Schneider Electric Pre Fabricated Modular Data
Center Overview & Discussion
Schneider Electric - Division - Name – Date
1
Schneider Electric is the Global Leader in
Pre Fabricated Modular Solutions
In January 2014 Schneider Electric acquired AST Modular the global leader in pre fabricated modular and containerized and modular Data Centers
AST leads the pre-fabricated Modular Data Center Market (>20% market share)
Over 600 Data Center projects successfully executed to date
Projects deployed in over 50 countries
First company to build a Tier 3 multi-Container Data Center
Pioneered the manufacturing of high quality purpose built containerized data centers (2001)
AST customers include IT leaders including IBM, HP, Dell, and Silicon Graphics
Schneider Electric - Division - Name – Date
2
Schneider Has Deep Experience in Delivering
Pre Fabricated Solutions
Schneider Electric - Division - Name – Date
3
Schneider Electric - Division - Name – Date
4
20 ’ & 40’ ISO
-All in one containers
-Multi container parks
25 ’ & 45’ NON ISO
-All in one modules
-Contiguous IT rooms
Secure IT rooms
-Indoor & Out Door
-Secure and any size
Schneider Electric - Division - Name – Date
5
AST IT Modules
Compact ISO All-in-One
(20ft Enclosure,7Racks, UPS, PDU,
Overhead DX Cooling,
Standard ISO All-in-One
(40ft Enclosure, up to 19 racks,
PDU, overhead DX cooling
Ruggedized Solutions for
Industrial
(40ft Enclosure, up to 19 racks,
PDU, overhead DX cooling,
Ruggedized versions available
Multi-Bay IT Modules
(25ft – 40ft enclosure, Non-ISO design for more space. Cooling options - In-Row CW Perimeter CW,
Air Economizer Cooling, DCIM)
Modular Room
(20 x 45ft Enclosure,24 Racks, PDU,
3 Perimeter CRACs CW cooling,
DCIM)
Schneider Electric - Division - Name – Date
6
Overview
Non-ISO design is wider, taller, deeper than container and engineered to provide a spacious, functional workspace for IT personnel
Efficient, scalable design allows for custom, multi-module configurations from 20
– 240 racks
Multiple cooling solutions for chilled water, DX and air economization (In-row, Perimeter, End-of-
Row)
Robust frame design simplifies installation and ganging together
Best option for a complete configurable space.
Schneider Electric
Walk Through Our Demo Module Outside
- Division - Name – Date
7 7
IT Rooms are joined together to form an “open white space”
IT room
Schneider Electric - Division - Name – Date
8
IT Room Modules
90kW All-in-One
(40ft Enclosure,10 Racks, UPS, PDU, In-
Row DX Cooling, DCIM)
110kW Single Module
(40ft Enclosure, 10 racks, PDU, In-Row
CW cooling, DCIM)
205kW Single
Module
(53ft Enclosure,14 racks, PDU, In-Row CW cooling, DCIM)
240kW Dual Module
(20 x 45ft Enclosure 22 Racks, PDU, In-
Row CW cooling, DCIM)
240kW Dual Module
(20 x 45ft Enclosure,24 Racks, PDU, 3
Perimeter CRACs CW cooling, DCIM)
Schneider Electric - Division - Name – Date
9
Schneider Electric offers scalable, easy-to-deploy,
90 kW All in One Pre Fabricated Data Center (Non ISO)
Direct Expansion
Condenser Units
Schneider Electric - Division - Name – Date
Symmetra PX
100 kW UPS
9 Server Racks;
1 Networking
Rack
10
Input Power Voltage (Nominal) 480V AC; 3 Phase; 60 Hz
Max. Input Current 273A
Power Distribution
Total IT Load
90kW at N+1
(10 racks at 9 kW per Rack)
86 kW (Not Supported by UPS) Cooling Power Requirement
Non-Critical Power 9kW
Nominal Output Voltage to Rack 208V 3PH with Overload Protection
Main Distribution
Rack Distribution
AP8868 Metered, 10kW, 208V, 16A (20)
(36) C13 & (6) C19 - (2 per rack)
UPS and Battery System
UPS
Battery Type
Estimated Runtime
Symmetra PX 100kW, 208V at N+1
Double Conversion online
VRLA – Long Life Battery Modules (10)
5mins @ Full Load
Cooling
ACCD75204 Direct Expansion
Type,
Number of Units
Cooling Capacity
Internal Operating Humidity 10% - 95%
Internal Operating Temperature 60 ° F to 80° F (15.6° C to 26.7° C)
Racks
2 ACRD501 InRow Cooling Units
2 ACRP101 InRow Cooling Units
107 kW n+1
Rack Qty, Size and Type
Hot aisle
Cold aisle
Air blocking
Management System and Safety
9 - AR3300 - 42U x 600 mm (w) x 1200 mm (d)
1 - AR3350 - 42U x 750 mm (w) x 1200 mm (d)
36" w x 34' 0" l (922 mm x 10445 mm)
45" w x 34' 0" l (1152 mm x 10445 mm)
2 Interior Doors
StruxureWare Data Center Expert
Environmental Monitoring
Interface that monitors, manages and controls devices that provide power, cooling, security and environmental data.
Cooling Unit Temp Sensors: AP9335T (Qty 20);
Temp and Humidity Probes: AP9335TH (Qty 4);
Door Monitors NBE50302 (Qty 3);
Entrance/Staging
Lobby and
Electrical Room
Modular Power
Distribution
4 InRow
Cooling Units
FM-200 clean agent system with smoke/heat detection, auto/manual actuation, and audible/strobe alarms.
3 Exits
Fire Suppression,
Alarms, Controls
Fire Suppression and Detection
Emergency Exits
Physical
Length
Width
Height
Weight (Estimated)
Entrance Lobby for
Environmental Separation
Stacking
Environmental (external)
Operating Min/Max Temp.
Seismic and Wind Loading
Operating Altitude
12.3 m (40' 0")
3.5 m (11' 6")
3 m (10' 0")
Loaded: 47,122 lbs. (21,419 kg) (Typical)
1,103 lbs/m
2
(500 kg/m
2
)
4' 11" (1.5 m) w x 10' 9" (3.28 m) l
Optional
-20 ° to 50°C
Site Specific
0 – 1000m
Schneider Electric offers scalable, easy-to-deploy,
Prefabricated Data Center Modules.
Direct Expansion
Condenser Units
Symmetra PX
100 kW UPS
9 Server Racks;
1 Networking
Rack
Input Power Voltage (Nominal)
Max. Input Current
Power Distribution
480V AC; 3 Phase; 60 Hz
273A
Total IT Load
Cooling Power Requirement
90kW at N+1
(10 racks at 9 kW per Rack)
86 kW (Not Supported by UPS)
Non-Critical Power 9kW
Nominal Output Voltage to Rack 208V 3PH with Overload Protection
Main Distribution
Rack Distribution
AP8868 Metered, 10kW, 208V, 16A (20)
(36) C13 & (6) C19 - (2 per rack)
UPS and Battery System
UPS
Battery Type
Estimated Runtime
Cooling
Symmetra PX 100kW, 208V at N+1
Double Conversion online
VRLA
– Long Life Battery Modules (10)
5mins @ Full Load
ACCD75204 Direct Expansion
Type,
Number of Units
Cooling Capacity
Internal Operating Humidity 10% - 95%
Internal Operating Temperature 60 ° F to 80° F (15.6° C to 26.7° C)
Racks
2 ACRD501 InRow Cooling Units
2 ACRP101 InRow Cooling Units
107 kW n+1
Rack Qty, Size and Type
Hot aisle
Cold aisle
Air blocking
Management System and Safety
9 - AR3300 - 42U x 600 mm (w) x 1200 mm (d)
1 - AR3350 - 42U x 750 mm (w) x 1200 mm (d)
36" w x 34' 0" l (922 mm x 10445 mm)
45" w x 34' 0" l (1152 mm x 10445 mm)
2 Interior Doors
StruxureWare Data Center Expert
Environmental Monitoring
Interface that monitors, manages and controls devices that provide power, cooling, security and environmental data.
Cooling Unit Temp Sensors: AP9335T (Qty 20);
Temp and Humidity Probes: AP9335TH (Qty 4);
Door Monitors NBE50302 (Qty 3);
Entrance/Staging
Lobby and
Electrical Room
Modular Power
Distribution
4 InRow
Cooling Units
FM-200 clean agent system with smoke/heat detection, auto/manual actuation, and audible/strobe alarms.
3 Exits
Schneider Electric - Division - Name – Date
Fire Suppression,
Alarms, Controls
11
Fire Suppression and Detection
Emergency Exits
Physical
Length
Width
Height
Weight (Estimated)
Entrance Lobby for
Environmental Separation
Stacking
Environmental (external)
Operating Min/Max Temp.
Seismic and Wind Loading
Operating Altitude
12.3 m (40' 0")
3.5 m (11' 6")
3 m (10' 0")
Loaded: 47,122 lbs. (21,419 kg) (Typical)
1,103 lbs/m
2
(500 kg/m
2
)
4' 11" (1.5 m) w x 10' 9" (3.28 m) l
Optional
-20 ° to 50°C
Site Specific
0 – 1000m
NAM 90 kW All-in-One IT Module – PFMIED090D1N10A
2 bay, 24 Rack In-Row, 240kW shown
240kW cooling capacity
415V distribution @11kW per rack (2N)
Power monitoring, management and controls
Fire detection and
Staging Lobby and Electrical
Room suppression
Staging lobby for outside isolation In-Row
Cooling
Units
Schneider Electric - Division - Name – Date
415 Modular
Power
Distribution
24 NetShelter Racks
Aisle Containment
12
Schneider Electric - Division - Name – Date
13
Schneider Electric - Division - Name – Date
14
Phased Deployment View of (4)100 Rack IT Bays
Phase 3
Phase 4
Phase 1
100 Racks
Phase 2
100 Racks
Schneider Electric - Division - Name – Date
Gensets
Chillers
15
● Expandable rooms are secure, water, dust & fire proof thermally insulated modular IT rooms.
●
Rooms are built sized to any requirement.
● Installed Indoors or outdoor.
● Shelters can be disassembled & relocated.
● Rooms can expanded in a clean method.
● No construction construction dust or debris affecting expansion while operating.
● Visiting customers experience a “clean room” secure IT white space.
Schneider Electric - Division - Name – Date
16
Schneider specific features
Echain cable management
Schneider Electric - Division - Name – Date
Seismic
Rack Mount
Sliding Rail
System
17
Power Modules
250kW
20ft Enclosure with UPS,
Switchgear, cooling, DCIM
500kW
40ft Enclosure with UPS,
Switchgear, cooling, DCIM
1.2 MW
Skid mounted, UPS,
Switchgear, DCIM
Schneider Electric - Division - Name – Date
18
Air
Conditioners
Critical
Output
Switchboard
500kW
Symmetra
PX UPS
Fire Suppression
System
Schneider Electric - Division - Name – Date
Primary
Switchboard
500kW Module
Symmetra N+1
UPS(250/500kW)
5 min Runtime
Switchboard w/ integrated
ATS
Power monitoring, management and controls
Environmental cooling
Fire Suppression
UL Listed
19
1.2 MW Skid Shown
Allows for quick deployment within an existing building that is scalable for larger data centers.
N+1 UPS MW UPS
5 min Runtime
Switchboard w/ integrated ATS
Power monitoring, management and controls
Schneider Electric - Division - Name – Date
20
Cooling Modules
500kW Hydronics Modules
(Support 3-250kW Chillers)
1000kW Hydronics Modules
(Support 3-500kW Chillers)
Chiller Skids & Enclosures
Packaged Chiller, pump, and
Tank with connecting piping
250kW – 1.2 MW Packaged
Air Cooled Chillers -
Options with and without free cooling
Ecobreeze ISO frame
50kW increments up to 400kW of total cooling capacity (DCIM)
Schneider Electric - Division - Name – Date
21
AST Cooling Offer – CW & DX (Pending UL Certification)
Chilled Water Block Unit – CWB
Chilled water room cooling for prefabricated IT modules without raised floors
Capability
● Fits both ISO and Non-ISO prefab modules
● Designed to operate at higher water temperatures (15C)
● Top return with front supply air discharge
● Humidifier and electric reheat control options
Hot Corridor Heat Exchanger – HCX
Overhead cooling for prefabricated ISO IT modules
20 kW - 40 kW
● Chilled Water or Direct Expansion
● No floor space - located over the racks and hot aisle/corridor
●
Maintenance all done from hot aisle/corridor
● Requires chilled water plant or remote condensing unit
Schneider Electric - Division - Name – Date
22
AST Cooling Offer – Air Economizer
Natural Free Cooling Unit – NFC
Indirect Free Cooling for small or constrained data center spaces
50 kW
● Independent operating unit
● Heat Pipe heat exchanger isolating indoor and outdoor air
● Chilled Water, Direct Expansion, Humidity Control and Evaporative Cooling
Options
● Flexibility to have external heat rejection for mechanical cooling as required
- Chilled Water Plant or External Condensing Units
Direct Free Cooling Unit – DFC
Direct Free Cooling for small or constrained data center spaces
75 kW
● Uses air directly from outside for free cooling
● Chilled Water, Direct Expansion, Humidity Control and Evaporative Cooling
Options
● Flexibility to have external heat rejection for mechanical cooling as required
- Chilled Water Plant or External Condensing Units
Schneider Electric - Division - Name – Date
23
Global References
Education - Canada Utility - Australia
Healthcare - Italy
Schneider Electric - Division - Name – Date
Military - Europe
24
Global References
IT Software Company Government Customer – US
Global Bank – Denmark
Schneider Electric - Division - Name – Date
Cloud Service Provider –
Iceland
25
Mission-Critical Services
●
Consulting and Planning
–
Assessment, analysis, strategic planning and O&M program development services.
●
Design and Construction
–
Engineering, design-build and construction project management of facility expansions and new facility projects.
●
Commissioning
–
Data center and LEED commissioning from project inception to integrating testing.
●
Operations and Maintenance
–
Managed
Services and on-site Critical Facility
Management.
● Energy Management – Energy assessments, system optimization, and efficiency improvement projects.
● Alarm and Incident Management – 24x7 remote monitoring services through the
Schneider International Operations Center
(NOC).
Lifecycle Service Solutions
Schneider Electric - Division - Name – Date
26
Design-Build Benefits
2/2012
Schneider Design Build Outcomes
Singular Accountability/Project Ownership
Fully Integrated Project Delivery
Speed to Market – Reduced Project Timelines
Fewer Change Orders – Less Cost Overruns
Continuous Project Budgeting and Scheduling
Datacenter/Mission Critical Specific Team Skill Set
Competitively Bid All Major Cost Items
Schneider Electric - Division - Name – Date
12/2013
27
28
Discussion, Questions and Answers
Scott Fleming
Pre Fabricated Data Center Specialist scott.fleming1@schneider-electric.com
(925) 963 5468
Overview
ISO shipping container is defined to 8ft wide and lengths of 10ft, 20ft, 40ft, and 53ft in U.S.
Containers are designed to be strong, rugged, environmentally sound and easily transportable anywhere in the world
8ft width limits usable space for hot and cold aisles.
Height is also limited
Schneider has unique solutions for slide racks and flexible cable trays to allow full access to front and rear of racks to overcome space limitations
Overhead cooling units (DX and CW) are available to maximize rack space
Schneider Electric - Division - Name – Date
29 2
9
200kW – 1.2MW
5 Racks – 200 Racks
Schneider Electric - Division - Name – Date
DX – Chilled Water – Direct Air – Indirect Air
30