STRUCTURAL PLAN GENERAL NOTES: 1.0 GENERAL : GCpi = PRODUCT OF INTERNAL PRESSURE & GUST EFFECT FACTOR IN NSCP TABLE 207-4. 1.1 UNLESS NOTED OTHERWISE, ALL DIMENSIONS SHOWN ARE IN MILLIMETERS AND ELEVATIONS SHOWN ARE IN METERS. 1.2 THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE, AND SHALL NOTIFY THE ENGINEER OF DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND INFORMATION SHOWN ON THE DRAWINGS BEFORE PROCEEDING WITH THE WORK. THIS SHALL INCLUDE THE LOCATION AND DIMENSIONS OF GROOVES, REGLETS, SLEEVES, CURBS, OPENINGS, EMBEDDED OR ATTACHED ITEMS, ETC. (REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING.) 1.3 ALL FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, SECTIONS OR DETAILS. SPECIFIC NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. 1.4 THE STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURES. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION UNLESS SO STATED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PROTECT THE STRUCTURES, ADJACENT PROPERTIES, WORKMEN AND OTHER PERSONS DURING ALL PHASES OF CONSTRUCTION. 1.5 THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN CHARGE OF ANY CONDITION WHICH IN HIS OPINION MIGHT ENDANGER THE STABILITY OF THE STRUCTURES OR CAUSE DISTRESS IN THE STRUCTURES. 1.6 THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACINGS AND SHORINGS FOR ALL THE STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE STABILITY DURING ALL PHASES OF CONSTRUCTION. 1.7 1.8 1.9 3.4. SEISMIC LOAD , E SEISMIC LOADS FOR BUILDING STRUCTURES ARE CALCULATED BASED ON THE FOLLOWING: E = rEh + Ev Em = Vo Eh WHERE: E = EARTHQUAKE LOAD ON THE STRUCTURE Eh = THE EARTHQUAKE LOAD DUE TO THE BASE SHEAR, V, OR THE DESIGN LATERAL FORCE Fp. Em = THE ESTIMATED MAXIMUM EARTHQUAKE FORCE THAT CAN BE DEVELOPED IN THE STRUCTURE. Ev = THE LOAD EFFECT RESULTING FROM THE VERTICAL COMPONENT OF THE EARTHQUAKE GROUND MOTION AND IS EQUAL TO AN ADDITIONAL OF 0.5 Ca I D TO THE DEAD LOAD EFFECT. D, FOR STRENGTH DESIGN, AND MAY BE TAKEN AS ZERO FOR ALLOWABLE STRESS DESIGN. Vo = THE SEISMIC FORCE AMPLIFICATION FACTOR THAT IS REQUIRED TO ACCOUNT FOR STRUCTURAL OVERSTRENGTH. r WHERE: THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE PROPER ALIGNMENT OF THE STRUCTURES DURING AND AFTER THE INSTALLATION OF ALL STRUCTURAL AND FINISH MATERIALS. TYPICAL DETAILS AND GENERAL NOTES ON S-1 AND S-2 SHALL APPLY TO ALL PARTS OF THE WORKS UNLESS OTHERWISE SHOWN ON THE DRAWINGS. AB = THE GROUND FLOOR AREA OF THE STRUCTURE. 2.0 STANDARDS AND REFERENCES : THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION OF THE PROJECT: 2.1 AMERICAN CONCRETE INSTITUTE ( ACI PUBLICATIONS ) ; ACI 318-05 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE ACI 315-94 MANUAL OF STANDARD PRACTICE FOR DETAILS AND DETAILING OF CONCRETE REINFORCEMENT. 2.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATION: MANUAL OF STEEL CONSTRUCTION, NINTH EDITION. "ALLOWABLE STRESS DESIGN" (ASD) 2.3 AMERICAN WELDING SOCIETY (AWS) PUBLICATION D.1.1-2000. 2.4 AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM) 2.5 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) VOL. 1, SIXTH EDITION 2010. 2.6 ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES (ASEP) HANDBOOK OF STRUCTURAL STEEL SHAPES AND SECTIONS, 2004 2.7 EARTHQUAKE BASE SHEAR, (V) : THE TOTAL DESIGN BASE SHEAR IN A GIVEN DIRECTION SHALL BE DETERMINED FROM THE FOLLOWING FORMULA: V = Cv I (W) RT AND NEED NOT EXCEED THE FOLLOWING: V = 2.5 Ca I (W) R V = 0.11 Ca I W IN ADDITION FOR SEISMIC ZONE 4, THE TOTAL BASE SHALL ALSO BE NOT LESS THAN THE FOLLOWING: SEISMIC ZONE FACTOR, IMPORTANCE FACTOR GLOBAL DUCTILITY CAPACITY SEISMIC FORCE OVERSTRENGTH FACTOR SEISMIC SOURCE TYPE NEAR - SOURCE FACTOR, Nv NEAR - SOURCE TYPE, Na 3.1. DEAD LOADS (DL) : 24.00 77.00 18.00 200 200 2107 2730 1100 kN/m3 kN/m3 kN/m3 Pa Pa Pa Pa Pa BASIC FLOOR AREA HALLWAYS ABOVE GROUND FLOOR STAIRS, HALLWAYS, AND ASSEMBLY ROOF 1900 3800 4800 900 Pa Pa Pa Pa 4.1.1 = 0.40 = 1.5 = 8.5 (SMRF) = 2.8 =A = 1.6 = 1.2 fc' = 28MPa (4,000 PSI) fc' = 21MPa (3,000 PSI) 4.1.2 ALL CONCRETE SHALL BE DEPOSITED, VIBRATED AND CURED IN ACCORDANCE WITH ACI STANDARD 318-2005. 4.1.3 MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE AS FOLLOWS: A. FOOTINGS & BOT. OF FOOTING TIE BEAM = 75mm (CAST AGAINST EARTH) B. BEAMS AND COLUMNS = 40mm (TO STIRRUPS AND TIES) C. SLABS AND WALLS = 20mm (CAST AGAINST FORMS) 4.1.4 BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATIVE TO THE WORK. 4.1.5 WHEN CONCRETE WILL BE EXPOSED TO EXTERNAL SOURCES OF CHLORIDES IN SERVICES, SUCH AS DEICING SALTS, BRACKISH WATER, SEAWATER OR SPRAY FROM THESE SOURCES, CONCRETE MUST BE PROPORTIONED TO SATISFY THE SPECIAL EXPOSURE REQUIREMENTS OF ACI 318-2005. q = VELOCITY PRESSURE, KN/m -6 Z I R Vo CONCRETE USED IN THIS WORK SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH @ 28 DAYS AS FOLLOWS: COLUMN, BEAM, SLAB, & OTHERS FOOTING 3 2 = 47.3 x 10 Kz Kzt V Iw WHERE : Kz = VELOCITY PRESSURE COEFFICIENT GIVEN IN NSCP TABLE 207.3 EXPOSURE B. Kzt = TOPOGRAPHIC FACTOR = 1.0 V = BASIC WIND SPEED SHOWN IN NSCP FIG. 207-1 = 250kph I = IMPORTANCE FACTOR = 1.15 G = GUST EFFECT FACTOR SHOWN = 0.85 Cp = EXTERNAL PRESSURE COEFFICIENT SHOWN IN NSCP FIG. 207-3 LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE. 4.2.5 UNLESS INDICATED OTHERWISE, SPLICING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH ACI 318-2005. 4.2.6 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS : A. BEAMS AND FOOTING TIE BEAMS : TOP AND BOTTOM BARS SHALL NOT BE SPLICED WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN ; AT LEAST TWO EXTRA STIRRUP - TIES SHALL BE PROVIDED AT ALL SPLICES. THE SPLICE LENGTH SHALL NOT BE LESS THAN THE LENGTH IN ITEM 4.2.9 BELOW. B. COLUMNS : SPLICES WHEN PERMITTED SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND LAP SPLICE SHALL NOT BE LESS THAN 40 BAR DIAMETERS. THE USE OF APPROVED MECHANICAL DEVICES MAY BE PERMITTED PROVIDED THAT NOT MORE THAN ALTERNATE BARS ARE SPLICED AT ANY LEVEL AND THE MINIMUM VERTICAL DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600mm. 4.2.7 UNLESS INDICATED OTHERWISE, ALL BEAMS TERMINATING AT THE COLUMN SHALL HAVE TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF THE COLUMN, TERMINATING IN A STANDARD 90° HOOK LENGTH OF ANCHORAGE NOT LESS THAN 600mm. 4.2.8 SHOP DRAWINGS FOR BENDING AND CUTTING OF REINFORCEMENT SHALL BE SUBMITTED FOR APPROVAL TO THE ENGINEER PRIOR TO FABRICATION. 4.2.9 SPLICE LENGTH OF REINFORCING BARS SHALL BE AS SHOWN IN THE TABLE BELOW. 4.3 STRUCTURAL STEEL/ANCHOR BOLTS/BOLTS/WELDS & WELDMENTS 4.3.1 ALL STRUCTURAL STEEL SHALL HAVE A MINIMUM YIELD STRENGTH, Fy = 248 MPa (36 KSI) AND SHALL CONFORM TO ASTM A 36 SPECIFICATIONS. 4.3.2 ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC SPECIFICATIONS (9TH EDITION) AND CODE OF STANDARD PRACTICE AS AMENDED TO DATE. 4.3.3 ALL COLD FORMED STEEL SHALL HAVE A MINIMUM STRENGTH, Fy = 230 MPa (33 KSI) 4.3.4 NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGS HAVE BEEN APPROVED BY THE STRUCTURAL ENGINEER. 4.3.5 ALL SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS D.1.1-2000 AND PERFORMED BY QUALIFIED WELDERS. 4.3.6 UNLESS INDICATED OTHERWISE, WELDING ELECTRODES SHALL BE E70XX, MINIMUM THICKNESS OF WELD SHALL BE 3mm. 4.3.7 UNLESS OTHERWISE INDICATED ALL ANCHOR BOLTS SHALL CONFORM TO ASTM A307 SPECIFICATIONS. 4.3.8 4.1.6 ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF 7 CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP. 4.2 REINFORCING BARS : 4.2.1 UNLESS OTHERWISE SPECIFIED ON PLANS, ALL REINFORCING BARS SHALL BE DEFORMED WITH A MINIMUM YIELD STRENGTH, fy = 414 MPa (60,000 PSI). FOR DIAMETER 12mm AND BELOW, USE fy = 275 Mpa (40,000 PSI) 4.4.3 4.4.5 GROUT MASONRY IN 2.4m MAXIMUM LIFTS. REINFORCING SHALL BE SECURED AGAINTS DISPLACEMENT PRIOR TO GROUTING BY WIRE POSITIONERS AT INTERVALS NOT EXCEEDING 200 BAR DIAMETERS NOR 3m. 4.4.6 IF WORK IS STOPPED ONE (1) HOUR OR LONGER, PROVIDE HORIZONTAL CONSTRUCTION JOINTS BY STOPPING THE GROUT 50mm BELOW THE TOP OF THE BLOCK. 6.4 GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAM AT POINT WHERE CRITICAL BENDING STRESSES OCCUR. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED STRENGTH OF THE BAR, NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE ALLOWED TO BE SPLICED THEREIN. 6.5 FOR BAR TERMINATIONS OF TOP BARS AT SUPPORT AND MIDSPAN BARS, CUT-OFF ONLY TWO BARS AT EVERY 0.3m INTERVAL (UNLESS REQUIRED IN SPECIFICATIONS, OR NOTED OTHERWISE.) 7.1 FOOTINGS WERE DESIGNED USING AN ASSUMED ALLOWABLE SOIL BEARING CAPACITY OF 150 kPa AT DEPTHS INDICATED IN THE DRAWING. IN CASE THE ACTUAL SOIL BEARING CAPACITY IS FOUND LESS THAN THE ASSUMED 150 kPa, NOTIFY THE STRUCTURAL ENGINEER FOR PROPER REVISION OF FOOTINGS. 7.2 CONFIRMATION OF ACTUAL SOIL BEARING CAPACITY SHALL BE PERFORMED PRIOR TO THE CONSTRUCTION OF THE FOUNDATION. 7.3 WHERE LOOSE/SOFT MATERIAL IS ENCOUNTERED AT DEPTH OF FOOTING/FOUNDATION INDICATED, EXCAVATE TO FIRM LAYER AND REPLACE LOOSE/SOFT MATERIALS UNDERNEATH THE FOOTING WITHIN THE FOOTING AREA PLUS 1/2 DEPTH OF SOIL MATERIAL ON ALL SIDES WITH SELECTED BACKFILL. COMPACT SELECTED BACKFILL TO 95% MAXIMUM DRY DENSITY ( ASTM D1557). 7.4 ALL COLUMN FOOTINGS SHALL REST ON 100mm THK COMPACTED GRAVEL BASE COURSE, UNLESS OTHERWISE STATED. 7.5 FILL/BACKFILL SHALL BE PLACED IN 200mm LAYERS AND EACH LAYER SHALL BE COMPACTED TO 95% MAXIMUM DRY DENSITY BEFORE SUBSEQUENT LAYERS ARE TO BE LAID. LAP SPLICE (m) STANDARD HOOK (m) UNIT WEIGHT (kg/m) MIN. LAP SPLICE LENGTH OF COL. REINF. INDIVIDUAL BARS 90° 180° 135° TOP BAR OTHERS TOP BAR W/ TIES W/ SPIRAL 10 0.50 0.15 0.13 0.10 0.42 0.30 0.42 0.30 0.617 0.30 0.30 12 0.50 0.20 0.15 0.12 0.42 0.30 0.42 0.30 0.889 0.30 0.30 16 0.60 0.25 0.18 0.14 0.73 0.52 0.87 0.62 1.580 0.52 0.47 20 0.60 0.30 0.20 0.20 0.91 0.65 1.10 0.78 2.469 0.65 0.58 25 0.68 0.40 0.28 0.26 1.15 0.82 1.40 1.00 3.858 0.80 0.73 28 0.86 0.48 0.38 - 1.45 1.03 1.53 1.09 4.840 0.90 0.82 32 1.12 0.56 0.43 - 1.90 1.35 1.74 1.24 6.327 1.03 0.93 36 1.43 0.61 0.48 - 2.40 1.70 2.00 1.40 8.00 1.20 1.05 TENSION BAR COMP. BAR OTHERS NOTES: UNLESS INDICATED OTHERWISE, CMU REINFORCEMENT SHALL BE 10mmØ HOR. BARS SPACED @ 600mm AND 10mmØ VERT. BARS SPACED @ 600mm. ALL WALLS SHALL BE CONSTRUCTED IN CONVENTIONAL RUNNING BOND, UNLESS NOTED OTHERWISE. WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS. REINFORCING BARS SHALL BE SYMMETRICAL ABOUT THE CENTER LINE WHENEVER POSSIBLE. UPPER LAYER SHALL BE PLACED DIRECTLY ABOVE THOSE IN THE BOTTOM LAYER. SPACING OF BARS IN LAYER SHALL NOT BE LESS THAN 0.025m NOR ONE BAR DIAMETER. ANCHORAGE LENGTH (m) ALL CELLS SHALL BE SOLIDLY FILLED WITH GROUT. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 13.80 MPa (2,000 PSI) @ 28 DAYS. 4.4.4 6.3 BAR DIAMETER (mm) BOLTS FOR MEMBER CONNECTIONS SHALL BE HIGH STRENGTH BOLTS, CONFORMING TO ASTM A325 FRICTION TYPE WITH WASHERS. CMU USED IN THESE WORKS SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGTH @ 28 DAYS AS FOLLOWS : 100mm THICK NON-LOAD BEARING CMU, f'm = 2.4 MPa (350 PSI) 150mm THICK NON-LOAD BEARING CMU, f'm = 2.4 MPa (350 PSI) IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS , USE SEPARATORS OF SIZE NOT LESS THAN 25mm BARS SPACED ABOUT 1.00m ON CENTER AND PLACED DIAGONALLY. IN NO CASE SHALL THERE BE LESS TWO (2) SEPARATORS BETWEEN LAYERS OF BARS. LAP SPLICE & ANCHORAGE LENGTH TABLE 4.4 CONCRETE MASONRY UNITS (CMU) 4.4.1 6.2 7.0 FOUNDATIONS : C. CONCRETE MASONRY UNIT (CMU) WALLS : VERTICAL BARS SHALL BE SPLICED AT THE TOP OF WALL FOOTING OR TIE BEAM AND AT THE BOTTOM OF RC LINTEL BEAM OR BEAMS. SPLICE LENGTHS SHALL BE 600mm MIN. 4.4.2 WHERE : P = DESIGN WIND PRESSURE, KN/m2 4.2.4 4.1 NORMAL WEIGHT CONCRETE : 3.3. WIND LOAD (WL) WIND LOADING ON MWFRS (MAIN WIND FORCE RESISTING SYSTEM) : P = qh[(GCpf)-(GC pi )] ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT. 4.0 MATERIALS : 3.2. LIVE LOADS (LL) : 3.2.1 3.2.2 3.2.3 3.2.4 V = 8.5 Z Nv I (W) R WHERE: 3.0 BASIC DESIGN LOADS : CONCRETE STEEL SOIL CEILING MISCELLANEOUS 100mm THK.CHB WALL 150mm THK.CHB WALL FLOOR TILES PLUS MORTAR 4.2.3 BUT SHALL NOT BE LESS THAN THE FOLLOWING: UNIFORM BUILDING CODE (UBC), VOL. 2 1997 EDITION 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.1.7 3.1.8 ALL REINFORCING BARS SHALL BE CLEANED OF RUST, GREASE OR OTHER MATERIALS WHICH TEND TO IMPAIR BOND. = RELIABILITY / REDUNDANCY FACTOR WHICH SHALL NOT BE TAKEN LESS THAN 1.0 AND GREATER THAN 1.5, IS GIVEN BY THE FOLLOWING FORMULA: 6.1 r =2rmax AB rmax = THE MAXIMUM ELEMENT-STORY SHEAR RATIO. FOR A GIVEN DIRECTION OF LOADING, THE ELEMENT-STORY SHEAR RATIO IS THE RATIO OF THE DESIGN OF STORY SHEAR IN THE HEAVILY LOADED SINGLE ELEMENT DIVIDED BY THE TOTAL DESIGN STORY SHEAR. FOR MOMENT FRAMES, IT SHALL BE TAKEN AS THE MAXIMUM OF THE SUM OF THE SHEARS IN ANY TWO ADJACENT COLUMNS IN A MOMENT FRAME BAY DIVIDED BY THE STORY SHEAR. FOR COLUMNS COMMON TO TWO BAYS, 70 PERCENT OF THE SHEAR IN THAT COLUMN MAY BE USED IN THE COLUMN SHEAR SUMMATION. THE CONTRACTOR SHALL INFORM THE SUB-CONTRACTORS THAT NO CONSTRUCTION MATERIALS SHALL BE STORED ON POURED FLOORS, AND SHALL ENSURE THAT THE SUB-CONTRACTORS DO NOT VIOLATE THIS IMPORTANT REQUIREMENT. 4.2.2 5.0 CONSTRUCTION JOINTS : 5.1 CONTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS TO LEAST IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO APPROVAL OF THE ENGINEER. 5.2 UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JOINTS @ 6.00m MAXIMUM CENTER TO CENTER. 6.0 NOTES ON BEAMS AND GIRDERS : 6.1 UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AND GIRDERS AT LEAST 0.006m FOR EVERY 4.50m OF SPAN EXCEPT CANTILEVERS FOR WHICH THE CAMBERS SHALL BE AS NOTED IN THE PLANS OR AS ORDERED BY THE DESIGNERS. BUT IN NO CASE LESS THAN .019m FOR EVERY 3.00m OF FREE SPAN. COLUMN/WALL FACE 1. ACI SECTION 12.4 STATES THAT DEVELOPMENT LENGTH OF INDIVIDUAL BARS W/IN A BUNDLE, IN TENSION OR COMPRESSION, SHALL BE THAT FOR THE INDIVIDUAL BAR, INCREASED 20% FOR THREE BAR BUNDLE, AND 33% FOR FOUR BAR BUNDLE. 180° HOOK 2. FOR COLUMNS, AT ANY LEVEL NO MORE THAN ALTERNATE BARS SHOULD BE SPLICED. NOT MORE THAN 33% OF THE BARS SHALL BE SPLICED W/IN THE REQUIRED LAP LENGTH. MINIMUM DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600mm. 3. TOP BARS ARE HORIZONTAL BARS W/ MORE THAN 300mm DEPTH OF CONCRETE CAST BELOW THE REINFORCEMENT. 4. AS MUCH AS POSSIBLE, SPLICES SUBJECTED TO TENSILE STRESSES ARE DISCOURAGE, THESE SHOULD BE AVOIDED OR PROVIDED W/ STANDARD HOOKS. ANCHORAGE LENGTH 135° HOOK 1 S-1 90° HOOK DETAIL SCALE NTS STANDARD DETAIL CONNECTION 10mm Ø AS SHOWN 10mm Ø @ 400mm O.C. t SION ES PR DE 100 T/5 T/3 T WEAKENED PLANE JOINT CONSTRUCTION JOINT NOTE: PROVIDE 90° HOOK WHERE t EXCEEDS 50mm 1. CONTROL JOINTS CAN BE EITHER CONSTRUCTION JOINTS OR WEAKENED PLANE JOINTS. DEPRESSED SLAB & SLAB EDGE DETAILS SCALE T/3 50mm 2. FOR CLOSURE SLABS AT OPENINGS AND BLOCKS OUT, REBARS TO BE THE SAME SIZE, AND 2/3 THE SPACING OF BARS AS ADJACENT SLABS. 25mm-75mm TYP. 1 S-2 T/2 NOTE: 1. REINF. TO BE SAME BAR SIZE AND SPACING AS ADJACENT REINF. BARS ON SLABS. MAX. SAWED JOINT WITH SEALANT TOOLED JOINT T/3 250mm Ø 2-10mmØ TYP. 6t OR 450 MIN SLAB THICKNESS, T 25mm-75mm TYP. 6mm h<600 150 TYP. PIPE SLEEVE OPENING FOR SLABS 2 S-2 NTS SCALE CONTROL JOINTS FOR SLAB-ON GRADE 3 S-2 NTS SCALE NTS 250 100 CHB WALL NOTE: 16mm Ø VERT. BARS @ 400mm O.C. DECK SLAB L/3 L/3 L/3 2-10mmØ MAIN BARS 300 10mm Ø TIES/ STIRRUPS @ 200mm O.C. h<3000 DECK SLAB R.C. EDGE BEAM WALL BASE STIRRUPS @ 100mm O.C. MAX. SPACING 2D 150 R.C. EDGE BEAM L CL OF COLUMN D 16mm Ø VERT. BARS @ 200mm O.C. h<3000 1000 < H < 3500 16mm Ø VERT. BARS @ 400mm O.C. 10mm Ø TIES/ STIRRUPS @ 200mm O.C. UNLESS OTHERWISE NOTED IN THE PLAN, PROVIDE FRAMING STIFFENER COLUMNS & STIFFENER BEAMS NOT MORE THAN 3.0m APART. 10mm Ø HOR. BARS @ 300mm O.C. H/2 10mm Ø HOR. BARS @ 400mm O.C. H < 1000 R.C. WALL 100 150 TOP BARS NOTE: CASE 2 4 S-2 4-12mm Ø MAIN BARS t<3000 TYPICAL DETAIL SECTION OF PARAPET SCALE LINTEL IN BLOCK WALLS (SAME THICKNESS AS CMU) 1200 1500 1800 2100 2400 2700 13.8 13.8 13.8 17.2 17.2 17.2 200 225 250 250 300 300 2-10mm Ø 2-12mm Ø 2-10mm Ø 2-12mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 2-16mm Ø 3000 3300 3600 3800 4100 4400 17.2 17.2 17.2 350 400 450 3-16mm Ø 3-16mm Ø 2-16mm Ø 2-16mm Ø 4-16mm Ø 2-16mm Ø HEIGHT OF LINTEL BEAM (mm) REINFORCEMENT BOTTOM SCALE DOWELS MIN. fc' Mpa STIRRUPS TOP 12mm THK. COMPRESSIBLE JOINT FILLER W/ SEALANT (TYP.) S-2 SCALE STIFFENER/ BOND BEAM BOT. OF BEAM 12mm THK. COMPRESSIBLE JOINT FILLER W/ SEALANT (TYP.) 200 LINTEL BEAM 200 13 S-2 HORIZONTAL BARS CHB WALL VERTICAL BARS BOT. BARS CLEAR SPAN TOTAL LENGTH FINISH FLOOR LINE FFL MTS 8 S-2 TYP. CHB WALL ELEVATION SCALE MTS 1-16mm Ø VERT. BAR DOWELS DOWELS REINF. CONCRETE LINTEL BEAM IN CHB WALLS SCALE 100 450 TYP. OPENING S-2 PLASTER BOT. OF BEAM DOOR OPENING 7 MTS STIFFENER/ BOND BEAM 12 S-2 LINTEL BEAM 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 10mm Ø @ 200 TYP. SPLICE DETAILS FOR BEAMS FRAMING INTO COLUMN 6 NTS TOP BARS DEPTH OF LINTEL BEAM NO SPLICE t<3000 TYPICAL DETAIL OF STIFFENER BEAMS & COLUMNS 5 S-2 NTS TOTAL LENGTH mm 1800 2100 2400 2700 3000 3300 CLEAR SPAN L (mm) BOTTOM BARS (UNLESS OTHERWISE NOTED ON PLANS) 12mm CASE 1 9 S-2 SECTION SCALE MTS 10 S-2 SECTION SCALE MTS W SCHEDULE OF FOOTINGS BARS ``A'' (TOP BAR ALONG L) REINFORCEMENT D (DEPTH) mm t (THICK.) mm L (LENGTH) mm W (WIDTH) mm ''A'' ''B'' ''C'' ''D'' F1 700 300 1800 1800 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING F2 700 300 2000 2000 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING F3 700 300 2000 2000 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING F4 700 300 2500 2500 - - 15-20mm Ø 15-20mm Ø ISOLATED FOOTING 0.3L2 0.3L2 B AT SUPPORT TOP BARS ARRANGEMENT AT MID - SPAN BOTTOM TOP BOTTOM AT AT EXT. MID SUPP. SPAN WEB BAR ELEVATION 6 250x350 4-20mm Ø 4-20mm Ø 3-20mm Ø 3-20mm Ø FTB2 300x450 5-20mm Ø 5-20mm Ø 3-20mm Ø 3-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 5@150mm, REST@ 200mm O.C. 4 3 3980 ST-3 7 6 4100 NOT TO C2 FTB-1 C2 FTB-1 4100 C2 FTB-1 8 4100 9 4100 10 4100 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 150mm THK. CHB WALL FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-2 C1 2 WF2 400 FTB-2 FTB-2 FTB-1 C1 1 LEAN CONCRETE BASE ST-3 FTB-2 FFL 3-10mm Ø LONG. BARS F1 10mm Ø BARS SPACED TO MATCH SLAB REINFORCING BARS 3-10mm Ø LONG. BARS 10mm Ø @ 250mm O.C. 3 C2 10mm Ø VERT. BARS @ 400mm O.C. 10mm Ø VERT. BARS @ 400mm O.C. ALTERNATE 90° BEND C2 FTB-1 100mm THK. CHB WALL 10mm Ø HOR. BARS @ EVERY 3RD COURSE 3000 F3 FTB-2 F3 FTB-2 F3 FTB-2 F3 FTB-2 F2 FTB-2 F2 FTB-2 5010 FTB-2 F2 SCALE NGL 11 3980 FTB-1 TO SCALE D F1 NOT ST-3 200 C2 DETAIL REFERENCE OF FOOTINGS 2 TYPICAL FOOTING TIE BEAM DETAIL BOTTOM BARS SECTION FOR THICKNESS, t 500mm 10mm Ø HOR. BARS @ EVERY 3RD COURSE 5 4100 SECTION 600 3300 PLAN L2 REMARKS FTB1 2 100mm THK. WELL-COMPACTED GRAVEL BASE BOT. BARS 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 3@150mm, REST@ 200mm O.C. 1 t BARS ``D'' (BOT. BAR ALONG W) L1 STIRRUPS SIZE SPACING AT INT. SUPP. NGL FTB BARS ``C'' (BOT. BAR ALONG L) TOP BARS D 0.3L1 0.25L1 100 100 REINFORCING SIZES ( mm ) +- 600 BARS ``B'' (TOP BAR ALONG W) SCHEDULE OF FOOTING TIE BEAMS (FTB) MARK FGL REMARKS 500 BOTTOM L TOP H MARK 2 1 100mm THK COMPACTED GRAVEL BASE 300 WALL FOOTING DETAIL NOT TO SCALE C2 F1 F4 WF1 FTB-2 F4 FTB-2 F4 FTB-2 F4 FTB-2 F4 FTB-2 F4 FTB-2 F4 FTB-2 FTB-2 FTB-2 5330 F4 FTB-2 F4 WF1 FTB-2 F1 SHAFT SHAFT C WF1 150MM (EXTERIOR) 100MM (INTERIOR) SHAFT SHAFT WF1 FACE OF WALL 12mm THK PRE-FORMED ELASTOMERIC JOINT FILLER WITH SEALANT CHB WALL C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 FTB-1 C1 FTB-2 F1 10mm Ø @ EVERY 3rd LAYER, HORIZONTAL BARS F4 FTB-2 F4 FTB-2 F4 FTB-2 WF2 F4 FTB-2 F4 FTB-2 F4 FTB-2 FTB-2 F4 FTB-2 F4 FTB-2 F4 5010 10mm Ø @ 600mm O.C. VERTICAL BARS C2 200 C1 F1 t FTB-2 C2 t/3 B REBARS OF SLAB ON FILL 100mm THK COMPACTED GRAVEL BASE 125 G.F.L. 200 A C2 FTB-1 F1 C2 FTB-1 C2 F2 FTB-1 F2 C2 FTB-1 C2 F2 FTB-1 F3 C2 FTB-1 C2 F3 FTB-1 F3 C2 FTB-1 F3 C2 N.G.L. F1 USE: 125mm THK SLAB ON FILL WITH 10mm Ø BARS SPACED @ 250mm O.C. BOTHWAYS 1 ST-3 LOWER GROUND FOUNDATION & FRAMING PLAN SCALE 1:100 M. 100mm THK. COMPACTED GRAVEL FILL ON A COMPACTED EARTH FILL 5 ST-3 FTB 4 ST-3 WALL ON FOOTING TIE BEAM NOT TO SCALE 100 TYP. SLAB ON TYPICAL SLAB ON GRADE DET. NOT TO SCALE 1 2 REINFORCING BARS 125 SHORT SPAN LONG SPAN END MIDDLE END REMARKS MIDDLE TOP Ø10 200 200 200 200 BOT. Ø12 300 300 300 300 TWO-WAY GRID 38MM CLR. 10mmØ BAR @ 0.3m O.C 12mmØ BAR @ 0.3m O.C GRID S2 S1 S1/3 1-Ø16 TOP & BOT. BARS (TYP. ALL AROUND) 75MM MAX. GRID S1/4 0.60 db 4 (T 0 db YP .) 40db S-1 BAR DIA. 0.10 ALL BAR THICKNESS LOCATION (mm) MARK 0.12 FLOOR LEVEL "Ø GROOVE 40 40db (TYP.) SCHEDULE OF SLABS 2-Ø16 @ 75 DIAGONALS AT MID-DEPTH OF SLAB AT EACH CORNER BEAM (FOR ONE-WAY SLAB) S1/3 S2/3 (FOR TWO-WAY SLAB) S1/4 S2/4 S2/3 S2/4 5 ST-4 DISCONTINUOUS END TYPICAL CANOPY DETAIL NOT TO SCALE 1. ALL TOP AND BOTTOM SLAB BARS INTERRUPTED BY OPENING SHALL BE REPLACED BY ADDITIONAL REINFORCING EQUAL TO THAT INTERRUPTED. PLACE HALF OF THE ADDITIONAL REINFORCING ON EACH SIDE OF OPENING AND EXTEND SAME LENGTH AS REQUIRED OR BAR LAP OF INTERRUPTED REINFORCING. S2/5 S2/5 S1/5 NOTE (1) AT 75MM SPACING NOTES: CONTINUOUS END S1/7 EXTEND BARS UP TO BEAM SUPPORT 2. SEE ARCHITECTURAL & MECHANICAL PLANS FOR SLAB OPENING LOCATION. NOT 2 3300 TO 3 3980 3. OMIT TRIMMER BARS WHERE OPENING IS FRAMED BY BEAMS. SCALE 4 5 4100 4100 6 4100 7 8 4100 4100 9 4100 10 3980 4. BOXED OUT OPENINGS, RECESSES AND PIPE SLEEVE CLUSTERS SHALL BE TREATED AS FRAMED SLAB OPENING. 5. MAXIMUM DIMENSION FOR EACH SIDE OF OPENING SHALL BE 1200MM. OPENINGS BEYOND THE SAID DIMENSION ARE SUBJECT TO THE APPROVAL OF THE ENGINEER. 11 3000 3 ST-4 TYPICAL SLAB OPENING DETAIL NOT TO 150 G3 G3 G3 G3 G3 G3 S-1 G3 S-1 BB2 G3 G3 B G3 G3 B G3 VARIES G2 STAIRS Ø10 @ 300 HOR. BARS Ø10 @ 300 HOR. BARS G3 G3 G3 G3 G3 G3 G3 S-1 S-1 G1 S-1 G1 S-1 G1 S-1 G1 S-1 G1 G1 G1 S-1 G2 G2 G2 G2 G2 S-1 S-1 S-1 B B G2 LOWER GROUND FLOOR LEVEL G2 S-1 S-1 S-1 B B B B 1 ST-4 B UPPER GROUND FRAMING PLAN SCALE 1:100 M. LOWER GROUND FLOOR LEVEL WF1 Ø100MM PERFORATED PIPE TAP TO NEAREST DRAIN Ø100MM PERFORATED PIPE TAP TO NEAREST DRAIN FTB Ø100MM PERFORATED PIPE TAP TO NEAREST DRAIN FTB G2 VERIFY S-1 Ø12 @ 200 VERT. BARS Ø10 @ 300 HOR. BARS LOWER GROUND FLOOR LEVEL S-1 G1 G1 5010 10mm Ø @ 600mm O.C. VERTICAL BARS Ø12 @ 200 VERT. BARS FTB A BB2 CHB WALL S-1 B BB2 Ø12 @ 200 VERT. BARS SHAFT S-1 G1 S-1 UPPER GROUND LEVEL SHAFT S-1 G1 S-1 G1 S-1 G1 S-1 G1 G1 G1 G1 SHAFT G1 S-1 SHAFT G2 5330 S-1 150 UPPER GROUND LEVEL WF1 C STAIRS 150 UPPER LEVEL G1 S-1 G2 G1 S-1 G2 G1 S-1 G2 G1 S-1 G2 G1 G2 G1 S-1 G2 H G3 S-1 G2 G1 G1 5010 G2 G1 D SCALE LESS THAN H/2 1 TYPICAL SLAB DETAIL GREATER THAN H/2 2 ST-4 VERIFY 4 ST-4 VERIFY TYPICAL RETAINING WALL DETAIL NOT TO SCALE SCHEDULE OF COLUMNS COL. MARK C1 FLOOR LEVEL COL. MARK C2 C1 FLOOR LEVEL FOUNDATION THIRD FLOOR TO TO SECOND FLOOR ROOF BEAM C2 TOP OF BEAM CANTILEVER BEAM 400X400 350X350 SIZE (mm) 300X300 300X300 4-25mm Ø & 4-20mmØ 8-20mm Ø VERT. REINF. 8-16mm Ø 8-16mm Ø TIES 300 SIZE (mm) 1@50mm,2@100mm,3@150mm, rest @ 200mm 200 2-16mmØ VERT. REINF. TIES CANTILEVER BEAM L 1@50mm,2@100mm, 3@150mm, rest @ 200mm 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. ELEVATION 2-16mmØ VERT. BARS SECTION SECOND FLOOR 3 THIRD FLOOR ST-5 SIZE (mm) 350X350 300X300 VERT. REINF. 8-20mm Ø 8-20mm Ø TIES TYPICAL BEAM DETAIL (B) NOT TO H2 TO SCALE 1@50mm,2@100mm,3@150mm, rest @ 200mm TOP OF BEAM 10 G2 G2 G2 G2 G2 S-1 G3 S-1 G3 S-1 G3 S-1 G3 S-1 G3 S-1 G1 G2 G1 G2 G1 3980 G3 S-1 11 3000 G3 G3 SHAFT G2 G2 G2 G2 G2 G2 S-1 G2 S-1 G3 G2 H1/4 G3 G1 S-1 G3 G1 S-1 G3 G1 S-1 G3 G1 S-1 G3 G1 S-1 G3 G1 S-1 G3 G1 G3 G1 5010 G3 G1 B STAIRS G1 S-1 TIES SHAFT S-1 G1 S-1 G1 S-1 G1 S-1 G1 S-1 G1 S-1 G1 S-1 G1 G1 STAIRS SHAFT G2 5330 SHAFT C LAP SPLICE 9 4100 LAP SPLICE 8 4100 H1/4 7 4100 H1/2 G3 6 4100 H1 G3 S-1 G1 G1 5010 G2 5 4100 G1 D 4 4100 G1 3 3980 G1 2 3300 G1 1 G2 A 1 ST-5 TYPICAL SECOND & THIRD FLOOR FRAMING PLAN SCALE 1:100 M. 2 ST-5 100mm THK COMPACTED TYPICAL COLUMN DETAIL GRAVEL BASE NOT TO SCALE L1 L2 0.3L2 0.3L1 0.25L1 B TOP BARS SEE TYP. BEAM (B) DEATILS SEE SCHEDULE OF BEAMS AND GIRDERS L2 L1 CANTILEVER BEAM L3 L 2 /3 1200 2D LAP SPLICES ARE ALLOWED ONLY IN THIS POINT BUNDLED BARS L 2 /3 L 3 /3 2D 2D ADDITIONAL TOP BARS ADDITIONAL TOP BARS 2D CONT. TOP BARS 0.125L1 0.15L2 0.15L2 600 WEB BARS 600 h 300 H L 3 /3 LAP SPLICES ARE ALLOWED ONLY IN THIS POINT SEE SECTION OF CANTILEVER BEAM ELEVATION ADDITIONAL BOT. BARS 2 - 12mm Ø STIFF. BARS L 2 /5 CONTINUOUS BOT. BARS L 2 /5 L 3 /5 BOT. BARS SECTION L 3 /5 b STIFF. BARS TOP BARS B H 3-25mmØ MAIN BARS 3-16mmØ MAIN BARS SECTION (CANTILEVER BEAM) 2 ST-6 1 2 3300 TYPICAL BEAM DETAIL NOT TO 3 3980 4 4100 NOT ST-6 5 4100 TYPICAL BEAM DETAIL WITH CUT-OFF BARS 3 SCALE 6 4100 7 8 4100 4100 9 4100 10 3980 TO SCALE 11 3000 SCHEDULE OF BEAMS AND GIRDERS REINFORCING MARK RG1 RG1 RG1 RB1 RG1 RG1 RG1 RB1 RG1 RG1 RG1 RG1 ARRANGEMENT AT MID - SPAN TOP BOTTOM TOP BOTTOM AT AT EXT. MID SUPP. SPAN AT INT. SUPP. STIRRUPS SIZE SPACING SHAFT G1 350X450 5-25mm Ø 3-25mm Ø 3-25mm Ø 3-25mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G2 300X400 4-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G3 350X450 5-20mm Ø 3-20mm Ø 3-20mm Ø 4-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. RG1 RG1 SECOND FLOOR SHAFT RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 SHAFT RG1 5330 SHAFT C G1 350X450 5-25mm Ø 3-25mm Ø 3-25mm Ø 3-25mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G2 300X400 4-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G3 350X450 5-20mm Ø 3-20mm Ø 3-20mm Ø 4-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. THIRD FLOOR RB1 RB1 RB1 RG1 RG1 RG1 1 ST-6 RB1 RG1 RB1 R.C. GUTTER RB1 RG1 RG1 ROOF BEAM FRAMING PLAN SCALE 1:100 M. RG1 RB1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 5010 RG1 RG1 B A AT SUPPORT BARS GROUND FLOOR RB1 RG1 RB1 RG1 RG1 5010 RG1 RB1 RG1 RG1 RB1 RG1 RG1 RB1 R.C. GUTTER RG1 RB1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 D SIZES ( mm ) RB1 RG1 G1 300X400 6-20mm Ø 3-20mm Ø 3-20mm Ø 4-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G2 300X400 4-16mm Ø 3-16mm Ø 2-16mm Ø 3-16mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. G3 300X400 3-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. ROOF BEAM LEVEL RG1 250X300 3-16mm Ø 2-16mm Ø 2-16mm Ø 3-16mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. RB1 250X300 2-16mm Ø 2-16mm Ø 2-16mm Ø 3-16mm Ø 10mm Ø STIRRUPS 1@ 50mm, 3@100mm, 4@150mm,REST@ 200mm O.C. REMARKS 2000 b a a 300 STRUT1 TOP CHORD : 2L 50X50X6MM BOT CHORD : 2L 50X50X6MM WEB MEMB : L 50X50X3MM BP1 a 1133 1133 1133 1133 1133 2 4 5 4100 1133 6 4100 TRUSS 1 DETAIL NOT TO 7 4100 VERIFY SCALE 8 4100 4100 9 4100 10 3980 11 3000 0 3 3980 1133 10 2 1133 6800 ST-7 3300 a BP1 a : 2L 50X50X3MM b : 2L 50X50X6MM 6800 1 a STRUT1 VERIFY a a a 0 45 Ø10 @ 400 E.W. (UNLESS NOTED OTHERWISE) 12mmØ ROUND BAR CROSS BRACING W/ 12mm TURN BUCKLE D COMPACTED SELECT BORROW SUBBASE 300 R.C. GUTTER RB1 2-Ø10 CONT. W/ Ø10 TRANSV. BARS @ 400 O.C. MAX. 5010 55 RB1 250 6800 60cm X 60cm MANHOLE WITH 200mm HEIGHT CONCRETE UPSTAND RAMP ON-FILL DETAIL 3 NOT ST-7 RG1 C TO 12mmØ VERTICAL BARS SPACE @ 300mm O.C. 10mmØ HORIZONTAL BARS @ EVERY 3RD LAYER 2000 680 RG1 400 450 RB1 100 150 10 0 5010 6800 B RB1 A 150 R.C. GUTTER RG1 10mmØ REINF. BARS SPACE @ 300mm O.C. 12mmØ REINF. BARS SPACE @ 300mm O.C. USE LC 90X45X15X3.0MM THICK PURLINS SPACED @ 500MM O.C. WITH 10MMØ SAG RODS 1 ST-7 ROOF FRAMING PLAN SCALE 1:100 M. 4 ST-7 300 S -1 13600 TRUSS 1 TRUSS 1 TRUSS 1 TRUSS 1 TRUSS 1 TRUSS 1 TRUSS 1 TRUSS 1 S -1 TRUSS 1 5330 CONCRETE HOLLOW BLOCKS 6'' THK WITH PLASTER FINISH RB1 250 TYP. CON. GUTTER DETAILS NOT TO SCALE SCALE RIDGE LINE 6 10 SIZE OF FILLET WELD, t (mm) 3.O 3.O 5.0 3.0 6.O 4.5 8.O 150 RIDGE PURLIN 4 ROOF PURLINS WP NOTE: 2. COLUMN JOINT GUSSET AND CONTINUITY PLATES SHALL HAVE 100% ULTRASONIC INSPECTION FOR DELAMINATION BEFORE AND AFTER WELDING. 6 THK STEEL BENT PLATE W/ 6 THK STIFF. PLATE t t 70 30 50 GUSSET PLATE DIMENSION (WHERE REQ'D.) SHALL BE DICTATED BY THE MINIMUM REQUIRED LENGTH OF WELD. 80 SAGROD W/ STD NUTS & WASHER 2-12mm Ø x40 LONG BOLTS W/ STD.NUTS & WASHERS (EACH SIDE) 6 THK STEEL BENT PLATE W/ 6 THK STIFF. PLATE SAG ROD LINE 6.O 1. PURLIN 2-12mm Ø x40 LONG BOLTS W/ STD.NUTS & WASHERS (EACH SIDE) 150 SAG ROD W/STD NUTS & WASHER 70 50 MEMBER THICKNESS (mm) 30 GUSSET PLATE THICKNESS (mm) TOP CHORD OF TRUSS 2 PURLIN 50 TOP CHORD OF TRUSS 60 - TOP CHORD OF TRUSS GUSSET PLATE 120 (MIN.) 90 (MIN.) PURLIN FILLET WELD WEB MEMBER 1 TYPICAL SAGROD CONNECTION DETAIL S- SCALE NTS 2 SECTION 3 TYPICAL PURLIN CONNECTION DETAIL S- SCALE S- SCALE NTS NTS 4 SECTION S- SCALE NTS SCHEDULE OF WELDS SCALE NTS TOP CHORD GUSSET PLATE WP WEB MEMBERS TOP CHORD WEB MEMBERS GUSSET PLATE TOP CHORD WEB MEMBERS WP TYP GUSSET PLATE WP TYP t t TYP GUSSET PLATE t t t GUSSET PLATE WP WEB MEMBER TYP t 5 DETAIL 6 DETAIL 7 DETAIL 8 DETAIL 9 DETAIL S- SCALE S- SCALE S- SCALE S- SCALE S- SCALE NTS NTS GUSSET PLATE WEB MEMBERS WEB MEMBER TOP CHORD TYP GUSSET PLATE PER REQUIRED LENGTH TYP t t DETAIL SCALE t t t t TYP L50x50x5 GUSSET PLATE t BOTTOM CHORD WP PER REQ'D. LENGTH WEB MEMBERS NTS 12 S- DETAIL SCALE 13 NTS S- 1 ST-8 50x100x6 THK. STEEL PLATE PER REQ'D. LENGTH BOTTOM CHORD DETAIL SCALE S- TYP WP S- 10 WP t 11 PER REQ'D. LENGTH TOP CHORD t WP GUSSET PLATE TYP BOTTOM CHORD NTS 75 NTS WP BOTTOM CHORD PER REQUIRED LENGTH t t WEB MEMBERS NTS TYP t WP WEB MEMBERS PER REQ'D LENGTH t PER REQ'D LENGTH t t GUSSET PLATE TYP t 20 1 S-12 WEB MEMBERS DETAIL SCALE 14 NTS S- TRUSS CONNECTION DETAIL NOT TO 75 SCALE DETAIL SCALE NTS 15 S- ANGULAR BUCKLE DETAIL SCALE NTS NTS Ø12 @ 250 TOP & BOT BARS Ø16 @ 125 Ø16 @ 125 MAIN ENTRANCE PORCH LVL ± 456 GRADIENT =1:12 Ø10 NOSING BAR SIDEWALK LVL Ø10 @ 400 E.W. (UNLESS NOTED 300 Ø16 @ 125 TOP BAR 15 0 Ø12 @ 250 Ø16 @ 125 100 Ø16 @ 125 Ø10 @ 300 450 3-Ø16 150 LANDING LEVEL 2-Ø10 CONT. W/ Ø10 TRANSV. BARS @ 400 O.C. MAX. 400 L/4 Ø10 STIRRUPS, SPACED 1@50, 4@100, REST @ 200 TO CL 50 2 3-Ø16 ST-9 OTHERWISE) SECTION DETAIL SECTION OF PWD RAMP NOT TO SCALE 175 Ø16 @ 125 COMPACTED SELECT BORROW SUBBASE 250 Ø16 @ 150 SEE ARCH DWG. VERIFY STEPS Ø12 @ 250 TOP & BOT. BARS 400 Ø16 @ 125 L/4 Ø10 @ 400 E.W. (UNLESS NOTED OTHERWISE) 3-Ø16 Ø10 STIRRUPS, SPACED 1@50, 4@100, REST @ 200 TO CL COMPACTED SELECT BORROW SUBBASE 250 300 Ø10 NOSING BAR (TYP. AT ALL STEPS) 0 45 2-Ø10 CONT. W/ Ø10 TRANSV. BARS @ 400 O.C. MAX. 55 0 15 Ø10 BAR CHAIRS @ 450 (BOTH ENDS) (TYP. AT ALL STEPS) SEE ARCH DWG. VERIFY RISER LANDING LEVEL 0 15 Ø10 BAR CHAIRS @ 450 (BOTH ENDS) (TYP. AT ALL STEPS) MAIN/SERVICE/ REAR ENTRANCE LVL Ø10 NOSING BARS W/ Ø10 CHAIR BARS @ 450 O.C. (TYP.) 3-Ø16 150 300 L Ø10 @ 300 Ø16 @ 150 250 L/4 FFL 300 NGL 200 TYPICAL3 STAIR ON GRADE DETAIL DETAIL OF STAIR ON-FILL Ø16 @ 150 VERT. BARS E.F. ST-9 250 3-Ø10 LONG. BARS Ø10 @ 300 TRANS BARS 600 100mm THK. WELLCOMPACTED GRAVEL BASE 1 ST-9 DETAIL OF FIRE ESCAPE STAIR NOT TO SCALE NOT TO SCALE