Example>
80
60
Total
heat exchanger
40
DX
Coil
Humidifier
41.91 kJ/Kg
20/15 ℃
36.6 kJ/Kg
Humidifying
RA
Heat recovery
heating
Humidifying
20.61 kJ/Kg
20
OA
Absolute Humidity (kg/kg’)
2/1℃
SA
Heating
20℃
RH 59%
7℃
RH 87%
16.4℃
RH 67%
10.6℃
RH 79%
40 ℃
RH 12.2 %
29.5℃
RH 40%
-5
0
5
10
15
20
25
30
35
40
Dry bulb (℃)
Enthalpy efficiency
h( SA)  h(OA)
100
h( RA)  h(OA)
36 .6  20 .61

 100 = 75 %
41 .91  20 .61

16
Operation mode
Operation mode
Energy recovery(Heat-Ex) and By-pass ventilation
Air flow
Damper
Energy recovery
(Heat exchange)
By-pass
<Wired remote controller>
<Energy recovery mode display>
<By-pass mode display>
18
Operation mode
Auto ventilation
-According to OA and Return air temperature, the mode is determined.
- The operation mode will be operating during 30 min.
Condition
Energy recovery
(Heat exchange)
|OA temp. –RA temp| >= 5℃
By-pass
|OA temp. –RA temp| < 5℃
Return air temp. sensor
Outdoor air temp. sensor
19
Operation mode
Clean up operation
-To make positive or negative pressure of room,
supply and exhaust air volume can be different by Clean up operation .
Switch 17 state
Supply air volume
Exhaust air volume
On
Selected fan mode
Silent fan mode
Off
Silent fan mode
Selected fan mode
Air volume difference
Max. 35 %
(Turbo and high fan mode)
-To avoid toilet odor, more air volume 10 ~ 15%
have to supply to make positive pressure of living
Toilet
Living Room
Positive pressure
20
Operation mode
Outing operation
Operation mode
Fan
Energy recovery ventilation
On : 10 min, Off : 50 min
Low
Quite operation
-The fan mode is fixed to the quite mode.
Fan mode
RHF050KHEA
RHF100KHEA
Turbo
38.5
40.5
High
36
38
Low
32
35
Quite
30
33
21
Operation mode
Energy saving operation
: Energy saving operation is run when all the following conditions are met.
1) One or more ERV units must be connected to MWR-WE10 (without or with indoor unit(s) )
2) Either the indoor unit or ERV must be ON (if the indoor unit is ON, it must not be FAN mode).
3) ERV must not be in Outing mode
4) ERV external control must not be enabled.
5) ERV must not be in “Centralized” control mode.
6) ERV must not be in “Kitchen Hood” control mode.
NOTE : The sub wired remote controller does not support energy saving mode
22
Operation mode
Energy saving operation
Cooling
Default setting temperature : 26°C.
User can change it
Heating
R : Room temperature / S : Setting temperature
Default setting temperature : 22°C.
User can change it
R
26°C
S
S
22°C
R
Energy
Saving
Out temp < Set temp
: Cool air intake ↑
Out temp < Room temp
: Cool air intake ↑
Set temp < Out temp
: Warm air intake ↑
Room temp < Out temp
: Warm air intake ↑
Out temp >= Set temp
: Heat exchange ↑
Out temp >= Room temp
: Heat exchange ↑
Set temp >= Out temp
: Heat exchange ↑
Room temp >= Out temp
: Heat exchange ↑
23
Operation mode
Auto operation (DX coil)
Suction air temp. sensor
Cooling operation
A area
B area
Suction air temp >= auto cooling setting temp.(*25 ℃)
Thermo off (Ventilation operation)
Heating operation
C area
Suction air temp < auto cooling setting temp – Thermo off gap temp.
(*25℃ – 10℃*)
Set temp. range :
Auto cooling set temp. : 15℃ ~ 30℃
Thermo off gap temp. : 5℃ ~ 15℃
Outdoor air temp. sensor
Outdoor air temp. sensor
* Default value can be changed by wired remote controller (SVC mode)
24
Operation mode
Heating operation (DX coil)
-After working of ventilation mode, cooling and heating mode of DX coli is possible.
Thermo on
Thermo off
Remark
Cooling
Suction air temp >= *Default set temp.
Suction air temp <= *Default set temp. – 4℃
*Default cooling set temp. : 25℃
(Set temp range : 15 ~ 30℃)
Heating
Suction air temp <=
*Default set temp. + **Compensation temp. - 6
Suction air temp >=
*Default set temp. + **Compensation temp. - 2
*Default cooling set temp. 22℃
**Compensation temp. : 2, 5 ℃
25
Safety operation
Prevention of condensate
System is capable of self adjustment depending on outdoor temperature to prevent it from
condensate on element
Outdoor Temp
Operation Type
Above 0℃
Normal Operation
0 ℃ > TOA >-5 ℃
“A” Type Cyclic
Operation
Discharge
On
On
Refer to below operation pattern
“B” Type Cyclic
Operation
-5 ℃ > TOA >-10 ℃
Intake
-10 ℃ > TOA >-15 ℃
Off
On
Below -15 ℃
Off
Off
‘A’ Type
80min
Both Intake and Discharge On
‘B’ Type
50min
Both Intake and Discharge On
10min
Only Discharge On
10min
Only Discharge On
80min
Both Intake and Discharge On
50min
Both Intake and Discharge On
Remarks
Repeated on a
regular time basis
10min
Only Discharge On
10min
Only Discharge On
26
Fan operation with CO2 sensor
Refresh system - CO2 Sensor( option)
CO2
Fresh Air
CO2
CO2
Note
1. K9 dip switch should be off position
2. In general, above 1000ppm is regarded
as pollution
☞ ERV is automatically operated to give fresh air into room by sensing CO 2 Level
Fan Speed depending on Co2 density
□ CO2 1200ppm ↑ : Turbo RPM
□ CO2 Density 800ppm ↑ : High RPM
□ CO2 Density 800ppm ↓ : Low RPM
27
Humidification
Humidification
Comparison of Humidifier kit
D Company
Samsung
Method
Vaporizing(Evaporating)
(Indirect water supply)
Vaporizing(Evaporating)
(Direct water supply)
Material
PET
(Poly Ethylene Terephthalate)
Ceramic
Image
Need to clean
It is possible that dust can stick the material
Cleanliness
during airflow and bacteria can breed in
drain pan
Life
Relatively Short
Possibility of corrosion and contamination is
higher than Inorganic material
as compared with mineral material
Don’t need to clean
because Self-Cleaning
Relatively Long
Because ceramic itself is inorganic
material, possibility of corrosion
and contamination is relatively low
29
Humidification
Components of Humidifier kit (Option )
Humidifier kit
RHF050KHEA
RHF100KHEA
Model
MVO-VA050100
MVO-VA100100
Pressure regulation valve
Solenoid valve
Strainer (1/2 Inch)
Humidifier element
Bracket
Water feed pipe
Connecting hose
Connecting hose
Regular
flow rate
RHF050KHEA
RHF100KHEA
0.2 L/min
0.4 L/min
30
Humidification
Humidifier kit assembling
K4 switch in PCB : Off position
Water spray hose
<Floating switch installation>
<Connection of hose>
<Connection wiring of float switch and solenoid valve>
<Installation of water feed pipe>
<Insulation>
31
Humidification
Maintenance of humidifier kit
 Intake air temperature : 0 ~ 40 ℃
 Supply water temperature : 2 ~ 40 ℃
 Supply water pressure : 0.08 ~ 0.7 Mpa
 Use soft water
 Use neutral detergent for cleaning
32
PCB
ERV Plus
• PCB
Test run button
IR sensor
Operation/Error
output
EEV
EA motor
Main address
RMC address
SW debugging
External damper
Room temp.
EVA in/out temp.
CO2 sensor
SA motor
(250VAC, 0.5A)
Inductor
Main power input
EA temp.
OA temp.
Humidifier
Option switch
Software upgrade
Float switch
MPI
Damper feedback
Internal damper
Comm. with outdoor unit (F1-F2)
Power supply to wired R/C (V1-V2)
Comm. with wired R/C (F3-F4)
Humidity control
Hood contact
External control
34
ERV Plus
• Power/Communication wiring
ERV
ERV
ERV
SAFE!
L
L
N
F1
F2
L
N
F1
F2
N
F1
ERV Plus
F2
EHP
ERV Plus
L
L
N
F1
F2
L
N
F1
F2
N
F1
F2
35
ERV Plus
• Push button
Operation
PUSH
When humidifier is used
(K4=ON)
Power LED
230VAC output to open the
humidifier valve.
The LED lamp blinks one
time
Damper operation
* Opens and closes one time.
* Keep the humidifier valve opened
The LED lamp blinks two
times.
Supply / Exhaust FAN operation
* Turbo breeze is generated
Supply / Exhaust Fan operation
* Turbo breeze is generated
* Keep the humidifier valve opened
The LED lamp blinks
three times.
Exit test run
Cancel the trial operation
No 230VAC output to close
the humidifier valve.
Return to the normal
state.
1st
No operation
2nd
Damper operation
* Opens and closes one time
3rd
4th
When humidifier is not used
(K4=OFF)
36
ERV Plus
• Option switch
SW No.
Function
ON
OFF
K1
Remote sensor
No use
Use
K2
Central control
No use
Use
K3
-
-
-
K4
Humidifier
No use
Use
K5
Heating temperature compensation
2℃
5℃
K6
Filter time
1000 hours
2000 hours
-
-
K7, K8
-
K9
EEV stop step in heating
160
35/160
K10
Priority of display on wired R/C
Low
High
K11
External control
No use
Use
K12
State output
Output during operation
Output during thermo-on
-
-
K13, K14
-
K15
External damper
No use
Use
K16
MPI
No use
Use
K17
CO2 sensor
No use
Use
K18
Special EEV control skip in heating
No use
Use
K19
Clean-up
K20
-
Exhaustion air RPM fixed to
RPM in Quiet mode
-
Supply air RPM fixed to RPM in
Quiet mode
-
37
ERV Plus
• Error code
Error code
Detail
E101
No communication between indoor unit and outdoor unit
(The indoor unit itself does not receive any communication signal from the outdoor unit)
E102
Communication error(s) occurred in other indoor unit(s).
(The indoor unit itself succeeded communicating with the outdoor unit)
E122
EVA-IN sensor error (open/short)
E123
EVA-OUT sensor error (open/short)
E128
EVA-IN sensor separated from the pipe
E129
EVA-OUT sensor separated from the pipe
E151
EEV opened
E152
EEV closed
E161
Mixed mode operation
E174
Heat exchanger suction air sensor(open/short)
E201
Communication error between outdoor unit and indoor unit(s) due to the mismatching of the
set number and installed number during tracking
E121
Indoor temperature sensor error (open/short)
E221
Outdoor temperature sensor error (open/short)
38
ERV Plus
• Error code
Error code
Detail
E139
CO2 sensor error (detached or no feedback)
E162
EEPROM error (read/write failure)
E163
EEPROM option setting error (wrong option code setting)
E186
MPI Error (detached or no feedback)
E561
Supply Air fan motor error (RPM less than 120 for 40 seconds)
E562
Exhaust Air fan motor error
E654
Damper error (When there is no feedback for 100 seconds after damper drive output)
E490
No operation due to low outdoor temperature
(Outdoor temp. < 0 ℃ and heat-EX suction air temp. < 0 ℃)
39
ERV Plus
• Connection with wired remote controller
F4
F3
V2
V1
F4
F4
F3
F3
V2 V1
V1
V2
MWTR-WE10
Wire specifications : 4-wire 0.75 ~ 1.5mm2 VCTF or equivalent
Wiring length : max. 100m
40
ERV Plus
• Energy saving operation – EHP-ERV combined
: The operation of an ERV-combined indoor unit is not interfered by energy saving operation, but performs
temperature control as it usually does.
ERV Plus
MWR-WE10
EHP
F3-F4
EHP
ERV Plus
When the E.Saver button is pressed
ON
- ERV : current operation mode  Energy saving operation
- EHP : No change in operation
- ERV controlled by room temperature (sensed by EHP or wired R/C),
set temperature and indoor temperature (sensed by ERV)
ON
(no Fan mode)
OFF
- ERV : OFF  energy saving operation
- EHP : No change in operation
- ERV controlled by room temperature (sensed by EHP or wired R/C),
set temperature and indoor temperature (sensed by ERV)
OFF
ON
- ERV : current operation mode  Energy saving operation
- EHP : No change in operation
OFF
OFF
- No energy saving operation
ON
(no Fan mode)
41
ERV Plus
• Energy saving operation – ERV only
ERV Plus
MWR-WE10
LOW
MEDIUM
HIGH
F3-F4
TURBO
ERV Plus
When the E.Saver button is pressed
ON
- Operated in Heat Exchange, LOW fan speed with repeating sequence of 30-minute operation
and 30-minute stop
OFF
- No Energy Saving operation
- “Restricted” displayed on wired R/C
User
command
ERV
operation
Energy Saving mode
By-Pass mode by MWR-WE10
HIGH fan speed
Heat Exchange
LOW fan speed
By-Pass
HIGH fan speed
Energy saving mode
30 minutes
OFF
Heat Exchange
LOW fan speed
By-Pass mode
30 minutes
42
ERV Plus
- Operation/Error state output
: ERV operation/error state output enabled by option setting (K12=OFF)
ERV Plus error
12VDC, 500mA
Comp. operation
12VDC, 500mA
4-wire cable of MIM-B14
ERV Plus error  voltage-free contact open
Rating : 250ADC, 3A
ERV Plus ON  voltage-free contact closed
Rating : 250VAC, 3A
MIM-B14
환기 ON or DX-coil ON ???
43
ERV Plus
- External control
- ERV ON/OFF control by external contact switch (enabled by option setting K11=OFF)
- Add the 6th digit of the option code by 8 to switch to OFF-only control mode
Option code
External
control
Kitchen hood
control
Humidifier
control
Model
ON/OFF control
OFF-only control
RHF050KHEA
015617-152380-200000-300000
01561F-152380-200000-300000
RHF100KHEA
015617-1C2373-200000-300000
01561F-1C2373-200000-300000
Switch state = ON
Switch state = OFF
ON
OFF
ON/OFF
control
ERV operation
Wired R/C
Able to use
Able to use
OFF-only
control
ERV operation
Unchanged
OFF
Wired R/C
Able to use
Unable to use
External control system
Type : Voltage-free switch
Tating : 5VDC, 5mA
Cable : Unshielded TP 2-wire of 0.75mm2 or greater, VCTF or equivalent
Length : Max. 100 meters
44
ERV Plus
- Kitchen hood control
: No need to set the option switch to enable kitchen hood control
External
control
Kitchen hood
control
Kitchen hood
Humidifier
control
Cable : Unshielded TP 2-wire,
0.75mm2 or greater,
VCTF or equivalent
Length : Max. 100 meters
Type : Voltage-free switch
Rating : 5VDC, 5mA
- Kitchen hood mode - SA RPM : Turbo, EA RPM : Mid
Kitchen hood switch
ON (closed)
OFF (open)
ERV operation
Wired R/C
Normal  Kitchen hood mode
“Hood” displayed in normal display
OFF  Kitchen hood mode
“Hood” displayed in OFF
Kitchen hood mode  Normal
“Hood” disappeared
Kitchen hood mode  OFF
“Hood” disappeared
NOTE : The fan speed can be changed by the wired remote controller in kitchen hood mode.
45
ERV Plus
- Humidify control
: Humidity control by humidifier and locally purchased humidity sensor enabled by option setting (K4=OFF)
External
control
Kitchen hood
control
1. Basic operation
Humidifier
control
Samsung
Humidifier
Humidity sensor
(locally purchased)
Cable : Unshielded TP 2-wire, 0.75mm2 or greater,
VCTF or equivalent
Length : Max. 100 meters
a. Humidity control enabled by option setting
b. Humidity control input closed : Humidifier stop
c. Humidity control input open : No change
2. Humidity sensor switch specifications
a. Type : Voltage-free switch
b. Rating : 5VDC, 5mA
3. Operation sequence
a. Humidifier operation by wired remote controller
b. Humidity level increase
c. Humidity sensor switch closed at the set level
d. Humidifier stop
46
ERV Plus
- External damper control
: External damper control or interlocking signal enabled by option setting (K13=OFF)
ERV operation
DAMPER output
ON
230VAC (max. 0.5A)
OFF
No voltage
Direct connection to external load
(load current : below 0.5A)
Relay/Magnet
switch
Connection to external load via relay/magnet
(load current : over 0.5A)
47
ERV Plus
- Internal damper control
: The internal damper is controller by pulse detection sensed by the micro switch and interval between pulses.
1
Four pulses  one rotation
3
2
1
3
2
T1
T2
T3
T1, T2 : short interval, T3 : Long interval
3
By-Pass mode
Heat Exchange mode
1. Internal damper operation start
2. Pulse from switch detected by controller.
3. Damper stop in detection of two short interval pulses
1. Internal damper operation start
2. Pulse from switch detected by controller.
3. Damper stop in detection of one long interval pulse
• Damper error - After the damper starts operating, E654 is displayed when the pulse from the switch is not
detected for 100 seconds.
48
ERV Plus
• CO2 sensor (MOS-C1)
- Pulse width variation depending on CO2 level (pulse period = 1004ms)
2ms
ppm
0ppm
4ms
2000
4ppm
1002ms
2
CO2
sensor
1002
H
L
OK
H
L
NG
H
L
NG
Pulse
width
2ms
2000ppm
- Two minutes after power-on, the CO2 sensor is maintained
at 500RPM as preheating standby
- An error is detected when the pulse from the CO2 sensor is
not generated for 2 minutes.
49
Download