1 Piping Systems 2 Piping Systems • • • • • • • SERIES LOOP MONOFLO SYSTEM DIRECT RETURN REVERSE RETURN PRIMARY/SECONDARY SYSTEM BASIC PRIMARY SYSTEM SYSTEM SYZER 3 4 Hydronic System Water Heater and Tank Open System • Static Head Loss • Friction Loss • Valve and Fitting Loss • Atmospheric Pressure • NPSH(a) vs. NPSH(r) 5 Hydronic System Cooling Tower Open System • Static Head Loss • Friction Loss • Valve and Fitting Loss • Atmospheric Pressure • NPSH(a) vs. NPSH(r) Chiller 6 Open System Pressures Pipe Friction Loss (Varies with flow) Total Static Head Total Suction Head Basin Water Level Condenser (Known head loss) Pump 7 Backflow Preventer Water Heater Cooling Tower Storage DHW System HW CW HW Water Heater City Main Water Meter Backflow Preventer PRV Pump CW HW Water Heater CW 8 Hydronic System Hot Water Coil Closed System • Friction loss • Valve and Fitting Loss • NO Static Head Loss • Pressurized System Hot Water Boiler 9 Closed System Pressures Hot Water Coil Multi-Level Building 1 PSI = 2.31 Feet Head (ft) = head (psi) x 2.31 specific gravity Hot Water Boiler 10 Closed System Pressures Example: 4-Story Building Hot Water Coil •60 feet to top of system •26 PSI of Static Pressure Static Pressure (26 PSI) +Minimum Pressure (4 PSI) 30 PSI Hot Water Boiler PRV setting = 30 PSI 11 Closed System Pressures Hot Water Coil Example: Single Story Building 12 PSI fill pressure System can be 18 feet tall Hot Water Boiler 12 Series Loop Piping 13 Monoflo System 14 Direct Return 15 Direct Return Piping 16 Reverse Return 17 Reverse Return Piping 18 Primary-Secondary Direct Return Supply Secondary Pumps Primary - secondary Common Return Primary Pumps 18 19 Primary-Secondary Reverse Return Terminals Terminals Terminals Supply Supply Return Secondary Pump Primary Chiller Pumps Return Common Pipe 19 20 Primary-Secondary-Tertiary Zone C Zone A Zone B Tertiary Pumps Common Pipe Secondary Pumps Modulating Control Valves Optional Variable Speed Pump DP Sensor Common Pipe Primary Pumps 20 21 Primary-Secondary-Tertiary Hybrid Zone C Zone A Zone B Tertiary Pump Secondary Pumps Supply Common Pipe Primary Pumps Return 22 Primary Variable Speed Two-position Control Valves Flow Meter DP Sensor Modulating Valve VFD VFD VFD 22 23 Primary / Secondary Terminology: “Pump #1 can be referred to as the source or primary pump and pump #2 as the load or secondary pump.” – 2004 ASHRAE Systems and Equipment Handbook, page 12.7 24 Law of the “T” The flow rate entering a tee must equal the flow rate leaving the tee! 25 Law of the “T” 50 GPM 100 GPM 50 GPM 26 Law of the “T” 50 GPM 100 GPM 150 GPM 27 Law of the “T” 50 GPM 50 GPM 100 GPM 100 GPM 50 GPM 28 Law of the “T” 100 GPM 100 GPM 100 GPM 100 GPM 0 GPM 29 Law of the “T” 175 GPM 175 GPM 100 GPM 100 GPM 75 GPM 30 Prim. / Sec. -- Basics -Common Pipe SECONDARY PRIMARY 31 Prim. / Sec. -- Basics -Common Pipe Flow Pump OFF 100 gpm A 100 B 100 32 Prim. / Sec. -- Basics -Common Pipe Flow Pump ON - 100 gpm 100 gpm A 0 B 100 gpm 33 Prim. / Sec. -- Basics -Common Pipe Flow Pump ON - 50 gpm 100 gpm A 50 Mixing @ tee B 100 gpm 34 Prim. / Sec. -- Basics -Common Pipe Flow Pump ON - 200 gpm 100 gpm A 100 B Mixing @ tee 100 gpm 35 Primary / Secondary --Bridge SUPPLY PRIMARY / SECONDARY COMMON RETURN 36 P/S bridge - Front Loaded Common Load = Production HWS TEMP. - 180F (flow in gpm) 500 SECONDARY PUMPS 500 O F F O N COMMON -- NO FLOW 0 500 500 EHW TEMP. 150 F HWR TEMP. - 150 F 37 P/S bridge - Front Loaded Common Load > Production HWS TEMP. - (flow in gpm) 171 F 500 SECONDARY PUMPS 700 O F F O N MIXING (500 @ 180) + (200 @ 150) 0 COMMON -- 200 500 EHW TEMP. 150 F HWR TEMP. - 150 F 700 38 Bridge Check Valve SUPPLY COMMON RETURN 39 P/S bridge - Front Loaded Common Production > Load HWS TEMP. 180F (flow in gpm) 1000 SECONDARY PUMPS 800 O N O N COMMON -- 200 500 500 Equally Loaded MIXING (800 @150) + (200 @ 180) EHW TEMP. 156 F HWR TEMP. - 150 F 800 40 Primary-Secondary System Relationship SUPPLY Step Function Linear Function PRIMARY / SECONDARY COMMON RETURN 41 T3 HWS T1 Boiler T2 3-10 pipe diameters between Tees T4 HWR Single Boiler - Primary / Secondary 42 Boiler Control T5 HWS T3 Boiler T4 T7 T1 Boiler T2 T6 HWR Dual Boiler - Primary / Secondary 43 T5 HWS T3 Boiler T1 Boiler T7 T4 T2 T6 HWR Dual Boiler - Primary / Secondary 44 Four Boiler Primary Secondary System . . 45 Low Temperature Application Water Source Heat Pump or Radiant Heating Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #1 B&G balance valves w/ bypass line to provide high temp inlet water to boiler T3 HWS T1 Boiler T2 3-10 pipe diameters between Tees T4 HWR Single Boiler - Primary / Secondary 46 Low Temperature Application Water Source Heat Pump or Radiant Heating Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #2 FPE Valve w/ bypass line to provide high temp inlet water to boiler T3 HWS T1 Boiler T2 3-10 pipe diameters between Tees T4 HWR Single Boiler - Primary / Secondary 47 Low Temperature Applications • Alternate: Condensing Boiler 48 Primary Only Piping • For boilers that can handle variable flow 49 System Syzer Calculator •Circular Slide Rule •Analog Calculator •Extremely Helpful Tool 50 Explanation • Non-product specific • Water Use Only 51 Heat Transfer Formula Q = m CP (T2 - T1) Energy = mass flow x specific heat x Delta T lb 1 Btu °F Btu / Hr = Btu / Hr = X Gal Min Hr lb 8.34 lb °F 60 Min 1 Btu 1 Gallon 1 Hour lb Btu / Hr = 500 GPM T °F °F 52 Scale 1: Heat Transfer / Flow 1 MBH = 1000 Btu/hr Δt from 1 to 200º F 53 Scale 1 - Example Problem • Determine flow required for 150,000 Bth/hr using a 300T. 10 gpm 54 “Tons” of refrigeration One ton 12,000 BTU hr therefore 12,000 BTU hr 20 tons X ton 240 , 000 BTU hr 55 Scale 1 - Example Problem Determine flow required for 20 tons cooling using a 100Dt. 20 tons x 12,000 BTUH/ton = 240,000 BTUH or 240 MBH 48 gpm 56 Scale 2: Pipe Sizing Window • Milinch • Ft/100ft • ASHRAE 57 Scale 2: Example Problem Determine pipe size for 70 gpm in a typical hydronic system. 2½” Pipe 3.5’/100’ 3” Pipe 1.2’/100’ 58 Scale 3: Flow Velocity Works with Scale 2 59 Scale 3: Example Problem What is the velocity of 1600 gpm through an 8” pipe? Problems? 10+ fps 60 Scale 3: Example Problem What is the velocity of 1600 gpm through an 8” pipe? Problems? 7 fps 61 Pipe Sizing / Fitting Pressure Drop • System Syzer Jacket • Based On Hydraulic Institute Standards • One Method, There Are Others! 62 Equivalent Lengths Table 11’ 63 Scale 4: Description • Pipe Length - TEL - 50% rule • Friction Loss • Total Pressure Drop 64 Scale 4: Example Problem What is the total pressure drop in a pipe with a TEL of 130’ and flow rate of 200 gpm? Scale 2 2.3’/100’ Or…. 2.3’/100’ x 130’ = 3’ 65 Scale 4: Example Problem The TEL of the longest circuit is 1500’. The head loss rate in the system piping is 3.4’/100’ at design flow. How much head does the pump have to provide to overcome the piping head loss? 1500’ 3.4’/100’ 50’ 66 Scale 5: Flow/Head Relationship 2 Q2 h2 h1 Q1 Q1= Known (design) flow Q2 = Final flow h1 = Known (design) head h2 = Final head 67 Scale 5: Example Problem A chiller has 12’ head loss at 100 gpm. What is its head loss at 150 gpm? 27’ 68 Scale 5: Example Problem A closed system has a flow rate of 200 gpm and a head loss of 30’. Plot the system curve. Flow vs Head 100 7.5 150 17 200 30 250 46 300 67 69 Plotting the System Curve