Medium Voltage Distribution Merlin Gerin data sheet 2007 LFP circuit breaker LFP circuit breaker is used to protect and control MV public or industrial distribution network. PE55821 SF6 breaking frontal version Frontal LFP is an indoor switchgear b Rated voltage up to 17.5 kV b Rated short-circuit breaking current up to 50 kA b Rated normal current 5000 A. LFP is available in 2 versions: b Basic fixed b Fixed with a support frame. Conformity with standards b IEC 60694: common specifications for high voltage switchgear and controlgear standards b IEC 62271-100: high voltage alternating current circuit breaker b IEC 62271-200 (previously IEC 60298): AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV. Certification b By independent laboratories in accordance with ISO/IEC 17025 and EN 45011 standard b Our factories implement a quality system certified to ISO 9001 and ISO 9002 standards by IQNET. Installation b Fixed b Designed for retrofit. Operation b The operating mechanism is identical to that of the Merlin Gerin SF6 MV circuit breaker SF ranges. A full range of accessories and auxiliaries factory-mounted or delivered separately b b b b b b b b Electrical characteristics according to IEC 62271-100 Rated voltage Ur kV (50/60 Hz) 12 15 17.5 - power frequency withstand Ud kV (50 Hz 1 min) 28 (*) 38 (*) 38 (*) - lightning impulse withstand Up kV peak 75 95 (*) 95 (*) Insulation level Electric motor (M) Undervoltage release (YM) Shunt opening releases (YO1, YO2) Low energy release (MITOP) Shunt closing release (YF) Auxiliary contacts Operations counter Locking by padlocks and/or leylocks/sealing. Rated current Ir A b b b b Short circuit current Isc kA 40 50 40 25 31.5 Asymmetry (%) 50 30 30 100 30 40 50 40 25 31.5 100 125 100 63 79 b b b b 5000 Short time withstand current Ik/tk kA/3 s Short-circuit making current Ip Peak kA 50 Hz Rated switching sequence O-3 min-CO-3 min-CO b Operating times Opening Service temperature T ms b 48 Breaking ms 70 Closing ms 65 °C – 25 to + 40 (*) For higher values: consult us b Available. Device Basic fixed 38 W 1040 H 597 D 611 Weight (kg) 270 50 38.5 50 270 25 140 DE57380EN Dimensions (mm) 80 330 60 H 417 Fixing 65 141 533 D W 34 Fixed with a support frame 270 1086 H 945 D 611 Weight (kg) 310 ART.829970 © Schneider Electric Industries SAS - All rights reserved W DE57381EN Dimensions (mm) 330 H 555 W Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F-92506 Rueil-Malmaison Cedex Tel: +33 (0)1 41 29 85 00 www.schneider-electric.com www.merlin-gerin.com 521 D As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Industries SAS Design: Schneider Electric Industries SAS Printing: Imprimerie du Pont de Claix/JPF - Made in France AMTED307007EN 05-2007