30 BAR. DIA. 40 30 BAR. DIA. L3/4 L3/2 VERIFY G. BEAMS AND GIRDERS L1 THICKNESS MINIMUM TEMPERATURE BARS 100 mm 10mmØ @ 275mm O.C. EACH WAY 112.5 mm 10mmØ @ 238mm O.C. EACH WAY 10mmØ @ 212mm O.C. EACH WAY 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING CODE OF AMERICAN CONCRETE INSTITUTE (ACI-318) FOR REINFORCED CONCRETE & STRUCTURAL STEEL WORK SHALL CONFORM WITH THE LATEST EDITION OF THE A.I.S.C. SPECIFICATIONS IN SO FAR AS THEY DO NOT CONFLICT WITH THE REQUIREMENTS OF THE NATIONAL STRUCTURAL CODE FOR BUILDINGS AND LOCAL CODES. 125 mm 137.5 mm 150 mm 2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF TWENTY EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE AGGREGATE AND SLUMPS AS FOLLOWS: 5 in. (130 mm) COLUMNS & BEAMS ON GROUND 3000 psi (20.7 MPa) 3/4 in. (19 mm) 5 in. (130 mm) SUSPENDED BEAMS 3000 psi (20.7 MPa) 3/4 in. (19 mm) 5 in. (130 mm) SUSPENDED SLABS 3000 psi (20.7 MPa) 3/8 in. (10 mm) 5 in. (130 mm) CURBS AND SLAB ON GRADE 2500 psi (17.2 MPa) 1 in. (25 mm) 4 in. (100 mm) MOULDINGS 3000 psi (20.7 MPa) 3/8 in. (10 mm) 5 in. (130 mm) L1/5 L4 L2/4 L2/4 L3/4 L3/4 3/4 EMBEDMENT LENGTH LENGTH IN TABLE 'A' TRANSVERSE TRIMMER BAR (TOP & BOTTOM) 30mm CLEAR (ALL AROUND) L1 L2 L3 INTERIOR COLUMN SUPPORT EXTERIOR COLUMN SUPPORT WHEN COUNTED FOR COMPRESSION EXTEND 20xDIA. BEYOND OPPOSITE FACE OF SUPPORT EXTERIOR GIRDER SUPPORT TENSION BARS EMBEDMENT LENGTH & LAP SPLICES (IN CENTIMETERS) 10mmØ @ 188mm O.C. EACH WAY EMBEDMENT LAPPED EMBEDMENT LAPPED 30 10mmØ @ 175mm O.C. EACH WAY 3. TYPICAL DETAIL OF PIPE SLEEVES THROUGH CONCRETE IS SHOWN AS FOLLOWS: fc' = 17.2 MPa (2500 psi) fc'= 20.7 MPa (3000 psi) BAR SIZES (mm) Ø10 30 30 30 5. UNLESS OTHERWISE NOTED IN THE PLANS, ALL BEDDED SLABS SHALL BE REINFORCED WITH 10mmØ REBAR AT 250 mm O.C. EACH WAYAT CENTER OF SLAB, AND CONSTRUCTION JOINTS FOR SAME SHALL NOT BE MORE THAN 8 METERS APART. Ø12 30 36 30 30 Ø16 36 45 30 43 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT DISCONTINUOUS EDGES AS SHOWN BELOW). Ø20 36 55 39 61 52.5 62.5 57.5 65 56 95 62 105 Ø28 71 121 77 131 Ø32 93 158 101 172 Ø36 151 179 128 218 HORIZONTAL DIAGONAL 1 1/2 in. (38mm) BEAM STIRRUPS AND COLUMN TIES 1 1/2 in. (38mm) WHERE CONCRETE IS EXPOSED TO EARTH BUT POURED AGAINST FORMS 2 in. (50mm) WHERE CONCRETE IS DEPOSITED DIRECTLY AGAINST EARTH 3 in (75mm) 1 in. (25mm) 8. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED AND SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. 9. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, TOOLS, EQUIPMENTS AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS. 10. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER APPROVED METHODS. 11. STRIPPING OF FORMS AND SHORES SHALL BE DONE AFTER A MINIMUM AMOUNT OF TIME 2. FOOTINGS SHALL REST ON NATURAL SOIL 1.50 METERS BELOW GRADE LINE, UNLESS OTHERWISE INDICATED BY THE ENGINEER. NO PART OF THE FOUNDATION SHALL REST ON FILL UNLESS REPLACED WITH 1.0 m DEEP WELL-COMPACTED CRUSHED ROCK FILL.. COMPACTION OF ALL SUBGRADE SHALL BE AT 95% OF MDD BASED ON ASTM D698. EMBEDMENT LAPPED Ø10 30 20 30 Ø12 20 30 21 34 Ø16 23 32.5 26 42.5 Ø20 28 37.5 31 50 Ø22 25 45 27.5 57.5 Ø25 37 51 41 67.5 Ø28 42 57.5 77 75 Ø32 46 64 52 85 Ø36 51 72 - - VERTICAL SLEEVE 4. THE CONTRACTOR SHALL HAVE THE RESPONSIBILITY TO DEVISE & IMPLEMENT EXCAVATION PROCEDURES THAT WILL ENSURE SAFETY OF LIFE & PROPERTY. CONTRACTOR SHALL ENSURE THAT ALL EXISTING STRUCTURES ARE PROPERLY AND ADEQUATELY SUPPORTED AGAINST SETTLEMENT OR MOVEMENT DURING CONSTRUCTION. 1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT NOT TO EXCEED 80 PCF. FOR LOAD BEARING TYPE CONCRETE BLOCKS, A MINIMUM COMPRESSIVE STRENGTH OF 6.90 MPa SHALL BE DEVELOPED. b t LINTEL IN BLOCK WALLS (PER 100mm THICKNESS) REINFORCEMENT HEIGHT OF LINTEL (cm) BOTTOM TOP 1.20 1.80 13.80 20 1-10mmØ 1-10mmØ 24 HRS. 3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200 mm) ON EACH SIDE OF MASONRY WALL OPENING. 1.50 1.90 13.80 20 1-10mmØ 1-10mmØ SUSPENDED SLABS EXCEPT WHEN ADDITIONAL LOADS ARE IMPOSED 1.80 2.20 13.80 20 1-10mmØ 1-10mmØ 8 DAYS 4. MASONRY WALL REINFORCEMENTS SHALL BE AS FOLLOWS, UNLESS NOTED: 2.10 2.50 17.20 20 1-16mmØ 1-10mmØ 2.40 WALLS 18 HRS. 2.80 17.20 20 1-16mmØ 1-10mmØ 2.70 3.10 17.20 20 1-20mmØ 1-10mmØ BEAMS 14 DAYS 3.00 3.40 17.20 30 1-16mmØ 1-10mmØ COLUMNS 3 DAYS 3.30 3.70 17.20 30 1-16mmØ 1-10mmØ 3.60 4.00 17.20 30 1-16mmØ 1-10mmØ 12. ON LAP SPLICE AND HOOKS: a. ALL BARS FOR BEAMS AND COLUMNS SHALL BE LAPPED WITH A MIN. LENGTH OF 30 x BAR DIAMETER. b. ALL BARS FOR SUSPENDED SLABS SHALLE BE SPLICED WITH A MIN. LENGTH OF 40 x BAR DIAMETER. c. NO MORE THAN 50% OF THE BARS SHALL BE SPLICED WITHIN THE REQUIRED LAP LENGTH. d. 90° HOOKS WITH 12 x BAR DIAMETER EXTENSION (SPECIFICALLY FOR BEAMS) SHALL BE ANCHORED INTO THE FAR FACE OF THE COLUMN. 13. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, REHANDLING OR FLOWING. ADEQUATE VIBRATION OR APPROVED EQUAL METHOD SHALL BE DONE DURING DEPOSITION OF CONCRETE. HORIZONTAL REINFORCEMENT 8" (200 mm) Ø12 @ 400 mm Ø10 @ 600 mm (3 LAYERS) 6" (150 mm) Ø10 @ 600 mm Ø10 @ 600 mm (3 LAYERS) 4" (100 mm) Ø10 @ 600 mm Ø10 @ 600 mm (3 LAYERS) 5. REINFORCING BARS SHALL BE LAPPED WITH A MINIMUM OF 30 BAR DIAMETERS WHERE SPLICED DOWELS FROM CONCRETE FOOTINGS OR SLABS SHALL EXTEND INTO THE BLOCK WALL AT A MINIMUM OF 30 BAR DIAMETERS. REBARS TO BE TIED PROPERLY WITH G.I. WIRES. CORNER WALL OPENING DIAMETER REINFORCING BARS DIAGONAL HORIZONTAL FOR SIZE AND SPACING OF HOR. & VERT. BARS SEE CONSTRUCTION NOTES STIRRUP VERTICAL 2 - Ø12STEEL 2 - Ø12 K. STRUCTURAL Ø< = 100 < 2 - Ø12 2 -USED Ø12 FOR FABRICATION 2 - Ø12 Ø12 ERECTION - @50 = 150 <Ø 1.150 ALL STRUCTURAL STEEL TO BE AND SHALL COMPLY < WITH ALL THE PERTINENT PROVISIONS OF AISC. 2 - Ø16 2 - Ø16 2 - Ø16 150 < Ø = 200 Ø12 - @50 2. ALL STRUCTURAL STEEL SHAPES & PLATES SHALL CONFORM TO STD. REQUIREMENTS < 250 2 - Ø20 2 - Ø16 2 - Ø16 Ø12 - @50 200 Ø= OF< AISC FOR ASTM A36 STEEL. MIN. YIELD STRENGTH = 248 MPa OR 36000 psi. 3. ALL COLD FORMED STEEL SHAPES SHALL CONFORM TO STD. REQUIREMENTS OF AISC FOR JIS G3141 SPCC. MIN. YIELD STRENGTH = 227 MPa OR 33000 psi. CHB WALL INTERSECTION WALL DOWEL BARS TO MATCH CHB HOR. BARS 12mm THK. EXPANSION JOINT WITH MASTIC FILLER 4. ALL PIPES & TUBES SHALL CONFORM TO STD. REQUIREMENTS OF ASTM A53. MIN. YIELD STRENGTH = 248 MPa OR 36000 psi. 5. ALL SHOP AND FIELD WELDS SHALL CONFORM WITH AWS STRUCTURAL WELD CODE D1-1. USE E60XX ELECTRODE. WELDING SHALL BE PERFORMED BY QUALIFIED WELDERS. 6. ALL BOLTS, NUTS AND WASHERS SHALL BE HIGH-STRENGTH & CONFORM TO A307 OR A325 UNLESS OTHERWISE INDICATED. ANCHOR BOLTS SHALL LIKEWISE BE OF EQUAL STRENGTH AS A325 BOLT OF THE SAME SIZE . R.C. COLUMN OR WALL INTERSECTING R.C. COLUMN OR WALL 1-Ø16mm VERT. BARS NOTE : USE 10mmØ STIRRUPS SPACED @ 200mm O.C. 'L' 0.20 6. ALL CELLS CONTAINING REINFORCING BARS OR INSERTS SHALL BE SOLIDLY FILLED WITH CONCRETE GROUT (REFER TO SPECIFICATIONS ). 'L' 0.20 0.20 FOR SIZE AND SPACING OF HOR. & VERT. BARS SEE CONSTRUCTION NOTES 0.20 OPENING OR END WALL 7. WELD HORIZONTAL BARS FOR CHB WALL TO STEEL COLUMNS WHERE APPLICABLE. 12mmØ BARS ON SIDES OF DOOR OPENING 14. SAMPLING FOR COMPRESSIVE STRENGTH TESTS SHALL BE MADE IN ACCORDANCE WITH SPECIFICATIONS. 1-Ø16mm VERT. BARS REINFORCING BAR FOR SLEEVES 1. REINFORCEMENTS FOR CONCRETE LINTEL BEAMS FOR OPENINGS (DOORS & WINDOWS) SHALL BE AS FOLLOWS: MIN. fc' MPa FOR SIZE AND SPACING OF HOR. & VERT. BARS SEE CONSTRUCTION NOTES PROVIDE 3-Ø10 EXTRA STIRR. EACH SIDE OF SLEEVES. 6. GENERALLY NO SPLICE SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING STRESSES OCCUR. SPLICES WHERE SO PERMITTED SHALL BE AS INDICATED IN TABLES A & B. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR. NO MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE ALLOWED TO BE SPLICED THEREIN. FOUNDATION VERTICAL REINFORCEMENT CHB WALL 12mm THK. EXPANSION JOINT WITH MASTIC FILLER 5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS SHALL BE 18.75mm CLEAR FOR JOISTS & 37.50mm CLEAR FOR BEAMS AND GIRDERS. CLEAR SPAN 'L' TOTAL LENGTH (L + 0.40 , m) (m) 1-Ø16mm VERT. BARS SLEEVES FOR UTILITY PIPES MAX. 1/3D 4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25mm DIAMETER BAR SEPARATORS SPACED ABOUT 90 cm ON CENTER. IN NO CASE SHALL THERE BE LESS THAN TWO (2) SEPARATORS BETWEEN LAYERS OF BARS. 2. PROVIDE 1-Ø10mm VERTICAL BAR AT CORNERS, INTERSECTIONS, END OF WALLS AND EACH SIDE OF OPENINGS. WALL THICKNESS STIRRUPS MAIN REINFORCEMENT H. LINTEL BEAMS IN CHB WALLS E. MASONRY AND CONCRETE BLOCKS 400 LAPPED 20 3. IF BEAM REINFORCING BARS END IN A WALL, THE CLEAR DISTANCE FROM THE BAR TO THE FARTHER FACE OF THE WALL SHALL NOT BE LESS THAN 25mm. EMDEDMENT LENGTH SHALL BE AS SHOWN IN TABLE-A & TABLE-B ACCORDINGLY. 3. THE CONTRACTOR SHALL NOTIFY IN WRITING THE ENGINEER AFTER FOOTING EXCAVATION HAS BEEN COMPLETED AND PRIOR TO CONCRETING TO CONFIRM THE DESIGN SOIL BEARING CAPACITY AND IF ACTUAL SOIL PROPERTY APPEARS WEAKER THAN ASSUMED. 6. FILL AND SUBGRADE UNDER SLABS AND FOOTINGS SHALL BE COMPACTED TO A MINIMUM 95% OF MDD (MAXIMUM DRY DENSITY) BASED ON ASTM D698. EMBEDMENT t OR 1/4D 1. FOOTINGS WERE DESIGNED FOR A SOIL BEARING CAPACITY OF 2000 psf FOR AN EMBEDMENT OF 2 METERS & 1470 psf FOR AN EMBEDMENT OF 1.5 METERS OR LESS. fc' = 17.2 MPa (2500 psi) fc'= 20.7 MPa (3000 psi) BAR SIZES (mm) D D. FOUNDATION AND FOOTINGS 5. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75 mm CLEAR FOR CONCRETE DEPOSITED AGAINST THE GROUND AND 50 mm CLEAR IF DEPOSITED AGAINST A FORMWORK. 12mm THK. EXPANSION JOINT WITH MASTIC FILLER 400 3/4 in. (19mm) SLAB ON GRADE WALLS ABOVE GRADE D TYPICAL DETAIL FOR BEAM OR SLAB CHANGE SOFFIT COMPRESSION BARS EMBEDMENT LENGTH & LAP SPLICES (IN CM) a. ALL SLABS ON GRADE SHALL BE DESIGNED WITH A MINIMUM WATER CEMENT RATIO OF OF 0.42. ANY DECREASE IN WORKABILITY SHALL BE COMPENSATED USING A PLASTICIZER. b. ALL SLOPES SHALL BE POURED INTEGRAL WITH SLAB OVERLAYS & TOPPING SHALL NOT BE ALLOWED UNLESS APPROVED OR SPECIFIED BY ENGINEER. c. CONTINUOUS WET CURING OF CONCRETE BY PONDING SHALL BE DONE FOR AT LEAST 14 DAYS UNLESS OTHERWISE SPECIFIED. 40 BAR DIA (MIN) STIRRUPS TABLE - B 4. BARS OF REINFORCED CONCRETE EXPOSED TO THE WEATHER SHALL PREFERABLE BE PROTECTED AT LEAST 38mm AND IN NO CASE LESS THAN 25mm CONCRETE COVER. THIS PROVISION MAY BE WAIVED WHEN ADEQUATE WATERPROOFING IS PROVIDED BUT SHALL IN NO CASE BE LESS THAN 20mm. SUSPENDED SLABS 40 BAR DIA 2t=FOR SLAB D=FOR BEAM 40 BAR DIA. a Ø22 Ø25 TYPICAL SLAB AND BEAM CONSTRUCTION JOINT DETAIL IN TWO WAY SLABS, EXTEND BARS UP TO BEAM SUPPORT 1. ALL EMBEDDED PIPES FOR UTILITIES, ETC. SHALL BE MAXIMUM 100mm DIAMETER SINGLE RIGID GALVANIZED IRON PIPE UNLESS OTHERWISE SPECIFIED OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. 2. SUCH PIPES WHEN SO EMBEDDED SHALL NOT TAKE UP MORE THAN FOUR (4) PERCENT OF THE GROSS AREA OF THE CONCRETE MEMBER. TABLE - A 7. ON SLABS ON GRADE: 3. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615. USE GRADE40 FOR Ø16mm & SMALLER, GRADE 60 FOR REBARS Ø20mm & BIGGER. ALL BARS 12mmØ AND BIGGER SHALL BE DEFORMED. BARS SMALLER THAN 12mmØ MAY BE PLAIN BARS. 6. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS. MAIN REINFORCEMENTS TO BE CONTINUOUS J. EMBEDDED PIPES IN CONCRETE SEE TABLE 'B' FOR LENGTH OF LAPPED SPLICE 2. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP OR EXTEND IN ACCORDANCE WITH TABLE-A OR B. 5-10mmØ TOP BARS SP. @ 200mm O.C. 5. IN GENERAL, THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS OTHERWISE SHOWN OR NOTED. 10mmØ x 1m LONG @ 300 O.C. NOTE: OMIT TRIMMER BARS WHERE OPENING IS FRAMED BY BEAM. OPENING SLAB SEE TABLE 'B' FOR LENGTH OF EMBEDMENT 5-10mmØ BOTTOM BARS SP. @ 200mm O.C. LOCATION L1/4 SEE TABLE 'A' FOR LENGTH OF EMBEDMENT (DOWEL) MAX. SLUMP 1 in. (25 mm) 2/3 L4 (DOWEL) MAX. AGGREGATE SIZE 3000 psi (20.7 MPa) L3/3 L3 SCHEDULE OF MINIMUM SLAB REINFORCEMENT B. CONCRETE AND REINFORCEMENT 28 DAYS STRENGTH L3/5 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND SHALL NOT BE LESS THAN 0.0025xBT, AND AS FOLLOWS: 6. IN CASE OF DISCREPANCIES AS TO THE LAYOUT DIMENSIONS AND ELEVATIONS BETWEEN THE STRUCTURAL PLANS AND OTHER DRAWINGS. THE CONTRACTOR SHALL NOTIFY BOTH THE STRUCTURAL ENGINEERS AND THE OWNER'S REPRESENTATIVE OR SITE ENGINER IN WRITING BEFORE PROCEEDING WITH AFFECTED WORK. FOUNDATION & RETAINING WALLS L2/5 L2 3. IF SLABS ARE REINFORCED BOTHWAYS, BARS ALONG THE SHORTER SPAN SHALL BE PLACED BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER AT THE SUPPORTS. FOR THE REINFORCING BARS NEAR THE SUPPORTS, THE SPACING OF THE BARS AT THE COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND A HALF (1-1/2) THAT IN THE MIDDLE STRIPS BUT IN NO CASE GREATER THAN TWO AND A HALF (2-1/2) TIMES THE SLAB THICKNESS NOR 450mm. 4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORINGS AND BRACING TO THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING CONSTRUCTION. 5. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS IN FLOOR SLABS, OPENINGS IN WALLS AND SLABS, INTERIOR PARTITIONS, LOCATION OF DRAINS, ETC. LOCATION L2/5 25 LONGITUDINAL TRIMMER BAR (TOP & BOTTOM) 1. TYPICAL BAR BENDING AND CUTTING DETAILS FOR BEAMS AND GIRDERS SHALL BE AS SHOWN IN FIGURE BELOW: L1/5 3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN. CHECK WITH MECHANICAL AND ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE. INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. WHERE JOINT IS AT POINT OF STRESS, PROVIDE SHEAR RODS WITH ENGINEERS APPROVAL BEAM a 2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEEL, MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED FOR ENGINEER'S APPROVAL BEFORE FABRICATION. MAIN REINFORCEMENTS TO BE CONTINUOUS (TOP & BOT. BARS) VERIFY DEPRESSION L2/4 t/3 t/3 L2/4 1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. t/3 L1/3 12mmØ x 1.00 m LONG DIAGONAL BAR @ MID-DEPTH OF SLAB AT ALL CORNERS 2. COLUMN AND PEDESTAL TIES SHALL BE PROTECTED BY A COVERING OF CONCRETE CAST MONOLITHICALLY WITH THE CORE WITH MINIMUM THICKNESS OF 38 mm AND NOT LESS THAN 1-1/3 TIMES MAXIMUM SIZE OF COARSE AGGREGATE. 400mm (TYPICAL) L1/3 1. OTHERWISE SPECIFIED, OPENINGS ON SUSPENDED SLABS SHALL HAVE ADDITIONAL REINFORCEMENT AS SHOWN BELOW: 1. FOR ALL TIED COLUMNS AND PEDESTALS, PROVIDE EXTRA 4 SETS OF TIES AT 100 mm O.C. FOR COLUMN REINFORCEMENTS JUST ABOVE THE FLOOR, JUST BELOW THE GIRDER AND AT CONSTRUCTION JOINTS. 2. UNLESS OTHERWISE DETAILED, IN CONTINUOUS SLABS HAVING SAME REINFORCEMENT RUNNING IN ONE DIRECTION, REINFORCING BARS SHALL BE BENT UP, EXTENDED, OR CUT AS FOLLOWS: A. GENERAL I. CONCRETE SLAB OPENINGS F. CONCRETE COLUMNS & PEDESTALS 1. ALL SLAB REINFORCEMENT SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM TOP OF SLAB. t=FOR SLAB D=FOR BEAM C. CONCRETE SLABS CONSTRUCTION NOTES ARE SUPPLEMENTAL TO AND FORM PART OF THE PLANS, DRAWINGS & SPECIFICATIONS. WHERE DETAILS OR REQUIREMENTS ARE NOT COVERED BY THE PLANS OR SPECIFICATIONS, THESE GENERAL CONSTRUCTION NOTES SHALL BE USED INSOFAR AS THEY ARE APPLICABLE TO SATISFY REQUIREMENTS OF GOOD CONSTRUCTION PRACTICE. IN CASE OF QUESTIONS ARISING FROM THE INTERPRETATION OF OR CONFLICT WITH OTHER DOCUMENTS, THE ATTENTION OF THE OWNER/ENGINEERS MUST BE CALLED IN WRITING. D/3 D/3 D/3 CONSTRUCTION NOTES OPENING 10mmØ BAR AROUND WINDOW OPENING (TYP.) TYPICAL MASONRY WALL CONNECTION DETAILS OPENING FIN. FLR. 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA SHEET NO. : OWNER : PROJECT TITLE : S-1 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 01 09 4175 2000 1200 C3 F2 7 C1 F1 6 C1 GB C3 GB GB C1 5 C1 C1 GB 2300 2300 F3 C3 C1 F1 5 4175 6 C1 D 3500 8 C3 F2 1000 7 C GB 8 B C1 GB 3500 A 1200 2000 D GB C GB B 1000 A F1 F3 1 F1 C1 C2 1 C1 F1 GB C1 GB GB C1 C2 C1 GB C2 C1 GB 2 C1 C1 C2 2000 C1 2650 F1 F3 C2 GB 3 GB 2 C1 2650 2000 F1 C1 F1 GB GB C1 F1 3 GB 4 GB 4 10mØ DRSB @ 300mm O.C. BOTH WAYS FOR ALL SLABS ON FILL GB 2850 2850 F1 GB GB C1 C2 C1 F3 FOUNDATION PLAN SCALE GRADE BEAM LAYOUT 1:100 SCALE SHEET NO. : OWNER : PROJECT TITLE : 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA 1:100 S-2 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 02 09 C 4175 2850 B3 B20 RB1 RB1 RB1 RB1 RB2 RB1 1 2ND FLOOR FRAMING PLAN SCALE RB1 RB1 2650 GR1 CB CB S14 CB GR1 S13 S12 B2 GR2 GR2 2650 S11 RB1 2 C1 S10 1 2000 GR1 PC RBCB S9 GR1 2 RB1 3 GR2 B3 B2 GR2 GR2 2000 S8 S5 S7 GR2 S6 RB1 4 RB1 C1 B1 3 RB2 RB1 GR2 RB1 RB1 GR1 GR2 GR2 2850 CB 4 RBCB 5 B3 S4 S3 B4 5 RB2 2300 GR2 2300 B3 GR2 D 4175 6 S2 C1 3500 1200 GR2 GR2 S1 CB 7 GR2 6 C 8 GR2 1200 B1 1000 7 2000 GR2 8 B RB1 3500 A RBCB 2000 D RB2 B 1000 A ROOF FRAMING PLAN 1:100 SCALE SHEET NO. : OWNER : PROJECT TITLE : 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA 1:100 S-3 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 03 09 FOOTING SECTION SCALE PLAN VIEW DNTS SCALE DNTS SCHEDULE OF ISOLATED FOOTING REINFORCEMENT DIMENSION X Y DIRECTION DIRECTION FOOTING MARK WIDTH LENGTH F1 1600 1600 350 16mm 9-16mm 9-16mm ISOLATED FOOTING @ DEPTH OF 1.50m FROM N.G.L. F2 1200 1200 400 16mm 8-16mm 8-16mm ISOLATED FOOTING @ DEPTH OF 1.50m FROM N.G.L. 2200 400 16mm 13-16mm 13-16mm CANTILEVER FOOTING REMARKS SCHEDULE OF REINFORCED CONCRETE BEAMS @ FOUNDATION LEVEL BEAM SECTION MARK GB WIDTH (B) DEPTH (H) 200mm 400mm LONGITUDINAL REINFORCEMENTS BAR Ø MIDSPAN RIGHT END LOCATION LEFT END SECTION SECTION SECTION TOP BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ BOTTOM BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ STIRRUPS 10mm :1@50mm 12@100mm 5@150mm REST @ 250mm O.C. TO C.L. @ DEPTH OF 1.50m FROM N.G.L. SEE CONSTRUCTION NOTES FOR MASONRY WALL REINFORCEMENTS (TYPICAL) 150mm THK. CONCRETE SLAB-ON-GRADE 10mmØ DRSB @ 300mm O.C. BOTH WAYS TOP OF SLAB (DOWEL) DOWEL TO MATCH CHB VERT. BARS (TYP) FFL DOWEL BARS TO MATCH CHB VERT. BARS DOWEL TO MATCH CHB VERT. BARS WHERE SLAB DEPRESSION OCCURS (TYP) FIN. FLR. LVL. NGL 30 BAR DIAMETER 2200 REMARKS 100 150 75 F3 THICKNESS RSB SIZE 6-Ø10 BARS (AS SHOWN) 3-Ø10 BOT. BARS SUBGRADE COMPACTED TO 95% MDD BASED ON ASTM D-698 Ø12 BOT. BARS @ 300 O.C. 50mm THK. GRAVEL BED COMPACTED TO 95% MDD BASED ON ASTM D-698 WF-1 AT EDGE / PERIMETER CHB WALL SLAB ON GRADE DETAILS SCALE Ø12 BOT. BARS @ 300 O.C. WF-2 AT INTERIOR CHB WALLS WF-3 AT INTERIOR WALLS WITH SLAB ELEVATION DIFFERENCE WALL FOOTING DETAILS NTS SCALE SHEET NO. : OWNER : PROJECT TITLE : 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA NTS S-4 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 04 08 LAT. TIES L/4 0.165L 0.22L GIRDER TO COLUMN CONNECTION DETAIL COLUMN ELEVATION SHOWING DOWELS AND TIES SPACING DETAILS SCALE NTS WALL REINFORCING AT R.C. COLUMN SPLICE WALL REINFORCING AT CORNER SCALE NTS WALL BASE REINFORCING AT INTERSECTION 400 CHB STIFFENER BEAM DETAILS SECTION STIFFENER COLUMN DETAILS ON CHB WALLS 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA SHEET NO. : OWNER : PROJECT TITLE : S-5 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 05 09 ELEVATION ELEVATION SECTION SECTION TYPICAL GRAVITY REINFORCED CONCRETE BEAM DETAIL TYPICAL DUCTILE MOMENT FRAME BEAM DETAIL SCALE SECTION OF 3 SETS STIRRUPS NTS SCALE SHEET NO. : OWNER : PROJECT TITLE : 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA NTS S-6 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 06 09 SCHEDULE OF REINFORCED CONCRETE BEAMS @ 2NDLEVEL BEAM SECTION MARK LONGITUDINAL REINFORCEMENTS WIDTH (B) DEPTH (H) GR1 200mm 450mm GR2 200mm 450mm B1 200mm 450mm B2 200mm 400mm B3 200mm 350mm B4 200mm 450mm CB 200mm 450mm BAR Ø LOCATION LEFT END SECTION MIDSPAN SECTION RIGHT END SECTION TOP BARS 5 - 16mmØ 3 - 16mmØ 5 - 16mmØ BOTTOM BARS 3 - 16mmØ 4 - 16mmØ 3 - 16mmØ TOP BARS 4 - 16mmØ 3 - 16mmØ 4 - 16mmØ BOTTOM BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ TOP BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ BOTTOM BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ TOP BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ BOTTOM BARS 2 - 16mmØ 3 - 16mmØ 2 - 16mmØ TOP BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ BOTTOM BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ TOP BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ BOTTOM BARS 3 - 16mmØ 5 - 16mmØ 3 - 16mmØ TOP BARS 4 - 16mmØ 4 - 16mmØ 4 - 16mmØ BOTTOM BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ TYPE STIRRUPS 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 175mm O.C. TO C.L. A SCHEDULE OF REINFORCED CONCRETE BEAMS @ ROOF LEVEL RB1 200mm 400mm RB2 200mm 400mm RBCB 200mm 400mm TOP BARS 3 - 16mmØ 2 - 16mmØ 3 - 16mmØ BOTTOM BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ TOP BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ BOTTOM BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ TOP BARS 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ BOTTOM BARS 2 - 16mmØ 2 - 16mmØ 2 - 16mmØ 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 10mm :1@50mm 12@100mm 5@150mm REST @ 200mm O.C. TO C.L. A 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA SHEET NO. : OWNER : PROJECT TITLE : S-7 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 07 09 SCHEDULE OF SLAB REINFORCEMENT SLAB NUMBERS THK TYPE S1 115 S2 BOTTOM REINFORCEMENT TOP REINFORCEMENT DISTRIBUTION SHORT SPAN (BENT UP) LONG SPAN (BENT UP) SS CONT. LS CONT. 2-Way #10 @ 180 #10 @ 180 -- #10 @ 180 #10 @ 180 115 2-Way #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 S3 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S4 115 2-Way #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 S5 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S6 115 2-Way #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 S7 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S8 115 2-Way #10 @ 180 #10 @ 180 -- #10 @ 180 #10 @ 180 S9 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S10 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S11 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S12 115 2-Way #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 S13 115 1-Way #10 @ 180 -- #10 @ 180 -- #10 @ 180 S14 115 2-Way #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 #10 @ 180 L/4 Ld L/4 250 L/4 400 400 STAIR DETAILS SCALE SHEET NO. : OWNER : PROJECT TITLE : 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA NTS S-8 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 08 09 A B C 3500 50 100 50 FULLY WELD 4175 50 2000 D 2" x 4" x 3 16 " C - PURLINS RAFTERS SPACED @ 500mm O.C. 1200 8 HT HT 1000 HT HT HT HT HT 6 HT HT 2300 12mm Ø SAG ROD NTS 1 " MS PLATE 4 2L 2" x 3" x 1 4" ANGLE BAR VERIFY T T 3 HT S-1 HT HT HT 2000 SCALE: HT HT HT HT HT B S-1 HT HT 925 925 VERIFY HT HT HT T HT 2650 DETAILS 2" x 4" x 3 16 " C - PURLINS CL T 2 CL HT HT HT T NTS HT HT 2850 A S-1 HT HT T 4 HT HT T 5 METAL FURRING, CEILING JOIST and CEILING HANGER HT HT SCALE: 4 - 12mm Ø x 350mm ANCHOR BOLT W/ NUT & WASHER 3" DIA. PVC PIPE DOWN SPOUT HT HT B S-1 AIR VENTILLATION PLAN HT HT HT HT HT 1 TYPICAL TRUSS DETAILS HT HT SCALE HT HT HT HT HT HT C D 4175 HT HT NTS VERIFY 7 HT 1" x 12" fascia board w/ SPANISH GUTTER CONCRETE BEAM (SEE STRUCTURAL DETAILS) 200mm x 300mm x 12mm THK. BASE PLATE 50 1 " BASE PLATE 4 12mm Ø BAR ANCHOR BOLT TRUSS BOTTOM CHORD 300 LONG SPAN RIB TYPE ROOF HT HT HT HT HT HT HT VERIFY T T TYPICAL HALF TRUSS DETAILS ROOF TRUSS PLAN SCALE NTS 1:100 SCALE 2-STOREY RESIDENTIAL MARK CHRISTIAN D. ESGUERRA SHEET NO. : OWNER : PROJECT TITLE : S-9 MR. MELCHOR L. LICUDAN CIVIL/STRUCTURAL ENGINEER PRC REG NO.: 0164558 EXPIRATION.: MARCH 21, 2024 PTR NO.: 7387127 DATE.: JANUARY 07, 2022 ISSUED AT: STA ROSA N.E. LOCATION : CAD BY : BRGY. BRGY. BANTUG CITY OF MUNOZ CHECKED BY : REVISION : 09 09