See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/224314054 Surge protection for low voltage power supplies in case of direct lightning strikes - testing of complete systems Conference Paper · July 2005 DOI: 10.1109/PTC.2005.4524816 · Source: IEEE Xplore CITATIONS READS 3 1,394 2 authors, including: Josef Birkl 25 PUBLICATIONS 119 CITATIONS SEE PROFILE All content following this page was uploaded by Josef Birkl on 26 September 2014. The user has requested enhancement of the downloaded file. 1 Surge protection for low voltage power supplies in case of direct lightning strikes testing of complete systems Josef Birkl, and Dr. Peter Zahlmann, DEHN + SÖHNE GMBH + Co. KG - Germany Abstract-- The latest generation of surge protective devices protects sensitive electronic equipment even in case of impulse currents and impulse voltages resulting from direct lightning strokes. Modern arresters should influence the power supply of downstream consumers the least possible. Laboratory tests at complete installations or parts of installations are a possibility to prove the efficiency of such protection devices. Also the performance of installation parts flown through by partial lightning currents can be examined in laboratory tests. The following paper will introduce test procedures by means of application examples in telecommunications and railway engineering, which allow to prove the lightning current carrying capability of system components, the continuity of supply for the system and equipment protection, even at direct lightning currents. These engineering and test services performed in the laboratories of the manufacturer of the SPDs provide a valuable contribution to proving the efficiency of the lightning and surge protective measures. Index Terms-- Lightning protection, surge protection, system testing. L I. INTRODUCTION aboratory testing is an effective way to simulate the effects of lightning and to prove the efficiency of surge protection systems. Surge protective devices (SPDs) have to withstand both the impact of high-energy lightning currents and the interaction with the mains power supply. The derivation of the relevant testing parameters by means of computer simulations are explained. The main focus of this paper is on SPDs for low- AC Power Circuits.. Specific examples have been selected to illustrate requirements for a reproducible and practice-oriented testing of surge protection systems. A. Necessity of system tests The basic proof that surge protective devices (SPDs) correspond to the requirements for use in low voltage installations has been provided for protective devices which comply with the valid product standards, such as IEC 6164311, UL 1449 and , IEEE C62.45-2002. [1]-[3]. The device tests described in the product standards refer almost entirely to the SPD itself. These tests, however, cannot always prove that the full protective effect from the SPDs is also provided in the actual installation environment. For a system test, the conditions must therefore be adapted as closely as possible to the actual system conditions. Such a test system installed in a laboratory includes therefore • • • • the required SPDs further protective devices installed in the system, like overcurrent protective devices and RCDs actual length and the type of connecting cables and their actual cabling, equipment to be protected These system tests aim at the most realistic replication possible of the actual installation conditions, where the SPDs are supposed to apply their protective effects. B. Choosing the right system test Laboratory examinations at complex lightning and surge protection systems should always be carried out in close cooperation between all parties involved , such as the user of the SPDs and their manufacturer. A general rule defining which system tests are required and sensible for each individual application is not possible due to the high number of the different parameters. Numerous system tests have been performed and the principal processing sequence, as shown in Fig. 1, turned out to be favorable: Fig. 1. System testing for a DC- power supply of a telecommunication system 2 The test procedures should be based on standardised test procedures as defined in the product and installation standards: The laboratory tests thus provide comparable and reproducible results. II. SELECTED LABORATORY TESTS Based on different application examples, the following will introduce test procedures which have turned out to be successful individually or in a complete test sequence within the scope of system tests. A. Railway Engineering – Determining the load parameters of SPDs A basic requirement for effective surge protection is the correct choice of SPDs in correspondence with the necessary impulse current capability on the respective installation site. Computer simulations provide a possibility to analyze the distribution of lightning currents within a complex electrical installation. Fig. 2 shows the complex installation environment of a lightning current arrester in railway systems. This analysis requires a description of all electrical parameters of the entire system as exactly as possible. For example, • the earthing resistances • the cable impedances and • the electrical parameters as well as the dynamic performance of the used SPDs are transferred into an electrical equivalent circuit diagram. Casel 2: Direct stroke into a distant mast itot = 100 kA (10/350) Assuming a defined total lightning current load of 100 kA 10/350 in the illustrated example, the lightning current distribution can now be determined within the entire system to be examined. In this case, the risk factors were thus determined for a switch-gear cabinet with integrated electronic system and lightning and surge protection, which is installed close to an electrified railway system. The maximum lightning current load for this specific cabinet was calculated considering different threat scenarios: • Direct stroke into the mast of the contact wire, adjacent to the distribution board • Direct stroke into a distant mast of the contact wire • Direct stroke into the overhead line of the low voltage power supply. The result of such a simulation then provides a matrix of the calculated load parameters of the SPD for the different threat scenarios. These calculated load values have to be aligned with the nominal performance parameters of the SPD provided for this application. This allows already a preliminary estimation, whether the SPDs have been chosen correctly for the actual installation site regarding their discharge capacity. Not only the peak currents loading the SPDs have to be taken into account but also the energy load, i.e. the load or specific energy. These calculated values form then the basis for the following lightning current tests in the laboratory – possibly including a certain safety margin. Case 3: Direct stroke into the low voltage overhead line itot = 100 kA (10/350) Case 1: Direct stroke into an adjacent mast itot = 100 kA (10/350) Low voltage 400 V / 50 Hz Low voltage overhead line Transformer station Station with electrical equipment and surge protection Contact wire 15 kV / 16 2/3 Hz Earthed rail Insulated rail Fig. 2. Installation environment of a Surge protection in a railway system Earthing system of the low voltage installation 3 B. Construction of switch-gear cabinets – Proof of lightning current carrying capability For most applications multipole SPDs are used. Therefore, the following will explain especially the decisive parameters of a lightning current test for multipole SPDs. The lightning current distribution among the individual protection paths of the SPD, e.g. Phase to Neutral or neutral to Earth has considerable importance. Therefore in the latest amendment of the IEC 61643-1 a total discharge current test has been introduced. This test is used to check for the cumulative effects that occur when multiple modes of protection of a multi-pole SPD conduct at the same time. The distribution of the impulse currents and it's characteristic parameters, such as peak current Ipeak, total charge Q and specific energy W/R are shown in table 1. TABLE 1 – TOLERANCES FOR PROPORTIONAL SURGE CURRENTS [1] Test classifi cation Proportional currents and tolerances ± 10 % I peak(1) = I peak(2) = I peak(N) = I peak / N Test class I ± 20 % Q ( 1) = Q (2) = Q ( N) = Q(I Total ) / N W/R ( 1) = W/R (2) = W/R (N) = W/R(I Total ) / N ± 35 % 2 Test class II I 8/20(1) = I 8/20(2) = I 8/20 (N) = I T otal / N ± 10% In the laboratory, this balanced distribution of the impulse currents is ensured by series inductances and resistances. These impedances consist typically of a resistance of 30 mΩ and an inductance of 25 µH. These values correspond to typical cable lengths of approximately 50 meters. For unbalanced protective circuits, an additional external balanced SPD is included into the test circuit, where required. Assuming a balanced surge current distribution amongst the phase lines and the neutral line represents a "worst-case" analysis. Surge-protection systems tested under these conditions can be applied in all application regardless the specific earthing conditions at the individual site. The test construction in the laboratory for proving the lightning current carrying capability of e.g. a telecommunication cabinet with integrated lightning current arrester, is shown in Fig.3. In addition, the equipment to be protected, which is in this example a dc power supply, is connected additionally to the output terminals of the surge protective unit. This test thus exceeds the standardised requirements considerably. However, it offers the user of the SPDs the most realistic proof possible about the actual lightning current carrying capability and the protection of downstream equipment. Following this total discharge current test the correction function both of the SPD and the connected power supply is verified. Fig. 3. Testing the lightning current carrying capability of a telecommunication power supply 4 C. Proof of SPD energy coordination One further important test is the proof of energy coordination between all SPDs installed into an electrical installation. Basically, it is supposed to be proven that none of the SPDs is overloaded at an assumed primary threat with values higher than their max. load parameters (e.g. max. peak current or max. energy absorption capacity). This has to be proven for the entire impulse current range (O-Imax). Different methods for coordinating SPDs are described in as IEC TR 62066 and , IEEE C62.41.1-2002. [4], [5]. In practice, coordination of external SPDs is no problem any more. Today, manufacturers offer coordinated SPD ranges (furnished with decoupling elements, if required) [6]. In contrast, energy coordination of external SPDs and surge protective elements already included in the equipment device to be protected, is often not provided. Especially the growing trend of installing lightning current arresters flown through by direct partial lightning currents and highly sensitive electronic devices next to each other within very small spaces, makes high requirements on the protective effect of such SPDs. In either case, the surge protective elements integrated into the terminal device have to be prevented from “skipping” the protection of the more powerful upstream SPDs. If the design of the SPD integrated into the terminal device can be influenced before, computer simulations can be an effective tool and help to test the aforementioned “blind spot” case. In all other cases, energy coordination can be proven by so-called “coordination tests” in laboratories. The most critical case during a coordination test is often not the maximum impulse current load to be expected. For high impulse currents even the low cable impedance of the internal wiring has often a sufficient de-coupling effect due to its high current steepness di/dt to activate upstream lightning current arresters before the integrated surge protection device is overloaded. Therefore, impulse current tests beginning with small impulse currents are required. The proof of energy coordination must be provided for each individual mode of protection. Therefore, quite comprehensive measurements have to be made to determine the partial currents for each protective element. To obtain comparable and reproducible results of such coordination measurements, a lightning current generator is required with a high “fictive” internal resistance. Only such a generator can ensure that the wave form and especially the steepness of the test current is not influenced by the changing impedance of the test units due to the response of the protective elements. In practice, a lightning current generator with a “fictive” internal resistance ≥ 10 Ω has proven to be sufficient. Figure 4 shows the current oscillograms of such a coordination test among several SPDs for lightning current generators with different “fictive” internal resistances [7]. Fig. 4. Lightning current generators with different “fictive” internal resistances D. Proof of continuity of supply The above test sequences B and C focussed on the lightning current load of the systems. Therefore the SPDs and the connected downstream equipment was tested with partial lightning currents but not connected to the low-voltage power supply during the tests.. But also the performance of the SPDs connected to low-voltage AC Power Circuits – and thus the reliability of power supply – are becoming more and more important for the user. Therefore, the next test to be introduced will include a test for the selectivity of backup fuses and SPDs of the “50 Hz world“. Especially "low-energy" surges have to be considered such as switching overvoltages or coupling by distant lightning strokes. Such low-energy transients arise much more frequently than the especially high-energy interfering currents of close or direct lightning strokes. If an SPD is activated by a low-energy disturbance, no interfering influences on the low voltage supply systems caused by e.g. voltage drops, mains follow currents, false tripping of fuses, should ideally arise neither during nor after the discharge. The mains performance of an SPD is examined during a standard-conform test according to IEC 61643-1 with the so-called "duty cycle test". Following the test procedures of this standard, the SPD is tested in combination with the maximum overcurrent protective device assigned by the manufacturer and at a maximum prospective short-circuit current permitted for the SPD. In real installations, however, there are often overcurrent protective elements installed with a much lower nominal current for reasons of overcurrent protection. In such cases, the frequency of follow currents and the follow current limitation of a lightning current arrester are the decisive parameters for a reliable power supply of a system. The proof of reliable power supply for the respective system configuration, is done by laboratory testing using the basic test procedures in the standards but selecting the actual the overcurrent protective element and the prospective shortcircuit current for the specific application. A complete test series with different prospective short-circuit currents results in a selectivity characteristic as shown in Figure 5. A statement about the reliability of supply at low-energy 5 transients can then be provided for an “SPD” and a “combination of surge and overcurrent protective devices” without requiring further tests. Applying modern lightning current arresters on a spark gap basis, it is ensured that lowenergy overvoltages are suppressed to a low protection level without leading to any 50Hz-mains follow currents. Should impulse currents arise with higher energies and possibly lead to follow currents, these should be limited to ensure that an upstream overcurrent protective element will not respond [8]. For example for tested the lightning current arrester (LCA), described by below diagram , the let-through integral (I2 x t) of the spark gap remains lower than the minimal melting integral of a 32A NH-fuse even at a prospective short-circuit current of 25kA (RMS). Due to the follow current limiting characteristic of uses spark gap, the actually flowing current will be limited to about 1,5% (500A peak) of the prospective value (40kA peak). Fig. 5. Selectivity-limit currents for Lightning Current Arresters (LCAs) in different technologies in comparison with different back-up-fuses That means in a real installation a tripping selectivity is given with all overcurrent protective devices upstream this SPD which have a nominal rating of ≥ 32 A. In order to achieve this power current limiting characteristic the arc voltage of this type of SPDs during the quenching phase hardly differs from the mains voltages. The above described parameters are derived from a complete test series performed for the lighting protection concept of the low-voltage power supply of mobile phone stations. Numerous applications have shown, that a follow current limitation of a SPD, as described above, increases the safety of power supply for the complete system, protected by such an arrester. E. Telecommunications - Proof of equipment protection from direct lightning currents For proving the resistance of electrical and electronic devices against interference or destruction in case of conducted impulse voltages or impulse currents IEC 61000-45 has stipulated defined test levels [6]. However, the standard already points out in the application section, that a proof of immunity of equipment does not always include the immunity against surges of a complete system. Furthermore it is clearly stated in the scope of this standard that direct lightning strokes are not considered. Therefore in the latest draft of IEC 61000-4-5 basic requirements for a system level immunity test are listed: • "In order to ensure system level immunity, a test at the system level is recommended to simulate the real installation. This simulated installation shall be comprised not only of individual EUT’s, but must shall also include protective devices (Surge Protective Devices – SPD’s) and the real length and type of the interconnection lines normally used, all of which can affect the overall system protection level." • "The simple addition of an external SPD that is not coordinated with other internal SPD’s, might have no effect, might reduce the effect on the overall system protection, or might improve overall system protection." • "In a real installation, higher voltage levels can be applied, but the surge energy will be limited by the installed protective devices in accordance with their current-limiting characteristics." The following described proposal of a test procedure for complete systems, fulfills all these requirements. This new test, called ”lightning current test under service conditions” combines the basic test procedures of EMC-testing with the lightning current tests levels, described in the SPD standards for direct lightning strokes. The equipment to be protected , an the externals SPDs, were tested in a common system test under most real service conditions. In contrast to the lightning current test as described in chapter B and C, the equipment to be protected is tested here under service conditions, i.e. the device is activated and connected to its nominal supply voltage and stressed with partial lightning currents. Figure 6 shows the complete test set-up of this “lightning current test under real service conditions”, including the switchboard, which contains the external SPDs and the downstream dcpower-supply to be protected. In this example, the proof of reliable power supply is provided by measuring the dc output voltage of the rectifier. Figure 7 shows clearly that the supply voltage of about 60 V dc is also given for the duration of a flowing 30 kA 10/350 impulse current (high-frequency voltage spikes superimposed on the dc supply voltage can be traced back to induction effects within the measuring loop). 6 Fig. 6. Lightning current test under real service conditions – Example: dc power supply Fig 7. Proof of continuity supply of a dc-rectifier even in case of partial lightning currents These proposed test scheme for complete systems has been successfully performed on various applications, such as: • Power supply of mobile phone base stations • AC-power supplies in railway applications • Pitch drive control systems of wind turbines • Water pumps and its control units • Central DC-AC-inverters of solar power-plants • Electronic power meters In these wide range of applications field experience has confirmed, that the test described in this paragraph simulates the installation conditions as realistic as possible, in which the system is intended to function later on. 7 F. Documentation of the tests The final step of such a customer-specific test program is a detailed and informative test documentation. Such a test report certifies and confirms the successful test of the respective test sequences performed. For comprehensive test constructions, as inevitably required for complex system tests, also the conditions of test constructions like • equipment connected • overcurrent protective elements • and especially the cabling must be documented and described as detailed as possible. III. SUMMARY For technical and economically optimal use of SPDs for protection of complex installations even against direct lightning strokes, both computer simulations and laboratory tests are helpful. • Computer simulations allow to determine the lightning current distribution within the installation to be protected and to analyse the dynamic performance of the SPDs to be used. The suitable SPDs are chosen accordingly and their installation sites are defined. • Equipment testing does not ensure the immunity of a system in case direct lightning strokes in all applications. For that reason a lightning current test under real service conditions on system level is proposed, which simulates the real installation and its environment as close as possible. • Ideally, such engineering and test services should be offered by the manufacturer of the SPDs. IV. REFERENCES Standards: [1] [2] [3] [4] [5] [6] IEC 61643-1 Ed. 2.: 2005-03 “Low-voltage surge protective devices Part 11: Surge protective devices connected to low-voltage power systems; Requirements and tests“. UL 1449 2nd edition, August 15, 1996: "Standard for transient voltage surge suppressors”. IEEE Recommended Practice on Surge Testing for Equipment Connected to Low-voltage (1000V and Less) AC Power Circuits, IEEE Standard C62.45-2002. IEC TR 62066: 2002 “Surge overvoltages and surge protection in lowvoltage a.c. power systems“. IEEE Guide on the Surge Environment in Low-voltage (1000V and Less) AC Power Circuits, IEEE Standard C62.41.1-2002. IEC 61000-4-5 Ed. 1.: 2001-12; Electromagnetic compatibility (EMC)Part 4-5: Testing and measurement techniques - Surge immunity test Papers from Conference Proceedings (Published): [7] [8] J. Birkl, P. Hasse, P. Zahlmann, "Test procedures for Surge protection systems to be installed in low-voltage power systems" in Proc. International conference on lightning protection, Rhodos 2000, pp. 854859 P. Hasse, P. Zahlmann, "Lightning currents and overvoltages - one arrester for universal use" in Proc. International conference on lightning protection, Cracow 2002, pp. 516-520. View publication stats V. BIOGRAPHIES Dipl. Ing. (FH) Josef Birkl (37) has worked for DEHN + SÖHNE since 1993. He studied Electrical Engineering at the University of Applied Sciences Regensburg. He is now head of the R & D laboratories of DEHN + SÖHNE. Furthermore, he is in charge of the elaboration and assessment of lightning and surge protection concepts via computer simulations and laboratory analysis as well as the design and realisation of complete customer-specific solutions. Dr-Ing Peter Zahlmann (50) studied electrical engineering at the Technical University of Ilmenau, where he was awarded his doctorate in 1983. Since 1 July 2004 he has been a CEO of DEHN + SÖHNE . Numerous patents for lightning protection components, surge protective devices and safety equipment for working at electrical installations resulted from his work. Dr Zahlmann contributes to national and international standardization of lightning and surge protection within the scope of technical-scientific associations and institutions like ABB, DKE/VDE and IEC.