Fire Alarm Panel MBS-802 Instruction manual Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 CONTENTS Page OPERATING INSTRUCTION ............................................................................................. 4 Front panel ................................................................................................................. 6 Functional description ............................................................................................... 7 Fire alarm ....................................................................................................... 7 Fault alarm ..................................................................................................... 7 Fault in a loop .................................................................................... 7 System fault ....................................................................................... 8 Mains fault ......................................................................................... 8 Battery fault........................................................................................ 8 Fuse fault............................................................................................ 8 Earth fault .......................................................................................... 9 Disconnection of functions ........................................................................................ 9 Loops disconnection ...................................................................................... 9 Loops reconnection ........................................................................................ 9 Alarm bells .................................................................................................... 10 Control outlets ............................................................................................... 10 Door release ................................................................................................... 10 Parallel outlet ................................................................................................. 10 One-man-testing ........................................................................................................ 10 TECHNICAL SPECIFICATION .......................................................................................... 13 Main panel MBS-802 ................................................................................................ 15 Standard equipment / outlets ......................................................................... 16 Standard functions ......................................................................................... 16 Panel dimensions, standard............................................................................ 16 Panel, layout .................................................................................................. 18 Remote panel MFT-802 ............................................................................................ 18 Relay control unit PRM-802...................................................................................... 18 Mimic panel MMP-802 ............................................................................................. 19 Detector types ............................................................................................................ 19 Alarm devices ............................................................................................................ 19 System current consumption ..................................................................................... 19 INSTALLATION .................................................................................................................. 21 Planning guidelines ................................................................................................... 23 Panel mounting / dimensions..................................................................................... 23 Choice of cable .......................................................................................................... 23 Cable mounting.............................................................................................. 23 System drawing ......................................................................................................... 24 Terminal connections ................................................................................................ 25 LOOP/DETECTOR DATA SHEETS ................................................................................... 28 General detector/loop connections ............................................................................ 30 Optical smoke detector, type ORM-130/A .................................................... 31 Ionic smoke detector, type IRM-131/A ......................................................... 33 Heat detector for engine room, type STMV-70S / STKR-70/120S ............... 35 Heat detector for accomodation, type STM-70S / STR-70S ......................... 37 UV flame detector, type UFM-810/A ............................................................ 39 Manual callpoint for accomodation, type KR1, surface mount ..................... 41 Fike : 40782449 page 2 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Manual callpoint for accomodation, type KR1, flush mount ........................ 43 Manual callpoint for engine room, type KSR1 .............................................. 45 General alarm callpoint, type SMK-2S/GA ................................................... 47 ALARM AND CONTROL DEVICES ................................................................................. 49 Alarm bell for accomodation, type MBF-6WE/24 ........................................ 51 Alarm bell for engine room, type MSB6B24 w. base WB4, KB-46 ............. 53 Alarm siren for accomodation, type AL100LT ............................................. 55 Alarm siren for engine room, type SEC-1992/24 .......................................... 57 Door holder magnet, type GPT-AG ............................................................... 59 COMMISSIONING .............................................................................................................. 62 Start the system .......................................................................................................... 64 Functional test ........................................................................................................... 64 Test procedure ............................................................................................... 65 Extended test procedure................................................................................. 66 Maintenance .............................................................................................................. 67 General spare parts .................................................................................................... 68 Fuses .............................................................................................................. 68 Microprocessor .............................................................................................. 68 Circuit boards ................................................................................................ 68 Miscellanious ................................................................................................. 68 Fault finding .............................................................................................................. 69 System fault indication .................................................................................. 69 Earth fault ...................................................................................................... 69 Fuse fault ....................................................................................................... 69 Mains fault ..................................................................................................... 70 Battery fault ................................................................................................... 70 Loop fault....................................................................................................... 70 PROGRAMMING................................................................................................................. 72 General instructions ................................................................................................... 74 Programming standard outlets MBS-802 .................................................................. 74 Programming sheet for standard outlets ........................................................ 75 Fike : 40782449 page 3 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 OPERATING INSTRUCTION Fike : 40782449 page 4 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 5 of 57 98.02.11 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Front panel 2 6 13 1 Sca n a Se r vo t e k n ik k a s 17 7 4 Fire alarm panel MBS-802 3 5 8 15 12 16 9 10 11 14 19 20 18 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 3 digit display for showing activated fire or fault loop number Green Mains (Power) lamp Red lamp for System fault Yellow lamp for Loop disconnected Yellow lamp for Control func. disconnected Red window sign for Fire alarm Yellow window sign for Fault alarm Switch with indicator for Alarm bells disconn./conn. Switch with indicator for Control outlets disconn./conn. Switch with indicator for Parallel alarm disconn./conn. Switch with indicator for Door release disconn./conn. Door switch for warning of disconnected operation Switch for selecting Loop no. in the display Switch for Loop disconn./conn. together with switch 13 Yellow lamps for Mains-, Battery-, Fuse-, and Earth fault Switch for selecting One-man-testing Switch for Fault test Switch for Lamp test Switch for Panel reset Switch with indicator for Alarm silence Fike : 40782449 page 6 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Functional description The central unit's primary function is to provide both visual and audible alarms. To ensure that the system is always in perfect working condition, the panel monitors continuously all internal circuits and functions, and all cables and externally mounted equipment. Any irregularities in the operation will be displayed on the alarm panel with a visual and audible warning. The fire alarm panel is operated by eleven switches and a 3-digits LED display. When the panel door is locked and the panel is in normal operation, only the lamp marked Mains (Power) is illuminated. The operating switches is located behind the front door. However, the switch Alarm silence can be operated through a hole in the front door. The switches for disconnection has a yellow indicating lamp and the switch Alarm silence has a green lamp. Each operating switch has a specific function which is indicated with a text over the switch. Fire alarm is indicated with a red flashing sign reading Fire. The red digital number on the display shows the loop number. The alarm bells and the internal buzzer sound. The acoustic alarm can be silenced by pressing the switch Alarm silence. The red sign marked Fire will now light continuously. The digital display still shows the loop that originated the alarm. The panel is reset by opening the front lid and pressing the switch Panel reset. The fire alarm area must always be inspected to determine the reason for the fire alarm. During a fire, follow the instructions found beside the panel. Fault alarm is indicated with a yellow flashing sign reading Fault. The red digital number on the display shows the loop number and one of the LEDs behind the front lid is lit. The internal buzzer sounds. The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow sign marked Fault will now light continuously. The digital display still shows the loop number that originated the fault signal. Any fault must be corrected as soon as possible. Contact local electrician or manufacturer's representative. When the fault is corrected, the panel is reset by opening the front door of the panel and pressing the switch Panel reset. Note! If more than one loop are in fire or fault position simultaneously, the digital number display will show the loop numbers in sequence. The fault signal that was detected first is shown for 3 seconds and the following loops for 1.5 seconds with a 0.5 seconds break between each indication. Maximum 8 loops can be shown in one sequence. Fault in a loop is indicated with a yellow flashing sign reading Fault. The red digital number on the display shows the loop number. The internal buzzer sounds. The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow sign marked Fault will now light continuously. The digital display still shows the loop number that originated the fault signal. When the fault is corrected, the panel can be reset by opening the front lid and pressing the switch Panel reset. See section 'COMMISSIONING\Fault finding'. Fike : 40782449 page 7 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Note : Fire alarms are given priority over fault alarms. A fire alarm signal will cancel all fault alarms on the panel and only the fire alarm with loop number will be displayed. System fault System fault is indicated by a red flashing LED and an intermittent sound in the internal buzzer. This fault is extremely serious since the panel's microprocessor has ceased to function. Take immediate contact with the manufacturer for repair/service. Mains fault is indicated by a yellow flashing sign reading Fault and a LED Mains fault behind the front lid. The internal buzzer sounds. Mains fault is activated if the mains supply is interrupted, if the voltage drops under 185 VAC, or if the mains fuses are blown either in the panel or externally. The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow window will then light continuously. The LED Mains (power) goes off. When the fault is corrected, the panel can be reset by opening the front lid and pressing the switch Panel reset. See section 'COMMISSIONING\Fault finding'. Battery fault is indicated by the yellow flashing sign reading Fault and a LED Battery fault behind the front lid. The internal buzzer sounds. Battery fault is activated if an error occures with the battery or the battery cables, the battery voltage drops below 22V, or the battery fuses are blown either in the panel or externally. The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow window will then light continuously. When the fault is corrected, the panel can be reset by opening the front lid and pressing the switch Panel reset. See section 'COMMISSIONING\Fault finding'. Fuse fault is indicated by the yellow flashing sign reading Fault and a LED Fuse fault behind the front lid. The internal buzzer sounds. Fuse fault is activated if a fuse in one of the alarm outlets are blown or there is a breakage in a circuit. Following circuits are monitored: - Alarm outlets 1-4 - Door release outlet - Data outlet The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow sign Fault will light continuously. When the fault is corrected, the panel can be reset by opening the front lid and pressing the switch Panel reset. See section 'COMMISSIONING\Fault finding'. Fike : 40782449 page 8 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Earth fault is indicated by the yellow flashing sign reading Fault and a LED Earth fault behind the front lid. The internal buzzer sounds. Earth fault is indicated if the following cables come in contact with earth either directly or via a resistance less than 1 kohm : - Battery pole + or - Loop conductor A or B - Alarm outlet + or - Door release + or - Data outlet + or The acoustic alarm can be silenced by pressing the switch Alarm silence. The yellow sign will light continuously. When the fault is corrected, the panel can be reset by opening the front lid and pressing the switch Panel reset. See section 'COMMISSIONING\Fault finding'. Disconnection of functions It can be necessary to disconnect some of the functions in the panel during service of the system or activities like welding or other smoke generating work. Follow the procedure for disconnection and reconnection : (all switches are located behind the front door) Loops disconnection Press the switch Loop no (no. 13). The digital number display shows 'U-1'. Press the switch repeatedly until the display shows the loop number intended to be disconnected. Press the switch Loop Disconnection/Reconnection (no. 14). The yellow LED Loop disconnected (no. 4) indicates that the loop is disconnected. The LED Loop disconnected is always lit if any loop is disconnected. If the switch is pressed once more the loop is reconnected and the LED goes off. The same procedure is used for both disconnections and reconnections. If the switches remains untouched for more than 10 seconds, the panel is automatically reset to normal operation. Loops reconnection Reconnect a loop by pressing the switch Loop no until the correct loop is displayed and the LED Loop disconnected lights. Then press the switch Loop Disconnect/ Reconnect to reconnect the loop and the LED goes off. Note! If the switch Loop no is pressed for more than 1 second, the display will advance automatically at a rate of 10 loop numbers per second as long as the switch is pressed. When the display runs past the last loop number it starts from the beginning again. A disconnected loop is always energized during normal operation. If a loop is disconnected and the panel's front is closed, the internal buzzer will sound. The manual callpoints are active even if the loop is disconnected. Fike : 40782449 page 9 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Alarm bells Press the switch Alarm bells under Function disconnection. The yellow LED indicator lights. Alarm outlet 1-4 are now disconnected and the panel can be tested without activating the alarm bells. The internal buzzer sounds if the door is closed. Control outlets Press the switch Control outlets under Function disconnection. The yellow LED indicator lights. Control outlets 1-3 are now disconnected and the panel can be tested without activating the control outlets. The internal buzzer sounds if the door is closed. Door release Press the switch Door release under Function disconnection. The yellow LED indicator lights. The outlet for the door magnets is now energized and the panel can be tested without activating the fire door release outlet. The internal buzzer sounds if the door is closed. Parallel outlet Press the switch Parallel alarm under Function disconnection. The yellow LED indicator lights. The parallel outlet is now disconnected and the panel can be tested without activating the parallel outlet. The internal buzzer sounds if the door is closed. One-man-testing This function enables one person to perform a complete test of the fire alarm system, including smoke and other types of detectors, together with an alarm sound coverage test. Follow this procedure for starting one-man-testing : Press the switch One-man-testing. The digital number display shows 'E 0' to signify that the function is activated. Only one loop can be tested at a time. The other loops will operate normally and give fire alarms both visually and acoustically. The first activated detector automatically selects which loop is in test status. After this activation the display shows 'E 1' and the display will act as an alarm counter for the following activations. Each activation operates the main panel both visually and acoustically. The alarm outlets are activated for approx. 4 seconds and then automatically silenced. A delay period of 30 seconds are then initiated to enable the detector to reach normal status. During the test the display shows the number of activated fire alarms. One-man-testing is reset by pressing the switch Panel reset. The panel is automatically reset 20 minutes after the last registered alarm. Fike : 40782449 page 10 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 11 of 57 98.02.11 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 TECHNICAL SPECIFICATION Fike : 40782449 page 12 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 13 of 57 98.02.11 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Main panel MBS-802 The fire alarm panel MBS-802 is mounted in a painted steel cabinet with an anodized aluminium front. The cabinet is designed in four different sizes A, B, C, and D (see table on the next page). All cabinets are designed for wall mounting, but they can be equipped with a frame for flush mounting. The cabinets can also be mounted together in units containing the main panel and additional equipment. Sca n a Se r vo t e k n ik k a s Fire Fire alarm panel MBS-802 Fault The front is equipped with eleven manual switches for the operation of the system, a Fire and a Fault window, three red digits seven-segments LED display, and LEDs for various fault indications. Each switch, lamp, and LED are labelled with a text for operation/function. All switches, lamps, and LEDs are located on a main operating board (MBD-94610) mounted on the rear side of the front panel. Additionally, a charging rectifier board (MLK-82930) is mounted on the lower rear side of the front panel. Due to the serial regulation of the charging rectifier, the front panel will always be warm, and it can occasionally be heated to approx. 70 degrees Celsius. The panel also contains a main relay/terminal board (MCA-82920) with all terminal inlets for mains and battery, and outlets for loops, alarm bells, control functions, fire doors, fire- and fault contacts, and data transmission to external equipment. MBS-802 is delivered for fire detection loops with end-of-line resistors. The panel is built up in steps of four loops to the maximum of 96 loops. MBS-802 can also be equipped for 2-wire loops with return to the panel. The panel is built up in steps of four loops to the maximum of 96 loops. MBS-802 can additionally be equipped with a mix of end-of-line resistors and 2-wire/return loops in the same panel. The total number of loops are still 96. Due to microprocessor technology the panels are delivered with a large number of technical features as standard, and with a still larger amount of programmable options. Fike : 40782449 page 14 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Standard equipment / outlets Manual keyboard and three-digits display for the operation of the system. Red lamp for Fire / Yellow lamp for Fault / 4 LEDs for fault indications. Outlets : 4 fused and monitored alarm outlets. Output voltage 24 VDC - 2A. (EOL 1k). 1 fused and monitored output for door magnets; 24 VDC - 2A. 3 separate, NC/NO control outlets. Max. 250 VAC - 5A. 1 NC/NO parallel outlet. Max. 24 VDC - 1A. 1 NC/NO fault outlet. Max. 24 VDC - 1A. 1 fused and monitored data outlet for remote panels and add. equipment. Loops : Terminals for connecting 16 loops (EOL 3k3) or 8 loops with 2-wire/return. Terminals for automatic GENERAL ALARM (seven short - one long signal; on ships). Terminals for manual GENERAL ALARM (continuous signal). Supply : Terminals for connecting mains supply/earth 230 VAC. Double 2.0A fuses. Terminals for connecting the batteries 24V. Double 6.3A fuses. Automatic charging rectifier 230 VAC / 24 VDC - 5A. Standard functions Each loop can be disconnected from the front panel. Each loop can be tested individually from the front panel. Alarm outlets 2 min. delayed for smoke detectors/no delay for man. callpoints (on ships) One-man-testing enables only one person to check out the complete system The acoustic alarm is automatically silenced after 10 minutes. The fire door outlet is automatically released 5 min. after a mains interruption. The functions Alarm bells-, Control outlets-, Door release- and Parallel alarm can separately be disconnected with LED indications. The circuitry for monitoring Mains-, Battery-, Fuse-, and Earth Fault can be tested by a common test switch. The panel can handle max. 8 loops simultanously shown in sequence on display. MBS-802 can be prepared for the connection of zener barriers and Exi-detectors. Panel dimensions, standard The standard cabinets are used for the main panel MBS-802, the relay unit PRM-802, the mimic panel MMP-802, and the battery cabinets SAS-15 / SAS-24. CABINET A B C D MFT Fike : 40782449 Height [mm] 266 376 596 706 156 Width [mm] 396 396 396 396 260 page 15 of 57 Depth [mm] 150 150 150 150 73 Weight [kg] 11.7 13.2 16.2 17.9 1.2 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Panel, layout MAIN CONNECTION BOARD MCA-82920 MAIN PROCESSOR BOARD MBD-94610 1 CHARGING RECTIFIER MLK-82930 2 3 4 5 6 1. Terminals for manual general alarm 2. Terminals for common outlets 3. Terminals for loop outlets 4. Teminals for mains and battery connection 5. Transformer 230/28V - 8A 7 8 9 6. Cable for internal connection 7. Flat cable (50) MBC - MCA 8. Rectifier bridge 9. Flat cable (16) MBC - MLK Remote panel MFT-802 The remote panel MFT-802 is activated by a fire and/or a fault alarm. An alarm is shown on the front panel as described for the main panel. The remote panel can only receive information from the main panel (no system operation). The push button Alarm silence stops the local buzzer and Lamp test tests the lamps and the display on the remote panel. MFT-802 is delivered in an anodized aluminium unit prepared for both wall and flush mounting. The dimensions are H x W x D (mm) : 156 x 260 x 73 mm. MFT-802 consists of board MFU90998. All lamps and push buttons are labelled with function texts. The panel can also be delivered in an A cabinet. MFT-802 is connected to the main panel with a three wire cable (see section 'INSTALLATION\Choice of cable'). Relay control unit PRM-802 The relay control unit PRM-802 consists of a data transmission board TDX-88215 and relay board ORK-84968 with 8 x NC/NO contacts and/or SUK-82965 with 8 x 24 VDC outlets. The boards are connected together with a 16 conductor flat cable and a complete system contains max. 4 relay boards (32 relays). The fuses and outlets (end-of-line resistor 1k) on the SUK-board are monitored by the main panel. PRM-802 is programmable and the outlets can be activated by both fire and fault alarms with different type of signals and delays. The standard unit is mounted in an A cabinet and handles 8 outlets. Expanded systems are built in larger cabinets. PRM-802 is connected to the main panel with a three wire cable (see section 'INSTALLATION\Choice of cable'). Fike : 40782449 page 16 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Mimic panel MMP-802 The mimic panel MMP-802 consists of a steel cabinet, an anodized aluminium front with a silk screened picture of the ship including stairs and escape routes, red LEDs for indicating the fire zones, and a lamp test button. The LEDs are controlled by a data transmission board TDX-88215 and a LED-driver board MUP-83992. The boards are connected together with a 16 conductor flat cable. A complete system contains max. 4 LED-driver boards (128 LEDs). MMP-802 is programmable and the red LEDs are activated by fire alarms. A mimic panel is always delivered as a special product according to customer requirements. MMP-802 is connected to the main panel with a three wire cable (see section 'INSTALLATION\Choice of cable'). Detector types ORM-130/A IRM-131/A UFM-810/A STMV-70S STM-70S KIR101 KSR1 SMK-2S/GA STR-70S STKR-70S SMM-S : Optical smoke detector : Ionic smoke detector : UV flame detector : Heat detector, class 2, humid areas : Heat detector, class 2, dry areas : Manual callpoint, dry areas : Manual callpoint, humid areas : General alarm callpoint : Heat detector, without LED : Heat detector, with LED : Manual callpoint, humid areas MBS63PV24 MBS6B24 A100LT SEC-1992/24 : Alarm bell 24 VDC, dry areas : Alarm bell 24 VDC, humid areas : Alarm siren 24 VDC, dry areas : Alarm siren 24 VDC, humid areas Alarm devices System current consumption Equipment MBS-802-4/8 Exp. per. 8 loops PRM-802-8 PRM-802-x8 MMP-802-16 MMP-802-x16 MFT-802 Detectors Alarm bells Door magnets Total current Num. Normal mA/unit Total mA 195 60 100 10 120 10 150 0.03 0 40 In Alarm mA/unit 550 60 260 170 220 120 500 20 30 0 Total mA Ia Calculation of battery capacity CAP (Ah) = 18 x In + 0.5 x Ia Fike : 40782449 page 17 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 INSTALLATION Fike : 40782449 page 18 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 19 of 57 98.02.11 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Planning guidelines An fire alarm system MBS-802 contains advanced electronic technology. To avoid problems and delays, it is of the utmost importance that the system is carefully planned before the installation starts. Check that all drawings and instruction manuals that will be needed during the installation are available at the plant. It is also important that all electricians get familiar with the system and the delivered material. They must examine one item of each kind and determine how to install the units and the colour-coding of the cables. Panel mounting / dimensions W1 H2 H1 0 W2 Cabinet (IP42) H1 [mm] W1 [mm] H2 [mm] W2 [mm] A 266 396 180 360 B 376 396 290 360 C 596 396 510 360 D 706 396 620 360 MFT 156 260 82 246 * The battery cabinets weight : SAS-15 = 18.9kg and SAS-24 = 25.0kg Depth [mm] 150 150 150 150 73 Weight [kg] 13.2 * 15.4 18.0 20.0 1.2 Choice of cable Only high-quality cable must be used. The following table shows the recommendations : Equipment Mains 220 VAC Battery 24 VDC Earth Alarm and control outlets Loops Data outlet Multi - cables Type of cable RXOP 2 x 1.5 mm2 RXOP 2 x 2.5 mm2 (min) PN 6.0 mm2 RXOP 2 x 1.5 mm2 RXOP 2 x 1.0 mm2 RXOP 3 x 1.5 mm2 RXOP X x 1.5 mm2 Cable mounting It is of the utmost importance that all cables are connected correctly to the terminals in the panels, detectors and other equipment connected to the fire alarm system. All cables must be connected to the terminals with end sleeves in order to avoid short circuiting between cable cores. Ensure that the end sleeves fit the cables (dimension). Avoid connecting two or more cables to the same terminal. If nescassary use an end sleeve with sufficient size for two (or more) cables. When dismanteling a cable, use a shrink tube at the cable end in order to avoid mechanical damage. Never use tape for the insulation of cables. Fike : 40782449 page 20 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 System drawing MAIN PANEL MBS-802 Ref. drawing MBS-KL BATTERY MAINS 6.0 Earth 24V EARTH 2x1.5 230V MAINS 230V 2x2.5 2x1.5 Ref. T001 BATTERY 24V 1 2 ALARM BELL OUTLETS 2x1.5 3 2x1.5 5 ALARM OUTLET 1-4 4 6 2x1.5 7 2x2.5 9 8 FIRE DOOR OUTLETS 3x1.5 DOOR MAGNETS 10 11 12 13 3x1.5 CONTROL OUTLETS 14 CONTROL OUTLET 1-3 15 16 3x1.5 Ref. T002 17 18 19 REMOTE PANEL MFT-802 - 20 D 21 + 22 3x1.5 ALARM OUTLET 3x1.5 FAULT ALARM OUTLET 3x1.5 20 23 PARALLEL ALARM 24 25 26 FAULT ALARM 27 28 eol D D 2x1.0 B A B DETECTION LOOPS REMOTE PANEL 21 22 D : Detectors, man.callpoints GA : General alarm callpoint eol : End-of-line resistor A B A eol D D 2x1.0 B A eol GA 2x1.0 For ships only. B 1 2 DETECTION Ref. T003 LOOPS 14 15 16 A File : MBS-802 ORG Rev. 01 DWG. DWG. Fike : 40782449 31.07.95 ST ISS. 16.09.97 TS ISS. 31.07.95 ST APP. APP. page 21 of 57 31.07.95 ST DATA SHEET NO. SC-100-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Terminal connections Note! The maximum load in normal operation must not exceed 2A or 4A in alarm operation. It is of the utmost importance to follow the wiring diagrams when all external equipment are connected to the panel. A 28 NO 27 C 26 NC 16 FAULT CONTACT B A 15 B 25 NC FUSES 2A SLOW BLOW 24 C 23 NO 22 + 21 D 20 - PARALLEL ALARM A 14 B A REMOTE PANEL 13 B A 12 B 19 NC C A LOOP CONNECTION 18 CONTROL OUTLET 3 17 NO 16 NC 15 C GEN.AL. CONTROL OUTLET 2 11 B A 10 B A 9 B A 8 B A 14 NO 7 B 13 NC 12 FUSES 2A SLOW BLOW C A CONTROL OUTLET 1 11 NO 10 + 9 - MAIN TERMINAL BOARD MCA-82920 6 B A 5 B A 4 DOOR MAGNETS B A 3 B A 8 + 7 - 6 + 5 - 4 + 3 - 2 + 1 - ALARM OUTLET 4 2 B A 1 ALARM OUTLET 3 B BATTERY + FUSES 6.3A ALARM OUTLET 2 24V ALARM OUTLET 1 MAINS - SLOW BLOW FUSES 2.0A SLOW BLOW EARTH Mains connection The terminals are marked "MAINS". Standard 230 VAC +10/-15 %, 47-63Hz. Other specifications to order. Power max. 200W. The inlet is fused with 2 x 2.0A slow blow. Battery connection The terminals are marked "BATTERY + 24V -". Charging voltage pre-adjusted to 27.0 VDC. Add 60 mA for each additional 8 loops. The inlet is fused with 2 x 6.3A slow blow. Alarm outlets 1-4 The terminals are marked "+ ALARM OUTLET 1-4 -". Alarm outlet no. 1 gives a continuous signal. Outlets 2-4 gives as standard an intermittent signal with a signal period of 3.2 seconds. On ships outlets 2-4 gives an continous signal. Maximum current draw for each outlet is 1A. The outlets are fused with 2 x 2.0A slow blow. Fike : 40782449 page 22 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Control outlets 1-3 The terminals are marked "CONTROL OUTLET 1-3 NC/C/NO". Potensial free change over contacts which are activated by fire alarm. Max. current draw 250 VAC - 5A. Door release outlet The terminals are marked "+ DOOR MAGNETS -". Normally voltage 24 VDC. Voltage is cut off during fire alarm and more than 5 minutes mains interruption. Max. current draw is 1A. The outlet is fused with 2 x 2.0A slow blow. Parallel alarm outlet The terminals are marked "PARALLEL ALARM NC/C/NO". Potensial free change over contact activated by fire alarm. Max. current draw 24 VDC/AC - 1A. Fault outlet The terminals are marked "FAULT CONTACT NC/C/NO". Potensial free change over contact activated by fault alarm. Max. current draw 24 VDC/AC - 1A. Remote panel outlet The terminals are marked "REMOTE PANEL + / D / - ". Three terminal outlets (+24V, D, 0V). Data is transmitted in serial form (300 baud). The outlet is fused with 2x 2.0A slow blow. Loop outlets The terminals for the loops are marked with "A and B - Loop X". The loop cable starts in the panel and connects all detectors and manual callpoints in parallel. The loop cable is ended in the last detector with an end-of-line resistor 3k3. Manual general alarm inlet The terminals are marked "GEN. ALARM". The general alarm push button with one closing contact is connected to the terminals. When the push button is activated, the alarm outlets 1-4 in the panel gives a continuous signal. Automatic general alarm inlet The terminals are marked "GEN. ALARM". The terminal inlet for this function is always the last loop in the panel. The general alarm push button with one closing contact is connected to the terminals. When the push button is activated, the alarm outlets 1-4 in the panel gives a repetetive signal with seven short and one long signal (standard on ships) ev. continous signal. Fike : 40782449 page 23 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 LOOP/DETECTOR DATA SHEETS Fike : 40782449 page 24 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 25 of 57 98.02.11 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 General detector/loop connections A+ 1 B- SMOKE DETECTOR TYPE ORM-130/A TYPE IRM-131/A 2 5 A+ 4 B- A A+ B B- CONVENTIONAL LOOP A B A+ B- HEAT DETECTOR L+ TYPE STMV-70S L- A+ B- A B A+ B- L- A B A B 1 2 5 STMV-70S A B L+ L- 4 HEAT DETECTOR TYPE STKR-70S L+ A+ B- ORM-130/A HEAT DETECTOR TYPE STM-70S A+ B- L+ L- KR1 A+ B- A B A+ B- 2 A+ HEAT DETECTOR TYPE STR-70S B- 1 5 4 A+ B- A+ B- UV FLAME DETECTOR TYPE UFM-810/A ORM-130/A 1 ORM-130/A 1 2 2 5 4 A+ B- MANUAL CALLPOINT TYPE KR1 A+ B- 1 2 3 A+ B- 5 4 MANUAL CALLPOINT TYPE KSR1 A+ A+ B- B- MANUAL CALLPOINT A+ B- 1 2 EOL 1A TYPE SMM-1S A B STR-70S GENERAL ALARM CALLPOINT SMK-2S/GA EOL 2A EOL The end-of-line resistor must be moved to the end of the loop / last detector. File : GENCON_E ORG Rev. 02 DWG. 20.07.94 ST ISS. DWG. 10.10.96 TS ISS. Fike : 40782449 20.07.95 ST APP. APP. page 26 of 57 20.07.94 ST DATA SHEET NO. SC-101-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Optical smoke detector, type ORM-130/A w. base 143A, 143VT, 143UH 122.0 92.0 106.0 42.0 40.0 143 UH 32.5 143VT PG16 114.0 3 5 4 2 6 143VT 3 4 143UH 145.0 ø6.0 1 1 2 5 6 PG16 3 Shield not required 2 LOOP A 1 B 2 Sc 3 4 143A REMOTE LAMP 1 ø3.8 EOL 4 5 B 5 A 6 Sc 6 LOOP 60.0 80.0 EOL The end-of-line resistor must be moved to the end of the line / last detector (value - see Instruction Manual) TECHNICAL DATA ORM-130A OPERATING VOLTAGE CURRENT - NORMAL 24VDC +/-4V 0.1 mA 20 mA CURRENT - ALARM PARALLEL IND. ENVIRONMENT TEMP. PROTECTION WEIGHT ART. NO. 143A 143A 143VT 143UH 73.0 max. 150 mA -20/+80 0 C IP54 ORM-130A IP42 50 g 14540 100 g 14220 IP55 340 g 14545 LED IP42 130 g 14543 File : ORM130A ORG Rev. 02 DWG. 05.05.94 ST ISS. DWG. 09.07.96 TS ISS. Fike : 40782449 05.05.94 ST APP. APP. page 27 of 57 05.05.94 ST DATA SHEET NO. DK-001-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Ionic smoke detector, type IRM-131/A w. base 143A, 143VT, 143UH 122.0 92.0 106.0 42.0 40.0 143 UH 32.5 143VT PG16 114.0 3 5 4 2 6 143VT 3 4 143UH 145.0 ø6.0 1 1 2 5 6 PG16 3 Shield not required LOOP 2 A 1 B 2 Sc 3 4 143A REMOTE LAMP 1 ø3.8 EOL 4 B 5 A 6 Sc 5 6 LOOP 60.0 80.0 EOL The end-of-line resistor must be moved to the end of the line / last detector (value - see Instruction Manual) TECHNICAL DATA IRM-131/A OPERATING VOLTAGE CURRENT - NORMAL 24VDC +/-4V 0.1 mA 20 mA CURRENT - ALARM PARALLEL IND. ENVIRONMENT TEMP. PROTECTION WEIGHT ART. NO. 143A 143A 143VT 143UH 73.0 max. 150 mA -20/+80 0 C IP54 IRM-131/A IP42 50 g 14540 100 g 14219 IP55 340 g 14545 LED IP42 130 g 14543 File : IRM131A ORG Rev. 01 DWG. 05.08.95 ST ISS. DWG. 23.08.96 TS ISS. Fike : 40782449 05.08.95 ST APP. APP. page 28 of 57 05.08.95 ST DATA SHEET NO. DK-010-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Heat detector for engine room, type STMV-70S / STKR-70/120S FOR PG16 FOR PG16 FOR PG16 68.0 77.0 FOR PG16 77.0 FOR PG16 62.0 A B L+ L- Sc Sc A A B B CONV. LOOP CONV. LOOP EOL EOL The joint for the screen must be isolated inside the unit Remote lamp The screen is not required on conventional loops. TECHNICAL DATA The end-of-line resistor must be moved to the end of the loop/last detector (value - see Instr. manual) STKR-70/90/120S STMV-70S 24 VDC 0.3 mA 24 VDC 0.35mA OPERATING VOLTAGE CURRENT - NORMAL CURRENT - ALARM PARALLEL INDICATION ENVIRONMENT TEMP. PROTECTION 25 mA max.50 mA -20/+70 0 C IP66 70 g 14560-62 WEIGHT ART. NO. 25 mA max.50 mA -20/+70 0 C IP66 70 g 14565 File : STMV70S ORG Rev. 01 DWG. 18.02.94 ST ISS. DWG. 28.10.94 ST ISS. Fike : 40782449 18.02.94 ST APP. APP. page 29 of 57 18.02.94 ST DATA SHEET NO. DK-002-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Heat detector for accomodation, type STM-70S / STR-70S 5.0 55.0 10.0 77.0 A S Servoteknikk OSLO-NORWAY 33.0 83.0 LAY OUT A A B A B A B B STM-70 STR-70S CONNECTIONS LOOP A A A B B B EOL A A B STR-70S STM-70 TECHNICAL DATA STM-70 STR-70S OPERATING VOLTAGE 24 VDC 24VDC CURRENT - NORMAL 0.3 mA 0 mA CURRENT - ALARM 25 mA 100 mA ENVIRONMENT TEMP. -20 to +550C -20 to +55 0C ALARM TEMPERATURE Grade 2/60 Grade 3/70 IP22 IP22 WEIGHT 50 g 50 g ART. NO. 14553 14550 PROTECTION B LOOP EOL The end-of-line resistor must be moved to the end of the loop/last detector. (value - see Instr.manual) File :STM-70S ORG Rev. 03 DWG. 24.08.94 ST ISS. DWG. 28.10.94 ST ISS. Fike : 40782449 24.08.94 ST APP. APP. page 30 of 57 24.08.94 ST DATA SHEET NO. DK-003-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 UV flame detector, type UFM-810/A w. base 143A, 143VT, 143UH 122.0 92.0 106.0 42.0 40.0 143 UH 32.5 143VT PG16 114.0 3 5 4 6 143VT 3 ø6.0 2 4 145.0 143UH 1 5 1 2 6 PG16 3 Screen not required LOOP 2 A 1 B Sc 2 143A REMOTE LAMP 3 4 1 ø3.8 EOL 4 5 B 5 A 6 Sc 6 LOOP 60.0 EOL 80.0 The end-of-line resistor must be moved to the end of the line / last detector (value - see Instruction Manual) TECHNICAL DATA UFM-810/A OPERATING VOLTAGE CURRENT - NORMAL CURRENT - ALARM PARALLEL INDICATION ENVIRONMENT TEMP. PROTECTION WEIGHT ART. NO. 24VDC +/-4V 2.3 mA 20 mA max. 40 mA -20/+80 0 C IP54 100 g 14546 143A 143A 143VT 143UH 73.0 IP42 50 g 14540 IP55 340 g 14545 UFM-810/A IP42 130 g 14543 LED Only 1 UFM per loop File : UFM810A ORG Rev. 02 DWG. 29.08.94 ST ISS. DWG. 09.07.96 TS ISS. Fike : 40782449 29.08.94 ST APP. APP. page 31 of 57 29.08.94 ST DATA SHEET NO. DK-004-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Manual callpoint for accomodation, type KR1, surface mount BRANN 87.0 KNUS GLASSET TRYKK HER 87.0 FIRE PRESS HERE BREAK GLASS AS Servoteknikk 19.5 KR1 87.0 87.0 60.0 SR3T-P .0 50 87.0 19.5 BLUE RED TECHNICAL DATA KR1 OPERATING VOLTAGE CURRENT-NORMAL CURRENT-ALARM ENVIRONMENT TEMP. 24 VDC 0.7 mA 0.7 mA PROTECTION WEIGHT ART. NO. SR3T-P -30 to +70 o C IP44 14006A 14005A LOOP B B A A LOOP File : uten_k_e ORG Rev. 04 DWG. DWG. Fike : 40782449 05.05.94 ST ISS. 11.10.96 TS ISS. 05.05.94 ST APP. APP. page 32 of 57 05.05.94 ST DATA SHEET NO. DK-005-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Manual callpoint for accomodation, type KR1, flush mount BRANN 87.0 KNUS GLASSET TRYKK HER 87.0 FIRE PRESS HERE BREAK GLASS AS Servoteknikk 19.5 87.0 KR1 30.5 89.0 ETT/1-P 40.0 60.0 55.0 87.0 25.0 3.5 89.0 3.5 60.0 79 .0 11.0 Panel cut out for desk mount. BLUE TECHNICAL DATA KR1 OPERATING VOLTAGE CURRENT-NORMAL CURRENT-ALARM ENVIRONMENT TEMP. 24 VDC 0.7 mA 0.7 mA PROTECTION WEIGHT ART. NO. RED ETT/1-P -30 to +70 o C IP44 14007A 14005A Total height above mounting surface: 30.5 mm LOOP A LOOP B A B File : innf_k_e ORG Rev. 04 DWG. DWG. Fike : 40782449 05.05.94 ST ISS. 10.10.96 TS ISS. 05.05.94 ST APP. APP. page 33 of 57 05.05.94 ST DATA SHEET NO. DK-005-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Manual callpoint for engine room, type KSR1 60.0 BRANN FIR E KNUS GLASSET TRYKK HER 170.0 PRESS HERE BREAK GLASS AS Servoteknikk 74.0 1 2 74.0 3 ø5.0 Shield wires connected to terminal in base unit. LOOP 123.0 A B A LOOP B 1 2 3 TECHNICAL DATA KSR1 OPERATING VOLTAGE 24 VDC CURRENT - NORMAL 0.7 mA 0.7 mA CURRENT - ALARM ENVIRONMENT TEMP. PROTECTION WEIGHT ART. NO. -30 to +70 0 C IP 65 430 g 14008 File : VANN_K_E ORG Rev. 04 DWG. 15.06.93 ST ISS. DWG. 23.08.96 TS ISS. Fike : 40782449 15.06.93 ST APP. APP. page 34 of 57 15.06.93 ST DATA SHEET NO. DK-006-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 General alarm callpoint, type SMK-2S/GA 45.0 93.0 M3 93.0 54.0 INLAY MOUNTING 70.0 GENERAL ALARM SURFACE MOUNTING Ø 4.5 Ø 4.5 54.0 17.0 INLAY MOUNT. FRAME P209205 60.0 FLUSH MOUNT. EOL EOL The end-of-line resistor must be moved to the end of the loop. (value-see Instr. manual) A GENERAL ALARM B SMK-2S/GA TECHNICAL DATA 24 VDC OPERATING VOLTAGE CURRENT - NORMAL 3 mA CURRENT - ALARM 25 mA 0 ENVIRONMENT TEMP. -10 to +70 C IP42 PROTECTION WEIGHT 140 g ART. NO. 14004 File : SMK2SGA ORG Rev. 02 DWG. 21.02.94 ST ISS. DWG. 28.10.94 ST ISS. Fike : 40782449 21.02.94 ST APP. APP. page 35 of 57 21.02.94 ST DATA SHEET NO. DK-008-E ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 ALARM AND CONTROL DEVICES Fike : 40782449 page 36 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 37 of 57 98.02.11 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Alarm bell for accomodation, type MBF-6WE/24 DIMENSIONS 150.0 MOUNTING 48.0 CONNECTIONS 85.7 (Installation box) - + + 85.7 Alarm outlet from panel + - + - Alarm outlet next bell + - Alarm outlet next bell ø4/5 Field wiring max. 2.5mm2 ø6/9 Remove the gong 60.0 Alarm outlet from panel SPECIFICATIONS TECHNICAL DATA MBF-6WE OPERATING VOLTAGE ENVIRONMENT TEMP 24 VDC 25 mA -10 to +50 O C SOUND OUTPUT 97 dB/m(A) CURRENT + - - + IP 21 PROTECT IO N WEIGHT 720 g 13009 ART. NO. (Wall mounting) VERTICAL MOUNTING ONLY ORG Rev. 03 DWG. 10.05.94 ST ISS. DWG. 30.08.97 ST ISS. Fike : 40782449 10.05.94 ST APP. 10.05.94 ST DATA SHEET NO. APP. page 38 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Alarm bell for engine room, type MSB6B24 w. base WB4, KB-46 67.0 150.0 BRANN 120.0 FIRE KB-46 86.0 ø7.0 WB4 133.0 60.0 ø3.5 M4.0 PG13.5 122.0 127.0 146.0 40.0 15.0 ALARM OUTLET (main panel) Red + + - Black MSB6B24 w. WB4 MSB6B24 w. KB-46 OPERATING VOLTAGE 24 VDC 24 VDC CURRENT 30 mA TECHNICAL DATA 30 mA o -20 to 70 C ENVIRONMENT TEMP o -20 to 70 C IP 54 IP40 WEIGHT 1.24 kg 1.0 kg ART. NO. 13017 13015 PROTECTION ALARM OUTLET (expansion) VERTICAL MOUNTING ONLY File : MSB6B24 ORG Rev. 02 DWG. 10.05.94 ST ISS. DWG. 19.08.97 TS ISS. Fike : 40782449 10.05.94 ST APP. APP. page 39 of 57 10.05.94 ST DATA SHEET NO. OA-002-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Alarm siren for accomodation, type AL100LT 114.0 79.0 85.0 170.0 83.0 98.0 - 20dB Volume control SUPPLY 12-48VDC + Link 1-2 : Slow alternating Link 2-3 : Whoop No link : Fast alternating TECHNICAL DATA A100LT OPERATING VOLTAGE ALARM CURRENT ALARM SOUND 24 VDC 320 mA 102dB/1m ENVIRONMENT TEMP. -25 to +55 C IP55 PROTECTION WEIGHT ART. NO. o 480 g 13164 File : AL100LT ORG Rev. 00 DWG. DWG. Fike : 40782449 14.09.94 ST ISS. ISS. 14.09.94 ST APP. APP. page 40 of 57 14.09.94 ST DATA SHEET NO. OA-006-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Alarm siren for engine room, type SEC-1992/24 75.0 103.0 P P 91.0 P DRY AREAS 91.0 IP65 P P = HOLES FOR PG13.5 NO. ALT TONES 800/970Hz - 1/4Hz 2 SWEEPING 800/970Hz - 7Hz 14 14 3 5 SWEEPING 800/970Hz - 1Hz CONTINUOUS - 2850Hz SWEEPING 2400 - 2850 Hz / 7Hz 14 14 4 6 SWEEPING 2400 - 2850Hz / 1Hz 4 4 Ø 5.0 50.0 60.0 Com + + Volume adj. 1 - - mA dB/1m 11111 18 104 11110 11101 19 18 105 105 11100 29 116 11011 23 23 114 113 7 SLOW WHOOP 14 11010 11001 15 103 8 SWEEP 1200 - 500Hz / 1Hz 14 11000 16 103 9 ALT TONES 2400 / 2850Hz - 1Hz 4 10111 27 113 10 INT. TONES 970Hz / 1Hz 14 10110 12 106 11 ALT. TONES 800 / 970Hz - 1Hz 14 10101 INT. TONES 2850Hz / 1Hz 4 10100 18 20 105 12 13 970Hz - 1/4sec. ON - 1.0sec. OFF 14 10011 7 116 102 14 15 16 CONTINUOUS 970Hz 554Hz / 100ms - 440Hz / 400ms 14 14 10010 10001 20 12 107 99 INT. 660Hz / 150ms - ON / OFF 16 INT. 660Hz / 1.8sec. - ON / OFF 17 10000 01111 9 17 12 87 91 18 19 INT. 660Hz / 6.5sec.ON - 13sec.OFF 18 CONTINUOUS 660Hz 19 01110 01101 20 21 ALT 554Hz / 440Hz / 1Hz 20 01100 INT. 660Hz / 1Hz 21 01011 9 87 22 INT. 2850Hz / 150ms ON - 100ms OFF 01010 SWEEP 800 - 970Hz / 50Hz 19 18 113 23 24 SWEEP 2400 - 2850Hz / 50Hz 22 23 24 2 - 2nd CODE TONES 1 01001 01000 Dip switch signal programming OPERATING VOLTAGE CURRENT (nom.) FREQUENCY TOL. VOLUME CONTROL OUTLET SIGNALS ALARM OUTLET (Main panel) + + - - ALARM OUTLET (Expansion) 105 112 SEC-1992 24VDC 30 mA +/- 15% Pot.meter DIP switch ENVIRONMENT TEMP. PROTECTION 90 95 22 TECHNICAL DATA - 90 10 14 13 o -20 to +55 C IP65 WEIGHT 360 g ART. NO. 13189 File : SEC1992 ORG Rev. 02 DWG. 16.09.93 ST ISS. DWG. 02.11.94 ST ISS. Fike : 40782449 16.09.93 ST APP. APP. page 41 of 57 16.09.93 ST DATA SHEET NO. OA-004-E ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Door holder magnet, type GPT-AG 52.0 42.0 Ø 6.3 52.0 116.0 Manual release button Plastic glands (PG 11) Plastic glands (PG 11) 40.0 Ø 6.3 60 0 60.0 40.0 50.0 60.0 GPT DOOR MAGNET + OUTLET (main panel) + EXPANSION - TECHNICAL DATA GPT-AG OPERATING VOLTAGE 24 VDC CURRENT 40 mA PROTECTION IP54 WEIGHT 73 g HOLDING POWER 60 kp ART. NO. 13401/13402 File : GPT-AG ORG Rev. 00 DWG. DWG. Fike : 40782449 10.05.94 ST ISS. ISS. 10.05.94 ST APP. APP. page 42 of 57 10.05.94 ST DATA SHEET NO. SA-002-E ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 43 of 57 98.02.11 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 COMMISSIONING Fike : 40782449 page 44 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 45 of 57 98.02.11 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Start the system During installation of the system all voltage supplies must be disconnected. When all cables for the complete fire alarm system are connected to the main panel, the system can be started by the following procedure : remove the mains- and battery fuses from the terminal inlets in the main panel connect both mains and battery voltage to the terminal inlets in the panel measure the voltage on the terminal inlets; mains / battery insert the battery fuses first and then the mains fuses in the fused terminal inlets Only the lamp Mains (Power) is lit. Now the system is in normal operation and it can be tested according to 'Functional test' below. Functional test Not all operational disturbances result in a fault alarm on the panel. To ensure that the system is always fully operational it must be tested at regular intervals. To ensure reliable operation of the fire alarm system a complete test must be carried out at 2 weeks intervals. Before starting the test, open the front door of the panel and press the following switches under Function disconnection : Alarm bells Control outlets Door release Parallel alarm Check that the indicators for each switch is lit. If the front door is closed in this position, the internal buzzer will sound. It is now possible to test the complete fire alarm system without activating the alarm bells or external equipment connected to the panel. Fike : 40782449 page 46 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Test procedure 1. Operate the switch Lamp test. All lamps will light except the green lamp in switch Alarm silence. All lamps except the signs Fire and Fault are LEDs with an expected life time of more than 10 years. The lamps in the Fire and Fault signs are tripled. Any reduction in light intensity must be corrected as soon as possible by changing lamps. 2. Press the Fault test switch and keep it pressed for at least 5 seconds. After approx. 4 seconds the buzzer sounds, the yellow sign Fault flashes, and the lamps Mains-, Battery-, Fuse- and Earth fault light. If the mains supply is connected, the Mains (Power) lamp goes off after approx. 30 seconds and the fault relay is activated. Press the switch Alarm silence. The buzzer stops and Fault sign lights continuously. The four yellow lamps are still lit. Reset the panel by pressing the switch Panel reset. 3. Check that the indicators for the switches Alarm bells-, Control outlets-, Door release and Parallel alarm disconnection still light. Press the switch Loop no once. The digital number display shows 'U-1'. Then press the switch One-man-testing for approx. 2 seconds to simulate fire alarm on loop no.1. The buzzer sounds and the red sign Fire flashes. Press the switch Alarm silence. The buzzer stops and the Fire sign lights continuously. Reset the panel by pressing the switch Panel reset. 4. The next step is to test the alarm bells. Press the switch Alarm bells disconnection and the indication lamp goes off. Check that the functions Control outlets, Door release and Parallel alarm are still disconnected. Repeat the test in step 3. The alarm bells are activated together with the optical and acoustical alarm on the panel. Follow the reset procedure in step 3. 5. The next step is to test the automatic fan stop, release of fire doors/dampers, and the operation of the parallel alarm. Press the switches Control outlets, Door release and Parallel alarm and the indication lamps go off. Repeat step 3. All outlets are activated together with the alarm bells. Follow the reset procedure in step 3. When the tests are completed, only the Mains (Power) lamp lights. Note! The buzzer will be activated if the panel door is closed with any of the outlet functions disconnected. Fike : 40782449 page 47 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Extended test procedure Upon starting the system and consequently every 6 months, the following test should be carried out by the manufacturer, his representative or other authorized personal : 6. Activate at least 1 thermal detector, 1 manual callpoint, and 1 smoke detector on each loop. During commissioning, after the installation of the system, all smoke detectors must be tested. 7. Check that the fire alarm is activated in the panel and that all signs are correctly displayed. 8. Check that all alarm bells are activated and that the alarm sound in the covered area is sufficient. 9. Check that all fire doors/dampers are released and that the ventilation fans are stopped (options). 10. Remove the battery fuses. Check the capacity of the batteries by connecting a batterytester. The voltage should be 27.0V for gas-tight lead accumulators. 11. Remove a mains fuse. Observe the Mains fault indication. Insert the fuse again and reset the panel. 12. Remove the battery fuses. Observe the Battery fault indication. Check the output voltage of the charging rectifier to 27.0V. Adjust if nescessary. Note that the battery fuses are inserted before adjusting charging voltage. 13. Connect the negative battery pole to earth. Observe the Earth fault indication. Remove the connection and reset the panel. Connect the positive battery pole to earth. Observe the Earth fault indication. Remove the connection and reset the panel. Note! On systems with zenerbarrieres the negative battery fuse will blow if the positive pole is connected to earth to prevent false fire alarms. 14. Remove one of the fuses for the alarm bell outlets. Observe the Fuse fault indication. Insert the fuse again and reset the panel. Repeat the test for all the fuses for the alarm bell outlets. 15. The extended test is now completed and only the lamp Mains (Power) lights. Fike : 40782449 page 48 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Maintenance The degree of protection offered by this system depends on the awarenes of its operators. It is essential that the person in charge is able to interpret the various alarm indications and consequently take appropriate action. The routine checks listed below should be carried out at regular intervals to ensure reliable operation of the system. Battery Check the battery poles every 14 days for corrotion and bad connections. Check also if the cables are damaged. Keep the batteries clean! Detectors Accumulating dust and paint in smoke detectors may cause false alarms. Therefore, check the detectors at regular intervals and replace them with new detectors when necessary. Replace malfunctioning detectors as soon as possible. Make sure that furnishing, storing etc. have not reduced the open space under the detectors to less than 0.5 meters. Manual callpoints Check the glas window of all manual callpoints. Make sure that all are visible and easily accessible. Alarm bells/device Check that all alarm bells, sirens, and horns are not cracked or damaged otherwise. All alarm devices must be tested at regular intervals. Additional equpiment All parts of the fire alarm system must always be kept free of dust, paint, and dirt. Fike : 40782449 page 49 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 General spare parts Fuses Art. no. 63245 63275 63245 Type Mains fuses Battery fuses Alarm fuses Art.no 51449 Type N80C51GB Art.no. 34489 34300 34305 34365 34409 34312 34313 34366 34387 34345 34341 Type MBD-94610 MCA-82920 MLK-82930 ELB-84940 STB-89410 DCC-82960 SUK-82965 ORK-84968 TDX-88215 MUP-83992 APE-83710 34386 GNU-88205 Art. no. 61310 53115 63605 66821 Type Type 4473 FB2502 120 758 S6031 Key 809 Description : 2.0A slow blow (5x20mm) : 6.3A slow blow (5x20mm) : 2.0A slow blow (5x20mm) Microprocessor Description Circuit boards Description : Main board for 16 loops : Main terminal board with relays : Charging rectifier/power supply : Loop circuit board for 16R loops : Terminal board for 16R loops : Loop circuit board for 8D loops : Relay board with 8 x 24V outlets : Relay board with 8 x NC/NO outlets : Serial data receiver board : Driver board for mimic panel 32 LEDs : Address-buffer board for panels with more than 32 loops : Data comm. board RS232C/RS422 Miscellanious Fike : 40782449 Description : Trafo 220V / 28V - 8A : Rectifier bridge 25A 200V : Lamp bulbs 24V 3W : Red plastic key page 50 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Fault finding This section gives a brief instruction in fault findings in the fire alarm system. The instruction only covers the minimum efforts necessary to detect a fault. We recommend that the manufacturer must be contacted if the fault has not been detected or found within one hour. System fault indication The microprocessor performs a continuous verification on the program memory. If the verification is not correct a System fault signal will follow. This fault indicates a serious fault in the panel's microprocessor. The panel is out of function. Contact the manufacturer without any delay. Earth fault An earth fault is likely to be found outside the panel. The method of elimination is used to locate the fault. Use the following procedure : Remove the alarm outlets one by one by removing both fuses on the main terminal board. Press the switch Panel reset each time. When the fault is reset in the panel, the correct wire/outlet has been found. Continue the search for earth connections on the installation. If not effective, proceed Remove the loop wires one by one from the terminal outlets. Press the switch Panel reset each time. When the fault is reset in the panel, the correct wire/outlet has been found. Continue the search for earth connections on the installation. If not effective, proceed Remove the door release wires from the main terminal board. Press the switch Panel reset. If the fault is reset in the panel, the correct wire/outlet has been found. Continue to search for earth connections on the installation. If not effective, proceed Remove the battery cables from the main terminal board. Press the switch Panel reset. If the fault is reset in the panel, the correct outlet has been found. Continue to search for the earth connections on the installation. If not effective contact the local electrician, the manufacturer or his representative. Fuse fault If this fault occures during installation/commissioning, check that all outlets are terminated with a resistor of 1 kohm in the last alarm device. For outlets not in use the resistor shall be connected to the terminal outlets. Check also all fuses for alarm-, fire doors-, and data outlets. If the fault occures during normal operation check all fuses. If OK, mount a 1kohm resistor directly to the terminal outlets and press the switch Panel reset each time. When the panel is reset, the correct outlet has been found. If not, continue to search for broken wires, bad connections, or missing end-of-line resistors on the installation. If not effective contact the local electrician, the manufacturer or his representative. Fike : 40782449 page 51 of 57 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 Mains fault Check if the mains voltage is connected to the panel. If not : check the general supply and the fire alarm supply fuses (blue colour). If these are OK check the mains fuses in the panel. Additionally check the output voltage (secondary) from the mains transformer in the panel to be approx. 28 VAC. If not effective contact the local electrician, the manufacturer or his representative. Battery fault Check the battery fuses in the panel (terminal inlets) and the battery cabinet by removing them and measure the conductors. Check the battery voltage to be higher than 22 VDC. If not : check the battery cables, external fuses and connections. If these are OK check the charging rectifier outlet to be 27.0 VDC. If not effective contact the local electrician, the manufacturer or his representative. Loop fault If this fault occures during installation/commissioning, check that all loops are terminated with a resistor of 3.3 kohm in the last detector. For loops not in use the resistor shall be connected to the terminal outlets. If the fault occures during normal operation : check the connections on the terminal outlets in the main panel. If OK disconnect the loop wires and mount a resistor (3.3kohm) directly to the terminal outlets and press the switch Panel reset. If OK, the fault is located on the loop outside the panel. Check the loop resistance with an instrument to be 3.3kohm < R < 3.5kohm. If not continue to search for broken/short circuit wires, bad connections in detectors/junction boxes, water leakages/humidity around the detectors, etc. If not effective contact the local electrician, the manufacturer or his representative. Note! When use of zenerbarriers the eol is 10k and not 3k3. Fike : 40782449 page 52 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 53 of 57 98.02.11 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 PROGRAMMING Fike : 40782449 page 54 of 57 ver. 7.1 Instruction manual MBS-802 Fike : 40782449 Scana Servoteknikk as page 55 of 57 98.02.11 ver. 7.1 Instruction manual MBS-802 Scana Servoteknikk as 98.02.11 General instructions The programming sheet is to be filled in by the customer or the electrician. The customer date and sign the 'Standard sheet for programming MBS-802' and return it to Scana Servoteknikk for programming of the fire alarm panel MBS-802. It is of the utmost importance that the programming sheets are filled in with accuracy to ensure correct and reliable data for the programming of the MBS-802. MBS-802 can be programmed on the alarm- and control outlets with the following functions : Instantaneous or delayed alarm. Reset of the outlets by the switch Alarm silence or Panel reset. The outlets activated by Fire or Fault signal or by both. The outlets having intermittent, double tone, or continuous signal. The outlets activated by all loops. The outlets activated by one or a group of loops. The outlets activated by a predefined group of at least two loops. The outlets activated by all loops in a group. Programming standard outlets MBS-802 The upper table with Customer, Plant, Panel, Program, S.no., O.no., Loop delay, Mainsfault delay, Date, and Sign is to be filled in by Scana Servoteknikk as. Activ F/E Fill in the letter F for fire or E for fault to indicate the type of operation for each outlet. Controlled by loops/addr. Fill in the loop numbers which shall activate the actual outlet. Cancel S/R Fill in the letter S for Alarm silence or R for Panel reset to indicate the cancelling of each outlet. Delay (min) Fill in the delay in minutes for the activation of each outlet. Signal Fill in the type of signal for each outlet (description or graphic). Disconnected Fill in the letter A for Alarm, C for Control outlet, P for Parallel alarm or D for Door hold to indicate the type of disconnection for each outlet. Fike : 40782449 page 56 of 57 ver. 7.1 Scana Servoteknikk as Instruction manual MBS-802 98.02.11 Programming sheet for standard outlets Customer: Panel : Plant : Scana Servoteknikk Date/Sign : Program : Loop delay : Terminal outlets Activ NO 28 Fault alarm C 27 NC 26 NC 25 Parallel alarm C 24 NO 23 + 22 Remote panel D 21 - 20 NC 19 Control outlet 3 C 18 NO 17 NC 16 Control outlet 2 C 15 NO 14 NC 13 Control outlet 1 C 12 NO 11 Door magnet + 10 - 9 Alarm outlet 4 + 8 (as Alarm outlet 3) - 7 Alarm outlet 3 + 6 - 5 Alarm outlet 2 + 4 - 3 Alarm outlet 1 + 2 - 1 S.no. : O.no. : Mainsf. delay : F : Fire alarm A : Alarm outlet E : Fault alarm C : Control outlet S : Al. Silence P : Parallel outlet R : Panel Reset D : Door outlet Customer Date/Sign : F/E Controlled by loops/addresses Canc Del S/R min Signal Discon *** **************** *** ** *********** ***** *** *** **************** **************** *** *** ** ** *********** *********** ***** ***** A/C/P/D Remarks : Fike : 40782449 page 57 of 57 ver. 7.1