Siemens Power Technologies International Model Validation using PSS®E Playback Model Restricted © Siemens Industry, Inc. 2015 All rights reserved. siemens.com/power-technologies/software PSS®E 34.1 PSS®E Playback Model (PLBVFU1) Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 2 September 2015 Siemens Power Technologies International PSS®E Playback Model PLBVFU1 overview • This model plays back a known set of voltage and frequency signals. • The PLBVFU1 model acts as a generator model. In using this generator model, do not attach an AVR or governor model to the machine associated with the PLBVFU1 model. • The played-in voltage and frequency signals must be described in a file as shown below, with each sample described in a separate record and the values in each line separated by spaces or commas: Time, voltage, frequency Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 3 September 2015 Siemens Power Technologies International PSS®E Playback Model PLBVFU1 overview • The file containing the measurement has to be supplied in a file with an extension “.plb”. The file name (without the “.plb” extension) has to be less than or equal to 12 characters long. This file has to exist in the working folder. If the “plb” file is not found, the PLBVFU1 model will keep the internal voltage and frequency fixed at the initial value (i.e., the playback feature will be ignored). • The voltage signal which is played back is the internal (Thevenin) voltage of the playback generator. The ZSORCE of the generator used to represent the PLVFBU1 model should be non-zero. • The sampled voltage and frequency values may be smoothed via a first order block with time constants Tv (for voltage signal) and Tf (for frequency signal). Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 4 September 2015 Siemens Power Technologies International PSS®E Playback Model Playback Model (voltage signal) Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 5 September 2015 Siemens Power Technologies International PSS®E Playback Model Playback Model (frequency signal) Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 6 September 2015 Siemens Power Technologies International PSS®E Playback Model Playback Model testing Unit to be tested Playback generator Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 7 September 2015 Siemens Power Technologies International PSS®E Playback Model Playback Model – PMU data vs. PSS®E simulation results Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 8 September 2015 Siemens Power Technologies International PSS®E Playback Model Conclusion • Playback model will be a valuable tool for Model validation – MOD-026, -027 • Model will be available in PSS®E version 34.1 • The model is supplied as part of PSS®E installation; therefore, use of this model will not require compilation and link. Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 9 September 2015 Siemens Power Technologies International Thank You Jay Senthil, Ph.D Senior Staff Engineer Siemens PTI 400 State Street, Schenectady, NY Phone: +1.518.395.5013 email: jayapalan.senthil@siemens.com Restricted © Siemens Industry, Inc. 2015 All rights reserved. Page 10 September 2015 Siemens Power Technologies International