Set the bus bar type to 33 kV and also set the Nominal Voltage of the bus to 33 kV Set the middle busbar to 11 kV and the lower busbar to 3.3 kV in the same way. transformer was connected in the one line diagram. Select Type > Select Project Type TR2 20;33/11;10%. In the same way set the values for the bottom transformer. Select Type / Select Project Type TR2 5;11/3.3;5%. Open the dialogue window to edit the external network. It is important to note that the external grid element has no type and all electrical data is stored in the element itself. Set the Load Flow and Short Circuit data as follows: Load Flow data: Bus Type = "SL'' (slack); Angle = 0.0 deg; Voltage Set Point = 1.0 p.u. VDE/IEC Short-Circuit: Short Circuit Power Sk''max = 10000 MVA; R/X ratio = 0.1 Open the dialogue window to the 11 kV asynchronous machine. Click Type / Select Project Type ASM 11kV 5MVA Load Flow data: Active Power = 4 MW. Open the dialogue window to the 3.3 kV asynchronous machine. Click Type / Select Project Type ASM 3.3kV 2MVA Load Flow data: Active Power = 1 MW