GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION ALARMS INTERPRETATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES BTGJ1_1_ALM BEARING METAL TEMP GEN #1 HIGH The generator bearing metal temperature #1 is very high BTGJ1_2_ALM BEARING METAL TEMP GEN JOURNAL #1 HIGH The generator bearing metal temperature (journal #1) is high BTGJ2_1_ALM BEARING METAL TEMP GEN #2 HIGH The generator bearing metal temperature #2 is very high BEARING METAL TEMP GEN JOURNAL #2 HIGH BEARING METAL TEMP TURBINE JOURNAL #1 HIGH BEARING METAL TEMP TURBINE JOURNAL #1 HIGH BEARING METAL TEMP TURBINE JOURNAL #2 HIGH BEARING METAL TEMP TURBINE JOURNAL #2 HIGH BEARING METAL TEMP TURBINE JOURNAL #3 HIGH BEARING METAL TEMP TURBINE JOURNAL #3 HIGH BEARING METAL TEMP THRUST ACTIVE 2 HIGH BEARING METAL TEMP THRUST ACTIVE 5 HIGH BEARING METAL TEMP THRUST ACTIVE 8 HIGH BEARING METAL TEMP THRUST INACTIVE 2 HIGH BEARING METAL TEMP THRUST INACTIVE 5 HIGH The generator bearing metal temperature (journal #2) is high BTGJ2_2_ALM BTJ1_1_ALM BTJ1_2_ALM BTJ2_1_ALM BTJ2_2_ALM BTJ3_1_ALM BTJ3_2_ALM BTTA1_2_ALM BTTA1_5_ALM BTTA1_8_ALM BTTI1_2_ALM BTTI1_5_ALM OMMO_5_9E_E0858_EN_V3 The turbine bearing metal temperature (journal #1) is high The turbine bearing metal temperature #1 is very high The turbine bearing metal temperature (journal #2) is high The turbine bearing metal temperature #2 is very high The turbine bearing metal temperature (journal #3) is high The turbine bearing metal temperature #3 is very high The bearing metal temperature (thrust active) is high The bearing metal temperature (thrust active) is high The bearing metal temperature (thrust active) is high The bearing metal temperature (thrust inactive) is high The bearing metal temperature (thrust inactive) is high All right reserved Copyright Revision : A ACTIONS TO BE TAKEN Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Check bearing. Check lube oil system and drain piping Date : 10/2011 Page :1/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN BTTI1_9_ALM BEARING METAL TEMP THRUST INACTIVE 9 HIGH The bearing metal temperature (thrust inactive) is high Check bearing. Check lube oil system and drain piping L12H_ACC_ALM PROTECTIVE MODULE ACCELERATION TRIP _ HP L12H_ALM ELECTRICAL OVERSPEED TRIP _ HP L12H_FLT_ALM L12H_P_ALM LOSS OF PROTECTIVE HP SPEED INPUTS PROTECTIVE MODULE OVERSPEED TRIP _ HP The speed control system has not limited turbine speed with the trip limits (fault detected by P module). The turbine trips during the electrical over-speed test. The speed control system hF not limited turbine speed within the trip limits. The turbine trips during the electrical over-speed test. Card VPRO fault Protective module over-speed fault. The trip circuit has been tripped by mechanical over-speed action. L12HBLT_ALM OVERSPEED BOLT TRIP _ HP L12HF_ALM Control speed signal loss and the unit trips. CONTROL SPEED SIGNAL LOSS _ HP Power supply fault, ground, short-circuit open. Speed magnetic pickups fault. L12HFD_C_ALM L12HFD_P_ALM CONTROL SPEED SIGNAL TROUBLE - HP PROTECTIVE SPEED SIGNAL TROUBLE - HP Determine and repair before restarting (mechanical, electrical or fuel or speed control trouble). Check the card VPRO in the module P Check the module over-speed (power supply, short, link, cut). Search the cause of this problem: Check electronic over-speed system. Check proper operation and setting of over-speed bolt assembly. Repair before starting and reset manually the mechanical over-speed limit switch on the over-speed bolt. Check speed system. Check supply, connections. Check the logic circuit. Check speed magnetic pickups. Signal from speed sensors is faulty. Check speed sensors and wiring. Signal from speed sensors is faulty. Check speed sensors and wiring. L20FTY_ALM CRUDE TO DIST FUEL XFER FAULT Transfer valve fault L20FTZ_ALM DIST TO CRUDE FUEL XFER FAULT Transfer valve fault L25A_ENAB_AL K25A RELAY HAS NOT BEEN ENABLED Synchronization permissive disable OMMO_5_9E_E0858_EN_V3 Determine and repair before restarting (mechanical, electrical or fuel or speed control trouble). All right reserved Copyright Revision : A Check proper operation of transfer valve Check limit switch. Check proper operation of transfer valve Check limit switch. Check synchronization permissive Date : 10/2011 Page :2/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L26AAH_ALM ATOMIZING AIR TEMP. HIGH Temperature high at the atomizing air compressor input. L26AAL_ALM ATOMIZING AIR TEMPERATURE LOW Temperature high at the atomizing air compressor input. L26BW_ALM L26CR1H_ALM L26CR1HH_ALM L26CR2H_ALM L26CR2HH_ALM L26CR3H_ALM L26CR3HH_ALM ON LINE WATER WASH TEMP NOT OK CRANKING MOTOR TEMP HIGH PHASE 1 CRANKING MOTOR TEMP VERY HIGH PHASE 1 TRIP CRANKING MOTOR TEMP HIGH PHASE 2 CRANKING MOTOR TEMP VERY HIGH PHASE 2 TRIP CRANKING MOTOR TEMP HIGH PHASE 3 CRANKING MOTOR TEMP VERY HIGH PHASE 3 TRIP Check water supply to the atomizing air pre-cooler, isolating valve position flow restrictions. Check proper operation of thermostatic valve VTR_2 and temperature switch 26AA_1. Check water supply to the atomizing air pre-cooler, isolating valve position flow restrictions. Check proper operation of thermostatic valve VTR_2 and temperature switch 26AA_1. On line temp NOT OK Check heater system The temperature of the phase R of the cranking motor is high The temperature of the phase R of the cranking motor is high The temperature of the phase S of the cranking motor is high The temperature of the phase S of the cranking motor is high The temperature of the phase T of the cranking motor is high The temperature of the phase T of the cranking motor is high Check the phases R of the cranking motor Check the electrical circuit Check the phases R of the cranking motor Check the electrical circuit Check the phases S of the cranking motor Check the electrical circuit Check the phases S of the cranking motor Check the electrical circuit Check the phases T of the cranking motor Check the electrical circuit Check the phases T of the cranking motor Check the electrical circuit Check air conditioners (proper operation, power supply). Clean the air conditioner filters, if necessary. Check the proper operation of the thermocouple 26 CT. NOTE: The control compartment doors must be closed. Check the temperature switch 26 FD_1. Check the forwarding distillate fuel system. Check the heater system of the distillate fuel (if used). Check the proper operation of the temperature switch 26 FD_1. Check the heating system. L26CTH_ALM CONTROL PANEL TEMPERATURE HIGH Air conditioners not maintaining proper temperature. L26FDH_ALM DISTILLATE FUEL TEMPERATURE HIGH The temperature of the distillate fuel is too high. L26FDL_ALM GAS OIL HEATER _ TEMPERATURE LOW The temperature of the gas oil is low. Temperature switch fault. OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN All right reserved Copyright Revision : A Date : 10/2011 Page :3/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L26FDLY_ALM LIQUID FUEL TEMPERATURE MEASURE FAULT The temperature of the liquid fuel is faulty. Check the temperature switch 26 FD_1. Check the forwarding distillate fuel system. Check the heater system of the distillate fuel (if used). Fuel pump #1 temperature fault Check the pump # 1 Fuel pump #2 temperature fault Check the pump # 2 Gas fuel temperature very is high. Check the proper operation of the temperature switch FTG. Check the gas skid (motor, fan, circuit, etc…) The measure of the heavy fuel temperature is faulty. Check temp sensor. L26FDPT1H_ALM L26FDPT2H_ALM L26FTGH_ALM L26FTH_ALM L26FU1H_ALM L26FU1L_ALM L26FU2LA_ALM L26FUPT1H_ALM L26FUPT2H_ALM L26GGC1_ALM L26GGC2_ALM L26GGH1_ALM L26GGH2_ALM L26GS10T12HA L26GS1HH_ALM L26GS1T3H_AL FUEL PUMP #1 TEMPERATURE FAULT FUEL PUMP #2 TEMPERATURE FAULT GAS FUEL TEMPERATURE HIGH HEAVY FUEL TEMP. MEASURE FAULT HEAVY FUEL OIL HIGH TEMPERATURE DURING HFO OPERATION LIQUID FUEL TEMP LOWER THAN HEAT TRACING SETPOINT HEAVY FUEL TEMPERATURE LOW HIGH TEMPERATURE INSIDE PUMP P201 - CHANGE OVER HIGH TEMPERATURE INSIDE PUMP P202 - CHANGE OVER GEN COLD AIR TEMP HIGH GEN COLD AIR TEMP VERY HIGH SHUTDOWN GEN HOT AIR TEMP HIGH GEN HOT AIR TEMP VERY HIGH SHUTDOWN GEN STATOR WIND. CENT. TEMP HIGH #10-11-12 GEN STATOR WIND. CENT. TEMP VERY HIGH #1-2-3 GEN STATOR WINDING CENTER TEMP HIGH #1-2-3 OMMO_5_9E_E0858_EN_V3 Generator cold gas temperature high Check the temperature measure system of the heavy fuel oil Check RTD Check the temperature measure system of the liquid fuel Check RTD "ftl" . Check the temperature measure system of the heavy fuel. Check the temperature measure system of the heavy fuel Check RTD fupt1 Check the temperature measure system of the heavy fuel Check RTD fupt2. Check cooling and sealing system Generator cold gas temperature high shutdown Check cooling and sealing system Generator hot gas temperature high Check cooling and sealing system Generator hot gas temperature high Normal shutdown Check cooling and sealing system Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections heavy fuel oil temperature is faulty. Liquid fuel temperature is too low. Heavy fuel temperature is too low. Liquid fuel temperature is too high. Liquid fuel temperature is too high. All right reserved Copyright Revision : A Date : 10/2011 Page :4/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L26GS2HH_ALM L26GS3HH_ALM L26GS4HH_ALM L26GS4T6H_AL L26GS7T9H_AL L26HA11HH_AL L26HA11LL_AL L26HAHH_ALM L26HALL_ALM L26HGHH_ALM L26HGLL_ALM L26HTHH_ALM L26HTLL_ALM L26PMBT1L_AL L26PMBT2L_AL L26QA_ALM ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN GEN STATOR WIND. CENT. TEMP VERY HIGH #4-5-6 GEN STATOR WIND. CENT. TEMP VERY HIGH #7-8-9 GEN STATOR WIND. CENT. TEMP VERY HIGH #10-11-12 GEN STATOR WINDING CENTER TEMP HIGH #4-5-6 GEN STATOR WINDING CENTER TEMP HIGH #7-8-9 HEAT VENT VERY HIGH TEMP. IN DLN COMPARTMENT HEAT VENT VERY LOW TEMP. IN DLN COMPARTMENT HEAT VENT VERY HIGH TEMP. IN AUXILIARY COMPARTMENT HEAT VENT VERY LOW TEMP. IN AUXILIARY COMPARTMENT HEAT VENT HIGH TEMP. IN LOAD COMPARTMENT HEAT VENT VERY LOW TEMP. IN LOAD COMPARTMENT HEAT VENT VERY HIGH TEMP. IN TURBINE COMPARTMENT HEAT VENT VERY LOW TEMP. IN TURBINE COMPARTMENT PERF MONIT INSTRUM BOX #1 TEMP VERY LOW PERF MONIT INSTRUM BOX #2 TEMP VERY LOW Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Generator Overload 2 of 3 Generator RTDs failure Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections DLN compartment temperature very high Start cooling fans DLN compartment temperature very low Check cooling fans Accessories compartment temperature high Start cooling fans Heating and ventilation fault Check heating and ventilation system Heat vent very high temp. In load compartment Check cooling and sealing system Heat vent very low temp. In load compartment Check cooling and sealing system Gas turbine compartment temperature high Start cooling fans Turbine compartment temperature low. Check the ventilation system. Performance monitoring instrumentation box #1 temperature regulation fault Performance monitoring instrumentation box #2 temperature regulation fault Check performance monitoring instrumentation box #1 temperature regulation Check performance monitoring instrumentation box #2 temperature regulation Check for proper operation of the lube oil heat exchangers, cooling water fans (proper rotation) and temperature regulating valve VTR_1. Check for proper operation of the temperature switch 26 QA_1. LUBE OIL HEADER TEMP. HIGH OMMO_5_9E_E0858_EN_V3 Lube header temperature above recommended limits. (See piping schematic). All right reserved Copyright Revision : A Date : 10/2011 Page :5/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L26QN_ALM LUBE OIL TANK TEMP. LOW Lube tank temperature below recommended limits (see piping schematic). L26QT_ALM LUBE OIL HEADER TEMP. HIGH TRIP Lube header temperature above recommended limits. L26WC_FLT COOLING WATER TEMPERATURE FAULT Cooling water temperature fault. COOLING WATER TEMPERATURE VERY HIGH Cooling water system fault. Pipes, radiators are dirty. Cooling fan motor fault. Temperature sensor fault. Leakage. WASTE TANK TEMPERATURE HIGH WATER INJECTION COMPARTMENT TEMPRATURE VERY HIGH WATER INJECTION COMPARTMENT TEMPERATURE VERY LOW Waste tank temperature high Water injection compartment temperature fault. Thermocouple fault. Water injection compartment temperature fault. Thermocouple fault. L27BLN11_ALM BATTERY CHARGER AC UNDERVOLTAGE Battery charger AC under-voltage. Charger faulty. L27BLN12_ALM BATTERY CHARGER AC UNDERVOLTAGE Battery charger AC under-voltage. Charger faulty. L27BLN13_ALM BATTERY CHARGER AC UNDERVOLTAGE Battery charger AC under-voltage. Charger faulty. L27BLN21_ALM BATTERY CHARGER # 2 AC UNDERVOLTAGE Battery charger # 2 AC under-voltage. Charger faulty. L26WCHH_ALM L26WP1_ALM L26WRHH_ALM L26WRLL_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A ACTIONS TO BE TAKEN Check for proper operation of the lube oil tank heaters. Starting is inhibited if the header temperature is low. Check for proper operation of the temperature switch 26QN_1. Check for proper operation of the lube oil heat exchangers, cooling water fans (proper operation) and temperature regulating valve VTR_1. Check the temperature switches 26 QT_1A and 26 QT_1B setting points. Check the proper operation of the temperature sensor. Check the cooling water system. Check cooling water system (fan motor, radiator, cleanliness of circuit, skid). Check the proper operation of the temperature sensor 26 WC. Check the correct circulation of the water in the circuit. Check the proper operation of the water pump. Check waste tank Check the thermocouple AT-WI-1. (Wiring, connection, etc…). Check the thermocouple AT-WI-1. (Wiring, connection, etc…). Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Date : 10/2011 Page :6/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L27BLN22_ALM BATTERY CHARGER # 2 AC UNDERVOLTAGE Battery charger # 2 AC under-voltage. Charger faulty. L27BLN23_ALM BATTERY CHARGER # 2 AC UNDERVOLTAGE Battery charger # 2 AC under-voltage. Charger faulty. L27BN_12_ALM AC BUS NORMAL INFORMATIONS MISMATCH Bus synchronizing potential not available. L27BN_ALM BUS UNDERVOLTAGE - NO AUTO SYNCH Bus synchronizing potential not available. L27BP1N_ALM DC SUPPLY #1 CRITICAL FAULT DC supply #1 critical fault L27BP2N_ALM DC SUPPLY #2 CRITICAL FAULT DC supply #2 critical fault L27BZ_12_ALM AC BUS UNDERVOLTAGE INFORMATIONS MISMATCH Bus synchronizing potential not available. L27DZ_ALM BATTERY DC UNDERVOLTAGE Battery system voltage is low. Battery charger is not functioning properly. Excessive drain on the batteries. Bad cells in battery. L27GPP1_ALM GEN PROTECTION MOD 1 125V SUPPLY FAULT Gen protection mod1 125v supply fault OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A ACTIONS TO BE TAKEN Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Check battery charger AC breaker. Check voltage magnitude. Check the proper operation of the battery charger. Check bus PT fuses and wiring. Do not use auto synchronizing or manual synchronizing until problem is resolved. Check relay 27B_1,2. Check bus PT fuses and wiring. Do not use auto synchronizing or manual synchronizing until problem is resolved. Check relay 27B_1,2. Check bus PT fuses and wiring. Do not use auto synchronizing or manual synchronizing until problem is resolved. Check relays 27B_1. Check bus PT fuses and wiring. Do not use auto synchronizing or manual synchronizing until problem is resolved. Check relays 27B_2. Check bus PT fuses and wiring. Do not use auto synchronizing or manual synchronizing until problem is resolved. Check relay 27B_1,2. Check battery charger for proper operation, correct excessive drain on battery, check for bad cells. Check battery charger fuses. NOTE: The gas turbine should not be operated unless DC power is available to the emergency DC lube oil pump. Check power supply Date : 10/2011 Page :7/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L27GPP2_ALM L27GRDAC_ALM L27GRDDC_ALM ALARM TEXT GEN PROTECTION MOD 2 125V SUPPLY FAULT GAS DETECT RACK 230 VAC POWER SPPLY FLT GAS DETECT RACK 125 VDC POWER SPPLY FLT POSSIBLES CAUSES ACTIONS TO BE TAKEN Gen protection mod2 125v supply fault Check power supply Gas detect rack 230 VAC power supply fault Check power supply 230 VAC of gas detection module Gas detect rack 125 VDC power supply fault Check power supply 125 VDC of gas detection module L27MC1AN_ALM MCC UNDERVOLTAGE Motor control center under-voltage. L27MC1N_ALM MCC UNDERVOLTAGE Motor control center under-voltage. L27MC2N_ALM MCC UNDERVOLTAGE Motor control center under-voltage. L27N_ALM NORMAL SUPPLY LOW VOLTAGE Normal incoming under-voltage L27QEL_ALM DC MOTOR UNDERVOLTAGE (LUBE OIL) DC power not supplied to emergency DC pump. 125 VDC supply fault. Pump fault Breaker opens. L27S_ALM STAND BY SUPPLY LOW VOLTAGE Emergency incoming under-voltage L27TF_ALM INLET FITER POWER SUPPLY FAULT The power supply of the inlet filter is faulty G60A PROTECTION POWER SUPPLY G60A protection power supply fault-trip FAULT L27X1_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check that power is supplied to the motor control center. Check 380 V on the bus bars. Check breaker: transformer supply 16 KVA and the transformer. Check relay 27 MC. Check that power is supplied to the motor control center. Check 380 V on the bus bars. Check breaker: transformer supply 16 KVA and the transformer. Check relay 27 MC. Check that power is supplied to the motor control center. Check 380 V on the bus bars. Check breaker: transformer supply 16 KVA and the transformer. Check relay 27 MC. Check Normal power supply 415 VAC at the Normal entry of MCC Check power to DC lube pump (MCC breaker on). Check the fuses and the relay 27 QE. Check the proper operation of pump motor. Check the mechanical status of the pump. NOTE: The gas turbine should not be operated unless DC power is available to the emergency DC lube pump. Check Emergency power supply 415 VAC at the Emergency entry of MCC Check the power supply Check power supply Date : 10/2011 Page :8/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L27X2_ALM L27X3_ALM ALARM TEXT POSSIBLES CAUSES G60B PROTECTION POWER SUPPLY G60B protection power supply fault-trip FAULT T60A PROTECTION POWER SUPPLY T60A protection power supply fault-trip FAULT 230VAC normal power supply fault #2 Check 230VAC normal power supply 230VAC UPS power supply fault #3 Check 230VAC UPS power supply 115VAC power supply fault #4 Check 115VAC power supply One of the detectors operating when no flame is present or flame detection before the firing sequence. L28FD_SD CHAMBER FLAMED OUT DURING SHUTDOWN Chamber flamed out during shutdown. L28FDT_ALM LOSS OF FLAME - TRIP Failure of flame detectors or loss of flame. START_UP FUEL FLOW EXCESSIVE TRIP On the liquid fuel circuit: Fuel leakage. Fuel loop system fault. On the gas fuel circuit: Purchaser gas supplies low pressure. Loss of the pressure between VSR and VGC. Gas leakage. Transmitters fault. L30AC_APU_AL L30AC1_ALM L30AC2_ALM L30AC3_ALM L30AC4_ALM ATOMIZING AIR TEMPERATURE FAULT AIR PROCESSING UNIT FAULT 400VAC POWER SUPPLY FAULT #1 230VAC NORMAL POWER SUPPLY FAULT #2 230VAC UPS POWER SUPPLY FAULT #3 115VAC POWER SUPPLY FAULT #4 OMMO_5_9E_E0858_EN_V3 Check power supply Atomizing air temperature fault. Thermocouples fault. Air processing unit problem Power supply 400VAC fault FLAME DETECTOR TROUBLE L30AAT_ALM Check power supply Check for proper operation of the flame detection system. Check that the flame detectors quartz windows are clean. Repair or replace if necessary. Check the fuel supply and the fuel control. Check the fuel nozzles. Check for following: fuel being supplied to the combustors, flame in all chambers, damaged crossfire tubes, or combustors. Check for proper control valve position and fuel pressure. Check for proper operation of the flame detectors 28 FD. On the liquid fuel circuit: Check for leakage. Check tripping setting point. Check fuel loop system operation. Check the operation of the bypass versus the control signal. On the gas fuel circuit: Check the purchaser gas supply. Check the opening of the transmitters isolation valves. Check the transmitters 96 FG_2A, 2B and 2C. Check the LVDT setting value and the calibration of the valve VSR. Check the thermocouples AAT-1A and 2A. (Wiring, connection, etc…). Check air processing unit Check 400VAC power supply L28FD_ALM L2SFT_ALM ACTIONS TO BE TAKEN All right reserved Copyright Revision : A Date : 10/2011 Page :9/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L30BT_ALM TURBINE COMPARTMENT VENTILATION FAULT The turbine compartment ventilation is faulty. L30BTA_ALM BEARING METAL TEMPERATURE HIGH The temperature of the bearing metal is high. L30BW_ALM TURBINE COMPARTMENT VENT. CHANGE OVER WASHING SKID FAULT Air fan changeover. Turbine compartment air fan fault. The washing skid is faulty. L30CBC_ALM COMP BLD VLV FAILURE TO OPEN The compressor bleed valve failed to open. L30BTX_ALM ACTIONS TO BE TAKEN Check the ventilation system of this compartment (power supply, motors, fans, electrical circuit...). Check the position of the vent flap. Check the lube oil collector temperature. Research the thermocouple, which occurred this alarm. Check the indications of it. Check the air fan system (power supply, motors, fans, relay, electrical circuit...). Check the washing skid. Check the proper operation of the purge valve. FIRE PROTECTION SYSTEM TROUBLE Fire protection system problem. Check the power supply of fire protection system. Check fire detectors and the electrical circuit. This trouble must be corrected as soon as possible. NOTE: Before this search, the fire protection must be inhibited. Do not forget to put again in service as soon as the maintenance is finished. Refer to specific chapters for more information about the fire protection. L30CD_ALM COOLDOWN TROUBLE Unit failed to go on cool-down, or the cool-down cycle was aborted prior to cool-down timer timeout Trouble during the cool-down sequence. Turning gear motor fault. Supply fault Check the turning gear system. Check the voltage supplies. Check the proper operation of the turning gear motor 88TG. L30COM_EXFLT EXCITER TO MKVI COMMUNICATION FAULT Exciter to mkVI communication fault Check power supply L30CC_ALM L30COMM_IO_R L30D_CTRL_OT L30DBEXX_ALM VCMI IO STATE EXCHANGE FOR <R> FAILED CONTROLLER OVERTEMPERATURE EXCITER FAIL - ABORTING DB CLOSURE OMMO_5_9E_E0858_EN_V3 Controller overtemperature Check R controller is on Check R controller is OK Check the 3 IONet cables are OK Check IONet cable is connected on the R controller VCMI board Refer to specific chapter. Exciter fail - aborting db closure Check exciter No more communication with R controller All right reserved Copyright Revision : A Date : 10/2011 Page :10/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L30DC1_ALM L30DPFLT_ALM L30EX_FSP L30EX_FTS L30EX_RS L30FAX_ALM L30FAX1_ALM L30FAX2_ALM L30FC1_ALM L30FC2_ALM ALARM TEXT 125VDC POWER SUPPLY FAULT #1 ALARM DEW POINT TEMPERATURE SENSOR FAULT EXCITER FAILURE TO STOP EXCITER FAILURE TO START EXCITER NOT READY TO START CRUDE OIL FWD SMOKE INHIBITION PUMP CHANGE OVER HEAVY FUEL ADDITIVE PUMP #1 FAULT HEAVY FUEL ADDITIVE PUMP #1 FAULT COOLING WATER FAN 1 ELECTRICAL TROUBLE COOLING WATER FAN 2 ELECTRICAL TROUBLE POSSIBLES CAUSES ACTIONS TO BE TAKEN 115 VDC MCC voltage lost Check 115 VDC MCC electrical circuit Check voltage feeding Dew point temperature sensor fault Change dew point temperature sensor Exciter failure to stop Exciter failure to stop Exciter not ready to start Check exciter cubicle Check exciter cubicle Check the condition to start For information For information Heavy Fuel Additive pump #1 fault Check the pump # 1 Heavy Fuel Additive pump #2 fault Check the pump # 2 The motor of the cooling water system fan #1 is faulty The motor of the cooling water system fan #2 is faulty L30FD_ALM FAILURE TO IGNITE Failure to fire within the one-minute period. L30FDX1_ALM L30FDX2_ALM L30FORCED_ALM FUEL FORWARDING PUMP #1 FAULT FUEL FORWARDING PUMP #2 FAULT FORCED LOGIC SIGNAL DETECTED Fuel forwarding pump #1 fault Fuel forwarding pump #2 fault One alarm or more is forced L30FPG2L_ALM GAS FUEL INTERVALVE PRESSURE (P2) LOW The high line inter-valve ventilation is faulty. Emergency motor fault Power supply fault L30FUX_ALM CRUDE OIL FWD CRUDE OIL FORWARDING PUMP FAULT Pump, motor fault. OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check electrical circuit Check motor fan #1 Check electrical circuit Check motor fan #2 Check that AC power is supplied to the ignition system. Check the fuel supply. Check if isolating valves on flame detectors are open. Check the proper operation of spark plugs and flame detectors. Check. Fuel forwarding pump #1 Check. Fuel forwarding pump #2 Unforced all the alarms Check gas compartment ventilation. Check motors. Check mechanical status of fans. Check pressure switches. Check the pump and corresponding motor Check if the motor is supplied. Check the pipes, valves, and filters, purge vents, leaks. Check the pressure switches (operation and setting). Date : 10/2011 Page :11/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L30FUX1_ALM HEAVY FUEL FEEDING PUMP #1 FAULT Motor fault Power supply fault Pump fault Check the mechanical status of the motor and the pump Check what the circuit is correctly positioned Check the supply of the motor drawer and the motor Check the fuses, breaker and the connection of the motor See alarm : L30FUX1_ALM See alarm : L30FUX1_ALM L30G60A_ALM L30G60B_ALM HEAVY FUEL FEEDING PUMP #2 FAULT GLOBAL ALARM FROM G60A GLOBAL ALARM FROM G60B Global alarm from G60A Global alarm from G60B. L30GGC_ALM GEN COLD AIR TEMP FAULT Generator RTD fault. L30GGH_ALM GEN HOT AIR TEMP FAULT GAS DETECTION RACK SYSTEM FAULT GEN STATOR WINDING CENTER TEMP SNSR FLT #10-11-12 GEN STATOR WINDING CENTER TEMP SNSR FLT #1-2-3 GEN STATOR WINDING CENTER TEMP SNSR FLT #4-5-6 GEN STATOR WINDING CENTER TEMP SNSR FLT #7-8-9 HEAT VENT DLN COMPARTMENT HEATER IN TROUBLE HEAT VENT AUXILIARY COMPARTMENT HEATER IN TROUBLE HEATER NOT DESIGNED TO RUN GT ON - STOP HEATER HEAT VENT LOAD COMPARTMENT HEATER IN TROUBLE HEAT VENT TURBINE COMPARTMENT HEATER IN TROUBLE HEAT VENT WATER INJ COMP VENT. ELECTRICAL FAULT Generator temperature fault Check G60A Check G60B Check RTD and associated connections for proper signal and replace faulty RTD. Check cooling and sealing system Check the gas detection rack Refer to the specific chapter about maintenance Check RTD and associated connections for proper signal and replace faulty RTD. Check RTD and associated connections for proper signal and replace faulty RTD. Check RTD and associated connections for proper signal and replace faulty RTD. Check RTD and associated connections for proper signal and replace faulty RTD. L30FUX2_ALM L30GRD_ALM L30GSC10T12A L30GSC1T3_AL L30GSC4T6_AL L30GSC7T9_AL L30HA11X_ALM L30HAX_ALM L30HEATR_ALM L30HG1X_ALM L30HTX_ALM L30JS_ALM OMMO_5_9E_E0858_EN_V3 Gas detection rack system fault Sensors fault detection Sensors fault detection Sensors fault detection Sensors fault detection Heat vent DLN compartment heater in trouble Check heat vent DLN compartment heater Heat vent auxiliary compartment heater in trouble Check heat vent auxiliary compartment heater Discrepancy between start order and feedback Check feedback match with heater status Heat vent load compartment heater in trouble. Check the heater. Heat vent turbine compartment heater in trouble Check heat vent turbine compartment heater Heat vent water injection compartment vent. Check the heater. All right reserved Copyright Revision : A Date : 10/2011 Page :12/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L30JSX_ALM HEAT VENT WI COMPARTMENT VENT. CHANGE OVER Air fan changeover. Water injection compartment air fan fault. L30LOAH_ALM BEARING DRAIN TEMPERATURE HIGH Bearing fault. Lube oil fault. Lube oil cooling system fault. Leakage. Check the air fan system (power supply, motors, fans, relay, electrical circuit...). Check lube oil feed and drain piping Check bearings and lube oil system. Check thermocouples. Check lube oil cooling. Check the correct circulation of the lube oil. Check for leakage. L30LSI_ALM BEARING DRAIN TEMPERATURE HIGH AIRCRAFT WARNING LIGHT ALARM L30LTA LOAD TUNNEL TEMPERATURE HIGH L30LTTH_ALM LUBE OIL THERMOCOUPLE FAULT SYNC INHIBITED-MAN (FVR) REG ACTIVE L30LOAHH_ALM L30MRSYNC_AL OMMO_5_9E_E0858_EN_V3 See alarm : L30LOAH_ALM See alarm : L30LOAH_ALM Aircraft warning ligh alarm Thermocouple fault For information Check the proper operation of ventilation system. Check the operation of the ventilators (rotation). Check the operation of the motors 88 TK1 and 2. Check the thermocouple TT_IB_1 (connection, shortcircuit, cut off, position). Check the sealing and the cleanliness of the pipes. Check the proper operation of thermocouples LTTH1 to 3. Sync inhibited man (FVR) reg active. For information Automatic shutdown. Ventilation system fault. Thermocouple fault. All right reserved Copyright Revision : A Date : 10/2011 Page :13/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT L30PPDA_125P_ALM PPDA 125V PBUS FEED FAULT L30PPDA_AC_IN_1_ALM L30PPDA_AC_IN_2_ALM PPDA AC INPUT 1 FAULT PPDA AC INPUT 2 FAULT PPDA/JPDD 125V POWER FEED FAULT PPDA <R> PBUS NOT REGULATING PPDA <S> PBUS NOT REGULATING PPDA <T> PBUS NOT REGULATING PPDA <R> PBUS SOURCE FAULT PPDA <S> PBUS SOURCE FAULT PPDA <T> PBUS SOURCE FAULT L30PPDA_JPDD_125V_ALM L30PPDA_PBUS_R_ALM L30PPDA_PBUS_S_ALM L30PPDA_PBUS_T_ALM L30PPDA_SRC_R_ALM L30PPDA_SRC_S_ALM L30PPDA_SRC_T_ALM POSSIBLES CAUSES Voltage failure Fuse fault Wrong barcode in software Wrong firmware loaded in IO pack IO pack Ethernet link or power supply disconnected Check alarm number in GEH-6721 vol II Check board power supply is correctly connected, else connect it. Check IO pack Ethernet link or power supply is correctly connected (Leds on IO pack must be active), else connect it. Check IR port of the IO pack is protected by its metallic plate, else turn the plate until IR port is hidden. Check barcode is identical on board and inside IO hardware configuration in the software, else change barcode number, build and download. Check firmware is correct in the IO pack, else download again the firmware with actual ToolbowST release. Check electrical cables are not cut, else replace cables. Check fuse have not melt, if yes, replace fuse. Check voltage is present, if not, re start power supply. See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM See : L30PPDA_125P_ALM Check the generator bearing system (power supply, pumps, electrical circuit...). Check the pressure switch. Check the relay 51 QV. Check the motor 88 QV (proper operation). Check the density analyzer. L30QB1_ALM GENERATOR BRG LIFT PUMPS ELECTRICAL FAULT The lift pumps are faulty L30QV_ALM OIL MIST ELIMINATOR FAULT The oil mist separator fan motor is in trouble. L30SG1_ALM DENSITY ANALYSER FAULT 1 The density analyzer is faulty. OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN All right reserved Copyright Revision : A Date : 10/2011 Page :14/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L30SPA COMBUSTION TROUBLE Faulty thermocouples, gas path hardware or uneven distribution of fuel to the fuel nozzles. L30SPT HIGH EXHAUST TEMP. SPREAD TRIP Faulty thermocouples, gas path parts or uneven distribution of fuel to the fuel nozzles. L30SPTA L30T60A_ALM L30TWW_ALM L30TXA_ALM L30TXAH1 L30UPSCS_ALM L30UPSMAJ_AL L30UPSMIN_AL L30UPSMOD_AL EXHAUST THERMOCOUPLE TROUBLE T60A GLOBAL A WATER WASH INHIBIT_WHEELSPACE TEMP. HIGH EXHAUST TEMPERATURE HIGH FIRST FAILED HIGH EXHAUST THERMOCOUPLE BATTERY CHARGER - CS FAULT INVERTER MAJOR UPS FAULT INVERTER MINOR GROUP FAULT INVERTER MODULE GROUP FAULT Faulty thermocouple. T60A global alarm The washing procedure is inhibited because the wheelspace temperature is too high. Thermocouples fault. The exhaust gas temperature is excessive. Thermocouples fault. Fuel control system fault. Ventilation system fault. Analyze data for trends. At earliest shutdown, check thermocouples. Perform bore scope or combustion inspection. Check flow divider, fuel pressures. Check for plugged nozzles. Analyze data for trends. Perform bore scope or combustion inspection. Check flow divider, fuel pressures. Check for plugged nozzles. Check thermocouples and wiring. Change if necessary. Check T60A Check the temperature and wait for an adequate wheelspace temperature. Check the thermocouples. Check all thermocouples. Replace any bad thermocouples. If problem is not thermocouples, isolate portion of control system causing problem. Check the temperature control loop and the fuel control system. See alarm : L30TXA_ALM See alarm : L30TXA_ALM Inverter static converter group fault MCC UPS major fault Inverter minor group fault Inverter module group fault Check inverter static converter group Check MCC UPS Check inverter minor group Check inverter module group fault Check the ventilation system of this compartment (power supply, motor, fans, electrical circuit...). Check the pressure switch. Check the position of vent flap. L30VG_ALM LOAD COMPT COOLING FAN CHANGE OVER The load compartment ventilation is faulty. L30VGX_ALM LOAD COMPARTMENT VENTILATION FAULT See alarm : L30VG_ALM OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN All right reserved Copyright Revision : A See alarm : L30VG_ALM Date : 10/2011 Page :15/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L30VL_ALM GAS CABINET _ EMERGENCY FAN ‘’ON’’ Fan fault: changeover to emergency fan. Motor fault. Pressure switch fault. L30VLX_ALM GAS COMPARTMENT VENTILATION FAULT The gas compartment ventilation is faulty. L30WCX_ALM COOLING WATER PUMP FAULT (CHANGEOVER) Motor fault Power supply fault Pump fault L30WCX1_ALM L30WCX2_ALM COOLING WATER MOTOR # 1 FAULT COOLING WATER MOTOR # 2 FAULT L30WN_ALM WATER INJECTION NOT SELECTED L30WN1_ALM WATER INJECTION PUMP ELECTRICAL FAULT L30WQER_ALM L30WR1X_ALM L30WSA1_ALM WATER INJ SERVO NOT FOLLOWING OUTPUT HEAT VENT WI COMPARTMENT HEATER IN TROUBLE WHEELSPACE TEMP. DIFFERENTIAL HIGH L30WSA2_ALM WHEELSPACE TEMPERATURE HIGH L32DW_ALM GENERATOR BREAKER TRIP_REVERSE POWER OMMO_5_9E_E0858_EN_V3 See alarm : L30WCX_ALM See alarm : L30WCX_ALM Water injection not selected. Water injection has been deselected. Power supply fault Pump fault Difference between the flow measured and the flow wanted ACTIONS TO BE TAKEN Check the gas skid ventilation system (motors, fans, power supply, etc.) Check the power supply of the motor 88 VL and its protections. Check the pressure switch 63 VL. Check gas compartment ventilation. Check motors, 88 VL _ 1,2. Check mechanical status of fans. Check pressure switches 63 VL _ 1,2. Check the mechanical status of the motor and the pump Check what the circuit is correctly positioned Check the supply of the motor drawer and the motor Check the fuses, breaker and the connection of the motor See alarm : L30WCX_ALM See alarm : L30WCX_ALM Research the cause of the injection deselecting. Check the mechanical status of the pump Check the supply of the pump Check the fuses, breaker and the connection of the pump Check the injection circuit to see why the measured flow is lower than the constant flow Heat vent WI compartment heater in trouble Check heat vent WI compartment heater Excessive differential between wheel-space thermocouples. Defect thermocouples (TTWS_XX). Thermocouples position fault. Combustion fault. Check thermocouples for shorts, grounds or opens. Replace failures. If condition persists investigate for seal failure. Check the thermocouples position. Check the combustion and regulation system. High wheel-space temperature (for proper value refer to control specification). Ventilation system fault. Thermocouples fault (TTWS_XX). Turbine fault. Fuel feeding system fault. All right reserved Copyright Revision : A Check thermocouples, investigate for seal failure. Check the ventilation system. Check the proper operation of the thermocouples. Turbine checking. Fuel feeding system checking (skid fuel). Date : 10/2011 Page :16/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L33ARS_ALM AC TRANSFER CB SPRING CHARGE FAILURE AC transfer cb spring charge failure Check circuit breakers 52AR & 52AS L33BT_ALM TURBINE COMPARTMENT VENT. FLAP CLOSED Flap closed in the turbine compartment. Limit switch fault. L33CDMN_ALM AT MIN TNR-REVERSE POWER NOT DETECTED Transducer fault System of detection fault Check the position of flap. Determine the cause of the flap closing. Check the limit switch 33 BT. Check the proper operation of the generator watts transducer and open the manually breaker if necessary Check the logic of command L33CL1_ALM CO2 LOCK OFF IN ZONE 1 CO2 emission L33CL2_ALM CO2 LOCK OFF IN ZONE 2 FIRE PROTECTION DLN COMPT CO2 LOCKED ALARM HEAT VENT AUXILIARY COMPARTMENT DOOR OPEN CO2 emission Refer to fire protection panel to determinate the fire zone. The unit should not be operated until the cause has been determined and corrected and the fire protection has been re-established in its normal condition (refilling of CO2 bottles, circuit reset...). Check for the causes of this trip; hot air or fuel or oil leaks, or short-circuits. NOTE: Restarting after an operation of the CO2 system requires that the CO2 system be reset, including all doors and dampers, and the CO2 release mechanism. WARNING: Carbon Dioxide, in a concentration sufficient to extinguish fire, creates an atmosphere that will not support life. It is extremely hazardous to enter the compartment after the CO2 system has been discharged. For further information, refer to Fire Protection System documentation if available. The extent and type of safeguards and personnel warning that may be necessary must be designed to meet the particular requirements of each situation. It is recommended that personnel be adequately trained as to the proper action to take in case of such an emergency. See alarm : L33CL1_ALM CO2 emission See alarm : L33CL1_ALM The door of the compartment auxiliary is open. Limit switch fault. Check the air inlet filter system. Check the limit switch 33 DT1. L33CL4_ALM L33DT1_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Date : 10/2011 Page :17/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L33DT2_ALM L33DT3_ALM L33JS_ALM ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN HEAT VENT AUXILIARY COMPARTMENT DOOR OPEN HEAT VENT AUXILIARY COMPARTMENT DOOR OPEN WATER INJECT COMP FLAP DAMPER NOT CLOSED The door of the compartment auxiliary is open. Limit switch fault. The door of the compartment auxiliary is open. Limit switch fault. Check the air inlet filter system. Check the limit switch 33 DT2. Check the air inlet filter system. Check the limit switch 33 DT3. Water inject comp flap damper not closed. Check damper L33PGC_ALM PRIMARY PURGE VALVES FAILURE TO CLOSE Either one or both of purge valves VA13_1and VA13_2 not functioning correctly. Either one or both of limit switches 33PG_1 and 33PG3 not functioning correctly. L33PGO_ALM GAS FUEL NOZ. PURGE VALVE FAIL TO OPEN The purge valves VA 13_1 and VA 13_2 failed to open. L33PLP_ALM PRIMARY LIQUID FUEL LOW PURGE FAULT L33PS1C_ALM VENT VALVE FSV452 NOT CLOSED L33PS2O_ALM VENT VALVE LIMIT SWITCH NOT OPEN L33PSC_ALM L33PSO_ALM L33S_ALM GENERATOR HOT GAS TEMPERATURE HIGH GAS FUEL VENT VALVE OPEN TROUBLE AUTOMATIC VALVES FAULT OMMO_5_9E_E0858_EN_V3 No detection of opening on liquid fuel purge system when purge is requested This alarm indicates the wrong position of the vent valve: The valve is blocked Valve fault Limit switch fault This alarm indicates the wrong position of the vent valve: The valve is blocked Valve fault Limit switch fault Check the proper operation of: _ Purge valves VA13_1 and VA13_2 _ Air valves VA36_1 and VA36_2 _ Solenoid valves 20PG_1 and 20PG_2. Check Speedtronic connections and interface. Check the limit switches 33PG_1 and 33PG_3 for set point and Speedtronic connections. Check the proper operation of the purge valves VA 13_1 and VA 13_2. Check the status of the solenoid valves 20 PG_1 and 20 PG_2. Check the proper operation of the limit switches 33 PG_2 and 33 PG_4. Control liquid fuel purge valve position (hi flow valve) Check that noting is blocking the valve Check the limit switch Check the valve Check that noting is blocking the valve Check the limit switch Check the valve Generator hot gas temperature high Refer to specific chapter Gas Fuel Vent Valve Open position trouble Check limit switch and valve Automatic valves fault Check valve All right reserved Copyright Revision : A Date : 10/2011 Page :18/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L33VG_ALM LOAD COOLING AIR FLAT DAMPER NOT CLOSED Damper not closed Limit switch fault L33VG11_ALM TURBINE GAS VENT VALVE POSITION FAULT Turbine gas vent valve position fault. Limit switch fault. L33VL_ALM HEAT VENT GAS/DLN COMPT VENT FLAP NOT CLOSED Compartment flap damper not closed Limit switch fault Valve position fault Limit switch fault Valve position fault Limit switch fault Valve position fault Limit switch fault Valve position fault Limit switch fault Something is blocking the valve Check what is blocking the valve and remove it L33WNO_ALM GAS FUEL SHUT OFF VALVE LIMIT SWITCH NOT CLOSED GAS FUEL SHUT OFF VALVE CLOSED TROUBLE GAS FUEL SHUT OFF VALVE LIMIT SWITCH NOT OPEN GAS FUEL SHUT OFF VALVE OPEN TROUBLE H2O INJ CTRL & XFER VLV FAIL TO CLOSE WATER INJECTION TROUBLE Check the position of the damper Determine the cause of the flap opening Check the limit switch 33VG Check the proper operation of vent valve 20 VG-1. Check the limit switch 33VG Check the position of the damper Determine the cause of the flap opening Check the limit switch Check valve 20VS position Check limit switch 33VS4 Check valve 20VS position Check limit switch 33VS4 Check valve 20VS position Check limit switch 33VS4 Check valve 20VS position Check limit switch 33VS4 There is a problem in the injection circuit L39VA_ALM HIGH VIBRATION ALARM Vibration at one or more bearings. Check the injection circuit Monitor vibration readings. Determine the cause of this trouble and repair. L39VD1_ALM VIBRATION BN GT. AXIAL SHAFT DISPLACEMENT ALERT VIBRATION BN GT. AXIAL SHAFT DISPLACEMENT DANGER VIBRATION SENSOR DISABLED L39VD3_ALM VIBRATION _ START INHIBIT GT axial shat displacement alert st 1 step GT axial shat displacement alert 2nd step Signal from vibration sensors is faulty. Start inhibited. Vibration protection system problem. Too many sensors in trouble or disabled. L39VDIFF_ALM VIBRATION DIFFERENTIAL TROUBLE L33VS411C_AL L33VS411CX_A L33VS421O_AL L33VS421OX_A L33WNC_ALM L39VCA_ALM L39VCD_ALM OMMO_5_9E_E0858_EN_V3 Vibration protection system problem. All right reserved Copyright Revision : A ACTIONS TO BE TAKEN Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration protection system. Check the vibration sensors. Check vibration protection system. Check the level of each sensor and determine the cause of the differential. Date : 10/2011 Page :19/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME POSSIBLES CAUSES ACTIONS TO BE TAKEN VIBRATION TRANSDUCER FAULT Vibration detector impedance is not within normal bounds or 3 or more gas turbine sensors are disabled or faulty. Check impedance or each vibration detector (open or short-circuit). Check the vibration protection system. NOTE: With the 3 or more sensors disabled or faulty, the start is inhibited. VIB BN GEN BRG #2 RADIAL SHAFT DISPLACEMENT ALERT VIB BN GEN BRG #2 RADIAL SHAFT DISPLACEMENT DANGER VIB BN GT BRG #1 RADIAL SHAFT DISPLACEMENT ALERT VIB BN GT BRG #1 RADIAL SHAFT DISPLACEMENT DANGER VIB BN GT BRG #2 RADIAL SHAFT DISPLACEMENT ALERT VIB BN GT BRG #2 RADIAL SHAFT DISPLACEMENT DANGER VIB BN GT BRG #3 RADIAL SHAFT DISPLACEMENT ALERT VIB BN GT BRG #3 RADIAL SHAFT DISPLACEMENT DANGER VIB BN GEN BRG #1 RADIAL SHAFT DISPLACEMENT ALERT VIB BN GEN BRG #1 RADIAL SHAFT DISPLACEMENT DANGER Generator bearing 2 radial shat displacement alert 1st step Generator bearing 2 radial shat displacement alert 2nd step GT bearing 1 radial shat displacement alert st 1 step GT bearing 1 radial shat displacement alert 2nd step GT bearing 2 radial shat displacement alert st 1 step GT bearing 2 radial shat displacement danger 2nd step GT bearing 3 radial shat displacement alert 1st step GT bearing 3 radial shat displacement alert 2nd step GT bearing 1 radial shat displacement alert st 1 step GT bearing 1 radial shat displacement alert 2nd step L39VSD_ALM HIGH VIBRATION SHUTDOWN High vibration L39VT_ALM HIGH VIBRATION TRIP High vibration L39VF_ALM L39VS10A_ALM L39VS10D_ALM L39VS1A_ALM L39VS1D_ALM L39VS2A_ALM L39VS2D_ALM L39VS3A_ALM L39VS3D_ALM L39VS9A_ALM L39VS9D_ALM ALARM TEXT OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check vibration sensors and wiring. Check for mechanical failures, observe vibration level Determine the cause of this trouble and repair Check the vibration sensor Check for mechanical failures, observe vibration level Determine the cause of this trouble and repair Check the vibration sensor Date : 10/2011 Page :20/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN The turbine gas is not on Total liquid or total gas Reduce the load that will be applied to the generator before closing again the generator breaker (network problems). Check the proper operation of the speed relay 14 HS circuit logic. Check fuel system AFPAT sensor fault Change AFPAT sensor Customer damper not in correct status to start GT. Check damper position AFPCS sensor fault Change sensor Both hydraulic pumps locked out Refer to specific chapter Bad signal from load control transducer. Check the transducer 96 GG (setting point, power supply, link). L3FS1C_T_ALM SHUT OFF VALVE SWITCH FAIL TO CLOSED This alarm indicates the wrong position of the shut off valve: The valve is blocked Valve fault Limit switch fault Check that noting is blocking the valve Check the limit switch Check the valve L3FTGL_ALM GAS FUEL TEMPERATURE LOW RECYCLING Trip unit. Gas fuel temperature very is low. L3FTGLT_ALM GAS FUEL TEMPERATURE GAS TOO LOW Gas temperature low. L3FTGLZ_ALM GAS FUEL TEMPERATURE LOW AFTER RECIRCULATION Gas fuel temperature low after re-circulation Check cooling and sealing system The transfer to heavy fuel is not authorized, because the temperature or pressure of the heavy fuel is not correct. Check the forwarding heavy fuel system and the heater system (if used). Check the inhibitor system. Check the temperature switch 26 FU_2, 26 FL_2 and pressure switch 63 FU_2 and 63 AD_1. L3A_ALM TURBINE UNDERSPEED l3ACS_ALM SERVOS CHECK FAULT TRIP AMBIENT PRESSURE MEASUREMENT FAULT DAMPER CUSTOMER START INHIBIT INLET PRESSURE MEASUREMENT FAULT BOTH HYDRAULIC PUMPS LOCKED OUT LOSS OF EXTERNAL SETPOINT LOAD SIGNAL L3APFLT_ALM L3CP_ALM L3CPRI_ALM L3DWBCOKZ_AL L3DWRF L3FUZ_ALM HEAVY FUEL TRANSFER PERMISSIVE TROUBLE OMMO_5_9E_E0858_EN_V3 The turbine speed is too low (< 95%) when complete sequence is reached (L3) (end of starting sequence). All right reserved Copyright Revision : A Check the proper operation of the temperature switch FTG. Check the gas skid (motor, fan, circuit, etc…) Check the gas heating system. Check the proper operation of the temperature switch 26 GL. Date : 10/2011 Page :21/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT L3GCVA_ALM GAS CONTROL VLV NOT FOLLOWING - ALARM L3GCVFLT_ALM GAS CONTROL VALVE SERVO TROUBLE L3GLTSDTC_AL L3GLTSUTC_AL L3GRVA_ALM SHUT DOWN GAS LEAK TEST COMPLETE START UP GAS LEAK TEST COMPLETE STOP/SPEED RATIO VLV NOT TRACKING ALARM L3GRVFLT GAS RATIO VALVE POSITION SERVO TROUBLE L3GRVT_ALM STOP/SPEED RATIO VLV NOT TRACKING TRIP L3IGVFLT_ALM INLET GUIDE VANE POSITION SERVO_TROUBLE OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES Start inhibited + transfer to fuel if running on gas or transfer to gas inhibited. The gas control valve feedback is abnormal. Supply fault. Sensors defected. Valve and servo-valve fault. Start inhibited + transfer to fuel if running on gas or transfer to gas inhibited. The gas control valve feedback is abnormal. Supply fault. Sensors defected. Valve and servo-valve fault. ACTIONS TO BE TAKEN Check LVDT, 96 GC_1, 2 (setting value, wiring). Check the calibration of the VGC. Check the proper operation of the servo-valve 65 GC_1. Check LVDT, 96 GC_1, 2 (setting value, wiring). Check the calibration of the VGC. Check the proper operation of the servo-valve 65 GC_1. Shut down gas leak test complete. No action Start up gas leak test complete No action Valve position fault LVDT fault Start inhibited + transfer to fuel if running on gas or transfer to gas inhibited. The gas ratio valve feedback signal is abnormal. Supply fault. Sensors defected. Valve and servo-valve fault. Valve position fault LVDT fault Check valve position Check LVDT Loss of feedback. At start-up, the inlet guide vanes are not closed. At normal speed, the inlet guide vanes are closed. All right reserved Copyright Revision : A Check LVDT, 96 SR (setting value, wiring). Check the calibration of the VSR. Check the proper operation of the servo-valve 90 SR. Check valve position Check LVDT Determine the cause and correct before restarting. The master reset must be initiated before starting. Check the proper operation of the solenoid valve 20 TV_1 and the control system of the jack. Check the setting values of the LVDT 96 TV_1 and 2. Refer to the control specification. Check logic circuit. Date : 10/2011 Page :22/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L3LFLT_ALM ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN LIQUID FUEL CONTROL FAULT Liquid fuel check system has detected an abnormal servo or LVDT position or signal. HP oil fault. Mechanical problem on the bypass. Check the fuel pressure before the nozzles. Check for the fuel leakage. Check the HP oil pressure and check for leakage. Check if the bypass is not clamped. Check the different devices (setting point, calibration). Check the regulation system. L3SFLT_ALM Start inhibited. Lube oil heaters fault (23 QT_1 to 6). LUBE OIL TANK TEMERATURE FAULT Lube oil pump in trouble (88QA_2). Loss of AC. MASTER PROTECTIVE START Turbine not ready to start CHECK ETR FAULT EXHAUST TC VTCC See : L3PTCC_1J1A_FLT COMMUNICATIONS FAULT CONTROL SYSTEM FAULT TRIP Control system fault L3SMT_ALM STARTING DEVICE TRIP. L3TFLT_ALM LOSS OF COMPRESSOR DISCHARGE Bad signal from compressor pressure transmitter (96 CD). PRESSURE BIAS L3TMFLT1_ALM TORQUE CONVERTER GV TROUBLE L3LTOT_ALM L3MP_ALM L3PTCC_ALM L3TNRERRX L3VLST_ALM L3WCTIM_ALM DWATT TOO LOW TO SUPPORT TNR_TNR LOWER HEAT VENT GAS PRESS ULTRA LOW DOWNSTREAM SSOV ON_LINE WATER WASH INHIBITED OMMO_5_9E_E0858_EN_V3 Failure of cranking motor to start. The torque converter guide vane position transducer is damaged or disconnected. Dwatt too low to support tnr_tnr lower Check the lube oil heaters (23 QT to 6). Check the lube oil circuit. Check the AC supply (415 VAC). Check start check screen on the HMI See : L3PTCC_1J1A_FLT Check control system Check the cranking motor cell, the breaker and the electrical motor. Identify the faulty circuit and repair. CAUTION: Take the safety recommendation for working on medium voltage. Check the transmitters and associated connections. Check the associated connections for proper bias signal. Check the pressure. Check the transducer. Verify the adjustment. Do not restart the unit before it is done. Check fuel supply Check FSR limitation Gas feeding pressure low Check the feeding of gas fuel The ‘’On-line’’ water wash is inhibited because the compressor inlet temperature is low. To continue the water wash sequence, select in the SPEEDTRONIC MARK V the ‘’Inlet air heating’’ circuit. All right reserved Copyright Revision : A Date : 10/2011 Page :23/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L3WWTDZ_ALM FALSE START DRAIN TC DIFF HIGH Spread between the Two TC’s, TC disconnected or broken. Check TC and connection. Repair wiring or replace TC if found damaged. L3Z_ALM FAILURE TO SYNCHRONIZE Unit did not synchronize and close generator breaker within the normal expected time. L43ADJ_ALM VSVO IN CALIBRATION MODE VSVO in calibration mode L43CR_ALM L43EX_ALM L43FL_T_ALM L43MAINT_ALM L45FP1_ALM L45FP2_ALM L45FP4_ALM L45FPX_ALM L45FTX1_ALM L45FTX2_ALM L45FTX4_ALM STARTING MEANS CRANKING MOTOR REMOTE POSITION EX2K MANUAL (FVR) REGULATOR ACTIVE TRANSFER TO LIQUID FUEL FAIL TRIP MAINTENANCE _ FORCING MODE ENABLED FIRE PRE-ALARM IN ZONE 1 FIRE PRE-ALARM IN ZONE 2 FIRE PREALARM ZONE #4 ALARM FIRE PROTECTION - GENERAL FIRE ALARM ZONE 1 & 2 FIRE IN ZONE #1 FIRE IN ZONE #2 FIRE ALARM ZONE #4 ALARM OMMO_5_9E_E0858_EN_V3 Investigate synchronization system to determine exact cause of problem. Check the stability of the turbine speed control. Finish calibration Set off calibration mode Starting motor remote selected No action EX2K manual (FVR) regulator active No action Transfer to liquid fail Transfer during more than 2 minutes Auto calibrate, memory changing or logic forcing mode of operation has been selected. Fire detection in compartment # 1 Fire detection in compartment # 2 Fire detection in compartment # 4 Check liquid fuel system When done with the operation, deselect the operation. See alarm : L33CL1_ALM See alarm : L33CL1_ALM See alarm : L33CL1_ALM Fire detection in compartment # 1 See alarm : L33CL1_ALM Fire in zone #1 Fire in zone #2 Fire is detected in Ò–4 zone. See alarm : L33CL1_ALM See alarm : L33CL1_ALM See alarm : L33CL1_ALM All right reserved Copyright Revision : A Date : 10/2011 Page :24/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L45HA4_ALM L45HA4H_ALM L45HA4HH_ALM L45HA4T_ALM ALARM TEXT HZD GAS DETEC DLN/AUX COMPT CARD FAULT OF SET 4 HZD GAS DETEC DLN COMP-DLN VENT/GAS CAB HIGH LEVEL HZD GAS DETEC DLN /AUX COMPT#4 VENT/GAS CAB HIGH HIGH LEVEL HZD GAS DETEC HIGH HIGH LEVEL INFORMATION OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN A leak of gas is detected in the DLN compartment. Gas leak detection alarm may be generated either by gas detection loop fault or by a real gas leak. Refer to Gas detection control system cabinet and relevant component literature for detailed fault analysis. Gas leak detection alarm must be considered as high priority. Continued operation of the turbine is not recommended. Proceed to normal shutdown to avoid later trip by higher detection level. For dual fuel machine, do not transfer to liquid fuel. This will not eliminate the leak if situated downstream the gas control valves. The leak shall remain at the same place with other fluid (e.g. purging air). Do not open the door of the enclosure, keep the area around free of people. Access to enclosure is only permitted when the main gas valve is closed and the line depressurised, the unit is stopped, on cooling sequence by ratchet system (Frame 6000B) or by barring system (Other Frame) with issuing of the relevant access permit or permit to work. Visual check the flanges (Refer to Residual risks summary/Maintenance phase) and the flexible metal hoses (Refer to GEK 111694) and all other connections. Pressurise the length/section of pipe according to End User procedure and appropriate precautions. It may be worth to use portable gas detectors and/or leak detection liquids or spray to find what caused the alarm. Repair the leak and reset the alarm after investigation. A leak of gas is detected in the DLN compartment. See alarm : L45HA4_ALM A leak of gas is detected in the DLN/auxiliaries compartment. #4 See alarm : L45HA4_ALM A leak of gas is detected in the ventilation compartment See alarm : L45HA4_ALM All right reserved Copyright Revision : A Date : 10/2011 Page :25/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L45HA5_ALM L45HA5HH_ALM L45HA6_ALM L45HA6HH_ALM L45HGD_PRETA L45HGDHH_ALM L45HGDSD_ALM ALARM TEXT HZD GAS DETEC DLN/AUX COMPT CARD FAULT OF SET 5 HZD GAS DETEC DLN /AUX COMPT#5 VENT/GAS CAB HIGH HIGH LEVEL HZD GAS DETEC DLN/AUX COMPT CARD FAULT OF SET 6 HZD GAS DETEC DLN /AUX COMPT#6 VENT/GAS CAB HIGH HIGH LEVEL START INHIBITED DUE TO GAS DETECTION FIRST LEVEL HZD GAS DETEC HIGH HIGH LEVEL INFORMATION HAZARDOUS GAS DETECTION FAILURE - SHUT DOWN OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN A leak of gas is detected in the DLN compartment. See alarm : L45HA4_ALM A leak of gas is detected in the DLN/auxiliaries compartment. #5 See alarm : L45HA4_ALM A leak of gas is detected in the DLN compartment. See alarm : L45HA4_ALM A leak of gas is detected in the DLN/auxiliaries compartment. #6 See alarm : L45HA4_ALM A leak of gas is detected in the ventilation compartment Check where the gas is detected An alarm indicate witch compartment is concern See alarm : L45HA4_ALM A leak of gas is detected in the ventilation compartment See alarm : L45HA4_ALM Start inhibited All right reserved Copyright Revision : A Date : 10/2011 Page :26/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L45HT1_ALM L45HT1H_ALM L45HT1HH_ALM L45HT1T_ALM L45HT2_ALM ALARM TEXT TURB COMPARTMENT GAS LEVEL HIGH-ALM TURBINE & EXTRACT DUCT COMB GAS LEVEL HIGH' HZD GAS DETEC TURBINE COMPT#1 HIGH HIGH LEVEL TURB COMPARTMENT LEVEL VERY HIGH-TRIP GT VENTILATION DUCT GAS LEVEL HIGH-ALM OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN Gas level high detected in the turbine compartment. Gas leak detection alarm may be generated either by gas detection loop fault or by a real gas leak. Refer to Gas detection control system cabinet and relevant component literature for detailed fault analysis. Gas leak detection alarm must be considered as high priority. Continued operation of the turbine is not recommended. Proceed to normal shutdown to avoid later trip by higher detection level. For dual fuel machine, do not transfer to liquid fuel. This will not eliminate the leak. The leak shall remain at the same place with other fluid (e.g. purging air). Do not open the door of the enclosure, keep the area around free of people. Access to enclosure is only permitted when the unit is stopped, on cooling sequence by ratchet system (Frame 6000B) or by barring system (Other Frame) with issuing of the relevant access permit or permit to work. Visual check the flanges (Refer to Residual risks summary/Maintenance phase) and the flexible metal hoses (Refer to GEK 111694). Pressurise the length/section of pipe according to End User procedure and appropriate precautions. It may be worth using portable gas detectors and/or leak detection liquids or spray to find what caused the alarm. Repair the leak and reset the alarm after investigation. Turbine compartment level very high. Check the gas sensors 45 HT-1HH, 2HH and 3-HH A leak of gas is detected in the turbine compartment. #6 See alarm : L45HT1_ALM Turbine compartment level very high. Check for leakage in the gas turbine compartment. Check the gas sensors 45 HT-1HH, 2HH and 3-HH. Gas level high detected in the GT ventilation duct. See alarm : L45HT1_ALM All right reserved Copyright Revision : A Date : 10/2011 Page :27/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L45HT2HH_ALM L45HT3_ALM L45HT3HH_ALM L45HT4_ALM L45HT4H_ALM L45HT4HH_ALM L45HT4T_ALM L45HT5_ALM L45HT5HH_ALM L45HT6_ALM L45HT6HH_ALM ALARM TEXT HZD GAS DETEC TURBINE COMPT#2 HIGH HIGH LEVEL HZD GAS DETEC TURBINE COMPT CARD FAULT OF SET 3 HZD GAS DETEC TURBINE COMPT#3 HIGH HIGH LEVEL HZD GAS DETEC TURBINE COMPT CARD FAULT OF SET 4 HZD GAS DETEC TURBINE COMPT VENT DUCT HIGH LEVEL HZD GAS DETEC TURBINE COMPT#4 HIGH HIGH LEVEL HZD GAS DETEC TURBINE COMPTVENTILATION DUCT TRIP HZD GAS DETEC TURBINE COMPT CARD FAULT OF SET 5 HZD GAS DETEC TURBINE COMPT#5 HIGH HIGH LEVEL HZD GAS DETEC TURBINE COMPT CARD FAULT OF SET 6 HZD GAS DETEC TURBINE COMPT#6 HIGH HIGH LEVEL OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN A leak of gas is detected in the turbine compartment. #2 See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. #3 See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. See alarm : L45HT1_ALM A leak of gas is detected in the ventilation compartment. See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. #4 See alarm : L45HT1_ALM A leak of gas is detected in the ventilation compartment See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. #5 See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. See alarm : L45HT1_ALM A leak of gas is detected in the turbine compartment. #6 See alarm : L45HT1_ALM All right reserved Copyright Revision : A Date : 10/2011 Page :28/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L48_ALM TURBINE INCOMPLETE SEQUENCE Failure of unit to reach complete sequence. L48CR_ALM TURBINE SHAFT FAILURE TO BREAK AWAY The time delay is finished and the turbine shaft does not breakaway. Starting means fault. L49X_ALM AUXILIARY MOTOR OVERLOAD One of the auxiliary motors is overloaded. L4CT_ALM CUSTOMER TRIP Customer trips input to the L4CT logic have caused an automatic trip of the unit. Check equipment, which is the cause of the problem in the normal sequence: starting system power, torque converter, fuel control, and acceleration loop. Check if the AUTO order has been executed. Check the operation of the auxiliaries. Check the starting means. Check the supplies. Check auxiliary motors to determine which motor is overloaded and the cause of the overloading. On the defective motor, check the overload relay, the fuses (or the CB), and the motor with the cables. Check the set point of the overload relay. Check the fuses FU.1, 2 on the motor overload circuit. Determine which of the customer trip devices caused the trip and correct. Operator selected excitation off. For information Regulation fan block starts L4EXOFF_ALM L4FCBRUN_ALM L4IGVT_ALM L4LTTH_T_ALM EX2K OPERATOR SELECTED EXCITATION OFF REGULATION FAN BLOCK STARTS INLET GUIDE VANE CONTROL TROUBLE TRIP The I.G.V. position is not correct. Adjustment of the hydraulic jack. Problem of the setting values. LUBE OIL HEADER TEMPERATURE SNSR FLT: TRIP The 3 thermocouple are faulty Temperature of lube oil is too high. Shutdown TG For information Check the I.G.V. control system. Check the proper operation and the setting values of the LVDT 96 TV_1 and 2. Check the adjustment of the hydraulic jack. Refer to the control specifications. Check the lube oil skid (exhauster, heater, pump). Check proper operation of thermocouple LTTH1/LTTH2/LTTH3. Breakers failure, wire lost, timer failure Check power supply, wiring, breakers, timer in M.C.C Breakers failure, wire lost, timer failure Check power supply, wiring, breakers, timer in M.C.C 88QA fault Check 88QA Check 88QE Check electrical circuit L4QETRPZ_ALM DC PUMP FIRST STEP TIMER FAILURE DC PUMP SCND STEP TIMER FAILURE AC PUMP FAILURE TRIP L4QETST_ALM DC PUMP TEST FAILED L4QESTP1_ALM L4QESTP2_ALM OMMO_5_9E_E0858_EN_V3 88QE fault All right reserved Copyright Revision : A Date : 10/2011 Page :29/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L4TK_WW_ALM EXHAUST FRAME BLOWER FAULT. WATER WASH INHIBITED Exhaust frame blower fault. Impossible to wash TG. L51QE_ALM EMERGENCY LUBE OIL OVERLOAD The emergency lube oil pump is faulty. L51QEFLT_ALM DC PUMP ABNORMAL POWER EMERGENCY LUBE OIL PUMP OUT OF SERVICE ATOMIZING AIR BOOSTER MCC CONTACT POSITION ALARM See alarm : L51QE_ALM Check the operation of the motors 88 TK_1 and _2. Inspect cooling airflow passages. Check the suction silencers. Check the pressure switches 63 TK _1,2. Check the time over current relay 51 QE. Check the mechanical status of the pump. Check supply of the motor pump. See alarm : L51QE_ALM See alarm : L51QE_ALM See alarm : L51QE_ALM Atomizing air booster Command trouble Check Atomizing air booster power supply in MCC Something is blocking the fan Motor overload Short circuit Motor fault Check that nothing is blocking the fan Check the fan can run in good conditions Check electrical circuit Check motor Determine the breaker, which is open, and find the reason of its position (overload, fuses fault, defected motor, mechanical problem of the motor or the fan, supply, etc.). Correct cause of problem and close breaker. L51QEOFF_ALM L52AB_ALM L52BT_ALM TURBINE COMPARTMENT VENT. FAULT L52FC1_ALM COOLING WATER FANS PERMANENT Breaker opened by operator or tripped by high motor BLOCK FDBCK FAULT temperature. L52FC2_ALM L52FDY_ALM L52FM_ALM L52G1_ALM L52HA11_ALM L52HA30_ALM COOLING WATER FANS REGULATOR See alarm : L52FC1_ALM BLOCK FDBCK FAULT FUEL FORWARDING MOTOR The remote breaker is detected open BREAKER OPEN FLOW DIVIDER STARTUP MOTOR Flow divider startup motor breaker fault BREAKER FAULT GENERATOR BREAKER TRIPPED GAS COMPARTMENT HEATER BREAKER FAULT AUXILIARY COMPARTMENT HEATER BREAKER FAULT OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN See alarm : L52FC1_ALM Determine the cause of this trouble and repair. Check flow divider startup motor breaker Generator breaker has been tripped by an automatic protective device or manually. Determine device that tripped the breaker. The problem should be corrected before coupling again. NOTE: For a new coupling, one must give a new start order for proper operation of synchronizing sequence. Discrepancy between start order and feedback Check feedback match with heater status Discrepancy between start order and feedback Check feedback match with heater status All right reserved Copyright Revision : A Date : 10/2011 Page :30/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L52HQ1_ALM HYDRAULIC SUPPLY AUXILIARY PUMP DISCREPANCY Motor, pump fault Motor supply fault. Oil leakage on HP circuit. Check for leakage. Check the mechanical status of the motor and the pump. Check the motor supply (fuses, breaker, connection) Check the proper operation of : _ the pressure switch 63 HQ_1. _ the pressure transmitter 96 HQ_1. _ the overload relays 49 HQ_1 and 2. Check the status of the filter (an alarm must appear). L52HT30_ALM TURBINE COMPARTMENT HEATER BREAKER FAULT Discrepancy between start order and feedback Checks feedback match with heater status L52JS_ALM HEAT VENT WI COMPARTMENT VENT. FAULT Something is blocking the fan Motor overload Short circuit Motor fault Check fuses, breakers, protections, and supply. Check the mechanical status of the fan and the motor in trouble. Check the proper operation of the water injection fan motor 88JS. After doing corrective action, close the breaker in trouble. L52MCBALM_ALM DEFAULTS FUSIBLES UNDERVOLTAGE RELAY Customer signal Specific customer L52QA_ALM AUXILIARY LUBE OIL PUMP MOTOR RUNNING The main lube oil pump is supplying insufficient lube oil pressure due to pump failure or leaks. Examine main lube pump. Check pump output and main lube filters for leaks or plugging. Check proper operation of pressure switch 63 QA. L52QB_ALM GENERATOR LIFT STANDBY BEAR LIFT OIL PMP RUNN Lube oil pump ready or running For information L52TG_ALM TURNING GEAR MOTOR TROUBLE The turning gear motor is not running during the turning gear sequence. EXHAUST FRAME BLOWER #1 DISCREPENCY EXHAUST FRAME BLOWER #2 DISCREPENCY Blower is running while there is no run signal Blower is not running while there is run signal Blower is running while there is no run signal Blower is not running while there is run signal LOAD COMP. COOLING FAN MOTOR TROUBLE The load compartment cooling fan motor is not running. L52TK1_ALM L52TK2_ALM L52VG_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check the turning gear motor drawer 88 TG (fuses, breaker, relay, power supply). Check the AC supply power. Check 88TK1 Check electrical circuit Check 88TK2 Check electrical circuit Check the power supply of the motor drawer in the T.C.C. Check the relay. Determine the trouble and repair as soon as possible. Date : 10/2011 Page :31/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT L52VL_ALM HEAT VENT DLN COMPARTMENT VENT. FAULT L52WCY_ALM POSSIBLES CAUSES The second fan motor starts (88VL_1 or 2). One of the two fan is in trouble One of the two motors is in trouble 88VL_1 or 88VL_2. Motor supply fault. Water pump breaker open Pump is running while there is no run signal Pump is not running while there is run signal ACTIONS TO BE TAKEN Check the electrical status of the motor. Check the motor supply (breaker, fuses, connection). Check the fan in trouble. Bad over-speed configuration trip Change the over-speed configuration trip with the toolbox L5CMPST_TRP WATER PUMP BREACKER OPEN WATER INJECTION PUMP DISCREPENCY VPRO - OS SETPOINT CONFIG ERROR TRIP VPRO - COMPOSITE TRIP(S) One or more module of one VPRO card fault L5E_ALM MANUAL TRIP _ LOCAL The emergency stop pushbutton has been pressed. Check modules on each VPRO cards Correct abnormality that caused the operator to push the emergency stop pushbutton. L5ESTOP1_ALM E-STOP 1 PROTECTIVE CIRCUIT LATCHED Emergency stop by protective circuit. L52WN1_ALM L5CFG_TRP_AL L5ESTOP1_FZA L5PPRO_LATCH L60BOG_ALM L60FSRG_ALM L60TRF_ALM L62CD_ALM VPRO - EMERGENCY STOP PB DEPRESSED Someone has depressed the emergency stop pb PROTECTIVE PPRO CARD TRIP Diagnostic alarm on the dedicated card PPRO LATCH Defaut communication TURBINE STARTUP BOGGED DOWN Problems during startup TRIP Manual FSR control has not been reset to a position where FSR GAG NOT AT MAX LIMIT it will not interfere with automatic FSR control. REGULATION IN FSR TEMPERATURE The regulation is in FSR temperature control. CONTROL The cool-down sequence has been interrupted before the COOLDOWN SEQUENCE RUNNING end of normal cycle. L62LV_ALM WATER WASH NEEDED Water wash needed after 15 operating with crude oil. L62TT2_ALM FAILURE TO START The master protective logic signal ‘’L4’’ has tripped the unit twice or if the unit is operating in remote, flame was not established after two tries at establishing flame. OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Close water pump breaker Check 88TK3 Check electrical circuit Correct abnormality that caused the emergency stop Check that the problem for witch the emergency stop pb was pressed is resolved WARNING NEVER DEPRESS THE EMERGENCY STOP PB BEFORE TO BE SURE THE PROBLEM IS RESOLVED Check Diagnostic alarm relating to the card mentioned by using the toolbox. Check trip diagram on HMI Refer to specific alarm(s) Raise the manual FSR control to maximum. Check the regulation system CPD. Continue cool-down sequence except in the case of major problem. Water wash has to be done, and then operation with crude oil is authorized. Check all signals going making up the ‘’L4’’ logic signal to determine which caused the problem or determine cause of lack of flame establishment. Date : 10/2011 Page :32/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L62WWY_ALM VENT AFTER AN OFF LINE WASHING INTERRUPTED Vent after an off line washing interrupted Refer to specific chapter L63AD4L_ALM ATOMIZING AIR DIFFERENTIAL PRESSURE LOW Atomizing air compressor not providing adequate pressure. Normal shutdown. Lack of air at the upstream of the compressor. Compressor fault (CA1_1 or 2). Step-up gear fault. Motor fault (88 AK_1 or 2). L63ADL_ALM ATOMIZING AIR DIFF. PRESSURE LOW Atomizing air compressor not providing adequate pressure. L63ADLA_ALM ATOMIZING AIR DIFFERENTIAL PRESSURE LOW The discharge pressure of the atomizing air H.P. compressor is too low. L63BWL_ALM SKID WASHING PRESSURE OR FLOW FAULT Skid washing pressure or flow fault L63CA1L_ALM INLET AIR FILTER COMPRESSED AIR PRESS LOW ALARM Air filter compressor pressure low. L63CPDL_ALM CPD PRESSURE LOW ALARM CPD pressure low alarm OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check atomizing air system. Check the valves .are correctly positioned. Check for leakage. Check the status (mechanical and electrical) of the compressors and the step-up gears. Check motor. Check the check valves before step-up gears. Check the proper operation of the pressure switches 63 AD_1, 2 and their setting point. Check the proper operation of the transmitter 96AD_1. Check atomizing air system. Check on running gear if the shaft driver atomizing air compressor is running: if coupling broken replace the atomizing air compressor before starting up the limit. If atomizing air compressor is correct, check compressor during operation (vibration) and the circuit (help with the pressure indicators). Check the pressure switches 63AD and their setting point. Check the atomizing air H.P. compressor. Check the atomizing air piping. Check the pressure switch 63 AD_1. Check washing skid Check the cleanliness of the air filter. Check the proper operation of the pressure switch 63 CA_1. NOTE: Refer to Manufacturer’s recommendations for air filters maintenance in specific volumes. Check GT compressor system Date : 10/2011 Page :33/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L63CSH_ALM COMPRESSOR INLET DIFF PRESSURE HIGH TRIP Inlet filter dirty. L63CSH_SENSR TURBINE COMPRESSOR INLET PRESS. SW. TROUBLE The pressure switches of the air inlet compressor are in trouble. L63CSHH_ALM COMPRESSOR INLET DIFF PRESSURE HIGH TRIP Inlet filter dirty. VANADIUM INHIBITOR FLOW CHECKING FUEL FWD PUMP DISCHARGE PRESSURE LOW FUEL FORWARDING PRESS. HIGH ALARM HEAT VENT 63FG-1 SENSOR TROUBLE HEAT VENT 63FG-2 SENSOR TROUBLE The pressure of the fuel additive is high Pressure switch fault GAS FUEL PRESSURE LOW Gas fuel pressure to turbine has been sensed as low. L63FLZ_ALM LIQUID FUEL PRESSURE LOW Inlet liquid fuel pressure is low. Pressure switch 63 FL_2 trouble (see control specifications for the setting value). Strainer, filter, pumps fault. Leakage. L63FU1L_ALM HEAVY FUEL OIL LOW PRESSURE AT The pressure of the heavy fuel is too low, and the unit PUMP DISCHARGE transfers automatically to distillate fuel. L63FAH_ALM L63FD1L_ALM L63FD2H_ALM L63FG1_ALM L63FG2_ALM L63FGL_ALM OMMO_5_9E_E0858_EN_V3 The pressure on the fuel-forwarding skid is low. The pressure on the fuel-forwarding skid is high. ACTIONS TO BE TAKEN Check the filter status. Change it, if necessary. Check the differential pressure switches 63 CS (operation and setting point). NOTE: Refer to specific volumes for Air filter maintenance. Check the state of the pressure switches 63 CS_1 and _2 (proper operation and setting point). Check their logic circuit. Check the filter status. Change it, if necessary. Check the differential pressure switches 63 CS (operation and setting point). NOTE: Refer to specific volumes for Air filter maintenance. Check the inhibition skid Check the forwarding skid. Check the pressure switch Check the forwarding skid. Check the pressure switch 63 FD_2. Heat vent 63FG-1 sensor trouble Check heat vent 63FG-1 sensor Heat vent 63FG-2 sensor trouble Check heat vent 63FG-2 sensor All right reserved Copyright Revision : A Check cause of low supply pressure: check the gas fuel pressure supply, the strainer and the pressure switch 63 FG_3. Check the fuel-forwarding skid (pumps, motors, filters). Check the pressure switch 63 FL_2 (operation and setting). Check the strainer filter at the turbine inlet. Check for leakage. Check the piping for leak. Check the pressure switch Check the heavy fuel forwarding system. Date : 10/2011 Page :34/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L63FU2LA_ALM HEAVY FUEL PRESSURE LOW The pressure of the heavy fuel is too low, and the unit transfers automatically to distillate fuel. L63FU3HZ_ALM NAPHTA PRESSURE HIGH Forwarding skid in trouble. Pressure switch faulty. L63GSD1H_ALM L63GSD2H_ALM GAS FUEL SCRUBBER GAS 101FI DIFF PRESS HIGH GAS FUEL SCRUBBER GAS 121FI DIFF PRESS HIGH Check the piping for leak. Check the pressure switch 63 FU_2. Check the heavy fuel forwarding system. Check the forwarding skid. Check the proper operation of the pressure switch 63 FU_3. Gas scrubber filter/sep 101FI DIF is clogged Clean gas scrubber filter/sep 101FI DIF Gas scrubber filter/sep 121FI DIF is clogged Clean gas scrubber filter/sep 121FI DIF L63HF1H_ALM HYDR. FILTER DIFF. PRESSURE HIGH The hydraulic oil filter is dirty. L63HQ1L_ALM HYDRAULIC SUPPLY PRESSURE LOW Hydraulic supply pressure is low. L63LF2H_ALM LIQUID FUEL FILTER DIFF. PRESS. HIGH The differential pressure too high at the fuel oil filter. L63LF30H_ALM CRUDE OIL FILTER CLOGGED Crude oil filter clogged L63LF3H_ALM FUEL FILTER DIFF. PRESSURE HIGH The filter of the fuel skid is dirty. L63LF7H_ALM LIQUID FUEL FILTER DIFF PRESS HIGH The filter of the fuel skid is dirty. OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN All right reserved Copyright Revision : A Check hydraulic pressure with the pressure gauge. Changeovers the hydraulic oil filters and replaces it if necessary. Check the pressure switch 63 HF. Check the closing of test valve. Check hydraulic supply pressure filter and differential pressure gauge, regulating valve or, pump or proper operation of pressure switch 63 HQ_1. Check the closing of the test valves. Check the filter status. Check for leakage. Inspect fuel oil filters and correct condition. Check proper operation of fuel oil filter differential pressure switch (operation and setting point) 63 LF_1. Change or repair if necessary. Check the closing of the test valve. Check filter Clean or change the filter Check the filter and changeover, if necessary. Check the differential pressure switch 63 LF_3. Check the filter and changeover, if necessary. Check the differential pressure switch 63 LF_3. Date : 10/2011 Page :35/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L63PGFT_ALM GAS FUEL NOZ. PURGE SYSTEM PRESSURE HIGH The two purge valves VA 13_1 and VA 13_2 are seen closed and the pressure switch 63 PG_1 has detected a high pressure. Check the position of the purge valves VA 13_1 and VA 13_2. Check the limit switches 33 PG_1 and 33 PG_3 (proper operation). Check the pressure switch 63 PG_1. L63PLLZ_ALM LIQUID FUEL PURGE LOW AIR PRESS The liquid fuel air purge pressure is low. Check the pressure switch 63PL-21. L63QA2L_ALM LUBE OIL PRESSURE ALARM BEARING Lube system leaks or pump or transmitter trouble. L63QBLY_ALM GEN BRG LIFT LOW PRESS AT PUMPS OUTLET Lift pump fault Motor fault Pressure switch fault L63QQ10H_ALM LUBE OIL MIST FILTER - DIFF. PRESS Clogged filter. - HIGH L63QQ1H_ALM MAIN LUBE OIL FILTER DIFF. PRESSURE HIGH L63QQ8H_ALM L63QT_ALM L63QT_SENSR TRIP OIL FILTER DIFF. PRESSURE HIGH TURBINE LUBE OIL HEADER PRESS LOW TRIP LUBE OIL PRESSURE SWITCH TROUBLE OMMO_5_9E_E0858_EN_V3 Repair leaks or pump. Check proper operation of the transmitter (96QA_2) and the pressure switch 63 QA-2. Check the closing of the test valves. Check the proper operation of the bearing lift pump Check the motor supply (fuses, breaker, connection) Check for leakage Check the proper operation of the pressure switch 63QB (operation and setting point) 88QA fault 88QE fault Loss of fluid pressure and deterioration of fluid purity may result. Change filter. Check the pressure switch 63QQ_1. Loss of fluid pressure and deterioration of fluid purity may result. Change filter. Check the pressure switch 63QQ_1. Check the lube oil filter. Check the pressure switch 63QQ_8. Check 88QA Check 88QE Bad signal from lube oil pressure switch. Check pressure switches 63QT_2A, 2B and 63QA. Clogged filter. The lube oil filter is dirty. All right reserved Copyright Revision : A Date : 10/2011 Page :36/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L63QTX_ALM TURBINE LUBE OIL HEADER PRESS LOW TRIP Lube oil pressure has fallen below the trip level. L63TF10H_ALM FLOW INLET FILTER DIFF PRESSURE Inlet filter excessive pressure drop. Filter is dirty. L63TF1H_ALM L63TFH_ALM L63TFH10_ALM TURBINE AIR INLET DIFF. PRESS. ALARM INLET FILTER PRESSURE DROOP TRIP ALARM INLET FILTER PRESSURE DROOP TRIP ALARM Check the proper operation of the pressure-regulating valve VPR_2. Check the proper operation of the lube oil pumps. Check for leakage. Check the pressure switch 63 QT_2A. Check the proper operation of the transmitter 96QA_2 Determine cause and correct before restarting unit. Check the pressure drop. If the pressure is excessive, change the air filters. If the pressure is correct, check the pressure switch 63 TF and its setting point. NOTE: Refer to Manufacturer’s recommendations for air filters maintenance in specific chapters. See alarm : L63TF10H_ALM See alarm : L63TF10H_ALM See alarm : L63TF10H_ALM See alarm : L63TF10H_ALM See alarm : L63TF10H_ALM See alarm : L63TF10H_ALM L63TK_ALM EXHAUST FRAME COOLING AIR PRESSURE LOW Exhaust frame blower motor not operating. Air passages blocked. L63TKY_ALM EXHAUST FRAME PRESSURE LOW Exhaust frame pressure low. L63VGH_ALM LOAD COMP INLET FILTER CLOGGED - BY PASS OPEN Heat vent load compartment inlet air filter clogged L63WC1L_ALM COOLING WATER PUMP DISCH PRESSURE LOW. The pressure of cooling water pump is low. L63WN3H_ALM WATER INJECTION FILTER DIFF PRESS HIGH The water filter is dirty. OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN All right reserved Copyright Revision : A Check the operation of the motors 88 TK_1 and _2. Inspect cooling airflow passages. Check the suction silencers. Check the pressure switches 63 TK _1,2. Check the operation of the motors 88 TK_1 and _2. Check the suction silencers. Check the pressure switches 63 TK _1,2. Clean heat vent load compartment inlet air filter#2 Check the pumps and motor. Check leakage. Check the status of the filters. Check the differential pressure, clean the filter or change it if necessary. Check the pressure switch 63 WN3. Date : 10/2011 Page :37/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L64D_ALM BATTERY 125 VDC GROUND Insulation failure has resulted in a ground on the 125 VDC system. L71CBL1_ALM L71CBL2_ALM L71CBL4_ALM CO2 GAS LOSS ZONE1 CO2 GAS LOSS ZONE2 CO2 GAS LOSS ZONE3 The CO2 bottles are empty The CO2 bottles are empty The CO2 bottles are empty L71FA1L_ALM FUEL ADDITIVE STORAGE TANKLEVEL LOW The level of the fuel additive storage tank is low. L71FA1LX_ALM L71FA2L_ALM L71FF2T_ALM L71FF2T_SNSR L71FF4L_ALM L71GS12A_ALM L71GS12B_ALM L71GS13_ALM CRUDE OIL FWD ADDITIVE STORAGE TANK- LEVEL LOW CRUDE OIL ADDITIVE SKID TANKFAULT LIQUID FUEL HIGH LEAKAGE ON SKID - TRIP LIQUID FUEL LEAKAGE SNSRS FAULT ON LIQUID SKID LIQUID FUEL LOW LEAKAGE LEVEL ON SKID GAS FUEL SCRUBBER 101FI-2A LEVEL HIGH GAS FUEL SCRUBBER 101FI-2B LEVEL HIGH GAS FUEL SCRUBBER 101FI-3 LEVEL HIGH OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN Immediate action should be taken to locate ground and to repair, because if a second ground occurs, this can result in severe damage to the wiring and to the battery. As soon as possible, shut down the unit and check the 125 VDC power. Isolate ground and remove from system. Check the DC motors and all circuits supplied with dc voltage. CAUTION: During this repair, the generator and the starting engine breakers must be opened for safety. Change the CO2 bottles Change the CO2 bottles Change the CO2 bottles Check the level in the tank. Check the level indicator 71 FA_1. Check for leaks. Check pipes. The level of the crude oil FWD additive storage tank is low. Additive tank The crude oil additive skid tank is fault. Check the tank. Liquid fuel low leakage level on GT frame Check for leakage Liquid fuel low leakage level on GT frame Sensors fault Check for leakage Check sensors Liquid fuel low leakage level on GT frame Check for leakage Condensate to high in gas separator Purge gas separator Condensate to high in gas separator Purge gas separator Condensate to high in gas separator Purge gas separator All right reserved Copyright Revision : A Date : 10/2011 Page :38/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L71GS1H_ALM L71GS1HT_SNS L71GS22A_ALM L71GS22B_ALM L71GS23_ALM L71GS2H_ALM L71GS2HT_SNS L71GSHHT L71GSHHT_ALM L71QH_ALM ALARM TEXT GAS FUEL COALESC FILTER #1 LEVEL HIGH GAS FUEL #1 COALESC FILTER LEVEL SENSOR TROUBLE GAS FUEL SCRUBBER 121FI-2A LEVEL HIGH GAS FUEL SCRUBBER 121FI-2B LEVEL HIGH GAS FUEL SCRUBBER 121FI-3 LEVEL HIGH GAS FUEL COALESC FILTER #2 LEVEL HIGH GAS FUEL #2 COALESC FILTER LEVEL SENSOR TROUBLE GAS FUEL SEPARATOR CONDENSATE VERY HIGH LEVEL TRIP GAS FUEL SEPARATOR CONDENSATE VERY HIGH LEVEL LUBE OIL LEVEL HIGH OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN Gas fuel coalesc filter #1 is clogged Clean gas fuel coalesc filter #1 Gas fuel #1 coalesc filter level sensor trouble Check gas fuel #1 coalesc filter level sensor Condensate to high in gas separator Purge gas separator Condensate to high in gas separator Purge gas separator Condensate to high in gas separator Purge gas separator Gas fuel coalesc filter #2 is clogged Clean gas fuel coalesc filter #2 Gas fuel #2 coalesc filter level sensor trouble Check gas fuel #2 coalesc filter level sensor Condensate to high in gas separator Purge gas separator Condensate to high in gas separator Purge gas separator High lube oil tank level or some liquid is coming in the tank. Check proper operation of the tank level 71QH_1. Investigate cause of high-level alarm and restore normal level. NOTE: Stop the unit if there is some other fluid with the lube oil (water or liquid fuel). In this case, never restart the unit before repair. All right reserved Copyright Revision : A Date : 10/2011 Page :39/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN Check proper operation of the level 96QL_1. Checks lube oil system for possible leakage or for excessive consumption. Check the transmitters 96QL-1. Repair and restore normal level with proper oil (see piping schematics for oil level reference and lube oil recommendations). NOTE: In these units, oil consumption is normal so, refilling is necessary periodically with proper oil. Check the level of water-cooling. Check the water-cooling system. Check the bottom of the generator package to define the leaks if there is any leak. Check the indicator switch. L71QL_ALM LUBE OIL LEVEL LOW Lube oil tank level low. L71WG1_ALM GENERATOR LIQUID LEVEL DETECTOR A leak of the water-cooling system, or a leak of oil, is detected. L71WG2_ALM GENERATOR LIQUID LEVEL DETECTOR 2# NDE See alarm : L71WG1_ALM See alarm : L71WG1_ALM Cooling water tank level low. The alarm will actuate when the cooling water tank level drops below a minimum level (see piping schematics). Repair leaks, and add properly treated water. Check for proper operation of level indicator 71WL. NOTE: If there is some water in the lube oil tank, one must stop the unit. Sump tank high level Empty sump tank Sump tank very high level Check limit switch and pump system Sump tank low level Check limit switch and pump system Electrical fault on the emergency lube oil pump motor Check the emergency lube oil pump and motor. L71WL_ALM L71WS1_ALM L71WS3_ALM L71WS4_ALM L72QE_ALM COOLING WATER LEVEL LOW SUMP TANK HIGH LEVEL LIMIT SWITCH SUMP TANK HIGH HIGH LEVEL SUMP TANK LOW LEVEL LIMIT SWITCH EMERGENGY LUBE OIL PUMP MOTOR ELECTRICAL FAULT OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Date : 10/2011 Page :40/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L72QETST_ALM DC PUMP DID NOT START Loss of DC power to aux lube oil pumps. Oil leakages. Motors fault Pumps fault. Sensor fault. L72QEZ_ALM EMERGENCY LUBE PUMP MOTOR RUNNING The main pump driven accessory gear and AC powered lube oil pump have not supplied sufficient lube oil pressure because of pump failure or leaks. Determine cause of DC power loss. Refer to the specific alarms about electrical faults signaled. Check the motors (88QE). Check the oil pumps. Check the status of the transmitter (63QE). Check for leaks and pump malfunction. Check proper operation of pressure switches 63 QL, 63 QT_2A and 63 QT_2B. The batteries compartment temperature is high. Check heating and ventilation system. The batteries compartment temperature is low. Check heating and ventilation system. The control compartment temperature is high. Check heating and ventilation system. The control compartment temperature is high. Check heating and ventilation system. Compressor bleed valves have not operated properly. They are in the wrong position or required an excessive amount of time to move from one position to the other. Investigate problem. The problem should be corrected before restarting. The Master reset switch must be pressed before restarting. Check proper operation of the solenoid valve 20 CB. Check the control air supply of VA 2_1, 2_2, 2_3, 2_4 valves and the opening of the isolating valve. Check the cleanliness of the air separator. Check the limit switches 33 CB. Over-speed trip being checked. See ‘’Over-speed trip checks’’ module 10 of this chapter. Remote breaker opening detected For information L74BATH_ALM L74BATL_ALM L74HL_ALM L74HT_ALM L83CBLIMIT L83HOST_ALM L83RBO_ALM L83WW_ALM L83WWON_ALM L86ARS_ALM BATTERIES COMPARTMENT TEMPERATURE HIGH BATTERIES COMPARTMENT TEMPERATURE LOW CONTROL COMPARTMENT TEMP LOW CONTROL COMPARTMENT TEMPERATURE HIGH COMP BLD VLV FAIL TO CLOSE LIMITED OVERSPEED TEST MODE SELECTED _ HP REMOTE BREAKER OPENING DETECTED WASHING ON-LINE PROHIB.INLET TEMP.LOW 24H DELAY NECESSARY SINCE THE LAST WW AC TRANSFER FAULT OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN The on-line water wash is inhibited because the temperature The on-line water wash will be possible as soon as the is low. temperature will be in the limit spread. 24 hours necessary since the last water wash. Wait the period of 24H to start again on-line washing. A512-40G1 loss of excitation (A) Check exciter cubicle All right reserved Copyright Revision : A Date : 10/2011 Page :41/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L86BTTEST_AL HEAT VENT TURB COMP TEST ABORTED BT test stopped because of ventilation pressure fault Check BT or leaks in compartment L86BTX_ALM LOSS OF TURBINE COMPARTMENT COOLING FAN The turbine compartment ventilation is faulty. L86CBA_ALM COMPRESSOR BLEED VALVE POSITION TROUBLE Compressor bleed valves have not operated properly. They are in the wrong position or required an excessive amount of time to move from one position to the other. L86CBT_ALM L86CPR_FLT COMPRESSOR BLEED VALVE POSITION TROUBLE TRIP COMP OPERATING LIMIT CONTROL FAULT See alarm : L86CBA_ALM See alarm : L86CBA_ALM Inlet heating control valve fault. Compressor discharge pressure transmitters fault. Check operation of bleed heat control valve. Check the compressor discharge pressure transmitters. Determine the cause of this fault before attempting a new start. NOTE: The master reset function must be selected before restarting. Check the proper operation of heavy fuel inhibitor pump. Check the tank level. Check the proper operation of heavy fuel inhibitor the pump. Check SRV valve Check regulation constant are the same e as in the A010 Check GCV valve Check regulation constant are the same e as in the A010 Check SRV valve Check regulation constant are the same e as in the A010 L86CRTX_ALM STARTING MOTOR PROTECTIVE LOCKOUT The cranking motor protective system has been initiated. L86FA_ALM FUEL ADDITIVE CIRCUIT FAULT Low level of inhibitor tank. Heavy fuel inhibitor pump faulty. L86FAX_ALM CRUDE OIL FWD Crude oil FWD additive pumps fault alarm L86FPG2HT_A POST-IGNITION P2 HIGH TRIP SRV valve to much opened L86FPG2IH_AL PRE-IGNITION P2 PRESS HIGH IGN INHIBIT GCV valve not enough opened L86FPG2LT_A POST-IGNITION P2 LOW TRIP SRV valve not enough opened L86FS_ALM LIQ FUEL FALSE START-USE RESET DISPLAY Liquid fuel false start-use reset display OMMO_5_9E_E0858_EN_V3 Check the ventilation system of this compartment (power supply, motors, fans, electrical circuit...). Check the position of vent flap. Check the proper operation of the limit switch 33BT Investigate problem. The problem should be corrected before restarting. The Master reset switch must be pressed before restarting. Check proper operation of the solenoid valve 20 CB. Check the control air supply of VA 2_1, 2_2, 2_3, 2_4 valves and the opening of the isolating valve. Check the cleanliness of the air separator. Check the limit switches 33 CB. All right reserved Copyright Revision : A After sequencing reset by 86FSRST_CPB Date : 10/2011 Page :42/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L86FT_ALM L86FUX_ALM L86G1AMON_AL L86G1BMON_AL L86G2AALM_AL L86G2AMON_AL ALARM TEXT POSSIBLES CAUSES HEAVY FUEL TEM. FAULT XFERT LOCKOUT COMPLETE LOSS OF HEAVY FUEL FWD PUMPs 74/86G-1A LOCK OUT RELAY COIL FAULT The temperature of the heavy fuel is not correct. The transfer is locked. Complete loss of heavy fuel FWD pumps crude oil FWD additive pumps. 74/86G-1B LOCK OUT RELAY COIL FAULT 74/86G-2A LOCK OUT RELAY TRIP 74/86G-2A LOCK OUT RELAY COIL FAULT L86G2BALM_AL 74/86G-2B LOCK OUT RELAY TRIP L86G2BMON_AL 74/86G-2B LOCK OUT RELAY COIL FAULT L86GCVT_ALM GAS CONTROL VLV NOT FOLLOWING - TRIP L86GLTA_ALM L86GLTB_ALM L86GSC10T12A L86GSC1T3_AL L86GSC4T6_AL L86GSC7T9_AL GAS LEAK TEST OF SRV FAILED GAS LEAK TEST OF GCV/VENT FAILED 2/3 GEN STATOR WIND. CENT. TEMP SNSR FLT #10-11-12 2/3 GEN STATOR WINDING CENTER TEMP SNSR FLT #1-2-3 2/3 GEN STATOR WINDING CENTER TEMP SNSR FLT #4-5-6 2/3 GEN STATOR WINDING CENTER TEMP SNSR FLT #7-8-9 OMMO_5_9E_E0858_EN_V3 74/86G-1A lock out relay coil fault Lockout relay 74/86G-1B is faulty. Wiring circuit in GCP sequence Tripping coil of the 52G circuit breaker is faulty. 74/86G-2A lock out relay trip 74/86G-2A lock out relay coil fault The lockout 74/86G-2B relay tripped in the GCP and sent opening order 41E and 52G breakers Lockout relay 74/86G-2B is faulty. Wiring circuit in GCP sequence Tripping coil of the 52G circuit breaker is faulty. Start inhibited + transfer to fuel if running on gas or transfer to gas inhibited. The gas control valve feedback is abnormal. Supply fault. Sensors defected. Valve and servo-valve fault. ACTIONS TO BE TAKEN Check heavy fuel heating system Check pumps. Check 74/86G-1A Check relay Check 74/86G-2A Check 74/86G-2A Check 74/86G-2B Check relay Check LVDT, 96 GC_1, 2 (setting value, wiring). Check the calibration of the VGC. Check the proper operation of the servo-valve 65 GC_1. Gas leak of SRV valve Check SRV valve Gas leak of GCV valve or Gas Purge Inter valve Check GCV valve or Gas Purge Inter valve Temperature sensor fault 2 of 3 Generator RTDs failure Temperature sensor fault 2 of 3 Generator RTDs failure Temperature sensor fault 2 of 3 Generator RTDs failure Temperature sensor fault 2 of 3 Generator RTDs failure Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections Decrease the generator load Check RTD and associated connections All right reserved Copyright Revision : A Date : 10/2011 Page :43/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L86GVA_ALM INLET GUIDE VANE CONTROL TROUBLE The I.G.V. position is not correct. Adjustment of the hydraulic jack. Problem of the setting values. Check the I.G.V. control system. Check the proper operation and the setting values of the LVDT 96 TV. Check the adjustment of the hydraulic jack. Discrepancy between start order and feedback Check feedback match with heater status L86HEATR_ALM L86JSX_ALM L86N_ALM L86N1MON_ALM L86N2MON_ALM L86NX_ALM L86PUR_ALM L86PURC_ALM L86PURT_ALM COMPARTMENT HEATER OPERATING - PRE IGNITION TRIP LOSS OF W. I. COMPARTMENT VENTILATION ELECTRICAL TROUBLE NORMAL SHUTDOWN 74/86N-1 LOCK-OUT RELAY COIL FAULT 74/86N-2 LOCK-OUT RELAY COIL FAULT STARTUP CHECK STOP GEN PROTECTION FAILURE SHUTDOWN HEAVY FUEL TG - TRIP HEAVY FUEL PURGE VALVE FAILURE TO OPEN HEAVY FUEL PURGE VALVE FAILURE TO CLOSE Loss of W.I. Compartment ventilation. Electrical trouble on the generator with normal shutdown for the unit. 74-86N-1 lock-out relay coil fault Check 74-86N-1 lock-out relay coil 74-86N-2 lock-out relay coil fault Check 74-86N-2 lock-out relay coil The general protection of the generator is defect Check generator system GT trip while running with heavy liquid fuel For information Check the proper operation of the purge valve. The heavy fuel purge valve failed to open. The heavy fuel purge valve failed to close. L86PURZ_ALM HEAVY FUEL PURGE TG TRIP SINCE 1 HOUR GT tripped since 1 hour and operator heavy purge confirmation not given L86QE_ALM DC PUMP ELECTRICAL TROUBLE START INHIBITED DC pump electrical trouble start inhibited L86S AUTO SYNCHRONIZING LOCKOUT Auto synchronizing self-checking system has detected a synchronizing equipment abnormality. OMMO_5_9E_E0858_EN_V3 Check fan Check electrical circuit Determine the electrical trouble with the matrix in the protection panel. NOTE: The unit should not be operated until the cause of the problem has been determined and corrected. Refer to specific chapters for more information about generator. All right reserved Copyright Revision : A Check the proper operation of the purge valve. Finish heavy fuel purge sequence Confirm purge Restart gas turbine heavy fuel when purge finished Check DC pump Check electrical circuit Investigate synchronization system to determine exact cause of problem. Refer to the Manufacturer’s documents about the synchronizing system. Date : 10/2011 Page :44/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L86T1AALM_AL 74/86T-1A LOCK OUT RELAY TRIP 74/86T-1A Lock out relay coil fault L86T1AMON_AL L86TCI L86TFB_ALM L86TFD_C L86TFD_NOFLOW L86TFD_O L86TFDLOW_AL L86TGT1_ALM L86TGT2_ALM 74/86T-1A LOCK OUT RELAY COIL FAULT COMPRESSOR INLET THERMOCOUPLES DISAGREE EXHAUST THERMOCOUPLES OPEN TRIP FALSE START DRAIN VALVE FAIL TO CLOSE FALSE START DRAIN SYSTEM BLOCKED FALSE START DRAIN VALVE FAILURE TO OPEN FSD VALVE CLOSED AT LOWER PRESS THAN EXPECTED GENERATOR DIFFERENTIAL TRIP CHANNEL 1 GENERATOR DIFFERENTIAL TRIP CHANNEL 2 74/86T-1A Lock out relay coil fault Check relay Check GCP Check relay Check GCP Bad thermocouple signal. Check thermocouples and wiring. Trip. Excessive number thermocouples fault. Position, connection, short-circuit, cut-off fault. Check and reconnect thermocouples. Check the connection and the position. Check for short-circuit and cut-off. Check limit switch wiring and good operation. Look for valve bloquage. Look for any foreign object or residual fuel in drain piping. Check valve operation. Check limit switch wiring and good operation. Look for valve bloquage. Valve stucked or limit switch failure Drain system clogged. Valve stucked or limit switch failure Valve spring damaged Check valve spring. Electrical trouble with emergency shutdown. Relay 86G indicate a generator differential. Electrical trouble with emergency shutdown. Relay 86G indicate a generator differential. The unit should not be operated until the cause of the problem has been determined and corrected. The unit should not be operated until the cause of the problem has been determined and corrected. Investigate problem. The problem should be corrected before restarting. The Master Reset switch must be pressed before restarting. NOTE: Refer to Manufacturer’s documents and to Control specification for proper values. L86TVA_ALM POSITION IGV FAULT L86TXT_ALM The temperature control system has not limited exhaust temperature within the trip limits. EXHAUST OVERTEMPERATURE TRIP Temperature control system fault. Fuel control system fault. Ventilation system fault. OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN On start-up, the inlet guide vanes are not closed. All right reserved Copyright Revision : A Check the temperature control loop and the fuel control system. Check the cooling and ventilation system. Date : 10/2011 Page :45/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES L86VGX_ALM LOSS OF LOAD GEAR COMPT COOLING FAN Air fan fault Motor fault Power supply fault L86VL1_ALM LOSS OF MCC VOLTAGE - LOSS OF VENTILATION SD The heat compartment ventilation is faulty. L86VLTEST_AL L86VLX_ALM HEAT VENT DLN COMP TEST ABORTED LOSS OF DLN COMPARTMENT VENTILATION L86WN1_ALM WATER INJ. SUCTION PRESSURE HIGH LOCKOUT L86WN2_ALM WATER INJ. DISCHARGE PRESS. LOW LOCKOUT L86WN3_ALM WATER INJ. FLOW HIGH LOCKOUT L86WN7_ALM WATER INJECTION LOW FLOW TRIP WATER L86WW_ALM L86WWTD OFF LINE COMP WW - USE RESET DISPLAY LOSS OF FALSE START DRAIN TEMPERATURE SENSORS NS OMMO_5_9E_E0858_EN_V3 ACTIONS TO BE TAKEN Check the load compartment cooling ventilation system Check the supply of motors 88VG Check fuses, breakers and protections Check the mechanical status of the fans and the motors Check the ventilation system of this compartment (power supply, motors, fans, electrical circuit...). Check the position of vent flap. Check the proper operation of the limit switch 33VL VL test stopped because of ventilation pressure fault Check VL or leaks in compartment Fans fault Check fans The water injection mode is automatically deselected. The water pressure at the inlet of the water injection skid is too high. Leakage. Dirt strainers. Test valves open. Isolating valves at the inlet pump closed. Check for leakage. Check the closing of the test valves. Check the status of the strainer. Check the opening of the isolating valve at the inlet pump. Check the pressure switch 63 WN_1 (operation and setting point). Check the opening of isolating valve of water inlet. Check for leakage. Check the pressure. The water injection mode is automatically deselected. Check the proper operation of the pressure switch 63 The water pressure at the outlet of the water injection skid is WN_2. too low. Check the proper operation of the water pump. Check the water injection system. Check the solenoid valve 20 WN. The water injection mode is automatically deselected. Check the flow pickup 77 WN. The injected water flow is higher than the authorized limit. Check the water injection system. Water injection trip. Check the flow pickup 77 WN. Water flow low. Check the limit switch 33 WN_0. Limit switch fault. Check the water injection system. Off line comp WW - use reset display After sequencing reset by L86WWRST_CPB TC failure or input card failure Check input card and check TC integrity All right reserved Copyright Revision : A Date : 10/2011 Page :46/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L90TKL_ALM EXHAUST FRAME COOLING SYS TRBL - UNLOAD Exhaust frame cooling sys trouble - unload Check cooling system L94BLN_ALM STARTUP CHECK STOP BATTERY CHARGER TROUBLE - SD The 2 batteries charger AC under voltage. The 2 batteries chargers are faulty. L94BTL_ALM HEAT VENT TURBINE COMPARTMENT SB FAN TEST FAILED The turbine ventilation is faulty. Motor 88BT_1 and 2 fault L94DP1_ALM L94DP2_ALM L94DP3_ALM L94F1B_ALM L94F2B_ALM L94F4B_ALM L94GLTSD_ALM L94GLTSU_ALM G60A CRITICAL FAILURE –TRIP G60B CRITICAL FAILURE – TRIP T60A CRITICAL FAILURE – TRIP FIRE PROTEC AUX/TURB/LOAD COMPT CO2 RELEASE FIRE PROTEC BEARING AREA CO2 RELEASE CO2 RELEASED ZONE #4 ALARM SHUTDOWN GAS LEAK TEST FAILED STARTUP GAS LEAK TEST FAILED STARTUP CHECK STOP LOAD TUNNEL TEMP HIGH SD G60A critical failure trip G60B critical failure trip T60A critical failure trip Check the 2 batteries charger AC breaker. Check voltage magnitude. Check the proper operation of the batteries charger. Check the ventilation system of this compartment. Check fuses, breakers, protections, and supplies. Check the mechanical status of the fan and the motor in trouble. Check the proper operation of each cooling air fan motor 88BT Check the position of vent flap. Check G60A Check G60B Check T60A CO2 emission See alarm : L33CL1_ALM CO2 emission See alarm : L33CL1_ALM See alarm : L33CL1_ALM Check for leakage Check for leakage L94LTTH_ALM LUBE OIL HEADER TEMPERATURE SNSR FLT: SHUTDOWN L94LV_ALM XFER TO DIST WATER WASH NEEDED CO2 emission Leakage in gas system during shutdown TG Leakage in gas system during startup TG Thermocouple faulty Shutdown TG 2 of the 3 thermocouple are faulty Temperature of lube oil is too high. Shutdown TG Transfer to distillate. Water wash needed after 15 operating with crude oil. L94PGT_ALM GAS FUEL NOZ. PURGE SYSTEM TROUBLE TRIP Inter-valve pressure between VA 13_1 and VA 13_2 is high during start-up: the unit trips. L94LTH_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check thermocouple ttib1 Check the lube oil skid (exhauster, heater, pump). Check proper operation of thermocouple LTTH1/LTTH2/LTTH3. Water wash has to be done, and then operation with crude oil is authorized. Check the proper operation and position of the purge valve VA 13_2. Check the status of the solenoid valves 20 PG_1 and 20 PG_2. Check the pressure switch 63 PG_1 (operation and setting point). Date : 10/2011 Page :47/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN L94TC_ALM TORQUE CONVERTOR DRAIN VALVE TROUBLE ALARM Check the proper operation of drain valve and solenoid The torque converter drain valve is not actuated in the same valve. time as the solenoid valve (20 TU_1). Check the limit switch 33 TC_1. L94TFD FALSE START DRAIN VALVE TURBINE SHUTDOWN Refer to L86TFD_NOFLOW or L86WWTD Refer to L86TFD_NOFLOW or L86WWTD L94VLL_ALM HEAT VENT DLN COMPARTMENT SB FAN TEST FAILED The turbine ventilation is faulty. Motor 88VL_1 and 2 fault Check the ventilation system of this compartment. Check fuses, breakers, protections, and supplies. Check the mechanical status of the fan and the motor in trouble. Check the proper operation of each cooling air fan motor 88VL Check the position of vent flap. L94VTSG1_ALM VOLTAGE MEASURE DOWNSTREAM 52G TROUBLE The mentioned breaker is open. Consequently the MKVI can not receive the voltage measurement (upstream 52G) for the synchronization. Close the breaker A issue detected on the fuse or MCB Inspection of the measurement cable. Replace the fuse FUSES OR MMCB FAULT FOR SYNC VT'S DOWNSTREAM 52L1&2 Q0xL&T NORMAL STOP PAUSED FOR CBV ACTUATION FIRED SHUTDOWN TOO LONG Normal stop paused for CBV actuation. Verify bleed valve circuit and switch position of bleed valve The fired shutdown is too long L95BT_ALM HEAT VENT TURB COMPT AIR INLET FLOW LOW The turbine ventilation is faulty. Motor 88BT_1 and 2 fault For information Check the ventilation system of this compartment. Check fuses, breakers, protections, and supplies. Check the mechanical status of the fan and the motor in trouble. Check the proper operation of each cooling air fan motor 88BT Check the position of vent flap. L95BTL_ALM HEAT VENT TURB COMPT AIR INLET FLOW VERY LOW See alarm : L95BT_ALM L94VTSG2_ALM L94X_S_ALM L94XZ_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A See alarm : L95BT_ALM Date : 10/2011 Page :48/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME L95VL_ALM L95VLL_ALM L96FG1_ALM L96FGDIFF_AL ALARM TEXT HEAT VENT DLN COMPT AIR INLET LOW FLOW HEAT VENT DLN COMPT AIR INLET LOW FLOW CONFIRMED HEAT VENT 96FG-1 SENSOR TROUBLE GAS FUEL PRESS TRANSMITTERS DIFF FAILURE L96FGH_ALM GAS FUEL PRESSURE HIGH L96FGL_ALM GAS FUEL SUPPLY PRESSURE LOW L96QV1_ALM LUBE OIL MIST ELIM HIGH PRESSURE LAAP4_SENSR LAAP4AFLT_ALM LAAP4BFLT_ALM LAAP4CFLT_ALM LAAP4FLT_T ATOMIZING AIR AAP4 XDUCER DIFF FAULT HIGH AA MANIFOLD PRESS XDUCER#A OUT OF RANGE AA MANIFOLD PRESS XDUCER#B OUT OF RANGE AA MANIFOLD PRESS XDUCER#C OUT OF RANGE LOSS OF AA MANIFOLD RATIO PROTECTION - TRIP OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN The turbine ventilation is faulty. Motor 88VL_1 and 2 fault Check the ventilation system of this compartment. Check fuses, breakers, protections, and supplies. Check the mechanical status of the fan and the motor in trouble. Check the proper operation of each cooling air fan motor 88VL Check the position of vent flap. See alarm : L95VL_ALM See alarm : L95VL_ALM Heat vent 96FG-1 sensor trouble Check heat vent 96FG-1 sensor Gas fuel pressure high. Pressure switch fault. Gas fuel pressure high. Pressure switch fault. Gas fuel pressure to turbine has been sensed as low. Purchaser gas supply fault. Leakage. Wiring, supply fault. Transmitter fault. Lube oil mist eliminator high pressure Leakage. Wiring, supply fault. Transmitter fault. The spread between the air pressure transmitters 96AA4A/B/C is too high. Atomizing air pressure transducer 94AA-4A reading out of range. Atomizing air pressure transducer 94AA-4A reading out of range. Atomizing air pressure transducer 94AA-4A reading out of range. Two atomizing air pressure transducers (96AA-4A/B/C) readings out of range. Check the gas fuel system. Check the pressure switch 63 FG. Check the gas fuel system. Check the pressure switch 63 FG. Check the cause of low supply pressure. Check the purchaser gas supply. Check for leakage. Check the transmitters 96 FG_1. Check the opening of the shutoff valve. All right reserved Copyright Revision : A Check for leakage. Check the transmitters 96 QV_1 Check the mentioned sensors, wirings or calibration. Check the mentioned sensor, wirings or calibration. Check the mentioned sensor, wirings or calibration. Check the mentioned sensor, wirings or calibration. Check the mentioned sensors, check-valves, atomizing air system or compressor. Date : 10/2011 Page :49/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME LAAP4STCK_ALM LAAPRH1_ALM LAAPRH2_ALM LAAPRH3_ALM LAAPRL1_ALM LAAPRL2_ALM LAAPRL3_ALM LAAPRTRP_ALM LAFPAP_SENSR LCPD_SENSR LCPRERR_ALM LDB_ABRT_ALM LDB_FAIL_ALM LDBMD_ON_ALM LDWATT_ALM LDWCAL_ALM LFAGNBA_A LFALNBA_A LFPG2_SENSR ALARM TEXT ATOMIZING AIR PRESSURE HIGH – START INHIBITED ATOMIZING AIR PRESS RATIO HIGH ON LIQ FUEL ATOMIZING AIR PRESS RATIO HIGH ON GAS FUEL ATOMIZING AIR PRESS RATIO HIGH ON MIXT FUEL ATOMIZING AIR PRESS RATIO LOW ON LIQ FUEL ATOMIZING AIR PRESS RATIO LOW ON GAS FUEL ATOMIZING AIR PRESS RATIO LOW ON MIXT FUEL ATOMIZING AIR PRESS RATIO LOW LOW TRIP BAROMETRIC PRESSURE TRANSDUCERS DISAGREE COMP DISCHARGE XDUCER DIFF FAULT HIGH COMP OP LIMIT PROTECTION MAX CTRL ERROR UNIT ABORTING DEAD BUS MODE UNIT NOT READY FOR DEAD BUS MODE UNIT READY FOR DEAD BUS MODE MEGAWATT TRANSDUCER SIGNAL TROUBLE GAS FUEL SUPPLY PRESSURE LOW GCV REG AT NULL COMP AUTHORITY LIMIT LCV REG AT NULL COMP AUTHORITY LIMIT INTERVALVE PRESSURE TRANSDUCERS DISAGREE OMMO_5_9E_E0858_EN_V3 POSSIBLES CAUSES ACTIONS TO BE TAKEN Atomizing air pressure too high. Start inhibited Check atomizing air system. Atomizing air pressure ratio High on liquid fuel Check atomizing air system. Atomizing air pressure ratio High on gas fuel Check atomizing air system. Atomizing air pressure ratio High on mixture operation Check atomizing air system. Atomizing air pressure ratio Low on liquid fuel Check atomizing air system, compressor or check-valves. Atomizing air pressure ratio Low on gas fuel Check atomizing air system, compressor or check-valves. Atomizing air pressure ratio low on mixture operation Check atomizing air system, compressor or check-valves. Atomizing air pressure ratio very low on liquid fuel. Check atomizing air system, compressor or check-valves. One transducer is out Check transducers One transducer is out Check transducers Inlet heating control valve fault. Compressor discharge pressure transmitters fault. Unit aborting dead bus mode Check operation of bleed heat control valve. Check the compressor discharge pressure transmitters. Refer to specific chapter. Unit not ready for dead bus mode Unit ready for dead bus mode Gas fuel supply pressure low Dead bus mode permissive Check the power transmitter and change it if its fault Check the electrical circuit Refer to specific chapter The pressure of the transducer is not correct Check GCV 1 valve The pressure of the transducer is not correct Check GCV 2 valve Inter-valve pressure transducers disagree Check transmitter settings Power transmitter fault All right reserved Copyright Revision : A Date : 10/2011 Page :50/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN LFQGUV_ALM The fuel gas system is in trouble. Check the fuel gas system and the gas skid. Flow divider fuel high flow difference Check flow divider. For information Check the regulated constants. For information Check the regulated constants. LPROFILE_ALM FUEL GAS FLOW OUT OF RANGE FLOW DIVIDER FUEL HIGH FLOW DIFFERENCE SRV OPEN AT 90 % - RISK OF TRIP ON HIGH EXH TEMP SRV VLV OPEN AT 95 % - XFER TO LIQUID FUEL TEMP. COMP LIMIT FSR BACKUP CONTROL ACTIVE GAS FUEL TEMPERATURE TC TROUBLE FREQUENCY OUT OF LIMIT FOR GC TEST. NEED MRST NGC TEST PB ACTIVATED GOV TEST ENABLED - SELECT NGC DISABLED AFTER TEST OVERFREQ OPERATION AT MAX TIME. INSPECTION REQU'D PROFILE TEST PB ACTIVATED LQEP2N_ALM DC PUMP ABNORMAL PRESSURE Motor, pump fault Transducer fault LQEP2NFLT_ALM EMERGENCY LO PUMP DISCH PRESS TRANSDUCER FAILURE 4-20mA 96QE-2 fault LTBRGH_ALM LUBE OIL TEMP BRG DELTA TEMP HIGH The delta temperature between turbine bearings fault Turbine bearings fault Lube oil fault Leakage LTBRGHH_ALM LUBE OIL TEMP BRG DELTA TEMP HH See alarm : LTBRGH_ALM LFQLDIFF_ALM LFSGRH_ALM LFSGRHH_ALM LFSRCPR_ALM LFTG_ALM LGCTESTOF_AL LNGC_ON_ALM LNGCPERM_ALM LOF_LIM_ALM OMMO_5_9E_E0858_EN_V3 Regulation system fault. Thermocouples fault. Check the regulation system. Check operation of bleed heat control valve. Check the thermocouples FT_GI_1, 2 and 3 (connection, wiring and operation). Indication about NGC test For information Indication about NGC test For information Indication about NGC test For information Total operating time in over frequency greater than the allowable limit Indication about profile test All right reserved Copyright Revision : A Turbine shutdown for boroscopic inspection recommanded Check the mechanical status of the motor and the pump. Check the motor supply (fuses, breaker, connection) Check transducer Check 4-20mA 96QE-2 transmitter (connections, cables.). Replace transmitter if necessary. Check the lube oil feed and drain piping Check turbine bearings and lube oil system Check thermocouples Check for leakage Check the correct circulation of the lube oil. See alarm : LTBRGH_ALM Date : 10/2011 Page :51/52 GE Energy Rev : A OPERATION AND MAINTENANCE MANUAL OPERATION SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN LTGBRGH_ALM LUBE OIL TEMP GEN BRG DELTA TEMP HIGH The delta temperature between generator bearings is fault Generator bearings fault Lube oil fault Leakage Check the lube oil feed and drain piping Check generator bearings and lube oil system Check thermocouples Check for leakage Check the correct circulation of the lube oil. LTGBRGHH_ALM LUBE OIL TEMP GEN BRG DELTA TEMP H-H See alarm : LTGBRGH_ALM See alarm : LTGBRGH_ALM LTNHLOSS_ALM LOSS OF CTRL SPEED SIGNAL START EMERGENCY LO PUMP No more speed signal detected on the VPRO cards LTTH1_ALM LUBE OIL THERMOCOUPLE #1 FAULT Temperature of lube oil is too high. LTTH2_ALM LTTH3_ALM LUBE OIL THERMOCOUPLE #2 FAULT LUBE OIL THERMOCOUPLE #3 FAULT INJECTION TO FUEL RATIO LOW 4 MIN AVG. INJECTION TO FUEL RATIO LOW. HOURLY AVG. FALSE START DRAIN TEMPERATURE TC#1 OUT OF RANGE FALSE START DRAIN TEMPERATURE TC#2 OUT OF RANGE See alarm : LTTH1_ALM See alarm : LTTH1_ALM If ‘’Request injection to fuel ratio’’ is greater than ‘’Actual injection to fuel ratios’’ during four minutes. If ‘’Request injection to fuel ratio’’ signal is greater than ‘’Actual injection to fuel ratio’’ signal during hourly average... Check the status of the control valve. TC failure or input card failure Check input card and check TC integrity TC failure or input card failure Check input card and check TC integrity MANUAL TRIP _ REMOTE The emergency stop pushbutton has been pressed. Correct abnormality that caused the operator to push the emergency stop pushbutton. LWLX4MIN LWLXHR LWWTD1_FLT LWWTD2_FLT R5E_ALM OMMO_5_9E_E0858_EN_V3 All right reserved Copyright Revision : A Check pickup system Check electrical circuit Check VPRO cards Check the lube oil skid (exhauster, heater, pump). Check proper operation of thermocouple See alarm : LTTH1_ALM See alarm : LTTH1_ALM Check the status of the control valve. Date : 10/2011 Page :52/52