Reconstruction substation of 35/6 kV "Crimea" Author: Voronov A. A. Scientific supervisor : Druzakin I. G. Purpose - to improve the reliability of power system substation "Crimea" The reasons: • Increse power consumption of consumers • Heavy wear equipment • Increasing the number of repairs • Old system of power Schema substation before reconstruction Schema after reconstruction Data for checking of working capacity of the new equipment. Equipment under voltage 35 kV: • Current of 3-phase short circuits on trunks 35 кV Is.c.(3)=2,04 кА • Shock current i im =5,21 кА • Actuation time of protection t = 2 sec. Equipment under voltage 6 кV: • Current of 3 phase short circuits on trunks 6 кV Is.c. (3). =5,83 кА • Shock current i im = 14,5 кА • Actuation time of protection t = 1,0 sec. The new substation equipment • Current transformers TLK-35-300, TLK-35200, TLK-35-150 • Current switches BB/TEL-10-20/1000 Y2 • Voltage transformers with natural oil-cooled, winding for insulation monitoring network • New transformer busline 60х6 мм2 to 35 kV and 80х8 мм2 to 6 kV. Protective relay Micom P123 • • • • 4-line LCD expresses real sizes registers up to 75 failures and transients The possibility of a logical connection between the elements Results • The chosen equipment indoor switchgear-35 kV and indoor switchgear -6 kV is checked up on conditions of thermal and electrotransient stability. • Choice and calculation of installations of microprocessor means of protection and emergency control schemes. • Round-the-clock real time-dispatching management is developed. • Payback period 4.35 years. Thank you for your attention