The FG series of explosive and toxic gas detectors and panels • State of the art technology • Full ATEX approvals • Comprehensive range Gas detectors for all applications • Residential • Non classified commercial • Potentially explosive zone 2 Eex-n • Potentially explosive zone 1 & 2 Eex-d Gas control panels • Conventional 4 – 8 detector • Addressable RS485 bus up to 200 detectors, 132 outputs On site maintenance • Handheld Calibration kit >Plug-in and infrared >Connect to test gas Gas panel expansion boards • Addressable, 8 way, 4 – 20 mA input boards • Addressable, 16 way, open collector output boards Choice of detector output • 4 – 20 mA into a gas control panel or other equipment • Optional 3 way relay board for fault and alarm to connect direct to fire panels Choosing the right product • By the approval requirement or environment • By the gas to be detected By the approval requirement or environment • Residential – no ATEX classification • Dust proof IP44 – non classified commercial and industrial areas – no ATEX • Potentially explosive zone 2 – ATEX Eex-n • Potentially explosive zone 1 and 2 – ATEX Eex-d By the approval requirement or environment Residential – no ATEX classification > Methane, LPG or CO > 12 / 24 Vdc or 230 Vac > Type codes FGE212/230 ME,LP FGT212/230 CO By the approval requirement or environment Non classified commercial and industrial areas – no ATEX > Petrol vapour or CO > Type codes FGE90VB FGT90CO By the approval requirement or environment Potentially explosive zone 2 – ATEX Eex-n > Methane, Petrol vapour, LPG and CO > Type codes FGE110 ME,VB,LP FGT110 CO By the approval requirement or environment Potentially explosive zone 1 or 2 – ATEX Eex-d > Methane, Hydrogen, LPG or CO > Type codes FGE150/170 ME,LP,H2 FGT150/170CO Detector standard features FGE/FGT200 Residential •Professional catalytic / electrochemical sensor •12/24 or 230V operation •Microprocessor operation •Watchdog monitoring with open collector output •Auto zeroing •Test pushbutton •Built-in buzzer •Alarm relay Detector standard features FGE/FGT90 IP44 •Professional catalytic / electrochemical sensor •12/24 operation •Cost effective for non-classified areas •IP44 •4-20 mA output Detector standard features FGE/FGT 110 ATEX Eex-n •Professional catalytic / electrochemical sensor •12/24 Vdc •Microprocessor operation •Watchdog and self diagnostic features •Auto zeroing •Drift compensation •Digital filter •4-20mA or optional 3 relay board Detector standard features FGE/FGT 150 ATEX Eex-d •Professional catalytic / electrochemical sensor •12/24 Vdc •Microprocessor operation •Watchdog and self diagnostic features •Auto zeroing •Drift compensation •Digital filter •4-20mA or optional 3 relay board Control panel standard features FGC108 4 – 8 input gas panel •4-20mA inputs •Microprocessor based •4 input, expandable to 8 (FGC104E) •Backlit LCD, 2x16 characters •Precise indication of gas concentration •Three alarm thresholds per detector •Five output relays •16 open collector outputs available on FGC104E •Built-in battery charger Control panel standard features FGC1100 8-104 input, 4-68 output •4-20mA inputs •Microprocessor based •Multiscan RS485 addressable bus •Backlit LCD, 256 x 64 pixel graphic LCD display •Programmable alarm thresholds per detector •Three alarm thresholds per detector •Powerful configuration software standard •RS232 and Centronics parallel port for data logging and graphics – SIA protocol •Built-in 3.5 Amp power supply Control panel standard features FGC1200 8-200 input, 4-132 output •4-20mA inputs •Microprocessor based •2 x Multiscan RS485 addressable bus •Backlit LCD, 256 x 64 pixel graphic LCD display •Programmable alarm thresholds per detector •Three alarm thresholds per detector •Powerful configuration software standard •RS232 and Centronics parallel port for data logging and graphics – SIA protocol •Built-in 3.5 Amp power supply Control panel accessories Expansion boards FGC104E Adds 4 inputs and 16 open collector outputs to the FGC108 gas panel FGC1208I Addressable RS485 module adds 8 detector inputs to the FGC1100/1200 FGC1216O Addressable RS485 module adds 16 open collector outputs to the FGC1100/1200 Training •A comprehensive tutorial is available > All you ever needed to know about gas > All you ever needed to know about ATEX •Technical support training available from Brussels End of presentation