Internal use only Daikin Altherma HT Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 2 Internal use only Product concept Cascade system: 2 refrigerant cycles with 2 inverter compressors Leaving water temperatures possible up to 80°C, ambient temperature down to -20°C Heating capacities: 11, 14 and 16kW (single and three phase) 1 2 down to -20°C up to 80°C Outdoor 8-Apr-15 3 Indoor Name: J. Logghe • Dept: New Business 3 Internal use only Product concept: 3 heat exchangers 1 Outdoor unit evaporator: air – R410A energy exchange 2 First plate heat exchanger: R410A – R134a energy transfer (indoor unit) 3 Second plate heat exchanger: R134a – H2O energy exchange, allowing LWT up to 80°C (indoor unit) On thermodynamic efforts only, no electrical heater Symbolic graph 3 R134a Second stage condense temperature 2 1 8-Apr-15 Intermediate condense temperature R410A Name: J. Logghe • Dept: New Business 4 Internal use only Product concept: target market Typical supply temperature areas of different heat generators Standard Boiler LT-Boiler Condensing Boiler Daikin Altherma Split + Monobloc Daikin Altherma (VL°C) Daikin Altherma HT 20 30 40 50 Floor heating 60 70 80 90 TARGET MARKET Fan convectors LT radiators 8-Apr-15 HT radiators Name: J. Logghe • Dept: New Business 5 Internal use only Product concept: target market Leaving water temperatures possible up to 80°C which makes it the perfect solution in combination with existing high temperature radiators Refurbishment market Outdoor unit Indoor unit (DHW tank included) High temperature radiators and domestic hot water Very efficient way to heat up the DHW, no electrical heater required 8-Apr-15 Name: J. Logghe • Dept: New Business 6 Internal use only Product concept: target market With a maximum TLWC of 80°C, the Daikin Altherma HT can cover the biggest part of the refurbishment market Cover more than 90% of the refurbishment demand 100% > 90% Demand coverage of refurbishment market (%) Max TLWC (°C) 25°C 8-Apr-15 60°C 65°C 80°C 90°C Name: J. Logghe • Dept: New Business 7 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 8 Internal use only Product features: indoor unit Easy installation thanks to the complete indoor unit with DHW tank and hydraulic components already included DHW tank: 200L or 260L 2285 mm 2010 mm Hydrobox (small footprint) 705 mm 8-Apr-15 Name: J. Logghe • Dept: New Business 9 Internal use only Product features: indoor unit If necessary, the DHW tank can also be installed next to the hydrobox 1580 mm 1335 mm 260L 200L Option kit for standalone tank EKFMAHTA includes: 1) top plate 2) adaptors (to go from quick couplers to screw connections) 3) piping between the screw connections (max distance between hydrobox and DHW tank is 25cm, longer pipes are field supply) 8-Apr-15 Name: J. Logghe • Dept: New Business 10 Internal use only Product features: hydrobox Heat exchanger Air purge R134a ↔ H2O Heat exchanger R410A ↔ R134a Pump (DC-inverter to maintain fixed ΔT) Manometer Expansion vessel (12L) Compressor R134a 8-Apr-15 Name: J. Logghe • Dept: New Business 11 Internal use only Product features: hydrobox 3 way valve located in hydrobox (only with DHW tank) 8-Apr-15 Name: J. Logghe • Dept: New Business 12 Internal use only Product features: PCB plate Switchbox is located behind the front plate of the hydrobox 8-Apr-15 Name: J. Logghe • Dept: New Business 13 Internal use only Product features: DHW tank Product line-up DHW tank 200 L Standard 260 L UK model Special: TBC DHW tank line-up: 6 models Option kit for UK: EKUHWHTA = other material name than on Daikin Altherma Split and Monobloc 8-Apr-15 Name: J. Logghe • Dept: New Business 14 Internal use only Product features: DHW tank Main parts DHW tank 8-Apr-15 Name: J. Logghe • Dept: New Business 15 Internal use only Product features: DHW tank Standard tank Naked tank lay-out Fully assembled (at factory) Front panels detached Top plate from Hydrobox or EKFMAHTA 8-Apr-15 Name: J. Logghe • Dept: New Business 16 Internal use only Product features: DHW tank UK tank: standard tank + factory fitted T&p valve Factory fitted T&p valve 8-Apr-15 Name: J. Logghe • Dept: New Business 17 Internal use only Product features: DHW tank Option kit on UK tank: EKUHWHTA Pressure reducing valve 7 Expansion relief valve <500 mm >300 mm Tundish Expansion vessel (18L) Tundish 7 H C 4 8 7 7 6 8-Apr-15 Name: J. Logghe • Dept: New Business 18 Internal use only Product features: DHW tank Special tank: standard tank + passivated + service opening TBC Passivated tank: requirement for Danmark Service hole: requirement for Switzerland and Germany Cleaning opening of 120 mm at the lowest third part of the tank 8-Apr-15 Name: J. Logghe • Dept: New Business 19 Internal use only Product features: DHW tank Tank performance: heat-up time (calculations) Size of the coil: length of 23m, surface area of 1,56m², internal coil volume of 7,5L Calculation example: ERSQ016AAV1 with EKHTS200 tank Up to a DHW temperature of 70°C, the part load capacity of the heat pump can still be exchanged to the DHW with the 1,56m² coil Altherma HT (200l coil 1.56 m^2) T(°C) Q(W) 90 20000 80 18000 70 16000 60 50 14000 T_in 12000 T_tank 10000 40 8000 30 Q 6000 20 4000 10 2000 0 0 8-Apr-15 T_out 1000 2000 3000 4000 5000 6000 7000 8000 9000 0 10000 Time(s) Name: J. Logghe • Dept: New Business 20 Internal use only Product features: DHW tank Tank performance: heat losses 200 l 260 l 201 258 193,5 250,5 Heat loss (kWh/24h) at dT = 45°C 1.2 1.5 Heat loss (W) at dT = 45°C 50 62,5 Max. temperature (°C) 75 75 Total capacity (L) Actual capacity (L) 8-Apr-15 Total capacity = internal volume of the tank (= effective water volume + coil volume Actual capacity = effective water volume inside the tank Name: J. Logghe • Dept: New Business 21 Internal use only Product features: DHW tank Tank performance: heat-up time and reheat time 8-Apr-15 Name: J. Logghe • Dept: New Business 22 Internal use only Product features: DHW tank Different possibilities to produce DHW Reheat operation: has always priority above space heating Disinfection operation: has always priority above space heating Storage operation - automatic operation (night and/or day timer) - manual operation Storage operation has priority above space heating, taking in account: - min/max running timers - smart logic function 8-Apr-15 Name: J. Logghe • Dept: New Business 23 Internal use only Product features: DHW tank Tank performance: maximum volume of usable hot water 8-Apr-15 Name: J. Logghe • Dept: New Business 24 Internal use only Product features: User interface User interface is mounted separately from indoor unit User interface can be used as a modulating room thermostat Optimized efficiency due to feedback of room temperature Optimized changeover from DHW heating to space heating Option kit: Remote user interface EKRUAHTA The same controller as supplied with indoor unit can be mounted parallel or on other location. If 2 controllers are installed, the installer needs to select 1 master & 1 slave. Not possible to use both user interfaces as a multi zone application (e.g. one in living room, other one in the kitchen) 8-Apr-15 Name: J. Logghe • Dept: New Business 25 Internal use only Product features: Control possibilities 1 Weather dependent floating setpoint: TLWC = f(Ta) 2 Thermostat control: user interface as room thermostat or normal room thermostat 3 Thermostatic valve 2 Ta T ROOM 1 master room (eg living room) ROOM 2 ROOM 3 Tl room thermostat TLWC 6 settings 1 2 3 4 5 20° C ON/OFF-valve manual control Ta thermostatic valve: temperature control by liquid or gas expansion 3 Weather dependent floating setpoint 1 8-Apr-15 radiator valve temperature control 7° C 27° C Name: J. Logghe • Dept: New Business 26 Internal use only Product features: Full H/P tariff Equipment allows for connection to a benefit kWh rate power supply New on Daikin Altherma HT Controllers are connected to a normal power connection When the benefit kWh rate power supply is interrupted, the compressor will stop operating, but there is no chance that the settings will be lost during longer power shutdowns 8-Apr-15 Name: J. Logghe • Dept: New Business 27 Internal use only Product features: zone 2 and zone 3 model Freeze protection for outdoor unit: bottom plate heater • A bottom plate heater will be standard in areas where low ambient temperatures can occur together with high humidity conditions (zone 2 model ERRQ), in other countries a bottom plate heater is available as an option (zone 3 model ERSQ). • To protect the outdoor unit against severe ice build-up on the air-cooled coil New on Daikin Altherma HT The bottom plate heater has no external thermostat, but is controlled by the PCB of the indoor unit ON/OFF depending on: - Hysteresis: 3° < Ta < 5° - Unit operation status 8-Apr-15 Ta 5°C 3°C Time Name: J. Logghe • Dept: New Business 28 Internal use only Product features: zone 2 and zone 3 model ‘cold’ climate Zone 2 model ERRQ: Outdoor unit is equipped with a zone 2 Bottom plate heater Zone 2 + 3 > 85% of the heating market Zone 3 model ERSQ: zone 3 Bottom plate heater as an option ‘mild’ climate ZONE 1 2 8-Apr-15 TEMP. COUNTRIES -30 ~ -20°C RU, FIN -20 ~ -10°C POL, GER, CE, Nor-EU (except FIN) Zone 2 countries: Only access to zone 2 models 3 -10 ~ 0°C SP, IT, GR, TKY, UK, IRL, BEL, NL, FR 4 0 ~ 10°C POR, ME, SA Zone 3 and 4 countries: 5 10 ~ 20°C centrral-AFR Access to both models Name: J. Logghe • Dept: New Business 29 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 30 Internal use only Applications examples Space heating & DHW heating: 1 RC in living room - No frequent start/stop of the unit and no big temperature fluctuations in the room - Smart logic functionality which controls the combined space heating and DHW demand 8-Apr-15 Name: J. Logghe • Dept: New Business 31 Internal use only Applications examples Space heating & DHW heating: 1 RC in living room, 1RC near the unit The main remote controller (C1) is installed in the living room and can access all settings (master). The second remote controller (C2) can not access schedule and parameter settings (slave) 8-Apr-15 Name: J. Logghe • Dept: New Business 32 Internal use only Applications examples Space heating & DHW heating: 1 external RT in living room, 1RC near the unit There is only room thermostat on/off control. There is no smart logic functionality for space heating, DHW operation is performed according to the min/max timer operation Daikin can not guarantee neither good operation nor reliability of the system, if a non-Daikin thermostat is used (= NO WARRANTY) 8-Apr-15 Name: J. Logghe • Dept: New Business 33 Internal use only Applications examples Multiple setpoint control Space 0: Radiators Space 1: Fan Coil Units Space 2: Under Floor Heating Tsetpoint = 65°C Tsetpoint = 45°C Tsetpoint = 35°C If there is a heat demand from space 0, the leaving water temperature delivered by the Daikin system is too high UFH 30° C 35° C 30° C 65° C A Temperature reducing device (TRD) is required for space 1 and 2, to lower the water temperature TRD 30° C When TRD’s are installed, the system can be configured to use multiple water set point. - The TRD’s are field supply - Control of the TRD’s is not done by the heat pump system - Operation and configuration of the TRD’s is the responsibility of the installer Daikin only offers the possibility to have multiple set points 8-Apr-15 Name: J. Logghe • Dept: New Business 34 Internal use only Applications examples Space heating & DHW heating: Radiators and UFH, DHW tank parallel - 2 space heating setpoints - 1 DHW setpoint no 3-way valve The DHW tank is installed in parallel with the TRD’s. This allows operating the unit in space heating and DHW heating simultaneously 8-Apr-15 Name: J. Logghe • Dept: New Business 35 Internal use only Applications examples Space heating & DHW heating: Radiators / FCU / UFH, DHW tank in a separate circuit - 3 space heating setpoints - 1 DHW setpoint [b-03] The DHW tank is installed in a separate circuit of the TRD’s. This configuration does not allow simultaneous DHW heating and space heating operation. 8-Apr-15 Name: J. Logghe • Dept: New Business 36 Internal use only Applications examples Space heating & DHW heating: space heating with an auxiliary boiler (alternating operation) - Bivalent operation is only possible for space heating operation, not for DHW heating operation - An auxiliary contact decides whether either the Daikin unit or the boiler will operate (e.g. outdoor thermostat, electricity tariff contact, manually operated contact) 8-Apr-15 Name: J. Logghe • Dept: New Business 37 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 38 Internal use only Product line-up Single Phase Three Phase Zone 2 Zone 3 Outdoor unit line-up: 12 models 11kW 14kW Single Phase 11kW Three Phase 14kW 200 L Standard 8-Apr-15 16kW 16kW 260 L UK model Special: TBC Indoor unit line-up: 6 models DHW tank line-up: 6 models Name: J. Logghe • Dept: New Business 39 Internal use only Product line-up: standard equipment 8-Apr-15 Name: J. Logghe • Dept: New Business 40 Internal use only Product line-up: optional equipment Optional kits connected to the indoor unit Demand PCB: required to be able to connect room thermostat or BUH kit and for multiple setpoint control (see service presentation) 8-Apr-15 Name: J. Logghe • Dept: New Business 41 Internal use only Product line-up: Combination table Combination table of outdoor and indoor unit 8-Apr-15 Name: J. Logghe • Dept: New Business 42 Internal use only Product line-up: optional equipment Optional kits connected to the outdoor unit A bottom plate heater is standard, the drain plug kit can not be installed 8-Apr-15 If a bottom plate heater is installed (EKBPHTH16A), than it’s not allowed to install the drain plug kit Name: J. Logghe • Dept: New Business 43 Internal use only Product line-up: optional equipment Optional kits connected to the DHW tank 8-Apr-15 Name: J. Logghe • Dept: New Business 44 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 45 Internal use only Nomenclature: Outdoor unit E R S Q 011 A A V1 Power supply code V1: 1~ / 220-240V / 50Hz Y1: 3~ / 380-415V / 50Hz Minor model change Major model change Capacity index kW Refrigerant code Q: R410A Temperature zone indication S: Ambient zone 3 R: Ambient zone 2 R: outdoor model E: European model 8-Apr-15 Name: J. Logghe • Dept: New Business 46 Internal use only Nomenclature: Indoor unit E K HBR D 011 A A V1 Power supply code V1: 1~ / 220-240V / 50Hz Y1: 3~ / 380-415V / 50Hz Minor model change Major model change Capacity index kW Refrigerant code D: R134a HBR: hydrobox H/O HT K: indoor model E: European model 8-Apr-15 Name: J. Logghe • Dept: New Business 47 Internal use only Nomenclature: DHW tank E K HT S (U) 200 A A: model change Water volume: 200: 200 L tank 260: 260 L tank DHW tank type: No letter: standard tank U: UK tank P: passivated + service opening S: Stainless steel tank HT: high temperature tank K: indoor model E: European model 8-Apr-15 Name: J. Logghe • Dept: New Business 48 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 49 Internal use only Specifications: Sound Data Outdoor unit 011 model 014 model 016 model Sound Pressure at 1m 52 dBA 53 dBA 55 dBA Sound Power 68 dBA 69 dBA 71 dBA Position for measuring the Sound Pressure level of the outdoor unit 8-Apr-15 Name: J. Logghe • Dept: New Business 50 Internal use only Specifications: Sound Data Indoor unit: Sound Pressure level Two different ways of measuring the Sound Pressure level of the indoor unit Sound Pressure level in front of the indoor unit Maximum Sound Pressure level possible at the four other microphones 8-Apr-15 Name: J. Logghe • Dept: New Business 51 Internal use only Specifications: Sound Data Indoor unit: Sound Pressure level Low sound mode has three different steps, Sound Pressure level of mode n°2 and n°3 is lower than n°1 8-Apr-15 Name: J. Logghe • Dept: New Business 52 Internal use only Specifications: Sound Data Indoor unit Sound Power 011 model 014 model 016 model 59 dBA 60 dBA 60 dBA Measurement condition: • Ta=7/6°C • Heating setpoint 70/80°C • Maximum compressor frequency 8-Apr-15 Name: J. Logghe • Dept: New Business 53 Internal use only Specifications: Operation range space heating Space heating Shift value of 5°C is possible via field setting 8-Apr-15 Name: J. Logghe • Dept: New Business 54 Internal use only Specifications: Operation range DHW heating DHW heating 8-Apr-15 Name: J. Logghe • Dept: New Business 55 Internal use only Specifications: Capacity table Conditions for Capacity table 8-Apr-15 Name: J. Logghe • Dept: New Business 56 Internal use only Specifications: Capacity table (nominal values) 8-Apr-15 Name: J. Logghe • Dept: New Business 57 Internal use only Specifications: Capacity table (peak values) 8-Apr-15 Name: J. Logghe • Dept: New Business 58 Internal use only Specifications: Capacity table (peak values) HC = f(Ta), TLW = 65°C 18,00 16,00 HC (kW) 14,00 12,00 10,00 8,00 6,00 4,00 2,00 0,00 -20 -15 -10 -5 0 5 10 15 Ta (°C) EKHBRD 011 8-Apr-15 EKHBRD 014 EKHBRD 016 Name: J. Logghe • Dept: New Business 59 Internal use only Specifications: Capacity table (peak values) COP = f(Ta), TLW = 65°C 4,00 3,50 3,00 COP 2,50 2,00 1,50 1,00 0,50 0,00 -20 -15 -10 -5 0 5 10 15 Ta (°C) EKHBRD 011 8-Apr-15 EKHBRD 014 EKHBRD 016 Name: J. Logghe • Dept: New Business 60 Internal use only Specifications: Capacity table (peak values) HC = f(Ta,TLW), EKHBRD 014 16,00 14,00 HC (kW) 12,00 10,00 8,00 6,00 4,00 2,00 0,00 -20 -15 -10 -5 0 5 10 15 Ta (°C) TLW = 45°C 8-Apr-15 TLW = 55°C TLW = 65°C TLW = 75°C TLW = 80°C Name: J. Logghe • Dept: New Business 61 Internal use only Specifications: Capacity table (peak values) COP = f(Ta,TLW), EKHBRD 014 4,50 4,00 3,50 COP 3,00 2,50 2,00 1,50 1,00 0,50 0,00 -20 -15 -10 0 -5 5 10 15 Ta (°C) TLW = 45°C 8-Apr-15 TLW = 55°C TLW = 65°C TLW = 75°C TLW = 80°C Name: J. Logghe • Dept: New Business 62 Internal use only Specifications: Capacity table (integrated values) 8-Apr-15 Name: J. Logghe • Dept: New Business 63 Internal use only Specifications: Capacity table (integrated values) HC = f(Ta), TLW = 65°C 18,00 16,00 14,00 HC (kW) 12,00 10,00 8,00 6,00 4,00 2,00 0,00 -20 -15 -10 -5 0 5 10 15 Ta (°C) EKHBRD 011 8-Apr-15 EKHBRD 014 EKHBRD 016 Name: J. Logghe • Dept: New Business 64 Internal use only Specifications: Capacity table (integrated values) COP = f(Ta,TLW), EKHBRD 014 4,50 4,00 3,50 COP 3,00 2,50 2,00 1,50 1,00 0,50 0,00 -20 -15 -10 0 -5 5 10 15 Ta (°C) TLW = 45°C 8-Apr-15 TLW = 55°C TLW = 65°C TLW = 75°C TLW = 80°C Name: J. Logghe • Dept: New Business 65 Internal use only Specifications: COP Peak values LT and HT COP values for 16kW model (3 phase) at Ta = 7°C): Daikin Altherma LT Split and Daikin Altherma HT 5 Daikin Altherma LT = excellent heat pump for Low Temperature applications COP 4,5 4 Daikin Altherma HT = excellent heat pump for High Temperature applications 3,5 3 Daikin Altherma HT 2,5 Daikin Altherma LT Split 2 30 40 50 60 70 80 TLW (°C) 8-Apr-15 Name: J. Logghe • Dept: New Business 66 Internal use only Specifications: Dimensions Indoor unit: hydrobox + DHW tank Outdoor unit 2285 mm 2010 mm 78 kg 70 kg V1: 144kg Y1: 147kg 8-Apr-15 1345 mm 120 kg V1: 144kg 705 mm Y1: 147kg Name: J. Logghe • Dept: New Business 67 Internal use only Specifications: Packing and shipping 4 EPS corners Top is made of carton Front-packing of DHW tank 8-Apr-15 The whole unit is foiled Back-packing of DHW tank Unit is fixed on palette Back-packing of Hydrobox Name: J. Logghe • Dept: New Business 68 Internal use only Table of contents 1. Product concept 2. Product features 3. Applications 4. Product line-up 4. Nomenclature 5. Specifications 6. Summary 8-Apr-15 Name: J. Logghe • Dept: New Business 69 Internal use only To summarize: product features Tlwc up to 80°C => refurbishment market, no booster heater Unit operates with guaranteed capacity down to - 20°C Newly designed casing in modern metallic color Integrated design of hydrobox and DHW tank All required hydraulic parts are included in hydrobox DC inverter pump to maintain fixed ΔT User interface can be used as a room thermostat Full H/P tariff Standard bottom plate heater on ERRQ, controlled by indoor unit Flat Peak capacity trend down to -7°C for Tlwc = 80°C 8-Apr-15 Name: J. Logghe • Dept: New Business 70