Enhancing Sustainability Advantages of pressure independent control valves; basic commissioning of Belimo PI valves. © Belimo University 2011, All Rights Reserved Enhancing Sustainability First, an analogy between air systems and hydronic systems. Why are there no more VAV pressure dependent air systems? Enhancing Sustainability Pressure Dependent VVT System Air Handling Unit Supply Duct How many Pressure Dependent VVT systems have you seen lately? Return Duct Bypass Duct Balancing Damper VVT Boxes Space Temp Enhancing Sustainability Pressure Dependent VVT System Air Handling Unit Part Load Performance: •Unable to respond to flow variation due Supply to changing pressure conditions. Return Duct Duct •Unstable control – system is Bypass Duct “oversized”. •Occupant comfort and energy Balancing Damper efficiency are compromised. VVT Boxes •Spaces too cold (or hot). Space Temp Enhancing Sustainability Pressure Independent VAV Box Air Flow Temp. Control Air Flow Measurement Device Controller Controller Part Load Performance: Pressure Independent Control Valve From Temp. Control •Flow is controlled under all pressure conditions. •Stable control – system is “rightsized”. Water Flow Measurement Device •Occupant comfort and energy efficiency are improved. Water Flow •Spaces at or near design. Pressure Independent Control Valve What is a pressure independent control valve? A PI Control Valve…. Is a 2-way control valve that supplies a precise flow at any given control signal… Regardless of pressure variations in a system. It is not just a control valve and flow limiting circuit setter in the same assembly! Note: Automatic or manual balance valves should NOT be used with PI valves. If they are already installed they should be set WIDE OPEN. Pressure Dependent Control Valve Flow rate through equal % globe valve as a function of differential pressure (Cv = 1.9). Pressure Independent Control Valve Flow rate through PI Control Valve as a function of differential pressure (3 GPM valve plotted). Equal % characteristic. Equal % Valve Characteristic 100 Resulting Energy Output of Coil Coil Energy Output (%) Energy Characteristic of Coil 90 80 70 60 50 Flow Characteristic of Equal % Control Valve 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 Signal (%) ASHRAE 2008 HVAC Systems and Equipment Handbook pg. 46.8 Advantages •Iowa Energy Center Pressure Independent Valves Study •Chilled Water Closed Loop Test PICCV Valve Water Flow SAT Setpoint Change Globe Valve Water Flow The Pressure Dependent Valve loses authority at part load. In effect, it becomes “Oversized” Advantages Energy saving potential Globe Valve PI Control Valve Advantages Energy saving potential Totalized Flow over 24 Hrs Globe Valve = 358.7 gallons PI Control Valve = 283.6 gallons Note: The over-flow and under-flow cycling of this control valve results in a net over-flow condition! Advantages Energy saving potential Pump Affinity Laws Globe Valve PI Control Valve HP = Horse Power GPM = Flow in Gallons/Minute HP1 GPM 1 HP2 GPM 2 3 3 HP 1 358.7 2.02 HP 2 283.6 Globe = 358.7 gallons PI Control Valve = 283.6 gallons A 26.5% increase in flow results in twice the horsepower requirements from the pump. Pressure Differential Sensor Setpoint = 10 psid Design: 400 Ton / 800 GPM CHW System @ 12˚ΔT Coil #4 0 - 200 gpm 2 psid 10ft H2O (4 psid) 10 psid 4 psid Coil #3 0 - 200 gpm 12 psid 10ft H2O (4 psid) 20 psid 4 psid Coil #2 0 - 200 gpm 22 psid 10ft H2O (4 psid) 30 psid 4 psid Coil #1 0 - 200 gpm 32 psid 10ft H2O (4 psid) Chiller VFD-Pump 200 tons Chiller VFD-Pump 200 tons Pressure Dependent Control Valves 40 psid 4 psid Advantages Energy saving potential Tons 24 GPM T Tons 24 800 GPM 12T 800 GPM Tons 2 800 GPM Tons 2 Tons 400 For a given load, flow and ΔT are inversely proportionate. As flow increases, ΔT drops. Pressure Differential Sensor Design: 400 Ton CHW System @ 12˚ΔT Coil #4 0 - 200 gpm Coil #3 0 - 200 gpm Coil #2 0 - 200 gpm Coil #1 0 - 200 gpm Chiller VFD-Pump 200 tons Chiller VFD-Pump 200 tons Pressure Dependent Control Valves Advantages 180 Ton Load (45%) Design: 400 Ton CHW System @ 12˚ΔT Coil #4 0 - 200 gpm •Hold the load constant and vary the flow. Pressure Dependent Control Valves Coil #3 0 - 200 gpm Coil #2 0 - 200 gpm Coil #1 0 - 200 gpm 42˚ CHWS 360 GPM Loop Flow 54˚ CHWR (12˚ΔT) Advantages Design: 400 Ton CHW System @ 12˚ΔT Pressure Dependent Control Valves 180 Ton Load (45%) Coil #4 0 - 200 gpm Coil #3 0 - 200 gpm Coil #2 0 - 200 gpm Coil #1 0 - 200 gpm 42˚ CHWS 52.9˚ CHWR 396 GPM Loop Flow (+10%) (10.9˚ΔT) Advantages Design: 400 Ton CHW System @ 12˚ΔT Pressure Dependent Control Valves 180 Ton Load (45%) Coil #4 0 - 200 gpm An increase in flow results in: Coil #3 0 - 200 gpm •Lower return temperature. •Reduced ΔT. Coil #2 0 - 200 gpm •Increased pumping power. Coil #1 0 - 200 gpm 42˚ CHWS 52.4˚ CHWR 414 GPM Loop Flow (+15%) (10.4˚ΔT) Design: 400 Ton CHW System @ 12˚ΔT Pressure Differential Sensor Coil #4 0 - 200 gpm Pressure Dependent Control Valves Coil #3 0 - 200 gpm Coil #2 0 - 200 gpm Coil #1 0 - 200 gpm With a 10% overflow ΔT Reduction goes From 12°F (Design) To 10.9°F (Actual) A reduction of 9%. Chiller 200 tons Chiller 200 tons With a 15% overflow ΔT Reduction goes From 12°F (Design) To 10.4°F (Actual) A reduction of 13%. Advantages Design: 400 Ton CHW System @ 12˚ΔT Pressure Dependent Control Valves 180 Ton Load (45%) 360 GPM Loop Flow CHWR CHWS 54˚ 42˚ (12˚ΔT) Chiller 200 tons VFD-Pump Arbitrary Value KW=1.0k 90% Load Chiller VFD-Pump 200 tons •Hold the load constant and vary the flow. Advantages Pressure Dependent Control Valves 180 Ton Load (45%) 396 GPM Loop Flow (+10%) CHWR CHWS 52.9˚ (10.9˚ΔT) 42˚ Chiller VFD-Pump 200 tons KW=1.33k 90% Load (396GPM/360GPM)3 = 1.33 (33% increase in pump power!) Chiller VFD-Pump 200 tons An increase in flow results in: •Lower return temperature. •Reduced ΔT. •Increased pumping power. Advantages Design: 400 Ton CHW System @ 12˚ΔT 180 Ton Load (45%) 414 GPM Loop Flow (+15%) Pressure Dependent Control Valves CHWR CHWS 52.4˚ (10.4˚ΔT) 42˚ Chiller 200 tons VFD-Pump (414GPM/360GPM)3 = 1.52 (52% increase in pump power!) KW=0.76k 45% Load Chiller 200 tons VFD-Pump KW=0.76k An additional pump and chiller were started to meet the flow demand, not cooling demand! 45% Load Also, a chiller receiving cold return water can’t load up! Belimo PI Valves Two Solutions for Today’s Hydronic Systems PICCV ePIV ½” – 2” 2 ½” – 6” 0.5 GPM – 100 GPM 105 GPM – 713 GPM Belimo Pressure Independent Valves Commissioning PICCV ePIV (Equal %) (Equal % or Linear; factory or field selectable) Belimo PI Valves PICCV Water passes through regulator Pressure is P2 (intermediate) Water exits valve Pressure is P3 (low) Water enters valve Pressure is P1 (high) Ports sense pressure drop and transfer it below regulator Low pressure pulls regulator down, against the spring force PICCV Process Flow Diagram Non-Spring Return Spring Return DDC Controls Valve Position Feedback (2-10 vdc (default)/vdc Variable) AI AO AO AI Control Signal (2-10 vdc (default)/vdc Variable) Min/Max actuator stroke % programming per application design flow. Note: Selection is made with PC Tool and ZTHGEN/ZTH-PICCV. Belimo MFT Actuator PICCV Valve Stem and Coupler Internal Mechanical ΔP Regulator P3 Equal % Characterized Ball Valve P2 Process Piping Process Piping Note: Shown for functional purposes only. Ancilliary piping, mechanical regulator and ball valve are machined into common valve body. Belimo ePIV •Magnetic Flow Sensor •Flow Feedback and •Control Signal •Smart Actuator •LGCCV Valve Magnetic Flow Sensor • Measures changes to the induced voltage of a conductive fluid through a controlled magnetic field. • No moving parts or openings to clog or jam. • No maintenance. Actuator/Flow Tolerances Controller starts to control if delta "flow actual value" and "flow set value" > 5% (50% of the Flow tolerance) Controller stops to control if delta "flow actual value" and "flow set value" < 1% (10% of the Flow tolerance) Flow Accuracy +/- 6% of Vnom Example Control Signal Y = 100GPM (stable no changes) If the measured Flow is higher then 105GPM Actuator will correct until measured Flow is 101GPM. If the measured Flow is lower then 95GPM Actuator will correct until measured Flow is 99GPM. ePIV Process Flow/ Logic Diagram DDC Controls Flow Feedback (2-10 vdc (default)/vdc Variable) AI AO AO AI ePIV Control Signal (2-10 vdc (default)/vdc Variable) Signal Conditioning (Linear or Equal % Scaling) Selectable Flow Feedback Note: Selection is made with PC Tool v3.5 and higher and ZTH-GEN. (Release code required) Flow Setpoint Internal Control Algorithm (PV=Input from Flow Sensor) Velocity to Flow Conversion (SP=Flow Setpoint from DDC) (PV) (CV) (CV=Output to Actuator for Valve Positioning) (FB=Flow Feedback to DDC) Actuator (Integral to ePIV Controller) Closed Loop Control 4-20 milliamp Valve Stem and Coupler Magnetic Flow Sensor (External to ePIV Controller) Process Piping LG-CCV Process Piping Installation Considerations • 5 straight pipe diameters before the flow sensor • no straight pipe requirement on the outlet of the valve STRAIGHT INLET LENGTHS •2-1/2” ePIV = 12.5” 4” ePIV = 20” •3” ePIV = 15” 5” ePIV = 25 6” ePIV = 30” Installation Considerations Actuator must be kept above horizontal! Introducing – the ePIV electronic Pressure Independent Valve • Cost effective flow sensor technology combined with Belimo’s industry leading intelligent actuators and proven characterized valve technology • Both non-spring and electronic fail-safe proportional models • Provides all the benefits of PI valves (accurate flow control, improved efficiency at part load by reduced pumping power, improved waterside ΔT) • Reduced cost, less weight, less raw materials, more sustainable! • True flow measurement, available to DDC system through feedback wire • Glycol concentration up 50% has no effect on flow measurement • Can be configured for either linear or equal percentage flow characteristic with a simple program change. Belimo Field Programming Tool Field adjustable programming tool allows: •PICCV •Control/feedback signal ZTH-GEN •Custom flows/adjust flows •Many other parameter adjustments • ePIV •Control/feedback signal •Custom flows/bias adjustment •Flow coefficient No external power needed; no battery; powered by actuator 24 vac! Just plug it into actuator. •Equal % or linear setting •Many other parameter adjustments Belimo PC Tool ePIV adjustments (PC Tool v3.5 and above) • Control/Feedback Signal Voltage – 2-10 VDC – 0-10 VDC – User selected • Flow Characteristic* – Equal Percentage – Linear • Maximum (Design) Flow • Bias Adjustment Commissioning Additional P/T PORT for verification of 5 psi (11.5 ft H20) minimum differential across the PI Valve. Minimum ΔP across valve must be verified with PI valve COMMANDED by DDC (or by programming tool) to design flow, not manually positioned! Commissioning Step 1: Ensure all strainers are clean and bypass valves are closed. Step 2: Command via DDC all PI valves to design flow. (Diversity assumed at 100%.) Step 3: Set distribution pump(s) to elevated speed by commanding ΔP setpoint or pump speed directly. Step 4: Find the “critical zone” (ie. the PI valve that has the least ΔP). Step 5: Increase or decrease pump speed/ΔP setpoint until critical zone has just over 5 psid (11.5 ft H20). The resulting ΔP at the system sensor will be the optimum system ΔP setpoint. Step 6: Verify total system flow is at design at main flow station (or by other method). Step 7: If flow is not within +/- 10% of design, start checking valves at terminal level, starting with largest valve(s) first (voltage, control signal, strainer, etc.) Commissioning • Belimo PI valves do NOT require that the entire system be placed in full design flow. Each PI valve flow can be verified individually with the rest of the system under normal control. 1) Command valve assembly to design. 2) Verify at least 5 psid across PI valve assembly. 3) Verify coil flow as per usual method (coil ΔP method, etc.) Link for PI valve commissioning document: www.piccv.com/pdf/PICCV_Application_Bulletin.pdf Questions?