I. STRUCTURAL DESIGN II. CONSTRUCTION NOTES A. CODES AND STANDARDS A. GENERAL 1. GOVERNING CODES ACI 318R-95 (REVISED 1995) UBC 1991 EDITION NSCP 2002 EDITION AISC 9TH EDITION 2. GOVERNING STANDARDS ASTM A36 ASTM 611 ASTM C33 / PNS 18 ASTM C39 ASTM C94 / PNS 46 ASTM C150 / PNS 07 PNS 16 SG 671 240 PA (5 PSF) 144 PA (3 PSF) 240 PA (5 PSF) 96 PA (2 PSF) 2. ROOF LIVE LOAD TRIBUTARY AREA (SQM) TA < 20 20 < TA < 60 TA > 60 LOAD (PA) 800 PA 700 PA 600 PA 3. FLOOR DEAD LOAD PARTITIONS FLOOR TILES MASONRY WALLS 960 PA (20 PSF) 1,200 PA (25 PSF) 3,255 PA (68 PSF) 3. ALL FILL AND BACKFILL MATERIALS SHALL BE COMPACTED IN LIFTS NOT EXCEEDING 200 MM THICK WITH ACCEPTABLE EQUIPMENT TO ACHIEVE A MINIMUM 95% MDD BASED ON ASTM D-698. IN-PLACE DENSITY SHALL BETESTED BY THE APPROVED INDEPENDENT TESTING LABORATORY USING ASTM D-1556 SAND CONE APPARATUS. 3. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW CONSTRUCTION. THIS SHALL INCLUDE BUT NOT LIMITED TO BRACING AND SHORING FOR LOAD IMPOSED DURING CONSTRUCTION. 4. FILL AND BACKFILL MATERIALS SHALL BE FREE FROMDEBRIS, WOOD, ROOTS, VEGETABLE MATTER, REFUSE, UNSOUND PARTICLES, DELETERIOUS OR OBJECTIONABLE MATERIALS. ACCEPTABLE MATERIALS SHALL BE CLASSIFIED AS GW, GM, GP, SW AND SM BY ASTM D-2467 AND CONFORM TO THE FOLLOWING: 4. ALL FOUNDATIONS SHALL REST ON 50MM THICK LEAN CONCRETE AT f'c = 6.895 MPA (1000 PSI) UNLESS NOTED OTHERWISE. 5. GENERAL NOTES AND TYPICAL DETAILS SHALL APPLY TO ALL DRAWINGS UNLESS SHOWN OR NOTED OTHERWISE. LIQUID LIMIT = ACCORDANCE WITH ASTM D-423 PLASTICITY INDEX = SHALL NOT EXCEED 25 SHALL NOT EXCEED 12 % WHEN TESTED IN ACCORDANCE WITH ASTM D-424 NO MORE THAN 25% BY WEIGHT AND SHALL BE FINER THAN NO. 200 SIEVE WHEN TESTED IN ACCORDANCE WITH ASTM D-1140. 6. ALL BAR DIAMETERS AND SPACINGS ARE IN MILLIMETER UNLESS OTHERWISE NOTED. 7. ALL DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON PLANS, SECTIONS AND DETAILS. ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE NOTED. SOIL COMPACTION REQUIREMENTS 90 % FDT = = 95 % FDT 85 % FDT = B. CONCRETE AND REINFORCING STEEL 1. MINIMUM CONCRETE COVER TO ALL REINFORCING BARS FOR NON-CORROSIVE ENVIRONMENT SHALL BE AS FOLLOWS: A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 75 MM B. FORMED SURFACES EXPOSED TO EARTH OR WEATHER D16MM DIA. BARS OR SMALLER 40 MM 50 MM OTHER BARS C. FORMED SURFACE NOT EXPOSED DIRECTLY TO WEATHER OR EARTH SLABS, WALLS AND JOISTS 20 MM 40 MM BEAMS, GIRDERS AND COLUMNS INSIDE THE BUILDING PARKING AREA LANDSCAPING F. CONSTRUCTION JOINTS 1. CONSTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS TO LEAST IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO APPROVAL OF THE ENGINEER. 2. SLAB ON GRADE SHALL HAVE CONTROL JOINTS AT 6.00M MAXIMUM CENTER TO CENTER UNLESS OTHERWISE SHOWN. 2. MINIMUM CONCRETE COVER FOR CORROSIVE ENVIRONMENT NOT EXPOSED TO EARTH OR GROUND WITH FORM: 50 MM A. REINFORCED CONCRETE WALL 50 MM B. SLAB C. BEAMS/COLUMNS 65 MM III. SITE SPECIFIC DESIGN PARAMETERS = ZONE BASIC WIND SPEED = EXPOSURE = = ALLOWABLE SOIL BEARING CAPACITY MINIMUM DEPTH OF FOOTING EMBEDMENT BELOW NATURAL GRADE LINE = 3. MINIMUM CONCRETE COVER FOR CORROSIVE ENVIRONMENT EXPOSED TO EARTH OR GROUND WITH FORM: A. REINFORCED CONCRETE WALL 62 MM B. SLAB 62 MM 80 MM C. BEAMS/COLUMNS 100 MM D. FOOTING SOIL TEST REPORT: BY = DATE = __________ 4 __________ __________ 2500 psi __________ __________ __________ __________ 4. REINFORCING BARS SHALL BE FREE OF RUST, GREASE OR OTHER MATERIALS THAT ARE LIKELY TO IMPAIR BOND WITH CONCRETE. 4. FLOOR LIVE LOAD ROOMS 2,400 PA (50 PSF) BAR SIZE (MM) D (MM) 180° L (MM) 135° D10MM Ø 40 75 75 D12MM Ø 48 75 75 L (MM) DETAILING DIMENSION 7. SPLICES REQUIRED IN THE REINFORCEMENT OF BEAMS/GIRDERS FRAMING INTO COLUMNS SHALL NOT BE LOCATED WITHIN THE COLUMN NOR WITHIN A DISTANCE OF TWICE THE BEAM/ GIRDER DEPTH FROM THE FACE OF THE COLUMN. AT LEAST TWO CLOSED STIRRUP TIES SHALL BE PROVIDED AT ALL SPLICES. 135° HOOK 9. CAMBER ALL BEAMS AT LEAST 0.006M FOR EVERY 4.50M BUT IN NO CASE LESS THAN 0.019M FOR EVERY 3.00M. BAR SIZE (MM) D (MM) 180° L (MM) 90° L (MM) D10MM Ø 60 65 120 D12MM Ø 72 65 145 D16MM Ø 96 65 195 2. THE CONTRACTOR SHALL FURNISH ALL PLATES, CLIP ANGLES, CONNECTORS ETC. FOR THE COMPLETION OF THE STRUCTURE EVEN IF SUCH ITEM IS NOT SHOWN ON DRAWINGS. NOTED. D20MM Ø 120 80 240 D25MM Ø 150 100 300 D28MM Ø 224 115 340 10. SPECIAL TIES/TRANSVERSE HOOP REINFORCEMENT SHALL BE PROVIDED WITHIN THE BEAM AND COLUMN JOINT. L STIRRUPS AND LATERAL TIES 8. LAP SPLICES SHALL BE MADE WITHIN THE CENTRAL HALF OF COLUMN HEIGHT AND THE SPLICE LENGTH SHALL NOT BE LESS THAN 1.30 TIMES THE DEVELOPMENT LENGTH. D W= 6. BAR SPLICES SHALL BE SECURELY WIRED TOGETHER. SPLICES IN REINFORCED CONCRETE BEAMS/GIRDERS, COLUMNS AND WALLS SHALL BE SHOWN IN THE DETAILS. FOR NON-STRUCTURAL WALLS, MASONRY WALLS AND SLABS, SPLICES SHALL LAP A MINIMUM OF 40 BAR DIAMETER AND SHALL BE STAGGERED WHEREVER POSSIBLE. D WHERE Z = I= C= Rw = L 5. ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT. 5. WIND LOAD A. BASIC WIND SPEED (REFER TO 2.3A OF NSCP) ZONE I 250 MPH 200 MPH ZONE II B. EXPOSURE EXPOSURE B HAS TERRAIN WITH BUILDINGS, FOREST OR SURFACE IRREGULARITIES, 6.0 METERS OR MORE IN HEIGHT, COVERING AT LEAST 20 % OF THE AREA EXTENDING 1.50 KM OR MORE FROM SITE. EXPOSURE C HAS TERRAIN WHICH IS FLAT AND GENERALLY OPEN, EXTENDING 800 METERS OR MORE FROM THE SITE IN ANY FULL QUADRANT. C. DESIGN WIND PRESSURE WHERE P = DESIGN WIND PRESSURE P = Ce Cqʆ Ce = COMBINED HEIGHT, EXPOSURE AND GUST FACTOR COEFFICIENT 0.63 AT EXPOSURE B 1.08 AT EXPOSURE C Cqʆ = PRESSURE COEFFICIENT FOR THE STRUCTURE OR PORTION OF STRUCTURE UNDER CONSIDERATION 6. EARTHQUAKE FORCE V = (Z I C / Rw) W 2. FORMWORKS SHALL BE IN PLACE PRIOR TO INSPECTION. CONCRETE POURING OF THE FOUNDATION SYSTEM SHALL NOT BE ALLOWED WITHOUT FIRST OBTAINING WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER-OF-RECORD, 2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE, WHICH SHALL INCLUDE THE DIMENSION AND LOCATION OF OPENINGS, GROOVES, REGLETS, PIPE SLEEVES, CONDUITS AND EMBEDDED OR ATTACHED ITEMS TO CONCRETE, ET CETERA. B. DESIGN LOADS 1. ROOF DEAD LOAD TRUSSES METAL ROOFING AND PURLINS CEILING ALL FIXTURES 1. THE STRUCTURAL ENGINEER-OF-RECORD, UPON NOTIFICATION, SHALL CONDUCT A THOROUGH INSPECTION OF THE FOUNDATION WORKS AFTER EXCAVATION FOR FOOTINGS ARE COMPLETE AND ANY REQUIRED REINFORCING STEEL ARE IN PLACE. 1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, THE ARCHITECTURAL, CIVIL, PLUMBING, ELECTRICAL AND MECHANICAL DRAWINGS. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE UNIFORM BUILDING CODE NATIONAL STRUCTURAL CODE OF THE PHILIPPINES, VOLUME I MANUAL OF STEEL CONSTRUCTION, ALLOWABLE STRESS DESIGN, AMERICAN INSTITUTE OF STEEL CONSTRUCTION STRUCTURAL STEEL STEEL SHEET, CARBON, COLD-ROLLED STRUCTURAL ALLOY SPECIFICATION FOR STEEL BARS FOR STEEL REINFORCEMENT STANDARD SPECIFICATION FOR CONCRETE AGGREGATES STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF CYLINDRICAL CONCRETE SPECIMENS STANDARD SPECIFICATION FOR READY-MIXED CONCRETE STANDARD SPECIFICATION FOR PORTLAND CEMENT PHILIPPINE NATIONAL STANDARD FOR CONCRETE HOLLOW BLOCKS SPECIFICATION FOR THE DESIGN OF COLD-FORMED STRUCTURAL STEEL MEMBERS BY AMERICAN IRON AND STEEL INSTITUTE ASTM 615 / PNS 49 E. FOUNDATION C. STRUCTURAL STEEL 0.40 FOR SEISMIC ZONE 4 1.00 IMPORTANCE FACTOR 2.75 MAXIMUM 8.00 DUAL SYSTEM DETAILING DIMENSION 90° HOOK 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) MANUAL 9TH EDITION UNLESS OTHERWISE SHOWN OR NOTED. 0.1375 MAXIMUM, TOTAL SEISMIC LOAD 1. CONCRETE ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS f'c= 21 MPA (3,000 PSI) 3. WELDING SHALL BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY CODE (AWS D1.1) UNLESS INDICATED OTHERWISE. WELDING ELECTRODES SHALL BE E70XX. 2. REINFORCING STEEL YIELD STRENGTH fy= 275 MPA (40,000 PSI) 4. ALL BOLTS AND THREADED FASTENERS SHALL CONFORM WITH ASTM A-325 UNLESS OTHERWISE D C. DESIGN MATERIAL STRESSES L DETAILING DIMENSION 3. STRUCTURAL STEEL YIELD STRENGTH fy= 250 MPA (36,000 PSI) 4. COLD-FORMED STEEL YIELD STRENGTH fy= 230 MPA (33,000 PSI) 5. MASONRY ULTIMATE COMPRESSIVE STRENGTH FOR BUILDING WALLS, PERIMETER FENCES AND TRENCHES fm'= 4.83 MPA (700 PSI) 6. MASONRY CONCRETE GROUT COMPRESSIVE STRENGTH f'c= 13.8 MPA (2,000 PSI) 7. MASONRY REINFORCING STEEL YIELD STRENGTH fy= 275 MPA (40,000 PSI) 8. STEEL PIPE YIELD STRENGTH fy= 250 MPA (36,000 PSI) PROJECT NAME AND LOCATION: 180° HOOK D. MASONRY MAIN BARS 1. ALL MASONRY WALLS/CONCRETE HOLLOW BLOCKS SHALL BE LAID IN FLEMISH BOND (INTERLOCKING COURSE) WITH FULL MORTAR BEDDING. STACK BOND SHALL BE USED ONLY WHEN SPECIFIED. 2. ALL CELLS SHALL BE FULLY FILLED WITH CONCRETE GROUT. STANDARD HOOKS AND DIMENSIONS 3. THE MINIMUM COMPRESSIVE STRENGTH OF CONCRETE HOLLOW BLOCK AT 28 DAYS SHALL BE 4.83 MPA (700 PSI) UNLESS OTHERWISE SPECIFIED. SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE CONSTRUCTION NOTES DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 1 15 11 37 1.0 GENERAL INSTRUCTIONS 200 CHB WALL WALL THICKNESS 1.1 THE ARCHITECT IN-CHARGE/CIVIL ENGINNER SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE AND SHALL NOTIFY THE ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND INFORMATION SHOWN IN THE DRAWINGS BEFORE PROCEEDING WITH THE WORK.THIS SHALL INCLUDE THE LOCATION AND DIMENSION OF GROOVES, REGLETS, SLEEVES , CURVES , OPENINGS , EMBEDDED OR ATTACHED ITEMS ,ETC.REFER TO ARCHITECTURAL ,MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS. 10mmØ TIES @ 150mm O.C. 2-12mm Ø HOR. BARS 200 (MIN) (MIN) 2-12mm Ø HOR. BARS 10mmØ TIES @ 150 O.C. WALL THICKNESS 1.2 ALL WORK AND MATERIALS SHALL CONFORM TO THE MINIMUM STANDARDS OF THE LATESTS EDITION OF THE UNIFORM BUILDING CODE AND SUCH REGULATING AGENCIES EXERCISING AUTHORITY OVER ANY PORTION OF WORK. CHB WALL 1.3 THE ARCHITECT IN-CHARGE/CIVIL ENGINEER SHALL PROVIDE ERECTION BRACING AND SHORING FOR ALL STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE STABILITY DURING ALL PHASES OF CONSTRUCTION. LINTEL BEAM BOND BEAM 1.4 ALL SLABS,BEAMS,GIRDERS,AND OTHER STRUCTURAL ELEMENTS WHICH ARE NOT INDICATED DETAILED,DESIGNATED OR INADVERTENTLY OMITTED BUT ARE NECESSARY BUT TO BE COORDINATED WITH THE ARCHITECTURAL AND OTHER ALLIED ENGINNERING AS WELL TO COMPLETE THE STRUCTURAL WORKS IN ACCORDANCE WITH THE INTENT OF THE PLANS AND SPECIFICATIONS SHALL BE BROUGHT UP DURING MEETINGS. 1.5 IN THE INTERPRETATION OF THESE DRAWINGS INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. STANDARD BEAM DETAILS 1.6 SPECIFICATION NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. 1.7 ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE NOTED. 1.8 SHOP DRAWINGS FOR STEEL AND CONCRETE CONSTRUCTION SHALL BE BE SUBMITTED FOR APPROVAL PRIOR TO FABRICATION. BAR SIZE ℓ db (MM) BASIC LENGTH ℓ db (MM) 1.9 ALL SPECIFICATIONS REFFERED TO IN THE DRAWINGS MUST BE THE LATEST EDITIONS UNLESS OTHERWISE NOTED. ℓ db (150MM MIN.) D12MM Ø 175 D16MM Ø 234 D20MM Ø 292 D25MM Ø 365 D28MM Ø 409 D32MM Ø 467 D36MM Ø - 2.0 FOUNDATION CRITICAL SECTION 2.1 FOOTINGS ARE DESIGNED FOR A NET ALLOWABLE SOIL BEARING PRESSURE OF 2000 Psf. AT A MINIMUM DEPTH OF (SEE DRAWING) FROM A NATURAL GRADE LEVEL. THE ARCHITECT IN-CHARGE/CIVIL ENGINNER SHALL REPORT IN WRITING TO THE DESIGNER ON ACTUAL CONDITIONS UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. CRITICAL SECTION 2.2 NO FOOTING SHALL REST ON FILL. FOOTINGS FOR CONCRETE HOLLOW BLOCKS WALLS AND OTHER MINOR STRUCTURE SHALL BE EMBEDDED AT LEAST 750 MM. FROM THE NATURAL GRADE LEVEL UNLESS OTHERWISE NOTED. db 150 db D10MM Ø ℓ db (150MM MIN.) 2.3 PROVIDE TEMPORARY MEANS FOR REMOVAL OF WATER FROM ANY SOURCE DURING CONSTRUCTION DEWATERING SHALL BE CAREFULLY AND PROPERLY PERFORMED TO AVOID DISTURBING FOUNDATIONS SLAB BEARING SURFACES. 180° HOOK 2.4 THE ARCHITECT IN-CHARGE/CIVIL ENGINEER SHALL DESIGN, INSTALL, AND MONITOR ALL EXCAVATION RETENTION SYSTEMS AS REQUIRED FOR PROTECTION OF ADJACENT PROPERTIES AND PROVIDE ALL MEASURES AND PRECAUTIONS TO MINIMIZE SETTLEMENT OF AND PREVENT DAMAGE TO ADJACENT EXISTING OR NEW CONSTRUCTION. 90° HOOK 2.5 DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL GROUND FLOOR HAVE BEEN PLACED AND THE CONCRETE HAS ATTAINED THE REQUIRED STRENGTH. 2.6 REFER TO ARCHITECTURAL DRAWINGS ELEVATIONS, DETAILS, REFER TO ARCHITECTURAL ,MECHANICAL, PLUMBING, AND OTHER TRADES FOR SUB-SOIL DRANAIGE SYSTEM , MACHINERY ANCHORS AND OTHER EMBEDDED ITEMS , DEPRESSIONS ,FINISHES , DOWELS FOR MASONRY WALLS , CURBS, ETC. DEVELOPMENT LENGTHS SHALL BE AS FOLLOWS: 2.7 ALL STRUCTURAL FILL MATERIALS SHALL BE COMPACTED TO 95% RELATIVE COMPACTION WITH ASTM D698. FILL SHOULD BE PLACED IN LIFTS NOT TO EXCEED 300MM. A. USE 0.70 ℓ db FOR BARS WITH SIDE COVER (NORMAL TO PLANE OF HOOK) NOT LESS THAN 65MM, AND FOR 90° HOOK, COVER ON BAR EXTENSION BEYOND HOOK NOT LESS THAN 50MM. B. USE 0.80 ℓ db FOR BARS WITH HOOKS ENCLOSED VERTICALLY OR HORIZONTALLY WITHIN LATERAL TIES OR STIRRUPS - TIES SPACED ALONG THE FULL DEVELOPMENT LENGTH ℓ dh NOT GREATER THAN 3db. C. USE 0.80 ℓ db FOR BARS NOT INCLUDED IN A AND B. 2.8 WHERE LOOSE MATERIAL IS ENCOUNTERED AT DEPTH OF EMBEDMENT INDICATED EXCAVATE TO FIRM LAYER. 3.0 REINFORCING STEEL 3.1 GRADE : ASTM A 615 GRADE 40 12 DIA. TO 25 DIA. ASTM A 615 GRADE 33 10 DIA. 10 DIA. AND SMALLER ASTM A 185 OR BS 4483 SLAB ON GRADE DEFORMED BARS (fy= 276 Mpa) DEFORMED BARS (fy=230 Mpa) WELDED WIRE FABRIC (fy= 500Mpa) STANDARD HOOK BARS 3.2 ALL BARS SHALL BE BENT COLD UNLESS PERMITTED BY THE STRUCTURAL ENGINEER. BAR SIZE ℓ db (MM) BASIC LENGTH ℓ db (MM) 3.3 THE MINIMUM LAP LENGHT ARE SHOWN THE TABULATION. (SEE TABLE 1). MINIMUM LENGTH ℓ db (MM) TOP BARS 3.4 ALL REINFORCING SHALL BE SUPPORTED IN CONFORMANCE WITH THE MANUAL OF STANDARD PRACTICE DETAILING REINFORCED CONCRETE STRUCTURE (ACI 315 LATEST EDITION). 3.5 ALL REINFORCING BARS SHALL BE CLEANED THOUROUHLY OF ALL LOOSE RUST, SOIL OR OTHER MATERIAL IMMEDIATELY PROIR TO PLACING CONCRETE. OTHERS ℓ db (300MM MIN.) 90 395 300 D12MM Ø 130 470 350 D16MM Ø 231 630 465 D20MM Ø 361 785 585 D25MM Ø 565 1185 915 D28MM Ø 708 1330 1020 D32MM Ø 925 1520 1170 3.6 ALL WELDING OF REINFORCEMENT SHALL CONFORM TO THE PROVISIONS OF THE STRUCTURAL WELDING CODE REINFORCING STEEL , AWS D 1.4. 3.7 A FULL MECHANICAL CONNECTION (REBAR SPLICER) SHALL DEVELOP IN TENSION OR COMPRESSION AS REQUIRED AT LEAST 125% OF THE SPECIFIED YIELD STRENGHT fy OF THE REBAR IF USED, SUBMIT SAMPLE FOR APPROVAL OF THE DESIGNER. 3.8 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES , SHALL BE LOCATED AS FOLLOWS: a.) INTERMEDIATE BEAMS, TOP BARS SHOULD BE SPLICED AT MIDSPAN AND BOTTOM BARS AT THE SUPPORT. b.)BEAMS FRAMING TO COLUMNS : TOP AND BOTTOM BARS SHALL NOT BE SPLICED WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN. THE SPLICE LENGHT SHALL NOT BE LESS THAN 1.3 x THE DEVELOPMENT LENGHT (Ld). c.) COLUMNS LAP SPLICES SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT AND THE SPLICE BAR SPLICE SHALL BE 0.60 M. IF STAGGARD SPLICING IS USED. d.) CMU WALLS: PROVIDE DOWELS ON R.C COLUMNS , BEAMS, FOOTINGS , AND FOOTINGS TIE- BEAMS TO MATCH CMU WALL REINFORCEMENT. CRITICAL SECTION db D10MM Ø STRAIGHT 3.7 UNLESS INDICATED OTHERWISE ALL BEAMS TERMINATING AT COLUMN SHALL HAVE TOP & BOTTOM BARS EXTENDING TO THE FAR FACE OF THE COLUMN. TERMINATING IN A STANDARD 90DEGRESS HOOK OF ANCHORAGE SHALL NOT BE LESS THAN 0.60 M. STRAIGHT BARS STANDARD DEVELOPMENT OF BARS PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE CONSTRUCTION NOTES DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 2 16 11 37 4.0 CONCRETE TABLE 1.0 4.1 UNLESS OTHERWISE INDICATED IN PLANS OR NOTED IN THE SPECIFICATIONS THE MINIMUM 28-DAYS CYLINDER COMPRESSIVE OF CONCRETE fc' SHALL BE AS FOLLOWS; a.) FOOTINGS , FOOTING TIE BEAMS , RETAINING WALLS AND BASEMENT WATER TANK. b.) COLUMNS , PEDESTALS , AND SHEAR WALLS c.) FLOOR SLABS, BEAMS AND GIRDERS d.) DECK FLOORS , CANOPIES e.) PARTITIONS , CURTAIN WALLS ,BEDDED SLABS SIDEWALKS , CURBS, AND GUTTER & OTHER NON-STRUCTURAL ELEMENTS f.) LEAN CONCRETE MINIMUM EMBEDMENT AND LAP SPLICE (mm.) 20.7Mpa(3000 Psi). 20.7Mpa(3000 Psi). 20.7Mpa(3000 Psi). 20.7Mpa(3000 Psi). 17.0Mpa(2500 Psi). fc' = 20.7 Mpa TO 40 Mpa BAR SIZE 10.0Mpa(1500 Psi). c.) AGGREGATE SIZE SHALL BE AS FOLLOWS: a.) 20 mm. SUSPENDED SLABS, BEAMS, GIRDERS,WALLS AND COLUMNS. b.) 40 mm. FOOTING , THICKENED SLABS AND SLAB ON GRADE. d.) MINIMUM COVERING OF CONCRETE FOR REINFORCING BARS SHALL NOT BE LESS THAN: -75mm. UNIFORMED CONCRETE DEPOSITED AGAINST GROUND. -50mm. FORMED CONCRETE AGAINST GROUND OR EXPOSED TO WEATHER FOR BARS LARGER THAN 16MM. IN DIAMETER. -40mm. FORMED CONCRETE AGAINST GROUND OR EXPOSED TO WEATHER FOR BARS 16MM. IN DIAMETER AND SMALLER. -40mm. BEAMS AND COLUMNS NOT EXPOSED TO GROUND OR TO WATER. -20mm. SLABS AND WALLS NOT TO EXPOSED TO GROUND OR TO WEATHER. -75mm. CONCRETE EXPOSED TO WEATHER. TOP BARS (W/IN 300 OF CONCRETE CAST BELOW) STRAIGHT EMBEDMENT Ld. EMBEDMENT LENGHT E W/ STD. END HOOK H 10 dia. 250 E = 25 E = 150 300 400 500 12 dia. 300 E = 150 E = 200 400 500 16 dia. 400 E = 200 E = 250 500 20 dia. 500 E = 250 E = 300 25 dia. 800 E = 300 E = 400 4.2 a.) CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION , RE -HANDLING OR FLOWING, PLACING SHALL BE DONE PREFERABLY WITH BUGGIES , BUCKETS OR WHEEL BARROWS. b.) NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR USUAL CONDITIONS WHERE VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH. OTHER THAN TOP BARS CLASS A Tension SPLICE ALSO FOR COMPRESSION SPLICE CLASS B Tension SPLICE (1.3 x LD.) CLASS C Tension SPLICE (1.7 x LD.) STRAIGHT EMBEDMENT (1.4 x LD.) CLASS A Tension SPLICE (1.4 x LD.) CLASS B Tension SPLICE (1.82 x LD.) CLASS C Tension SPLICE (2.38 x LD.) 350 350 450 600 600 400 400 600 700 600 700 500 500 700 900 600 700 900 700 700 900 1200 800 1000 1400 1100 1100 1500 1900 BEAM BOT. BARS WHERE TENSILE STRESS IN BARS <(0.5fy) & % of BAR SPLICE >75%. FOR CONCRETE WALL VERT. BAR SLAB & SLAB & BEAMS BARS WHERE TENSILE STRESS IN BARS<(0.5fy)& % of BARS SPLICE 100%. BEAM TOP BARS WHERE TENSILE STRESS IN BARS <(0.5fy) & % of BAR SPLICE >50%. BEAM TOP BARS WHERE TENSILE STRESS IN BARS <(0.5fy) & % of BAR SPLICE >75%. FOR CONCRETE WALL HOR. BAR BEAM TOP BARS WHERE TENSILE STRESS IN BARS<(0.5fy)& % of BARS SPLICE= 100%. e.) CONCRETE CYLINDERS SHALL BE TAKEN FOR EACH DAYS POUR AND EACH 50cu.m. OR FRACTION THEREOF CAST IN ACCORDANCE WITH ASTM C31 AND TESTED IN ACCORDANCE WITH ASTM C39. f.) WELDED WIRE FABRIC SHALL BE MADE OF COLD DRAWN WIRE AND SHALL CONFORM TO ASTM A185. h.) EXPOSED EDGES OF CONCRETE SHALL HAVE 25 MM.(1") CHAMFER UNLESS OTHERWISE NOTED OR DETAILED. i.) CONSTRUCTION JOINTS IN ALL FLOORS SHALL BE LOCATED WITHIN THE MIDDLE THIRD OF SPANS OF SLABS ,BEAMS , JOINTS, GIRDERS SHALL BE OFFSET A MINIMUM DISTANCE OF TWO TIMES THE WIDTH OF INTERSECTING LINES. REMARKS g.) PRIOR TO PLACING CONCRETE , ALL REINFORCING STEEL ANCHOR BOLTS , DOWELS , EMBEDDED STRUCTURAL STEEL SHAPES , BARS, PLATES , OR OTHER INSERTS SHALL BE WELL SECURED IN POSITION AND APPROVED BY THE ENGINEER. END ANCHORAGE FOR BOTTOM BARS OF SLAB & BEAMS. END ANCHORAGE FOR BOTTOM BARS OF SLAB & BEAMS,WALLS ,COLUMNS DOWELS TO FOOTINGS. FOR COLUMNS VERT. BARS BEAM BOTTOM BARS WHERE TENSILE STRESS IN BAR<(0.5fy) & % of BAR SPLICE > 50%. FOR BEAMS INTO WALLS. 5.0 MASONRY WALLS 5.1 CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 GRADE N. 5.2 MORTAR AND GROUT FOR ALL- REINFORCED MASONRY SHALL CONFORM TO ASTM 270-TYPE M AND SHALL HAVE A MINIMUM 28-DAYS STANDARD CYLINDER COMPRESSIVE STRENGHT OF 20.7 Mpa (3000 Psi). 5.3 ALL MASONRY WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF CONCRETE HOLLOW BLOCKS REINFORCEMENT UNLESS OTHERWISE INDICATED ON PLANS. SCHEDULE OF CONCRETE HOLLOW BLOCK REINFORCEMENTS BLOCK THICKNESS (mm) REINFORCEMENT HORIZONTAL VERTICAL 10mm.dia.AT 600 O.C. 10mm.dia.AT 600 O.C. BLOCK THICKNESS (mm) 6.0 REFERENCES REINFORCEMENT THE FOLLOWING SHALL GOVERN THE DESIGN FABRICATION AND CONSTRUCTION OF THE PROJECT: VERTICAL HORIZONTAL 6.1 AMERICAN CONCRETE INSTITUTE (ACI) PUBLICATIONS. 100 150 12mm.dia.AT 600 O.C. 12mm.dia.AT 600 O.C. ACI 318- 89 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE. ACI 315- 83 MANUAL OF STANDARD PRACTICE FOR DETAILING OF CONCRETE REINFORCEMENT. NOTE: 6.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATION. a. MINIMUM LAP SPLICES =250MM. b. PROVIDE RIGHT ANGLE REINFORCEMENT 700 MM.LONG. c. WHERE CHB WALLS ADJOIN COLUMNS RC BEAMS AND WALLS ,DOWELS, WITH THE SAME SIZE AND SPACING AS VERTICAL OR HORIZONTAL REINFORCEMENT SHALL BE PROVIDED. d. PROVIDE BEAM BLOCKS AT EVERY FOURTH COURSE AND POST AT 300 O.C. MANUAL OF STEEL CONSTRUCTION.,9TH EDITION. 6.3 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) 4TH. EDITION. , 1992. 5.4 UNLESS INDICATED OTHERWISE CMU WALLS USED IN THIS SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGHT AT 28 DAYS , f'm=4.83 Mpa. 5.5 UNLESS INDICATED OTHERWISE , ALL CMU WALLS SHALL BE FILLED SOLIDLY WITH GROUT. PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE CONSTRUCTION NOTES DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 3 17 11 37 A B LEGEND C INTERIOR WALL C1F1 COLUMN ONE - FOOTING ONE C2F2 COLUMN TWO - FOOTING TWO 6.00 M. 3.00 M. 3.00 M. C1F1 C1F1 C1F1 ELEV. 0 +175 6 3.21 M. FTB-2 W1F1 FTB-2 3.21 M. FTB-2 W1F1 FTB-2 6 WALL FOOTING ONE WF1 ELEV. 0 +175 5 C1F1 5 C1F1 3.21 M. FTB-2 FTB-2 3.21 M. FTB-1 ELEV. 0+ 225 4 C1F1 4 C1F1 SLAB ON FILL THICKNESS = 100 MM + FINISH W/ 10 MM Ø TEMP. BARS SPACED @ 400 MM O.C. BOTHWAYS 3 C1F1 3 C1F1 15.00 M. 3.21 M. FTB-2 FTB-2 3.21 M. 15.00 M. FTB-1 ELEV. 0+ 225 C1F1 C2F2 3.21 M. FTB-2 FTB-2 3.21 M. FTB-1 C1F1 C2F2 C1F1 2 2 FTB-2 2.15 M. 2.15 M. RAMP ELEV. 0+ 200 C2F2 C2F2 1 1 RAMP UP 1.50 M. 3.00 M. 1.50 M. 6.00 M. A S - 100 1 B C D FOUNDATION PLAN 4 PROJECT NAME AND LOCATION: SHEET CONTENTS: 1 DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: SCALE 100 RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE FOUNDATION PLAN DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 5 18 11 37 COLUMN SCHEDULE LEVEL COLUMN ( C - 1 ) COLUMN ( C - 2 ) COLUMN ( C - 3 ) COLUMN ( C - 4 ) COLUMN ( C - 5 ) FFL NAT. GRD. LINE FTB Y - BAR ( LONGITUDINAL ) DEPTH ROOF BEAM LEVEL FTB SIZE : X - BAR ( TRANS VERSE ) SIZE : 350 mm. x 350 mm. 100 MM. THK. GRAVEL FILL 300 mm. x 300 mm. MAIN BARS : MAIN BARS : 4 - 25 MM. Ø BARS. 8 - 20 MM. Ø BARS. T ADDITIONAL BARS : 8 - 20 MM. Ø BARS. TIES : TIES : 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. SECTION FOUNDATION LEVEL TO GROUND FLOOR LEVEL 2 S 5 SIZE : SCALE: 1:30 M. X - BAR ( TRANS VERSE ) SIZE : 350 mm. x 350 mm. DETAIL OF WF-1 300 mm. x 300 mm. MAIN BARS : Y - BAR ( LONGITUDINAL ) MAIN BARS : 4 - 25 MM. Ø BARS. 8 - 20 MM. Ø BARS. ADDITIONAL BARS : 8 - 20 MM. Ø BARS. TIES : TIES : 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. WIDTH GROUND LEVEL TO ROOF BEAM LEVEL LENGTH PLAN SIZE : SIZE : 350 mm. x 350 mm. 300 mm. x 300 mm. MAIN BARS : MAIN BARS : 4 - 25 MM. Ø BARS. 1 S 5 8 - 20 MM. Ø BARS. ADDITIONAL BARS : 8 - 20 MM. Ø BARS. TIES : TIES : 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. 3 TIES AT 10 MM. Ø 3 @ 50 , 5 @ 100 , 7 @ 150 REST 200 MM. TO CENTER. TYPICAL FOOTING DETAIL SCALE: 1:30 M. SCHEDULE OF FOOTING FOOTING DIMENSIONS REINFORCEMENTS FOOTING MARK REMARKS FTB BAR " X " BAR " Y " LENGTH WIDTH DEPTH F1 10 - 16 MM. DIA. 10 - 16 MM. DIA. 1300 1300 1200 250 SQUARE FOOTING F2 8 - 16 MM. DIA. 8 - 16 MM. DIA. 1200 1200 1200 250 SQUARE FOOTING THICKNESS 3 S 5 PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: WALL TO TIE-BEAM CONN. DETAIL SCALE: 1:20 M. RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE COLUMN SCHEDULE SCHEDULE OF FOOTING TYPICAL FOOTING DETAIL DETAIL OF WF-1 WALL TO TIE-BEAM CONNECTION DETAIL REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 6 19 11 37 A B LEGEND C B-1 S-1 5 3.21 M. S-1 4 G-1 S-1 3.21 M. B-1 B-2 S-2 B-4 B-1 3.21 M. 15.00 M. STAIR WELL 15.00 M. G-1 B-1 S-1 4 S-1 G-1 B-2 B-1 3.21 M. 5 G-1 6 B-1 3.21 M. 3.00 M. B-1 3.00 M. B-2 B-1 3.21 M. 6 6.00 M. 3 3 S-1 2 3.21 M. B-2 B-1 3.21 M. S-1 2 S-1 B-1 G-1 G-1 2.15 M. 1 B-3 1 S-1 B-2 B-3 B-1 2.15 M. B-2 B-1 1.50 M. 3.00 M. 1.50 M. 6.00 M. A S - 100 1 B C D SECOND FLOOR FRAMING PLAN 6 PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: 1 REVIEWED: SUBMITTED: SCALE 100 RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE SECOND FLOOR FRAMING PLAN DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 7 20 11 37 BEAM & GIRDER SCHEDULE FLOOR LEVEL BEAM MARK b ROOF LEVEL (mm) RB - 1 250 BAR ARRANGEMENT SUPPORTS h (mm) 400 SCHEDULE OF SLAB REINFORCEMENT BARS BEAM DIMENSIONS TOP MIDSPAN BOTTOM 5-20 mmØ 4-20 mmØ TOP 4-20 mmØ WEB BARS SUPPORTS BOTTOM STIRRUPS SIZE & SPACING 10mm Ø, 1@50 6@100, REST @ 200mm O.C. 300 2-16 mmØ 2-16 mmØ 2-16 mmØ 2-16 mmØ G-1 300 500 6-20 mmØ 4-20 mmØ 4-20 mmØ 6-20 mmØ REMARKS PARALLEL TO LONG SPAN 4-20 mmØ 200 THICKNESS MIDSPAN 10mm Ø, 1@50 7@100, REST @ 200mm O.C. RB - 2 REINFORCEMENT BARS MARK PARALLEL TO SHORT SPAN S-1 125 MM 10 mmØ @ 250 mm O.C. BENT-UP 2 OUT OF 3 @ L/4 FROM THE FACE OF THE SUPPORT 10 mmØ @ 190 mm O.C. BENT-UP 2 OUT OF 3 @ L/4 FROM THE FACE OF THE SUPPORT TWO-WAY S-2 125 MM 10 mmØ @ 250 mm O.C. TEMP. BARS 10 mmØ @ 250 mm O.C. BENT-UP 2 OUT OF 3 @ L/4 FROM THE FACE OF THE SUPPORT ONE-WAY 10mm Ø, 1@50 10@100, REST @ 200mm O.C. 2-16 mmØ 2 3 1 4 250 350 4-20 mmØ 2-20 mmØ 2-20 mmØ 4-20 mmØ 2-16 mmØ 10mm Ø, 1@50 8@100, REST @ 200mm O.C. B-2 250 350 4-16 mmØ 2-16 mmØ 2-16 mmØ 4-16 mmØ 2-16 mmØ 10mm Ø, 1@50 8@100, REST @ 200mm O.C. B-3 250 350 3-16 mmØ 2-16 mmØ 2-16 mmØ 3-16 mmØ 10mm Ø, 1@50 7@100, REST @ 200mm O.C. SB - 1 200 300 2-16 mmØ 2-16 mmØ 2-16 mmØ 2-16 mmØ 10mm Ø, 1@50 3@100, REST @ 200mm O.C. FTB - 1 300 500 4-20 mmØ 4-20 mmØ 4-20 mmØ 4-20 mmØ FTB - 2 250 350 5-20 mmØ 2-20 mmØ 3-20 mmØ 2-20 mmØ COL. COL. COL. COL. 10mm Ø, 1@50 10@100, REST @ 200mm O.C. 2-16 mmØ TIE BEAM SECOND FLOOR LEVEL B-1 10mm Ø, 1@50 8@100, REST @ 200mm O.C. SPAN RANGES 3.50 M. ( VERIFY ) SEE FLOOR FRAMING PLAN L1 A L3 L2 B TYPICAL TWO - WAY SLAB DETAIL 2D L2/3 L2/3 2D L3/3 2D L3/3 2D 2D LAP SPLICES ARE ALLOWED ONLY ON THIS PORTION LAP SPLICES ARE ALLOWED ONLY ON THIS PORTION A B SHORT SPAN = S S/4 CONTINOUS L2/5 L2/5 L2/5 L3/6 2 - 16 mm Ø SIDE BARS RC BEAM RC BEAM DISCONTINOUS EDGE CONTINOUS BEAM SECTION DETAIL RC SLAB SECTION DETAIL PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE BEAM AND GIRDER SCHEDULE SCHEDULE OF SLAB BEAM SECTION DETAIL TYPICAL TWO-WAY SLAB DETAIL RC SLAB SECTION DETAIL REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 8 21 11 37 A B LEGEND C 6.00 M. 3.00 M. RB- 2 RB- 2 6 6 3.00 M. RB- 1 RB- 1 TRUSS 1 TRUSS 1 3.21 M. GUTTER RB- 2 C PURLIN C PURLIN RB- 2 GUTTER TRUSS 1 3.21 M. TRUSS 1 RB- 2 3.21 M. TRUSS 1 RB- 1 3 3 RB- 1 15.00 M. RB- 1 4 GUTTER RB- 2 RB- 1 RB- 2 3.21 M. 15.00 M. 4 GUTTER 3.21 M. RB- 2 5 5 3.21 M. TRUSS 1 RB- 2 3.21 M. GUTTER RB- 2 TRUSS 1 2 2 TRUSS 1 C PURLIN TRUSS 1 C PURLIN RB- 2 GUTTER 3.21 M. TRUSS 1 2.15 M. RB- 2 RB- 2 CB- 1 CB- 1 1 GUTTER GUTTER 1 2.15 M. TRUSS 2 TRUSS 2 1.50 M. 3.00 M. 1.50 M. 6.00 M. A S - 100 1 B C D ROOF FRAMING PLAN 8 PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: 1 REVIEWED: SUBMITTED: SCALE 100 RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE ROOF FRAMING PLAN DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 9 22 11 37 6 mm. thk. GUSSET PLATE GA 26 ( .6mm thk. ) PRE - PAINTED PRE - FORMED 50 mm. x 100 mm. x 2.0 mm. C - PURLINS G.I.RIDGE ROLL. @ 700 mm. ON CENTER. 7981 965 1008 1008 1008 1008 1008 1008 965 APEX OF LINE 2007 GA 26 ( .5mm thk. ) PRE - PAINTED LONG SPAN CORRUGATED G.I. SHEET ROOFING. 2617 50 mm. x 50 mm. x 6 mm. CLIP ANGLE BAR. 12 mm. dia. ROUND BAR SAG ROD ( Bolt Type at Ends ) STAGGARD. 184 615 2- 65 mm. x 65 mm. x 6 mm. thk. 2- 65 mm. x 65 mm. x 6 mm. thk. ANGLE BAR ANGLE BAR TOP & BOTTOM CHORD. 250 mm. x 300 mm. x 12 mm. WEB / STRUT MEMBER. 4 - 20 mm. dia. x 300 mm. thk. STEEL BASE PLATE. ANCHOR BOLT. GA 26 ( .6mm thk. ) PRE - PAINTED PRE - FORMED G.I. GUTTER. 75 mm. dia. PVC DOWNSPOUT CLASS 100. T - 1 DETAIL 2- 65 mm. x 65 mm. x 6 mm. thk. ANGLE BAR TOP & BOTTOM CHORD. 50 mm. x 100 mm. x 2.0 mm. C - PURLINS @ 700 mm. ON CENTER. GA 26 ( .6mm thk. ) PRE - PAINTED PRE - FORMED RIDGE ROLL. 5100 300 600 600 600 600 300 1050 1151 1050 1787 GA 26 ( .5mm thk. ) PRE - PAINTED LONG SPAN CORRUGATED G.I. SHEET ROOFING. 637 2- 65 mm. x 65 mm. x 6 mm. thk. ANGLE BAR WEB / STRUT MEMBER. GA 26 ( .6mm thk. ) PRE - PAINTED PRE - FORMED G.I. GUTTER. 184 2- 65 mm. x 65 mm. x 6 mm. thk. ANGLE BAR TOP & BOTTOM CHORD. T - 2 DETAIL TRUSS DETAILS SCALE PROJECT NAME AND LOCATION: SHEET CONTENTS: 1: 20 DRAFTED/PREPARED BY: M. REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE TRUSS DETAILS DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 10 23 11 37 4 3 50 mm. x 100 mm. WOOD HANDRAIL. 900 4 3 LANDING SECOND FIN. FLR. LINE SECOND FIN. FLR. LINE 13 20 mm. SQUARE BAR RAILINGS. 12 250 RUN 250 RUN 200 RUN 11 S 200 RUN 12 mm. dia. BENT / REINFORCING BARS SPACED AT 150 mm. ON CENTER. STAIRS BRASS NOSING. 10 9 SL 650 AB 125 TH IC K NE S 12 mm. dia. REINFORCING BARS SPACED AT SHOWN. 7 6 100 12 mm. dia. REINFORCING BARS SPACED AT 150 mm. ON CENTER. 12 mm. dia. REINFORCING BARS. 12 mm. dia. TEMPERATURE BARS SPACED AT 150 mm. ON CENTER BOTHWAYS. 8 5 4 3 900 125 2 1 SECTION ELEVATION DETAIL FIN. FLR. LINE FIN. FLR. LINE 200 SECTION ELEVATION DETAIL FINISH GRADE 500 5 - 16 mm. dia. STRAIGHT BARS / REINFORCING SPACED AT SHOWN. 250 10 mm. dia. STIRRUPS SPACED AT 3 - 50 , 4 - 100 REST AT 200 mm. ON CENTER. 16 mm. dia. VERTICAL BARS SPACED AT 150 mm. ON CENTER. 100 mm. thk. GRAVEL FILL. 16 mm. dia. STRAIGHT BARS / REINFORCING 800 STAIRS DETAILS SCALE PROJECT NAME AND LOCATION: SHEET CONTENTS: 1: 20 M. DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO. REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS REGIONAL OFFICE NO. 8 LEYTE SECOND ENGINEERING DISTRICT CARIGARA, LEYTE STAIRS DETAILS DETAILED ENGINEERING DESIGN PLAN FOR CONSTRUCTION OF MULTI-PURPOSE BUILDING BARANGAY DISTRICT 3 , PASTRANA , LEYTE REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER DATE: DATE: DATE: DATE: S 11 24 11 37