Prof. Ramesh Bansal Dept. of Electrical Engineering University of Sharjah rbansal@sharjah.ac.ae; M9-210 Learning objectives After completing this chapter, you should be able to learn Ideal Transformer With An Imperfect Core Ideal Transformer With Loose Coupling Equivalent Circuit of a Practical Transformer Transformer Taps Losses and Transformer Rating Simplifying the Equivalent Circuit Voltage Regulation Measuring Transformer Impedance-OC & SC tests Per Unit Method and Per Unit Impedance of a Transformer Imperfect core means the permeability is not infinity. And it has electric losses due to eddy currents and hysteresis loops. In order to get electric model of the magnetic core, a resistance Rm is used to represent iron losses in the transformer. Also, magnetizing reactance Xm is used in shunt with the resistance to hold the magnetizing current and represent main flux in the circuit. The equivalent circuit for the real iron core is shown The total current taken by the real core, (imperfect), has two different components; one component that generates the losses If and the other component that develops the field in the transformer Im. The sum of these two components are called exciting current I0. (upto 5 %) of the full-load, (maximum current). Example 10.1: A large transformer operating at no-load draws an exciting current Io of 5 A when the primary is connected to a 120 V, 60 Hz source, (circuit shown previously). From a wattmeter test it is known that iron losses are equal to 180 W. Calculate A. The reactive power absorbed by the core B. The value of Rm and Xm Ans:572 Var, 80 Ohm, 25.2 C. The value of If, Im and Io Ohm 1.5A, 4.8A, 5A Solution: Io = 5 A , E1=120 V, F=60 Hz,. P0=180 W. A. S=I0E1=5x120=600VA =P+jQ=180+jQ Q=√(6002-1802)=572 var B. 𝑅𝑚 = E12/P0=1202/180=80 ohm, 𝑋𝑚 = E12/Q=1202/572=25.2 ohm C. Io =5A, If =E1/Rm=1.5A Im =E1/Xm=4.8A It is mentioned before, the core is not perfect, which means that the iron core does not collect all the flux lines and the flux lines will be distributed between the air and core. The flux distribution in the domain is shown in the figure below. The mutual flux will develop Ep and Es in both windings, (shown in the figure of previous slide). E p 4.44 fN1m Es 4.44 fN 2m The leakage flux, f 1 and f 2 in both sides interact with the windings and develop voltages as, E f 1 4.44 fN1 f 1 E f 2 4.44 fN 2 f 2 The simplest way to represent these four voltages is to arrange the winding as shown below. The primary and secondary voltages Ef1 and Ef2 are the voltage drop across reactance, which are called primary and secondary leakage reactance. These reactances can be calculated as, X f1 Ef1 I1 ,Xf2 Ef 2 I2 Example 10.2: The secondary winding of a transformer has 180 turns. When the transformer is under load, the secondary current has an effective value of 18 A, 60 Hz. Furthermore, the mutual Фm has a peak value of 20 mWb. The secondary leakage flux Фf2 has a peak value of 3 mWb. Calculate a. The voltage induced in the secondary winding by its leakage flux b. The value of the secondary leakage reactance c. The value of E2 induced by the mutual flux Фm Ans:143.9 V, j8Ω, 959 The circuit shown below indicates exact equivalent circuit of the transformer. Each winding is represented by an internal resistance and a leakage reactance. The two voltages E1 and E2 result from interaction between the mutual flux and the two windings. The electrical equivalent model of the iron core is given as parallel branch of Rm and Xm. Ideal Transformer Due to the voltage drops in transmission system lines, the voltage in a particular region of a distribution system may consistently be lower than normal. Under these conditions the voltage across the secondary is less than the normal. To correct this problem taps are provided either on the primary or the secondary sides to correct the voltage in the system. Some transformers are designed to change the taps automatically whenever the secondary voltage is not close to the preset value. Like any other machines, a transformer has losses, they are composed of the following: 1- I2R losses in the windings 2- Hysteresis and eddy losses in the core 3- Stray losses due to current induced in the tank and metal support by the primary and secondary leakage flux The losses appear in the form of heat and produce - an increase in the temperature - a drop in the efficiency The Apparent power rating of the transformer is the multiplication of the nominal, (maximum allowable for safe operation), voltage and nominal current. It is expressed in VA or kVA or MVA. The rated VA, frequency, nominal voltage are always shown on the nameplate. Example 10.4 The nameplate of a distribution transformer indicates 250 kVA, 60 Hz, primary 4160 V, secondary 480 V. a. Calculate the nominal primary and secondary currents b. If we apply 2000 V to the 4160 V primary, can we still draw 250 kVA from the transformer. (for safe operation) Ans:60 A, 521 A, S = 120 kVA The exact circuit of the transformer gives more details than what are needed for the analysis of the transformer. Two different cases will be studied for the transformer analysis. 1- At No Load At no-load condition, the current in the secondary side is zero. The only current which is considered is the no-load current, (exciting current). Therefore, the drop over the series impedance at the primary side is almost negligible (IO is so small). Thus, the parallel branches can be moved from its location to be close to the supply and simplify the circuit as shown below. 2- At Any Load When the transformer is fully loaded, (rated current), or with any load. The current in the primary side is about 20 times the no-load current. Therefore, the no-load current can be neglected with respect to the load current in the primary side. The approximate equivalent circuit is shown below. The approximate circuit can be referred to either primary side or secondary side. The circuit referred primary side. to Voltage regulation (VR) of transformer can be calculated on primary or secondary side Let the primary voltage held constant at its rated value. The voltage regulation on secondary side is defined as, VR Enl E f l E fl The voltage regulation depends on several factors Power factor Load impedance Load current The previous equation can be re-written into the following equation: VR Es nl Es f l Es fl Example 10.5: A single-phase transformer rated at 3000 kVA, 69 kV/4.16 kV, 60 Hz has a total internal impedance Zp of 127 Ω, referred to primary side (resistive part is neglected). Calculate: a. The rated primary and secondary currents b. The voltage regulation from no-load to full-load for a 2000 kW resistive load, knowing that the primary supply voltage is fixed at 69 kV. c. The primary and secondary currents if the secondary is accidentally short circuit. Two important tests can be applied on the transformer to determine the impedances of the shunt branches and of the series branch. The first test is called open-circuit test and the other test is called short-circuit test. Open-Circuit Test In this test, the transformer secondary side is opencircuit. Voltmeter, ammeter and wattmeter are installed and connected at the primary side as shown in the figure at right side. The equivalent circuit for open-circuit test is similar to the normal open circuit equivalent for the transformer. This circuit is depicted at the right side. The readings of voltmeter, ammeter and wattmeter are used to get the value of Xm and Rm. The analysis of the circuit depicted in the next slide, the main idea is that the transformer can be dealt as if it is a circuit with two parallel branches. Analysis of Open-Circuit S EP I o Q S 2 P2 Rm E 2P Pm Xm E 2P Qm EP a Es Short-Circuit Test In this test, the secondary side is short-circuit and the applied voltage is slightly increased till the primary current is equal to or close to the primary rated current. (The applied voltage is approximately 5% of the rated primary voltage). The voltage, current, and power are measured. From these measurements, the series parameters can be calculated as follows: Analysis of Short-Circuit Z p Z1eq E sc Psc , R p R1eq 2 I sc I sc X p X 1eq Z p2 R p2 Example 10.6: during a short circuit test on a transformer rated 500 kVA, 69 kV/4.16 kV, 60 Hz, the following voltage, current and power measurements were made. Terminals X1, X2 were in short circuit (see figure) Esc=2600, Isc=4A, Psc=2400W. Calculate the value of the reactance and resistance of the transformer referred to the HV side. (Ans.: Rp=150 ohm, Xp=632 Ohm) Example 10.7: An open-circuit test was conducted on the transformer given in example 10-6. (transformer rated 500 kVA, 69 kV/ 4.16 kV, 60 Hz). The following results were obtained when the low-voltage winding was excited (in some cases, such as in a repair shop, a 69 kV voltage may not be available and the open-circuit test has to be done by exciting the LV winding at its rated voltage). Es=4160 V Io=2 A Pm=5000 W calculate: a. The values of Xm and Rm on the primary side, (referred) b. The efficiency of the transformer when it supplies a load of 250 kVA, whose power factor is 80% (lagging).(giving that Rp=150 Ω) Solution Ans: 96.6% The per unit method is a way that refer any value to its corresponding base value. For the impedance, the impedance in ohm should be divided over a based impedance to get its per unit value. For the transformer, the series and shunt impedance of the transformer is commonly expressed in per unit in the name-plate. Z base Z pu Vbase I base Z [ ] Z base [] For transformer: Z base p Z base 1 Z pu 1 Z p [ ] Z base 1[ ] Z base s Z base 2 Z pu 2 Vrated p Vbase 1 Vrated 1 I base 1 I rated 1 I rated p Z1eq [] Z base 1[ ] Vbase 2 Vrated 2 Vrated s I base 2 I rated 2 I rated s Z 2 eq [] Z s [ ] Z base 2 [] Z base 2 [ ] Example 10.8 A transformer rated 250 kVA, 4160 V/480 V, 60 Hz has an impedance of 5.1%. Calculate a. The base impedance on the primary and secondary side b. The total internal impedance Zp of the transformer referred to the primary side Problem 10.11 to 10.31