Evolution of Antipumping relay
SF, LF, Evolis 24kV, EvolisHP
Anti pumping Relay
Description:
The anti-pumping relay is built into the mechanism of circuit breakers to ensure that the opening order
has priority.
This function prohibits re-closing of CB in case of fault tripping. In other words it prevents the possibility of
maintaining a permanent closing order inorder to avoid « pumping » of the CB
Antipumping relay:
Schneider Electric - Division - Name – Date
2
What’s new?
● Replacement of Electromechanical antipumping relay by Electronic version
due to obsolete component.
● Capable of handling multi-voltages, from 24V to 380V
● Input: DC/AC, Output: DC only. Associated closing release coil YF to have DC
ratings only
● New Electrical diagram: Change in assembling closing coil with relay
Please see attached file for the updated diagrams.
Schneider Electric - Division - Name – Date
3
Ex. of updated Electrical Diagram
Schneider Electric - Division - Name – Date
4
Change in the offer structure
● Configured full product:
● No impact in Elonet configuration.
● Additional bridge options of internal electrical connection is not possible
anymore. Only standard bridge remains unchanged.
● Additional leaflet with new electrical diagram is attached with user manual
systematically
● Spare part:
● Ref MV261200 will be replacing old references for RI mechanism in SF, LF,
Evolis 24 and Evolis HP ranges
● Ref MV261202 will be replacing old references for GmH mechanism in SF
MCset4, SF F400 and SF2 fixed versions.
● It is recommended to replace the closing coil and relay at the same time.
● Level C adaptation: