Arthur Miller, CMS, RCT HVACR Training Consultant www.kam-associates.com info@kam-associates.com OUTLINE 1. Air Flow Terminology 2. Classification of Duct Systems 3. Duct Design Methods 4. Fans 5. Ducts 6. Air Flow & Issues with Design of Ducts 7. Filters 8. Conclusion(s) & Solution(s) A ’PRACTICAL APPROACH’ ALONG WITH SOME THEORY 3 ¼ x 12 wall stack Who is Liable? A. The contractor – from design to installation to service B. The filter manufacturer C. The building owner D. Nobody AIR FLOW TERMINOLOGY CFM • Volume or Quantity of air 3 • measured in Ft /min FPM • Velocity of the air • measured in Ft/min STATIC • Resistance to the air flow • measured in inches of water column (“w.c.) Classification of Duct Systems 1. Low Pressure System - up to 2” w.c. 2. Medium Pressure System - up to 6” w.c. 3. High Pressure System - up to 10” w.c. Duct Design Methods 1. Velocity Method 2. Static Regain Method 3. Equal Friction Method Velocity Method 1. Select velocity for main and branch ducts. 2. Determine duct sizes. 3. Determine frictional pressure drops. 4. Select a fan. Static Regain Method 1. Select velocity for main ducts. 2. Velocities are selected so the static pressure at each take-off offsets the pressure loss of the preceding section of ductwork. 3. Select a fan. Equal Friction Method 1. Selection of friction loss. 2. Volume of air is known. 3. Duct is sized based on 1 and 2 above. 4. Select a fan or fan is selected. FANS The ‘HEART’ of the air delivery system Relationship between STATIC and CFM in respect to a FAN Are they A. a direct relationship B. an indirect relationship C. neither CFM STATIC STATIC CFM two configurations of fans 1. AXIAL 2. CENTRIFUGAL First, the Axial Fans Definition? What makes an axial fan an axial fan? ANSWER Discharge Air Flow PARALLEL to shaft of motor/fan (NO change in direction) TYPES 1. tubeaxial 2. vaneaxial 3. propeller TUBEAXIAL 1. operates at pressures up to 16” wc 2. wheel turns faster than propeller fan 3. efficiency up to 65% VANEAXIAL 1. operates at pressures up to 20” wc 2. uses guide vanes to improve efficiency and pressure 3. most energy efficient fan PROPELLER 1. operates at low speeds 2. handles large volumes of air at low pressure and at free delivery 3. efficiency is usually less than 50% Performance of PROPELLOR Fans PROPELLOR FAN What is the LOADING component on a PROPELLOR fan? A. CFM B. FPM C. STATIC STATIC This ‘LOAD’ is then imposed on the motor. respond? How will the motor STATIC AMPS STATIC AMPS APPLICATION(S) (1) The condenser conditioner is on very What will happen to the: fan delivery in cfm? fan motor amp. draw? an air dirty. Fan delivery in cfm Increases Decreases Remains the same Fan delivery in cfm Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same (2) What about a filter on an ice machine condenser? What happen to the: fan delivery in cfm? fan motor amp. draw? will Fan delivery in cfm Increases Decreases Remains the same Fan delivery in cfm Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same (3) Consider a window fan. Is ductwork connected to the fan? 1. YES 2. NO (3) Consider a window fan. Is ductwork connected to the fan? 1. YES 2. NO Now, the Centrifugal Fan Definition? What makes a centrifugal fan a centrifugal fan? ANSWER Discharge Air Flow PERPENDICULAR to shaft of motor/fan Types of Centrifugal Wheels 1. Backward Inclined (BI) 2. Air Foil Wheels (AF) 3. Forward Curve Wheels (FC) 4. Radial Blade Wheel Backward Inclined (BI) Backward Inclined (BI) 1. used with high pressure systems 2. high flow 3. high efficiency 4. noisy Air Foil Wheels (AF) Air Foil Wheels (AF) 1. used with high pressure systems 2. high flow 3. highest efficiency 4. noisy Forward Curve Wheels (FC) Forward Curve Wheels (FC) 1. used with medium pressure systems 2. high flow 3. best for moving large volumes against low static 4. quiet Radial Blade Wheel Radial Blade Wheel 1. used with high pressure systems 2. medium flow 3. best for moving air against high static and contaminated airstreams Performance of CENTRIFUGAL Fans CENTRIFUGAL FAN What is the LOADING component on a CENTRIFUGAL fan? A. CFM B. FPM C. STATIC CFM This ‘LOAD’ is then imposed on the motor. respond? How will the motor CFM AMPS CFM AMPS MOVIE TIME APPLICATION(S) How would following you answer questions CENTRIFUGAL fans? the regarding (1) An addition has been added to a building and the duct system has been added onto include this addition. What will be the: A. fan delivery in cfm? B. fan motor amp. draw? Fan delivery in cfm Increases Decreases Remains the same Fan delivery in cfm Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same (2) As the air filter gets contaminated, what will be the: A. fan delivery in cfm? B. fan motor amp. draw? more Fan delivery in cfm Increases Decreases Remains the same Fan delivery in cfm Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same (3) You remove a supply air panel on a ‘hot’ day just to cool you off. What will be the: A. fan delivery in cfm? B. fan motor amp. draw? Fan delivery in cfm Increases Decreases Remains the same Fan delivery in cfm Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same Fan motor amp. draw Increases Decreases Remains the same ‘CENTRIFUGAL’ FAN PERFORMANCE Fan Performance depends on (1) CFM (2) Outlet Velocity (3) Static Pressure (4) RPM (5) Brake Horsepower Determining Fan CFMs (1) Using a Fan Curve (2) Using a Fan Chart (3) Using a Fan Law (4) Using Instruments (1) Using a Fan Curve Relationship between STATIC and CFM in respect to a fan CFM STATIC STATIC CFM Relationship between STATIC and CFM in respect to the duct system CFM STATIC CFM STATIC 5 HP 3 HP 1 HP Original Operating Point New Operating Point (2) Using a Fan Chart PSC Motor ECM Motor And now, the new kid on the block. Dec Star Movie Using a Fan Law 1. six fan laws 2. HVACR is affected by one of them The physics of air flow dynamics dictates the following: • CFM – varies as the fan speed • Static – varies as the SQUARE of the speed • HP – varies as the CUBE of the speed APPLICATION If we increase the cfm ’ s by 20%, what will be required of the motor speed(rpm)? + 20% If we increase the cfm’s by 20%, what will happen to the static in the system? + 40% If we increase the cfm’s by 20%, what will happen to the horsepower required from the motor? + 80% Using Instruments 1. Anemometer 2. Velometer 3. Manometer with Pitot Tube 4. Balometer So why all the fuss about fans? Because they must deliver a volume of air that satisfies two requirements: a. Equipment Efficiency b. Customer Satisfaction AIR FLOW So how much CFM can you ‘shovel’ into a duct? That takes us to the DUCT CALCULATOR ‘Rule of Thumb’ Design Static Pressures .10 (.08) for SUPPLY AIR duct .08 (.06) for RETURN AIR duct .08 (.06) for HEAT PUMP SUPPLY duct .06 (.04) for HEAT PUMP RETURN duct Furnace Fan External Static Pressure .5” w.c. for the furnace fan, then subtract any external components: ACCA Manual D Component Static Pressure 1. Air conditioner coil = .25”w.c. 2. Filters = .10”w.c. 3. Electric heaters = .10”w.c. to .20”w.c. 4. Humidifiers = .10”w.c. 5. Supply Outlets = .03”w.c. 6. Return Inlets = .03”w.c. 7. Dampers = .03”w.c. Example #1 • Furnace fan = .50”w.c. • less AC coil = - .25”w.c. • less air filter = - .10”w.c. • less supply registers = - .03”w.c. • less return grilles = - .03”w.c. • less dampers = - .03”w.c. • left for duct system = .06”w.c. Example #2 • Furnace fan = .50”w.c. • less AC coil = - .00”w.c. • less air filter = - .10”w.c. • less supply registers = - .03”w.c. • less return grilles = - .03”w.c. • less dampers = - .03”w.c. • left for duct system = .31”w.c. Designing the Duct System Length of duct - measured Fittings - Equivalent Length tables Velocity Factor - Equivalent Length tables Supply and Return Plenums Take-off fittings Velocity Factor EL Values Fitting 0 1 2 3 4 5 or more 35 45 55 65 70 80 20 30 35 40 45 50 65 75 85 95 100 110 Velocity Factor EL Values Fitting 0 1 2 3 4 5 or more 35 45 55 65 70 80 20 30 35 40 45 50 65 75 85 95 100 110 CONCLUSION The equivalent length(EL) of the duct system has a direct relationship to the STATIC FILTERS Filters in relation to the SYSTEM STUDY • ASHRAE • Published October 2012 • by John Proctor, Member ASHRAE P.E. • California Energy Commission field research • Two year old homes • Most common replacement filter used is a 1 in. pleated filter • Air Conditioning Contractors of America’s Manual D • assumes pressure drop through a filter to be approx. 0.10 in. w.c. Field installations showed PD far in excess of 0.10 in. w.c. Static pressures for 34 split AC/furnaces Static pressures for 34 split AC/furnaces Metric Filter PD Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Return PS Total ESP Static pressures for 34 split AC/furnaces Metric Filter PD Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Return PS Total ESP Static pressures for 34 split AC/furnaces Metric Filter PD Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Return PS Total ESP Static pressures for 34 split AC/furnaces Metric Filter PD Mean: in. w.c. 0.282 - 0.417 0.887 Range: in. w.c. 0.275 – 0.792 - 0.143 – - 0.928 0.533 – 1.21 Return PS Total ESP Research results of PD for 53 ducted systems. Filter face area required for 0.05”w.c. PD at 400 cfm/ton for one manufacturer’s line of filters 16 x 25 = 400 2 in Filter face area required for 0.05”w.c. PD at 400 cfm/ton for one manufacturer’s line of filters • The following two charts are tests performed by Kevin O’Neill. • HVAC Service Manager • Carolina Clg. & Plbg. • Surfside Beach, SC Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME PRESSURE DROP (IN. W.C.) AIRFLOW Air flow hood and egg crate filter grille .03 in. 800 cfm Standard fiber glass filter Brand A .075 in. 800 cfm Standard fiber glass filter Brand B .08 in. 800 cfm Very dirty Brand A .15 in. 800 cfm 1 in. thick pleated Brand C - clean .2 in. 800 cfm 1 in. thick pleated Brand D - clean .2 in. 800 cfm Dirty 1 in. thick pleated Brand C @ 1 month .24 in. 800 cfm Dirty 1 in. thick pleated Brand C @ 3 months .32 in. 800 cfm Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME PRESSURE DROP (IN. W.C.) AIRFLOW Air flow hood and egg crate filter grille .03 in. 800 cfm Standard fiber glass filter Brand A .075 in. 800 cfm Standard fiber glass filter Brand B .08 in. 800 cfm Very dirty Brand A .15 in. 800 cfm 1 in. thick pleated Brand C - clean .2 in. 800 cfm 1 in. thick pleated Brand D - clean .2 in. 800 cfm Dirty 1 in. thick pleated Brand C @ 1 month .24 in. 800 cfm Dirty 1 in. thick pleated Brand C @ 3 months .32 in. 800 cfm Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME PRESSURE DROP (IN. W.C.) AIRFLOW Electrostatic filter Brand E .125 in. 800 cfm Electrostatic filter Brand F .14 in. 800 cfm Electrostatic filter Brand G .29 in. 800 cfm Electrostatic filter Brand H .35 in. 800 cfm Combination electronic, charcoal & fiber .18 in. glass - clean 800 cfm Same filter after 1 month of use .34 in. 800 cfm Same filter after 3 months of use .45 in. 800 cfm Filter Pressure Drop Table 20 in. x 20 in. x 1 in. – clean except as noted FILTER NAME PRESSURE DROP (IN. W.C.) AIRFLOW Electrostatic filter Brand E .125 in. 800 cfm Electrostatic filter Brand F .14 in. 800 cfm Electrostatic filter Brand G .29 in. 800 cfm Electrostatic filter Brand H .35 in. 800 cfm Combination electronic, charcoal & fiber .18 in. glass - clean 800 cfm Same filter after 1 month of use .34 in. 800 cfm Same filter after 3 months of use .45 in. 800 cfm CONCLUSION every system has air flow issues CONCLUSION Unfortunately there will always be those who: 1. will not keep up with technology. 2. have always done it this way. 3. don’t need to know that. 4. will do it the least expensive way. SOLUTIONS All designers of air flow systems need to check the manufacturer’s specs. of equipment designing a system. before SOLUTIONS Filters may be a point of interest for poor performance equipment and comfort. of SOLUTIONS The consumer is getting smarter about our industry and making demands on us. SOLUTIONS Professionalism has to be promoted inside and outside the industry. SOLUTIONS Continuing Education