Uploaded by l.reddy

5688 CCIAAVC 1312015

advertisement
MINISTRY
OF
ELECTRICITY
IRAQ SUPERGRID PROJECTS
400/132 KV GIS SUBSTATIONS
VOLUME 3
TECHNICAL SCHEDULES
JANUARY 2007
LIST OF REVISIONS
Current
Rev.
1
2
3
4
5
Date
19.11.04
18.03.05
Aug 05
Oct 05
Jan 07
Page
affected
ALL
ALL
ALL
ALL
ALL
Prepared
by
Checked by
(technical)
SSA
JK/MH
JK
MH/MH
JK/MH
JW
JK/MH
JK/MH
JW
JW
Checked by
(quality
assurance)
JW
JW
JW
JW
JW
Approved
by
JW
JW
JW
JW
JW
REVISION HISTORY
3
Aug 05
ALL
4
Oct 05
ALL
5
Jan 07
ALL
Updated with MOE comments and general alignment across
volumes.
Specification split into GIS and AIS versions.
Capacitor specification rationalised.
Impulse withstand and Power frequency withstand values
reviewed in accordance with IEC 60694.
Details for 11 kV (Tertiary) shunt reactors added.
General review
400kV GIS SUBSTATION – VOLUME 3
CONTENT SHEET
VOLUME 1
TECHNICAL SPECIFICATION – PLANT
VOLUME 2
TECHNICAL SPECIFICATION & SCHEDULES – CIVIL WORKS
VOLUME 3
TECHNICAL SCHEDULES – PLANT
400kV GIS SUBSTATION – VOLUME 3
CONTENTS
Page No.
SCHEDULE A -
MILESTONES FOR THE PURPOSE OF PAYMENT AND
HANDOVER TO THE CLIENT ............................................................ A.1
SCHEDULE B -
TIME PERIODS FOR PROCUREMENT, DESIGN,
MANUFACTURE, INSPECTION, TESTING, DELIVERY,
INSTALLATION, COMMISSIONING AND HANDOVER ..................... B.1
SCHEDULE C -
MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION.............................................................. C.1
SCHEDULE C1 -
400 KV GAS INSULATED SWITCHGEAR.......................................... C.1
SCHEDULE C2 -
400 KV AIS OUTDOOR SWITCHGEAR ............................................. C.2
SCHEDULE C3 -
132 KV GAS INSULATED SWITCHGEAR.......................................... C.2
SCHEDULE C4 -
132 KV AIS OUTDOOR SWITCHGEAR ............................................. C.3
SCHEDULE C5 -
11 KV METALCLAD SWITCHGEAR ................................................... C.4
SCHEDULE C6 -
TRANSFORMERS REACTORS AND AUXILIARY PLANT................. C.4
SCHEDULE C7 -
LV SERVICES EQUIPMENT............................................................... C.5
SCHEDULE C8 -
CABLES .............................................................................................. C.5
SCHEDULE C9 -
SUBSTATION CONTROL AND PROTECTION SYSTEMS`............... C.6
SCHEDULE D -
TECHNICAL PARTICULARS .............................................................. D.1
SCHEDULE D1 -
400 KV GAS INSULATED SWITCHGEAR........................................ D1.1
SCHEDULE D2 -
400 KV OPEN TERMINAL SWITCHGEAR ....................................... D2.1
SCHEDULE D3 -
132 KV GAS INSULATED SWITCHGEAR........................................ D3.1
SCHEDULE D4 -
132 KV OPEN TERMINAL SWITCHGEAR ....................................... D4.1
SCHEDULE D5 -
11 KV (TERTIARY) METALCLAD SWITCHGEAR............................ D5.1
SCHEDULE D6 -
CRANE FOR GIS BUILDING ............................................................ D6.1
SCHEDULE D7 -
400/132 KV POWER TRANSFORMERS .......................................... D7.1
SCHEDULE D8 -
400 KV SHUNT REACTORS............................................................. D8.1
SCHEDULE D9 -
EARTHING TRANSFORMERS (11 KV TERTIARY) ......................... D9.1
SCHEDULE D10 - AUXILIARY TRANSFORMERS (11 KV TERTIARY)....................... D10.1
400kV GIS SUBSTATION – VOLUME 3
CONTENTS - Continued
Page No.
SCHEDULE D11 - CAPACITORS (11 KV TERTIARY) ................................................. D11.1
SCHEDULE D12 - 11 KV (TERTIARY) SHUNT REACTORS ....................................... D12.1
SCHEDULE D13 - LVAC SWITCHGEAR ...................................................................... D13.1
SCHEDULE D14 - DC SYSTEM.................................................................................... D14.1
SCHEDULE D15 - 220 V AC UNINTERRUPTIBLE POWER SUPPLY ......................... D15.1
SCHEDULE D16 - 132/11 KV POWER CABLES .......................................................... D16.1
SCHEDULE D17 - LV CABLES ..................................................................................... D17.1
SCHEDULE D18 - PROTECTION SYSTEM ................................................................. D18.1
SCHEDULE D19 - SUBSTATION CONTROL SYSTEM ............................................... D19.1
SCEHDULE D20 - CONTROL, OPERATION, INDICATION AND ALARM CIRCUITS . D20.1
SCHEDULE D21 - BUSHINGS ...................................................................................... D21.1
SCHEDULE E -
TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS .............................................. E.1
SCHEDULE E1 -
DRAWINGS ISSUED WITH THE TENDER ........................................ E.1
SCHEDULE E2 -
DRAWINGS REQUIRED WITH TENDER ........................................... E.2
SCHEDULE E3 -
CONTRACT DRAWING REQUIREMENTS ........................................ E.3
SCHEDULE E4 -
CONTRACTOR’S SUBMITTALS - DRAWING AND DESIGN DATA .. E.5
SCHEDULE E5 -
INSTALLATION AND MAINTENANCE INSTRUCTIONS ................... E.7
SCHEDULE E6 -
FINAL RECORDS ............................................................................... E.7
SCHEDULE F -
DEVIATIONS FROM THE TECHNICAL SPECIFICATION ................. F.1
SCHEDULE G -
QUANTITIES AND PRICES ................................................................G.1
SCHEDULE J1 -
RECOMMENDED SPARES ...............................................................J1.1
SCHEDULE J2 -
SPECIAL TOOLS, TEST EQUIPMENT..............................................J2.1
SCHEDULE J3 -
TRANSFORMERS AND REACTORS QUANTITIES AND PRICES
FOR SPARE PARTS ..........................................................................J3.1
SCHEDULE K -
BUILDING SERVICES ........................................................................ K.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE L -
HEATING, VENTILATION AND AIR CONDITIONING .........................L.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE A
MILESTONES FOR THE PURPOSE OF PAYMENT AND HANDOVER TO THE
CLIENT
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE A - MILESTONES FOR THE PURPOSE OF PAYMENT AND HANDOVER
TO THE CLIENT
(Information to be provided with Tender)
The Tenderer is to indicate all milestones identified within the programme for the works as defined in this
Project Specification. The milestones should align with those included in the priced (fixed sum) activity
schedule.
Item
No
Description
Section
A.1
400kV SUBSTATION – VOLUME 3
SCHEDULE B
TIME PERIODS FOR PROCURMENT, DESIGN, MANUFACTURE, INSPECTION,
TESTING, DELIVERY, INSTALLATION, COMMISSIONING AND HANDOVER
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE B - TIME PERIODS FOR PROCUREMENT, DESIGN, MANUFACTURE,
INSPECTION, TESTING, DELIVERY, INSTALLATION, COMMISSIONING AND
HANDOVER
(Information to be provided with Tender.
All time periods are weeks from date of Notice to Proceed)
Description
Time within which:
1
All arrangement and equipment drawings shall be
submitted for approval
2
All schemes and functional drawings shall be
submitted for approval
3
All wiring and cable diagrams / schedules shall be
submitted
4
Plant shall be available for final inspection / test in
manufacturer’s works
5
Plant shall be delivered to site
6
Plant shall be installed
7
Overall works are commissioned
8
Overall works are handed over to client
B.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C
MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION
(Information to be supplied with Tender)
SCHEDULE C1 – 400 KV GAS INSULATED SWITCHGEAR
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
400 kV GIS:
Current transformers
Voltage transformers
Surge arresters
Circuit breaker operating mechanisms
Circuit breaker operating mech. motors
Disconnector/earth switch drive motors
Support insulators
Expansion bellows
Bursting discs
Gaskets
Conductors
Enclosures
SF6 Gas handling plant
SF6 Gas
Partial discharge capacitive couplers
Transducers
Local control cubicles
Indicating instruments
Control switches
Status indicators
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
C.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION – CONT
SCHEDULE C2 – 400 KV AIS OUTDOOR SWITCHGEAR
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
400 kV AIS Current transformers
400 kV AIS Voltage transformers
400 kV AIS Surge arresters
400 kV AIS Disconnector/earth
switches
Steel Structures
Conductor
Support insulators
Connectors
SCHEDULE C3 – 132 KV GAS INSULATED SWITCHGEAR
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
132 kV GIS:
Current transformers
Voltage transformers
Surge arresters
Circuit breaker operating mechanisms
Circuit breaker operating mech. motors
Disconnector/earth switch drive motors
C.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION – CONT
SCHEDULE C3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
SF6 Gas handling plant
SF6 Gas
Partial discharge capacitive couplers
Local control cubicles
GIS Switchroom Crane
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
SCHEDULE C4 – 132 KV AIS OUTDOOR SWITCHGEAR
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
132 kV AIS Current transformers
132 kV AIS Voltage transformers
132 kV AIS Surge arresters
132 kV AIS Disconnector/earth
switches
Steel Structures
Conductor
Support insulators
Connectors
C.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION – CONT
SCHEDULE C5 – 11 KV METALCLAD SWITCHGEAR
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
Metalclad enclosures
Circuit breakers
Circuit breaker operating mechanisms
Interrupters
Current transformers
Voltage transformers
Earthing switches
Low voltage equipment
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
SCHEDULE C6 - TRANSFORMERS REACTORS AND AUXILIARY PLANT
Item
No
Description
1
400/132 kV Transformer
2
Transformer Tap Changer
3
400 kV Shunt Reactor
4
11/0.4 kV Auxiliary
Transformer
5
Earthing Transformer
6
11 kV Tertiary Capacitor Bank
7
Series Reactor for Capacitor
Bank
8
11 kV Tertiary Reactor
Manufacturer
Place of
manufacture
Place of testing
and inspection
C.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION – CONT
SCHEDULE C7 - LV SERVICES EQUIPMENT
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
LVAC Equipment
DC Equipment
Batteries
UPS Equipment
Standby Diesel Generator
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
SCHEDULE C8 - CABLES
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
132 kV power cable
11 kV power cable
LV multicore / multipair cable
Cable glands
Cable trays
Cable ladder racks
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
C.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE,
TESTING AND INSPECTION – CONT
SCHEDULE C9 - SUBSTATION CONTROL AND PROTECTION SYSTEMS`
Item
Manufacturer
Place of
manufacture
Place of testing
and inspection
SCS Substation Computer
SCS Operator Workstations / HMI
Operator Desk and Chair
SCS Colour Visual Display Units
SCS Substation LAN
SCS Printers
SCS Bay Control Unit BCU
SCS I/O Cards for BCU
SCS Software Engineering
SCS Database Engineering
Protection Relays
Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval.
C.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D
TECHNICAL PARTICULARS
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR
Unit
Data
Required
1
GENERAL
1.1
Manufacturer & Place of manufacturing
1.2
Type designation
1.3
Type
1.4
Standards
1.5
Rated voltage
kV
420
1.6
System Voltage
kV
400
1.7
Rated frequency
Hz
50
1.8
Rated lightning impulse withstand voltage
KVp
kVp
1425
1665
kV
kV
kV
650
815
1.1 U phase
1.9
Offered
GIS
IEC
Phase to earth
Across the isolating distance
Metal enclosed,
gas insulated
GIS- indoor
IEC 62271 - 203,
60694, 60270,
60376, 60480
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
Phase to earth at SF6 pressure of 1 bar
1.10
Rated short-time withstand current (1 s)
kA
40
1.11
Rated peak withstand current
kA
100
1.12
Type of busbars
1.13
Type of enclosure
1.14
Material of enclosure for:
Breaker and Half
Single phase
enclosures
Circuit breaker
Busbars
Other compartments
Al/St
Al/St
Al/St
1.15
Material of HV conductor
Al/Cu
1.16
Material of contacts (indicate bi-metallic where
used)
1.17
Type of contact
-
Tulip
D1.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
1.18
1.19
Busbars
Busbar disconnect
Circuit breaker
Circuit disconnect
Cable box
Voltage transformer
Yes
Yes
Yes
Yes
Yes
Yes
Method of compensation of expansion and
contraction
-
For busbars
For enclosure
1.20
Type of pressure relief device
1.21
Rupturing pressure
1.22
Type of filter employed for moisture absorption
1.23
Design lifetime of moisture absorbent
1.24
Total mass of switchgear (average per bay)
kg
1.25
Mass of heaviest single component to be handled
during erection
kg
1.26
Total mass of SF6 gas (average per bay)
kg
1.27
Density of gas in:
-
1.28
Circuit breaker compartment
Other than circuit breaker compartments
Molecular Sieve
Years
10
(g/l)
(g/l)
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
Design maximum pressure for:
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
Maximum leakage rate for any gas compartment
per
annum
1.31
bar
Nominal working gas pressure at 50oC in:
-
1.30
Bursting disk
Nominal working gas pressure at 15oC in:
-
1.29
Offered
Minimum subdivision of switchgear:
Less than 1%
D1.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
1.32
Maximum leakage rate for the whole switchgear
1.33
Minimum operating period without total
replacement of SF6 gas
1.34
Minimum thickness of enclosure
mm
1.35
Minimum enclosure puncturing time due to internal
arc fault at short-time withstand current
ms
1.36
Minimum factors of safety for switchgear
-
-
per
annum
years
Busbars or other connections based on elastic
limit
Complete insulators based on electromechanical test
Insulator metal fittings based on elastic limit
Steel structures based on elastic limit of
tension members and on crippling loads of
compression members
Foundations for structures against overturning
or uprooting under maximum simultaneous
working loadings
Data
Required
Less than 1%
Offered
10
Greater than 500
2.5
2.5
2.5
2.5
2.5
1.37
Seismic factor
UBC Zone 3
2
CIRCUIT BREAKER
2.1
Manufacturer & Place of manufacturing
2.2
Type designation
2.3
Type
2.4
Standards
2.5
Rated voltage
kV
420
2.6
Rated Current at 50 0C
(Contractor to confirm by calculation)
- Main busbar
- Bay busbar
- Line transformer Circuit
A
A
A
4000
2000
1600
Single pressure
puffer, SF6
IEC 62271 - 203,
IEC 62271-100,
61233, 60694,
60427, 60376,
60480
D1.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
2.7
Rated frequency
2.8
Rated lightning impulse withstand voltage
-
2.9
Phase to earth
Across the isolating distance
Data
Hz
Required
50
kVp
kVp
1425
1665
kV
kV
650
815
Offered
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
2.10
Rated short-time withstand current (1 s)
kA
40
2.11
Rated peak withstand current
kAp
100
2.12
Rated operating sequence
2.13
Auto reclosing
2.14
Rated making current
kAp
O -0.3 sec- CO -3
min - CO
O -0.3 sec- CO -3
min - CO
100
2.16
Rated breaking current (asymmetrical)
kA
-
%dc
To IEC 62271100
%dc
2.17
Rated breaking current under out-of-phase
conditions
2.18
First phase to clear factor
2.18a
Transient Recovery Voltages
2.19
Rated capacitive breaking current
kA
1.3
TRVs
To IEC 62271100
To IEC 62271100
Rated line charging breaking current
Rated cable charging breaking current
Rated Single/Back to Back Capacitor bank
breaking current
A
A
A
D1.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
2.20
Rated small inductive/reactor breaking currents of:
-
small inductive
reactor
Data
Required
To IEC 62771110
A
A
2.21
Maximum overvoltage factor on any switching duty
pu
2.5
2.22
Maximum overvoltage factor when interrupting
rated line/cable/capacitor bank charging currents
pu
2.5
2.23
Maximum overvoltage factor when switching small
inductive/reactor currents
pu
2.5
2.24
Maximum total break time (trip initiation to final arc
extinction)
ms
60
2.25
Opening time (trip initiation to contact separation)
-
Without current
With 100% rated breaking current
ms
ms
2.26
Maximum time interval between opening of first
and last phase of three phase circuit breakers
ms
2.27
Maximum time interval between opening of
interrupters of one phase
ms
2.28
Closing time from energisation of close coil to
latching of circuit breaker in fully closed position
ms
2.29
Making time (energisation of close coil to contact
touch)
-
Offered
Without current
100% making current
3
ms
ms
2.30
Maximum time interval between closure of first
and last phase of three phase circuit breaker
ms
2.31
Maximum time interval between closure of
interrupters of one phase
ms
2.32
Minimum time from extinction of main arc to
contact make during auto-reclosing duty
ms
2.33
Mechanical life of circuit breaker and mechanism
in No. of operations
3
10,000
D1.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
2.34
Offered
Electrical contact life in number of operations at:
-
Rated current - 2000 A
Fault current - 40 kA
Cumulative ampere rating
15 to 20
2.35
Number of current interrupting break units in
series per phase
2.36
Type of operating mechanism
2.37
Type of power device (motor charged)
-
For closing
-
For opening
two
Spring-charged
or hydraulic
2.38
Hand operating facility
Spring or
hydraulic
Spring or
hydraulic
yes
2.39
Hand charging facility
yes
2.40
Manual spring release
yes
2.41
Mechanical on/off indicator
yes
2.42
Mechanical spring charge / discharge indication
yes
2.43
Charging time
2.44
Number of trip coils
2
2.45
Number of close coils
1
2.46
Nominal control and operating voltage
V
110 DC
2.47
Nominal heater voltage
V
220 AC
2.48
Rated power of trip coil
W
2.49
Rated power of close coil
W
2.50
Rated motor power
W
2.51
Total load of heaters for circuit breaker
W
2.52
Mass of circuit breaker complete (three pole)
kg
2.53
Mass of single phase circuit breaker
2.54
Emergency Trip Facility during failure of DC
supply
s
-
-
-
yes
D1.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
3
DISCONNECTS
3.1
Manufacturer & Place of Manufacturing
3.2
Type designation
3.3
Type of operating mechanism
3.4
Standards
3.5
Rated voltage
3.6
Rated current at 50oC
(Contractor to confirm by calculation)
Motor
IEC 62271-102,
IEC 60694,
61128, 62271 203, 60265
kV
420
Bay selectors
Circuit disconnector
A
A
2000
1600
3.7.
Rated frequency
Hz
50
3.8.
Rated lightning impulse withstand voltage
kVp
kVp
1425
1665
kV
kV
650
815
3.9.
Offered
Phase to earth
Across the isolating distance
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
3.10
Rated short time withstand current (1 s)
kA
40
3.11
Rated peak withstand current
kAp
100
3 .12
Maximum capacitive current that can be
interrupted by the isolator
A
3.13
Total time from initiation of opening operation to
isolator in fully open position
s
3.14
Time from contact separation to extinct of
capacitive arc
s
3.15
Total time from initiation of opening operation to
time when isolator gap can withstand phase
voltage
s
3.16
Hand operating facility
yes
D1.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
yes
3.17
Locking arrangement in on/off position
3.18
Nominal control and operating voltage
3.19
Automatic isolation of control supplies when lock
off
yes
3.20
Accessibility to operating mechanism from ground
level or catwalk
yes
3.21
Nominal heater voltage
V
3.22
Rated power of operation coil
W
3.23
Rated motor power
W
3.24
Total load of heaters for isolator
W
3.25
Total mass of three phase isolator complete
kg
3.26
Mass of single phase isolator
kg
3.27
Contact type
4
EARTHING SWITCH
4.1
Manufacturer & place of manufacturing
4.2
Type designation
4.3
Type of operating mechanism
4.4
Standards
4.5
Rated voltage
kV
420
4.6
Rated frequency
Hz
50
4.7
Rated lightning impulse withstand voltage phase
to earth
kVp
1425
4.8
Rated power frequency withstand voltage phase
to earth
kV
650
4.9
Rated short time withstand current (1 s)
kA
40
4.10
Rated peak withstand current
kAp
100
4.11
Hand operating facility
V
Offered
110 DC
220 AC
Tulip
Motor
IEC 62271-102,
IEC 60694,
62271 - 203
yes
D1.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
yes
4.12
Locking arrangement in on/off position
4.13
Nominal control and operating voltage
4.14
Automatic isolation of control supplies when lock
off
yes
4.15
Accessibility to operating mechanism from ground
level or catwalk
yes
4.16
Nominal heater voltage
V
4.17
Rated power of operating coil
W
4.18
Rated motor power
W
4.19
Total load of heaters for earthing switch
W
4.20
Total mass of earthing switch complete
kg
5
HIGH SPEED EARTHING SWITCH
5.1
Manufacturer & place of manufacturing
5.2
Type designation
5.3
Type of operating mechanism
5.4
Standards
5.5
Rated voltage
kV
420
5.6
Rated frequency
Hz
50
5.7
Rated lightning impulse withstand voltage phase
to earth
kVp
1425
5.8
Rated power frequency withstand voltage phase
to earth
kV
650
5.9
Rated short time withstand current (1 s)
kA
40
5.10
Rated peak withstand current
kAp
100
5.11
Rated short-circuit making current
kAp
100
5.12
Rated capacitive symmetrical breaking current
A
5.13
Rated inductive symmetrical breaking current
A
V
Offered
110 DC
220 AC
Motor-spring
IEC 62271-102,
IEC 60694,
61129, 62271 203
D1.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
5.14
Total time from initiation of opening operation to
earth switch in fully open position
ms
5.15
Time from contact separation to extinction of arc
when interrupting rated breaking current
ms
5.16
Making time
ms
5.17
Charging time
5.18
Hand operating facility
yes
5.19
Locking arrangement in on/off position
yes
5.20
Nominal control and operating voltage
5.21
Automatic isolation of control supplies when lock
off
yes
5.22
Accessibility to operating mechanism from ground
level or catwalk
yes
5.23
Nominal heater voltage
V
5.24
Rated power of operation coil
W
5.25
Rated motor power
W
5.26
Total load of heaters for earthing switch
W
5.27
Total mass of earthing switch complete
kg
6
CURRENT TRANSFORMER
6.1
Manufacturer & place of manufacturing
6.2
Type
6.3
Standards
6.4
Rated voltage
GIS
Cores
kV
V
420
Rated lightning impulse withstand voltage phase
to earth
GIS
Cores
kVp
kVp
1425
6.5
Offered
s
V d.c.
110
220 AC
Toroidal, GIS
enclosed or
external
IEC 60694,
60044-1
D1.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
6.6
Rated power frequency withstand voltage phase
to earth
GIS
Cores
6.7
Rated power frequency voltage between
secondaries
6.8
Inter-turn test
M/P type
Class PX
kV
kV
kV
650
3 kV (EK < 2 kV)
5 kV (EK ≥ 2 kV)
kV
3
kVp
4.5
To IEC 60044-1
50
6.9
Rated frequency
Hz
6.10
Rated continuous thermal current at 50oC
A
6.11
Rated short-time withstand current (1 s)
kA
40
6.12
Rated dynamic current
kAp
100
6.13
Are earthed metal screens fitted between primary
and secondary windings
6.14
Is current transformer housed in a separate gas
compartment
6.15
Details of all current transformers are to be
provided by the Contractor post contract award
-
Number of cores
Rated extended primary current
Ratio (TR = turns ratio)
•
•
•
•
-
Offered
A
A
A
A
I core
II core
III core
IV core
Class
7
VOLTAGE TRANSFORMERS
7.1
Manufacturer & Place of manufacturing
7.2
Type designation for
-
Line transformer – 3 phase
-
Busbar transformer – 3 phase
D1.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
Inductive, SF6
gas insulated,
enclosed
7.3
Type
7.4
Standards
7.5
Rated voltage
kV
420
7.6
Rated frequency
Hz
50
7.7
Rated lightning impulse phase to earth
KVp
1425
7.8
Rated power frequency withstand voltage phase
to earth
kV
650
7.9
Maximum permissible partial discharge level
Um
pC
10
7.10
Maximum permissible partial discharge level
1.2Um /√3
pC
5
7.11
Maximum capacitive current discharge rating
A
7.12
Method of suppressing ferroresonance
phenomena
7.13
Line bay voltage transformer
-
Offered
IEC
60186,60694,
62271 - 203,
60044-2
Number of secondaries
Rated transformation ratio
Rated accuracy class
kV
• I secondary
• II secondary
-
Rated output
• I secondary
• II secondary
7.14
VA
VA
Mass of single/three phase voltage
transformer
kg
Busbar voltage transformer
-
Number of secondaries
Rated transformation ratio
Rated accuracy class
kV
• I secondary
D1.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
-
Rated output (Burden to be 25-100% rated
burden)
Offered
VA
• I secondary
-
Mass of single/three phase voltage
transformer
kg
8
SURGE ARRESTERS
8.1
Type
8.2
Standard
8.3
Rated/system voltage
kV
420/400
-
pu
2.5
Hz
50
IEC 60099-4,
60099-1 60099-5,
60694
Maximum overvoltage factor on the system
due to any switching duty
8.4
Rated system frequency
8.5
Condition of system neutral
8.6
Nominal Discharge current
kA crest
8.7
Energy capability as per IEC 60099-4
kJ/ kV
8.8
Rated voltage - MOA
8.9
Long duration discharge class as per IEC 60099-4
Class
8.10
Maximum Continuous Operating Voltage (COV)
kV
8.11
TOV capability for
-
8.12
kV
1 sec
10 sec
3
kV
kV
Maximum residual voltage with current wave
-
8.14
Solid
Switching Surges - 1kA / 2kA
8/20 μs - 5kA
8/20 μs - 10kA
kV
kV
kV
Discharge current withstand strength
-
kAp
Ap
High current (4/10 μs)
Low current 2000A
D1.13
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D1 – 400 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
8.15
Offered
Pressure relief capability
High current (0.2 s)
Low current
kA
8.16
Rating of earth connections
kA/sec
8.17
Surge counter provided
9
CABLE BOX (WHEN APPLICABLE).
9.1
Manufacturer & Place of manufacturing
9.2
Type of designation
9.3
Standards
9.4
Cable HV test withstand capability
kV
9.5
Rated normal current at 40oC
A
9.6
Required current at 50oC (Contractor to confirm by
calculation)
A
9.7
Rated short time withstand current (1s)
kA
40
9.8
Rated peak withstand current
kA
100
9.9
Total mass of three phase cable box complete
kg
10
MANUFACTURER QUALITY SYSTEM IN
ACCORDANCE TO ISO 9000, 9001, 9002, 9003
AND 9004
10.1
Date of issue
10.2
Validity
11
TYPE TEST CERTIFICATE TO BE ISSUED BY
INDEPENDENT LABORATORY OR
INDEPENDENTLY WITNESSED TYPE TEST
CERTIFICATE TO BE SUBMITTED
-
40/1
Yes
IEC 60859
Yes
Latest
Valid Certificates
–Yes
Yes
D1.14
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR
Unit
Data
Required
1
GENERAL
1.1
Standards
1.2
IEC
IEC 62271-100,
62271-102, 60694,
60233, 60044,
60186, 60383,
60815
Rated voltage
kV
420
1.3
System Voltage
kV
400
1.4
Rated frequency
Hz
50
1.5
Rated lightning impulse withstand voltage
Phase to earth
Across the isolating distance
kVp
kVp
1425
1665
Rated power frequency withstand voltage
Phase to earth
Across the isolating distance
kV
kV
520
610
1.7
Rated short-time withstand current (1 s)
kA
40
1.8
Rated peak withstand current
kA
100
1.9
Rated Current – Cable Feeder at 50 oC
(Contractor to confirm by calculation)
A
1.6
1.10
Material of HV conductor
Aluminium
1.11
Material of contacts
Bi-metallic
1.12
Minimum factors of safety for switchgear
Busbars or other connections based on
elastic limit
2.5
Complete insulators based on electromechanical test
2.5
Insulator metal fittings based on elastic limit
2.5
Steel structures based on elastic limit of
tension members and on crippling loads of
compression members
2.5
Foundations for structures against
overturning or uprooting under maximum
simultaneous working loadings
2.5
Offered
D2.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
mm/kV
Data
Required
31
1.13
Creepage distance (based on Um)
1.14
Seismic factor
2
ISOLATORS
2.1
Type designation
2.2
Type of operating mechanism
2.3
Standards
2.4
Maximum capacitive current that can be
interrupted by the isolator
A
2.5
Total time from initiation of opening operation
to isolator in fully open position
s
2.6
Time from contact separation to extinct of
capacitive arc
s
2.7
Total time from initiation of opening operation
to time when isolator gap can withstand
phase voltage
s
2.8
Hand operating facility
Yes
2.9
Locking arrangement in on/off position
Yes
2.10
Nominal control and operating voltage
2.11
Automatic isolation of control supplies when
lock off
Yes
2.12
Accessibility to operating mechanism from
ground level
Yes
2.13
Nominal heater voltage
V
2.14
Rated power of operation coil
W
2.15
Rated motor power
W
2.16
Total load of heaters for isolator
W
2.17
Total mass of three phase isolator complete
kg
2.18
Mass of single phase isolator
kg
2.19
Contact type
2.20
Type of interlocking
Offered
As UBC
Motor
IEC 62271-102,
IEC 60694, 61128,
60265
V
110 DC
220 AC
D2.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
3
EARTHING SWITCH
3.1
Type designation
3.2
Type of operating mechanism
3.3
Standards
3.4
Hand operating facility
Yes
3.5
Locking arrangement in on/off position
Yes
3.6
Nominal control and operating voltage
3.7
Automatic isolation of control supplies when
lock off
Yes
3.8
Accessibility to operating mechanism from
ground level
Yes
3.9
Nominal heater voltage
V
3.10
Total load of heaters for earthing switch
W
3.11
Total mass of earthing switch complete
kg
Offered
Hand
IEC 62271-102,
60694
V
110 DC
220 AC
D2.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
4
CURRENT TRANSFORMER
4.1
Type
4.2
Standards
4.3
Rated continuous thermal current at 50oC
Offered
Post
IEC 60694,
60044-1
Rated extended
primary current
Note: All Cl PX CTs shall be ISN 1.2 A
4.4
Cable feeder bays current transformer
To suit specific
requirements
Number of cores
Rated extended primary current
Ratio (TR – turns ratio)
I core
II core
III core
IV core
A
A
A
A
Class
I core
II core
III core
IV core
Knee point voltage (Ek)
I core
II core
III core
IV core
V
V
V
V
Exciting current (IE) at Ek
I core
II core
III core
IV core
mA
mA
mA
mA
Rated output (burden to be 25-100% rated
burden)
I core
II core
III core
IV core
VA
VA
VA
VA
D2.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
Total mass of single phase current
transformer complete
4.5
Offered
kg
Bus coupler and bus section bays current
transformer
To suit specific arrangement
Number of cores
120%
5
CAPACITIVE VOLTAGE TRANSFORMERS
5.1
Type
5.2
Standards
5.3
Maximum permissible partial discharge level
Um
pC
IEC 60186,
IEC/PAS 600445:2002
10
5.4
Maximum permissible partial discharge level
1.2Um /√3
pC
5
5.5
Method of suppressing ferroresonance
phenomena
5.5
Line voltage transformer
5.7
Number of secondaries
Capacitive
2
Rated transformation ratio
kV
132/√3 /
0.11/√3 /0.11/√3
Rated accuracy class
I secondary
II secondary
3P/1.0
3P
Rated output (burden to be 25-100% rated
burden)
I secondary
II secondary
VA
VA
Mass of single phase voltage transformer
kg
D2.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
6
SURGE ARRESTERS
6.1
Type
6.2
Standard
6.3
Rated/system voltage
kV
6.4
Maximum overvoltage factor on the system
due to any switching duty
pu
2.5
6.5
Rated system frequency
Hz
50
6.6
Condition of system neutral
6.7
Nominal Discharge current
kA crest
6.8
Energy capability as per IEC 60099-4
kJ/ kV
6.9
Rated voltage - MOA
6.10
Long duration discharge class as per IEC
60099-4
6.11
Maximum Continuous Operating Voltage
(COV)
6.12
TOV capability for
Offered
IEC 60099-4,
60099-1 60099-5,
60694
145/132
Solid
kV
Class
kV
1 sec
10 sec
kV
kV
6.14
Switching Surges - 1kA / 2kA
8/20 μs - 5kA
8/20 μs - 10kA
kV
kV
kV
6.15
Discharge current withstand strength
High current (4/10 μs)
Low current 2000A
kAp
Ap
6.16
Pressure relief capability
High current (0.2 s)
Low current
kA
kA/sec As per IEC
6.17
Rating of earth connections
40/1
6.18
Surge counter provided
Yes
D2.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
7
BUSBARS AND CONNECTIONS
7.1
Type (flexible or tubular)
7.2
Material
7.3
Short-circuit current rating / duration
7.4
Normal current rating
Offered
kA/s
A
A
at 40oC
at 50oC
7.5
Maximum continuous current rating
A
7.6
Flexible conductors
stranding
nominal cross-sectional area
outer diameter
no. of conductors per bundle
spacing between conductors
mm2
mm
7.7
Tubular conductors
nominal cross-sectional area
outer diameter
inner diameter
mm2
mm
mm
7.8
Maximum stress at surface of flexible
conductor
7.9
Radio influence voltage level measured at 1.1
times Us/√3 at 1 MHz
mm
kV/mm
µV
D2.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
8
POST TYPE INSULATORS
8.1
Type designation
8.2
Insulator material
8.3
Number of units in complete post insulator
8.4
Length of each unit
8.5
Mass of complete post insulator
kg
8.6
Maximum cantilever working load (complete
post insulator)
N
8.7
Minimum cantilever breaking load, upright
(complete post insulator)
N
8.8
Power frequency withstand voltage dry: wet
kV
8.9
Basic insulation level
kVp
8.10
Minimum dry/wet switching surge withstand
level
kVp
8.11
Radio influence voltage level measured at 1.1
times Us/√3 at 1 MHz
µv
Offered
mm
D2.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
9
TENSION AND SUSPENSION
INSULATORS
9.1
Type designation
9.2
Insulator material
9.3
Number of units in string
mm
9.4
Greatest diameter of units
mm
9.5
Distance between centres of units
mm
9.6
Length of string, overall
mm
9.7
Mass of string complete with all fittings
kg
9.8
Maximum working load
N
9.9
Power frequency withstand voltage of
complete string
kV
9.10
Basic insulation level of complete string
kVp
9.11
Minimum wet switching surge withstand level
of complete string
kVp
9.12
Radio influence voltage measured at 1.1
times Us/√3 at 1 MHz
µv
Offered
D2.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D2 – 400 KV OPEN TERMINAL SWITCHGEAR – Cont
Unit
Data
Required
10
400 KV LINE TRAPS
10.1
Maker's type and designation
10.2
Main coil insulation – class
10.3
Rated continuous current
A
10.4
Rated short time current (1 second/3
seconds)
kA
10.5
Power frequency
10.6
Insulating level across line traps at:
10.6.1
Power frequency
10.6.2
Impulse
10.7
Rated voltage level of protective device
kV
10.8
Centre frequency
kHz
10.9
Bank width of blocking range
kHz
10.10
Self resonant frequency
kHz
10.11
Tapping loss
10.12
Blocking impedance
Ω
10.13
Total mass
kg
Offered
db
D2.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR
Unit
Data
Required
1
GENERAL
1.1
Manufacturer & Place of manufacturing
1.2
Type designation
1.3
Type
1.4
Standards
1.5
GIS
Metal enclosed,
gas insulated GISindoor
IEC
IEC 62271 - 203,
60694, 60270,
60376, 60480
Rated voltage
kV
145
1.6
System Voltage
kV
132
1.7
Rated frequency
Hz
50
1.8
Rated lightning impulse withstand voltage
kVp
kVp
650
750
kV
kV
kV
275
315
1.1 U phase
1.9
Offered
Phase to earth
Across the isolating distance
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
Phase to earth at SF6 pressure of 1 bar
1.10
Rated short-time withstand current (1 s)
kA
40
1.11
Rated peak withstand current
kA
80
1.12
Type of busbars
1.13
Type of enclosure
1.14
Material of enclosure for:
Double
Single/Three
phase enclosed
Circuit breaker
Busbars
Other compartments
Al/St
Al/St
Al/St
1.15
Material of HV conductor
Al/Cu
1.16
Material of contacts (indicate bi-metallic where
used)
-
D3.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
1.17
Type of contact
1.18
Minimum subdivision of switchgear:
-
1.19
Busbars
Busbar isolator
Circuit breaker
Circuit isolator
Cable box
Voltage transformer
Yes
Yes
For busbars
For enclosure
1.20
Type of pressure relief device
1.21
Rupturing pressure
1.22
Type of filter employed for moisture absorption
1.23
Design lifetime of moisture absorbent
1.24
Total mass of switchgear (average per bay)
kg
1.25
Mass of heaviest single component to be handled
during erection
kg
1.26
Total mass of SF6 gas (average per bay)
kg
1.27
Density of gas in:
-
bar
Circuit breaker compartment
Other than circuit breaker compartments
Molecular Sieve
Years
10
(g/l)
(g/l)
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
Nominal working gas pressure at 50oC in:
-
1.30
Bursting disk
Nominal working gas pressure at 15oC in:
-
1.29
Offered
Method of compensation of expansion and
contraction
-
1.28
Data
Required
Tulip
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
Design maximum pressure for:
-
Circuit breaker compartment
Other than circuit breaker compartment
bar
bar
D3.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
1.31
Maximum leakage rate for any gas compartment
per
annum
1.32
Maximum leakage rate for the whole switchgear
1.33
Minimum operating period without total
replacement of SF6 gas
per
annum
years
1.34
Minimum thickness of enclosure
mm
1.35
Minimum enclosure puncturing time due to internal
arc fault at short-time withstand current
ms
1.36
Minimum factors of safety for switchgear
-
-
Busbars or other connections based on elastic
limit
Complete insulators based on electromechanical test
Insulator metal fittings based on elastic limit
Steel structures based on elastic limit of
tension members and on crippling loads of
compression members
Foundations for structures against overturning
or uprooting under maximum simultaneous
working loadings
1.37
Seismic factor
2
CIRCUIT BREAKER
2.1
Manufacturer & Place of manufacturing
2.2
Type designation
2.3
Type
2.4
Standards
2.5
Rated voltage
2.6a
Rated Current – Busbars, Bus Section and Bus
Coupler
-
Data
Required
Less than 1%
Offered
Less than 1%
10
Greater than 500
2.5
2.5
2.5
2.5
2.5
Single pressure
puffer, SF6
IEC 62271 - 203,
IEC 62271-100,
61233, 60694,
60427, 60376,
60480
at 50 0C (Contractor to confirm by calculation)
kV
132
A
3150
D3.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
2.6b
2.6c
at 50 0C (Contractor to confirm by calculation)
A
1600
A
1600
Hz
50
kVp
kVp
650
750
kV
kV
275
315
Rated Current – Incoming Feeder
-
at 50 0C (Contractor to confirm by calculation)
2.7
Rated frequency
2.8
Rated lightning impulse withstand voltage
-
2.9
Offered
Rated Current – Transformer/Transformer Feeder
Phase to earth
Across the isolating distance
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
2.10
Rated short-time withstand current (1 s)
kA
40
2.11
Rated peak withstand current
kAp
80
2.12
Rated operating sequence
2.13
Auto reclosing
2.14
Rated making current
kAp
O -0.3 sec- CO -3
min - CO
O -0.3 sec- CO -3
min - CO
80
2.16
Rated breaking current (asymmetrical)
kA
To IEC 62271-100
-
%dc
%dc
2.17
Rated breaking current under out-of-phase
conditions
2.18
First phase to clear factor
2.18a
Transient Recovery Voltages
2.19
Rated capacitive breaking current
Rated line charging breaking current
Rated cable charging breaking current
Rated Single/Back to Back Capacitor bank
breaking current
kA
1.3
TRVs
To IEC 62271-100
To IEC 62271-100
A
A
A
D3.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
2.20
Rated small inductive/reactor breaking currents of:
-
small inductive
reactor
Data
Required
To IEC 62771-110
A
A
2.21
Maximum overvoltage factor on any switching duty
pu
2.5
2.22
Maximum overvoltage factor when interrupting
rated line/cable/capacitor bank charging currents
pu
2.5
2.23
Maximum overvoltage factor when switching small
inductive/reactor currents
pu
2.5
2.24
Maximum total break time (trip initiation to final arc
extinction)
ms
60
2.25
Opening time (trip initiation to contact separation)
-
Without current
With 100% rated breaking current
2.26
Maximum time interval between opening of first
and last phase of three phase circuit breakers
2.27
Maximum time interval between opening of
interrupters of one phase
2.28
Closing time from energisation of close coil to
latching of circuit breaker in fully closed position
2.29
Making time (energisation of close coil to contact
touch)
-
Offered
Without current
100% making current
ms
ms
ms
3
-
-
-
ms
ms
ms
2.30
Maximum time interval between closure of first
and last phase of three phase circuit breaker
2.31
Maximum time interval between closure of
interrupters of one phase
2.32
Minimum time from extinction of main arc to
contact make during auto-reclosing duty
2.33
Mechanical life of circuit breaker and mechanism
in No. of operations
ms
3
-
-
ms
300
-
10,000
D3.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
2.34
Offered
Electrical contact life in number of operations at:
-
Rated current - 3150A/1600A
Fault current - 40 kA
Cumulative ampere rating
15 to 20
2.35
Number of current interrupting break units in
series per phase
2.36
Type of operating mechanism
2.37
Type of power device (motor changed)
-
For closing
-
For opening
one
Spring-charged or
hydraulic
2.38
Hand operating facility
Spring or
hydraulic
Spring or
hydraulic
yes
2.39
Hand charging facility
yes
2.40
Manual spring release
yes
2.41
Mechanical on/off indicator
yes
2.42
Mechanical spring charge / discharge indication
yes
2.43
Charging time
2.44
Number of trip coils
2
2.45
Number of close coils
1
2.46
Nominal control and operating voltage
V
110 DC
2.47
Nominal heater voltage
V
220 AC
2.48
Rated power of trip coil
W
2.49
Rated power of close coil
W
2.50
Rated motor power
W
2.51
Total load of heaters for circuit breaker
W
2.52
Mass of circuit breaker complete (three pole)
kg
2.53
Mass of single phase circuit breaker
s
-
-
-
D3.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
2.54
Emergency Trip Facility during failure of DC
supply
3
DISCONNECTS
3.1
Manufacturer & Place of Manufacturing
3.2
Type designation
3.3
Type of operating mechanism
3.4
Standards
3.5
Rated voltage
3.6
Rated current at 50oC
(Contractor to confirm by calculation)
-
IEC 62271-102,
IEC 60694,
61128, 62271 203, 60265
Busbars, Bus Section and Bus Coupler
Circuits
Rated frequency
3.8
Rated lightning impulse withstand voltage
3.9
Offered
Motor
3.7
-
Data
Required
yes
Phase to earth
Across the isolating distance
kV
145
A
A
3150
1600
Hz
50
kVp
kVp
650
750
kV
kV
275
315
Rated power frequency withstand voltage
-
Phase to earth
Across the isolating distance
3.10
Rated short time withstand current (1 s)
kA
40
3.11
Rated peak withstand current
kAp
80
3 .12
Maximum capacitive current that can be
interrupted by the isolator
A
3.13
Total time from initiation of opening operation to
isolator in fully open position
s
3.14
Time from contact separation to extinct of
capacitive arc
s
D3.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
3.15
Total time from initiation of opening operation to
time when isolator gap can withstand phase
voltage
3.16
Hand operating facility
yes
3.17
Locking arrangement in on/off position
yes
3.18
Nominal control and operating voltage
3.19
Automatic isolation of control supplies when lock
off
yes
3.20
Accessibility to operating mechanism from ground
level or catwalk
yes
3.21
Nominal heater voltage
V
3.22
Rated power of operation coil
W
3.23
Rated motor power
W
3.24
Total load of heaters for isolator
W
3.25
Total mass of three phase isolator complete
kg
3.26
Mass of single phase isolator
kg
3.27
Contact type
4
EARTHING SWITCH
4.1
Manufacturer & place of manufacturing
4.2
Type designation
4.3
Type of operating mechanism
4.4
Standards
4.5
Rated voltage
kV
145
4.6
Rated frequency
Hz
50
4.7
Rated lightning impulse withstand voltage phase
to earth
kVp
650
4.8
Rated power frequency withstand voltage phase
to earth
kV
275
Offered
s
V
110 DC
220 AC
Tulip
Motor
IEC 62271-102,
IEC 60694, 62271
- 203
D3.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
4.9
Rated short time withstand current (1 s)
kA
Required
40
4.10
Rated peak withstand current
kA
80
4.11
Hand operating facility
yes
4.12
Locking arrangement in on/off position
yes
4.13
Nominal control and operating voltage
4.14
Automatic isolation of control supplies when lock
off
yes
4.15
Accessibility to operating mechanism from ground
level or catwalk
yes
4.16
Nominal heater voltage
V
4.17
Rated power of operating coil
W
4.18
Rated motor power
W
4.19
Total load of heaters for earthing switch
W
4.20
Total mass of earthing switch complete
kg
5
HIGH SPEED EARTHING SWITCH
5.1
Manufacturer & place of manufacturing
5.2
Type designation
5.3
Type of operating mechanism
5.4
Standards
5.5
Rated voltage
kV
145
5.6
Rated frequency
Hz
50
5.7
Rated lightning impulse withstand voltage phase
to earth
kVp
650
5.8
Rated power frequency withstand voltage phase
to earth
kV
275
V
Offered
110 DC
220 AC
Motor-spring
IEC 62271-102,
IEC 60694,
61129, 62271 203
D3.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
5.9
Rated short time withstand current (1 s)
kA
Required
40
5.10
Rated peak withstand current
kAp
80
5.11
Rated short-circuit making current
kAp
80
5.12
Rated capacitive symmetrical breaking current
A
5.13
Rated inductive symmetrical breaking current
A
5.14
Total time from initiation of opening operation to
earth switch in fully open position
ms
5.15
Time from contact separation to extinction of arc
when interrupting rated breaking current
ms
5.16
Making time
ms
5.17
Charging time
5.18
Hand operating facility
yes
5.19
Locking arrangement in on/off position
yes
5.20
Nominal control and operating voltage
5.21
Automatic isolation of control supplies when lock
off
yes
5.22
Accessibility to operating mechanism from ground
level or catwalk
yes
5.23
Nominal heater voltage
V
5.24
Rated power of operation coil
W
5.25
Rated motor power
W
5.26
Total load of heaters for earthing switch
W
5.27
Total mass of earthing switch complete
kg
6
CURRENT TRANSFORMER
6.1
Manufacturer & place of manufacturing
6.2
Type
6.3
Standards
Offered
s
V d.c.
110
220 AC
Toroidal, GIS
enclosed
IEC 60694,
60044-1
D3.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
6.4
GIS
Cores
6.5
kV
V
145
720
kVp
kVp
650
kV
kV
kV
275
3 kV (EK < 2 kV)
5 kV (EK ≥ 2 kV)
Rated lightning impulse withstand voltage phase
to earth
GIS
Cores
6.6
Offered
Rated voltage
Rated power frequency withstand voltage phase
to earth
GIS
Cores
6.7
Rated power frequency between secondaries
6.8
Inter-turn test
3 kV
M/P type
Class PX
4.5 kV peak
To IEC 60044-1
6.9
Rated frequency
6.10
Rated continuous thermal current at 50oC
6.11
Rated short-time withstand current (1 s)
kA
40
6.12
Rated dynamic current
kAp
80
6.13
Are earthed metal screens fitted between primary
and secondary windings
6.14
Is current transformer housed in a separate gas
compartment
6.15
Transformer bays current transformer:
-
Hz
Rated extended
primary current
To suit specific
Number of cores
Rated extended primary current
Ratio (TR = turns ratio)
•
•
•
•
•
50
arrangement
I core
II core
III core
IV core
V core
A
A
A
A
A
D3.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS – CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR – Cont
Unit
Data
Required
-
•
•
•
•
•
-
mA
mA
mA
mA
mA
I core
II core
III core
IV core
V core
VA
VA
VA
VA
VA
To suit specific
Number of cores
Rated extended primary current
Ratio (TR = turns ratio)
Knee point voltage (Ek)
arrangement
Bus Section & Bus Coupler CT No.1
-
6.18
I core
II core
III core
IV core
V core
Line bays current transformer
-
6.17
V
V
V
V
V
Rated output (Burden to be 25-100% rated
burden)
•
•
•
•
•
6.16
I core
II core
III core
IV core
V core
Exciting current (IE ) at Ek
•
•
•
•
•
-
I core
II core
III core
IV core
V core
Knee point voltage (Ek)
•
•
•
•
•
-
To suit specific
Number of cores
Rated extended primary current
Ratio (TR = turns ratio)
arrangement
Bus Section & Bus Coupler CT No. 2 (at the other
side of circuit breaker)
-
Offered
Class
Number of cores
To suit specific
arrangement
D3.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
7
VOLTAGE TRANSFORMERS
7.1
Manufacturer & Place of manufacturing
7.2
Type designation for
-
Line transformer – 3 phase
Busbar transformer – 3 phase
7.3
Type
7.4
Standards
7.5
Rated voltage
kV
Inductive, SF6 gas
insulated,
enclosed
IEC 60186,60694,
62271 - 203,
60044-2
145
7.6
Rated frequency
Hz
50
7.7
Rated lightning impulse phase to earth
kVp
650
7.8
Rated power frequency withstand voltage phase
to earth
kV
275
7.9
Maximum permissible partial discharge level
Um
pC
10
7.10
Maximum permissible partial discharge level
1.2Um /√3
pC
5
7.11
Maximum capacitive current discharge rating
A
TBA
7.12
Method of suppressing ferroresonance
phenomena
7.13
Line bay voltage transformer
-
Offered
Rated extended primary current
Ratio (TR = turns ratio)
Number of secondaries
Rated transformation ratio
Rated accuracy class
kV
• I secondary
• II secondary
-
Rated output
• I secondary
• II secondary
VA
VA
D3.13
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
7.14
Mass of single/three phase voltage
transformer
Offered
kg
Busbar voltage transformer
-
Number of secondaries
Rated transformation ratio
Rated accuracy class
kV
• I secondary
-
Rated output (Burden to be 25-100% rated
burden)
VA
• I secondary
-
Mass of single/three phase voltage
transformer
8
SURGE ARRESTERS
8.1
Type
8.2
Standard
8.3
Rated/system voltage
-
kg
IEC 60099-4,
60099-1 60099-5,
60694
Maximum overvoltage factor on the system
due to any switching duty
kV
145/132
pu
2.5
Hz
50
8.4
Rated system frequency
8.5
Condition of system neutral
8.6
Nominal Discharge current
kA crest
8.7
Energy capability as per IEC 60099-4
kJ/ kV
8.8
Rated voltage - MOA
8.9
Long duration discharge class as per IEC 60099-4
Class
8.10
Maximum Continuous Operating Voltage (COV)
kV
8.11
TOV capability for
-
Solid
kV
kV
kV
1 sec
10 sec
D3.14
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
Data
Required
8.12
8.14
kV
kV
kV
Switching Surges - 1kA / 2kA
8/20 μs - 5kA
8/20 μs - 10kA
Discharge current withstand strength
-
8.15
Offered
Maximum residual voltage with current wave
High current (4/10 μs)
Low current 2000A
KAp
Ap
Pressure relief capability
High current (0.2 s)
Low current
kA
8.16
Rating of earth connections
kA/sec
8.17
Surge counter provided
9
CABLE BOX
9.1
Manufacturer & Place of manufacturing
9.2
Type of designation
9.3
Standards
9.4
Rated voltage
kV
145
9.5
Rated lightning impulse withstand voltage phase
to earth
kVp
650
9.6
Rated power frequency withstand voltage phase
to earth
kV
275
9.7
Cable HV test withstand capability
kV
9.8
Rated frequency
Hz
9.9
Rated normal current at 40oC
A
9.10
Required current at 50oC (Contractor to confirm by
calculation)
A
9.11
Rated short time withstand current (1s)
kA
40
9.12
Rated peak withstand current
kA
80
9.13
Total mass of three phase cable box complete
kg
-
As per IEC
40/1
Yes
IEC 60859
50
D3.15
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D3 – 132 KV GAS INSULATED SWITCHGEAR - Cont
Unit
10
MANUFACTURER QUALITY SYSTEM IN
ACCORDANCE TO ISO 9000, 9001, 9002, 9003
AND 9004
10.1
Date of issue
10.2
Validity
11
TYPE TEST CERTIFICATE TO BE ISSUED BY
INDEPENDENT LABORATORY OR
INDEPENDENTLY WITNESSED TYPE TEST
CERTIFICATE TO BE SUBMITTED
Data
Required
Yes
Offered
Latest
Valid Certificates
–Yes
Yes
D3.16
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR
Unit
Data
Required
1
GENERAL
1.1
Standards
1.2
IEC
IEC 62271-100,
62271-102, 60694,
60233, 60044,
60186, 60383,
60815
Rated voltage
kV
145
1.3
System Voltage
kV
132
1.4
Rated frequency
Hz
50
1.5
Rated lightning impulse withstand voltage
kVp
kVp
650
750
Phase to earth
Across the isolating distance
kV
kV
275
315
1.7
Rated short-time withstand current (1 s)
kA
40
1.8
Rated peak withstand current
kA
62.5
1.9
Rated Current – Cable Feeder
at 50 oC (Contractor to confirm by calculation)
A
1600 (or to suit)
Phase to earth
Across the isolating distance
1.6
Offered
Rated power frequency withstand voltage
1.10
Material of HV conductor
Aluminium
1.11
Material of contacts
Bi-metallic
1.12
Minimum factors of safety for switchgear
Busbars or other connections based on
elastic limit
2.5
Complete insulators based on electromechanical test
2.5
Insulator metal fittings based on elastic limit
2.5
Steel structures based on elastic limit of
tension members and on crippling loads of
compression members
2.5
Foundations for structures against
overturning or uprooting under maximum
simultaneous working loadings
2.5
D4.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
1.13
Creepage distance (based on Um)
1.14
Seismic factor
mm/ kV
Data
Required
31
Offered
UBC Zone 3
D4.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
2
CAPACITIVE VOLTAGE TRANSFORMERS
2.1
Type
2.2
Standards
2.3
Maximum permissible partial discharge level
Um
pC
10
2.4
Maximum permissible partial discharge level
1.2Um /√3
pC
5
2.5
Method of suppressing ferroresonance
phenomena
2.6
Line voltage transformer
2.7
Number of secondaries
Offered
Capacitive
IEC 60186,
IEC/PAS 600445:2002
2
Rated transformation ratio
kV
132/√3 /
0.11/√3 /0.11/√3
Rated accuracy class
3P/1.0
3P
I secondary
II secondary
Rated output (burden to be 25-100% rated
burden)
I secondary
II secondary
VA
VA
Mass of single phase voltage transformer
kg
D4.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
3
BUSBARS AND CONNECTIONS
3.1
Type (flexible or tubular)
3.2
Material
3.3
Short-circuit current rating / duration
3.4
Normal current rating
kA/s
Offered
40/1
A
at 40oC
at 50 oC
A
3.5
Maximum continuous current rating
A
3.6
Flexible conductors
stranding
nominal cross-sectional area
outer diameter
no. of conductors per bundle
spacing between conductors
1600
mm2
mm
mm
3.7
Tubular conductors
nominal cross-sectional area
outer diameter
inner diameter
3.8
Maximum stress at surface of flexible
conductor
3.9
Radio influence voltage level measured at 1.1
times Us/√3 at 1 MHz
mm2
mm
mm
kV/mm
µV
D4.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
4
POST TYPE INSULATORS
4.1
Type designation
4.2
Insulator material
4.3
Number of units in complete post insulator
4.4
Length of each unit
4.5
Mass of complete post insulator
kg
4.6
Maximum cantilever working load (complete
post insulator)
N
4.7
Minimum cantilever breaking load, upright
(complete post insulator)
N
4.8
Power frequency withstand voltage dry: wet
kV
4.9
Basic insulation level
kVp
4.10
Minimum dry/wet switching surge withstand
level
kVp
4.11
Radio influence voltage level measured at 1.1
times Us/√3 at 1 MHz
µv
Offered
mm
D4.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
5
TENSION AND SUSPENSION
INSULATORS
5.1
Type designation
5.2
Insulator material
5.3
Number of units in string
mm
5.4
Greatest diameter of units
mm
5.5
Distance between centres of units
mm
5.6
Length of string, overall
mm
5.7
Mass of string complete with all fittings
kg
5.8
Maximum working load
N
5.9
Power frequency withstand voltage of
complete string
kV
5.10
Basic insulation level of complete string
kVp
5.11
Minimum wet switching surge withstand level
of complete string
kVp
5.12
Radio influence voltage measured at 1.1
times Us/√3 at 1 MHz
µv
Offered
D4.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D4 – 132 KV OPEN TERMINAL SWITCHGEAR - Cont
Unit
Data
Required
6
LINE TRAPS
6.1
Maker's type and designation
6.2
Main coil insulation – class
6.3
Read continuous current
6.4
Rated short time current (1 second/3
seconds) kA
6.5
Inductance at 50 Hz
6.6
Insulating level across line traps at:
6.7
Power frequency
6.8
Impulse
6.9
Rated voltage level of protective device
kV
6.10
Centre frequency
kHz
6.11
Bank width of blocking range
kHz
6.12
Self resonant frequency
kHz
6.13
Tapping loss
db
6.14
Blocking impedance
Ω
6.15
Total mass
kg
Offered
A
mH
D4.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR
Unit
1
GENERAL
1.1
Manufacturer & Place of Manufacturing
1.2
Type designation
1.3
Type of Switchgear
1.4
Standards
1.5
Number of years equipment of identical design has
been in service
1.6
Rated voltage
1.7
Rated normal current
Data
Required
Metal clad - air
insulated, indoor
switchgear with
Vacuum Circuit
Breaker
IEC 60298,
62271-100,
60694, 60529
Years
kV
12
At 50oC (contractor to confirm by calculation)
−
Incoming bay, busbar & bus-section bay
−
Outgoing bay
A
A
4000
1600/600 to suit
1.8
Rated frequency
Hz
50
1.9
Rated lightning impulse withstand voltage
1.10
Offered
−
Phase to earth
kV
95
−
Across the isolating distance
KV
110
KV
KV
38
45
Rated power frequency withstand voltage
−
−
Phase to earth
Across the isolating distance
1.11
Partial discharge test voltage
KV
IEC 60270
1.12
Rated short-time withstand current (1s)
KA
50
1.13
Rated peak withstand current
KA
125
D5.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
1.14
Type of busbars
1.15
Method of earthing
−
−
Minimum subdivision of cubicles at compartments
1.17
Are busbars segregated
Between phases
Between cubicles
Busbar/ CTs/
Circuit Breaker/
Cable/ VTs/Relay
compartment
Yes
Yes
1.18
Material of cover
Metallic
1.19
Material of partitions
Metallic
1.20
Material of shutters
Metallic/Earthed
1.21
Busbars and joints fully encapsulated
Yes
1.22
Busbar and feeder shutters lockable with individual
manual and automatic features
Yes
1.23
Offered
Busbars side
Line side
1.16
−
−
Data
Required
Single
Protection class
−
−
−
−
−
−
General
Busbars, cable compartment, internal partitions
Circuit breaker compartment
• Door closed
• Door open
LV compartment
Shutters and spouts
Pressure relief device/flaps
1.24
The way of securing (opening/closing of doors)
1.25
Material of HV conductor
1.26
Material of contacts
1.27
Type of pressure relief device
1.28
Method of personnel protection in case of operation
of pressure relief device
IP41
IP3XD
IP41
IPXX
IP41
IP4X
IP 5X
Hinged doors
Copper
Silver-plated
copper
D5.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
1.29
Total mass of switchgear (average per bay)
1.30
Minimum factors of safety for switchgear (minimum
2.5)
−
−
−
−
−
Data
Required
Offered
kg
Busbars or other connection based on elastic
limit
Complete insulators based on electromechanical test
Insulator metal fittings based on elastic limit
Steel structures based on elastic limit of tension
members and on crippling loads of compression
members
Foundations for structures against overturning or
uprooting under maximum simultaneous working
loading
2.5
2.5
2.5
2.5
2.5
1.31
Manufacturer quality assurance according to
ISO 9000, 9001, 9002, 9003 and 9004
Yes
1.32
Type test certificate to be issued by Independent
laboratory or independently witnessed type test
certificate available
Yes
1.33
Emergency manual trip facility (during failure of DC
supply)
Yes
2
CIRCUIT BREAKER
2.1
Manufacturer & Place of manufacturing
2.2
Type designation
2.3
Type
2.4
Fully encapsulated
2.5
Standards
2.6
Rated voltage
kV
2.7
Rated normal current at 40oC (Incomer/bus section;
Feeder)
A
2.8
Required current at 50oC (Incomer/bus section;
Feeder)
(Contractor to confirm by calculation)
A
Vacuum, Truck
mounted,
withdrawable
Yes
IEC 60298,
62271-100,
60694, 60427
12
4000/1600/630
D5.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
2.9
Rated frequency
2.10
Rated lightning impulse withstand voltage
−
−
2.11
Hz
Phase to earth
Across the isolating distance
Data
Required
50
kVp
kVp
95
110
kV
kV
38
45
Offered
Rated power frequency withstand voltage
−
−
Phase to earth
Across the isolating distance
2.12
Rated short-time withstand current (1 s)
kA
50
2.13
Rated peak withstand current
kAp
125
2.14
Rated operating sequence
2.15
Rated making current
kA
125
2.16
Rated breaking current (symmetrical)
kA
50
2.17
Rated breaking current (asymmetrical)
kA
To IEC 62271100
2.18
Rated breaking current under out of phase conditions
kA
2.19
First pole to clear factor
2.20
Rated line charging breaking current
A
2.21
Rated cable charging breaking current
A
2.22
Rated small inductive breaking current of
O-0.3 sec - CO - 3 min - CO
A
-
unloaded transformer
reactor
2.23
Maximum overvoltage factor on any switching duty
2.24
If the Overvoltage factor above, is in excess of 2.5 pu,
then detail steps taken to protect the system from
overstressing, by the use of suitable Metal-Oxide
surge arresters
2.25
Maximum peak value of switching overvoltage when
interrupting capacitive currents
2.26
Maximum peak value of switching over-voltage when
interrupting low inductive and reactor currents
pu
<2.5
kV
kV
D5.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
2.27
Maximum total break time (trip initiation to final arc
extinction)
2.28
Opening time (trip initiation to contact separation)
−
−
2.29
Without current
With 100% rated breaking current
Maximum time interval between opening of first and
last phase of three phase circuit breakers
2.30
Closing time from energisation of close coil to latching
of circuit breaker in fully closed position
2.31
Making time (energisation of close coil to contact
touch)
−
−
ms
Data
Required
60
ms
ms
ms
3
ms
ms
ms
Without current
With 100% rated current
2.32
Maximum time interval between closure of first and
last phase of three phase circuit breaker
ms
3
2.34
Mechanical life of CB and Mechanism in number of
operations
min
5000
2.35
Electrical contact life at rated current in No. of
operations
2.36
Electrical contact life at 100% fault current in No. of
operations
10
2.37
Internal arcing tests in the switchgear enclosure to
IEC 60298 – Annex AA
Adjacent
compartments
are not affected
2.38
Mechanical means for withdrawal
2.39
Type of operating mechanism
2.40
Manual spring discharge facility
Yes
2.41
Interlock facilities complying with requirements of
specification
Yes
2.42
Type of power device
−
−
2.43
Offered
yes
3 pole
For closing
For opening
Motor-Spring
Spring
Hand charging facility
Yes
D5.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
Data
Required
2.44
Charging time
2.45
Number of trip coils
1
2.46
Number of close coils
1
2.47
Nominal control and operating voltage
V
110 DC
2.48
Nominal heater voltage
V
220
2.49
Rated power of trip coil
W
2.50
Rated power of close coil
W
2.51
Rated motor power
W
2.52
Does earthing of truck remain effective until fully
withdrawn
2.53
Total load of heaters for circuit breaker
W
2.54
Mass of circuit breaker complete (three pole set)
kg
2.55
Partial discharge test voltage
kV
2.56
Manufacturer quality assurance according to ISO
9000, 9001, 9002, 9003 and 9004
Yes
2.57
Type test certificate to be issued by independent
laboratory or independently witnessed type test
certificate available
Yes
3
BUSBARS
3.1
Rated current at 50oC
−
−
Manufacturer’s Standard
Corresponding site rating
3.2
Maximum temperature rise
3.3
Cross Section
3.4
Material of barriers between units
3.5
Insulation of Busbars:
−
−
Offered
S
Yes
IEC 60270
A
A
o
C
mm2
Material
Maximum working temperature
o
C
D5.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
3.6
Type test certificate to be issued by independent
laboratory or independently witnessed type test
certificate available
4
EARTHING SWITCH
4.1
Manufacturer & Place of Manufacturing
−
−
4.2
Data
Required
Yes
at busbar side
at line side
Type designation
−
−
at busbar side
at line side
4.3
Type of operating mechanism
4.4
Standards
4.5
Rated voltage
kV
12
4.6
Rated frequency
Hz
50
4.7
Rated lightning impulse withstand voltage phase to
earth
kV
95
4.8
Rated power frequency withstand voltage phase to
earth
kV
38
4.9
Rated short time (1 s) current
kA
50
4.10
Peak Current
kAp
125
4.11
Total mass of three phase complete earthing switch
−
−
4.12
4.14
Manual
IEC 62271-102
kg
kg
at busbar side
at line side
Type of contacts
−
−
4.13
Offered
Moving
Fixed
Copper
Copper
Moving contacts are directly connected to earthing
system via copper connectors
Yes
Continuous running earth bar has been provided
Yes
D5.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
Data
Required
5
CURRENT TRANSFORMER
5.1
Manufacturer & Place of manufacturing
5.2
Type
5.3
Type of primary winding (e.g. bar, wound, etc.)
5.4
Standards
5.5
Rated voltage
kV
12
5.6
Rated lightning impulse withstand voltage phase to
earth
kV
95
5.7
Rated power frequency withstand voltage phase to
earth
kV
38
5.8
Partial discharge test voltage
kV
IEC 60270
5.9
Rated frequency
Hz
50
5.10
Rated continuous thermal current at 50oC
5.11
Rated short-time withstand current (1 s)
kA
50
5.12
Rated dynamic current
kA
125
5.13
Are earthed metal screens fitted between primary and
secondary windings
5.14
Details of all current transformers are to be provided
by the Contractor after contract award
-
Offered
Cast-resin multicore, multi-ratio
indoor
IEC 60044-1
Rated extended
primary current
Type designation
Number of cores
Rated extended primary current in percentage of
rated primary current
Ratio (TR – turns ratio)
•
•
•
I core
II core
III core
A
A
A
D5.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D5 - 11 KV (TERTIARY) METALCLAD SWITCHGEAR - Cont
Unit
6
VOLTAGE TRANSFORMERS (3-phase sets to be
provided)
6.1
Manufacturer & Place of manufacturing
6.2
Type designation for
−
−
−
Data
Required
Offered
Line transformer
Busbar transformer
Power transformer bay
6.3
Type
6.4
Standards
Inductive cast resin single pole
insulated
IEC 60044-2
6.5
Rated voltage
kV
12
6.6
Rated frequency
Hz
50
6.7
Rated lightning impulse phase to earth
kV
95
6.8
Rated power frequency withstand voltage phase to
earth
kV
38
6.9
Partial discharge test voltage
kV
IEC 60270
6.10
Type of primary isolation
6.11
Line voltage transformer & Busbar Voltage
Transformer
−
−
−
−
−
Drawout
Number of secondaries
Rated transformation ratio
Rated accuracy class
Rated output
Total mass of three phase voltage transformer
complete
kV
VA
kg
7
Manufacturer quality system in accordance with ISO
9000, 9001, 9002, 9003 and 9004
Yes
8
Type test certificate to be issued by independent
laboratory or independently witnessed type test
certificate available.
Yes
D5.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D6 - CRANE FOR GIS BUILDING
Unit
1
Manufacturer
2
Type
3
Capacity
4
Test load, dynamic
5
Operating speed:
-
6
%
Hoist
Trolley travel
Bridge travel
M/min
M/min
M/min
Voltage
Frequency
V
Hz
380/220
50
Span
Length of runway
Total lift of hook
m
m
m
Crane drive motors
-
9
t
Dimensions
-
8
Overhead
travelling
Operating power source and terminal voltage
-
7
Data
Required
Offered
Manufacturer
Type
Trolley drive motors
-
Manufacturer
Type
10
Operator/Maintenance cage provided with trolley
yes
11
Enclosed current collector
yes
12
Hoist
-
Manufacturer
Type
Type of control
13
Total required power
14
Weights
-
Pendant or
infrared
kW
Bridge complete
Trolley complete
Runway complete
t
t
t
D6.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D6 - CRANE FOR GIS BUILDING - CONT
Unit
15
Reference Standards
16
Manufacturer's Quality Assurance
17
Type Test Certificates (to be issued by independent
laboratory or independently witnessed type test
certificate)
Data
Required
Offered
BS 466, 2573
ISO 9000 to
9004
yes
D6.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS
Item
No
1
Description
Unit
Data
Description of transformers
2
Type of transformers:
2.1
Indoor or outdoor
2.2
Shell or core
2.3
Auto or separate windings
2.4
Three phase or single phase units
2.5
Cooling (IEC letter symbols)
3
Site Conditions
3.1
Altitude above sea level
m
Less than 1000m
3.2
Air temperature minimum
°C
-10
3.3
Air temperature maximum
°C
+55
4
IEC ratio power at terminals of:
4.1
HV winding
MVA
250
4.2
LV winding
4.3
Tertiary winding
5
Continuous maximum ratings at
winding terminals according to
tapping position when operating
under site conditions:
5.1
Required
Transmission
autotransformer
Provided
Outdoor
Auto
Single
ONAF1/ANAFZ/ANAN
250
MVA
75
HV winding
MVA
250
5.2
LV winding
MVA
250
5.3
Tertiary winding
MVA
75
6
Maximum ONAN and ONAF ratings
of winding terminals irrespective of
tapping position, when operating
under site conditions
6.1
ONAN ratings:
6.1.1
HV winding
MVA
150
6.1.2
LV winding
MVA
150
D7.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
6.1.3
Description
Unit
Tertiary winding
6.2
ONAF2 ratings:
6.2.1
HV winding
MVA
6.2.2
LV winding
MVA
6.2.3
Tertiary winding
MVA
7
Rated voltage corresponding to
principal tapping
7.1
HV
kV
400
7.2
LV
kV
138.6
7.3
Tertiary
kV
11
8
System highest voltage:
8.1
HV
kV
420
8.2
LV
kV
145
8.3
Tertiary
kV
12
9
Method of system earthing
9.1
HV system
Solid
9.2
LV system
Solid
9.3
Tertiary system
10
Method of earthing of transformers
10.1
HV winding
Solid
10.2
LV winding
Solid
10.3
Tertiary winding
11
Rated frequency
12
Rated lighting impulse withstand
level
12.1
MVA
Data
Required
45
Provided
Earthing transformer
Earthing transformer
Hz
50
HV winding
kVp
1300
12.2
LV winding
kVp
550
12.3
Tertiary winding
kVp
125
D7.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
13
Description
Unit
Switching impulse withstand level
13.1
HV winding
kVp
1050
13.2
LV winding
kVp
-
13.3
Tertiary winding
kVp
-
14
Maximum system symmetrical rms
fault current (1 phase or 3 phase) at
the terminals of the transformer
which the windings must be capable
of withstanding
14.1
HV terminals
kA
40
14.2
LV terminals
kA
40
14.3
Tertiary terminals
kA
50
14.4
Asymmetrical crest factor
15
Phase connections
15.1
IEC vector group symbols
15.2
Whether links are required for
alternative IEC vector group
15.3
Alternative vector group required
16
Windings
16.1
Common winding
Graded
16.2
Series winding
Graded
17
Whether one winding is a stabilising
winding only
Provided
2.55
YNyn0d11
No
-
No
-
If so, whether the winding is to be
brought out to If so, whether the
winding is to be brought out to
separate bushing insulator(s) or
cable box terminals for test
purposes
(For earthing see Item 10)
18
Data
Required
Whether `on-load' or `off-circuit' tap
changing equipment or links are
required
On load
D7.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
19
Description
Unit
Data
Required
Provided
Tapping quantities transformer
designation
HV
LV
19.1
Minimum voltage ratio
366.6
145.2
19.2
Maximum current tapping (HV)
382.6
145.2
19.3
Maximum current tapping (LV)
400
125.4
19.4
Principal tapping
400
138.6
19.5
Maximum voltage tapping (LV)
400
145.2
19.6
Maximum voltage ratio
400
118.8
See note below
220
Tapping steps:
20.1
Approximate size
20.2
Approximate number
21
Excess of continuously applied
voltage over tapping voltage for any
tapping when transformer is
delivering tapping power
%
1
20
5%
22
Whether tappings are preferred on
any particular winding
22.1
On common winding
22.2
IEC category of voltage variation
22.3
On series winding
22.4
IEC category of voltage variation
22.5
On Tertiary winding
22.6
IEC category of voltage variation
-
23
Whether on-load tap changing
equipment shall be suitable for
supervisory control and indication
Yes
24
Remote tap change control panel
Yes
CFVV
No
No
D7.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
24.1
Whether required
24.2
Exterior finish
25
Automatic voltage control
equipment
25.1
Whether required
Yes
25.2
Whether to be suitable for remote
adjustment of setting
Yes
26
Whether equipment shall be
provided to permit automatic
synchronised operation of on-load
tap changing equipment in parallel
with similar transformers
Yes
27
Whether gas and oil actuated relay
shall be fitted to each tap selector
compartment
Yes
28
Bushing insulators or cable boxes
for line terminals
28.1
HV and LV
28.2
Tertiary
28.3
Filling medium for cable boxes
Air
29
Whether disconnecting chambers
are required
Bushing insulator or cable box for
neutral terminals, if any:
Yes
30
Description
Unit
Data
Required
Yes
Provided
To match existing plant
Oil/SF6 bushing or
Oil/Air as applicable
Cable box*
30.1
HV
Bushing
30.2
LV
Bushing
30.3
Tertiary
31
Whether accommodation for current
transformers shall be provided on:
31.1
HV terminals
Yes
31.2
LV terminals
Yes
31.3
Common winding neutral end
Yes
31.4
Tertiary terminals
Yes
-
D7.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
32
Description
Unit
Data
Required
Provided
Whether tapping shall be brought
out from each capacitance graded
type bushing insulator to a separate
terminal for power factor testing on
site, on:
32.1
HV bushings
N/A (Unless Oil/air
supplied)
32.2
LV bushings
N/A (Unless Oil/air
supplied)
32.3
Tertiary bushings
No
33
Whether pressure relief device is to
be fitted
Yes
34
Whether first filling of oil shall be
supplied for the transformer and its
associated oil filled equipment
Yes
35
Whether transformer shall be
transported filled with oil or with a
suitable gas
Gas
36
Minimum capacity of conservator
between highest and lowest visible
levels, as percentage of total cold
oil volume of the transformer
37
Whether marshalling unit shall be
provided
%
7.5
Yes
IF SO:
37.1
Whether free-standing kiosk or
transformer mounted cabinet
Free standing
37.2
Whether metalclad heater to be
provided
Yes
38
Type of dehydrating breather:
38.1
Silica Gel
No
38.2
Automatic of the repetitive cycle
type (Dehydrating)
Yes
39
Whether wheels shall be provided
If so:
Yes
39.1
Whether plain or flanged
To be agreed with
M.O.E.
D7.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
39.2
Description
Unit
Data
Required
Yes
Whether required to turn through
90°
39.3
Gauge of track
40
Whether winding or oil temperature
indicators are required
Yes
40.1
HV winding wti
Yes
40.2
LV winding wti
Yes
40.3
Tertiary winding (wti)
Yes
40.4
Oil temperature indicator
Yes
41
Whether winding temperature
indicator remote repeaters are
required
No
42
Whether the forced cooling
equipment is to be operated
automatically from contacts on the
winding temperature indicator
Yes
43
Whether electrical energy will be
provided on site for erection
purposes
Provided
To be agreed with
M.O.E.
To be agreed with
M.O.E
IF SO:
Maximum available power
kVA
44
Supply voltage for transformer
auxiliaries
V
45
Whether control and instrument
wiring shall conform to specified
colour code
46
Impulse tests: (state whether "type"
or "routine")
46.1
Whether recurrent surge
oscillograph tests are to be carried
out
Yes
46.2
Whether HV winding to be directly
impulse tested
Yes
380/220
Yes
Routine
D7.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
46.2.1
46.2.2
Description
Unit
Data
Required
Yes
Whether chopped waves to be
included
Provided
For tests of HV winding impedance
to earth from:
-
Other HV terminals
LV terminals
Tertiary terminals
Earthed
Earthed except tested
phase
Resistance earthed
46.3
Whether LV winding to be directly
impulse tested
Yes
46.3.1
Whether chopped waves to be
included
Yes
46.3.2
For tests on LV winding, impedance
to earth from:
-
Earthed
Earthed except tested
phase
Resistance earthed
Other LV terminals
HV terminals
Tertiary terminals
46.4
Whether tertiary winding to be
directly impulse tested
Yes
46.4.1
Whether chopped waves to be
included
No
46.4.2
For tests on tertiary winding,
impedance to earth from:
-
Other tertiary terminals
HV terminals
-
LV terminals
47
Dielectric tests on windings with
Um » 300 kV, non-uniform
insulation:
47.1
Whether tests shall be conducted in
accordance with Method 1 or
Method 2, to IEC 60076-3
47.2
If Method 2, voltage level U2 at
which partial discharge
measurements shall be made
48
Whether zero phase sequence
impedance test required
Earthed
Earthed except for
tested phase
Earthed except for
tested phase
Method 1
Yes
D7.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
49
Description
Vacuum test level
Data
m bars
(a)
Required
25
50
Maximum temperature rise above
ambient at IEC rated power
51.1
Of windings:
51.1.1
Hot spot
°C
51.1.2
Average (by resistance)
°C
55
51.2
Of oil:
15.2.1
Top of oil
°C
50
51.2.2
At inlet to cooler
°C
51.2.3
At outlet from cooler
°C
52
Maximum flux density in iron at
rated voltage and power frequency
and at rated voltage ratio
52.1
Wound limbs
T
52.2
Unwound limbs
T
52.3
Yokes
T
52.4
Shields
T
53
Maximum flux density in iron under
the most onerous voltage conditions
and at power frequency:
53.1
Wound limbs
T
53.2
Unwound limbs
T
53.3
Yokes
T
53.4
Shields
T
54
Maximum current density in
windings at IEC rated power:
54.1
HV
A/mm2
54.2
LV
A/mm2
54.3
Tertiary
A/mm2
Provided
D7.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
Description
Unit
Data
Required
54.4
Tapping
55
Magnetising current (HV winding)
55.1
At 90% rated voltage
A
55.2
At 100% rated voltage
A
55.3
At 110% rated voltage
A
55.4
At the maximum voltage equivalent
to the value quoted in Schedule D
Part I
A
56
No load losses at rated voltage ratio
and IEC rating (guaranteed value) :
kW
57
Input to cooling plant
kW
58
Load losses at 75°C and rated
ONAF power:
i)
On principal (normal) tapping,
58.1
Tap position number
58.2
HV /LV (guaranteed value)
kW
58.3
HV/ tertiary at tertiary rated power
kW
58.4
LV/ tertiary winding at tertiary rated
power
kW
ii)
On tapping for maximum loss
58.5
Tap number
58.6
HV /LV (guaranteed value)
kW
58.7
HV/ tertiary at tertiary rated power
kW
58.8
LV/ tertiary winding at rated power
kW
59
Load losses at 75°C and rated
ONAN power
kW
i)
On principal (normal) tapping,
59.1
Tap position number
Provided
A/mm2
D7.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
59.2
HV /LV (guaranteed value)
kW
59.3
HV/ tertiary at tertiary rated power
kW
59.4
LV/ tertiary winding at rated power
kW
ii)
On tapping for maximum loss
59.5
Tap number
59.6
HV /LV
kW
59.7
HV/ tertiary at tertiary rated power
kW
LV/ tertiary winding at rated power
kW
60.1
Total losses at 75°C and normal
voltage
At IEC rating (guaranteed value)
kW
60.2
At ONAN rating
kW
60.3
Proportion of sum of fixed and load
losses at rated power which will be
supplied during the temperature rise
test
60
61
Description
Unit
Provided
%
Impedance voltage at 75°C on
principal tapping - per cent on
primary winding rating (including all
tolerances)
MAX/MIN
MAX/MIN
61.1
Between HV and LV windings
%
61.2
Between HV and tertiary windings
%
61.3
Between LV and tertiary windings
60
Impedance voltage at 75°C at each
end of tapping range - per cent on
primary winding rating (including all
tolerances)
60.1
Data
Required
18-19
MAX/MIN
MAX/MIN
Between HV and LV windings
At maximum voltage ratio
At minimum voltage ratio
60.4
Connecting leads from winding to
tap changer
60.5
Tertiary windings
D7.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
61
Description
Unit
Calculated thermal time constant:
61.1
Natural cooling
s
61.2
Forced cooling
s
62
Oil circulation (i.e. natural/partially
directed/directed)
62.1
To the windings:
62.1.1
HV
62.1.2
LV
62.1.3
Tapping
62.1.4
Tertiary
62.2
Through the windings:
62.2.1
HV
62.2.2
LV
62.2.3
Tapping
62.2.4
Tertiary
63
Core construction
63.1
Taped/banded/bolted limbs
63.2
Taped/banded/bolted yokes
63.3
Taping/banding material
63.4
Number of limbs
63.5
Number of limbs wound
64
Type of joint in magnetic core (90%
butt, overlap, mitre etc)
64.1
Whether tank or other flux shields
are incorporated
64.2
Type of core steel
64.3
Specific loss of core steel at 1.5
tesla
Data
Required
Provided
W/kg
D7.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
65
Description
Unit
Data
Required
Provided
Voltage rating of neutral bushing or
cable box:
65.1
HV neutral
kV
65.2
LV neutral
kV
65.3
Tertiary neutral
kV
66
Type of on-load voltage control
equipment:
66.1
Single or double compartment type
etc
66.2
Manufacturer's type designation
67
Tappings
67.1
Arrangement of tappings (Linear,
Coarse/fine, Reversing)
67.2
Which winding is tapped and where
(e.g. neutral end)
67.3
Size of step as percentage of
winding rated voltage
67.4
Number of steps
68
Minimum thickness of tank base
plate
Base plate
68.1
With flat base
Length not exceeding 2500mm
Length exceeding 2500mm not
exceeding 7500mm
Length exceeding 2500mm
19
19
25
6
6
9
32
16
9
12
6
9
68.2
%
With fabricated underbase
Length not exceeding 2500mm
Length exceeding 2500mm
68.3
Top
69
Material of transformer tank
70
Thickness of radiator plates and/or
cooling tubes
Side
plate
Base
plate
Side
plate
mm
mm
D7.13
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
71
Description
Unit
Data
Required
Provided
Number of coolers or cooler banks
per transformers
72
Rating of each cooler or cooler
bank
kW
73
Total oil required (including cooling
system) litres
74
Filling medium of transformer tank
for shipment
75
Total volume of conservator
litres
76
Volume of oil in conservator
between the highest and lowest
visible levels
litres
77
Mass of core and windings
tonnes
78
Mass of copper required in the
complete transformer
kg
79
Mass of core laminations
80
Total mass of complete transformer
including cooling gear, voltage
regulating equipment, all fittings and
oil
tonnes
81
Mass of transformer as arranged for
transport
(heaviest part)
tonnes
82
Maximum noise level (`A' weighting)
dB
83
Dimensions of transformer arranged
for transport:
83.1
Height
m
83.2
Width
m
83.3
Length
m
84
Time for which transformer can
safely withstand
30 per cent over-voltages
kg
88
D7.14
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D7 – 400/138.6 KV POWER TRANSFORMERS - Cont
Item
No
85
Description
Unit
Data
Required
Provided
Whether any reactors, capacitors,
linear or non-linear resistors are
immersed in the oil of the
transformer or tap changer tank
86
Transformer magnetising
characteristics (on nominal
tapping), and allowable duration:
86.1
250 MVA TRANSFORMER
VOLTAGE
ph-ph
kV
360
400
440
480
520
560
600
87
Flux-current (B-H curve for the
transformers):
88
Confirm that the life of the
transformer will not be significantly
reduced if subjected to the
overvoltages specified in
Schedule D Part I
MAGNETISING
CURRENT current/ph
(A rms/ph) (s)
YES/NO
YES/NO
(Delete as applicable)
D7.15
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D8 - 400 KV SHUNT REACTORS
Item
No
1
Description
Unit
Data
Description of reactor
1.1
Indoor or outdoor installation
1.2
Shell or core construction
1.3
Gapped core or coreless type
1.4
Three phase or single phase units
2
Site conditions
2.1
Altitude above sea level m
2.2.1
Air minimum
°C
-10
2.2.2
Air maximum
°C
+55
3
Continuous maximum rating (CMR)
when operating under site
conditions:
4
Rated frequency
Hz
50
5
Rated voltage
kV
420
6
Nominal voltage
kV
400
7
Vector group symbol
YN
8
Method of system earthing
Solid - Effective
9
Method of earthing the reactors
Not applicable
10
Type of cooling
ONAN
11
Impulse withstand level (full wave
1.2/50 microsecond) under site
conditions
12
Whether star connected winding
shall be fully insulated or graded
Required
Provided
Outdoor
Three or single
Less than 1000m
50MVA
kVp
1425
Graded
13
Bushing insulators or cable boxes or
sealing ends for:
13.1
Line terminals
Oil/SF6 bushing or
Oil/Air as applicable
13.2
Neutral end terminals
Bushing
D8.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D8 - 400 KV SHUNT REACTORS - Cont
Item
No
14
Description
Unit
Data
Required
14.1
Line terminals
Yes
14.2
Neutral end terminals
Yes
15
Whether tapping shall be brought
out from each capacitance graded
type bushing insulator to a separate
terminal for power factor testing on
site
N/A (Unless Oil/Air
Supplied)
16
Whether pressure release device is
to be fitted
Yes
17
Whether first filling of oil shall be
supplied for the reactor and its
associated oil filled equipment
18
19
Provided
Whether accommodation for current
transformers shall be provided on:
Yes
Whether reactor shall be transported
filled with oil or a suitable gas
Gas
Minimum capacity of conservator
between highest and lowest visible
levels, as percentage of total cold oil
volume of the reactor
7.5%
20
Whether marshalling kiosk or reactor
mounted cabinet
Marshalling kiosk
21
Type of dehydrating breather:
21.1
Silica Gel
No
21.2
Automatic of the repetitive cycle
(Dehydrating)
Yes
22
Whether wheels are required
If yes:
Yes
22.1
Whether plain or flanged
To be agreed with
M.O.E
22.2
Whether required to turn through 90°
Yes
22.3
Gauge of track
To be agreed with
M.O.E.
23
Whether oil temperature indicator is
required
Yes
D8.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D8 -400 KV SHUNT REACTORS - Cont
Item
No
24
Description
Unit
Vacuum test level
m bars
(a)
25
IEC rated power
MVAr
26
IEC rated lightning impulse
withstand voltage
27
Maximum temperature rise above
ambient at IEC rated power
27.1
Of windings
27.1.1
Hot spot
°C
27.1.2
Average (by resistance)
°C
55
27.2
Of oil
27.2.1
Top oil
°C
50
27.2.2
At inlet to cooler
°C
27.2.3
At outlet to cooler
°C
28
Maximum flux density in iron at
rated voltage and power frequency
28.1
Cores
T
28.2
Yokes
T
28.3
Shields
T
29
Maximum current density in winding
at IEC rated power
30
Total losses at 75°C and rated
voltage
31
Impedance at 75°C at IEC rated
voltage and IEC rated power
32
Resistance of windings at 75°C
33
Type of winding
34
Conductor material (e.g. copper,
work hardened copper etc.)
35
Conductor insulation
Data
Required
25
Provided
kVp
A/mm²
kW
ohms/p
hase
D8.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D8 - 400 KV SHUNT REACTORS - Cont
Item
No
36
Description
Unit
Data
Required
Calculated thermal time constant
Provided
s
37
Type of joint in magnetic core (90°
butt, overlap, mitre etc.)
37.1
Whether tank or other flux shields
are incorporated
37.2
Type of core steel
37.3
Specific loss of core steel at 1.5
tesla
38
Voltage rating of neutral bushing or
cable box
39
Minimum thickness of tank base
plate
39.1
With flat base
19
6
39.2
Length not exceeding 2500mm
Length exceeding 2500mm not
exceeding 7500mm
Length exceeding 2500mm
19
25
6
9
32
16
9
12
6
9
W/kg
kV
Base plate
With fabricated underbase
Length not exceeding 2500mm
Length exceeding 2500mm
39.3
Top
40
Material of reactor tank
41
Thickness of radiator plates and/or
cooling tubes
42
Number of coolers or cooler banks
per reactor
43
Rating of each cooler or cooler
bank
44
Total oil required (including cooling
system)
45
Filling medium of reactor tank for
shipment
46
Total volume of conservator
Side
plate
Base
plate
Side
plate
mm
mm
kW
litres
litres
D8.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D8 - 400 KV SHUNT REACTORS - Cont
Item
No
47
Description
Unit
Data
Required
Volume of oil in conservator
between the highest and lowest
visible levels
Provided
litres
48
Mass of core and winding
tonnes
49
Mass of copper required in the
complete reactor
kg
50
Mass of core laminations
kg
51
Total mass of complete reactor
including control gear, all fittings
and oil
tonnes
52
Mass of reactor as arranged for
transport (heaviest part)
tonnes
53
Maximum noise level (‘A’ weighing)
54
Dimensions of reactor arranged for
transport
54.1
Height
m
54.2
Width
m
54.3
Length
m
55
Departure from linearity of
voltage/current characteristic at
following percentages of rated
voltage
55.1
110 per cent
A
55.2
120 per cent
A
55.3
130 per cent
A
55.4
Whether above values will be
demonstrated by test
dB
D8.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D9 – EARTHING TRANSFORMERS (11 KV TERTIARY)
Unit
Data
Required
Offered
1
EARTHING TRANSFORMER
1.1
Manufacturer & Place of manufacturing
1.2
Type designation
1.3
Type
Three phase,
oil immersed,
core type
1.4
Standards
IEC 60076-1, 2, -3, -5, -10,
60296
NEMA TR1
1.5
Mounting
Outdoor,
wheel
1.6
Rated voltage
kV
11
1.7
Rated frequency
Hz
50
1.8
Vector group
1.9
Cooling
1.10
Method of earthing
1.10.1
HV winding
1.11
Type (graded/non-graded) of windings
1.11.1
HV winding
1.12
Rated voltage of windings
1.12.1
HV winding
1.13
Highest voltage for equipment
1.13.1
HV winding
ZN
ONAN
Solid
Non-graded
kV
11
kV
12
D9.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D9 – EARTHING TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
95
1.14
Rated lightning impulse withstand voltage at HV
Terminal
1.15
Rated power frequency withstand voltage at
1.15.1
HV terminal
kV
38
1.16
HV neutral terminal
kV
38
1.17
Maximum temperature rise at rated power at:
1.17.1
Windings
K
55
1.17.2
Hot spot of windings
K
68
1.17.3
Top oil
K
50
1.17.4
Oil at inlet of cooler
K
1.17.5
Oil at outlet of cooler
K
1.17.6
Core
K
1.18
Losses at rated voltage and rated frequency
1.19
Maximum current density at rated power:
1.19.1
HV winding
A/mm2
1.19.2
LV auxiliary winding
A/mm2
1.20
Symmetrical short circuit withstand current (duration
2 s) at:
1.20.1
HV terminal
1.21
Magnetising current (HV winding)
1.21.1
At 90% rated voltage
A
1.21.2
At 100% rated voltage
A
1.21.3
At 110% rated voltage
A
kV
kW
kA
50
D9.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D9– EARTHING TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
1.22
Maximum flux density in core at rated voltage, power
frequency
T
1.23
Limitation and withstanding of fault current in neutral for
30s
A
1.24
Resistance of winding at 75°C:
1.24.1
HV side
Ω/phase
1.25
Zero phase sequence impedance of inter-star windings
at 75°C
Ω/phase
1.26
Terminal connection
1.26.1
HV terminal
1.26.3
HV neutral terminal
1.27
Isolating link for test purposes (not required if separable
connector allows testing)
1.28.1
HV terminal
Yes
1.29.2
LV terminal
No
1.30
Mounting of current transformer at
1.30.1
HV terminal
1.30.2
Neutral terminals
1.31
Current transformers
To be
calculated
Air-filled cable
box
Air-filled cable
box
In tank
In tank or box
To suit
HV Neutral
Number of cores
Rated extended primary current
Ratio (TR = turns ratio)
I core
II core
A
A
Class
I core
II core
D9.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D9– EARTHING TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
Knee point voltage (Ek)
I core
II core
V
V
Exciting current (IE ) at Ek
I core
II core
mA
mA
Rated output (Burden to be 25-100% rated burden)
I core
II core
1.32
Oil:
1.32.1
Manufacturer
1.32.2
Type designation
1.32.3
Standards
1.32.4
Minimum flash point
1.32.5
Viscosity
VA
VA
IEC 60296
o
C
At 20oC
At 50oC
At 80oC
mm2/s
mm2/s
mm2/s
1.32.6
Maximum dielectric strength for 1 min
1.32.7
Dielectric factor
1.32.8
Acidity (neutralization value)
1.33
Type of dehydrating breather (Non-sealed
transformers)
1.34
Conductor material (e.g. copper, work hardened
copper, etc.):
1.34.1
HV windings
1.35
Conductor insulation:
1.35.1
HV winding
1.36
Calculated thermal time constant
1.37
Thickness of transformer tank
kV
mgKOH/
g
Silicagel –
automatic
recharge type
min
D9.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D9 – EARTHING TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
1.37.1
Sides
mm
1.37.2
Bottom
mm
1.37.3
Top
mm
1.38
Material of transformer tank
1.39
Thickness of radiator plates
mm
1.40
Total volume of conservator
litres
1.41
Masses of transformer
1.42
Core and coils
kg
1.43
Total mass excluded oil
kg
1.44
Oil mass
1.45
Total mass
kg
1.46
Mass of transformer as arranged for transport (heaviest
part)
kg
1.47
Dimensions of transformer arranged for transport
• in tank
• in radiators
• total
Data
Required
Offered
kg
kg
kg
Height
Width
Length
m
m
m
1.48
Maximum noise level (to NEMA TR1)
dB
1.49
Vibration test (Y/N)
1.50
Conservator vessel, radiators, fan grilles, control boxes
or cubicles and pipework anticorrosion protection
1.51
Tank anticorrosion protection
1.52
Control/Protection voltage
1.53
Manufacturer quality assurance
56
N
Hot dip
galvanized
and painted
V
110 DC
Yes
According to ISO 9000, 9001, 9002, 9003 and 9004
1.54
Type test certificates to be issued by:
Independent Laboratory or independently witnessed
type test certificate
Yes
D9.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10 –AUXILIARY TRANSFORMERS (11 KV TERTIARY)
Unit
Data
Required
Offered
1
AUXILIARY TRANSFORMER 11/0.380 KV; WITH
AUXILIARY WINDING
1.1
Manufacturer & Place of manufacturing
1.2
Type designation
1.3
Type
1.4
Standards
1.5
Mounting
1.6
Rated voltage ratio
kV
11/0.380
1.7
Rated frequency
Hz
50
1.8
Vector group
Dyn11
1.9
Cooling
ONAN
1.10
Method of earthing
1.10.1
HV winding
Solid
1.10.2
LV winding
Solid
1.11
Type (graded/non-graded) of windings
1.11.1
HV winding
Non-graded
1.11.2
LV auxiliary winding
Non-graded
1.12
Rated voltage of windings
1.12.1
HV winding
Three phase,
oil immersed,
core type
IEC 60076-1, 2, -3, -5, -10,
60296
NEMA TR1
Outdoor,
wheel
Transformer
kV
11
D10.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10 –AUXILIARY TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
0.380
1.12.2
LV auxiliary winding
1.13
Highest voltage for equipment
1.13.1
HV winding
kV
12
1.13.2
LV auxiliary winding
kV
0.420
1.14
Rated lightning impulse withstand voltage at HV
Terminal
kV
95
1.15
Rated power frequency withstand voltage at
1.15.1
HV terminal
kV
38
1.15.2
LV terminal
kV
3
1.16
HV neutral terminal
kV
38
1.17
Rated power at site conditions
kVA
Rated to suit
1.18
Maximum temperature rise at rated power at:
1.18.1
Windings
K
55
1.18.2
Hot spot of windings
K
68
1.18.3
Top oil
K
50
1.18.4
Oil at inlet of cooler
K
1.18.5
Oil at outlet of cooler
K
1.18.6
Core
K
1.19
Temperature rise of winding due to short circuit
duration of 2 s and HV side short circuit current of
25 kA
1.20
No load losses at rated voltage and rated frequency
kV
kW
D10.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10 –AUXILIARY TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
1.21
Load losses at 75°C, and rated frequency, rated power
and principal tapping:
1.22
Maximum current density at rated power:
1.22.1
HV winding
A/mm2
1.22.2
LV auxiliary winding
A/mm2
1.23
Symmetrical short circuit withstand current (duration
2 s) at:
1.23.1
HV terminal
kA
1.23.2
LV auxiliary terminal
kA
1.24
Magnetising current (HV winding)
1.24.1
At 90% rated voltage
A
1.24.2
At 100% rated voltage
A
1.24.3
At 110% rated voltage
A
1.25
Maximum flux density in core at rated voltage, power
frequency and principal tapping
T
1.26
Type of tap changing
1.27
Type designation of off-load tap changer
1.28
Tapped winding
1.29
Tapping range
1.30
Tapping step
2.5%
1.31
Number of steps (positions)
4 (5)
1.32
Impedance voltage range at 75°C and principal tapping:
1.33
At principal tapping
> 4%
1.33.1
At maximum voltage ratio
>4%
1.33.2
At minimum voltage ratio
>4%
50
Off-load
HV
+5% -5%
D10.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10–AUXILIARY TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
Data
Required
Offered
1.34
Resistance of winding at 75°C and principal tapping:
1.34.1
HV side
Ω/phase
1.34.2
LV auxiliary side
Ω/phase
1.35
Terminal connection
1.35.1
HV terminal
Air-filled cable
box
1.35.2
LV terminal
Air-filled cable
box
1.35.4
LV neutral terminal
Air-filled cable
box
1.36
Isolating link for test purposes (not required if
separable connector allows testing)
1.36.1
HV terminal
Yes
1.36.2
LV terminal
No
1.37
Mounting of current transformer at
1.37.1
HV terminal
1.37.2
Neutral terminals
1.38
Oil:
1.38.1
Manufacturer
1.38.2
Type designation
1.38.3
Standards
1.38.4
Minimum flash point
1.38.5
Viscosity
In tank
In tank or box
IEC 60296
o
C
At 20oC
At 50oC
At 80oC
mm2/s
mm2/s
mm2/s
1.38.6
Maximum dielectric strength for 1 min
1.38.7
Dielectric factor
1.38.8
Acidity (neutralization value)
kV
mgKOH/g
D10.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10–AUXILIARY TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
1.39
Type of dehydrating breather (Non-sealed
transformers)
1.40
Conductor material (e.g. copper, work hardened
copper, etc.):
1.40.1
HV windings
1.40.2
LV windings
1.41
Conductor insulation:
1.41.1
HV winding
1.41.2
LV winding
1.42
Calculated thermal time constant
1.43
Thickness of transformer tank
1.43.1
Sides
mm
1.43.2
Bottom
mm
1.43.3
Top
mm
1.44
Material of transformer tank
1.45
Thickness of radiator plates
mm
1.46
Total volume of conservator
litres
1.47
Masses of transformer
1.48
Core and coils
kg
1.49
Total mass excluded oil
kg
1.50
Oil mass
1.51
Total mass
kg
1.52
Mass of transformer as arranged for transport
(heaviest part)
kg
1.53
Dimensions of transformer arranged for transport
Data
Required
Offered
Silicagel –
automatic
recharge type
min
• in tank
• in radiators
• total
kg
kg
kg
Height
Width
Length
m
m
m
D10.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D10 –AUXILIARY TRANSFORMERS (11 KV TERTIARY) - Cont
Unit
1.54
Maximum noise level (to NEMA TR1)
1.55
Vibration test (Y/N)
1.56
Conservator vessel, radiators, fan grilles, control
boxes or cubicles and pipework anticorrosion
protection
1.57
Tank anticorrosion protection
1.58
Control/Protection voltage
1.59
Manufacturer quality assurance
dB
Data
Required
Offered
56
N
Hot dip
galvanized
and painted
V
110 DC
Yes
According to ISO 9000, 9001, 9002, 9003 and 9004
1.60
Type test certificates to be issued by:
Independent Laboratory or independently witnessed
type test certificate
Yes
D10.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D11 – CAPACITORS (11 KV TERTIARY)
Unit
Data
Required
1.1
Assigned rated current
A
1.2
Assigned rated voltage
kV
1.3
Assigned rated output
1.4
Whether complete 3-phase bank is star
or delta connected
1.5
Rated frequency
1.6
Temperature category to IEC 60871
1.7
Nominal capacitance:
1.7.1
For each element
µF
1.7.2
For each capacitor unit
µF
1.7.3
Capacitance of single phase bank
µF
1.8
Dielectric embodied in elements:
1.8.1
Whether paper and/or plastic film
1.8.2
Thickness of each:
(a)
(b)
1.8.3
Offered
MVAr
Hz
Paper
Film
µm
µm
Number per layer:
Of paper
Of film
1.9
Element foils thickness
1.10
Method of making connections to element foils
1.11
Details of impregnating medium:
1.11.1
Trade name
1.11.2
Chemical compound
1.12
Nominal rated voltage of elements
1.13
Design maximum dielectric stresses:
(a)
(b)
µm
V
Paper
Film
V/µm
V/µm
D11.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D11 – CAPACITORS (11 KV TERTIARY) – Cont
Unit
Data
Required
1.14
Minimum rms breakdown voltage of individual
elements
1.15
Connection of elements per capacitor unit:
1.15.1
Number in parallel
1.15.2
Number in series
1.16
Rated voltage UN of capacitor unit
kV
1.17
Rated current of unit
A
1.18
Rated output of unit
MVAr
1.19
Connection of capacitors:
1.19.1
Number of units in parallel per phase
1.19.2
Number of unit groups in series per phase
1.20
Details of fusing arrangement and whether internal
or external
1.21
Losses in capacitor unit determined as described in
IEC 60871 at dielectric temperatures of:
20 °C
75 °C
1.22
Variation of losses due to temperature variation over
the ambient temperature range for the temperature
category stated in Item 1.6
W/ kVAr at °C
W/ kVAr at °C
V
W/kWAr
W/ kVAr
W/ kVAr
W/ kVAr
1.23
Variation of capacitance due to temperature
variation over the ambient temperature range for the
temperature category stated in Item 1.6
1.24
Maximum operating surface temperature
rise of container (above an ambient temperature of 50°C)
°C
Maximum internal hot spot
temperature rise (above ambient stated in Item
1.24)
°C
1.25
1.26
Weight of complete unit capacitor including all
fittings and impregnating medium
Offered
%
kg
D11.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D11 – CAPACITORS (11 KV TERTIARY) – Cont
Unit
Data
Required
1.27
Total weight of complete 3-phase capacitor bank
arranged for transport
kg
1.28
Thickness of container:
mm
1.28.1
Top
mm
1.28.2
Sides
mm
1.28.3
Bottom
mm
1.29
Type of connector provided at HV terminals of
capacitor bank
1.30
Type of connector provided at neutral ends of
capacitor bank
1.31
Minimum ambient temperature at which a capacitor
bank at this temperature may be energised at rated
voltage and frequency without damage to, or loss of
life of, unit capacitors or deterioration of associated
fuses
1.32
Details of discharge device:
1.32.1
Type
1.32.2
Connection
1.32.3
Number of devices (per element, of group of
elements)
1.32.5
Voltage rating/device
V
1.32.6
Current rating/device
mA
1.32.7
Total loss per device at rated current
W
1.32.8
Total loss per unit capacitor at rated current
W
1.32.9
Estimated times for discharge down to the voltage
limit specified in IEC 60871:
(a) For a unit capacitor
(b) For the complete single phase bank
Offered
°C
Minutes
Minutes
D11.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D12 - 11 KV (TERTIARY) SHUNT REACTORS
Unit
Data
Required
1
Description of reactor
1.1
Indoor or outdoor installation
1.2
Shell or core construction
1.3
Gapped core or coreless type
1.4
Three phase or single phase units
2
Site conditions
2.1
Altitude above sea level m
2.1.1
Air minimum
°C
-10
2.1.2
Air maximum
°C
+55
3
Continuous maximum rating
(CMR) when operating under site
conditions:
4
Rated frequency
Hz
50
5
Rated voltage
kV
12
6
Nominal voltage
kV
11
7
Vector group symbol
8
Method of system earthing
9
Method of earthing the reactors
10
Type of cooling
11
Impulse withstand level (full wave
1.2/50 microsecond) under site
conditions
12
Whether star connected winding
shall be fully insulated or graded
13
Bushing insulators or cable boxes
or sealing ends for:
13.1
Line terminals
13.2
Neutral end terminals
14
Whether accommodation for
current transformers shall be
provided on:
Provided
Outdoor
Three
Less than 1000 m
25 MVA
YN
Transformer
Not applicable
ONAN
kVp
95
Cable
-
D12.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D12 -11 KV (TERTIARY) SHUNT REACTORS - Cont
Unit
Data
Required
No
14.1
Line terminals
14.2
Neutral end terminals
No
15
Whether tapping shall be brought
out from each capacitance
graded type bushing insulator to a
separate terminal for power factor
testing on site
N/A
16
Whether pressure release device
is to be fitted
Yes
17
Whether first filling of oil shall be
supplied for the reactor
Yes
18
Whether reactor shall be
transported filled with oil or a
suitable gas
Oil
19
Minimum capacity of conservator
between highest and lowest
visible levels, as percentage of
total cold oil volume of the reactor
20
Whether marshalling kiosk or
reactor mounted cabinet
Reactor mounted
cabinet
21
Whether plain or flanged
To be agreed with
M.O.E.
21.1
Silica Gel
Yes
21.2
Automatic of the repetitive cycle
(Dehydrating)
No
22
Whether wheels are required
If yes:
Yes
22.1
Whether plain or flanged
To be agreed with
M.O.E.
22.2
Whether required to turn through
90°
To be agreed with
M.O.E.
22.3
Gauge of track
To be agreed with
M.O.E.
23
Whether oil temperature indicator
is required
24
Vacuum test level
Provided
7.5%
Yes
m bars
(a)
D12.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D12 -11 KV (TERTIARY) SHUNT REACTORS - Cont
Unit
Data
Required
25
IEC rated power
26
IEC rated lightning impulse
withstand voltage
27
Maximum temperature rise above
ambient at IEC rated power
27.1
Of windings
27.1.1
Hot spot
°C
27.1.2
Average (by resistance)
°C
55
27.2
Of oil
27.2.1
Top oil
°C
50
27.2.2
At inlet to cooler
°C
27.2.3
At outlet to cooler
°C
28
Maximum flux density in iron at
rated voltage and power
frequency
28.1
Cores
T
28.2
Yokes
T
28.3
Shields
T
29
Maximum current density in
winding at IEC rated power
30
Total losses at 75°C and rated
voltage
31
Impedance at 75°C at IEC rated
voltage and IEC rated power
32
Resistance of windings at
75°Cohms/phase
33
Type of winding
34
Conductor material (e.g. copper,
work hardened copper etc.)
35
Conductor insulation
36
Calculated thermal time constants
Provided
MVAr
kVp
95
A/mm²
kW
D12.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D12 -11 KV (TERTIARY) SHUNT REACTORS - Cont
Unit
Data
Required
37
Type of joint in magnetic core
(90° butt, overlap, mitre etc.)
37.1
Whether tank or other flux shields
are incorporated
37.2
Type of core steel
37.3
Specific loss of core steel at 1.5
tesla
W/kg
38
Voltage rating of neutral bushing
or cable box
kV
39
Minimum thickness of tank base
39.1
With flat base
39.2
Provided
Base
Plate
19
Side
Plate
6
Length not exceeding 2500 mm
19
6
Length exceeding 2500 mm not
exceeding 7500 mm
25
9
Length exceeding 2500 mm
32
16
Length not exceeding 2500 mm
9
6
Length exceeding 2500 mm
12
9
Base
Plate
Side
Plate
With fabricated underbase
39.3
Top
mm
40
Material of reactor tank
41
Rating of each cooler or cooler
bank
42
Total oil required (including
cooling system) litres
43
Total mass of compelte reactor
including control gear, all fittings
and oil
Tonnes
44
Mass of reactor as arranged for
transport (heaviest part)
Tonnes
45
Maximum noise level (‘A’
weighting)
46
Dimensions of reactor arranged
for transport
kW
dB
D12.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D12 -11 KV (TERTIARY) SHUNT REACTORS - Cont
Unit
Data
Required
46.1
Height
m
46.2
Width
m
46.3
Length
m
47
Departure from linearity of
voltage/current characteristic at
following percentages of rated
voltage
47.1
110 per cent
A
47.2
120 per cent
A
47.3
130 per cent
A
47.4
Whether above values will be
demonstrated by test
Provided
D12.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D13 – BUSHINGS
Item
No.
1
Description
Nominal voltage (UN)
Unit
kV
Required
380
132
2
Site altitude above sea level for
which bushings are to be suitable
where this exceeds 1000 m
3
Minimum nominal specific
creepage distance in mm per unit
of system highest voltage
mm/kV
31
4
Impulse withstand level (full wave
1.2/50 microsecond) under site
conditions
kVp
1425
650
5
Switching surge withstand level
kVp
1050
-
6
Arcing horns or rings
7
Radio influence voltage
measured at 110 per cent of the
maximum line to ground operating
voltage and at 1000 kHz, shall be
less than
µV
500
8
Maximum symmetrical fault
current
kA
40
Offered
11
Less than 1000 m
95
-
Yes Where Oil/Air
Bushings provided
40
50
D13.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR
Unit
Data
Required
A
LVAC SWITCHGEAR (380/220 V, 50 Hz)
1
GENERAL
1.1
Rated voltage
V
380
1.2
Rated frequency
Hz
50
2
LVAC SWITCHBOARD
2.1
Manufacturer
2.2
Type designation
2.3
Type of switchboard
2.4
Standards
2.5
Number of years equipment of identical
design has been in service
2.6
Rated current of busbars at 50°C ambient
temperature
2.7
Busbar cross section
2.8
Busbar insulation material
2.9
Busbar insulation maximum working
temperature
210
Temperature rise on continuous operation at
rated current
at 50°C
2.11
Rated short-time withstand current (1 s)
kA
2.12
Rated peak withstand current
kA
2.13
Test voltage (1 min)
V
2.14
Impulse Withstand Voltage
2.15
Type of internal barriers, shutters, etc.
2.16
Degree of protection
Offered
Metal-clad
withdrawable type,
multi-tier
IEC 60439
A
mm2
°C
2500
kVp
Metallic
IP51
D14.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
2.17
Offered
Overall dimensions per cubicle
−
−
−
−
Width
Depth
Height
Weight
mm
mm
mm
kg
2.18
Method of circuit breaker withdrawal
manual
3
CIRCUIT BREAKER
3.1
Manufacturer
3.2
Type designation
3.3
Type
3.4
Number of poles
3.5
Standard
3.6
Rated current at 50°C
A
3.7
Rated short-time withstand current (1 s)
kA
3.8
Rated peak withstand current
kA
3.9
Rated symmetrical breaking current
kA
3.10
Rated making current
kA
3.11
Breaking time
3.12
Material of:
Air, withdrawable
3
IEC 60947-2
s
− moving contacts
− fixed contacts
3.13
Design of:
− moving contacts
− fixed contacts
3.14
3.15
Operating mechanism
− Motor rated power
− Motor operating voltage
W
V
Weight of draw-out unit
kg
D14.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
3.16
Type tests
3.16.1
Temperature Rise Test
Offered
Have heating tests at continuous rated normal
current been carried out?
− report number
− date
3.16.2
Basic Impulse Voltage Type Test:
Has B.I.V test been completed?
− circuit breaker
− report number
− date
3.16.3
Life Test:
Has 2000 operating life test at no load (deenergised) been carried out?
− report number
− date
4
MOULDED CASE CIRCUIT BREAKERS
(MCCBs)
4.1
Manufacturer
4.2
Type designation
4.3
Withdrawable MCCBs type
4.4
Number of poles
4.5
Standards
4.6
Rated current at 50°C
A
4.7
Rated short-time withstand current (1 s)
kA
4.8
Rated peak withstand current
kA
4.9
Rated breaking current
kA
4.10
Remote signalling
4.11
Operating mechanism
yes
3
IEC 60947-2
yes
D14.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
4.12
Mass
5
CURRENT TRANSFORMERS
5.1
Manufacturer
5.2
Type
5.3
Type of primary winding (e.g. bar, wound,
etc.)
5.4
Standards
5.5
Rated voltage
kV
5.6
Rated lightning impulse withstand voltage
phase to earth
kV
5.7
Rated power frequency withstand voltage
phase to earth
kV
5.8
Partial discharge test voltage
kV
5.9
Rated frequency
Hz
5.10
Rated continuous thermal current at 50oC
5.11
Rated short-time withstand current (1 s)
kA
5.12
Rated dynamic current
kA
5.13
Line current transformer
5.13.1
Type designation
5.13.2
Number of cores
5.13.3
Rated extended primary current
%
5.13.4
Ratio (TR = turns ratio)
•
I core
•
II core
A
A
5.13.5
Class
•
I core
•
II core
5.13.6
Knee point voltage (EK)
•
I core
•
II core
Offered
IEC 60044-1
50
V
V
D14.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
5.13.7
5.13.8
Exciting current (IE) at EK
•
I core
•
II core
A
A
Rated output (burden to be 25-100% rated
burden)
•
I core
•
II core
6
INSTRUMENTS
6.1
Manufacturer
6.2
Standards
6.3
Type designation
Offered
VA
VA
IEC 60051
− Ammeter
− Voltmeter
6.4
Total scale range
−
−
Ammeter
Voltmeter
6.5
Dimensions
mm
6.6
Accuracy
7
PROTECTION RELAYS
7.1
Earth Fault Protection
7.1.1
Manufacturer
7.1.2
Type reference
7.1.3
Relay design (electromechanical, static,
microprocessor-based, numerical)
7.1.4
Range of current settings, percent of current
rating
7.1.5
Range of time multiplier setting
7.1.6
Current at which relay resets, percent of
current setting
%
7.1.7
Current at which relay picks-up, percent of
current setting
%
%
D14.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
7.1.8
Self-checking facility
7.1.9
CT’s requirements
7.1.10
Tripping contacts ratings
7.2
Restricted Earth Fault Protection
7.2.1
Manufacturer
7.2.2
Type reference
7.2.3
Relay design (electromechanical, static,
microprocessor-based, numerical)
7.2.4
Estimated minimum faults setting (% of CT
rating)
%
7.2.5
Operating time at 5 x setting
ms
7.2.6
Maximum primary out-of-zone fault current at
which protection is stable
7.2.7
Offered
A
State principle of operation, i.e.
H
H - high impedance
L - low impedance
7.2.8
Current transformer requirements:
− Required knee point voltage, Vk
− CT maximum winding resistance
− Magnetising current at Vk
V
Ω
A
7.2.9
Self monitoring
yes
7.2.10
Self checking
yes
7.2.11
Tripping contacts rating
7.3
Undervoltage / Overvoltage Relay
7.3.1
Manufacturer
7.3.2
Type reference
7.3.3
Relay design (electromechanical, static)
7.3.4
Total scale range
V
D14.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D14 – LVAC SWITCHGEAR - Cont
Unit
Data
Required
7.3.5
Operate time at instantaneous voltage change
for undervoltage / overvoltage relay
ms
7.3.6
Reset ratio overvoltage / undervoltage
%
7.3.7
Self monitoring
7.3.8
Self checking
8
Manufacturer quality system in accordance
with ISO 9000, 9001, 9002, 9003 and 9004
yes
9
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
yes
Offered
D14.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15– DC SYSTEM
110 V D.C System
Unit
Data
Required
1
110 V D.C SYSTEM - SUBSTATION
SERVICES SUPPLY
1.1
110 V Battery Units
1.1.1
Manufacturer
1.1.2
Type designation
1.1.3
Number of battery units
1.1.4
Type of cell
1.1.5
Operating voltage per cell
1.1.6
Number of cells
1.1.7
Standard
1.1.8
Discharge capacity:
1.1.9
Nickel-Cadmium
V
* IEEE 1115 for
calculation
* IEC 60623,
60478, 60439 for
equipment
10 hour rate
Ah
−
−
−
−
5 hour rate
3 hour rate
1 hour rate
30 minute rate
Ah
Ah
Ah
Ah
min. 250 (to be
confirmed by
calculation)
Final cell voltage after discharge:
V
V
V
V
V
10 hour rate
5 hour rate
3 hour rate
1 hour rate
30 minute rate
Ampere hour efficiency:
−
−
−
−
1.1.11
2
−
−
−
−
−
−
1.1.10
Offered
%
%
%
%
10 hour rate
5 hour rate
3 hour rate
1 hour rate
Watt hour efficiency:
−
−
−
%
%
%
10 hour rate
5 hour rate
3 hour rate
D15.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
110 V D.C System
Unit
Data
Required
−
−
1.1.12
Maximum charging voltage per cell
V
1.1.13
Normal charging rate range
A
1.1.14
Maximum charging rate range
A
1.1.15
Float charging rate
A
1.1.16
Boost charging rate
A
1.1.17
Normal voltage across battery on float
charge
V
1.1.18
Voltage per cell on float charge
V
1.1.19
Normal voltage across battery on boost
charge
V
1.1.20
Voltage per cell on boost charge
V
1.1.21
Overall dimensions of one cell
mm
1.1.22
Quantity of electrolyte per cell
Litres
1.1.23
Overall dimensions of each stand
1.1.24
Number of stands
1.1.25
Number of tiers
1.1.26
Material and cross section of connections:
−
−
−
−
Offered
%
%
1 hour rate
30 minute rate
mm
mm2
mm2
mm2
mm2
between cells
between tiers
between stands
to battery fuse box
1.1.27
Method of treating copper connection
against corrosion
1.1.28
Method of protecting copper connections
against accidental short circuiting
1.1.29
Estimated short circuit current from fully
charged battery
1.1.30
Anticipated life of electrolyte under actual
operating conditions
A
Years
D15.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
110 V D.C System
Unit
Data
Required
1.1.31
1.1.32
Anticipated life of electrolyte under actual
operating conditions
Offered
Years
Operating temperatures:
-
Normal operation
maximum
minimum
-
Emergency discharge
maximum
minimum
°C
°C
°C
°C
1.2
110 V D.C Battery Chargers
1.2.1
Manufacturer
1.2.2
Type designation
1.2.3
Degree of protection
IP 51
1.2.4
Number of chargers
2 x 100% for
each battery
1.2.5
Type
1.2.6
Charging characteristic
1.2.7
Input voltage
V
3 Phase, 380
1.2.8
Input frequency and range
Hz
50 ± 5%
1.2.9
Input power
kVA
1.2.10
Minimum working power factor
1.2.11
Overload range
%
1.2.12
Voltage ripple
%
1.2.13
Ripple frequency
Hz
1.2.14
Means of adjusting output
1.2.15
Details of any forced cooling equipment
for chargers
1.2.16
Ambient temperature range
°C
1.2.17
Ambient relative humidity range
%
1.2.18
Mean time between failure (MTBF)
Years
D15.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
110 V D.C System
Unit
Data
Required
1.2.19
Overall dimensions (shall be a separate
free-standing panel/cubicle)
mm
1.2.20
Weight
kg
1.2.21
Boost charge maximum permitted
constant potential per cell
V
Boost charge maximum permitted current
as percentage of 5 hour capacity
%
Time to be re-charge to 90% capacity at
maximum permitted voltage and current
hrs
1.2.22
1.2.23
1.3
Battery Fuse Boxes
1.3.1
Manufacturer
1.3.2
Type designation
1.3.3
Degree of protection
1.3.4
Fuse rated current at 50oC
1.3.5
Remote signalling
1.4
110 V D.C. Switchboards
1.4.1
Manufacturer
1.4.2
Type designation
1.4.3
Degree of protection
1.4.4
Standards
1.4.5
Rating voltage
V
1.4.6
Rated current of busbars at 50oC ambient
temperature
A
1.4.7
Busbar cross section
1.4.8
Busbar insulation material
1.4.9
Number of circuits
1.4.10
Main isolator rating
A
1.4.11
Main fuse rating
A
1.4.12
Single line diagram number
Offered
IP 51
yes
IP 51
IEC 60439
110
mm2
D15.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
110 V D.C System
Unit
Data
Required
Offered
Arrangement drawing number
1.4.13
Details of Contactors:
−
−
−
−
−
−
−
Manufacturer
Type designation
Type
Site current rating (at 50°C)
Rated breaking capacity
Short time current (1 s)
Maximum operating time
A
kA
kA
• opening
• closing
−
−
1.4.14
V/W
Manufacturer
Type Designation
Brochure number
Details of Undervoltage / Overvoltage
Protection:
−
−
−
1.4.16
Voltage / power coil rating
Typical circuit diagram number
Details of Earth Fault Protection:
−
−
−
1.4.15
msec
msec
Manufacturer
Type Designation
Brochure number
Instruments
−
−
−
−
Manufacturer
Voltmeter (type)
Ammeter (type)
Instruments
Details of Moulded Case Circuit Breakers
(MCCBs)
-
Manufacturer
Type designation
Number of poles
Standards
Rated current at 50°C
Rated short-time withstand current
(1s)
Rated breaking capacity
Remote signalling
A
kA
kA
Yes
D15.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
110 V D.C System
Unit
Data
Required
1.4.17
Offered
Details of Miniature Circuit Breakers
(MCBs)
−
−
−
−
−
−
−
−
Manufacturer
Type designation
Number of poles
Standards
Rated current at 50°C
Rated short-time withstand current
(1s)
Breaking capacity at
Remote signalling
Manufacturer quality system in
accordance with ISO 9000, 9001, 9002,
9003 and 9004
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
A
kA
kA
Yes
Yes
Yes
D15.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM
48 V D.C System
Unit
Data
Required
1
48 V D.C SYSTEM - SUBSTATION
SERVICES SUPPLY
1.1
48 V Battery Units
1.1.1
Manufacturer
1.1.2
Type designation
1.1.3
Number of battery units
1.1.4
Type of cell
1.1.5
Operating voltage per cell
1.1.6
Number of cells
1.1.7
Standard
1.1.8
Discharge capacity:
1.1.9
Nickel-Cadmium
V
* IEEE 1115 for
calculation
* IEC 60623,
60478, 60439 for
equipment
10 hour rate
Ah
−
−
−
−
5 hour rate
3 hour rate
1 hour rate
30 minute rate
Ah
Ah
Ah
Ah
min. 250 (to be
confirmed by
calculation)
Final cell voltage after discharge:
V
V
V
V
V
10 hour rate
5 hour rate
3 hour rate
1 hour rate
30 minute rate
Ampere hour efficiency:
−
−
−
−
1.1.11
2
−
−
−
−
−
−
1.1.10
Offered
%
%
%
%
10 hour rate
5 hour rate
3 hour rate
1 hour rate
Watt hour efficiency:
−
−
−
%
%
%
10 hour rate
5 hour rate
3 hour rate
D15.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
48 V D.C System
Unit
Data
Required
−
−
1.1.12
Maximum charging voltage per cell
V
1.1.13
Normal charging rate range
A
1.1.14
Maximum charging rate range
A
1.1.15
Float charging rate
A
1.1.16
Boost charging rate
A
1.1.17
Normal voltage across battery on float
charge
V
1.1.18
Voltage per cell on float charge
V
1.1.19
Normal voltage across battery on boost
charge
V
1.1.20
Voltage per cell on boost charge
V
1.1.21
Overall dimensions of one cell
mm
1.1.22
Quantity of electrolyte per cell
Litres
1.1.23
Overall dimensions of each stand
1.1.24
Number of stands
1.1.25
Number of tiers
1.1.26
Material and cross section of connections:
−
−
−
−
Offered
%
%
1 hour rate
30 minute rate
mm
mm2
mm2
mm2
mm2
between cells
between tiers
between stands
to battery fuse box
1.1.27
Method of treating copper connection
against corrosion
1.1.28
Method of protecting copper connections
against accidental short circuiting
1.1.29
Estimated short circuit current from fully
charged battery
1.1.30
Anticipated life of electrolyte under actual
operating conditions
A
Years
D15.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
48 V D.C System
Unit
Data
Required
1.1.31
1.1.32
1.1.33
1.1.34
Estimated short circuit current from fully
charged battery
Offered
A
Anticipated life of electrolyte under actual
operating conditions
Years
Anticipated life of electrolyte under actual
operating conditions
Years
Operating temperatures:
−
Normal operation
°C
°C
maximum
minimum
−
Emergency discharge
°C
°C
maximum
minimum
1.2
48 V D.C Battery Chargers
1.2.1
Manufacturer
1.2.2
Type designation
1.2.3
Degree of protection
IP 51
1.2.4
Number of chargers
1.2.5
Type
2 x 100% for
each battery
Thyristor
Controlled
1.2.6
Charging characteristic
1.2.7
Input voltage
V
3 Phase, 380
1.2.8
Input frequency and range
Hz
50
1.2.9
Input power
kVA
1.2.10
Minimum working power factor
1.2.11
Rated output power
1.2.12
Output voltage range:
−
−
kW
V
V
float charge
boost charge
D15.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
48 V D.C System
Unit
Data
Required
1.2.13
−
−
A
A
float charge
boost charge
Accuracy of output voltage
%
1.2.14
Overload range
%
1.2.15
Voltage ripple
%
1.2.16
Ripple frequency
Hz
1.2.17
Means of adjusting output
1.2.18
Details of any forced cooling equipment
for chargers
1.2.19
Ambient temperature range
°C
1.2.20
Ambient relative humidity range
%
1.2.21
Mean time between failure (MTBF)
1.2.22
Overall dimensions (shall be a separate
free-standing panel/cubicle)
mm
1.2.23
Weight
kg
1.2.24
Boost charge maximum permitted
constant potential per cell
V
Boost charge maximum permitted current
as percentage of 5 hour capacity
%
Time to be re-charge to 90% capacity at
maximum permitted voltage and current
hrs
1.2.25
1.2.26
Offered
Continuous output current range:
1.3
Battery Fuse Boxes
1.3.1
Manufacturer
1.3.2
Type designation
1.3.3
Degree of protection
1.3.4
Fuse rated current at 50oC
1.3.5
Remote signalling
Years
IP 51
yes
D15.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
48 V D.C System
Unit
Data
Required
1.4
48 V D.C. Switchboards
1.4.1
Manufacturer
1.4.2
Type designation
1.4.3
Degree of protection
1.4.4
Standards
1.4.5
Rating voltage
V
1.4.6
Rated current of busbars at 50oC ambient
temperature
A
1.4.7
Busbar cross section
1.4.8
Busbar insulation material
1.4.9
Number of circuits
1.4.10
Main isolator rating
A
1.4.11
Main fuse rating
A
1.4.12
Single line diagram number
1.4.13
Arrangement drawing number
1.4.14
Details of Contactors:
−
−
−
−
−
−
−
−
−
1.4.15
IP 51
IEC 60439
48
mm2
Manufacturer
Type designation
Type
Site current rating (at 50°C)
Rated breaking capacity
Short time current (1 s)
Maximum operating time
•
•
Offered
A
kA
kA
msec
msec
opening
closing
Voltage / power coil rating
Typical circuit diagram number
V/W
Details of Earth Fault Protection:
−
−
−
Manufacturer
Type Designation
Brochure number
D15.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D15 – DC SYSTEM - Cont
48 V D.C System
Unit
Data
Required
1.4.16
−
−
−
1.4.17
Offered
Details of Undervoltage / Overvoltage
Protection:
Manufacturer
Type Designation
Brochure number
Instruments
−
−
−
−
Manufacturer
Voltmeter (type)
Ammeter (type)
Instruments
Details of Moulded Case Circuit Breakers
(MCCBs)
−
−
−
−
−
−
−
−
1.4.18
Manufacturer
Type designation
Number of poles
Standards
Rated current at 50°C
Rated short-time withstand current
(1s)
Rated breaking capacity
Remote signalling
A
kA
kA
Yes
Details of Miniature Circuit Breakers
(MCBs)
−
−
−
−
−
−
−
−
Manufacturer
Type designation
Number of poles
Standards
Rated current at 50°C
Rated short-time withstand current
(1s)
Breaking capacity at
Remote signalling
Manufacturer quality system in
accordance with ISO 9000, 9001, 9002,
9003 and 9004
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
A
kA
kA
Yes
Yes
Yes
D15.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D16 - 220 V AC UNINTERRUPTIBLE POWER SUPPLY
Unit
Data
Required
1
Offered
GENERAL
The uninterruptible power supply (UPS)
shall consist but not be limited to the
following items:
− 48 V DC / 220 V AC inverters
yes
− static interrupters and transfer switches
yes
− 220/220 V single phase isolating bypass transformer
yes
−
yes
manual by-pass switch
− UPS distribution board
yes
2
INVERTER
2.1
Manufacturer
2.2
Type designation
2.3
Degree of protection
2.4
Rated output power
2.5
Rated input voltage and range
2.6
Rated input current
A
2.7
Rated output voltage
V
2.8
Steady state voltage variation
%
2.9
Rated output current
A
2.10
Rated output frequency
Hz
2.11
Steady state frequency variation
%
2.12
Total harmonic distortion
%
2.13
Rated output power factor
2.14
Maximum harmonic distortion:
−
−
IP51
VA
min 1200 (to be
confirmed by
calculation)
V±%
%
%
at any single frequency
at all frequencies
D16.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D16 - 220 V AC UNINTERRUPTIBLE POWER SUPPLY - Cont
Unit
Data
Required
2.15
Radio frequency interference (RFI)
classification
2.16
Output voltage rise time on turn-on
ms
2.17
Output voltage decay time on turn-off
ms
2.18
Maximum transient voltage variation after
full load acceptance or rejection for:
− 1 cycle
− 0.1 s
− 1s
Offered
%
%
%
2.19
Method of cooling
2.20
Ambient temperature range
°C
2.21
Maximum temperature rise (inside)
°C
2.22
Ambient relative humidity
%
2.23
Method of protecting inverters against high
intensity D.C voltage surges
2.24
Mean time between failure (MTBF)
2.25
Dimensions
mm
2.26
Weight
kg
3
STATIC SWITCH
Years
A detailed description of offered static
switch with data and diagram to be
provided
4
ISOLATION BY-PASS TRANSFORMER
4.1
Manufacturer
4.2
Standard applied
4.3
Type designation
4.4
Maximum continuous capacity
4.5
Number of phase
1
4.6
Rated voltage under full load
V
VA
D16.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D16 - 220 V AC UNINTERRUPTIBLE POWER SUPPLY - Cont
Unit
Data
Required
4.7
Protection class
Dimensions overall
mm
Total weight
kg
5
MANUAL BY-PASS SWITCH
5.1
Manufacturer
5.2
Type of designation
5.3
Rated current at 50°C
6
DISTRIBUTION BOARD
6.1
Manufacturer
6.2
Type designation
6.3
Degree of protection
6.4
Busbar insulation material
6.5
Number of circuits
6.6
Details of Miniature Circuit Breakers
(MCBs)
−
−
−
−
−
−
−
Offered
IP
A
IP 51
Manufacturer
Type designation
Number of poles
Standards
Rated current at 50oC
Rated breaking capacity
Remote signalling
A
kA
Manufacturer quality system in accordance
with ISO 9000, 9001, 9002, 9003 and 9004
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
yes
yes
D16.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES
132 kV Power Cables
Unit
1
GENERAL
1.1
Name of manufacturer
1.2
Place of manufacture
1.3
Manufacturers type or drawing reference number
1.4
Circuit rating required
1.5
Constructional and Testing standards
Data
Required
Offered
MVA
Standard(s) to which cable complies
1.6
General description of cable
Voltage designation Uo/U(Um)
Number of cores
Conductor size
Conductor material
Type of insulation
Type of metal screen/sheath
Type of armour
Type of oversheath
kV
mm2
aluminium
XLPE
lead
MDPE
1.7
Year of first commercial operation of cable type
2
CONSTRUCTIONAL FEATURES
2.1
Conductor
Material
Nominal cross-section
Type of conductor
Overall diameter
Water blocking method
Semi conducting binder tape
2.2
mm2
aluminium
mm
yes/no
Conductor screen
Type of material
Extruded semi
conductive,
cross-linkable,
fully bonded
Nominal thickness
2.3
one
mm
Insulation
Material
Thickness: Minimum average
Thickness: Minimum at a point
Nominal overall diameter
XLPE
mm
mm
mm
D17.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
132 kV Power Cables
2.4
Unit
Insulation screen
Type of material
Extruded semi
conductive,
cross-linkable
Nominal thickness
2.5
mm
XLPE Manufacturing Methods
-
2.6
Data
Required
Offered
Extrusion line type e.g. CCV
Single pass, triple extrusion
Curing method
Cooling method
yes/no
Bedding (if applicable)
Type and material
2.7
Metallic screen on each core
Type and material
copper wire or
tape
Nominal thickness
Nominal diameter over the screen
2.8
Bedding layer
Type and material
Nominal thickness
Minimum thickness
2.9
mm
mm
Armour
Nominal diameter under the armour
Type and material
Armour wire diameter or dimensions of strip
2.10
mm
mm
mm
mm
Protective anti-corrosion external sheath covering
Type and material
Colour
Nominal thickness
Minimum thickness
Termite resistant
Type of anti-termite protection
MDPE
mm
mm
yes/no
2.11
Nominal overall cable diameter
mm
2.12
Weight of completed cable
kg/m
yes
D17.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
132 kV Power Cables
Unit
3
CURRENT RATINGS
3.1
Maximum continuous rating, direct-buried, assuming:
Ground temperature at burial depth of 35oC
Soil thermal resistivity of 2.5K.m/W
Depth of laying 0.8m
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat formation spaced at one cable diameter (single
point bonded)
Calculation Method
3.2
IEC 60287
A
A
IEC 60287
Maximum continuous rating, in-air, assuming:
Air temperature (in shade) of 50 oC
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat formation spaced at one cable diameter (single
point bonded)
Calculation Method
3.4
Maximum permissible conductor temperature for
continuous operation
3.5
Conductor short circuit capacity
Short circuit current
Duration
Permissible maximum temperature
3.6
A
A
Maximum continuous rating, in single way ducts,
assuming:
Ground temperature at burial depth of 35oC
Soil thermal resistivity of 2.5K.m/W
Depth of laying 0.8m
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat touching formation (single point bonded)
Calculation Method
3.3
Data
Required
Offered
A
A
IEC 60287
o
C
kA
s
o
C
40
3
250
kA
s
o
C
3
200
Screen / armour short circuit capacity
Short circuit current
Duration
Permissible maximum temperature
4
ELECTRICAL CHARACTERISTICS
4.1
DC resistance of conductor at 20ËšC
Ω/m
D17.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
132 kV Power Cables
Unit
4.2
Ω/m
AC resistance of conductor at 50 Hz and maximum
conductor temperature
trefoil touching (solid bonded)
flat formation (single point bonded)
4.3
Positive Sequence Resistance of cable at 50 Hz
trefoil touching (solid bonded)
flat formation (single point bonded)
4.4
Positive Sequence Reactance of cable at 50 Hz
trefoil touching (solid bonded)
flat formation (single point bonded)
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
4.5
Zero Sequence Resistance of cable at 50 Hz in trefoil
touching formation (solid bonded)
Ω/m
4.6
Zero Sequence Reactance of cable at 50 Hz in trefoil
touching formation (solid bonded)
Ω/m
4.7
Capacitance per core
pF/m
5
LOSSES
5.1
Total losses per three phase circuit when operating at
nominal voltage and 50Hz and at the current ratings
stated in Item 2 :
W/m
laid direct in trefoil touching (solid bonded)
laid direct in flat formation (single point bonded)
W/m
W/m
in ducts in trefoil touching (solid bonded)
in ducts in flat touching formation
single point bonded)
in air in trefoil touching (solid bonded)
in air in flat formation (single point bonded)
W/m
W/m
6
INSTALLATION DATA
6.1
Minimum cable bending radius when laid:
Data
Required
Offered
W/m
W/m
During installation
Adjacent to joints and terminations
mm
mm
6.2
Minimum internal diameter of pipes or ducts
mm
6.2
Maximum permissible pulling force of total cable
kN
D17.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
132 kV Power Cables
Unit
7
COMMISSIONING TESTS
7.1
Recommended tests after all terminating and jointing
has been completed but before connection to the
system.
Data
Required
Offered
D17.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
11 kV Power Cables
Unit
1
GENERAL
1.1
Name of manufacturer
1.2
Place of manufacture
1.3
Manufacturers type or drawing reference number
1.4
Circuit rating required
1.5
Constructional and Testing standards
Data
Required
Offered
MVA
Standard(s) to which cable complies
1.6
General description of cable
Voltage designation Uo/U(Um)
Number of cores
Conductor size
Conductor material
Type of insulation
Type of metal screen/sheath
Type of armour
Type of oversheath
kV
mm2
copper
XLPE
1.7
Year of first commercial operation of cable type
2
CONSTRUCTIONAL FEATURES
2.1
Conductor
Material
Nominal cross-section
Type of conductor
Overall diameter
Water blocking method
Semi conducting binder tape
2.2
mm2
Copper
mm
yes/no
Conductor screen
Type of material
Extruded semi
conductive,
cross-linkable,
fully bonded
Nominal thickness
2.3
one
mm
Insulation
Material
Thickness: Minimum average
Thickness: Minimum at a point
Nominal overall diameter
XLPE
mm
mm
mm
D17.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
11 kV Power Cables
2.4
Unit
Insulation screen
Type of material
Extruded semi
conductive,
cross-linkable
Nominal thickness
2.5
mm
XLPE Manufacturing Methods
-
2.6
Data
Required
Offered
Extrusion line type e.g. CCV
Single pass, triple extrusion
Curing method
Cooling method
yes/no
Bedding (if applicable)
Type and material
2.7
Metallic screen on each core
Type and material
copper wire or
tape
Nominal thickness
Nominal diameter over the screen
2.8
Bedding layer
Type and material
Nominal thickness
Minimum thickness
2.9
mm
mm
Armour
Nominal diameter under the armour
Type and material
Armour wire diameter or dimensions of strip
2.10
mm
mm
mm
mm
Protective anti-corrosion external sheath covering
Type and material
Colour
Nominal thickness
Minimum thickness
Termite resistant
Type of anti-termite protection
MDPE
mm
mm
yes/no
2.11
Nominal overall cable diameter
mm
2.12
Weight of completed cable
kg/m
yes
D17.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
11 kV Power Cables
Unit
3
CURRENT RATINGS
3.1
Maximum continuous rating, direct-buried, assuming:
Ground temperature at burial depth of 35oC
Soil thermal resistivity of 2.5K.m/W
Depth of laying 0.8m
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat formation spaced at one cable diameter (single
point bonded)
Calculation Method
3.2
IEC 60287
A
A
IEC 60287
Maximum continuous rating, in-air, assuming:
Air temperature (in shade) of 50 oC
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat formation spaced at one cable diameter (single
point bonded)
Calculation Method
3.4
Maximum permissible conductor temperature for
continuous operation
3.5
Conductor short circuit capacity
Short circuit current
Duration
Permissible maximum temperature
3.6
A
A
Maximum continuous rating, in single way ducts,
assuming:
Ground temperature at burial depth of 35oC
Soil thermal resistivity of 2.5K.m/W
Depth of laying 0.8m
Thermally independent of other cable circuits
trefoil touching (solid bonded)
flat touching formation (single point bonded)
Calculation Method
3.3
Data
Required
Offered
A
A
IEC 60287
o
C
kA
s
o
C
50
1
250
kA
s
o
C
3
200
Screen / armour short circuit capacity
Short circuit current
Duration
Permissible maximum temperature
4
ELECTRICAL CHARACTERISTICS
4.1
DC resistance of conductor at 20ËšC
Ω/m
D17.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
11 kV Power Cables
Unit
4.2
Ω/m
AC resistance of conductor at 50 Hz and maximum
conductor temperature
trefoil touching (solid bonded)
flat formation (single point bonded)
4.3
Positive Sequence Resistance of cable at 50 Hz
trefoil touching (solid bonded)
flat formation (single point bonded)
4.4
Positive Sequence Reactance of cable at 50 Hz
trefoil touching (solid bonded)
flat formation (single point bonded)
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
Ω/m
4.5
Zero Sequence Resistance of cable at 50 Hz in trefoil
touching formation (solid bonded)
Ω/m
4.6
Zero Sequence Reactance of cable at 50 Hz in trefoil
touching formation (solid bonded)
Ω/m
4.7
Capacitance per core
pF/m
5
LOSSES
5.1
Total losses per three phase circuit when operating at
nominal voltage and 50Hz and at the current ratings
stated in Item 2 :
W/m
laid direct in trefoil touching (solid bonded)
laid direct in flat formation (single point bonded)
W/m
W/m
in ducts in trefoil touching (solid bonded)
in ducts in flat touching formation
(single point bonded)
in air in trefoil touching (solid bonded)
in air in flat formation (single point bonded)
W/m
W/m
6
INSTALLATION DATA
6.1
Minimum cable bending radius when laid:
Data
Required
Offered
W/m
W/m
During installation
Adjacent to joints and terminations
mm
mm
6.2
Minimum internal diameter of pipes or ducts
mm
6.2
Maximum permissible pulling force of total cable
kN
D17.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D17 – 132/11 KV POWER CABLES - Cont
11 kV Power Cables
Unit
7
COMMISSIONING TESTS
7.4
Recommended tests after all terminating and jointing
has been completed but before connection to the
system.
Data
Required
Offered
D17.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D18 - LV CABLES
LV Cables
Unit
Data
Required
1
380 VOLT POWER CABLES
1.1
Manufacturer
1.2
Cable type
Cu/XLPE/
SWA/LSOH
1.3
Standards
IEC 60189, 60227,
60228, 60287,
60724, 60811,
60885. BS 6724,
BS EN 50265
1.4
Rated voltage
1.5
Test voltage (1 min)
1.6
Conductor
−
−
−
−
−
Cross sectional area
Material: copper
Design (stranded, sectoral, etc.)
Overall dimensions
No. of Cores
1.7
Insulation
1.8
Fillers
−
1.9
VAC/min
4000
mm2
min 2.5
Cu
Stranded
mm
Material: polypropylene
Type
Nominal thickness
mm
Armour
−
−
−
1.11
600/1000
Armour bedding
−
−
1.10
V
Offered
Type of wire
Number of wire
Diameter of wire
No.
mm
Outer covering
−
−
LSOH
Material
Minimum average thickness
mm
D18.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D18 - LV CABLES - Cont
LV Cables
Unit
Data
Required
1.12
−
−
−
1.13
mm
kg
m
Overall diameter
Weight per metre
Maximum drum length
Cable drums
−
−
−
1.14
Offered
Completed cable
*
m
m
kg
Overall diameter
Width
Weight loaded
Continuous current carrying capacity based
on the conditions specified:
One Circuit
Two Circuits
Three Circuits
A
A
A
Drawn into ducts
−
−
−
*
A
A
A
Laid in the ground
−
−
−
*
A
One Circuit
Two Circuits
Three Circuits
In air
−
One Circuit at 50°C
1.15
Maximum conductor temperature
1.16
Conductor short circuit current
o
C
Carrying capacity for one second,
cable loaded as above prior to short
circuit and final conductor
90
KA
o
C
Temperature of
1.17
Minimum radius of bend around which
cable can be laid
−
−
−
m
m
m
Laid direct
In ducts
In air
D18.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D18 - LV CABLES - Cont
LV Cables
Unit
Data
Required
1.18
−
1.19
mm
*
Per km of cable at 20oC of conductor
ohm
Maximum AC resistance
−
1.21
Nominal internal diameter of pipes or
ducts through which cable may be
pulled
Maximum DC resistance
−
1.20
Offered
Ducts
*
Of conductor per km of cable at
maximum conductor temperature
ohm
Insulation resistance
−
per km of cable per core
Mega
ohm
1.22
Manufacturer quality assurance according
to ISO 9000, 9001, 9002, 9003 and 9004
*
The tenderer may provide a table of data
for each of the cables offered.
1.23
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
2
MULTICORE CONTROL CABLES
2.1
Manufacturer
2.2
Cable type
2.3
Standards
2.4
Rated Voltage
2.5
Test voltage (1 min)
2.6
Cores
−
IEC 60189, 60227,
60228, 60287,
60724, 60811,
60885. BS 6724,
BS EN 50265
Number of cores
V
600/1000
V AC/min
4000
No
2, 3, 4,7, 12, 19,
27, 37
D18.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D18 - LV CABLES - Cont
LV Cables
Unit
Data
Required
2.7
−
−
2.8
LSOH
Type
Nominal thickness
mm
Number of wire:
Diameter of wire
No.
mm
LSOH
Material:
Minimum average thickness
mm
Overall diameter
Weight per metre
Maximum drum length
mm
kg
m
Mean electrostatic capacity
−
−
2.14
mm
mm
Completed cable
−
−
−
2.13
Thickness nominal
Minimum
Outer covering
−
−
2.12
XLPE
Armour
−
−
2.11
mm2
Armour bedding
−
−
2.10
Cross sectional area: annealed copper
Material
Insulation
−
−
2.9
Offered
Conductor
*
*
*
*
of each conductor to earth per km
of each core at 20°C
pF
Maximum DC resistance
−
−
−
per km of each core at 20°C max.
1.5mm2
2.5mm2
2.15
Minimum radius of bend round which cable
can be laid
2.16
Manufacturer quality assurance according
to ISO 9000, 9001, 9002, 9003 and 9004
ohm
ohm
mm
D18.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D18 - LV CABLES - Cont
LV Cables
Unit
Data
Required
2.17
*
Offered
Type test certificate to be issued by
independent laboratory or independently
witnessed type test certificate available
The tenderer may provide a table of data
for each of the cables offered.
D18.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM
General Protection Requirements
Unit
Data
Required
Offered
1
OPERATING PERAMETERS
1.1
Auxiliary voltage range (Vn = 110Vdc)
Vdc
77→150
1.2
Input frequency range (50Hz nominal)
Hz
47.5→52.5
2
TYPE TESTS
2.1
Atmospheric Environment
2.2
2.3
Operation -25C and 55C for 96hrs, IEC 60068-2-1
Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93%
Yes
Tested to IEC 60068-2-78 with severity class 56 days
Yes
Enclosure
IEC 60529
2.4
IP50
Mechanical Environment
Vibration
Shock and bump
Seismic
2.5
Yes
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
Yes
Yes
Yes
Insulation
Rated insulation
1000 V high impedance protection CT inputs
250 V for other circuits
Yes
1000 V open contact withstand
Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1
Yes
Impulse voltage
IEC 60255-5 test voltage 5 kV
Yes
D19.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
General Protection Requirements
2.6
Unit
Data
Required
Offered
Electromagnetic Compatibility
1 MHz Burst disturbance tes
IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
Yes
IEC 60255-22-2 severity class III
Radiated Electromagnetic Field Disturbance
Yes
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Electromagnetic Emissions
Yes
IEC 60255-25
Fast Transient Disturbance
As
appropriate
IEC 60255-22-4 severity level IV
D19.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Distance Protection
Unit
Data
Required
Offered
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR BASED,
NUMERICAL)
4
DISTANCE PROTECTION REQUIREMENTS
4.1
3 zone ph-ph & ph-E
4.2
Phase fault & Earth fault characteristic shapes (Mho, Quad)
4.3
Operating time
4.4
Switch On To Fault
Yes
4.5
Power swing blocking (depending on relaying point in the
power system)
Yes
4.6
Voltage transformer supervision
Yes
4.7
Time delays for all zones
Yes
4.8
Zone enable/disable for all zone
Yes
4.9
Teleprotection modes PUR/POR/Block (Selectable)
Yes
4.10
DEF plain & Blocking modes (Selectable)
Yes
4.11
Z1 min and max operating time (mid zone)
5
OTHER REQUIREMENTS
5.1
Thermal overload, (49)
Yes
5.2
Circuit breaker failure. 50BF- (dependent on application)
Yes
5.3
Event recording function
Yes
5.4
Disturbance recording function
Yes
5.5
Fault locator function
Yes
5.6
Integral operator interface for local interrogation
Yes
5.7
Programmable scheme logic
Yes
Numerical
Yes
<30ms
ms
<30
D19.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Distance Protection
Unit
5.8
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
5.9
Tripping contacts rating
Carry continuous
Make
Break dc
5A
30A maximum for 0.2s
50W resistive
25W inductive(L/R40ms)
Data
Required
Offered
Yes
Yes
5.10
Self checking facility
Yes
5.11
Integral intertrip send and receive, with external input
interface
Yes
Intertrip send and receive operate time
6
COMMUNICATIONS
6.1
Protection
Direct optical fibre
Others (please list)
6.2
1300nm single mode
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 60870-5-103
others
6.3
Yes
TYPE TEST CERTIFICATE PROVIDED
Yes
Yes
D19.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Feeder Differential Protection
Unit
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR BASED,
NUMERICAL)
4
FEEDER DIFFERENTIAL PROTECTION REQUIREMENTS
4.1
Fault settings (% of relay rating)
4.2
Minimum current at one feeder end for relay operation at
that end:
(a)
(b)
4.3
Data
Required
Offered
Numerical
Phase faults
Earth faults
Minimum current at one feeder end for relay operation at
both feeder ends:
(a)
(b)
Phase faults
Earth faults
4.4
Effect of load current on settings given in 3.5, 3.6 above
4.5
Operating time at 5 x setting
4.6
Maximum primary out-of-zone fault current at which
protection is stable
4.7
Insulation level between pilot wires and relay equipment
45ms
15 kV
5
PILOT WIRE REQUIREMENTS:
5.1
Number of cores
5.2
Insulation level between cores
5.3
Insulation level between cores and cable sheath
5.4
Any other requirements
6
PILOT WIRE SUPERVISION
Yes
Check Relay (Setting ranges - Ph F 0.4In – 2.0In, EF 0.2In –
0.8In)
Yes
7
TWO WAY INTERTRIP FUNCTION
D19.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Feeder Differential Protection
8
Unit
Data
Required
Offered
TRIPPING CONTACTS RATING
Carry continuous
Make
Break dc
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
9
SELF-MONITORING
10
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Main Transformer Biased Differential Protection
Unit
Data
Required
Offered
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR BASED,
NUMERICAL)
4
BIASED DIFFERENTIAL FUNCTION
4.1
Operation time at 5 times setting
4.2
Adjustable bias characteristics
Yes
4.3
Differential current stage Id >>
Yes
4.4
Magnetisation inrush restraint
Yes
4.5
“5th” Harmonic inrush restraint
Yes
4.6
Maximum through fault current for which relay remains
stable (multiple of rating)
4.7
CT ratio and vector group compensation
5
RESTRICTED EARTH FAULT FUNCTION
5.1
HV REF
Not used
5.2
LV REF
Not used
5.3
Principle of operation
numerical
ms
<25
High
High impedance/Low impedance
5.4
Metrosil requirements
5.5
Operation time at 5 times settings
6
OTHER REQUIREMENTS
6.1
Phase overcurrent function 50/51 (requirement depending
on application)
6.2
Earth fault protection 51N (requirement depending on
application)
6.3
Integral operator interface for local interrogation
Yes
6.4
Programmable scheme logic
Yes
ms
<30
D19.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Main Transformer Biased Differential Protection
6.5
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
6.6
Tripping contacts rating
Carry continuous
Make
Break dc
Unit
Data
Required
Offered
Yes
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
6.7
Event recording function
Yes
6.8
Disturbance recording function
Yes
6.9
Fault recording function
Yes
6.10
Self monitoring and alarm facility
6.11
Integral intertrip send and receive
7
COMMUNICATIONS
7.1
Control
7.2
Communication ports (Front/rear etc)
7.3
Physical links (RS485/Fibre optic)
7.4
Protocols supported
•
•
8
Yes
IEC 60870-5-103
others
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Low Impedance Busbar Protection Including Breaker Failure
Protection
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR-BASED,
NUMERICAL)
Unit
Data
Required
Offered
Numerical
State principle of operation, i.e. low impedance
Low Z
4
LOW IMPEDANCE BUSBAR PROTECTION INCLUDING
BREAKER FAILURE PROTECTION FUNCTIONS
4.1
Integral check zone feature (state principle of operation)
Yes
4.2
Distributed Bay Modules and Central Unit (Y/N)
Yes
4.3
Maximum number of Bays
4.4
Isolator replica
4.5
CT saturation detector and stabilisation
4.5
Integral CT supervision
4.6
CT matching functions
4.7
Phase segregated protection
4.8
Sensitivity
(a) Phase faults
(b) Earth faults
A sec’y
A sec’y
4.9
Operating time at 5 x fault setting
4.10
Two stage Circuit Breaker Failure
Adjustable current setting
Adjustable time delays per stage
5
OTHER REQUIREMENTS
5.1
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
5.2
Tripping contacts rating
Carry continuous
Make
Break dc
ms
30
Yes
Yes
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
D19.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Low Impedance Busbar Protection Including Breaker Failure
Protection
5.3
Event recording function
Unit
Data
Required
Offered
Yes
5.4
Disturbance recording function
5.5
Self monitoring and alarm facility
6
COMMUNICATIONS
6.1
Bay to central Module communication
f.o.
6.2
Integral operator interface for local interrogation
Yes
7
CONTROL
7.1
Communication ports (Front/rear etc)
7.2
Physical links (RS485/Fibre optic)
7.3
Protocols supported
•
•
8
Yes
Yes
IEC 60870-5-103
others
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Multi-Functional Overcurrent & Earth Fault Protection
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR-BASED,
NUMERICAL)
4
MULTI-FUNCTIONAL OVERCURRENT & EARTH FAULT
PROTECTION FUNCTIONS
4.1
Number of phase CT inputs
4.2
Number of earth fault CT inputs
4.3
Standard, Very and Extreme Inverse and definite time
characteristics curves conforming to IEC 60255
4.4
Number of inverse overcurrent functions (per phase)
4.5
Number of high set overcurrent functions (per phase)
4.6
Number of low set overcurrent functions (per phase)
4.7
Number of inverse earth fault functions
4.8
Number of high set earth fault functions
4.9
Number of low set earth fault functions
4.10
Number of group settings
4.11
Earth fault element suitable of high impedance REF (with
external resistor)
4.12
Operating time at 5 x setting when configured for REF
4.13
Suitable for Blocked Overcurrent busbar protection scheme
5
OTHER FUNCTIONS PROVIDED
•
•
5.1
Unit
Data
Required
Offered
Numerical
Yes
Yes
ms
30
Yes
Y/N
Y/N
Thermal overload 49
Directional OC&EF
Number of output relays
•
•
Rated for tripping
Rated for control and alarm
5.2
Integral metering functions
Yes
5.3
Opto-isolator inputs
Yes
D19.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Multi-Functional Overcurrent & Earth Fault Protection
5.4
Programmable scheme logic
5.5
Event and Fault recording functions
5.6
Self-monitoring facility
5.7
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
5.8
Tripping contacts rating
Carry continuous
Make
Break dc
COMMUNICATIONS
6.1
Integral operator interface for local interrogation
7
CONTROL
7.1
Communication ports (Front/rear etc)
7.2
Physical links (RS485/Fibre optic)
7.3
Protocols supported
8
Data
Required
Offered
Yes
Yes
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
6
•
•
Unit
Yes
Yes
IEC 60870-5-103
others
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Multi-Functional Directional Overcurrent & Earth Fault Protection
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR-BASED,
NUMERICAL)
4
MULTI-FUNCTIONAL DIRECTIONAL OVERCURRENT &
EARTH FAULT PROTECTION FUNCTIONS
4.1
Number of phase CT inputs
4.2
Number of earth fault CT inputs
4.3
Three phase VT input
4.4
Method of determining zero sequence voltage
•
•
Unit
Data
Required
Offered
Numerical
Yes
Y/N
Y/N
Broken delta VT input
Derived mathematically
4.5
Standard, Very and Extreme Inverse and definite time
characteristics curves conforming to IEC 60255
Yes
4.6
Number of inverse DOC overcurrent functions (per phase)
4.7
Number of high set DOC functions (per phase)
4.8
Number of low set DOC functions (per phase)
4.9
Number of inverse DEF functions
4.10
Number of high set DEF functions
4.11
Number of low set DEF functions
4.12
Number of group settings
5
OTHER FUNCTIONS PROVIDED
5.1
•
Non-directional overcurrent 50/51
Y/N
5.2
•
Non-directional earth fault 50 N/51 N
Y/N
5.3
•
Thermal overload 49
Y/N
5.4
•
Suitable for Blocked Overcurrent busbar protection
scheme
D19.13
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Multi-Functional Directional Overcurrent & Earth Fault Protection
5.5
•
5.6
Number of output relays
•
•
Unit
Data
Required
Offered
Earth fault element suitable of high impedance REF
(with external resistor)
Rated for tripping
Rated for control and alarm
5.7
Integral metering functions
Yes
5.8
Opto-isolator inputs
Yes
5.9
Programmable scheme logic
Yes
5.10
Event and Fault recording functions
5.11
Self-monitoring facility
5.12
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
5.13
Tripping contacts rating
Carry continuous
Make
Break dc
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
6
COMMUNICATIONS
6.1
Integral operator interface for local interrogation
7
CONTROL
7.1
Communication ports (Front/rear etc)
7.2
Physical links (RS485/Fibre optic)
7.3
Protocols supported
•
•
8
Yes
Yes
Yes
IEC 60870-5-103
Others
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.14
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Differential Protection and Back-Up Distance
Unit
Data
Required
Offered
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR BASED,
NUMERICAL)
4
DIFFERENTIAL PROTECTION REQUIREMENTS
4.1
Phase segregated protection
Yes
4.2
Ratio and Vector correction for CTs
Yes
4.3
Adjustable biased differential protection characteristic
Yes
4.4
Sensitivity:
-
Numerical
For phase faults
For earth faults
4.5
Operating time
ms
<30
5
DISTANCE PROTECTION REQUIREMENTS
5.1
Zone ph-ph & ph-E
5.2
Phase fault & Earth fault characteristic shapes (Mho, Quad)
5.3
Operating time
5.4
Switch On To Fault
Yes
5.5
Power swing blocking (depending on relaying point in the
power system)
Yes
5.6
Voltage transformer supervision
Yes
5.7
Time delays for all zones
Yes
5.8
Zone enable/disable for all zones
Yes
6
OTHER REQUIREMENTS
6.1
Thermal overload, 49 – (requirement if cable overtemperature unsuitable for tripping)
Yes
6.2
Circuit breaker failure. 50BF- (dependent on application)
Yes
6.3
Event recording function
Yes
6.4
Disturbance recording function
Yes
Yes
<30ms
D19.15
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Differential Protection and Back-Up Distance
Unit
Data
Required
Offered
Yes
6.5
Fault locator function
6.6
Integral operator interface for local interrogation
Yes
6.7
Programmable scheme logic
Yes
6.8
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
Yes
6.9
Tripping contacts rating
Carry continuous
Make
Break dc
5A
30A maximum for 0.2s
50W resistive
25W inductive(L/R40ms)
Yes
6.10
Self checking facility
Yes
6.11
Integral intertrip send and receive, with external input
interface
Yes
7
COMMUNICATIONS
7.1
Protection
Direct optical fibre
7.2
1300nm single mode
Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
ƒ
ƒ
8
IEC 60870-5-103
others
Yes
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.16
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Restricted Earth Fault Protection
Unit
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR-BASED,
NUMERICAL, E-M)
4
RESTRICTED EARTH FAULT PROTECTION FUNCTIONS
4.1
Estimated minimum fault setting (% of CT rating)
%
4.2
Operating time at 5 x setting
ms
4.3
State principle of operation,
•
•
Metrosils provided
4.5
Self monitoring (excluding EM)
4.6
User-friendly HMI, Windows based software for relay setting,
relay configuration and event, disturbance and fault record
management.
4.7
Tripping contacts rating
Carry continuous
Make
Break dc
Yes
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
4.8
Communications (numerical relays)
4.9
Integral operator interface for local interrogation
5
CONTROL
5.1
Communication ports (Front/rear etc)
5.2
Physical links (RS485/Fibre optic)
Yes
Protocols supported
•
•
6
Numerical
H = high impedance
L = low impedance
4.4
5.3
Data
Required
Offered
Yes
IEC 60870-5-103
others
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.17
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Trip Circuit Supervision
Unit
Data
Required
Offered
1
MANUFACTURER
2
TYPE REFERENCE
3
RELAY DESIGN (MICROPROCESSOR, BASED
NUMERICAL)
4
TRIP CIRCUIT SUPERVISION FUNCTIONS
4.1
Operating time
4.2
Supervision of the whole trip circuit with CB open and
closed.
Yes
4.3
Relay operated indicator
Yes
5
TYPE TEST CERTIFICATE PROVIDED
Yes
Numerical
ms
D19.18
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D19 - PROTECTION SYSTEM - Cont
Multi-Contact Tripping Relays
Unit
1
MANUFACTURER
2
TYPE REFERENCE
3
MULTI-CONTACT TRIPPING RELAYS FUNCTIONS
3.1
Operating time
3.2
Is relay mechanically latched or self resetting?
3.3
Method used to reset latched relay (hand or electrical)
3.4
Burden at rated voltage
3.5
Minimum voltage at which reliable operation occurs
3.6
Tripping contacts rating
Carry continuous
Make
Break dc
ms
Data
Required
Offered
<12
5A
30A maximum for 0.2s
50W resistive
25W inductive (L/R40ms)
3.7
Relay operated indicator type
4
TYPE TEST CERTIFICATE PROVIDED
Yes
D19.19
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM
Substation Control System
Unit
Data
Required
Offered
Yes
1
SUBSTATION CONTROL SYSTEM
2
MASTER CONTROL UNIT
2.1
Substation Computer
2.1.1
Manufacturer
Yes
2.1.2
Model
Yes
2.1.3
Processor
2.1.4
Type
2.1.5
Word length
Bits
2.1.6
Clock speed (minimum)
MHz
2.1.7
Memory size
2.1.8
Supplied (minimum)
Mb
2.1.9
Supportable/expandable
Gb
2.1.10
Hard disk size
2.1.11
Supplied (minimum)
Gb
2.1.12
Supportable/expandable
Gb
2.1.13
Optical Storage
2.1.14
Operating system
2.1.15
Software supplied
2.1.16
Operating temperature range
°C
2.1.17
Maximum relative humidity
%
2.1.18
Nominal voltage
2.1.19
Operating frequency
Hz
2.1.20
Starting current
A
2.1.21
Power requirement
W
2.1.22
Mean time between failure
h
2.1.23
Mean time to repair
h
2.2
Gateway
2.2.1
Manufacturer
Yes
V ac
Yes
D20.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
Data
Required
Offered
2.2.2
Model
Yes
2.2.3
Processor
2.2.4
Type
2.2.5
Word length
Bits
2.2.6
Clock speed (minimum)
MHz
2.2.7
Memory size
2.2.8
Supplied (minimum)
Mb
2.2.9
Supportable/expandable
Gb
2.2.10
Hard disk size
2.2.11
Supplied (minimum)
Gb
2.2.12
Supportable/expandable
Gb
2.2.13
Communication Protocols To Control Centre(s)
2.2.14
NCC Main IEC 60870-5-101
Yes
2.2.15
NCC Alt IEC 60870-5-101
Yes
2.2.16
NCC TCP/IP Intranet
Yes
2.2.17
DCC Main IEC 60870-5-101
Yes
2.2.18
DCC Alt IEC 60870-5-101
Yes
2.2.19
NCC IEC 60870-5-104
Yes
2.2.20
DCC IEC 60870-5-104
Yes
2.2.21
Communication Protocols in Substation
2.2.22
NCC IEC 60870-5-103
Yes
2.2.23
DCC IEC 60870-5-103
Yes
2.2.24
NCC IEC 60870-5-101
Yes
2.2.25
DCC IEC 60870-5-101
Yes
2.2.26
List other operating Protocols
2.2.28
V.35 interface at 64Kb/s
Yes
2.2.29
X.21 / V.11 interface at 64Kb/s
Yes
2.2.30
Operating system
D20.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
Data
Required
Offered
2.2.31
Operating temperature range
°C
2.2.32
Maximum relative humidity
%
2.2.33
Nominal voltage
2.2.34
Operating frequency
Hz
2.2.35
Starting current
A
2.2.36
Power requirement
W
2.2.37
Mean time between failure
h
2.2.38
Mean time to repair
h
2.3
Operator Workstations / HMI
2.3.1
Manufacturer
Yes
2.3.2
Model
Yes
2.3.3
Literature reference for principle of operation
Yes
2.3.4
Processor
2.3.5
Type
2.3.6
Word length
Bits
2.3.7
Clock speed (minimum)
MHz
2.3.8
Memory size
2.3.9
Supplied (minimum)
Mb
2.3.10
Supportable/expandable
Gb
2.3.11
Hard disk size
2.3.12
Supplied (minimum)
Gb
2.3.13
Supportable/expandable
Gb
2.3.14
Optical Storage
2.3.15
Pointer Device
2.3.16
Operating system
2.3.17
Operator interface screens
2.3.18
Operating temperature range
°C
2.3.19
Maximum relative humidity
%
V dc
Yes
D20.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
Data
Required
Offered
2.3.20
Nominal voltage
V ac
2.3.21
Operating frequency
Hz
2.3.22
Starting current
A
2.3.23
Power requirement
W
2.3.24
Mean time between failure
h
2.3.25
Mean time to repair
h
2.3.26
Operator Desk
Yes
2.3.27
Manufacturer
Yes
2.3.28
Type of construction
2.3.29
Finish and material of working surfaces
2.3.30
Method of mounting VDUs
2.3.31
Number
2.3.32
Operator Chairs
2.3.33
Manufacturer
2.3.34
Type of construction
2.3.35
Type of upholstery
2.3.36
Number
2.4
Colour Visual Display Units (VDUs)
2.4.1
Manufacturer
Yes
2.4.2
Model
Yes
2.4.3
Literature reference for principle of operation
Yes
2.4.4
Screen size across diagonal
mm
2.4.5
Usable display area
mm
2.4.6
Resolution (minimum)
2.4.7
Dot pitch
mm
2.4.8
Operating temperature range
°C
2.4.9
Operating relative humidity range
%
2.4.10
Nominal voltage
pixels
V ac
D20.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
Data
Required
Offered
2.4.11
Operating frequency
Hz
2.4.12
Starting current
A
2.4.13
Power requirement
W
2.4.14
Approximate lifetime of monitor under continuous use
h
2.4.15
Mean time between failure
h
2.4.16
Mean time to repair
h
2.5
Substation Local Area Network (LAN)
2.5.1
Architecture and Technology
Yes
2.5.2
Literature reference for principle of operation
Yes
2.5.3
Transmission medium (e.g. optical fibre) and physical
specification
2.5.4
Protocols
2.5.5
IEC 60870-5-101
2.5.6
IEC 60870-5-104
2.5.7
IEC 61850
2.5.8
List all other protocols
2.5.9
Data transmission rate(s)
2.5.10
Mbps
Physical arrangement - Identify all main elements in the
supply including hubs, concentrators, bridges, routers,
gateways switches etc. and the number of each
2.5.11
For each element of the LAN indicate the
2.5.12
No and type of ports
2.5.13
% of spare for each type of port
2.5.14
2.5.15
Yes
Management software package, functions and facilities,
and hardware platform
% Loading under various system activity scenarios
including
2.5.16
normal loading for performance testing
%
2.5.17
high loading for performance testing
%
2.5.18
system power up
%
2.5.19
main server fail-over and database resynchronisation
2.5.20
Overall availability
%
D20.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
2.6
Individual Elements
2.6.1
For each element of the LAN equipment provide the
following information
2.6.2
Manufacturer
2.6.3
Type
2.6.4
Nominal voltage
2.6.5
Power requirements
2.6.6
Range of ambient temp. and max relative humidity for
continuous reliable operation
2.6.7
Mean time between failures
2.6.8
Mean time to repair
2.7
Printers
2.7.1
Logging Printer
2.7.2
Manufacturer
2.7.3
Model
2.7.4
Literature reference for principle of operation
2.7.5
Number
2.7.6
Mounting arrangement
2.7.7
Method of printing (e.g. ink jet)
2.7.8
Print speed
2.7.9
Paper feed mechanism
2.7.10
Number of columns (minimum)
2.7.11
Operating temperature range
°C
2.7.12
Maximum relative humidity
%
2.7.13
Nominal voltage
2.7.14
Operating frequency
Hz
2.7.15
Power requirement
W
2.7.16
Max noise level at 1 m
2.7.17
Mean time between failure
h
2.7.18
Mean time to repair
h
Data
Required
Offered
V ac
W
o
C
%RH
Yes
ppm
V ac
dB(A)
D20.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20- SUBSTATION CONTROL SYSTEM - Cont
Substation Control System
Unit
Data
Required
Offered
2.7.19
Colour Printers
2.7.20
Manufacturer
Yes
2.7.21
Model
Yes
2.7.22
Literature reference for principle of operation
Yes
2.7.23
Number
2.7.24
Mounting arrangement
2.7.25
Print speed (minimum)
2.7.26
Technology
2.7.27
Resolution
2.7.28
Paper size
2.7.29
Sheet feed paper tray capacity
2.7.30
Internal memory (minimum)
Mb
2.7.31
Operating temperature range
°C
2.7.32
Maximum relative humidity
%
2.7.33
Nominal voltage
2.7.34
Operating frequency
Hz
2.7.35
Power requirement
W
2.7.36
Max noise level at 1 m
2.7.37
Mean time between failure
h
2.7.38
Mean time to repair
h
ppm
dpi
Sheets
V ac
dB(A)
D20.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
Data
Required
Offered
3
BAY CONTROL UNIT HARDWARE
3.1
General
Yes
3.1.1
Manufacturer
Yes
3.1.2
Module designation
Yes
3.1.3
Literature reference for principle of operation
Yes
3.1.4
Power supply
3.1.5
Power requirements
3.1.6
Maximum Number of expansion modules
3.1.7
Mean-time to repair for each type of RTU
H
3.1.8
Mean-time between failure for each type of RTU
H
3.1.9
Local LCD Display
3.1.10
Operating temperature range
3.1.11
Operating relative humidity range
3.2
BCU Enclosure
3.2.1
Manufacturer
3.2.2
Module designation
3.2.3
Literature reference for enclosure
3.2.4
Weight
3.2.5
Dimensions
3.2.6.0
Degree of protection
3.2.6.1
Flush Mounted housing
3.2.6.2
Surface mounted housing
3.3
IEC Standards ( Or Equivalent )
3.3.1
EMC Type tests (Provide Class/Level or Severity
rating)
3.3.2
EMC Compliance IEC 60255-22-3
3.3.3
Dielectric withstand test IEC 60255--5
3.3.4
High Voltage impulse test IEC 60255-5
3.3.5
Fast transient disturbance test IEC 61000-4-4 and
60255-22-4
V dc
110
W
°C
0 – 50
D20.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.3.6
Oscillatory transient IEC 61000-4-12
3.3.7
Radiated immunity test IEC 61000-4-6 and 60255-22-3
3.3.8
Electrostatic discharge test IEC 61000-4-2 and 6025522-2
3.3.9
1 MHz Burst disturbance test to IEC 60255-22-1
3.3.10
Electromagnetic emissions to IEC 60255-25
3.3.11
Emitted interference test IEC 61000-4-3
3.3.12
Mechanical test Compliance
3.3.13
Vibration test IEC 60255-21-1
3.3.14
Shock test IEC 60255-21-2
3.3.15
Seismic test IEC 60255-21-3
3.3.16
Temperature rise test IEC 60068-2-1 and 2-2
3.3.15
Relative humidity test 60068-2-78
3.3.16
Enclosure test to IEC 60529 IP50
3.4
BCU Functions
3.4.1
The monitoring functions include:
3.4.2
Switching status monitoring (breakers)
3.4.3
Indication & alarm status monitoring
3.4.4
Analogue measurements (currents, voltages, etc.)
3.4.5
Resolution of time tagging
3.4.6.0
The control functions include:
3.4.6.1
Close / open of circuit breakers
3.4.6.2
Close / Open of isolators / disconnectors
3.4.6.3
Transformer Automatic tap change control
3.4.6.4
Breaker Voltage Synchronisation Check Control
3.4.6.5
Bay interlocking facilities
3.4.7
The reporting functions include:
3.4.7.1
Sequence of Events recording
3.4.7.2
Post – Mortem Review / Fault waveform capture
ms
Data
Required
Offered
1
D20.9
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.4.7.3
Tenderers to state memory capacity and functionality
of Sequence of events and fault waveform capture
3.5
BCU Configuration
3.5.1
Number of processors
3.5.2
Main processor
3.5.3
Secondary processors
3.5.4
Communication processor (module)
3.5.5
Type of communication between processors
3.5.6
LCD Display and selector Buttons on front of BCU
3.5.6.1
Functionality to include
3.5.6.2
Full control of circuit bay
3.5.6.3
Status of bay plant
3.5.6.4
Circuit active line diagram
3.5.6.5
Power system Measurements
3.5.6.6
Display alarms and events
3.6
Processing Units
3.6.1
Main CPU
3.6.2
Manufacturer
3.6.3
Module designation
3.6.4
Literature reference for principle of operation
3.6.5
Mean - time between failure
h
3.6.6
Power requirements
W
3.6.7
Type of processor
3.6.8
Word length
bit
3.6.9
Clock speed
MHz
3.6.10
Kinds of memory used:
3.6.10.1
Type, size and extension capabilities
KByte
3.6.10.2
Type, size and extension capabilities
Kbytes
3.6.10.3
Type, size and extension capabilities
Kbytes
Data
Required
Offered
Yes
D20.10
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.7
Secondary CPU
3.7.1
Manufacturer
3.7.2
Module designation
3.7.3
Literature reference for principle of operation
3.7.4
Mean - time between failure
h
3.7.5
Power requirements
W
3.7.6
Type of processor
3.7.7
Word length
bit
3.7.8
Clock speed
MHz
3.7.9
Kinds of memory used:
3.7.9.1
Type, size and extension capabilities
Kbytes
3.7.9.2
Type, size and extension capabilities
Kbytes
3.7.9.3
Type, size and extension capabilities
Kbytes
3.8
Communications
3.8.1
Manufacturer
3.8.2
Module designation
3.8.3
Literature reference for principle of operation
3.8.4
Number of communications channels
3.8.5
Type of processor
3.8.6
Word length
3.8.7
Clock speed
3.8.8
Type and size of memory
3.8.9
Line interface to communication channel
3.8.10
Kinds of memory used:
3.8.11
Number and type of communication ports
3.8.12
Meantime between failure
h
3.8.13
Power requirement
W
3.8.14
Communication Interfaces
Data
Required
Offered
Yes
bit
MHz
B/s
D20.11
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
Data
Required
Offered
3.8.14.1
IEC60870-5-101 direct to Control Centre(s)
3.8.14.2
IEC60870-5-103 interface to protection IED
3.8.14.3
IEC61850 interface to substation LAN
3.8.14.4
IEC60870-5-101 for remote downloading of BCU data
3.8.14.5
List all Protocols available at BCU
3.8.15
Local interface for Laptop Computer
3.8.16
IED interface
3.8.16.1
List of manufactures the BCU has interfaced
Yes
3.8.16.2
Standard communication protocols available
Yes
3.8.16.3
Optional communication protocols available
Yes
3.9
Power Supply Module
3.9.1
Module designation
3.9.2
Literature reference for principle of operation
3.9.3
Maximum number of modules per processor
3.9.4
Nominal Input voltage
3.9.5
Operating voltage range
3.9.6
Power requirement
3.9.7
Isolation
3.9.8
Meantime between failure
h
3.9.9
Power requirement
W
3.10
Digital Input Module
3.10.1
Module designation
3.10.2
Literature reference for principle of operation
3.10.3
Maximum number of modules per processor
3.10.4
Input voltage
3.10.5
Is contact input type configurable as
3.10.5.1
Status and alarms
3.10.5.2
Sequence of events
VDC
W
V dc
D20.12
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.10.5.3
BCD or parallel inputs
3.10.5.4
Pulse accumulator
3.10.5.5
Or any combination of these
3.10.6
Standard number of inputs per module:
3.10.6.1
double position
3.10.6.2
single position
3.10.7
Type of input circuit isolation
3.10.8
Input galvanic separation
3.10.9
Impulse voltage withstand
kV
3.10.10
Scan time
ms
3.10.11
Minimal pulse duration
ms
3.10.12
Input impedance
3.10.13
Filter time constant
3.10.14
Meantime between failure
h
3.10.15
Power requirement
W
3.11
Pulse Counting Module
3.11.1
Is this facility incorporated into the digital input module?
3.11.2
Module designation
3.11.3
Literature reference for principle of operation
3.11.4
Maximum number of modules per processor
3.11.5
Type of counter
3.11.6
Maximum count
3.11.7
Storage and resetting under control of external clock?
3.11.8
Number of inputs per module
3.11.9
Input current
3.11.10
Impulse voltage withstand
kV
3.11.11
Signal range : pulse widths
ms
3.11.12
Meantime between failure
h
Data
Required
Offered
ohm
ms
mA
D20.13
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.11.13
Power requirement
3.12
Command Output Module
3.12.1
Module designation
3.12.2
Literature reference for principle of operation
3.12.3
Maximum number of modules per processor
3.12.4
Contact ratings
3.12.4.1
Switched voltage
V
3.12.4.2
Switched power
VA max
3.12.4.3
Switched current
A
3.12.4.4
Range of duration of command output
S
3.12.5
Number of two position output channel per module
3.12.6
3.12.7
Data
Required
Offered
W
Are outputs activated by select-check-actuate
procedure?
Are welded contacts checked prior to command
output?
3.12.8
Are the outputs fused and fuse status monitored?
3.12.9
Impulse voltage withstand
kV
3.12.10
Meantime between failure
h
3.12.11
Power requirement
W
3.13
Digital Output Module
3.13.1
Module designation
3.13.2
Literature reference for principle of operation
3.13.3
Number of outputs per module
3.13.4
Maximum number of modules per processor
3.13.5
Maximum output current
3.13.6
Maximum switched output voltage
V
3.13.7
Impulse voltage withstand
kV
3.13.8
Type of protection against back EMF
kV
3.13.9
Command duration adjustable in the range
s
3.13.10
Meantime between failure
h
mA
D20.14
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.13.11
Power requirement
3.14
Analogue to digital conversion module
3.14.1
Module designation
3.14.2
Literature reference for principle of operation
3.14.3
Number of inputs per module
3.14.4
Maximum number of modules per processor
3.14.5
Resolution
3.14.6
Accuracy
%
3.14.7
Common mode noise rejection
dB
3.14.8
Normal mode noise rejection
dB
3.14.9
Conversion time
ms
3.14.10
Scanning time (per channel)
ms
3.14.11
Meantime between failures
h
3.14.12
Power requirement
W
3.15
Analogue Input Module
3.15.1
Module designation
3.15.2
Literature reference for principle of operation
3.15.3
Maximum number of modules per processor
3.15.4
Scanning resolution
3.15.5
Accuracy
3.15.6
How are overflow and conversion failures dealt with?
3.15.7
Conversion time
3.15.8
Input filter attenuation at 50 Hz
3.15.9
Input signal types (e.g. 4-20 mA)
3.15.10
Method of isolation
3.15.11
Impulse voltage withstand
3.15.12
Input impedance
3.15.13
Type of ADC switching
Data
Required
Offered
W
bits
bits
%
dB
kV
ohm
D20.15
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.15.14
Standard number of inputs per module
3.15.15
Meantime between failure
h
3.15.16
Power requirement
W
3.16
Analogue Output Module
3.16.1
Module designation
3.16.2
Literature reference for principle of operation
3.16.3
Number of outputs per module
3.16.4
Maximum number of modules per processor
3.16.5
Output voltage range
V
3.16.6
Output current range
mA
3.16.7
Type of isolation
3.16.8
Load resistance range
3.16.9
Maximum error over-current ranges
%
3.16.10
Impulse voltage withstand
kV
3.17
Direct AC Connection Voltage
3.17.1
Module designation
3.17.2
Literature reference for principle of operation
3.17.3
Maximum number of modules processor
3.17.4
Number of inputs per module
3.17.5
Input voltage ranges
3.17.6
Input filter attenuation at 50 Hz
dB
3.17.7
Burden on instrument transformer circuit
VA
3.17.8
Conversion time
ms
3.17.9
Scanning resolution
bits
3.17.10
Accuracy
3.17.11
What calculations are supported?
3.17.12
How are overflow and conversion failures dealt with?
3.17.13
Method of isolation
Data
Required
Offered
ohms
V ac
%
D20.16
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Bay Control Unit Hardware
Unit
3.17.14
Impulse voltage withstand kV
3.18
Direct AC Connection Current
3.18.1
Module designation
3.18.2
Literature reference for principle of operation
3.18.3
Maximum number of modules processor
3.18.4
Number of inputs per module
3.18.5
Input current ranges
A
3.18.6
Input filter attenuation at 50 Hz
dB
3.18.7
Burden on instrument transformer circuit
VA
3.18.8
Conversion time
ms
3.18.9
Scanning resolution
bits
3.18.10
Accuracy
3.18.11
What calculations are supported?
3.18.12
How are overflow and conversion failures dealt with?
3.18.13
Method of isolation
3.18.14
Impulse voltage withstand kV
Data
Required
Offered
kV
%
kV
D20.17
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
BCU Software
Unit
4
BCU SOFTWARE
4.1
General Requirements
4.1.1
Program structure
4.1.2
System software
4.1.3
Standard functions programs
4.1.4
User functions programs
4.2
Capability of:
4.2.1
BCU program downloading from Control Centre
4.2.2
Application configuration from Control Centre
4.2.3
Remote selection of processing parameters
4.2.4
Selection of communication protocols
4.2.5
Selection of operation modes (cyclic, polled, etc.)
4.2.6
Appropriate protection of software against power failure
4.2.7
Automatic BCU re-start without software down-loading
4.3
System Software
4.3.1
Operating System (Monitor) Functions and capabilities
4.3.2
Calendar Program Type, Functions and capabilities
4.3.3
Time Synchronization Program Functions and
capabilities
4.3.4
Data
Required
Offered
Database Updating Program Functions and capabilities
4.3.5
Testing and Diagnostics Programs Functions and
capabilities
4.4
Standard Functions Programs
4.4.1
Data Communication Programs: Functions and
capabilities
4.4.2
Capability of communication protocol selection
4.4.3
Capability of operating modes selection
D20.18
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
BCU Software
Unit
4.5
Analogue Measurements, Scanning and
Transmission Programs
4.5.1
Capabilities of adjustments
4.5.2
Transducers constants
4.5.3
Periodic transmission/transmission by exception
4.5.4
Automatic checking of A/D-conversion accuracy
4.5.5
Smoothing
4.5.6
Threshold values
4.5.7
Limits
4.5.8
Scan duration (range)
4.5.9
Cycle duration (range)
s
4.5.10
Priority of transmission
s
4.5.11
Digital Input Data Scanning and Transmission Program
4.6
Functions and capabilities
4.6.1
Capability of adjustments
4.6.2
Scan duration (range)
4.6.3
Transient time of status information (range)
4.6.4
Cycle duration (range)
4.6.5
Debouncing filter
4.6.6
Suppression of intermediate status information
4.6.7
Time tagging
4.6.8
Transmission mode
4.6.9
Priority of transmission
4.7
Alarm and Event handling
4.7.1
Grouping of alarms and events
4.7.2
Maximum number of groups
4.8.0
Supervisory Control Programs: Functions and
capabilities
4.8.1
Select before execute
4.8.2
Target check
Data
Required
Offered
ms
ms
s
D20.19
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
BCU Software
Unit
4.8.3
Cancelling control after adjustable time delay
4.8.4
Capability of adjustments:
4.8.5
Duration of output (range)
s
4.8.6
Allowed duration of execution (range)
s
4.8.7
Sequence of Events programs
4.8.8
Minimal sequence of events time resolution
4.8.9
Sequence of events memory capacity
4.8.10
Events time resolution (adjustable range)
4.8.11
Priority of transmission
4.8.12
Post - Mortem Review / Program
4.8.13
Selection of analogues for post-mortem review
4.8.14
Short interval time resolution (adjustable range)
s
4.8.15
Long interval time resolution (adjustable range)
s
4.9
Data processing programs: Functions and
capabilities
4.9.1
Required minimum data processing:
4.9.2
Logic functions
4.9.3
Arithmetical functions (MW , Mvar etc )
4.9.4
Limiting functions
4.9.5
Comparative functions
4.9.6
Time functions
Data
Required
Offered
ms
s
D20.20
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Gateway Software
Unit
5.
GATEWAY SOFTWARE
5.1
General Requirements
5.1.1
Database management application
5.1.2
Alarm and Event Grouping
5.1.3
Alarm and Event Separation for NCC and DCC
5.1.4
Alarm and Event storage and remote / local access
5.2
Capability of:
5.2.1
Gateway program downloading from Control Centre
5.2.2
Application configuration from Control Centre
5.2.3
Remote selection of processing parameters
5.2.4
Selection of communication protocols
5.2.5
Selection of operation modes (cyclic, polled, etc.)
5.2.6
Appropriate protection of software against power failure
5.2.7
Automatic re-start without software down-loading
5.3
System Software
5.3.1
Operating System (Monitor) Functions and capabilities
5.3.2
Calendar program Type, functions and capabilities
5.3.3
Time Synchronization Program Functions and
capabilities
5.3.4
Data Base Updating program Functions and
capabilities
5.3.5
Testing and Diagnostics Programs Functions and
capabilities
Data
Required
Offered
D20.21
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6
TRANSDUCERS
6.1
Current transducer.
6.1.1
Manufacturer
6.1.2
Type reference
6.1.3
Number
6.1.4
Principle (e.g. 3 phase, 3 wire, unbalanced)
6.1.5
Output range
6.1.6
Input ranges available
6.1.7
Burden on instrument transformer circuit
VA
6.1.8
Insulation level
kV
6.1.9
Impulse withstand level
6.1.10
Minimum accuracy over working range
%
6.1.11
Response time (0 to 90%)
ms
6.1.12
Mounting details
6.1.13
Operating temperature range
°C
6.1.14
Operating humidity range
%
6.1.15
Auxiliary supply if required
6.1.16
Voltage range
6.1.17
Power requirements
VA
6.1.18
Frequency
Hz
6.1.19
Type of overload protection
6.1.20
Permissible continuous input overload
6.2
Voltage transducer
6.2.1
Manufacturer
6.2.2
Type
6.2.3
Number
6.2.4
Output range
6.2.5
Input ranges available
Data
Required
Offered
mA
A
kV peak
V
%A
mA
V
D20.22
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6.2.6
Burden on instrument transformer circuit
VA
6.2.7
Insulation level
kV
6.2.8
Impulse withstand level
6.2.9
Minimum accuracy over working range
%
6.2.10
Response time (0 to 90%)
ms
6.2.11
Mounting details
6.2.12
Operating temperature range
°C
6.2.13
Operating humidity range
%
6.2.14
Auxiliary supply
6.2.15
V range
6.2.16
Power requirements
VA
6.2.17
Frequency
Hz
6.2.18
Type of overload protection
6.2.19
Permissible continuous input overload
6.3
Active Power MW
6.3.1
Manufacturer
6.3.2
Type reference
6.3.3
Number
6.3.4
Principle (e.g. 3 phase, 3 wire, unbalanced)
6.3.5
Output range
6.3.6
Input ranges available
6.3.7
Voltage
V
6.3.8
Current
A
6.3.9
Burden on instrument transformer circuit
6.3.10
Current Transformer (CT)
VA
6.3.11
Voltage Transformer (VT)
VA
6.3.12
Insulation level
kV
6.3.13
Impulse withstand level
Data
Required
Offered
kV peak
V
%V
mA
kV peak
D20.23
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6.3.14
Minimum accuracy over working range
%
6.3.15
Response time (0 to 90%)
ms
6.3.16
Mounting details
6.3.17
Operating temperature range
°C
6.3.18
Operating humidity range
%
6.3.19
Auxiliary supply if required
6.3.20
Voltage range
6.3.21
Power requirements
VA
6.3.22
Frequency
Hz
6.3.23
Type of overload protection
6.3.24
Permissible continuous input overload
Data
Required
Offered
V
•
Voltage
%V
•
Current
%A
6.4
Reactive Power MVArs
6.4.1
Manufacturer
6.4.2
Type reference
6.4.3
Number
6.4.4
Principle (e.g. 3 phase, 3 wire, unbalanced)
6.4.5
Output range
6.4.6
Input ranges available
6.4.7
Voltage
V
6.4.8
Current
A
6.4.9
Burden on instrument transformer circuit
6.4.10
Current Transformer (CT)
VA
6.4.11
Voltage Transformer (VT)
VA
6.4.12
Insulation level
kV
6.4.13
Impulse withstand level
6.4.14
Minimum accuracy over working range
mA
kV peak
%
D20.24
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6.4.15
Response time (0 to 90%)
6.4.16
Mounting details
6.4.17
Operating temperature range
°C
6.4.18
Operating humidity range
%
6.4.19
Auxiliary supply
6.4.20
Voltage range
6.4.21
Power requirements
VA
6.4.22
Frequency
Hz
6.4.23
Type of overload protection
6.4.24
Permissible continuous input overload
Data
Required
Offered
ms
V
•
Voltage
%V
•
Current
%A
6.5
Frequency
6.5.1
Manufacturer
6.5.2
Type
6.5.3
Number
6.5.4
Measurement range
Hz
6.5.5
Output range
mA
6.5.6
Input ranges available
V ac
6.5.7
Burden on instrument VT circuit
VA
6.5.8
Insulation level
kV
6.5.9
Impulse withstand level
6.5.10
Minimum accuracy over working range
%
6.5.11
Response time (0 to 90%)
ms
6.5.12
Mounting details
6.5.13
Operating temperature range
6.5.14
Auxiliary supply
6.5.15
Voltage range
kV peak
°C
V
D20.25
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6.5.16
Power requirements
VA
6.5.17
Frequency
Hz
6.5.18
Type of overload protection
6.5.19
Permissible continuous input overload %V
6.6
Power Factor
6.6.1
Manufacturer
6.6.2
Type
6.6.3
Number
6.6.4
Measurement range
6.6.5
Output range
mA
6.6.6
Input ranges available
V ac
6.6.7
Burden on instrument VT circuit
VA
6.6.8
Insulation level
kV
6.6.9
Impulse withstand level
6.6.10
Minimum accuracy over working range
%
6.6.11
Response time (0 to 90%)
ms
6.6.12
Mounting details
6.6.13
Operating temperature range
6.6.14
Auxiliary supply
6.6.15
Voltage range
6.6.16
Power requirements
VA
6.6.17
Frequency
Hz
6.6.18
Type of overload protection
6.6.19
Permissible continuous input overload
Data
Required
Offered
%
kV peak
°C
V
%
•
Voltage
%V
•
Current
%A
6.7
Combined active and reactive power
6.7.1
Manufacturer
D20.26
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D20 - SUBSTATION CONTROL SYSTEM - Cont
Transducers
Unit
6.7.2
Type
6.7.3
Number
6.7.4
Measurement range
6.7.5
Input ranges available
6.7.6
Voltage
V ac
6.7.7
Current
A
6.7.8
Burden on instrument transformer circuit
6.7.9
Current Transformer (CT)
VA
6.7.10
Voltage Transformer (VT)
VA
6.7.11
Insulation level
kV
6.7.12
Impulse withstand level
6.7.13
Minimum accuracy over working range
%
6.7.14
Response time (0 to 90%)
ms
6.7.15
Number of analogue outputs
6.7.16
Analogue output range
6.7.17
Calculations available
6.7.18
Serial output protocol
6.7.19
Mounting details
6.7.20
Operating temperature range
6.7.21
Auxiliary supply
6.7.22
Voltage range
6.7.23
Power requirements
VA
6.7.24
Frequency
Hz
6.7.25
Type of overload protection
6.7.26
Permissible continuous input overload
Data
Required
Offered
kV peak
mA
°C
V
•
Voltage
%V
•
Current
%A
D20.27
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE D – TECHNICAL PARTICULARS - CONT
SCHEDULE D21 - CONTROL, OPERATION, INDICATION AND ALARM
CIRCUITS
Item No
Device
Function
Operating
supply
voltage
Required
1
Gas And/Or Oil
Actuated Relay
(a) Alarm
(b) Trip
48 V dc
110 V dc
Yes
Yes
2
Winding temperature
indicator
Alarm
Trip
Cooler Control
48 V dc
110 V dc
220/380 V ac
HV
Yes
LV
Yes
Tertiary Yes
3
Winding temperature
indicator remote
repeater
Indication
4
Oil temperature
indicator
Alarm
Trip
48 V dc
110 V dc
Yes
Yes
5
Tap-changing
equipment
Control
Indication
220/380 V ac
48 V dc
Yes
Yes
6
Fan failure
Alarm
48 V dc
Yes
7
Oil flow failure
Alarm
48 V dc
Yes
8
Remote electrical
indicator to show if
units of a group of
transformers are in
parallel on different
tappings
Indication
Alarm
48 V dc
-
Yes
No
Indication
Alarm
48 V dc
-
Yes
No
Indication
48 V dc
Yes
9
10
Transformer “tap
change in progress”
remote electrical
indication
Transformer “voltage
ratio” remote
electrical indication
HV
LV
Tertiary
Provided
No
No
No
D21.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E
TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING AND
MAINTENANCE INSTRUCTIONS
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS
This Schedule details the requirements for drawings, documents, operating and maintenance
instructions, samples and models as may be required to describe the Works.
SCHEDULE E1 - DRAWINGS ISSUED WITH THE TENDER
The drawings listed below form an integral part of this specification and are to provide a guide
regarding the system electrical connection, location and arrangement.
Drawing
Title
1 IQ 18284
E
Typical 400/132 kV GIS Substation - Single Line Diagram of 400 kV
Switchgear
1 IQ 18285
D
Typical 400/132 kV GIS Substation - Single Line Diagram of 132 kV
Switchgear
1 IQ 18286
E
Typical 400/132 kV GIS Substation - Single Line Diagram of 400 kV
Substation Protection
1 IQ 18287
E
Typical 400/132 kV GIS Substation - Single Line Diagram of 132 kV
Substation Protection
1 IQ 18288
C
Typical 400/132 kV Substation - Single Line Diagram of LVAC
Supplies
3 IQ 18289
B
Typical 400/132 kV Substation - Single Line Diagram of 110V DC
Supplies
3 IQ 18290
B
Typical 400/132 kV Substation - Single Line Diagram of 48V DC
Supplies
3 IQ 18291
D
Typical Substation Diagrams - Symbols List
1 IQ 18292
D
Typical 400/132 kV GIS Substation - General Arrangement of
Buildings and Roads
1 IQ 18293
D
Typical 400/132 kV GIS Substation - Layout and Elevation of
400 kV GIS Switchgear Building
1 IQ 18294
C
Typical 400/132 kV GIS Substation - Layout and Elevation of
132 kV GIS Switchgear Building
1 IQ 18295
C
Typical 400/132 kV Substation - Layout of Control and Relay
Building
1 IQ 18296
C
Typical 400/132 kV Substation - Layout and Elevation of Substation
Store, Workshop and Car Port
2 IQ 18297
C
Typical 400/132 kV and 132/33/11(6.6) kV Substation – Layout of
Guard House
1 IQ 18298
C
Typical 400/132 kV Substation - Layout of Staff Housing
E.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS
SCHEDULE E1 - DRAWINGS ISSUED WITH THE TENDER - Cont
Drawing
Title
1 IQ 18300
B
Typical 400/132 kV and 132/33/11(6.6) kV Substation - Fence
Details
2 IQ 18303
B
Typical 400/132 kV and 132/33/11(6.6) kV Substation Arrangement of Control Desk
1 IQ 18304
E
Typical 400/132 kV and 132/33/11(6.6) kV Substation - Outdoor
Open Terminal Electrical Safety Clearances
1 IQ 18305
B
Typical 400/132 kV and 132/33/11(6.6) kV Substation - Road Cross
Sections and Drainage Details
1 IQ 18306
B
Typical 400/132 kV and 132/33/11(6.6) kV Substation - Details of
Sanitary Drainage System
SCHEDULE E2 - DRAWINGS REQUIRED WITH TENDER
The Contractor shall submit with this Tender full details to describe the proposal and as a minimum
shall include the following information:
(a)
General arrangement of the switchyard showing general equipment layout, overall dimensions
of equipment bays, and phase-phase and phase-earth clearances where applicable.
(b)
Outline drawings of switchgear bays, circuit breakers, disconnect switches, earthing switches
and other main plant showing overall dimensions and weights, including details for shipping.
(c)
Typical drawings of protection equipment, relay panels, and associated equipment enclosures
(d)
General arrangement for transformers and reactors.
(e)
Bushings or cable termination details for transformers.
(f)
Descriptive information and drawings dealing with tank, core and winding arrangements
including type of coils, insulation, use of grading, on-load tap-changing equipment and location
of all ancillary devices.
(g)
Evidence of Type testing on similar switchgear and transformer units.
The contractor shall include any other drawings, catalogues, descriptions and photographs necessary
to present a clear picture of the type and class of equipment being submitted.
E.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E3 - CONTRACT DRAWING REQUIREMENTS
Following award of Contract the Contractor shall submit for approval drawings, which shall be in
sufficient detail to show:
1
Substation General Arrangement and Single Line Diagrams
(a)
General arrangement at each substation. (These drawings shall give the principal dimensions
and positions of the circuit breakers, disconnecting switches, etc.)
(b)
Single line diagram of the main high-voltage connections, showing protection and metering
circuits.
2
Switchgear and Associated Control and Protection
(a)
Section drawings of circuit breakers showing general details of construction.
(b)
General arrangement of control and indicating panels.
(c)
General arrangement of relay panels.
(d)
Typical diagrams of unit protective equipment and busbar zone protection.
(e)
General arrangement of battery charging equipment.
(f)
General arrangement of auxiliary switchgear.
(g)
General arrangement, details and schematic diagram of oil filtering and storage equipment (if
any are required).
(h)
General arrangement and details of isolating switches and earthing blades.
(j)
General arrangement, details and schematic diagram of compressed air system, if required.
(k)
Details of bushing, post and suspension insulators.
(m)
General arrangement and details of surge arresters and associated surge counters.
(n)
Sectional elevation drawings of each type of circuit breaker bay showing positions of current
transformers and other apparatus forming an integral part of each unit.
(p)
Details and schematic diagram of interlocking.
(q)
Complete schematic diagrams of:
(i)
Direct current tripping connections;
E.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E3 - CONTRACT DRAWING REQUIREMENTS – Cont
(ii)
Direct current control and indication connections;
(iii)
Current transformer connections;
(iv)
AC voltage connections for protective equipment, indication and synchronizing;
(v)
Connections of electrical interlocking equipment;
(vi)
Connections of busbar zone protective equipment.
(r)
Complete wiring diagrams.
(s)
Details of protective relays, accessories and current transformers including particulars of
wiring and drilling dimensions.
(t)
Details and arrangements of auxiliary plant and kiosks.
(u)
Details of circuit breakers handling equipments.
(v)
Details of instrument scales.
(w)
Material lists.
(y)
Layout and schedule of multi-conductor cables.
(z)
Details of transformer fire protection equipment (if any are required).
3
Transformers
(a)
The general arrangement and dimensions of the equipment to be supplied under the Contract.
(b)
Detail drawings showing core clamping, winding arrangements, tank and wheel detail
dimensions, cooler details and control cubicle details.
(c)
The weight of each part on all detail drawings.
(d)
The nature of the material from which the various parts are to be made and their surface
finishes.
(e)
The weld details and machining and assembly tolerance of all assemblies.
(f)
The manner in which such parts are designed to function.
(g)
Name plate details.
(h)
Wiring diagrams and catalogue numbers of all electrical equipment.
E.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E3 - CONTRACT DRAWING REQUIREMENTS – Cont
(j)
Complete electrical wiring diagrams.
(k)
Complete electrical wiring diagrams.
(m)
Material lists of all ancillary equipment - starters, fans, relays, bushings etc.
(n)
The location of checks, anchors, grout pockets and the like in structures constructed by others.
Such drawings shall be provided not less than six months prior to the scheduled start of
construction of the structure effected.
(p)
Final issues of all applicable drawings
(q)
Drawings, submitted by the Contractor shall be in sufficient detail to show:
4
(i)
The general arrangement and dimensions of the parts and the size of each major part of
the equipment to be supplied under the contract.
(ii)
The weight of each major part on all detail drawings. The shipping weight and
dimensions shall also be given.
(iii)
The nature of the material and surface finish from which the various parts are to be made.
(iv)
The weld details and machining and assembly tolerance of all assemblies.
(v)
The manner in which such parts are designed to function.
(vi)
Wiring diagrams and catalogue numbers of all electrical equipment
Civil, architectural and building services
Submittals required for are required to fully detail all substation buildings, roads, drainage equipment
foundations building serves and air conditioning equipment as specified.
SCHEDULE E4 - CONTRACTOR’S SUBMITTALS - DRAWING AND DESIGN
DATA
The Contractor shall submit all drawings, samples and models for approval in sufficient time to permit
modifications to be made if such are deemed necessary, and the drawings and samples and models
to be re-submitted without delaying the initial deliveries or completion of the Contract Works. The time
allowed for the Employer to review and comment on drawings, samples and models shall be agreed.
If the Contractor requires early review of any drawing in order to avoid delay in the completion of the
Contract Works, he shall advise the Engineer to such effect when submitting the drawing.
E.5
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E4 - CONTRACTOR’S SUBMITTALS - DRAWING AND DESIGN
DATA - Cont
The drawing format and the indexing system will be agreed at the first Contract meeting between the
Contractor and the Engineer. The number of copies of each drawing or of any subsequent revision to
be submitted to the Engineer for review shall be advised to the Contractor by the Engineer.
Drawings, samples and models submitted by the Contractor and approved by the Engineer shall not
be departed from without the instruction in writing of the Engineer.
The Engineer reserves the right to request any further additional information that may be considered
necessary in order fully to review the Contractor’s drawings.
Any drawing modified from a previously submitted drawing shall bear a new version number. Revised
drawings reissued for review shall have at least one copy clearly marked indicating the amendments
to the drawing. Revision boxes must be provided giving the date, revision letter and brief description
of each drawing.
Any drawing or document submitted for information only shall be indicated as such by the Contractor.
Drawings submitted for information only will not be returned to the Contractor unless the Engineer
considers that such drawings do need to be reviewed, in which case they will be returned suitably
stamped with comments.
Following final review, further copies of the reviewed drawing shall be marked “Issued for
Construction” and shall be supplied to the Engineer for distribution and to Site.
All drawings shall be drawn to one of the preferred scales quoted in Table 7 of BS Publication
PD6031 and on paper of the appropriate size from the International Series of A sizes.
Except as otherwise specifically approved, all drawings shall be of size not greater than A0 (normally
841 mm x 1189 mm) nor smaller than A4 (normally 210 mm x 297 mm).
All drawings shall be accurately drawn to scale on sheets of specified size and shall be legible.
Wording on drawings shall be in English. All units and dimensions shall be in the metric (S.I) system.
Symbols shall be in accordance with approved standards. Drawings submitted for approval shall be to
scale not less than 1:20. All important dimensions shall be given and the material of which each part
is to be constructed shall be indicated.
The Contractor shall be responsible for any discrepancies or errors in or omissions from the drawings,
whether such drawings have been approved or not by the Engineer. Approval given by the Engineer
to any drawing or sample shall neither relieve the Contractor from his liability to complete the Contract
Works in accordance with this Specification and the Conditions of Contract nor exonerate him from
any of his guarantees, or relieve the Contractor of responsibility for correctness, nor for results arising
from errors or omissions nor for failure in the matter of guarantee, which may become evident during
erection or subsequent operation.
E.6
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E4 - CONTRACTOR’S SUBMITTALS - DRAWING AND DESIGN
DATA - Cont
All drawings, samples and models shall be submitted in accordance with the provisions of this
Specification and shall become the property of the Employer.
If revisions are required after a drawing has been submitted, the Contractor shall resubmit the
specified number of reproductions to the Engineer.
All drawings submitted by the Contractor shall have the following particulars in the lower right hand
corner in addition to the Contractor’s name, date, scale, number and title of the drawing, contract
number, substation title and equipment description.
Ministry of Electricity
Baghdad, Iraq
SCHEDULE E5 - INSTALLATION AND MAINTENANCE INSTRUCTIONS
The Contract Price shall be deemed to include illustrated installation and maintenance instructions
written in English.
The instructions are to be as simple and clear as possible, fully illustrated with drawings and diagrams
as necessary and detailed with part numbers for ordering of replacements. Two copies are required
for use of the Engineer during erection work.
A further 6 copies are to be reproduced as a book or books of approximately A4 size and bound into
strong black durable imitation leather covers inscribed upon the front generally in the form of the title
page to this document except that the references to Specification, Conditions of Contract, drawings,
etc, will be replaced by “Installation and Maintenance Instructions”.
The name of the main Contractor, but not that of any subcontractor, may also be inscribed upon the
cover after the description of the plant. The name of the Ministry of Electricity shall be inscribed upon
the spine.
SCHEDULE E6 - FINAL RECORDS
After completion of work on Site all Contract drawings shall be revised where necessary to show the
equipment as installed and two copies of revised drawings shall be submitted for review. A complete
set of reviewed records shall be provided comprising, one full size reproducible copy and one full size
print. Record drawings shall be endorsed “As Constructed” and shall be correctly titled and carry the
Engineer’s review number, Contractor’s drawing number and where appropriate the Ministry of
Electricity’s number allocated to the item.
E.7
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING
AND MAINTENANCE INSTRUCTIONS - CONT
SCHEDULE E6 - FINAL RECORDS - Cont
After final review of the “As Constructed” record drawings the Contractor shall submit two complete
sets of records on compact discs, one of which is for the Ministry of Electricity. Electronic copies of
the drawings shall be in CAD 2002 format suitable for reproduction on paper using the Engineer’s
preferred software packages. Each disc shall provide a comprehensive drawing list containing the
drawing number, sheet, revision and title of every drawing. Each single file drawing record shall be
self-supporting, complete with unique title and drawing number, without referencing other files. Nonstandard items such as fonts, line types, etc should not be used. If compression techniques are
applied to files then any software necessary to decompress the files shall be included on the discs.
The Contractor shall ensure that all information contained on the discs has been checked for virus
contamination. Each compact disc shall be supplied suitably encased and accompanied with printed
documentation describing the contents of the compact discs, the formats and software used to
compile the discs and the print hardware required to reproduce the record drawings.
Final record copies shall be handed over before the issue of the Taking Over Certificate.
E.8
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE F
DEVIATIONS FROM THE TECHNICAL SPECIFICATION
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE F - DEVIATIONS FROM THE TECHNICAL SPECIFICATION
(Information to be provided with Tender)
The Tenderer shall set out below a tabulated statement showing clearly section by section compliance
and departures from the Specification and details of alternative proposals. The Tenderer will be
deemed to have complied with the Specification in all respects and as written unless qualified in this
Schedule.
Section
Departure from the requirements of the Project Specification
with details of alternative proposals
F.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE G
QUANTITIES AND PRICES
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE G – QUANTITIES AND PRICES
PREAMBLE
The prices inserted in Schedule G shall include all the requirements in the Invitation to Tender. The
quantities, rates and prices in Schedule G shall include all design, testing, inspection, plant, labour,
supervision, materials, erection, maintenance, transportation, handling, storage, supply and use of
Contractor’s equipment, temporary works, insurance, profit; together with all general risks, liabilities
and obligations set out or implied in the Contract.
The cost of items against which the Tenderer has failed to enter a price shall be deemed to be
covered in the Tender price. The whole cost of complying with the provisions of the Invitation to
Tender shall be included in the items provided in Schedule G and where no items are provided, shall
be deemed to be distributed among the rates and prices for related items of work.
G.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE G - QUANTITIES AND PRICING - CONT
(Information to be provided with Tender)
This Schedule shall be completed for the Proposal as per the Specifications
Item
no.
Description
Qty
Supply,
delivery and
insurance to
site
Installation,
commissioning
and insurance at
site
Total Price
G.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J1
RECOMMENDED SPARES
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J1 - RECOMMENDED SPARES
(Information to be provided with Tender)
The Tenderer is required to provide a list of recommended spares for a 5-year period from the end of
the Defect Liability Period for the Work. All unit prices quoted shall be valid for any spare parts
ordered by the Client in this period.
Main equipment type
Part no/description
Quantity
Unit price
J1.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J2
SPECIAL TOOLS, TEST EQUIPMENT
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J2 - SPECIAL TOOLS, TEST EQUIPMENT
(Information to be provided with Tender)
Details of all special tools and test equipment required should also be provided. All unit prices quoted
shall be valid for tools and test equipment ordered by the Client during the Contract Period.
The work to be done under this section consists of the supply, delivery to site and guarantee of all
tools and equipment for operation and maintenance of the substations. All tools shall be of the best
quality and of the class most suitable for working under the conditions specified. All material used in
the tools and equipment shall be new. These shall include, but not necessarily be limited to, the
items listed in the following sections.
A lump sum shall be quoted in the Schedule of Prices for all Tools and Equipment, except where
separate prices are specifically requested.
Main equipment type
Part no/description
Quantity
Unit price
Heavy Equipment
(a)
Supply two mobile cranes with jib length
and lifting capacity suitable for maintenance
of all switchgear equipment; in the
substation. Provide an optional separate
price for this equipment.
(b)
Supply two mobile aerial buckets, suitable
for inspection and washing of 400 kV
substation insulators. Provide an optional
separate price for this equipment.
(c)
Supply one mobile oil filter plant, suitable
for filtration of the main 400 kV transformer
oil. Provide an optional separate price for
this equipment.
(d)
At each substation, supply one set of
jacking devices suitable for use in
installation or removal of the main system
transformers as applicable
(e)
Supply one mobile SF6 Gas Handling Plant
Workshop Equipment
(a)
Steel work benches, approximately 10
square metres of working surface.
(b)
Distilled water plant.
J2.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J2 - SPECIAL TOOLS, TEST EQUIPMENT - CONT
Main equipment type
Part no/description
(c)
Drill Press complete with 2 sets of assorted
drills.
(d)
Bench Grinder, fine and coarse wheels,
complete with spare wheels.
(e)
Electric Welder, complete with assorted
rods.
(f)
Moisture absorbing material drying oven
Quantity
Unit price
Industrial vacuum cleaner.
(g)
Tool racks and boxes as required.
(h)
Assorted slings and lifting tackle.
(j)
Vices.
Hand Tools
(a)
Two sets of flat spanners, in sixes suitable
for the equipment supplied.
(b)
Two sets of socket spanners, in sizes
suitable for the equipment supplied.
(c)
Inspection lamps.
(d)
Assorted screwdrivers.
(e)
Electricians knives.
(f)
Hammers
(g)
Hacksaws.
(h)
Pliers.
(j)
Files
(k)
Blow torch
(l)
Soldering Iron.
(m)
One set of taps and dies, in sizes suitable
for the equipment supplied.
Special Tools
(a)
Earthing and Safety Equipment
(b)
4 sets - 132 kV insulated earthing rods,
J2.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J2 - SPECIAL TOOLS, TEST EQUIPMENT - CONT
Main equipment type
Part no/description
(c)
2 sets - 11 kV insulated earthing rods,
(d)
Earthing connections with suitable clamps
(e)
One - 132 kV neon indicator,
(f)
One - 11 kV neon indicator
(g)
One - 33 kV neon indicator.
(h)
2 pairs - Rubber gloves.
(j)
6 - Safety hats,
(k)
6- pairs -. Safety glasses
(l)
2 - Lineman's safety belts
(m)
50 - Warning plates.
(n)
4 - First aid kits.
(p)
Sufficient length of white rope to rope off
two maintenance areas in the substation.
Quantity
Unit price
Test Equipment
(a)
One set of Oil Testing Equipment, suitable
for sample testing of transformer, reactor
and circuit breaker oils.
(b)
One AV Primary injection test set
(c)
One 5000 Volt, motor-driven Megger
insulation tester.
(d)
One set of Meters to cover all types of
substation maintenance (V meter,
Ammeter, W meter, AC and DC).
(e)
One AC Secondary injection test set.
(f)
One Double Beam oscilloscope, complete
with trolley.
(g)
Two AVO multimeters, in ever-ready cases.
(h)
One 50 C Volt hand driven Megger
insulation tester.
J2.3
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J2 - SPECIAL TOOLS, TEST EQUIPMENT - CONT
Main equipment type
Part no/description
(i)
One 1000 Volt hand-driven Megger
insulation tester.
(k)
Test equipment for protection with
necessary transformers, wires, tools, etc.
Quantity
Unit price
J2.4
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J3
TRANSFORMERS AND REACTORS QUANTITIES AND PRICES FOR SPARE
PARTS
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J3 - TRANSFORMERS AND REACTORS QUANTITIES AND PRICES
FOR SPARE PARTS
This Schedule shall be completed by the Tenderer. Each Tenderer shall in addition to the specified
spares, provide details of additional items recommended by him. These items are optional and shall
only be included in the definite work on written instructions from the Engineer.
Description
Recommended
Number for 10
year maintenance
period
Price
Autotransformers
400 kV bushings
132 kV bushings
Neutral Air/oil bushings
Set of autotransformer gaskets, complete (400MVA
transformer)
Fans with motors, complete
Gas/oil relay (main unit) if similar type otherwise one of
each type.
Gas/oil relay (tap changer) if similar type otherwise one of
each type.
Oil level gauges if similar type otherwise one of each
type.
Oil temperature indicator if similar type otherwise one of
each type.
Winding temperature indicators if similar type otherwise
one of each type.
Dehydrating breathers
Set of tap changer spares: details of spares offered
including diverter switch, motor drive etc to be specified.
Tap position indicators
AVC relay
Fan motor protection relays
Pressure relief device
J3.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE J3 - TRANSFORMERS AND REACTORS QUANTITIES AND PRICES
FOR SPARE PARTS - CONT
Recommended
Number for 10
year maintenance
period
Description
Price
Contactors of each type
MCBs complete with bases and holders of each rating
Cubicle heaters
Thermostats
400 kV Reactor
400 kV bushings
Sets of shunt reactor gaskets complete
Gas/oil relay
Oil level gauge
Silicon gel breather
Oil temperature indicator
Earthing Transformers
Set of gaskets, complete
Gas/oil relay
Pressure relief device
J3.2
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE K
BUILDING SERVICES
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE K - BUILDING SERVICES
The Tenderer is to provide the name of the Manufacturer on this sheet against the item of
Plant/Equipment to be provided; and provide full details of the Plant/Equipment appended to the
Tender.
DATA
BUILDING SERVICES
Required
1
LIGHTING AND SMALL POWER
1.1
Distribution Boards:
1.2
Main Switches:
1.3
Luminaires Type / Weather proof outside
1.4
Luminaires Type / For emergency lighting
1.5
Luminaires Type / Explosion proof for battery room
1.6
Columns:
1.7
Earthing and Bonding Materials:
2
FIRE DETECTION SYSTEM
3
FIRE FIGHTING SYSTEM
3.1
Portable Extinguisher CO2 type
3.2
Portable Extinguisher, Dry powder type
3.3
Mobile Extinguisher, Foam Type (Outdoor)
Offered
K.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE L
HEATING, VENTILATION AND AIR CONDITIONING
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE L - HEATING, VENTILATION AND AIR CONDITIONING
The Tenderer is to provide the name of the Manufacturer on this sheet against the item of
Plant/Equipment to be provided; and provide full details of the Plant/Equipment appended to the
Tender.
DATA
HEATING, VENTILATION AND AIR CONDITIONING
Required
1
Split unit air conditioning
2
Battery room axial flow fans
3
Twin fan toilet extract units
4
Switchgear room supply and extract ventilation for high
ambient temperature control
5
Switchgear room fresh air supply over pressurization unit
6
Extraction fans
7
Low velocity supply, return, exhaust and fresh air duct of
required thickness including all hangers, supports and
required accessories
8
Insulation to sheet metal ductwork thickness and type of
materials
9
Grilles and diffusers supply, return, all as described in the
specification
10
Weather louvres
11
Exhaust louvres
12
Sand filters louvers factory assembled
13
Offered
Fire dampers, size, material and type
14
Volume control dampers type and material
15
Filters for fresh air intakes and ahu
16
Automatic control system complete for a/c and ventilating
system including control panel
L.1
400kV GIS SUBSTATION – VOLUME 3
SCHEDULE M
GUARANTEED TRANSFORMER (AND REACTOR) LOSSES AND PENALTIES
The Tenderer shall complete the following guarantees based on highest declared rated power at Site
conditions.
400/138.6/11kV, 250/250/75MVA, auto transformer (comprising 3x83.33MVA single phase units) as
specified.
Item
Description
Unit
1
No load losses (NNL) at rated voltage ratio at
IEC rating
Load losses (LL) at 75°C and rated ONAF power
and principal tapping:
HV/LV winding at IEC rating
kW
kW
Total losses (TL=NNL+LL)
kW
2
3
Declared value
250 MVAr 400kV Shunt Reactors where specified
Item
Description
Unit
4
No load losses (NNL) at rated voltage ratio at IEC
rating
kW
5
Load losses (LL) at 75°C and rated ONAF power
and principal tapping:
HV/LV winding at IEC rating
kW
6
Total Reactor losses (TL=NNL+LL)
kW
Declared value
1. Loss Evaluation
For the purposes of tender evaluation the 400/138.6kV transformer (and where applicable the 400kV
reactor) losses will be capitalized, in the following manner:
Transformers
No-load loss (NLL)
2932 US$/kW at rated voltage
Load loss (LL)
688US$/kW at rated MVA and voltage
Reactors
No-load loss
2932 US$/kW at rated voltage
Capitalisation (PV) Price
capital value + NLL + LL
M.1
400kV GIS SUBSTATION – VOLUME 3
2. Penalties
A maximum variation of +10% of the total declared losses (TL) is permitted. Any transformer or
reactor with losses more than +10% of the Total Loss (TL) declared will be rejected, unless otherwise
agreed by the Engineer.
For transformers or reactors with total losses within +5% of the declared losses no variation of the
contract price will be made.
For transformers or reactors where the total losses are between +5% to +10% of the total declared
losses the contract price will be reduced by the total capitalised cost of losses in excess of the
capitalised cost of the declared guaranteed losses.
For any transformer or reactor with total losses less than 100% of the guaranteed losses, no variation
of the Contract price will be made.
M.2
400kV GIS SUBSTATION – VOLUME 3
Download