Uploaded by Sholi Likhin

20131005085916

Foreword, Contents
General description
SIMADYN D
Function Description and
User Information
General Diagnostics
Communication Error Codes
Reference Manual
Error Supplementary Codes
6DD1987-1AB0
Safety Guidelines
This Manual contains notices which you should observe to ensure your own personal safety, as
well as to protect the product and connected equipment. These notices are highlighted in the
Manual by a warning triangle and are marked as follows according to the level of danger:
_________________________________________________________________________
Danger
!
indicates that death, severe personal injury or substantial property damage
will result if proper
precautions are not taken.
_________________________________________________________________________
_________________________________________________________________________
!
Warning
indicates that death, severe personal injury or substantial property damage
can result if proper
precautions are not taken.
_________________________________________________________________________
_________________________________________________________________________
!
Caution
indicates that minor personal injury or property damage can result if proper precautions are not
taken.
_________________________________________________________________________
_________________________________________________________________________
Note
draws your attention to particularly important information on the product, handling the product,
or to a particular part of the documentation.
_________________________________________________________________________
Correct usage
Note the following:
_________________________________________________________________________
Warning
!
Trademarks
This device and its components may only be used for the applications described in the catalog
or the technical description, and only in connection with devices or components from other
manufacturers which have been approved or recommended by Siemens.
_________________________________________________________________________
SIMATIC and SIMADYN D are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to
trademarks might infringe upon the rights of the trademark owners.
Copyright  SIEMENS AG 1997 All rights reserved
Disclaimer of liability
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration or a utility model or design,
are reserved.
We have checked the contents of this manual for agreement with
the hardware and software described. Since deviations cannot be
precluded entirely, we cannot guarantee full agreement. However,
the data in this manual are reviewed regularly and any necessary
corrections included in subsequent editions. Suggestions for
improvement are welcomed.
Siemens AG
Drives and Standard Products Group
ASI 1 Variable-Speed Drives Division
Frauenauracher Straße 80
91056 Erlangen
Siemens Aktiengesellschaft
 Siemens AG 1997
Technical data subject to change.
Order No. 6DD1987-1AB0
Foreword
NOTES
• This Reference Manual is provided solely as a additional
information source and is not necessarily up-to-date.
•
Purpose of this
Manual
No guarantee can be made for the technical correctness of this
manual.
This Reference Manual will help you
• when troubleshooting the SIMADYN D control system, and
• serve as Reference Manual.
The individual diagnostic capabilities will be explained.
Target group
This manual is intended for engineers commissioning SIMADYN D
programs. It is assumed that these persons are knowledgeable about
instrumentation and control.
Validity of this
Manual
This manual is valid for SIMADYN D Version 3.1 of D7-SYS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 06.97
iii
Foreword
Comprehensive user documentation which is intended for selective use,
is available to support personnel when configuring and programming a
SIMADYN D control task. The following information together with Fig. 01 will help you select the user documentation which you actually require.
Overview of the
SIMADYN D
documentation,
Version V5.0
Significance
Symbol
?
This subject is documented in an online help
Reference Manual for selective use
The documentation introduces you to the methodology used.
The documentation is supplemented by an online help.
Online help
Manuals can be individually ordered.
1
Introduction
SIMADYN D
Simple to assemble and configure
1
Manual
SIMADYN D
Hardware
1
Manual
SIMADYN D
System software and
D7-SYS configuring
D7-SYS communication
configuring
Complete
Index
SIMADYN D
Glossary and complete index
Online help
Manual
SIMADYN D
SIMADYN D
Basis software for D7-SYS
?
Help on events
Online help
Manual
SIMADYN D
CFC for SIMADYN D
Continuous Function
Chart
Online help
Reference
Manual
1
SIMADYN D
Function block library
Online help
Fig. 0-1 Overview of SIMADYN D documentation, Version V5.0
iv
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 06.97
Foreword
Introduction
Simply to assemble and
configure
The Introduction provides an extremely simple entry into the methodology
when assembling and programming the SIMADYN D control system. It is
especially conceived for first-time users of a control system.
System software and
configuring D7-SYS
This Manual provides basic knowhow about the structure of the operating
system and an application program of a SIMADYN D CPU. It should be
used to obtain an overview of the programming methodology, and as basis
for a user program design and configuration .
D7-SYS communication
configuring
This Manual provides you with basic knowhow about the SIMADYN D
communications capability and how to configure links to communication
partners
Function block library
This Reference Manual provides you with an overview of SIMADYN D
function blocks, such as closed-loop control-, communication blocks etc .
Basis software for
D7-SYS
This Manual explains the essential use and the functions of the STEP 7
automation software with a main focus on the SIMADYN D control system.
For first users of SIMADYN D, the Manual provides an overview on
configuring, programming and commissioning a SIMADYN D subrack.
When working with the basis software, you can access the contextsensitive online help which provides support when it comes to detailed
questions regarding software use.
CFC for SIMADYN D
Continuous Function
Chart
The CFC language (Continuous Function Chart) allows you to graphically
interconnect blocks.
The following manuals are available: "CFC for S7, Continuous Function
Chart" and "CFC for SIMADYN D, Continuous Function Chart".
Further, when using the software, you can access the online help which can
answer detailed questions regarding the use of the editors/compilers.
Hardware
The complete SIMADYN D hardware spectrum is described as reference in
this Manual.
Table 0-1 Information overview of the SIMADYN D Manuals, Version V5.0
Guide
This reference Manual is sub-divided as follows:
• resources for troubleshooting
• various error classes
• error codes
The "General diagnostics" Reference Manual consists of the following
documents:
Document
Edition
1
General description
06.97
2
Function Description and User Information
06.97
3
Communication Error Codes
06.97
4
Error Supplementary Codes
06.97
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 06.97
v
Foreword
Special
information
The user section of this Manual does not contain any detailed
instructions with individual steps, but instead is intended to explain the
basic procedure. More detailed information on the software dialogs and
their handling, are provided in the online help.
Additional support
Please contact your local Siemens partner if you have questions
regarding the software which are neither addressed in the paper
documentation nor in the online help. You can use a Hotline:
• Tel.:
+49(9131) 98-5000
• Fax:
+49(9131) 98-1603
• e-mail:
simadyn.hotline@erlf.siemens.de
If you have any questions or comments regarding this Manual, please
complete the questionnaire at the end of the Manual and send it to the
address below. Please let us know your personal opinion about the
Manual
We offer appropriate courses to make it easier for you to get to know the
SIMADYN D automation system. Please contact the Central Training
Center in Erlangen:
• Tel.:
+49(9131) 7-27689, -27972
• Fax:
+49(9131) 7-28172
• Internet: http://www.atd.siemens.de/it-dl/training
• Intranet: http://training.erlm.siemens.de
vi
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 06.97
Inhaltsverzeichnis
1 General description............................................................................................................. 1-1
1.1 The various resources for troubleshooting................................................................. 1-1
1.2 System error fields.................................................................................................... 1-3
2 Function description and user instructions ...................................................................... 2-1
2.1 Acknowledging errors................................................................................................ 2-1
2.2 The various SIMADYN D error classes ..................................................................... 2-1
2.2.1 Error in the INIT operating mode, 7-segment display "0" ................................ 2-1
2.2.2 Error in the RUN operating mode, 7-segment display "E", "C", "A" ................. 2-8
2.2.2.1 Error, task administrator "E" ......................................................... 2-8
2.2.2.2 Error communications "C" ............................................................ 2-9
2.2.2.3 User error "A"............................................................................. 2-10
2.2.2.4 Fatal system error "H" ................................................................ 2-10
2.3 Background processing........................................................................................... 2-14
2.3.1 Online test mode.......................................................................................... 2-14
2.3.2 Monitoring error, 7-segment display "b"........................................................ 2-14
3 Communication Error Codes .............................................................................................. 3-1
3.1 Overview .................................................................................................................. 3-1
3.2 Error Codes .............................................................................................................. 3-2
3.2.1 Data Interface Access Mechanisms ............................................................... 3-2
3.2.2 Data Interface Initialization Errors (IB Errors) ............................................... 3-18
3.2.3 Network ....................................................................................................... 3-18
3.2.4 Service ........................................................................................................ 3-31
3.2.4.1 Display ....................................................................................... 3-32
3.2.4.2 Specific SS52 ............................................................................ 3-37
3.2.5 Process Data ............................................................................................... 3-38
3.2.6 Message System ......................................................................................... 3-41
3.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace)................................ 3-46
3.2.8 Time ............................................................................................................ 3-53
3.2.8.1 Device........................................................................................ 3-55
3.2.8.2 Download................................................................................... 3-58
3.2.9 Central Blocks for Links ............................................................................... 3-60
3.2.9.1 Coupling Memory Link................................................................ 3-60
3.2.9.2 Rack Link ................................................................................... 3-63
3.2.9.3 PN Local Link............................................................................. 3-68
3.2.9.4 Link DUST1................................................................................ 3-71
3.2.9.5 Link SINEC H1........................................................................... 3-71
3.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung ............... 3-75
3.2.9.7 EP Link ...................................................................................... 3-81
3.2.9.8 Link DUST7................................................................................ 3-84
3.2.9.9 Link DUST2................................................................................ 3-89
3.2.9.10 Link DUST3.............................................................................. 3-93
3.2.9.11 USS Link.................................................................................. 3-97
3.2.9.12 Rack Link Fiber Optic Cable................................................... 3-101
3.2.10 Gerätekopplung und Parameterbearbeitung auf T400.............................. 3-108
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
vii
Inhaltsverzeichnis
4 Error Supplementary Codes ............................................................................................... 4-1
4.1 Supplementary code "bsspvw_geme"....................................................................... 4-1
4.2 Supplementary code "bsspvw_info" .......................................................................... 4-2
4.3 Supplementary code "zbin_komdat" ......................................................................... 4-3
4.4 Supplementary code "zgsd_zini_nachtrag" ............................................................... 4-6
viii
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
1
General description
1.1
The various resources for troubleshooting
The following resources are available in the system for troubleshooting:
NOTE
The 7-segment display on the CPU module is the first resource which
permits rough troubleshooting. Depending on the error type, instead of
the configured CPU number, a symbol is displayed which classifies the
error. The first error which was identified, is displayed, flashing. After
being acknowledged with the red button on the CPU module, the error
code of the next error which was identified, is then displayed. The
sequence in which these error codes are displayed depends on the
priority of the error.
The following can be displayed on the 7-segment display:
At initialization or
in the off status,
operating mode
INIT
In cyclic operation
RUN operation
mode
Initialization running (short numbers
can also appear here)
<OFF> or <.>
Processor crashed, no further
diagnostics possible. Replace the
memory module or CPU module
CPU number, cyclic operation without system error
..
Monitoring error, cyclic operation; service possible; refer to
the Chapter "Monitoring errors
Communication errors, cyclic operation, service possible;
refer to the Chapter "Communication errors"
Task administration error, cyclic operation; service possible;
refer to Chapter "Task administration errors"
User error, generated by the USF function block, cyclic
operation; service possible; refer to the Chapter "User errors"
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
1-1
General description
In non-cyclic
operation, STOP
operation mode
Initialization error, no cyclic operation; service possible; refer
to Chapter "Initialization errors"
Non-maskable interrupt, no cyclic operation; service possible;
refer to the Chapter "Fatal system errors"
(as running light). Error when loading the system software, no
further diagnostics possible. The memory module could be
defective or data incorrectly loaded into it.
Stop mode, initiated by the user. Fast download
NOTE
System error fields and exception buffers are memory areas in which
detailed information on the errors which have occurred, can be saved.
Non-critical errors from the various software components (operating
system, communications,...) are saved in the system error fields.
The current system status is saved in the exception buffer when a fatal
error occurs, which results in standard processing being stopped.
These error fields are read-out, e. g. using CFC in the test mode.
1-2
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
General description
1.2
System error fields
In addition to the displayed symbols in the CPU 7-segment display,
detailed error information is saved in the central RAM area of the CPU
module. These data areas are designated system error fields.
The system error fields, described here are called INIT_ERR and
SYS_ERR.
Hardware-related error information is coded in the system error field
INIT_ERR.
The various software components (operating system, communications,
monitor, user, ...) enter their error information in the SYS_ERR system
error field.
The first error field is used to identify which of the software components
was the first to flag an error. It is possible to identify the first one from a
series of saved errors (which may subsequently initiate other errors).
The first error field is a bit field in which each software component has an
assigned bit. This is set to ’1’, if this component is the first to enter an
error.
First error field
SYS_ERR_ERST
The assignment of the bits can be seen from the following table:
First error field
Byte 1
Byte 0
15 14 13 12 11
10
Always 0
Usergenerated
error code
1) ->
0400H
9
8
Always
0
7
6
5
4
3
2
1
0
Always
0
Communications
error
Hardware
failure
(monitoring
error)
Task
administration
error
Al Fatal
w system
a
error
y
s
0
0040H
0020H
0008H
0001H
Table 1.2-1 Assignment of the bits
1) These hexadecimal values are valid for the appropriate software
components, as a maximum of one bit can be set in the first error field
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
1-3
General description
1-4
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2
Function description and user instructions
2.1
Acknowledging errors
If an error occurs, then this is indicated on the CPU 7-segment display.
With the exception of fatal system errors (NMI) and communication
errors, these errors can be acknowledged by depressing the
acknowledge key. The highest-priority error message is always displayed
first. After depressing the acknowledge button, the next highest priority
error message is displayed. The appropriate symbol is displayed,
flashing, to identify that the displayed error was the first one to occur. If
there are no more errors, the logical CPU module number is displayed.
2.2
The various SIMADYN D error classes
2.2.1
Error in the INIT operating mode, 7-segment display "0"
The errors of the INIT operating mode are saved in the FLAGH, FPNIB,
PNINKO, KO_CBUS and KO_LBU elements of the SYS_ERR error field
and in the INIT_ERR error field.
For errors, which occur when the system is initialized, the user program
doesn’t run-up. However, the service utility can be used and can be used
for diagnostics.
Error diagnostics should start at that CPU module, which was the first to
display an error message . If there is no CPU module which can be
identified as having been the first, then that CPU should be selected,
which displays a , and which is to the furthest left in the subrack.
The significance of the error field contents is listed in the following
pages:
However, if fatal system errors occur at initialization (e. g. non-maskable
interrupt NMI), initialization is aborted, and an appears in the
7-segment display.
NOTE
Fatal system errors can occur following an initialization error, for
example, if a function block addresses hardware, which wasn’t previously
correctly initialized. Thus, when fatal system errors occur during the
initialization phase, the error field should first be investigated for
initialization errors!
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-1
Function description and user instructions
Initialization error FLAGH
Set bit
Significance
0
Error when initializing the DRAM memory object
1
Error when initializing the SRAM memory object
2
Error at C BUS upload
3
Error at C BUS download
4
Error when creating the C BUS buffer system
5
Error when initializing the C bus buffer system
6
Error at L BUS upload
7
Error at L BUS download
8
Error when creating the C BUS buffer system
9
Error when creating the L bus buffer system
10
Error when initializing the task manager
11
RAM change is inhibited in the change memory
12
Änderungsspeicherinhalt kann nicht geladen werden; Speicherplatzmangel beim Service
13
Fehler bei der Initialisierung der Dollarsignale
14
15
CPU hat kein Anwenderprogramm
Bits 0-10, subsequent errors or system errors; the user cannot
resolve these errors
Bit 11 can be an error due to an erroneous change memory,
especially for test operation, can be resolved, if, in the change
memory
the correct test byte ID AA (hexa) is entered in byte 0, and
a 0 is entered in byte 2.
!
ATTENTION The change memory entries are then lost!
Bit 13: siehe Diagnose der Dollarsignal Initialisierungsfehler
Bit15: Anwenderprogramm laden
2-2
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
PN initialization- and PN-IB error FBNIB
Set bit
Significance
8
Group display from the initialization blocks. (also refer to system error field INIT_ERR, )
9
When requesting a mirror register area in a KS, the slot number or location ID are
inconsistent, or the memory object ID illegal
10
The requested mirror register area has already been set-up in the local RAM or in the
communications buffer module
11
Number of CPU modules in the C/L bus directory > 1 with the ID, no C/L bus buffer
module
15
Group display when communications is initialized
Subsequent errors or system errors; they cannot be resolved by
the user
Error flags from the coordination associated with initializing a multiprocessor system, is entered in the PNINKO element.
Coordination error
at PN Initialization
PNINKO
Bits are set for the various error statuses, if the delay time, defined in the
operating system, is not adequate for synchronization, i. e. the
appropriate initialization stage must be aborted. Even bits (0,2,..)
designate the bus master, uneven bits, the bus slaves. Bits 0-7 are used
for the C-bus coordination, bits 8-15, for L-bus coordination.
Set bits for
Synchronizing is canceled for the defined
operation
Master
Slave
C bus
L bus
C bus
L bus
0
8
1
9
2
10
3
11
3
11
Loading the mirror register into the
communications buffer
4
12
5
13
Re-loading the KS information into the local
RAM
6
14
7
15
Initialization- or final synchronization
6
14
6
14
FP initialization, possibly due to erroneous
user function blocks. Also refer to KO_CBUS
and KO_LBUS
Copying local information into the KS
Before re-loading the KS lists into the local
RAM
Subsequent errors or system errors-CPU, which caused the
error, can be identified from KO_CBUS and KO_LBUS
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-3
Function description and user instructions
Missing checkback
signal from the
C bus or L bus
KO_CBUS and
KO_LBUS
The CPU modules are marked in these error fields, which hadn’t
synchronized with the CPU being investigated. The type of synchronizing
error is defined in the PNINKO component. The non-synchronized CPU
modules are logged using a bit pattern
in the components
"
"
"
KO_CBUS for the C bus
KO_LBUS " " L bus
and the appropriate bits ("PN No." - 1) set to 1, whereby the PN No. is
the logical CPU number (CPU No. = Bit No. + 1).
Example: SIMADYN D CPU 7 does not checkback via the C bus
=> KO_CBUS = 0040.
Diagnosing
initialization errors
with the system
error field
INIT_ERR
If errors are identified in the initialization blocks during the initialization
phase, then this is indicated in the group display of the
SYS_ERR_FPNIB components of the system error field SYS_ERR, and,
detailed information regarding the error is also saved in the system error
field INIT_ERR. Only module errors are registered in the error field
INIT_ERR, for those modules which are located from the CPU module,
being investigated, up to the next CPU module, inserted to the right in
the subrack.
Monitoring errors, i. e., errors, which were first identified during normal
operation, are also logged in INIT_ERR.
The INIT_ERR system error field is 25 words long (50 bytes). A word is
reserved for each module, whereby word- and slot number are clearly
assigned to one another (word 1 to word 24 correspond to slots 1 to 24).
Each SIMADYN D CPU saves its own error information in word 0.
An error is displayed, if in one or several words of this field, a value is
not equal to 0.
The following messages are possible in word 0:
Error number
(hexadecimal)
2-4
Significance
1XXX
L bus interrupt is not received from the slave CPU
2XXX
C bus interrupt was not received from the slave CPU
4XXX
L bus KS cannot be accessed for slave CPU
8XXX
C bus KS cannot be accessed for slave CPU
FXXX
The length of the interrupt vector table in a CPU initialization block is inconsistent
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
Measures:
Check the daisy chain jumpers and insert as configured
System error or subsequent error, cannot be resolved by the user
The error numbers, listed here, can be located in words 1-24 of error
field INIT_ERR.
System errors or subsequent errors, cannot be resolved by the
user
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-5
Function description and user instructions
Error number
(hexadecimal)
01XX
011X
0111
Significance
PAD initialization
CPU module error
Incorrect module code
Incorrect module, incorrect type or development status
Measure: Insert the right CPU module type
012X
Periphery initialization error
Measure: Insert the correct module into the correct slot
0121
Invalid slot number transferred
0122
Incorrect module code
0124
No access to the module
0128
Invalid memory range size
014X
Chip select error
0141
Address limits for chip select B interchanged
0142
Address limits for chip select C interchanged
0144
Invalid slot basis address
018X
Warnings
0181
All chip select inhibited
0182
Chip select address exceeded
0184
Illegal mask for chip select A
02XX
0200
Memory initialization
L-bus communications buffer cannot be accessed from KS-IB
Measure: Test the communications buffer module
0201
Not possible to access the C-bus communications buffer from KS-IB
Measure: Check the communications buffer
0202
Error during memory object initialization
0204
Communication resource list not available
04XX
0401
Illegal memory object ID
0402
Non-configured memory used
0404
Not sufficient memory available
0408
Memory object inhibited
0410
Distribution mode illegal
08XX
2-6
Requesting the mirror register
Special periphery, IB errors
0801
C-bus connection not available
0802
Synchronizing error (is signaled as monitoring error)
0804
Incorrect slot number
Measure: Insert the module into the correct slot
0808
Incorrect configured special periphery
0810
Dual port RAM unable to be accessed
0820
L-bus connection not available
0840
Configuring error
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
Error number
(hexadecimal)
0FXX
0F1X
Significance
Monitoring error
Memory test error, can be signaled both as initialization error as well as monitoring
error
0F10
User memory error
Measure: Progam a new memory module
0F11
RAM error: Defective address line
Measure: Change the module
0F12
Memory module error
Measure: Program a new memory module
0F14
RAM error: Data line defective
Measure: Change the module
0F18
Special periphery test error
0F1F
Incorrect transfer parameter
0F2X
Error when testing
0F20
Incorrect slot number
Measure: Insert the module into the correct slot
0F21
Battery failure
Measure: Insert a battery or replace the battery
0F22
Module does not respond
Measure: Insert the correct module type
0F24
Fatal system error on another CPU module
Measure: Search for errors on other CPU modules
0F4X
Overload, area X5
Short-circuit or excessive current (not a brief overload condition).
Measure: Check the periphery
0F41
Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8
0F42
Overlaod, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18
0F8X
0F84
0F88
0FCX
Overload, area X6
Short-circuit or excessive current (not a brief overload condition).
Measure: Check the periphery
Overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
Overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
Overload, areas X5 and X6 simultaneously
Short-circuit or excessive current (not a brief overload condition).
Measure: Check the periphery
0FC5
Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 and
overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
0FC9
Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 and
overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
0FC6
Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 and
overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
0FCA
Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 and
overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-7
Function description and user instructions
2.2.2
Error in the RUN operating mode, 7-segment display "E", "C", "A"
Errors, occurring in normal operation, are saved in the DAT, COM_PM,
COM_EXC, and ANW elements of the SYS_ERR error field.
2.2.2.1
Error, task administrator "E"
If a task administrator error occurs, the user program continues to run as
well as it can. For cycle errors, or inhibited tasks, low-priority tasks are
either not processed, or not on a regular basis.
Errors of the task administrator are recorded in the SYS_ERR_DAT
components of the SYS_ERR system error field. This field is 5 bytes
long, which are assigned to the existing tasks (bytes 0 - 4 for cyclic tasks
T1 - T5).
A task, which was processed error-free, has the value 0 in "its" byte. Bits
which have been set, have the following significance (several bits can be
simultaneously set):
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Cycle error
which cannot
be resolved
(endless loop)
Internal
error
Software
watchdog
(only for T1)
No free buffer in
the C bus
communications
buffer
Not used
No free buffer in
the L-bus
communications
buffer
No free
local buffer
Cycle error
or task
back-up
System errors or subsequent errors, cannot be resolved by the
user
Cycle errors
Before a task is started, it is checked as to whether the task to be started
can be completely executed within the task sampling time, or if it is
always in the ’continuous’ status. This means, it is flagged as the highestpriority task. If this is the case, the task start is bypassed, i. e. the task is
not processed for one cycle.
However, a cycle error is only flagged, when several task starts fail, i. e.
not at the first failure. Thus, seldom failures, which do not negatively
influence program execution, are simply bypassed.
2-8
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
If several cycle errors occur one after the other then you can assume
that a task has a significant problem. The cause can be an endless loop
within this task, or that practically no computation time is made available
for this task over a longer time period (this computation time is
completely used by higher-priority tasks), and can therefore not be fully
computed.
in the 7-segment
Thus, in this case, processing is stopped (with an
display) and the diagnostics mode (communications utility service) is
started.
The user can resolve a cycle error, e. g. by increasing the sampling time
of the task involved or by reducing the configured function blocks in the
particular task.
Task "bottleneck"
Task "bottleneck" for a particular task is only registered, if the task is not
flagged as being the highest-priority task; however it should be started
again. Generally, the cause is a cycle error of a higher-priority task.
The task start is evaluated just as for cycle errors, and generates the
same display bit. The same task-specific error information is used.
For a task "bottleneck", using the PSL function block, the utilization of
the individual tasks should be determined, and, if required, reduced by
re-configuring the software (as for cycle errors).
No free local buffer
This error is the result that the data sink no longer enables the data
buffer. The task start is skipped.
Software watchdog
A software watchdog occurs if the basic sampling time is not processed
four times consecutively (one after another). The basic cycle timer is reinitialized with the configured basic sampling time, and processing
continued.
If two software watchdogs occur one after the other, then instead of the
in
basic cycle timer being re-initialized, processing is aborted (with an
the 7-segment display) and diagnostics operation (service communications utility) started.
2.2.2.2
Error communications "C"
Communication errors are entered in the SYS_ERR_COM_PM
components of the SYS_ERR error field. Several entries are possible.
The SYS_ERR_COM_EXC components specify which communication
errors have been entered.
A communications error consists of an error number, a supplementary ID
as well as the configured chart- and block name and an address to
localize the function block to be entered.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-9
Function description and user instructions
2.2.2.3
User error "A"
The user himself specifies the entries in the SYS_ERR_ANW
components of the SYS_ERR system error field. The USF function block
makes the entry.
2.2.2.4
Fatal system error "H"
If a fatal system error occurs, processing (initialization or normal
operation) is interrupted, and the system goes into the stop mode. The
error cause is available for diagnostic purposes.
NOTE
Before investigating a fatal system error, the INIT_ERR and SYS_ERR
system error fields should first be investigated. If errors are entered there
(especially hardware (monitoring) errors), then this could be the cause of
a fatal system error.
A SAVE area is set-up in the upper area, in the local RAM of each CPU
module. This area is not erased at re-initialization, if the status of the
RAM copy is appropriate. An error buffer is set-up in this SAVE area,
which includes the error protocol (error report) consisting of several
messages.
The error buffer consists of an administration part and a ring buffer, in
which the error messages are saved. The ring buffer is implemented as
buffer which can be overwritten, i. e. if the buffer is full with error
messages, then the new messages overwrite the oldest messages.
There are 2 different types of error messages. A long message is output
in the case of a non-maskable interrupt NMI. A short message for a
power OFF.
The service communications utility is available, (even if it has not been
configured) to troubleshoot fatal system errors. It can be accessed via
the local diagnostics interface, after pressing the acknowledge button.
Using the service utility, the error causes can be output in plain text.
What is especially important is the error cause, specified under an ID
code and supplementary ID. If a function block is being calculated at the
instant that the system error occurs, then this is output. In addition, the
results of the last bus accesses are displayed; these are important, if a
bus access is the error cause. Further, all of the process registers are
displayed for the system specialists to allow them to make a precise
error analyses.
2-10
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
NMI handling
When a non-maskable interrupt occurs, this is considered as fatal error
and causes initialization or normal operation to be interrupted. All of the
modules, inserted in the subracks, are no longer processed.
is displayed on the CPU module display of the
A large flashing
is displayed as
faulted module, which caused this fatal error. A large
steady display on the other CPU modules which received an NMI as
result of the faulted module. The debug monitor can be activated by
pressing the acknowledge button or setting the status value. The
symbols output on the 7-segment display have the following significance:
Steady
Flashing
:
CPU module was shutdown by another module.
:
Fatal error on this CPU module (error cause).
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-11
Function description and user instructions
Example for an error protocol (error report) for fatal system errors
Information on the last crash:
Time:
01.01.93 04:16:24.9294 h
ID:
#5 CPU
Supplementary ID:
28 (unaligned instruction fetch)
EPC:
0x04C4F19A
Return jump address: 0x801201f8
Running task:
Started levels:
Last processed FB:
Last L-bus access:
- Access type:
- BUS address:
- Retries:
Last C-bus access:
- Access type:
- BUS address:
- Retries:
T2
T2(NRM),T5(NRM),BACKGROUND
FP-KRUMMS.AY0815 (Typ: ADD8F)
(ALE: 0x80107D84 CODE:
0x801201E0)
Crash instant
} Crash
cause
Crash adress and
adress of the last function call
The running and started tasks at the
crash instant as well as the processed
function block with information on
the data- and code areas
Data on the system bus accesses.
This data is especially interesting,
if an erraneous bus access is specified
as the cause of the crash in the ID
(NMI) and supplementary ID.
q_read_2byte
0xB0F25874
0
q_read_2byte
0xB4F400B4
0
The processor status at the crash instant:
EPC
: 0x04C4F19A
BadVAddr: 0x04C4F19A
Status : 0xF000FC14
mdlo
: 0x04C4F19A
fpc_csr : 0x00000F04
Register dump of all process register
Especially important:
EPC (crash adress, as above) and
BadVAddr (bad virtual adress, adress
which was erroneously accessed
(mainly for ID TLB and CPU))
CAUTION: The value of a0, a1 (and possibly a2)
is not valid!
r00/0 :
r04/a0:
r08/t0:
r12/t4:
r16/s0:
r20/s4:
r24/t8:
r28/gp:
0x00000000
0x80064FC8
0x80064FC4
0x04C4F19A
0x800650CC
0x8006548C
0xFFFFFFFF
0x80088BA0
r01/at:
r05/a1:
r09/t1:
r13/t5:
r17/s1:
r21/s5:
r25/t9:
r29/sp:
0x00000000
0x80064F44
0x80065048
0x8007FE90
0x8006511C
0x00000020
0x8007FE90
0x80064EA8
r02/v0:
r06/a2:
r10/t2:
r14/t6:
r18/s2:
r22/s6:
r26/k0:
r30/s8:
0x00000001
0x0000000A
0x19999999
0x00000000
0x00000000
0x800812E0
0x00000210
0x04C4F19A
r03/v1:
r07/a3:
r11/t3:
r15/t7:
r19/s3:
r23/s7:
r27/k1:
r31/ra:
0xB8803000
0x00000000
0x00000000
0x00000000
0x8006548C
0x80400000
0x04C4F19A
0x801201f8
d00:
+Denorm
d08: +4.687500e+01
d16: +3.000001e+03
d24: -1.818767e-12
d02: +6.400000e+01
d10:
+Denorm
d18: +4.687500e+01
d26:-1.227518e+306
d04:
+Denorm
d12:
+Denorm
d20:
QNaN
d28:-3.691391e+249
d06: +9.999000e-01
d14:+2.660285e+154
d22:+8.329648e+298
d30:-2.374690e-237
f00: +4.787490e+01
f08: +0.000000e+00
f16: +1.024000e+03
f24:
QNaN
f02: +0.000000e+00
f10:
+Denorm
f18: +0.000000e+00
f26:
QNaN
f04:
f12:
f20:
f28:
f06: +4.764729e+05
f14: -1.960343e+37
f22:
QNaN
f30: -4.550802e-04
+4.687500e+01
+4.787490e+01
-1.693935e+38
-6.835168e-27
------------------------ End of the diagnostics -----------------------
2-12
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Function description and user instructions
Causes of fatal
errors
A fatal system error can have the following causes (ID codes). A
supplementary ID describes the error cause in more detail.
ID
Supplementary ID code (precise description)
NMI
a non-maskable interrupt
second bus clear for task-controlled access
bus clear for direct access
timeout during L/C-bus arbitration/assignment
(module missing/defective, daisy chain missing)
ready internal from L/C bus (error on another
CPU module)
ready internal from the local expansion bus (LE bus)
system bus controller overrun
timeout when accessing the local periphery
spurious interrupt (an interrupt source cannot be
identified)
direct access to the L/C bus (bypassing the
driver functions)
exceptional status of the CPU
internal error
reserved Instruction
unknown Syscall
unaligned instruction fetch (jump to address which
cannot be divided by four)
user access to kernel space
unaligned load/store to coprozessor 0/2/3
unaligned load/store to L-/C-bus address space
break 6/7 not in div/mul context
unknown break value
reserved exception
task running in endless loop
FPU exception status
fpu fault at non-fpu instruction
illegal fpu sub opcode
operation on NaNs
add/sub/division of infinities
mul of infinity and 0
exception status of the TLB
TLB modified exception
TLB read/write miss (access to illegal address)
UTLB miss (access to illegal address)
basic cycle time failure
power down
power down/reset in the normal mode
power down/reset in the stop mode (after another
exception)
CPU
FPU
TLB
TIME
OFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
2-13
Function description and user instructions
2.3
Background processing
If the CPU has no tasks to process during normal operation, it processes
the background task.
As background task, the following functions are simultaneously available:
− the online test mode and
− a service utility
The online test mode is normally processed in the background after
initialization was successfully completed. However, if the acknowledge
button is pressed at the end of initialization, then only the service
communications utility is activated.
Errors in the background processing are saved in the UEB element of the
error field SYS_ERR.
2.3.1
Online test mode
In the online test mode, for example, a battery test, a memory module
checksum test etc. are executed. The memory module checksum routine
determines the memory module checksum and compares it with the
checksum calculated by the programmer and that saved in the memory
module. If a memory module checksum error is identified in the online
test mode, the user can remove the error by repeatedly generating the
memory module. For battery test errors, he can replace the battery.
2.3.2
Monitoring error, 7-segment display "b"
The background processing errors are known as monitoring errors. They
are registered during the online test mode, and in the normal mode by an
"b" at the 7-segment display. Further, the error information is saved in
the system error fields. However, there are also errors, which are
identified during initialization, but, due to their low significance, are
flagged as monitoring errors and normal mode is still permitted. If a
monitor error is identified, then the appropriate bit of the slot number of
the associated board is set in the SYS_ERR_UEB component of the
SYS_ERR system error. Further, detailed information is saved in the
appropriate word of the INIT_ERR system error, in the slot number of the
associated module.
2-14
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3 Communication Error Codes
3.1
Overview
The distribution with regard to the individual functionalities is as follows:
Number Range
Total
Functionality
Already Utilized
6000 - 60DF
6000 - 60BF
Data Interface Access Mechanisms
60E0 - 60FF
60E0 - 60E3
Data Interface Initialization Errors
6100 - 61FF
6100 - 61AA
Network Management
6200 - 6280
6200 - 6206
Service
6300 - 6380
6300 - 6333
Process Data
6400 - 6480
6400 - 6421
Message System
6500 - 6580
6500 - 654A
Trace
6600 - 6680
6600 - 660B
Time
6700 - 67FF
6700 - 6718
Devices
6800 - 68FF
6800 - 6810
Down Load
6900 - 6BFF
6900 - 6A6F
Central Blocks for Links
6C00 - 6FFF
7C00 - /CFF
Unassigned
7C00 - 7CB66
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Gerätekopplung und Parameterbearbeitung auf T400
3-1
Communication Error Codes
3.2
Error Codes
The error codes are structured according to the same scheme as with the
"Error Diagnostics Communication V3.2’’. The codes consists of:
6100 Hex Error
Number in Hex
Format
F:
R:
A:
EQ:
EM:
AM:
AA:
Error Cause
System Reaction
Resolve By
Definition Location and Equate of the Error Codes
Module, that determines the Error
Module, that displays the Error
Display Type of the Error
The extended error codes EQ, EM and AM (not printed in bold) are of no
significance for the designer. They are only supplementary information
for the hotline or the development department of SIMADYN D.
3.2.1 Data Interface Access Mechanisms
The error codes designated with ①, have no equates in SDZ.SD, but are
converted as follows from the defined acknowledge value:
Error Code = SDZ_QUIT_xxx ) 6010 Hex.
The error codes designated with ② , have no equates in SDZ.SD, but are
converted as follows from the defined acknowledge value:
Error Code = SDZ_QUIT_xxx * 20 Hex ) 6060 Hex.
3-2
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6000 Hex
6001 Hex
6002 Hex
6003 Hex
6004 Hex
6005 Hex
F:
No error detected.
R:
Error free function.
A:
Not necessary.
EQ:
SDZ_FRW_ZC_DATA_OK.
EM:
ZC.CSF.
AM:
Block invoking the function zc_start.
AA:
None.
F:
(Only receiver) transmitter has not identified itself, i.e. the
channel is not yet in operation.
R:
Receive operation has not yet taken place.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_SEND_N_STARTKLAR.
EM:
ZCRD.CSF.
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
(Only transmitter) receiver has not yet identified itself, i.e.
channel not yet in operation.
R:
Transmit operation has not taken place.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_EMPF_N_STARTKLAR
EM:
ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
Transmitter:
Handshake / Select: User data length of the data to be
transmitted is zero and channel is empty.
Refresh / Multiple: User data length is zero and channel
is readyfor operation.
Receiver:
Not Select: User data length of the data to be received is
zero and no acknowledge exists from the transmitter.
Select: User data length of the data to be received is
zero.
R:
Transmit / Receive operation has not taken place.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_N_ATG
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
(Only transmit)
Handshake/Select:
User data buffer in the channel is
still full and no
acknowledge exists from the receiver.
Refresh:
User data buffer is being read in the
channel.
Multiple:
Cannot occur.
R:
Transmit operation has not taken place.
A:
Re-invoke function zc_start.
EQ:
SDZ_FRW_ZC_PUF_VOLL
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
Not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-3
Communication Error Codes
6006 Hex
F:
6007 Hex to 600F
Hex
6010 Hex
utilized.
6011 Hex
F:
6012 Hex
F:
6013 Hex
F:
6014 Hex
F:
3-4
F:
(Only select transmit): another transmitter has temporarily
occupied
the channel.
R:
Transmit operation has not taken place.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_SEND_KAN_BLOCK
EM:
ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
Defined acknowledge was inserted into the channel.
R:
Acknowledge operation has taken place.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_QUIT_ABGESETZT
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
The acknowledge ‘‘Remote Link Partner Missing’’ was read from
the
channel.
R:
Line to link partner defective;
The link partner is missing.
A:
Check line;
Re-invoke the function zc_start
EQ:
SDZ_QUIT_KOP_PART_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
(Only receiver) the acknowledge "Transmit Pause’’ was read
from the
channel.
R:
Transmitter temporarily does not carry out transmit
operations.
A:
Re-invoke the function zc_start.
EQ:
SDZ_QUIT_SEND_PAUSE _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
(Only transmit) the acknowledge ‘‘Receive Pause’’ was read
from the
channel.
R:
Receiver temporarily does not carry out receive
operation.
A:
Re-invoke the function zc_start.
EQ:
SDZ_QUIT_EMPF_PAUSE _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
The acknowledge ‘‘Break’’ was read from the channel.
R:
The link partner has temporarily disconnected.
A:
Re-invoke the function zc_start.
EQ:
SDZ_QUIT_BREAK _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6015 Hex
F:
6016 Hex
F:
6017 Hex
F:
6018 Hex
F:
The acknowledge ‘‘NMC Off" was read from the channel.
R:
The corresponding NMC FB in the link has switched to
the ‘‘OFF’’
state.
A:
Investigate the NMC block that transmitted the
acknowledge.
EQ:
SDZ_QUIT_NMC_AUS _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
(Only SINEC L2 DP)
The acknowledge ‘‘Station cannot be Controlled’’ was
read
from the channel.
R:
Bit 1 of the station diagnostics (byte 0 of slave station)
was set.
A:
Check station.
EQ:
SDZ_QUIT_STAT_N_STEUER _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
(Only SINEC L2 DP)
The acknowledge ‘‘Station not on the SI NEC L2 DP Bus’’
was read
from the channel.
R:
Bit 0 of the station diagnostics (byte 0 of the slave
station) was set.
A:
Check if station is operational;
Check whether bus cable is connected.
EQ:
SDZ_QUIT_STAT_N_AM_BUS _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
(Only SINEC L2 DP)
The acknowledge ‘‘Station Diagnostics Error’’ was read
from the
channel.
R:
Two or several bits of the station diagnostics (byte 0 of
slave station) were set.
A:
Two or more of the above described errors
(SDZ_QUIT_BG_AUS_PORT_ERR,
SDZ_QUIT_ADR_ERR_PARA_ERR,
SDZ_QUIT_STAT_N_STEUER,
SDZ_QUIT_STAT_N_AM_BUS) have occurred.
EQ:
SDZ_QUIT_STAT_DIAG_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-5
Communication Error Codes
6019 Hex
F:
(Only
SINEC-L2-DP)
The acknowledge "Slave already configured by another
Master"
was read from the channel.
Is "another Master" a PG --> temporary fault
Is "another Master" a general DP-Master --> two Masters
configure
the same slave; hard fault
A:
Is "another Master" a PG: When the PG releases the
slave, then
Master can access slave again
Is "another Master" a general DP-Master: check bus
configuration
EQ:
SDZ_QUIT_MASTER_LOCK _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
The acknowledge "Transmission error: Parity, Framing or
Overrun"
was read from the channel.
R:
The received telegram will be discarded
A:
Check hardware layout;
i.e. terminating resistor, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_POF_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
The acknowledge "BCC error" was read from the channel.
R:
The received telegram will be discarded
A:
Check hardware layout;
i.e. terminating resistor, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_BCC_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
The acknowledge "DUST3: No connect (no DLE)" was read from
the
channel.
R:
Connect is repeated
A:
Start-up link partner;
Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_KOP_NO_ACK _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
The acknowledge "DUST3: receive character delay" was read
from the
channel.
R:
The received telegram will be discarded
A:
Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_EZVZ_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
R:
601A Hex
F:
601B Hex
F:
601C Hex
F:
601D Hex
F:
3-6
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
601E Hex
601F Hex
6020 Hex
6021 Hex to 602E
Hex
602F Hex
6030 Hex
F:
The acknowledge "DUST3: Invalid receive string, receive
character
during
transmission" was read from the channel.
R:
The received telegram will be discarded
A:
Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_CHAR_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
F:
The acknowledge "DUST3: Invalid receive telegram type" was
read
from the channel.
R:
The received telegram will be discarded
A:
Check SIMATIC S5 configuring with regard to the
transmit telegram
type
EQ:
SDZ_QUIT_TEL_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
F:
The acknowledge "DUST3 / USS: Faulty or no reaction telegram"
was
read from the channel.
R:
The received telegram will be discarded
A:
Start-up link partner;
Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.
EQ:
SDZ_QUIT_TEL_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Warning status
not utilized
F:
F:
The acknowledge index from the user is invalid.
R:
No transmit / receive acknowledge operation took place.
A:
Contact Siemens AG.
EQ:
SDZ_FRW_ZC_USER_QUIT_ERR
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start.
AA:
Block dependent.
Memory assigning for ZCDAT structure temporarily not possible.
Exact cause see chapter Error Supplementary Code
bsspvw_geme.
R:
ZCDAT structure has not been set, link initialization
cannot be started.
A:
Re-invoke function zc_start.
EQ:
SDZ_FRW_ZC_N_ANM
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-7
Communication Error Codes
6031 Hex
6032 Hex
6033 Hex
6034 Hex
6035 Hex
6036 Hex
6037 Hex to 603E
Hex
603F Hex
3-8
F:
The CIP entry for the link was found.
R:
ZCDAT structure has been set, link initialization can be
started.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_CIP_ETG_OK
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
The link in the CIP entry is enabled.
R:
Initialization of the link has begun.
A:
Re-invoke function zc_start.
EQ:
SDZ_FRW_ZC_KOP_FREI_OK
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
The link in the CIP entry has not yet been enabled.
R:
Initialization of the link has not yet been started.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_KOP_N_FREI
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
The DEXDO3 area is enabled.
R:
The DEXDO3 enable is set to ‘‘Free’’ in the interface.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_DEXDO_FREI_OK
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
The DEXDO3 area has not yet been enabled.
R:
The DEXDO3 enable is set to ‘‘Disable’’ in the interface.
A:
Re-invoke the function zc_start.
EQ:
SDZ_ZC_FRW_ZC_DEXDO_N_FREI
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
F:
Link enabled, channel initialization running.
R:
Channel registration or channel registration checks are
started.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_KAN_INIT_START
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
reserved for debug purposes (within zc_start).
F:
Channel initialization completed without error.
R:
Channel registration or channel registration check is
completed,
channel is switched to transmit / receive operation.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_KAN_INIT_OK
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6040 Hex
F:
Back plane bus access unsuccessful.
R:
Exception processing has started, a new initialization is
subsequently implemented.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_EXC
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
not utilized.
6042 Hex to 604E
Hex
604F Hex
F:
6050 Hex
F:
6051 Hex
F:
6052 Hex
F:
6053 Hex
F:
(Multiple receiver) data inconsistent in intermediate buffer.
R:
Transmitter has overwritten the data in the channel
before the receiver
could read it.
A:
Re-invoke the function zc_start.
EQ:
SDZ_FRW_ZC_DATA_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Warning state.
The buffer status is faulty in the channel.
R:
The information in the channel management is
inconsistent, further
processing
of the channel is not possible.
A:
Contact Siemens AG.
EQ:
SDZ_FRW_ZC_PUF_ZUS_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The channel status in the channel is faulty.
R:
The information in the channel management is
inconsistent, further
processing
of the channel is not possible.
A:
Contact Siemens AG.
EQ:
SDZ_FRW_ZC_KAN_ZUS_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Refresh receiver) buffer semaphore is blocked.
R:
The information in the channel management is
inconsistent, further
processing of
the channel is not possible.
A:
Contact Siemens AG.
EQ:
SDZ_FRW_ZC_PUF_SEM_SPERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Entry in ZCVWL list not possible, since the ZCVWL list is already
full.
R:
ZCDAT area was not set, link initialization cannot be
started.
A:
Reduce the link partners on the processor board.
EQ:
SDZ_FRW_ZC_ZCVWL_VOLL
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-9
Communication Error Codes
6058 Hex
Memory assigning for ZCDAT structure not possible,
exact error cause see section Error Supplementary Code
bsspvw_geme.
R:
ZCDAT area was not set, link initialization cannot be
started.
A:
Reduce the RAM requirement in the application.
EQ:
SDZ_FRW_ZC_ZCDAT_VOLL
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
F:
(Only PN local link) the CIP entry cannot be accessed, since it
points to another processor board.
R:
ZCDAT structure was set, but the link initialization cannot
be started.
A:
Board name at the communications port must
correspond to the nameof the processor board.
EQ:
SDZ_FRW_ZC_CIP_NAM_KENN_N_ADR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
F:
The CIP entry for the link does not exist.
R:
ZCDAT structure was set, but the link initialization cannot
be started.
A:
Check the configured name at the communications port.
EQ:
SDZ_FRW_ZC_CIP_NAM_N_KENN
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
F:
Unknown function return value of the function zbak_cip_suche.
R:
ZCDAT structure was set, but the link initialization cannot
be started.
A:
Contact Siemens AG.
EQ:
SDZ_FRW_ZC_CIP_SUCH_FRW_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Not utilized.
6059 Hex
F:
6054 Hex
6055 Hex
6056 Hex
6057 Hex
3-10
F:
Channel registration not possible since memory location in
DEXDO3
interface is too small.
R:
Channel is not switched to the transmit / receive
operation.
A:
Implement a memory reorganization (using CDV
connector at the
corresponding central block) in order to
remove possible channel
corpses;
Reduce the link partners in the application.
EQ:
SDZ_FRW_ZC_MEM_KURZ
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
605A Hex
F:
605B Hex
F:
605C Hex
F:
605D Hex
F:
605E Hex
F:
Channel with the desired channel names found but channel
registration
check faulty because channel mode of the
channel and the user are
different.
R:
Channel is not switched to the transmit / receive
operation.
A:
Check the desired channel modes of the link partner.
EQ:
SDZ_FRW_ZC_KAN_MOD_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Channel with the desired channel names found but channel
registration
check faulty because the user data structure of
the channel and the
user are different.
R:
Channel is not switched to the transmit / receive
operation.
A:
Check the user data structures (connector types) of the
link partner.
EQ:
SDZ_FRW_ZC_DATA_STR_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Channel with the desired channel names found but channel
registration
check faulty because the user data length of the
channel and the user are different.
R:
Channel is not switched to the transmit / receive
operation.
A:
Check the desired user data lengths of the link partner.
EQ:
SDZ_FRW_ZC_DATA_LEN_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Channel with the desired channel names found but channel
registration
check faulty because the utility type of the
channel and the user are
different.
R:
Channel is not switched to the transmit / receive
operation.
A:
Check the user types of the link partner.
EQ:
SDZ_FRW_ZC_DIENSTTYP_ERR
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Configuring error in the PROFIBUS DP (SS52)
R:
Channel is not released in the transmit/receive mode.
A:
Check the configuring; make sure that:
Mode = Refresh or (for receivers) Multiple
Utility type = Process data
First character in the address stage 2 = "0" or "1"
EQ:
SDZ_FRW_ZC_CSL2A_ERR
EM:
ZCIN.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’, KFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-11
Communication Error Codes
605F Hex
F:
6060 Hex
F:
6061 Hex
F:
6062 Hex
F:
6063 Hex
F:
3-12
Internal error in the PROFIBUS DP (SS52)
R:
Channel is not released in the transmit/receive mode.
A:
Inform Siemens AG.
EQ:
SDZ_FRW_ZC_VARTYP_ERR
EM:
ZCIN.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’, KFF
(Only receiver) the acknowledge ‘‘Incorrect Transmit Address’’
was
read from the channel.
R:
No connection to the link partner, because no remote
partner can be accessed under this transmit address.
A:
Check the transmit address of the link partner.
EQ:
SDZ_QUIT_SEND_ADR_ERR _
EM:
ZCRD.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Only transmit) the acknowledge ‘‘Incorrect Receive Address’’
was
read from the channel.
R:
No connection to the link partner, since no remote
partner can be accessed under this receive address.
A:
Check the receive address of the link partner.
EQ:
SDZ_QUIT_EMPF_ADR_ERR _
EM:
ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Only for networks)
The acknowledge ‘‘Data Block False’’ was read from the
channel.
R:
The network could not connect to the last rack.
A:
Check that the utility types of the transmit and receive
blocks concur with one another;
Check that the desired data lengths of the transmit and
receive blocks concur with one another;
Check that the channel modes of the transmit and
receive blocks concur with one another;
Reduce the number of interface users for an end
interface on CSH11
or CS7 boards.
EQ:
SDZ_QUIT_TRANSIT_NDB_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge "No resources" was read by the channel.
R:
No connect to link partner, since no resources are
available.
A:
CSH11: Check the buffer dimensioning in the NML
configuring and modify if necessary.
SS52: No help
EQ:
SDZ_QUIT_N_RESOURCE _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Block dependant
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6064 Hex
F:
6065 Hex
F:
6066 Hex
F:
6067 Hex
F:
The acknowledge ‘‘Type Mis-Match’’ was read from the channel.
R:
No connection to the link partner, since the channel type
does not
match to the link partner.
A:
Check the channel type of the utility block:
Firmware is not permitted to synchronize itself as a
receiver to the channel type multiple or as a transmitter to the
channel type select.
EQ:
SDZ_QUIT_TYP_MISMATCH _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge ‘Impermissible Utility Type’’ was read from the
channel.
R:
No connection to the link partner, since the utility type of
the channel
was faulty or not permitted by the link partner.
A:
Utilize a block, whose utility type is permitted by the link
partner;
for SINEC L2 DP only the utility type process data is
permitted.
EQ:
SDZ_QUIT_ILLEGAL_DIENSTTYP _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge ‘‘CIP User Data Length does not match the
Address
Stage 2’’ was read from the channel.
R:
No connection to the link partner, since the required
length of the user
data and the address stage 2 are
incompatible.
A:
Select another address stage;
Adapt the size of the data to be transmitted in the
address stage.
EQ:
SDZ_QUIT_NDL_N_ADR2 _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge "Incorrect address stage 1" was read by the
channel.
R:
No connect to link partner, since the channel’s address
stage 1 does not match the link partner.
A:
Check the address stage 1 value range.
EQ:
SDZ_QUIT_ADR1_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Block dependant
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-13
Communication Error Codes
6068 Hex
F:
6069 Hex
F:
606A Hex
F:
606B Hex
F:
606C Hex
F:
3-14
The acknowledge "Incorrect address stage 2" was read by the
channel.
R:
No connect to link partner, since the channel’s address
stage 2 does not match the link partner.
A:
Check the address stage 2 value range.
USS: Check whether the station number has been
entered into thering buffer or whether a broadcast channel to a
device has been
registered or whether an address stage 2
is configured
EQ:
SDZ_QUIT_ADR2_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Block dependant
The acknowledge ‘‘CIP User Data Length does not match the
User Data length of the VARANM Area’’ was read from the
channel.
R:
SW or HW error.
A:
Contact Siemens AG.
EQ:
SDZ_QUIT_NDL_N_VARANM _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge ‘‘Transmitter Already Registered’’ was read
from the channel.
R:
No connection to the link partner, since a transmitter is
already
registered and a maximum of one is permitted.
A:
Remove a transmitter.
EQ:
SDZ_QUIT_SEND_ANM _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge ‘‘Receiver Already Registered’’ was read from
the
channel.
R:
No connection to the link partner, since a receiver is
already registered
and a maximum of one is permitted.
A:
Remove a receiver.
EQ:
SDZ_QUIT_EMPF_ANM _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
The acknowledge ‘‘Invalid Data Format in VARANM Area’’ was
read
from the channel.
R:
No connection to the link partner, since the data format
to be transmitted is not permitted.
A:
Check permissible data formats according to the table.
EQ:
SDZ_QUIT_DATA_FORMAT _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
606D Hex
F:
606E Hex
F:
606F Hex
F:
6070 Hex
F:
The acknowledge ‘‘VARANM Area too Large’’ was read from the
channel.
R:
SW or HW error.
A:
Contact Siemens AG.
EQ:
SDZ_QUIT_VARANM_LEN_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Only SINEC L2 DP)
ET200U:
The acknowledge ‘‘Board Pulled’’ was
read from the channel.
ET200K:
The acknowledge ‘‘Port Faulty’’ was read
from the channel.
R:
Bit 3 of the station diagnostics (byte 0 of the slave
station) was set.
A:
Check allocated station.
EQ:
SDZ_QUIT_BG_AUS_PORT_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Only SINEC L2 DP)
ET200U:
The acknowledge ‘‘Incorrect Address ID’’
was read from the channel.
ET200K:
The acknowledge ‘‘Parameter Fault’’
was read from the channel.
R:
Bit 2 of the station diagnostics (byte 0 of the slave
station) was set.
A:
Check station parameters.
EQ:
SDZ_QUIT_ADR_ERR_PARA_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
(Only SINEC-L2-DP)
The acknowledge "Configuring error: Station type does
not match
IM318B" was read from the channel.
R:
No data exchange takes place via this channel with the
corresponding
Slave-Station.
A:
COM ET200: Check configuration of this station.
EQ:
SDZ_QUIT_PARA_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’
KFF
(6070, pointer to configured name,
Suppl. info dependent upon message generating block)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-15
Communication Error Codes
6071 Hex
F:
6072 Hex
F:
6073 Hex
F:
6074 Hex
F:
3-16
The acknowledge "maximum number of channel connects
reached,
no further channels possible" was read from the channel.
R:
No data exchange takes place via this channel with the
corresponding
link partner.
A:
Reduce number of transmit / receive function blocks
EQ:
SDZ_QUIT_MAX_CHANNEL _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’
KFF
(6071, pointer to configured name,
Suppl. info dependent upon message generating block)
The acknowledge "incorrect mode (mode of operation)" was read
from
the channel.
R:
No data exchange takes place via this channel with the
corresponding
link partner.
A:
Check mode (mode of operation: Refresh, Handshake,
Select, Multiple)
EQ:
SDZ_QUIT_MODE_ERR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’
KFF
(6072, pointer to configured name,
Suppl. info dependent upon message generating block)
(Only SINEC-L2-DP)
Channel’s user data length does not match the COM
ET200 configuring.
R:
No data exchange to the corresponding link partner takes
place via this channel.
A:
SIMADYN D : Match the amount of data to be
transmitted;
COM ET200: modify configuration.
EQ:
SDZ_QUIT_NDL_N_AWI _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Block dependant
(Only SINEC-L2-DP)
Channel does not match COM ET200 configuring
(Address Stage1,
Station Number)
R:
No data exchange to the corresponding link partner takes
place via this channel.
A:
Match the address stage1 and station number in COM
ET200.
EQ:
SDZ_QUIT_N_STAT_ADR1 _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
Block dependant
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6075 Hex
6076 Hex
6077 Hex
6078 Hex to 60BE
Hex
60BE Hex
60BF Hex
F:
(Only SINEC L2 DP)
The acknowledge ‘‘No AWI Data Configured for the
Channel’’ was read
from the channel.
R:
No connection to the link partner, since the AWI data
area does not exist in the link partner.
A:
SIMADYN D: Remove transmit / receive FB;
COM ET200: Configure input / output bytes for station.
EQ:
SDZ_QUIT_NO_AWI_DATA _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
F:
The acknowledge "Receive telegram is larger than the available
user data buffer" was read from the channel.
R:
No data exchange takes place via this channel with the
corresponding
link partner.
A:
Check configuring;
ensure that the maximum transmit data length does not
exceed the receive data length.
EQ:
SDZ_QUIT_NDL_ZUKL _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’
KFF
(6076, pointer to configured name,
Suppl. info dependent upon message generating block)
F:
User data length too large for the link.
R:
No data exchange to the corresponding link partner takes
place via this channel.
A:
Reduce the amount of user data
EQ:
SDZ_QUIT_NDL_ZUGR _
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block that invokes the function zc_start
AA:
7-Seg ’C’
KFF
(6077, pointer to configured name,
Additional information dependant upon message
generating block)
not utilized.
F:
F:
Unknown acknowledge value detected by the channel
management.
R:
SW or HW error.
A:
Contact Siemens AG.
EQ:
SDZ.SD
EM:
ZCRD.CSF, ZCWR.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
Unknown status flag in the ZCDAT structure.
R:
The channel is disabled.
A:
Contact Siemens AG.
EQ:
SDZ.SD
EM:
ZCIN.CSF
AM:
Block invoking the function zc_start.
AA:
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-17
Communication Error Codes
3.2.2 Data Interface Initialization Errors (IB Errors)
60E0 Hex
F:
60E1 Hex
F:
60E2 Hex
F:
60E3 Hex
F:
The IB could not create the PN local KDR list.
Exact cause of error, see section Error Supplementary
Code bsspvw_info.
R:
Processor board is not initialized.
A:
Contact Siemens AG.
EQ:
ZG_ERR_NUM_KDR_LIST_N_EIN
EM:
ZG.CSF
AM:
ZG.CSF
AA:
7-Seg. ‘I’.
The IB could not create the PN local ZCVWL list.
Exact cause of error, see section Error Supplementary
Code bsspvw_info.
R:
Processor board is not initialized.
A:
Contact Siemens AG.
EQ:
ZG_ERR_NUM_ZCVWL_LIST_N_EIN
EM:
ZG.CSF
AM:
ZG.CSF
AA:
7-Seg. ‘I’.
The IB could not create the PN local ZINI list.
Exact cause of error, see section Error Supplementary
Code bsspvw_info.
R:
Processor board is not initialized.
A:
Contact Siemens AG.
EQ:
ZG_ERR_NUM_ZINI_LIST_N_EIN
EM:
ZG.CSF
AM:
ZG.CSF
AA:
7-Seg. ‘I’.
The IB could not create the PN local list.
Exact cause of error, see section Error Supplementary
Code bsspvw_info.
R:
Processor board is not initialized.
A:
Contact Siemens AG.
EQ:
ZG_ERR_NUM_CIP16K_LIST_N_EIN
EM:
ZG.CSF
AM:
ZG.CSF
AA:
7-Seg. ‘I’.
3.2.3 Network
6100 Hex
3-18
F:
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the @NMC initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NMC_ZUGR_KDR
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6101 Hex
F:
6102 Hex
F:
6103 Hex
F:
6104 Hex
F:
6105 Hex
F:
6106 Hex
F:
6107 Hex
F:
Faulty operating status.
R:
Abort the @NMC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NMC_BZS_ERR
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
Initialization error.
R:
Abort the @NMC initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NMC_INI
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
General @NMC group error.
R:
Abort the @NMC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NMC_INT_ERR
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
Channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the @NMC normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NMC_DREI_APFEL
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
No longer sufficient RAM memory available .
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @NMC normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NMC_NO_MEM
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
Error in function zbin_komdat.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the @NMC normal mode.
A:
See section Error Supplementary Code zbin_komdat.
EQ:
ZF_ERR_NUM_NMC_ZBIN_KOMDAT
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
Invoking the sub-task not successful.
R:
Abort the @NMC initialization.
A:
Check the configured sampling time.
EQ:
ZF_ERR_NUM_NMC_INI_SUB_TASK
EM:
_NMC.CSF
AM:
_NMC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-19
Communication Error Codes
6108 Hex to 611E
Hex
6120 Hex
not utilized.
6121 Hex
F:
6122 Hex
F:
6123 Hex
F:
6124 Hex
F:
6125 Hex
F:
3-20
F:
No @NMC configured or correctly initialized.
R:
Abort the NRI initialization.
A:
Correct @NMC configuring.
EQ:
ZF_ERR_NUM_NRI_N_NMC
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ’C’; YTS
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the NRI initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NRI_N_KDR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ’C’; YTS.
Faulty ISA connector.
R:
Abort the NRI initialization.
A:
Correctly configured the ISA connector.
EQ:
ZF_ERR_NUM_NRI_ISA_ERR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
RAM memory assigning for NMC-NRI element not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_ELEM
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
RAM memory assigning for NMC-NRI buffer not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_BUF
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
RAM memory assigning for NRI-NMC buffer not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_MEM_NRI_NMC_BUF
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6126 Hex
F:
6127 Hex
F:
6128 Hex
F:
6129 Hex
F:
612A Hex
F:
612C Hex
F:
612E Hex
F:
RAM memory assigning for RIL not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_MEM_RIL
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS
Unknown operating status.
R:
Abort the NRI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NRI_BZS_ERR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ’C’; YTS
Configured data interface not found.
R:
Abort the NRI normal mode.
A:
Correctly configure the CTS connector.
EQ:
ZF_ERR_NUM_NRI_N_CIP
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ’C’; YTS.
Channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NRI normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NRI_KAN_ERR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
Error during channel search interface channel Read.
R:
Abort the NRI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NRI_N_IK1_SUCHE
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS
Error during channel search interface channel Write.
R:
Abort the NRI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NRI_N_IK2_SUCHE
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
RAM memory assigning for VARANM area IKR not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_VARANM_IKR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-21
Communication Error Codes
612F Hex
F:
6130 Hex
6131 Hex
6132 Hex
6133 Hex
6134 Hex to 6135
Hex
6136 Hex
3-22
RAM memory assigning for KOMDAT area IKR not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_KOMDAT_IKW
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
not utilized.
F:
RAM memory assigning for VARANM area IKW not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_VARANM_IKW
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
F:
RAM memory assigning for KOMDAT area IKW not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_KOMDAT_IKW
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
F:
RAM memory assigning for intermediate buffer IKW not
possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NRI normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NRI_N_ZW_IKW
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
not utilized.
F:
The function zbak_kop_typ could not find the ZINI list;
or the function zbak_kop_typ could not find the desired
CIP entry in the
ZINI lists;
or the function return value of the function zbak_kop_typ
is unknown.
R:
Abort the NRI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NRI_ZBAK_KOP_TYP_FRW_ERR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6137 Hex
F:
The link type is not supported.
R:
Abort the NRI normal mode.
A:
Configure NRI-FB on a board, that has network
capability.
EQ:
ZF_ERR_NUM_NRI_KOP_TYP_ERR
EM:
NRI.CSF
AM:
NRI.CSF
AA:
7-Seg. ‘C’; YTS.
not utilized.
6138 Hex to 613F
Hex
6140 Hex
F:
6141 Hex
F:
6142 Hex
F:
6143 Hex
F:
6144 Hex
F:
6145 Hex
No @NMC initialized.
R:
Abort the NSI initialization.
A:
Correctly configure @NMC.
EQ:
ZF_ERR_NUM_NSI_N_NMC
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
No NTC initialized.
R:
Abort the NSI initialization.
A:
Correctly configure NTC.
EQ:
ZF_ERR_NUM_NSI_N_NTC
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
No NET list exists.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the NSI initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NSI_N_NET
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
Faulty operating state.
R:
Abort the NSI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NSI_N_DEF
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
Faulty return value of the zc_start function.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NSI normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NSI_ZC
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-23
Communication Error Codes
6146 Hex
F:
6147 Hex
6148 Hex
6149 Hex
614A Hex
614B Hex to 6161
Hex
6162 Hex
3-24
No global list KDR exists.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the NSI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NSI_N_KDR
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ’C’; YTS
not utilized.
F:
No back-up list exists.
R:
Abort the NSI initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NSI_BCK_LIST
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
F:
RAM memory assigning not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NSI initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NSI_N_RAM
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS.
F:
Error in function zbin_komdat.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the NSI initialization.
A:
See section Error Supplementary Code zbin_komdat.
EQ:
ZF_ERR_NUM_NSI_ZBIN
EM:
NSI.CSF
AM:
NSI.CSF
AA:
7-Seg. ‘C’; YTS
not utilized.
F:
Faulty return value for the function zc_start.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NSL normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NSL_N_DEF
EM:
NSL.CSF
AM:
NSL.CSF
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6163 Hex
6164 Hex
6165 Hex to
6166Hex
6167 Hex
6168 Hex
6169 Hex to 617F
Hex
6180 Hex
6181 Hex
F:
Channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NSL normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NSL_ZC
EM:
NSL.CSF
AM:
NSL.CSF
AA:
7-Seg. ‘C’; YTS.
F:
Faulty operating status.
R:
Abort the NSL normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NSL_BZS
EM:
NSL.CSF
AM:
NSL.CSF
AA:
7-Seg. ’C’; YTS
not utilized.
F:
Insufficient RAM memory available.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NSL initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NSL_N_RAM
EM:
NSL.CSF
AM:
NSL.CSF
AA:
7-Seg. ‘C’; YTS.
F:
Error in the function zbin_komdat.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the NSL initialization.
A:
See section Error Supplementary Code zbin_komdat.
EQ:
ZF_ERR_NUM_NSL_ZBIN
EM:
NSL.CSF
AM:
NSL.CSF
AA:
7-Seg. ’C’; YTS.
not utilized.
F:
F:
No function block NTD correctly initialized.
R:
Abort the NTC normal mode.
A:
Correctly configure function block NTD.
EQ:
ZF_ERR_NUM_NTC_NO_NTD
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
No data interface for processing received from @NMC.
R:
Abort the NTC normal mode.
A:
This function block does not need to be configured.
EQ:
ZF_ERR_NUM_NTC_GOT_NO_CIP
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-25
Communication Error Codes
6182 Hex
F:
6183 Hex
F:
6184 Hex
F:
6185 Hex
F:
6186 Hex
6187 Hex
F:
6188 Hex
F:
6189 Hex
F:
3-26
The @NMC is not (no longer) active.
R:
Abort the NTC normal mode.
A:
Analyze the @NMC error message.
EQ:
ZF_ERR_NUM_NTC_NMC_OFF
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Faulty operating status.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_BZS_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Error while accessing the global list KDR.
R:
Abort the NTC initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZUGR_KDR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS
Multiple configuring NTC.
R:
Abort the NTC initialization.
A:
The function block NTC does not need to be configured.
EQ:
ZF_ERR_NUM_NTC_MEHRFACHPROJ
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
not utilized.
Insufficient RAM memory available.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NTC normal mode.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NTC_NO_MEM
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Insufficient memory available on MM11.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NTC initialization.
A:
Create available memory.
EQ:
ZF_ERR_NUM_NTC_NO_NET_MEM
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Unknown channel mode.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_KANALMODUS_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
618A Hex
F:
618B Hex
F:
618C Hex
F:
618D Hex
F:
618E Hex
F:
618F Hex
F:
Unknown channel status.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_KAN_STATUS
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
An invalid value is to be written into a status byte.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_KAN_FLAGS_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Invalid transit ID read from the channel.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_TRANSIT_KENNUNG_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Invalid transit direction of the channel determined.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_TRANSIT_RICHTUNG_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
Channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NTC normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NTC_DREI_APFEL
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
The function znak_transit_kennung could not find a channel with
the
desired register number;
or the return value of the function znak_transit_kennung
is unknown.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KENNUNG_FR
W_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-27
Communication Error Codes
6190 Hex
F:
6191 Hex
F:
6192 Hex
F:
6193 Hex
F:
6194 Hex
F:
3-28
The function znei_transit_kennung could not find a channel
with the desired register number;
or the function znei_transit_kennung determined that the
semaphore
for the transit ID in the channel is disabled;
or the return value of the function znei_transit_kennung
is unknown.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNEI_TRANSIT_KENNUNG_FR
W_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
The function znak_prk_aktiv determined that the desired link is
not a rack link;
or the return value of the function znak_prk_aktiv is
unknown.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNAK_PRK_AKTIV_FRW_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
Unknown return value of the function znei_kanal_komdat.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNEI_KANAL_KOMDAT_FRW_E
RR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Unknown return value of the function znak_dexdo_zugriff.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNAK_DEXDO_ZUGRIFF_FRW_
ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
The function znak_varanm_laenge could not find a channel with
the
desired registered number;
or the return value of the function znak_varanm_laenge
is unknown.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNAK_VARANM_LAENGE_FRW
_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6195 Hex
F:
6196 Hex
F:
6197 Hex
F:
6198 Hex
F:
6199 Hex
F:
619A Hex
F:
Unknown return value of the function znak_transit_kanal.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KANAL_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
Faulty return value of the function zc_start.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NTC normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NTC_ZC_START_FRW_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Internal error.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_INT_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
Several transmitters / receivers for the same handshake / refresh
channel.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_KAN_HR_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ‘C’; YTS.
The function zcei_kan_nam_loesch could not find a channel with
the
desired registered number;
or the return value of the function zcei_kan_nam_loesch
is unknown.
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZCEI_KAN_NAM_LOESCH_FRW
_ERR
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
The function zcak_kanal_nummer_bestimmen could not find a
channel
with the desired registered number; or the return
zcak_kanal_nr_bestimmen is unknown.
value of the function
R:
Abort the NTC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTC_ZCAK_KAN_NR_BEST_FRW_ER
R
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-29
Communication Error Codes
619B Hex to 619F
Hex
61A0 Hex
61A1 Hex
61A2 Hex
61A3 Hex
614A Hex to 61A7
Hex
61A8 Hex
61A9 Hex
3-30
not utilized.
F:
No function block NTC active.
R:
Abort the NTD initialization.
A:
Correctly configure the function block NTC.
EQ:
ZF_ERR_NUM_NTD_NO_NTC
EM:
NTD.CSF
AM:
NTD.CSF
AA:
7-Seg. ’C’; YTS.
F:
Faulty return value of the function zc_start.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the NTD normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_NTD_KAN_ERR
EM:
NTD.CSF
AM:
NTD.CSF
AA:
7-Seg. ’C’; YTS.
F:
Too little RAM memory.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the NTD initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_NTD_N_MEM
EM:
NTD.CSF
AM:
NTD.CSF
AA:
7-Seg. ‘C’; YTS.
F:
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the NTD initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTD_N_KDR
EM:
NTD.CSF
AM:
NTD.CSF
AA:
7-Seg. ‘C’; YTS.
not utilized.
F:
F:
Copy relationship failed (whilst reading the source channel).
R:
Copy relationship is no longer processed. The block
remains enabled.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTD_STS_ERR_QUELLE
EM:
NTD.CSF
AM:
NTD.CSF
AA:
YTS.
Copy relationship failed (whilst writing to the destination
channel).
R:
Copy relationship is no longer processed. The block
remains enabled.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_NTD_STS_ERR_ZIEL
EM:
NTD.CSF
AM:
NTD.CSF
AA:
YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
61AA Hex
F:
61AB Hex
F:
Incorrect function return value.
R:
NTD is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_NTD_N_CIP
EM:
NTD.CSF
AM:
NTD.CSF
AA:
7-Seg. ’C’
Too many data interfaces (CIP).
R:
NTC is disabled
A:
Reduce the number of data interfaces (fewer
MM11/MM4 or CS11/CS21)
EQ:
ZF_ERR_NUM_NTC_CIP_ANZ
EM:
NTC.CSF
AM:
NTC.CSF
AA:
7-Seg. ’C’
3.2.4 Service
6200 Hex
F:
6201 Hex
F:
6202 Hex
F:
6203 Hex
F:
General initialization error.
Exact cause see section Error Supplementary Code
bsspvw_geme.
zbin_komdat and
R:
Abort the initialization, SER block not operating.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_SER_INIT_ERR
EM:
zdsest.csf
AM:
zdsest.csf
AA:
7-Seg. ‘C’; YTS.
Initialization errors: insufficient RAM memory available.
Exact cause see section Error Supplementary Code
bsspvw_geme.
zbin_komdat and
R:
Abort the initialization, SER block not operating.
A:
Create available RAM memory.
EQ:
Z_ERR_NUM_SER_INIT_NO_MEM
EM:
zdsest.csf
AM:
zdsest.csf
AA:
7-Seg. ’C’; YTS.
Initialization error: request channel cannot be initialized.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the initialization, SER block not operating.
A:
Check specifications at the CTS and US connectors.
EQ:
Z_ERR_NUM_SER_INIT_KOMDAT_RD
EM:
zdsest.csf
AM:
zdsest.csf
AA:
7-Seg. ’C’; YTS.
Initialization error: reply channel cannot be initialized.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the initialization, SER block not operating.
A:
Check specifications at the CTS and US connectors.
EQ:
Z_ERR_NUM_SER_INIT_KOMDAT_WR
EM:
zdsest.csf
AM:
zdsest.csf
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-31
Communication Error Codes
6204 Hex
F:
6205 Hex
F:
6206 Hex
F:
Initialization error: sub-task not created.
R:
SER block cannot operate.
A:
Check configured sampling times.
EQ:
Z_ERR_NUM_SER_INIT_SUB_TASK
EM:
zdsest.csf
AM:
zdsest.csf
AA:
7-Seg. ’C’; YTS.
Request channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
SER block is disabled.
A:
See section Data Interface Access Mechanisms.
EQ:
Z_ERR_NUM_SER_KAN_ERR_RD
EM:
zdsekrd.csf
AM:
zdsekrd.csf
AA:
7-Seg. ‘C’; YTS.
Reply channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
SER block is disabled.
A:
See section Data Interface Access Mechanisms.
EQ:
Z_ERR_NUM_SER_KAN_ERR_WR
EM:
zdsekwr.csf
AM:
zdsekwr.csf
AA:
7-Seg. ‘C’; YTS.
3.2.4.1 Display
6281 Hex
F:
6282 Hex
F:
6283 Hex
F:
3-32
Configuring FB type @DIS0R, connector DIS:
Multiple configuring of display system with the same
name.
R:
Block is disabled.
A:
Enter correct specification at connector DIS.
EQ:
Z_ERR_NUM_DIS_MEHRFACH
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring FB type @DIS0R: Invalid sampling time.
R:
Block is disabled.
A:
Configure @DIS0R with valid sampling time (30ms <= t
<= 300ms)
EQ:
Z_ERR_NUM_DIS_ABTASTZEIT
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring FB type @DIS0R or DISxy, connector ST1 and ST2:
No display station specified.
R:
Block is disabled.
A:
Specification at connector ST1 or ST2 not equal to zero.
EQ:
Z_ERR_NUM_DIS_NOSTATION
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6284 Hex
F:
6285 Hex
F:
6286 Hex
F:
6287 Hex
F:
6288 Hex
F:
Configuring @DIS0T or DISxy, connector DIS:
Associated central block @DIS0R or @DIS0T is not
configured.
R:
Block is disabled.
A:
Configure block type @DIS0R and @DIS0T with the
same specification at connector DIS.
EQ:
Z_ERR_NUM_DIS_NO_ZB
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring @DIS0T or DISxy, connector DIS:
Associated central block @DIS0R is not configured.
R:
Block is disabled.
A:
Configure block type @DIS0R with the same
specification at connector
DIS.
EQ:
Z_ERR_NUM_DIS_NO_DIS
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring @DIS0T or DISxy:
Sampling time does not match the associated @DIS0R.
R:
Block is disabled.
A:
Configure block with the same sampling time as
@DIS0R.
EQ:
Z_ERR_NUM_DIS_AKT_AUFGABE
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring DISA4, connector Y or DISS4, connector X:
Type switching to V4 is not permitted.
R:
Block is disabled.
A:
Set different connector type.
EQ:
Z_ERR_NUM_DIS_V4
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Configuring DISxy, connector ST1 and ST2:
Configured stations are not all initialized by the central
block @DIS0R.
R:
Block is disabled.
A:
Only specify those stations at ST1, ST2, that are also
specified at
@DIS0R.
EQ:
Z_ERR_NUM_DIS_STA_NOZB
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-33
Communication Error Codes
6289 Hex
F:
628A Hex
F:
628B Hex
F:
6290 Hex
F:
6291 Hex
F:
3-34
Configuring DISx, connector KEY:
Process data number is already defined (for a display
station).
R:
Block is disabled.
A:
Select other process data number or check specification
at ST1, ST2.
EQ:
Z_ERR_NUM_DIS_PZD_DOP
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address of
the display station)
Configuring DIS1x, connector KEY:
Binary value number is already defined (for a display
station).
R:
Block is disabled.
A:
Select other binary value number or check specification
at ST1, ST2.
EQ:
Z_ERR_NUM_DIS_BIN_DOP
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address of
the display station)
Configuring DISxy, connector KEY: Invalid value configured.
R:
Block is disabled.
A:
Configure valid value (review block description).
EQ:
Z_ERR_NUM_DIS_KEY
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Internal: Error during memory create.
Precise cause: review section Error suppl. code
bsspvw_geme.
R:
Block is disabled.
A:
Reduce the RAM requirements in the application.
EQ:
Z_ERR_NUM_DIS_GEME
EM:
ZDDI.CSF, function BSSPVW_GEME
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of
BSSPVW_GEME)
Internal: Error during Save-memory create for setpoint.
Precise cause: review section Error suppl. code
bsspvw_geme.
R:
Block is disabled.
A:
Reduce the SAVE requirements in the application.
EQ:
Z_ERR_NUM_DIS_GEMESAV
EM:
ZDDI.CSF, function BSSPVW_GEME
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of
BSSPVW_GEME)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6292 Hex
F:
6293 Hex
F:
6294 Hex
F:
6295 Hex
F:
6296 Hex
F:
6297 Hex
F:
6298 Hex
F:
Internal: Error during SAVE-pointer create for setpoint.
R:
Block is disabled.
A:
Reduce the SAVE requirements in the application.
EQ:
Z_ERR_NUM_DIS_SAVPUF
EM:
ZDDI.CSF, function BSSAVPUF_GEME
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Internal: KDR list not found
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_KDR
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Internal: Error during sampling time calculation
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_AMPI_TN
EM:
ZDDI.CSF, function AMPI_TN
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI_TN)
Internal: Error during receive channel initialization.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_KOMDAT_EMPF
EM:
ZDDI.CSF, function ZBIN_KOMDAT
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl.
code = FRW of ZBIN_KOMDAT)
Internal: Error during transmit channel initialization.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_KOMDAT_SEND
EM:
ZDDI.CSF, function ZBIN_KOMDAT
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl.
code = FRW of ZBIN_KOMDAT)
Internal: Implementation error.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_IMPLEM
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Internal: Implementation error
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_FORMAT
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-35
Communication Error Codes
6299 Hex
F:
629A Hex
F:
629B Hex
F:
62A0 Hex
F:
62A1 Hex
F:
62A2 Hex
F:
3-36
Internal: (P32) Error during connector description fetch.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_BESCHR
EM:
ZDDI.CSF, function AMPI/AFPI
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI/AFPI
function)
Internal: (P16) Segment pointer fetch unsuccessful.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_BSBI_SEG
EM:
ZDDI.CSF, function BSBI_SEG
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Internal: (P16) Dimension text fetch unsuccessful.
R:
Block is disabled.
A:
Inform Siemens AG.
EQ:
Z_ERR_NUM_DIS_BSBI_DIM
EM:
ZDDI.CSF, function BSBI_DIM
AM:
ZDDI.CSF
AA:
YTS; 7-Seg. ’C’, KFF
Dialog unit: Incorrect request ID in the telegram.
R:
Transmit an error telegram to the dialog unit.
A:
Check dialog unit.
EQ:
Z_ERR_NUM_DIS_AUFKENN
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address;
Error telegram: Error class, (Error number = Request ID)
Dialog unit: Incorrect telegram length.
R:
Transmit an error telegram to the dialog unit.
A:
Check dialog unit.
EQ:
Z_ERR_NUM_DIS_AUFLGE
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address;
Error telegram: Error class, (Error number = Telegram
length)
Dialog unit: Incorrect process data number requested.
R:
Transmit an error telegram to the dialog unit.
A:
Check dialog unit.
EQ:
Z_ERR_NUM_DIS_PZDNR
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address;
Error telegram: Error class, (Error number = PZD
number)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
F:
Dialog unit: Incorrect binary value number requested.
R:
Transmit an error telegram to the dialog unit.
A:
Check dialog unit.
EQ:
Z_ERR_NUM_DIS_BINNR
EM:
ZDDI.CSF
AM:
ZDDI.CSF
AA:
YTS, YAC = Station address;
Error telegram: Error class, (Error number = BIN
number)
62A4 Hex
F:
62A5 Hex
62A6 Hex
F:
FB-DIAL2A: Impermissible specification at connector ST1 or
ST2.
R:
Block disables.
A:
Correct specification: 3<=ST1<=ST2<=123.
EQ:
Z_ERR_NUM_DPDIAG_ST1_ST8_NZUG
EM:
DIAL2A.CSF
AM:
DIAL2A.CSF
AA:
7-Seg ’C’, KFF
FB-DIAL2A: Too little memory (RAM) available.
R:
Block disables.
A:
Reduce configuring.
EQ:
Z_ERR_NUM_DPDIAG_N_SLAVE_LI
Z_ERR_NUM_DPDIAG_N_ZWI_PU
Z_ERR_NUM_DPDIAG_N_VARANM_BER
EM:
DIAL2A.CSF
AM:
DIAL2A.CSF
AA:
7-Seg ’C’, KFF
FB-@SYL2A: Impermissible specification at connector SEL.
R:
Block disables.
A:
Correct specification at connector SEL: 1<=SEL<=8.
EQ:
Z_ERR_NUM_DPSYNC_SEL_NZUG
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
7-Seg ’C’, KFF
FB-@SYL2A: Impermissible specification at connector CNX.
R:
Block disables.
A:
Correct specification at connector CNX: CNX>0.
EQ:
Z_ERR_NUM_DPSYNC_UNTERS_NZUG
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
7-Seg ’C’, KFF
FB-@SYL2A: Impermissible specification at connector CTS:
Board does not exist or not a CS7.
R:
Block disables.
A:
Correct specification at connector CTS.
EQ:
Z_ERR_NUM_DPSYNC_CIP3_NVH
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
7-Seg ’C’, KFF
62A3 Hex
3.2.4.2 Specific SS52
62A7 Hex
62A8 Hex
F:
62A9 Hex
F:
62AA Hex
F:
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-37
Communication Error Codes
62AB Hex
F:
62AC Hex
F:
62AD Hex
F:
FB-@SYL2A: Impermissible specification at connector CTS:
Only CS7/SS52 permitted with FB-@CSL2A.
R:
Block disables.
A:
Correct specification at connector CTS.
EQ:
Z_ERR_NUM_DPSYNC_KOP_NZUG
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
7-Seg ’C’, KFF
FB-@SYL2A: Impermissible multiple configuring.
R:
Block disables.
A:
Remove block.
EQ:
Z_ERR_NUM_DPSYNC_FB_MEHRFACH
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
7-Seg ’C’, KFF
FB-@SYL2A: Waiting for SS52 firmware.
R:
Wait.
A:
SS52 installed?
EQ:
Z_ERR_NUM_DPSYNC_SS52_WAIT
EM:
@SYL2A.CSF
AM:
@SYL2A.CSF
AA:
Warning
3.2.5 Process Data
6000 Hex to 60BF
Hex
6310 Hex
see section Data Interface Access Mechanisms.
6311 Hex
F:
3-38
F:
RAM memory assigning for VARANM area not possible.
Exact error cause see section Error Supplementary Code
bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
Z_FRW_ZDPD_N_MEM_VARANM
EM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
ZDPD.CSF
AM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
CCC4.CSF, CDC4.CSF
AA:
7-Seg. ‘C’; YEV.
Fehler bei Auswertung der Adreßparameter (Eingang AT, AR).
Genaue Fehlerursache siehe Abschnitt Fehlerzusatzcode
zbin_kombat.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
Z_FRW_ZDPD_INIT_KOMDAT_ERR
EM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
ZDPD.CSF
AM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
CCC4.CSF, CDC4.CSF
AA:
7-Seg. `C'; YEV.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6312 Hex
F:
6313 Hex to 631E
Hex
631F Hex
F:
6320 Hex
6321 Hex
6322 Hex
6323 Hex
6324 Hex to 631F
Hex
Specification at the MOD connector faulty.
R:
Block reverts to the dead status.
A:
Correct the specification at the MOD connector, only the
H, R, S or M
letters are permissible.
EQ:
Z_FRW_ZDPD_INIT_KOMDAT_ERR
EM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
ZDPD.CSF
AM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
CCC4.CSF, CDC4.CSF
AA:
7-Seg. ‘C’; YEV.
utilized for internal purposes.
Unknown function return value of the function zc_start.
R:
Block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_FRW_ZDPD_UNDEF
EM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
CCC4.CSF, CDC4.CSF
AM:
_CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,
CCC4.CSF, CDC4.CSF
AA:
7-Seg. ‘C’; YEV.
F:
RAM memory assigning for reference list not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CTV_N_MEM_REF_LISTE
EM:
_CTV.CSF, CTV.CSF
AM:
_CTV.CSF, CTV.CSF
AA:
7-Seg. ‘C’; YEV.
F:
RAM memory assigning for reference list not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CRV_N_MEM_REF_LISTE
EM:
_CRV.CSF, CRV.CSF
AM:
_CRV.CSF, CRV.CSF
AA:
7-Seg. ‘C’; YEV.
F:
Reference list no found; no virtual connection configured.
R:
Block reverts to the dead status.
A:
Check the virtual connection at the AT connector.
EQ:
ZF_ERR_NUM_CTV_N_REF_LISTE
EM:
_CTV.CSF, CTV.CSF
AM:
_CTV.CSF, CTV.CSF
AA:
7-Seg. ‘C’; YEV.
F:
Reference list no found; no virtual connection configured.
R:
Block reverts to the dead status.
A:
Check the virtual connection at the AR connector.
EQ:
ZF_ERR_NUM_CRV_N_REF_LISTE
EM:
_CRV.CSF, CRV.CSF
AM:
_CRV.CSF, CRV.CSF
AA:
7-Seg. ‘C’; YEV.
utilized for internal purposes.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-39
Communication Error Codes
6330 Hex
F:
6331 Hex
F:
6332 Hex
F:
6333 Hex
F:
6334 Hex
F:
3-40
RAM memory assigning for intermediate buffer not possible.
Exact error cause of error see section Error
Supplementary Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CTV_N_MEM_ZW
EM:
_CTV.CSF, CTV.CSF
AM:
_CTV.CSF, CTV.CSF
AA:
7-Seg. ‘C’; YEV.
RAM memory assigning for intermediate buffer not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CRV_N_MEM_ZW
EM:
_CRV.CSF, CRV.CSF
AM:
_CRV.CSF, CRV.CSF
AA:
7-Seg. ‘C’; YEV.
RAM memory assigning for intermediate buffer not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CCC4_N_MEM_ZW
EM:
CCC4.CSF
AM:
CCC4.CSF
AA:
7-Seg. ‘C’; YEV.
RAM memory assigning for intermediate buffer not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Block reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CDC4_N_MEM_ZW
EM:
CDC4.CSF
AM:
CDC4.CSF
AA:
7-Seg. ‘C’; YEV.
unknown connector type during evaluation of the return value
from
function zbak_kon_typ_wandel
R:
Block reverts to the neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CRV_CTV_KON_N_KENN
EM:
ZBAK.CSF
AM:
_CRV.CSF, _CTV.CSF, CRV.CSF, CTV.CSF
AA:
7-Seg. ’C’;
KFF (6334,pointer to configured name,0)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.6 Message System
6400 Hex
F:
6401 Hex
F:
6402 Hex
F:
6403 Hex
F:
6404 Hex
F:
6405 Hex
F:
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the MSI initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSI_N_KDR
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ‘C’;
No central block @MSC configured.
R:
Abort the MSI initialization.
A:
Configure central block @MSC.
EQ:
ZF_ERR_NUM_MSI_N_MSC
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ’C’;
RAM memory assigning not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the MSI initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_MSI_N_MEM
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ’C’;
KOMDAT area cannot be initialized.
Exact cause see section Error Supplementary Code
zbin_komdat.
R:
Abort the MSI initialization.
A:
See section Error Supplementary Code zbin_komdat.
EQ:
ZF_ERR_NUM_MSI_KOMDAT_INIT
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ’C’;
Channel continuously faulty.
Exact cause see section Data Interface Access
Mechanisms.
R:
Abort the MSI normal mode.
A:
See section Data Interface Access Mechanisms.
EQ:
ZF_ERR_NUM_MSI_KAN_ERR
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ’C’;
Faulty operating status.
R:
Abort the MSI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSI_BZS_ERR
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ‘C’;
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-41
Communication Error Codes
6406 Hex
F:
6407 Hex
F:
6408 Hex
F:
6409 Hex
F:
640A Hex
F:
640B Hex
F:
3-42
Faulty message format.
R:
Abort the MSI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSI_MF_ERR
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ‘C’;
Unknown return value of the function zc_start.
R:
Abort the MSI normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSI_ZC_START_FRW_ERR
EM:
MSI.CSF
AM:
MSI.CSF
AA:
7-Seg. ‘C’;
@MSC configured in incorrect sampling time.
R:
Abort the @MSC initialization.
A:
@MSC must be configured with the correct sampling
time.
EQ:
ZF_ERR_NUM_MSC_TN_ERR
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ’C’;
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the @MSC initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSC_N_KDR
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ’C’;
Multiple configuring of the @MSC.
R:
Abort the @MSC initialization.
A:
@MSC may only be configured once per rack.
EQ:
ZF_ERR_NUM_MSC_MEHR_PROJ
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ‘C’;
Global list of the SAVE area not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the @MSC initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSC_N_SAVE
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ‘C’;
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6410 Hex
Too little memory available in the SAVE area.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @MSC initialization.
A:
Create available SAVE memory.
EQ:
ZF_ERR_NUM_MSC_N_MEM_SAVE
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ‘C’;
F:
Too little memory for the message sequencing buffer.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @MSC initialization.
A:
Create available memory.
EQ:
ZF_ERR_NUM_MSC_N_MEM_MFP
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ’C’;
F:
Connector SAV of the @MSC can’t be changed online.
R:
Abort the @MSC initialization.
A:
Set connector SAV to initial value.
Changes only in the configuring.
EQ:
ZF_ERR_NUM_MSC_INV_PROJ
EM:
_MSC.CSF
AM:
@MSC
AA:
7-Seg. ’C’;
F:
No memory for the entry description system error.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @MSC initialization.
A:
Create available SAVE memory.
EQ:
ZF_ERR_NUM_MSC_N_MEM_EB_C
EM:
_MSC.CSF
AM:
_MSC.CSF
AA:
7-Seg. ’C’;
not utilized.
6411 Hex
F:
6412 Hex
F:
640C Hex
640D Hex
640E Hex
640F Hex
F:
No memory in RAM area for static intermediate buffer.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @MSC initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_MSC_N_KOM_ERROR
EM:
_MSC.CSF
AM:
_MSC.CSF
AA:
7-Seg. ’C’;
No message evaluation blocks configured.
R:
Abort the @MSC normal mode.
A:
Configure function blocks MSI.
EQ:
ZF_ERR_NUM_MSC_N_MA
EM:
_MSC.CSF
AM:
_MSC.CSF
AA:
7-Seg. ’C’;
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-43
Communication Error Codes
6413 Hex
F:
6414 Hex
F:
6415 Hex
F:
6416 Hex
F:
3-44
Faulty operating status communication error evaluation.
R:
Abort the @MSC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSC_MZC_ERR
EM:
_MSC.CSF
AM:
_MSC.CSF
AA:
7-Seg. ’C’;
Faulty operating status.
R:
Abort the @MSC normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_MSC_BZS_ERR
EM:
_MSC.CSF
AM:
_MSC.CSF
AA:
7-Seg. ’C’;
Global list KDR not found.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the ME initialization.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_ME_N_KDR
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
No central block @MSC available.
R:
Abort the ME initialization.
A:
Configure central block @MSC.
EQ:
ZF_ERR_NUM_ME_N_MSC
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6417 Hex
6418 Hex
6419 Hex
641A Hex to 641F
Hex
F:
Too little SAVE memory area for pointer.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the ME initialization.
A:
Create available SAVE memory.
EQ:
ZF_ERR_NUM_ME_N_MEM_SAVE
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
F:
Too little SAVE memory for insertion description.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the ME initialization.
A:
Create available SAVE memory.
EQ:
ZF_ERR_NUM_ME_N_MEM_FB
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
F:
Too little RAM memory for the static intermediate buffer.
Exact cause see section Error Supplementary Code
bsspvw_info.
R:
Abort the ME initialization.
A:
Create available RAM memory.
EQ:
ZF_ERR_NUM_ME_N_MEM_SP
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-45
Communication Error Codes
6420 Hex
F:
6421 Hex
F:
Faulty operating status.
R:
Abort the ME normal mode.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_ME_BZS_ERR
EM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AM:
MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,
MED.CSF,
MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,
MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
Faulty return value of a zdms function.
R:
Abort the block.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_ZDMS_FRW_ERR
EM:
_MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF,
MES4.CSF,
MES16.CSF, MED.CSF, MED2.CSF,
MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF,
MEDV2.CSF, MESV4.CSF, MEDV4.CSF
AM:
_MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF,
MES4.CSF,
MES16.CSF, MED.CSF, MED2.CSF,
MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF,
MEDV2.CSF, MESV4.CSF, MEDV4.CSF
AA:
7-Seg. ’C’;
3.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace)
6500 Hex
F:
6501 Hex
F:
3-46
RAM memory assigning for reference list not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the block initialization.
A:
Restrict the memory area to the local RAM;
Reduce configured value of the NTV connector.
EQ:
Z_ERR_NUM_TC_INI_NO_RAM_1
EM:
ZDTR.CSF
AM:
@TCI , @TCP
AA:
7-Seg. ’C’; YTS
RAM memory assigning for the trace buffer not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the control block initialization.
A:
Restrict the memory area to the local RAM;
Reduce configured value of the TBL connector.
EQ:
Z_ERR_NUM_TC_INI_NO_RAM_2
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6502 Hex
F:
6503 Hex
F:
6504 Hex
6505 Hex
6506 Hex
6507 Hex
6508 Hex
SAVE memory assigning for reference list not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the control block initialization.
A:
Restrict the memory area to the local SAVE area;
Reduce configured value of the NTV connector.
EQ:
Z_ERR_NUM_TC_INI_NO_SAVE_1
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
SAVE memory assigning for the trace buffer not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the @ control block initialization.
A:
Restrict the memory area to the local SAVE area;
Reduce configured value of the TBL connector.
EQ:
Z_ERR_NUM_TC_INI_NO_SAVE_2
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
RAM memory assigning for channel VARANM area not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the control block initialization.
A:
Restrict the memory area to the local RAM.
EQ:
Z_ERR_NUM_TC_INI_NO_RAM_3
EM:
ZDTR.CSF, _TCI.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
RAM memory assigning for channel buffer area not possible.
Exact cause see section Error Supplementary Code
bsspvw_geme.
R:
Abort the control block initialization.
A:
Restrict the memory area to the local RAM.
Reduce configured value of the NTV connector.
EQ:
Z_ERR_NUM_TC_INI_NO_RAM_4
EM:
ZDTR.CSF, _TCI.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
is not utilized.
F:
Configured value at TBL connector is equal to zero.
R:
Abort the control block initialization.
A:
Configure value not equal to zero at the TBL connector.
EQ:
Z_ERR_NUM_TC_INI_BAD_TBL
EM:
ZDTR.CSF, TRCC2.CSF
AM:
@TCI, @TCP, TRCC2
AA:
7-Seg. ’C’; YTS.
F:
TRC ID at the control block multiply exists.
R:
Abort the control block initialization.
A:
Select new unique TRC ID.
EQ:
Z_ERR_NUM_TC_INI_TC_DUP
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-47
Communication Error Codes
6509 Hex
650A Hex
650B Hex
650C Hex
650D Hex
650E Hex
650F Hex
3-48
F:
Global KDR list not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
Abort the control block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_NO_KDR
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
Global KOMM_ERROR list not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
Abort the control block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_NO_KOM
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ‘C’; YTS.
F:
KOMDAT area of the request channel was not correctly
initialized.
Exact cause of error see section Error Supplementary
Code zbin_komdat.
R:
Abort the control block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_NO_KDB_1
EM:
ZDTR.CSF
AM:
@TCI.CSF
AA:
7-Seg. ‘C’; YTS.
F:
KOMDAT area of the reply channel was not correctly initialized.
Exact cause of error see section Error Supplementary
Code zbin_komdat.
R:
Abort the control block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_NO_KDB_2
EM:
TCI.CSF, ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
SAVE area full.
R:
Abort the control block initialization.
A:
Restrict the memory area in the local SAVE area.
EQ:
Z_ERR_NUM_TC_INI_NO_SAVE_3
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS
F:
List of the SAVE area not available.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
Abort the control block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_NO_SAVE_4
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
is not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6510 Hex
6511 Hex
6512 Hex
6513 Hex
6514 Hex to 651F
Hex
6520 Hex
6521 Hex
6522 Hex
F:
Error during channel access to request channel.
Exact cause of error see section Data Interface Access
Mechanisms.
R:
@TCI reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_ZP_CHA_IN
EM:
_TCI.CSF
AM:
@TCI
AA:
7-Seg. ’C’; YTS.
F:
Error during channel access to reply channel.
Exact cause of error see section Data Interface Access
Mechanisms.
R:
@TCI reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_ZP_CHA_OUT
EM:
ZDTR.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
No acquisition block has been initialized.
R:
Acquisition block reverts to the dead status.
A:
Configure acquisition block with corresponding TRC ID.
EQ:
Z_ERR_NUM_TC_ZP_NO_TRI
EM:
_TCI.CSF, _TCP.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
F:
Unknown connector format to be recorded.
R:
Block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_BAD_FORMAT
EM:
TRCC2.CSF
AM:
TRCC2
AA:
7-Seg. ’C’; YTS.
are not utilized.
F:
Global KDR list does not exist.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
Abort the acquisition block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TR_INI_NO_KDR
EM:
ZDTR.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
is not utilized.
F:
Multiple configuring of the same acquisition block in the same
task.
R:
Abort the acquisition block initialization.
A:
Re-configure.
EQ:
Z_ERR_NUM_TR_INI_NO_TCI
EM:
ZDTR.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ‘C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-49
Communication Error Codes
6523 Hex
F:
6524 Hex
F:
6525 Hex
F:
6526 Hex
F:
6527 Hex
F:
3-50
List of the SAVE area does not exist.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
Abort the acquisition block initialization.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TR_INI_NO_SAVE_1
EM:
ZDTR.CSF, TRCC2.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
SAVE area full.
R:
Abort the acquisition block initialization.
A:
Reduce memory requirements in the local SAVE area.
EQ:
Z_ERR_NUM_TR_INI_NO_SAVE_2
EM:
ZDTR.CSF, TRCC2
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
SAVE memory assigning for reference list body not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Abort the acquisition block initialization.
A:
Reduce memory requirements in the local SAVE area.
EQ:
Z_ERR_NUM_TR_INI_NO_SAVE_3
EM:
ZDTR.CSF, TRCC2.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
SAVE memory assigning for trace value list not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Abort the acquisition block initialization.
A:
Reduce memory requirements in the local SAVE area;
Reduce configured value at the NTV connector of the
corresponding @TCI.
EQ:
Z_ERR_NUM_TR_INI_SAVE_4
EM:
ZDTR.CSF, TRCC2.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
RAM memory assigning for reference list body not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Abort the acquisition block initialization.
A:
Reduce memory requirements in the local RAM area.
EQ:
Z_ERR_NUM_TR_INI_NO_RAM_1
EM:
ZDTR.CSF, TRCC.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6528 Hex
6529 Hex
652A Hex
652B Hex to 653F
Hex
6540 Hex
F:
RAM memory assigning for trace value list not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
Abort the acquisition block initialization.
A:
Reduce memory requirements in the local RAM area;
Reduce configured value at the NTV connector of the
corresponding @TCI.
EQ:
Z_ERR_NUM_TR_INI_NO_RAM_2
EM:
ZDTR.CSF, TRCC.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
F:
No control block with corresponding TRC ID initialized.
R:
Abort the acquisition block initialization.
A:
Configure control block with corresponding TRC ID.
EQ:
Z_ERR_NUM_TR_INI_UNKWN_TRC
EM:
ZDTR.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
F:
Connector ID not uniquely selected.
R:
Abort the acquisition block initialization.
A:
Utilize unique connector ID at the acquisition block.
EQ:
Z_ERR_NUM_TR_INI_DUP_CID
EM:
TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF
AM:
TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
are not utilized.
F:
6541 Hex
F:
6542 Hex
F:
Unknown block status for control block.
R:
Control block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_ZP_BAD_BZS
EM:
_TCI.CSF, _TCP.CSF, TRCC2.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF, TRCC2
AA:
7-Seg. ’C’; YTS.
Ring buffer size too small.
R:
Control block reverts to the dead status.
A:
Enlarge trace buffer / configure fewer acquisition blocks.
EQ:
Z_ERR_NUM_TR_ZP_SM_UMPUF
EM:
_TCP.CSF
AM:
@TCP
AA:
7-Seg. ’C’; YTS.
Sampling time for the control block cannot be determined.
R:
Control block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TC_INI_BAD_TIME
EM:
_TCI.CSF, _TCP.CSF
AM:
@TCI, @TCP
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-51
Communication Error Codes
6543 Hex
F:
6544 Hex
F:
6545 Hex
F:
Information function of the operating system could not be
invoked.
R:
Acquisition block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TR_INI_BAD_AFPI
EM:
TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF
AM:
TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
6546 Hex
F:
6547 Hex
F:
6548 Hex
F:
Invalid value at the HIA of TRHI
R:
TRHI reverts to the dead status.
A:
Configure a value between 0 and 10 at the connector
HIA of the TRHI.
EQ:
Z_ERR_NUM_TR_INI_PARAM_ANZ
EM:
TRHI.CSF
AM:
TRHI
AA:
7-Seg. ’C’; YTS.
TRHI block multiply configured.
R:
TRHI reverts to the dead status.
A:
Configure only one TRHI per trace system.
EQ:
Z_ERR_NUM_TR_INI_MEHR
EM:
TRHI.CSF
AM:
TRHI
AA:
7-Seg. ’C’; YTS.
Channel length at the group telegram has been configured too
small.
R:
@TCP reverts to the dead status.
A:
Select a larger connector CHA of the @TCP. The
minimum number is
located at the supplement of the
communication error message.
EQ:
Z_ERR_NUM_TC_ZP_CHA
EM:
_TCP.CSF
AM:
@TCP
AA:
7-Seg. ’C’; YTS.
3-52
Sampling time for the acquisition block cannot be determined.
R:
Acquisition block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TR_INI_BAD_TIME
EM:
_TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF,
TRPF.CSF
AM:
@TRI , TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
Unknown block status for acquisition block.
R:
Acquisition block reverts to the dead status.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_TR_ZP_BAD_BZS_
EM:
_TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF,
TRPF.CSF
AM:
@TRI, TRP1, TRP2, TRP4, TRPF
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6549 Hex
654A Hex
654B Hex to 657F
Hex
F:
Too many acquisition blocks at the group telegram output.
R:
@TCP reverts to the dead status.
A:
Configure fewer than 256 acquisition blocks
(TRP1,TRP2,TRP4,TRPF).
EQ:
Z_ERR_NUM_TC_TRP_ANZ
EM:
_TCP.CSF
AM:
@TCP
AA:
7-Seg. ’C’; YTS.
F:
Length of the output channel is less than 200 bytes.
R:
Block reverts to the dead status.
A:
Set the output channel size (connector CHA) to at least
200.
EQ:
Z_ERR_NUM_CHA_OUT_LEN
EM:
ZDTR.CSF
AM:
@TCP, @TCI
AA:
7-Seg. ’C’; YTS.
not utilized.
3.2.8 Time
6600 Hex
6601 Hex
6602 Hex
6603 Hex
F:
The board name at the TM connector refers to a board that does
not
exist in the rack or cannot function as a time source.
R:
RTCM reverts to the dead status.
A:
Enter the name of a board that can act as a time source:
- Master Processor Board,
- CSH11,
- MM3,
- SS5,
- CS21.
EQ:
ZF_ERR_NUM_RTCM_SZQ_N_VALID
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
not utilized.
F:
Unknown operating status of the RTCM block.
R:
RTCM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_RTCM_BZS_ERR
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
F:
Memory assigning for the local structures not possible.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
RTCM reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_RTCM_N_MEM
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-53
Communication Error Codes
6604 Hex
6605 Hex
6606 Hex
6607 Hex
6608 Hex
6609 Hex
660A Hex
3-54
F:
Several RTCM blocks were configured in the same rack.
R:
RTCM reverts to the dead status.
A:
Remove one of the configured RTCM blocks.
EQ:
ZF_ERR_NUM_RTCM_MEHR_PROJ
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
F:
A SS5 import board (at the TM connector) and a SS5 export
board
(at the TTM connector) are simultaneously configured.
R:
RTCM reverts to the dead status.
A:
Another clock source must be configured at the TM
connector;
The name of the SS5 export board at the TTM connector
must be
removed.
EQ:
ZF_ERR_NUM_RTCM_CSL2F_PROJ
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
F:
PN local KDR list not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
RTCM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_RTCM_N_KDR
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS
not utilized.
F:
The rack has no CBUS connection.
R:
RTCM reverts to the dead status.
A:
Utilize rack with CBUS connection (i.e. SR8).
EQ:
ZF_ERR_NUM_RTCM_N_CBUS
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
F:
RTCM block was configured with an impermissible sampling time
(not between 128 ms and 512 ms).
R:
RTCM reverts to the dead status.
A:
Configure the sampling time between 128 ms and 512
ms.
EQ:
ZF_ERR_NUM_RTCM_ABTASTZEIT_ERR
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
F:
The RTCM block is configured on a board that is not a master.
R:
RTCM reverts to the dead status.
A:
Configure RTCM block on a processor board (processor
1) installed to the left.
EQ:
ZF_ERR_NUM_RTCM_N_MASTER
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
660B Hex
F:
660C Hex
F:
The clock specification at the connectors XYR, XMO, XDA, XHR
and / or XMI are invalid.
R:
RTCM reverts to the dead status.
A:
Check specifications at the connectors XYR, XMO, XDA,
XHR and
XMI Permissible values are:
00 v XYR v 99
01 v XMO v 12
01 v XDA v 31
00 v XHR v 23
00 v XMI v 59
EQ:
ZF_ERR_NUM_RTCM_STELL_N_VALID
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
Access to link memory unsuccessful.
R:
RTCM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_RTCM_BUS_ZUGR_ERR
EM:
RTCM.CSF
AM:
RTCM.CSF
AA:
7-Seg. ’C’; YTS.
3.2.8.1 Device
6700 Hex
F:
6701 Hex
F:
6702 Hex
F:
Incorrect assignments UP connector
R:
@DPH reverts to a neutral state
A:
Check specification at connector UP. Permissible values:
1-3
EQ:
ZF_ERR_NUM_DPH_UP
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
Invalid combination UP and PHL connector
R:
@DPH reverts to a neutral state
A:
Check specifications at the UP and PHL connectors.
Invalid combination:
PHL = 0 ( 3 word PIV interface )
UP = 1 ( SINEC-L2-DP protocol )
EQ:
ZF_ERR_NUM_DPH_UP_PHL
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
KDR list not found
R:
@DPH reverts to a neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_DPH_NO_KDR
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF (Suppl. code = FRW of
SDB_FUNC_BSSPVW_INFO)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-55
Communication Error Codes
6703 Hex
F:
6704 Hex
F:
6705 Hex
F:
6706 Hex
F:
6707 Hex
F:
6710 Hex
F:
6711 Hex
F:
3-56
Multiple configuring of central blocks
R:
@DPH reverts to a neutral state
A:
Connector value PHS must differ on local processor for
each @DPH block.
EQ:
ZF_ERR_NUM_DPH_MEHR_PROJ
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
No memory available
R:
@DPH reverts to a neutral state
A:
Reduce memory requirement
EQ:
ZF_ERR_NUM_DPH_NO_MEM
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF (Suppl. code = FRW of
SDB_FUNC_BSSPVW_GEME)
No parameter block DPI configured
R:
@DPH reverts to a neutral state
A:
Configure at least one block DPI with the same
connector value PHS
EQ:
ZF_ERR_NUM_DPH_NO_DPI
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
Internal error
R:
@DPH reverts to a neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_DPH_DPI_AK
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
Internal error
R:
@DPH reverts to a neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_DPH_INT_ERR
EM:
_DPH.CSF
AM:
_DPH.CSF
AA:
7-Seg. ’C’; YTS, KFF
KDR list not found
R:
DPI reverts to a neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_DPI_NO_KDR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
7-Seg. ’C’; YTS, KFF (Suppl. code = FRW
SBD_FUNC_BSSPVW_INFO)
No central block @DPH configured
R:
DPI reverts to a neutral state
A:
Configure central block @DPH with the same connector
specification
PHS
EQ:
ZF_ERR_NUM_DPI_NO_DPH
EM:
DPI.CSF
AM:
DPI.CSF
AA:
7-Seg. ’C’; YTS, KFF
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6712 Hex
F:
6713 Hex
F:
6714 Hex
F:
6715 Hex
F:
6716 Hex
F:
6717 Hex
F:
Faulty cascade sequencing
R:
DPI reverts to a neutral state
A:
A request was transferred from several parameter blocks
DPI to the
same central block. Check the cascade
configuring !
EQ:
ZF_ERR_NUM_DPI_IC_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
7-Seg. ’C’; YTS, KFF
Internal error
R:
DPI reverts to a neutral state
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_DPI_INT_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
7-Seg. ’C’; YTS, KFF
Incorrect parameter ID at the PR connector
R:
DPI does not generate request
A:
Specify correct value at the connector PR. Permissible
values: 0-11
EQ:
ZF_ERR_NUM_DPI_REQ_PR_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
QS1; YTS
Incorrect parameter number at the PN connector
R:
DPI does not generate request.
A:
Specify correct value at the connector PN. Permissible
values: 0-2047
EQ:
ZF_ERR_NUM_DPI_REQ_PN_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
QS1; YTS
Incorrect parameter index at the PI connector
R:
DPI does not generate request
A:
Specify correct value at the connector PI. Permissible
values: 0-254
EQ:
ZF_ERR_NUM_DPI_REQ_PI_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
QS1; YTS
Double word request with PIV interface length of 3 words at the
connector PR
R:
DPI does not generate request
A:
Configure correct word request at connector PR
EQ:
ZF_ERR_NUM_DPI_PR_4_BYTE_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
QS1; YTS
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-57
Communication Error Codes
F:
No reply from the device within the TIME-OUT period
R:
DPI has not received reply
A:
Increase TIME-OUT period (connector RCM) at the
central block @DPH, check communication with the device.
EQ:
ZF_ERR_NUM_DPI_RES_TIME_OUT_ERR
EM:
DPI.CSF
AM:
DPI.CSF
AA:
QS2; YTS
6800 Hex
F:
6801 Hex
F:
6802 Hex
F:
6803 Hex
F:
6804 Hex
F:
6805 Hex
F:
Internal status error 1.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_BZS
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Internal status error 2.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ATG_STATE
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Internal status error 3.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ANT_STATE
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Internal status error 4.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_KON_STATE
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Internal status error 5.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_KOP_STATE
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Too little memory.
R:
Block LPN disables.
A:
Reduce application’s RAM requirements.
EQ:
ZF_ERR_NUM_LPN_NO_MEM
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
6718 Hex
3.2.8.2 Download
3-58
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6806 Hex
F:
6807 Hex
F:
6808 Hex
F:
6809 Hex
F:
680A Hex
F:
680B Hex
F:
680C Hex
F:
Multiple configuring of the block LPN.
R:
Block LPN disables.
A:
Only configure one LPN-FB per processor board.
EQ:
ZF_ERR_NUM_LPN_MULT
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
KDR list not found
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_NO_KDR
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Job request channel continually faulty.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ATG_KAN
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Job request initialization faulty
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ATG_KOMDAT_INIT
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Job request initialization faulty.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ATG_KAN_INIT
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Reply channel continually faulty.
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ANT_KAN
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Reply channel initialization faulty
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ANT_KOMDAT_INIT
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-59
Communication Error Codes
680D Hex
F:
680E Hex
F:
680F Hex
F:
6810 Hex
F:
Reply channel initialization faulty
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_ANT_KAN_INIT
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Unknown card type
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_CARD_TYPE_ERR
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Internal card programming error
R:
Block LPN disables.
A:
Inform Siemens AG..
EQ:
ZF_ERR_NUM_LPN_BSFC_FRW_ERR
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
Sub-task initialization not possible
R:
Block LPN disables.
A:
Configure LPN-FB in a different sampling time.
EQ:
ZF_ERR_NUM_LPN_INI_SUB_TASK
EM:
LPN.CSF
AM:
LPN.CSF
AA:
QTS; YTS
3.2.9 Central Blocks for Links
3.2.9.1 Coupling Memory Link
6900 Hex
F:
6901 Hex
F:
3-60
Several @CMM blocks were configured with the same coupling
memory board names.
R:
@CMM reverts to the dead status.
A:
Remove one of the configured @CMM blocks.
EQ:
ZF_ERR_NUM_CMM_MEHR_PROJ
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_CIP_FREI_FRW_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6902 Hex
F:
The CIP entry for the @CMM block cannot be accessed.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
6903 Hex
F:
6904 Hex
F:
6905 Hex
F:
6906 Hex
F:
6907 Hex
F:
6908 Hex
F:
The CIP entry for the @CMM block does not exist.
R:
@CMM reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CMM_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_SUCH_FRW_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_REOR_FRW_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CMM block.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_BZS_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for the warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CMM reverts to the dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CMM_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-61
Communication Error Codes
6909 Hex
F:
690A Hex
F:
690B Hex
F:
690C Hex
F:
690D Hex
F:
690E Hex
F:
3-62
@CMM block was configured in an impermissible sampling time
(not between 32 ms and 255 ms).
R:
@CMM reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CMM_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CMM reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CMM_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the reorganization structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CMM reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CMM_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_fb_init.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_FB_INIT_FRW_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Link type in CIP entry is not set to ‘‘Coupling Memory Link’’.
R:
@CMM reverts to the dead status.
A:
Check the configured name at the CTS connector;
Check that the configured block type corresponds to
@CMM
EQ:
ZF_ERR_NUM_CMM_KOP_TYP_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_ANM_FRW_ERR
EM:
_CMM.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
F:
Unknown registered status determined in DEXDO3 management
section.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CMM_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CMM.CSF
AA:
7-Seg. ’C’
6910 Hex
F:
6911 Hex
F:
6912 Hex
F:
Several @CS11 blocks were configured with the same CS11
board names.
R:
@CS11 reverts to the dead status.
A:
Remove one of the configured @CS11 blocks
EQ:
ZF_ERR_NUM_CS11_MEHR_PROJ
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_CIP_FREI_FRW_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CS11 block cannot be accessed.
R:
@CMM reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
6913 Hex
F:
6914 Hex
F:
690F Hex
3.2.9.2 Rack Link
The CIP entry for the @CS11 block does not exist.
R:
@CS11 reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CS11_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_SUCH_FRW_ERR
EM:
._CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-63
Communication Error Codes
6915 Hex
F:
6916 Hex
F:
6917 Hex
F:
6918 Hex
F:
6919 Hex
F:
691A Hex
F:
3-64
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_REOR_FRW_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CS11 blocks.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_BZS_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for the warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS11 reverts to the dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CS11_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
@CS11 block was configured in a impermissible sampling time
(not between 32 ms and 255 ms).
R:
@CS11 reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CS11_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Memory assignment not possible for the exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS11 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CS11_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
691B Hex
F:
691C Hex
F:
691D Hex
F:
691E Hex
F:
691F Hex
F:
6920 Hex
F:
Memory assigning not possible for the reorganization structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS11 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CS11_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_fb_init.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_FB_INIT_FRW_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Link type or sub-link type is not set to "CS11 rack link".
R:
@CS11 reverts to the neutral state
A:
Check the configured name at the CTS connector;
The configured name at the CTS connector must
correspond to a
CS11 board
EQ:
ZF_ERR_NUM_CS11_KOP_TYP_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_ANM_FRW_ERR
EM:
_CS11.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
Unknown registered status detected in DEXDO3 management
section.
R:
@CS11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS11_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CS11.CSF
AA:
7-Seg. ’C’
The configured name of the @CS21 block corresponds to
another in
the link.
R:
@CS21 reverts to the dead status.
A:
Check, whether the name at the CTS connector
corresponds to another CS21 block;
Check, whether the @CS21 block has been multiply
configured on the
same CS21 board.
EQ:
ZF_ERR_NUM_CS21_MEHR_PROJ
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-65
Communication Error Codes
6921 Hex
F:
6922 Hex
F:
6923 Hex
6924 Hex
6925 Hex
6926 Hex
6927 Hex
6928 Hex
3-66
The CIP entry for the @CS21 block cannot be accessed.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CS21 block does not exist.
R:
@CS21 reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CS21_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function zbak_cip_suche.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_CIP_SUCH_FRW_ERR
EM:
._CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
not utilized.
F:
There are already three registered @CS21 blocks in the link.
R:
@CS21 reverts to the dead status.
A:
Power down rack and power up again after 10 seconds;
Check whether more than three CS21 boards exist on
the link;
Check whether the @CS21 block has been multiply
configured on the
same CS21 board.
EQ:
ZF_ERR_NUM_CS21_SCHON_DREI_CS21
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
The configured CS11 board does not exist.
R:
@CS21 reverts to the dead status.
A:
Check the configured CS11 name at the MTS connector.
EQ:
ZF_ERR_NUM_CS21_CS11_N_KENN
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _cs21_anmeldung.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_ANM_FRW_ERR
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Unknown operating status of the @CS21 block.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_BZS_ERR
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6929 Hex
692A Hex
692B Hex
692C Hex
692D Hex
692E Hex
692F Hex to 6931
Hex
F:
SAVE memory assigning not possible for the warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme
R:
@CS21 reverts to the dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CS21_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
@CS21 block was configured in an impermissible sampling time
(not between 32 ms and 255 ms).
R:
@CS21 reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CS21_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Memory assigning not possible for exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS21 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CS21_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Memory assigning not possible for reorganization structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS21 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CS21_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function zp_fb_init.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_FB_INIT_FRW_ERR
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-67
Communication Error Codes
6932 Hex
6933 Hex
6934 Hex to 693F
Hex
F:
Link type or sub-link type is not set to "CS11 rack link".
R:
@CS21 reverts to the neutral state
A:
Check the configured name at the CTS connector;
The configured name at the CTS connector must
correspond to a
CS21 board
EQ:
ZF_ERR_NUM_CS21_KOP_TYP_ERR
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
F:
The software version on the processor board is not compatible
with the version in the CS11 rack.
R:
@CS21 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CS21_VERSION_ERR
EM:
_CS21.CSF
AM:
_CS21.CSF
AA:
7-Seg. ’C’
not utilized.
3.2.9.3 PN Local Link
6940 Hex
F:
6941 Hex
F:
6942 Hex
F:
6943 Hex
F:
3-68
The @CPN block was multiply configured on the same processor
board.
R:
@CPN reverts to the dead status.
A:
Remove one of the configured @CPN blocks.
EQ:
ZF_ERR_NUM_CPN_MEHR_PROJ
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_CIP_FREI_FRW_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CPN block cannot be accessed,
since it is pointing to another processor board.
R:
@CPN reverts to the dead status.
A:
Board name at the CTS connector must correspond to
the name of the processor board.
EQ:
ZF_ERR_NUM_CPN_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CPN block does not exist.
R:
@CPN reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CPN_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6944 Hex
F:
6945 Hex
F:
6946 Hex
F:
6947 Hex
F:
6948 Hex
F:
6949 Hex
F:
Unknown function return value of the function zbak_cip_suche.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_CIP_SUCH_FRW_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_REOR_FRW_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CPN block.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_BZS_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CPN reverts to dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CPN_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
@CPN block was configured in an impermissible sampling time
(not between 32 ms and 255 ms)
R:
@CPN reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CPN_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-69
Communication Error Codes
694A Hex
F:
694B Hex
F:
694C Hex
F:
694D Hex
F:
694E Hex
F:
694F Hex
F:
3-70
Memory assigning not possible for exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS21 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CPN_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS21 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CPN_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_fb_init.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG
EQ:
ZF_ERR_NUM_CPN_FB_INIT_FRW_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Link type is not set to ‘‘PN Local Link’’.
R:
@CS21 reverts to the dead status
A:
Check the configured name at the CTS connector;
Check that the configured block type corresponds to
@CS21.
EQ:
ZF_ERR_NUM_CPN_KOP_TYP_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_ANM_FRW_ERR
EM:
_CPN.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
Unknown register status detected in the DEXDO3 management
section.
R:
@CPN reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CPN_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CPN.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.9.4 Link DUST1
6965 Hex
6966 Hex
6969 Hex to 6996
Hex
F:
Specification at the TWU connector faulty.
R:
@CSD01 reverts to the dead status.
A:
Set specifications at the TWU connector to only decimal
values be
tween 0 and 1000.
EQ:
ZF_ERR_NUM_CSD1_TWU_ERR
EM:
_CSD01.CSF
AM:
_CSD01.CSF
AA:
7-Seg. ’C’
F:
Specification at the BDR connector faulty.
R:
@CSD01 reverts to the dead status.
A:
The specification at the BDR connector can only
correspond to one of the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200
EQ:
ZF_ERR_NUM_CSD1_BDR_ERR
EM:
_CSD01.CSF
AM:
_CSD01.CSF
AA:
7-Seg. ’C’
not utilized.
3.2.9.5 Link SINEC H1
6970 Hex
F:
6971 Hex
F:
6972 Hex
F:
6973 Hex
F:
Several @CSH11 blocks were configured with the same CSH11
board names.
R:
@CSH11 reverts to the dead status.
A:
Remove one of the configured @CSH11 blocks.
EQ:
ZF_ERR_NUM_CSH1_MEHR_PROJ
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_CIP_FREI_FRW_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSH11 block cannot be accessed.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSH11 block does not exist.
R:
@CSH11 reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CSH1_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-71
Communication Error Codes
6974 Hex
F:
6975 Hex
F:
6976 Hex
F:
6977 Hex
F:
6978 Hex
F:
6979 Hex
F:
3-72
Unknown function return values of the function zbak_cip_suche.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_CIP_SUCH_FRW_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown function return values of the function
zp_dexdo_reorganization.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_REOR_FRW_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CSH11 block.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_BZS_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CSH11 reverts to dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CSH1_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
@CSH11 block was configured in an impermissible sampling
time
(not between 32 ms and 255 ms)
R:
@CSH11 reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CSH1_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
697A Hex
F:
697B Hex
F:
697C Hex
F:
697D Hex
F:
697E Hex
F:
697F Hex
F:
Memory assigning not possible for the exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CSH11 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSH1_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CS21 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSH1_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_fb_init.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_FB_INIT_FRW_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Link type not set to ‘‘CSH11 Link’’.
R:
@CSH11 reverts to the dead status.
A:
Check the configured name at the CTS connector;
Check that the block type corresponds to @CSH11.
EQ:
ZF_ERR_NUM_CSH1_KOP_TYP_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_ANM_FRW_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-73
Communication Error Codes
6980 Hex
F:
6981 Hex
F:
6982 Hex
F:
6983 Hex
F:
6984 Hex
F:
6985 Hex
F:
6986 Hex
F:
3-74
CSH11 firmware has detected an unrepairable error.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_INI_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
CSH11 firmware has reverted to an error status.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_TOT
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown status of the CSH11 firmware.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_ZUS_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_FIRM_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Length of the specified address at the MAA connector is false.
R:
@CSH11 reverts to the dead status.
A:
Specification at the MAA connector must be exactly 12
characters
long.
EQ:
ZF_ERR_NUM_CSH1_STRING_LEN_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Specification at the MMA connector faulty.
R:
@CSH11 reverts to the dead status.
A:
The address at the MAA connector must correspond to a
hexa decimal number, i.e. only numbers 0, 1, 2, 3, 4, 5, 6, 7, 8,
9 and letters a, b, c,
d, e, f are permitted.
EQ:
ZF_ERR_NUM_CSH1_STRING_ERR
EM:
_CSH11.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the firmware structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CSH11 reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSH1_N_MEM
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6987 Hex
6988 Hex
6989 Hex to 698F
Hex
F:
Unknown function return value of the function _csh11_init.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSH1_INI_FRW_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function
_csh11_firmware_init.
R:
@CSH11 reverts to the dead status.
A:
Contact Siemens AG
EQ:
ZF_ERR_NUM_CSH1_FIR_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
not utilized.
3.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung
6990 Hex
F:
6991 Hex
F:
6992 Hex
F:
6993 Hex
F:
Several communications central blocks were configured
with the same CS7 board names or interface name.
R:
@CSxyz reverts to the dead status.
A:
Remove one of the configured @CSxyz blocks
EQ:
ZF_ERR_NUM_CL2F_MEHR_PROJ
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown return function of the function zp_cip_freigabe.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_CIP_FREI_FRW_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSxyz block cannot be accessed.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSxyz block does not exist.
R:
@CSxyz reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CL2F_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-75
Communication Error Codes
6994 Hex
F:
6995 Hex
F:
6996 Hex
F:
6997 Hex
F:
6998 Hex
F:
6999 Hex
F:
3-76
Unknown function return value of the function zbak_cip_suche.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_CIP_SUCH_FRW_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_REOR_FRW_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CSxyz block.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_BZS_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CSxyz reverts to dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CSH1_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSH11.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG
EQ:
ZF_ERR_NUM_CL2F_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSxyz.CSF
@CSxyz block was configured in an impermissible sampling
time
(not between 32 ms and 255 ms)
R:
@CSxyz reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CL2F_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
699A Hex
F:
699B Hex
F:
699C Hex
F:
699D Hex
F:
699E Hex
F:
699F Hex
F:
69A0 Hex
F:
Memory assigning not possible for the exception structure.
R:
@CSxyz reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CL2F_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the reorganization structure.
R:
@CSxyz reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CL2F_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown function return value for the function zp_fb_init.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_FB_INIT_FRW_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Link type is not set to ‘‘CSL2x Link’’.
R:
@CSxyz reverts to the dead status.
A:
Check the configure name at the CTS connector;
Check that the block type corresponds to @CSxyz.
EQ:
ZF_ERR_NUM_CL2F_KOP_TYP_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown function return value for the function
zp_anmelde_ueberwachung.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_ANM_FRW_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
CSL2x firmware has detected an unrepairable error.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_INIT_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-77
Communication Error Codes
69A1 Hex
F:
69A2 Hex
F:
69A3 Hex
F:
69A4 Hex
69A5 Hex
69A6 Hex
69A7 Hex
3-78
CSL2x firmware has reverted to an error status or SS5x module
insert is missing.
R:
@CSxyz reverts to the dead status.
A:
SS5x module in the CS7 board;
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_TOT
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown status of the CSL2x firmware.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_ZUS_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_FIRM_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
F:
Station address false at the MAA connector.
R:
@CSxyz reverts to the dead status.
A:
The specification at the MAA connector must correspond
to a
number between 1 and 126. (@CSL2A: between 1 and
123)
EQ:
ZF_ERR_NUM_CL2F_STAT_ADR_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
not utilized.
F:
Memory assigning not possible for the firmware structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme
R:
@CSxyz reverts to the dead status.
A:
Reduce the RAM requirement of the application.
EQ:
ZF_ERR_NUM_CL2F_N_MEM
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _csl2f_init.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
69A8 Hex
F:
69A9 Hex
F:
69AA Hex
F:
69AB Hex
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
69AC Hex
69AD Hex
69AE Hex
Unknown function return value of the function
_csl2f_firmware_init.
R:
@CSxyz reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CL2F_FIR_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Specification of the BDR connector faulty.
R:
@CSxyz reverts to the dead status.
A:
The coded baud rate at the BDR connector must
correspond to
a number between 0 and 5 (@CSL2A: between 0 and 8).
EQ:
ZF_ERR_NUM_CL2F_BDR_ERR
EM:
_CSxyz.CSF
AM:
_CSxyz.CSF
AA:
7-Seg. ’C’
Specification of the AST connector faulty.
R:
@CSL2L reverts to the dead status.
A:
The value at the BDR connector must correspond to
a number between 0 and 126.
EQ:
ZF_ERR_NUM_CL2L_AST_ERR
EM:
_CSL2L.CSF
AM:
_CSL2L.CSF
AA:
7-Seg. ’C’
Projektierungsfehler Eingang LTT
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Eingang LTT korrigieren
ZF_ERR_NUM_STD_KON_LTT
_peer.csf
_peer.csf
Projektierungsfehler Eingang LTR
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Eingang LTR korrigieren
ZF_ERR_NUM_STD_KON_LTR
_peer.csf
_peer.csf
Projektierungsfehler Anschluss CTS
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Anschluss CTS korrigieren (X01, X02 beachten)
ZF_ERR_NUM_STD_KON_CTS
_peer.csf, _uss_s/m
_peer.csf, _uss_s/m
Fehler bei Kommunikationsinitialisierung („ZINI-Eintrag“)
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Siemens AG benachrichtigen
ZF_ERR_NUM_STD_FRW_ZINI
diverse
diverse
Zusatzcode: Rückgabewert der Funktion zg_zini_Nachtrag
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-79
Communication Error Codes
69AF Hex
F:
R:
A:
EQ:
EM:
AM:
69B0 Hex
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
R:
A:
EQ:
EM:
AM:
F:
69B1 Hex
69B2 Hex
69B3 Hex
69B4 Hex
69B5 Hex
69B6 Hex
R:
A:
EQ:
EM:
AM:
3-80
Fehler bei Speicherbeschaffung
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Projektierung verkleinern
ZF_ERR_NUM_STD_FRW_GEME
diverse
diverse
Zusatzcode: Rückgabewert der Funktion bsspvw_geme
Schnitstelle X01/X02 ist belegt
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Nur eine Kopplung pro Schnittstelle projektieren
ZF_ERR_NUM_STD_SST_BELEGT
_peer.csf, _uss_s/m
_peer.csf, _uss_s/m
Projektierungsfehler Eingang BDR
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Eingang BDR korrigieren
ZF_ERR_NUM_STD_KON_BDR
_peer.csf, _uss_s/m
_peer.csf, _uss_s/m
Projektierungsfehler Eingang MAA
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Eingang MAA korrigieren
ZF_ERR_NUM_STD_KON_MAA
_uss_s
_uss_s
Projektierungsfehler Eingang PZD
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Eingang PZD korrigieren
ZF_ERR_NUM_STD_KON_PZD
_uss_s
_uss_s
Schnitstelle X01 nicht für USS freigegeben
USS wird nicht gestartet, es läuft Service auf X01
Schalter S1/8 auf T400 auf ON stellen
ZF_ERR_NUM_STD_SST_SPERR_X01
_uss_s/m
_uss_s/m
Zwei USS-Kopplungen auf T400
Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld
Nur eine USS-Kopplung auf T400 projektieren
ZF_ERR_NUM_STD_USS_DOPPELT
_uss_s/m
_uss_s/m
Empfangene Telegrammlänge passt nicht zur projektierten
Länge
Telegramm wird verworfen
Telegrammlänge des Kommunikationspartners mit projektierter
Länge abgleichen
(USS-Slave: Eingänge PAR, PZD; USS-Master: Anzahl virtueller
Verbindungen)
ZF_ERR_NUM_STD_TEL_LEN_EMPF
_uss_s/m
_uss_s/m
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.9.7 EP Link
69D0 Hex
F:
69D1 Hex
F:
69D2 Hex
F:
69D3 Hex
F:
69D4 Hex
F:
69D5 Hex
F:
Several @CEP22 resp. @CEP blocks have been configured with
the
same EP22 board name.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Remove one of the configured @CEP22 resp. @CEP
blocks.
EQ:
ZF_ERR_NUM_EP22_MEHR_PROJ
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_CIP_FREI_FRW_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CEP22 resp. @CEP block cannot be
accessed.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CEP22 resp. @CEP block does not
exist.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_EP22_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_CIP_SUCH_FRW_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_REOR_FRW_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-81
Communication Error Codes
69D6 Hex
F:
69D7 Hex
F:
69D8 Hex
F:
69D9 Hex
F:
69DA Hex
F:
69DB Hex
F:
3-82
Unknown operating status of the @CEP22 resp. @CEP block.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_BZS_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for the warm start flag.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_EP22_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
SAVE are not found.
Exact cause of error see section Error Supplementary
Code bsspvw_info
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
@CEP22 resp. @CEP block was configured in an impermissible
sampling time (not between 32 ms and 255 ms).
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_EP22_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the exception structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_EP22_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for the reorganization structure.
Exact cause of error see section Error Supplementary
Code sspvw_geme.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_EP22_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
69DC Hex
F:
69DD Hex
F:
69DE Hex
F:
69DF Hex
F:
69E0 Hex
F:
69E1 Hex
F:
69E2 Hex
F:
Unknown function return value of the function zp_fb_init.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_FB_INIT_FRW_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Link type in the CIP entry is not set to ‘‘Coupling Memory Link’’.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Check the configured name at the CTS connector;
Check that the configured block type corresponds to
@CEP22 resp. @CEP.
EQ:
ZF_ERR_NUM_EP22_KOP_TYP_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_ANM_FRW_ERR
EM:
_CEP22.CSF resp. _CEP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
CEP22 firmware has detected an unrepairable error.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_INIT_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
CEP22 firmware has reverted to an error status.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_TOT
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
Unknown status of the CEP22 firmware.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_ZUS_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-83
Communication Error Codes
69E3 Hex
F:
69E4 Hex to 69E5
Hex
69E6 Hex
F:
69E7 Hex
69E8 Hex
69E9 Hex to 69EF
Hex
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_FIRM_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
not utilized.
Memory assigning not possible for the firmware structure.
Exact cause of error see section Error Supplementary
Code bsspvw_geme.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_EP22_N_MEM
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _CEP22_init resp.
_CEP_init.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function
_CEP22_firmware_init.
R:
@CEP22 resp. @CEP reverts to the dead status.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_EP22_FIR_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CEP22.CSF resp. _CEP.CSF
AA:
7-Seg. ’C’
not utilized.
3.2.9.8 Link DUST7
69F0 Hex
3-84
F:
Several communication central blocks were configured with the
same
CS7 board names or interface names.
R:
@CSD07 reverts to the dead state.
A:
Remove one of the configured @CSD07 blocks;
Correct the interface specification of one @CSD07
block.
EQ:
ZF_ERR_NUM_CSD7_MEHR_PROJ
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
69F1 Hex
F:
69F2 Hex
F:
69F3 Hex
F:
69F4 Hex
F:
69F5 Hex
F:
69F6 Hex
F:
69F7 Hex
F:
Unknown function return value of the function zp_cip_freigabe.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_CIP_FREI_FRW_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD07 block is not accessible.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD07 block does not exist.
R:
@CSD07 reverts to the dead state.
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CSD7_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_CIP_SUCH_FRW_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_REOR_FRW_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown operating status of the @CSD07 block.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_BZS_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD07 reverts to the dead state.
A:
Reduce the SAVE requirement in the application
EQ:
ZF_ERR_NUM_CSD7_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-85
Communication Error Codes
69F8 Hex
F:
69F9 Hex
F:
69FA Hex
F:
69FB Hex
F:
69FC Hex
F:
69FD Hex
F:
3-86
SAVE area not found.
Exact cause of error see section Error supplementary
code bsspvw_info.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
@CSD07 block configured in impermissible sampling time (not
between 32ms and 255ms)
R:
@CSD07 reverts to the dead state.
A:
Configure the sampling time between 32ms and 255ms
EQ:
ZF_ERR_NUM_CSD7_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for exception structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD07 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD7_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD07 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD7_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_fb_init.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_FB_INIT_FRW_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Link type is not set to "DUST1" or "CS7".
R:
@CSD07 reverts to the dead state.
A:
Check the configured name at CTS connector;
Check that block type corresponds to @CSD07
EQ:
ZF_ERR_NUM_CSD7_KOP_TYP_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
69FE Hex
F:
69FF Hex
F:
6A00 Hex
F:
6A01 Hex
F:
6A02 Hex
F:
6A03 Hex
F:
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_ANM_FRW_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
@CSD07
AA:
7-Seg. ’C’
DUST1 firmware has detected an unrepairable error.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_DUST_INIT_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
DUST1 firmware has reverted to an error status or SS4 adapter
module missing.
R:
@CSD07 reverts to the dead state.
A:
Install SS4 module in CS7 board;
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_DUST_TOT
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown status of the DUST1 firmware.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_ZUS_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_FIRMWARE_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-87
Communication Error Codes
6A04 Hex
6A05 Hex
6A06 Hex
6A07 Hex
6A08 Hex
6A09 Hex
6A0A Hex to 6A0F
Hex
3-88
F:
Memory assigning not possible for firmware structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD07 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD7_N_MEM
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
F:
Specification at SPB connector faulty.
R:
@CSD07 reverts to the dead state.
A:
Specification at TWU connector can only be in range 0,
1 or 2 .
EQ:
ZF_ERR_NUM_CSD7_SPB_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
F:
Specification at PAR connector faulty.
R:
@CSD07 reverts to the dead state.
A:
Specification at BDR connector can only be in range 0, 1
or 2 .
EQ:
ZF_ERR_NUM_CSD7_PAR_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
F:
Specification at BDR connector faulty.
R:
@CSD07 reverts to the dead state.
A:
Specification at BDR connector can only correspond to
one of the
following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200
EQ:
ZF_ERR_NUM_CSD7_BDR_ERR
EM:
_CSD07.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _CSD7_init.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function
_CSD7_firmware_init.
R:
@CSD07 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD7_FIR_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSD07.CSF
AA:
7-Seg. ’C’
not utilized
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.9.9 Link DUST2
6A10 Hex
F:
6A11 Hex
F:
6A12 Hex
F:
6A13 Hex
F:
6A14 Hex
F:
6A15 Hex
F:
Several communication central blocks were configured with the
same
CS7 board names or interface names.
R:
@CSD02 reverts to the dead state.
A:
Remove one of the configured @CSD02 blocks;
Correct the interface specification of one @CSD02 block
EQ:
ZF_ERR_NUM_CSD2_MEHR_PROJ
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_CIP_FREI_FRW_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD02 block is not accessible.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD02 block does not exist.
R:
@CSD02 reverts to the dead state.
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CSD2_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_CIP_SUCH_FRW_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_REOR_FRW_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-89
Communication Error Codes
6A16 Hex
F:
6A17 Hex
F:
6A18 Hex
F:
6A19 Hex
F:
6A1A Hex
F:
6A1B Hex
F:
3-90
Unknown operating status of the @CSD02 block.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_BZS_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD02 reverts to the dead state.
A:
Reduce the SAVE requirement in the application
EQ:
ZF_ERR_NUM_CSD2_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error supplementary
code bsspvw_info.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
@CSD02 block configured in impermissible sampling time (not
between 32ms and 255ms)
R:
@CSD02 reverts to the dead state.
A:
Configure the sampling time between 32ms and 255ms
EQ:
ZF_ERR_NUM_CSD2_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for exception structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD02 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD2_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD02 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD2_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6A1C Hex
F:
6A1D Hex
F:
6A1E Hex
F:
6A1F Hex
F:
6A20 Hex
F:
6A21 Hex
F:
6A22 Hex
F:
Unknown function return value of the function zp_fb_init.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_FB_INIT_FRW_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Link type is not set to "DUST1" or "CS7".
R:
@CSD02 reverts to the dead state.
A:
Check the configured name at CTS connector;
Check that block type corresponds to @CSD02
EQ:
ZF_ERR_NUM_CSD2_KOP_TYP_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_ANM_FRW_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
DUST1 firmware has detected an unrepairable error.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_DUST_INIT_ERR
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
DUST1 firmware has reverted to an error status or SS4 adapter
module missing.
R:
@CSD02 reverts to the dead state.
A:
Install SS4 module in CS7 board;
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_DUST_TOT
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
Unknown status of the DUST1 firmware.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_ZUS_ERR
EM:
ZP.CSF,_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-91
Communication Error Codes
6A23 Hex
6A24 Hex
6A25 Hex
6A26 Hex
6A27 Hex
6A28 Hex
6A29 Hex to 6A2F
Hex
3-92
F:
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_FIRMWARE_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
F:
Memory assigning not possible for firmware structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD02 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD2_N_MEM
EM:
ZP.CSF,
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
F:
Specification at PAR connector faulty.
R:
@CSD02 reverts to the dead state.
A:
Specification at TWU connector can only be in range 0
to 1 .
EQ:
ZF_ERR_NUM_CSD2_TWU_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
F:
Specification at BDR connector faulty.
R:
@CSD02 reverts to the dead state.
A:
Specification at BDR connector can only correspond to
one of the
following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200
EQ:
ZF_ERR_NUM_CSD2_BDR_ERR
EM:
_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _csd2_init.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
Z_ERR_NUM_CSD2_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the
function_csd2_firmware_init.
R:
@CSD02 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD2_FIR_INIT_FRW_ERR
EM:
ZP.CSF,_CSD02.CSF
AM:
_CSD02.CSF
AA:
7-Seg. ’C’
not utilized
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.9.10 Link DUST3
6A30 Hex
F:
6A31 Hex
F:
6A32 Hex
F:
6A33 Hex
F:
6A34 Hex
F:
6A35 Hex
F:
Several communication central blocks were configured with the
same
CS7 board names or interface names.
R:
@CSD03 reverts to the dead state.
A:
Remove one of the configured @CSD03 blocks;
Correct the interface specification of one @CSD03 block
EQ:
ZF_ERR_NUM_CSD3_MEHR_PROJ
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_CIP_FREI_FRW_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD03 block is not accessible.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSD03 block does not exist.
R:
@CSD03 reverts to the dead state.
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CSD3_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_CIP_SUCH_FRW_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_REOR_FRW_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-93
Communication Error Codes
6A36 Hex
F:
6A37 Hex
F:
6A38 Hex
F:
6A39 Hex
F:
6A3A Hex
F:
6A3B Hex
F:
3-94
Unknown operating status of the @CSD03 block.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_BZS_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD03 reverts to the dead state.
A:
Reduce the SAVE requirement in the application
EQ:
ZF_ERR_NUM_CSD3_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
SAVE area not found.
Exact cause of error see section Error supplementary
code bsspvw_info.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
@CSD03 block configured in impermissible sampling time (not
between 32ms and 255ms)
R:
@CSD03 reverts to the dead state.
A:
Configure the sampling time between 32ms and 255ms
EQ:
ZF_ERR_NUM_CSD3_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for exception structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD03 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD3_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD03 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD3_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6A3C Hex
F:
6A3D Hex
F:
6A3E Hex
F:
6A3F Hex
F:
6A40 Hex
F:
6A41 Hex
F:
6A42 Hex
F:
Unknown function return value of the function zp_fb_init.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_FB_INIT_FRW_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Link type is not set to "DUST1" or "CS7".
R:
@CSD03 reverts to the dead state.
A:
Check the configured name at CTS connector;
Check that block type corresponds to @CSD03
EQ:
ZF_ERR_NUM_CSD3_KOP_TYP_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_ANM_FRW_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
DUST1 firmware has detected an unrepairable error.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_DUST_INIT_ERR
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
DUST1 firmware has reverted to an error status or SS4 adapter
module missing.
R:
@CSD03 reverts to the dead state.
A:
Install SS4 module in CS7 board;
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_DUST_TOT
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
UInknown status of the DUST1 firmware.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_ZUS_ERR
EM:
ZP.CSF,_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-95
Communication Error Codes
6A43 Hex
6A44 Hex
6A45 Hex
6A46 Hex
6A47 Hex
6A48 Hex
6A49 Hex to 6A4F
Hex
3-96
F:
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_FIRMWARE_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
F:
Memory assigning not possible for firmware structure
Exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSD03 reverts to the dead state.
A:
Reduce the RAM requirement in the application
EQ:
ZF_ERR_NUM_CSD3_N_MEM
EM:
ZP.CSF,
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
F:
Specification at BCC connector faulty.
R:
@CSD03 reverts to the dead state.
A:
Specification at BCC connector can only be in range 0 to
1.
EQ:
ZF_ERR_NUM_CSD3_TWU_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
F:
Specification at BDR connector faulty.
R:
@CSD03 reverts to the dead state.
A:
Specification at BDR connector can only correspond to
one of the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200
EQ:
ZF_ERR_NUM_CSD3_BDR_ERR
EM:
_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function _csd3_init.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
F:
Unknown function return value of the function
_csd3_firmware_init.
R:
@CSD03 reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSD3_FIR_INIT_FRW_ERR
EM:
ZP.CSF,_CSD03.CSF
AM:
_CSD03.CSF
AA:
7-Seg. ’C’
not utilized.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
3.2.9.11 USS Link
6A50 Hex
F:
6A51 Hex
F:
6A52 Hex
F:
6A53 Hex
F:
6A54 Hex
F:
6A55 Hex
F:
Several communication central blocks were configured with the
same
CS7 board names or interface names.
R:
@CSU reverts to the dead state
A:
Remove one of the configured @CSU blocks;
correct the interface specification of one @CSU block.
EQ:
ZF_ERR_NUM_CSU_MEHR_PROJ
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zp_cip_freigabe.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_CIP_FREI_FRW_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSU block is not accessible.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
The CIP entry for the @CSU block does not exist.
R:
@CSU reverts to the dead state.
A:
Check the configured name at the CTS connector.
EQ:
ZF_ERR_NUM_CSU_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function zbak_cip_suche.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_CIP_SUCH_FRW_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_dexdo_reorganization.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_DEX_REOR_FRW_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-97
Communication Error Codes
6A56 Hex
F:
6A57 Hex
F:
6A58 Hex
F:
6A59 Hex
F:
6A5A Hex
F:
6A5B Hex
F:
3-98
Unknown operating status of the @CSU block.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_BZS_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
SAVE memory assigning not possible for warm start flag
exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSU reverts to the dead state.
A:
Reduce the SAVE requirement in the application.
EQ:
ZF_ERR_NUM_CSU_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
SAVE area not found.
exact cause of error see section Error supplementary
code bsspvw_info.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
@CSU block was configured in impermissible sampling time
(not between 32ms and 255ms).
R:
@CSU reverts to the dead state.
A:
Configure the sampling time between 32 ms and 255 ms.
EQ:
ZF_ERR_NUM_CSU_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for exception structure
exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSU reverts to the dead state.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSU_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for reorganization structure
exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSU reverts to the dead state.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSU_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6A5C Hex
F:
6A5D Hex
F:
6A5E Hex
F:
6A5F Hex
F:
6A60 Hex
F:
6A61 Hex
F:
6A62 Hex
F:
unknown function return value of the function zp_fb_init.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_FB_INIT_FRW_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
lLnk type is not set to "USS" or "CS7".
R:
@CSU reverts to the dead state.
A:
Check the configured name at CTS connector;
Check that block type corresponds to @CSU.
EQ:
ZF_ERR_NUM_CSU_KOP_TYP_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function
zp_anmelde_ueberwachung.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_ANM_FRW_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown register status detected in DEXDO3 management
section.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
USS firmware has detected an unrepairable error.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_DUST_INIT_ERR
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
USS firmware has reverted to an error status or SS4 adapter
module
missing.
R:
@CSU reverts to the dead state.
A:
Install SS4 module in CS7 board;
A:
Contact Siemens AG
EQ:
ZF_ERR_NUM_CSU_TOT
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown status of the USS firmware.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_ZUS_ERR
EM:
ZP.CSF,_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-99
Communication Error Codes
6A63 Hex
F:
6A64 Hex
F:
6A65 Hex
F:
6A66 Hex
F:
6A67 Hex
F:
6A68 Hex
F:
3-100
Unknown function return value of the function
zp_firmware_zyklisch.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_FIRM_ZYK_FRW_ERR
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Memory assigning not possible for firmware structure
exact cause of error see section Error supplementary
code bsspvw_geme.
R:
@CSU reverts to the dead state.
A:
Reduce the RAM requirement in the application.
EQ:
ZF_ERR_NUM_CSU_N_MEM
EM:
ZP.CSF,
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Specification at PPT connector faulty.
R:
@CSU reverts to the dead state
A:
Specification at PPT connector can only be in range 0 to
32767.
EQ:
ZF_ERR_NUM_CSU_PPT_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Specification at HCT connector faulty.
R:
@CSU reverts to the dead state.
A:
Specification at HCT connector can only be in range 0 to
32767.
EQ:
ZF_ERR_NUM_CSU_HCT_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Specification at BDR connector faulty.
R:
@CSU reverts to the dead state.
A:
Specification at BDR connector can only correspond
to one of the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200,38400
EQ:
ZF_ERR_NUM_CSU_BDR_ERR
EM:
_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
Unknown function return value of the function _csu_init.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_INIT_FRW_ERR
EM:
ZP.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6A69 Hex
6A6A Hex to 6A6F
Hex
F:
Unknown function return value of the function
_csu_firmware_init.
R:
@CSU reverts to the dead state.
A:
Contact Siemens AG.
EQ:
ZF_ERR_NUM_CSU_FIR_INIT_FRW_ERR
EM:
ZP.CSF,_CSU.CSF
AM:
_CSU.CSF
AA:
7-Seg. ’C’
not utilized.
3.2.9.12 Rack Link Fiber Optic Cable
6A90 Hex
F:
6A91 Hex
F:
6A92 Hex
F:
6A93 Hex
F:
Several @CS1 blocks were configured with
the same CS11/12/13/14 board names.
R:
@CS1 is disabled
A:
Reconfigure;
only one @CS1 central block permitted
EQ:
ZF_ERR_NUM_CS1_MEHR_PROJ
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A90, pointer to configured name, 0)
Unknown function return value from the function
zp_cip_freigabe.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_CIP_FREI_FRW_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A91, pointer to configured name,
function return value of the function zp_cip_freigabe)
The CIP entry for the @CS1 block cannot be accessed.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A92, pointer to configured name, 0)
The CIP entry for the @CS1 block does not exist.
R:
@CS1 is disabled
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CS1_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A93, pointer to configured name, 0)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-101
Communication Error Codes
6A94 Hex
F:
6A95 Hex
F:
6A96 Hex
F:
6A97 Hex
F:
6A98 Hex
F:
3-102
Unknown function return value from the function
zbak_cip_suche.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_CIP_SUCH_FRW_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A94, pointer to configured name,
function return value of the function zbak_cip_suche)
Unknown function return value from the function
zp_dexdo_reorganisation.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_DEX_REOR_FRW_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A95, pointer to configured name,
function return value of the function
zp_dexdo_reorganisation)
Unknown operating status of the @CS1 block.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_BZS_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A96, pointer to configured name, not defined)
SAVE-memory create for warm start flag not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS1 is disabled
A:
Reduce the SAVE requirements in the application
EQ:
ZF_ERR_NUM_CS1_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A97, pointer to configured name, not defined)
SAVE area not found.
Precise cause of error, review section Error suppl. code
bsspvw_info
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A98, pointer to configured name, not defined)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6A99 Hex
F:
6A9A Hex
F:
6A9B Hex
F:
6A9C Hex
F:
6A9D Hex
F:
@CS1 block was configured in an invalid sampling time
(not between 32ms and 255ms).
R:
@CS1 is disabled
A:
Configure the sampling time between 32ms and 255ms
EQ:
ZF_ERR_NUM_CS1_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’’
KFF
(6A99, pointer to configured name, not defined)
Memory create for exception structure not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS1 is disabled
A:
Reduce the RAM requirements in the application
EQ:
ZF_ERR_NUM_CS1_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9A, pointer to configured name, not defined)
Memory create for reorganization structure not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS1 is disabled
A:
Reduce the RAM requirements in the application
EQ:
ZF_ERR_NUM_CS1_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9B, pointer to configured name, not defined)
Unknown function return value from the function zp_fb_init.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_FB_INIT_FRW_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9C, pointer to configured name,
function return value of the function
zp_dexdo_reorganisation)
Link type not set to "CS11/12/13/14 Rack Link".
R:
@CS1 is disabled
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CS1_KOP_TYP_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9D, pointer to configured name, 0)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-103
Communication Error Codes
6A9E Hex
F:
6A9F Hex
F:
6AA0 Hex
F:
6AA1 Hex
F:
6AA2 Hex
F:
6AA3 Hex
F:
3-104
Unknown function return value from the function
zp_anmelde_ueberwachung.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_ANM_FRW_ERR
EM:
_CS1.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9E, pointer to configured name,
function return value of the function
zp_anmelde_ueberwachung)
Unknown connect status in DEXDO3 management area.
R:
@CS1 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS1_ANM_STATUS_ERR
EM:
ZP.CSF
AM:
_CS1.CSF
AA:
7-Seg. ’C’
KFF
(6A9F, pointer to configured name, 0)
The configured name of the @CS2 block matches another in the
link.
R:
@CS2 is disabled
A:
Reconfigure;
only one @CS2 central block permitted.
EQ:
ZF_ERR_NUM_CS2_MEHR_PROJ
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA0, pointer to configured name, 0)
The CIP entry for the @CS2 block cannot be accessed.
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_CIP_NAM_KEN_N_AD
EM:
ZBAK.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA1, pointer to configured name, 0)
The CIP entry for the @CS2 block does not exist.
R:
@CS2 is disabled
A:
Check the configured name at the CTS connector
EQ:
ZF_ERR_NUM_CS2_CIP_NAM_N_KENN
EM:
ZBAK.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA2, pointer to configured name, 0)
Unknown function return value from the function
zbak_cip_suche.
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_CIP_SUCH_FRW_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA3, pointer to configured name,
function return value of the function zbak_cip_suche)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6AA4 Hex
6AA5 Hex
6AA6 Hex
6AA7 Hex
6AA8 Hex
6AA9 Hex
not utilized
F:
Eight @CS2 blocks already connected in the link.
R:
@CS2 is disabled
A:
Power down rack and after 10 sec. power up again
Check whether more than eight CS2 boards exist in the
link or whether the @CS2 block is multiply configured on the
same CS21/22 board
EQ:
ZF_ERR_NUM_CS2_SCHON_ACHT_CS22
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA5, pointer to configured name, 0)
F:
The configured CS11/12/13/14 board does not exist.
R:
@CS2 is disabled
A:
Check the configured CS11/12/13/14 name at the MTS
connector
EQ:
ZF_ERR_NUM_CS2_CS1_N_KENN
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’’
KFF
(6AA6, pointer to configured name, 0)
F:
Unknown function return value from the function
_cs2_anmeldung.
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_ANM_FRW_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA7, pointer to configured name,
function return value of the function _cs2_anmeldung)
F:
Unknown operating status of the @CS2 block.
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_BZS_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA8, pointer to configured name, faulty
operating status)
F:
SAVE-memory create for warm start flag not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS2 is disabled
A:
Reduce the SAVE requirements in the application
EQ:
ZF_ERR_NUM_CS2_SAVE_ZU_KURZ
EM:
ZP.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AA9, pointer to configured name, not defined)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-105
Communication Error Codes
6AAA Hex
6AAB Hex
6AAC Hex
6AAD Hex
6AAE Hex
6AAF Hex to 6AB0
Hex
3-106
F:
SAVE area not found.
Precise cause of error, review section Error suppl. code
bsspvw_info
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_SAVE_N_KENN
EM:
ZP.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AAA, pointer to configured name, not defined)
F:
@CS2 block was configured in an invalid sampling time
(not between 32ms and 255ms) or the sampling time of
the @CS1
does not fit.
R:
@CS2 is disabled
A:
Configure the sampling time between 32ms and 255ms
or
check the sampling time of the @CS1
EQ:
ZF_ERR_NUM_CS2_ABTASTZEIT_ERR
EM:
ZP.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AAB, pointer to configured name, 0)
F:
Memory create for exception structure not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS2 is disabled
A:
Reduce the RAM requirements in the application
EQ:
ZF_ERR_NUM_CS2_EXC_ZU_KURZ
EM:
ZP.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AAC, pointer to configured name, not defined)
F:
Memory create for reorganization structure not possible
Precise cause of error, review section Error suppl. code
bsspvw_geme
R:
@CS2 is disabled
A:
Reduce the RAM requirements in the application
EQ:
ZF_ERR_NUM_CS2_REORG_ZU_KURZ
EM:
ZP.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AAD, pointer to configured name, not defined)
F:
Unknown function return value from the function zp_fb_init.
R:
@CS2 is disabled
A:
Inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_FB_INIT_FRW_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’’
KFF
(6AAE, pointer to configured name,
function return value of the function zp_fb_init)
not utilized
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
6AB1 Hex
F:
6AB2 Hex
F:
6AB3 Hex
F:
6AB4 Hex
F:
Link type not set to "CS22 Rack Link in the expanded
address area" or "CS22 Rack Link in the special
peripherals area".
R:
@CS2 is disabled
A:
Check the configured name at the CTS connector
otherwise
inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_KOP_TYP_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AB1, pointer to configured name, 0)
Three @CS2 blocks already connected in the link.
R:
@CS2 is disabled
A:
Power down rack and after 10 sec. power up again
Check whether more than three CS21 boards exist in the
link or
whether the @CS2 block is multiply configured on the
same CS21
board
EQ:
ZF_ERR_NUM_CS2_SCHON_DREI_CS21
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AB2, pointer to configured name, 0)
The software version on the processor board is not compatible
with the
version in the CS11/12/13/14 rack.
R:
@CS2 is disabled
A:
Check the versions in all the connected racks, otherwise
inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_VERSION_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AB3, pointer to configured name, 0)
Memory size of the CS22 and the CS12/13/14 do not match
R:
@CS2 is disabled
A:
Check the EMA connectors on the CS12/13/14-IB or
CS22-IB,
otherwise inform Siemens AG.
EQ:
ZF_ERR_NUM_CS2_MEM_SIZE_ERR
EM:
_CS2.CSF
AM:
_CS2.CSF
AA:
7-Seg. ’C’
KFF
(6AB4, pointer to configured name, 0)
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-107
Communication Error Codes
3.2.10 Gerätekopplung und Parameterbearbeitung auf T400
7C00 Hex
F:
R:
A:
EQ:
EM:
AM:
Parameternummer ist nicht vorhanden
Auftrag wird nicht ausgeführt
Parameternummer überprüfen
ZF4_GER_ERR_PRP_NO_PARA_NR
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 0
7C01 Hex
F:
R:
A:
EQ:
EM:
AM:
PEN-Eingang erlaubt keine Änderung der Parameter
Parameter wird nicht geändert
FB-@DRIVE, Eingang PEN auf 1 setzen
ZF4_GER_ERR_PRP_NO_PEN
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 1
7C02 Hex
F:
R:
A:
MIN- / MAX-Grenze ueberschritten
Parameter wird nicht geändert
Wert für Parameterauftrag so ändern, daß er innerhalb der
Grenzwerte liegt. Oder Grenzwerte ändern, falls Grenzwerte
über PLIM-Bausteine festgelegt wurden, und RESET der T400.
ZF4_GER_ERR_PRP_OFF_LIMIT
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 2
EQ:
EM:
AM:
R:
A:
EQ:
EM:
AM:
Keine gueltiger Parameterauftrag, Auftragsnummer und
Parameternummer konnten nicht aus der Parameter ID bestimmt
werden.
Auftrag wird nicht bearbeitet
Parameter ID überprüfen und gültige Parameter ID angeben
ZF4_GER_ERR_PRP_NO_PARA_ID
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 3
7C05 Hex
F:
R:
A:
EQ:
EM:
AM:
Ungueltiger Datentyp
Auftrag wird nicht ausgeführt
Gültigen Datentyp für Parameterauftrag verwenden
ZF4_GER_ERR_PRP_ILLEGAL_DATA_TYPE
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 5
7C12 Hex
F:
R:
A:
EQ:
EM:
AM:
Parameter auf einem Ausgang ist nicht änderbar
Auftrag wird nicht ausgeführt
Parameter auf einen Eingang projektieren
ZF4_GER_ERR_PRP_NO_INPUT
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert 18
7C03 Hex
3-108
F:
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
7C66 Hex
F:
R:
A:
EQ:
EM:
AM
Schreibschutz der Speicherkarte ist eingelegt
Abspeichern in das EEPROM ist nicht möglich.
Siemens AG benachrichtigen
ZF4_GER_ERR_PRP_SAVE_PROTECT
zf4ger.csf
_drive.csf, YTx,
Fehlernummer wird als zusätzlicher Parameterrückgabewert bei
der Auftragsantwort mit zurückgesendet.
7C70 Hex
F:
R:
A:
EQ:
EM:
AM:
Kanalzustand ist AUS aufgrund Baugruppen-Konfiguration
Keine weitere Bearbeitung
Überprüfen, ob die Baugruppen richtig gesteckt sind
ZF4_GER_ERR_PRP_KAN_ZUS_OFF
zf4ger.csf
_drive.csf, YTx
7C72 Hex
F:
R:
Funktionsbaustein ist mehrfach projektiert
Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltet
Funktionsbaustein nur einmal projektieren
ZF4_GER_ERR_MEHRFACH
_drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
_drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
A:
EQ:
EM:
AM:
7C7A Hex
F:
R:
A:
EQ:
EM:
AM:
7C7B Hex
F:
R:
A:
EQ:
EM:
AM:
7C7E Hex
F:
R:
A:
EQ:
EM:
AM:
Abtastzeit nicht 10 .. 200ms
Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltet
Abtastzeit ändern, so daß sie zwischen 10 ms und 200 ms liegt.
ZF4_GER_ERR_ABTASTZEIT
_drive.csf
_drive.csf, YT1
Fehler bei der Speicherbeschaffung
Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltet
Siemens AG benachrichtigen
ZF4_GER_ERR_GEME
_drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
_drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
Zusatzinformation im Kommunikationsfehlerfeld: Rückgabewert
der Funktion bsspvw_geme
ungueltiges Request-Buffer-Status-Byte
Paramterkanal wird nicht bearbeitet.
Hardware überprüfen, Siemens AG benachrichtigen
ZF4_GER_ERR_PRP_RQU_BUFFER
zf4ger.csf
_drive.csf, YT1
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-109
Communication Error Codes
7C7F Hex
F:
R:
A:
EQ:
EM:
AM:
kein Zugriff auf Reply-Buffer möglich
Paramterkanal wird nicht bearbeitet.
Hardware überprüfen, Siemens AG benachrichtigen.
ZF4_GER_ERR_PRP_RPL_NO_ACC
zf4ger.csf
_drive.csf, YTx
7C80 Hex
F:
R:
A:
EQ:
EM:
AM:
ungueltiges Reply-Buffer-Status-Byte
Paramterkanal wird nicht bearbeitet.
Hardware überprüfen, Siemens AG benachrichtigen.
ZF4_GER_ERR_PRP_RPL_BUFFER
zf4ger.csf
_drive.csf, YTx
7C81 Hex
F:
R:
A:
EQ:
EM:
AM:
Vorheriger Speicherauftrag noch in Arbeit.
Auftrag wird nicht ausgeführt.
Auftrag wiederholen.
ZF4_GER_ERR_PRP_SAVE_BUSY
zf4ger.csf
_drive.csf, Ytx
Fehlernummer wird als zusätzlicher Parameterrückgabewert bei
der Auftragsantwort mit zurückgesendet.
7C83 Hex
F:
R:
A:
EQ:
EM:
AM:
Kanalkennung fehlerhaft
Paramterkanal wird nicht bearbeitet.
Hardware überprüfen, Siemens AG benachrichtigen.
ZF4_GER_ERR_PRP_NO_KAN_KNG
zf4ger.csf
_drive.csf, YTx
7C84 Hex
F:
Parameterfunktion nicht implementiert, Parameter
Auftragsnumer ist ungültig oder Parameterauftrag kann auf der
T400 nicht bearbeitet werden.
Paramterauftrag wird nicht ausgeführt.
Gültigen Parameterauftrag projektieren.
ZF4_GER_ERR_PRP_NO_PKW
zf4ger.csf
_drive.csf, YTx, Parameterrückgabewert
R:
A:
EQ:
EM:
AM:
7C8D Hex
F:
R:
A:
EQ:
EM:
AM:
3-110
Fehler bei der Übertragung neuer Konfigurationsdaten zum
Comboard
kein Datenaustausch zum Comboard.
An Baseboard oder FB CBCONF andere Konfigurationsdaten für
Comboard einstellen und diese zum Comboard übertragen.
ZF4_GER_ERR_CBCONF
_drive.csf
_drive.csf, cbconf.csf, YTS
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
7C8F Hex
F:
R:
A:
EQ:
EM:
AM:
A:
EQ:
EM:
AM:
Parametertabelle ist nicht vorhanden
Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltet
Siemens AG benachrichtigen
ZF4_GER_ERR_PRP_PTAB
_drive.csf
_drive.csf, YT1
7C93 Hex
F:
R:
A:
EQ:
EM:
AM:
Request-Buffer-Channel-Control is OFF
Parameterkanal wird nicht bearbeitet
Kommunikationpartner überprüfen.
ZF4_GER_ERR_PRP_RQU_CC_OFF
zf4ger.csf
_drive.csf, YTx
7C94 Hex
F:
R:
A:
EQ:
EM:
AM:
kein Zugriff auf Request-Buffer möglich
Parameterkanal wird nicht bearbeitet
Kommunikationpartner überprüfen.
ZF4_GER_ERR_PRP_RQU_NO_ACC
zf4ger.csf
_drive.csf, YTx
7C95 Hex
F:
R:
A:
EQ:
EM:
AM:
Reply-Buffer-Channel-Control is OFF
Parameterkanal wird nicht bearbeitet
Kommunikationpartner überprüfen.
ZF4_GER_ERR_PRP_RPL_CC_OFF
zf4ger.csf
_drive.csf, YTx
7C97 Hex
F:
R:
A:
EQ:
EM:
AM:
Auf Parameterantwort vom anderen Board warten.
Auf Parameterantwort vom anderen Board warten.
Überprüfen, ob anderes Board korrekt arbeitet.
ZF4_GER_ERR_PRP_RPL_WAIT
zf4ger.csf
_drive.csf, YT5
7C98 Hex
F:
R:
Timeout beim Warten auf Parameterantwort vom anderen Board
Parameterantwort „Auftrag konnte nicht ausgeführt werden“ mit
Zusatzinformation „Timeout
beim Warten auf Quittung vom
anderen Board“ wird gesendet
Überprüfen, ob anderes Board korrekt arbeitet.
ZF4_GER_ERR_PRP_RPL_WAITOUT
zf4ger.csf
_drive.csf, YT5
7C92 Hex
F:
R:
Falsche Baugruppe rechts
Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltet
Anderen Baugruppe rechts verwenden
ZF4_GER_ERR_KOPP_R
_drive.csf
_drive.csf, YT1
A:
EQ:
EM:
AM:
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-111
Communication Error Codes
7C9C Hex
F:
R:
A:
EQ:
EM:
AM:
Speicherkarte ist nicht „SIMADYN D konform“
Parameterauftrag wurde nicht ausgeführt
Siemens AG benachrichtigen
ZF4_GER_ERR_PRP_SAVE_NONCOMP
zf4ger.csf
_drive.csf, YTx, als Parameterrückgabewert
7C9D Hex
F:
R:
A:
EQ:
EM:
AM:
Speicherkarte wurde beim letzten Schreibvorgang defekt. Alle
weiteren Versuch zu schreiben sind zwecklos
Parameterauftrag wurde nicht ausgeführt
Siemens AG benachrichtigen
ZF4_GER_ERR_PRP_SAVE_DEFECT
zf4ger.csf
_drive.csf, YTx, als Parameterrückgabewert
7C9E Hex
F:
R:
A:
EQ:
EM:
AM:
Speicherplatz im EEPROM ist nicht ausreichend
Parameterauftrag wurde nicht ausgeführt
keine
ZF4_GER_ERR_PRP_SAVE_NO_SPACE
zf4ger.csf
_drive.csf, YTx, als Parameterrückgabewert
7CA1 Hex
F:
Konvertierung von Float auf I4 hat fehlgeschlagen, Float -Zahl
war zu groß
Parameterauftrag wird nicht ausgeführt.
kleinere Float-Zahlen im Parameterauftrag versenden,
Parameterkanal verwenden, über den Float-Zahlen versendet
werden können (siehe PCF-/PTF-Eingang am FB @Drive)
ZF4_GER_ERR_PRP_NO_KONV_NFI4
zf4ger.csf
_drive.csf, Ytx
Fehlernummer wird als zusätzlicher Parameterrückgabewert bei
der Auftragsantwort mit zurückgesendet.
R:
A:
EQ:
EM:
AM:
7CA6 Hex
F:
R:
A:
EQ:
EM:
AM:
7CA7 Hex
3-112
F:
R:
A:
EQ:
EM:
AM:
Zentralbaustein FB-@Drive fehlt
Eintrag ins Kommunikationsfehlerfeld, Abschaltung des
suchenden Bausteins
FB @Drive projektieren
ZF4_GER_ERR_N_DRIVE
zf4ger.csf, pname.csf, ptrans.csf, cbconf.csf, tfaw.csf, rfaw.csf
pname.csf, plim.csf, plim_i.csf, plim_d.csf, ptrans.csf,
cbconf.csf, tfaw.csf, rfaw.csf
YTS-Ausgänge
Kanal fehlerhaft
Kommunikation wird abgebrochen
Board überprüfen, Siemens AG benachrichtigen
ZF4_GER_ERR_PKZ_BREAK
zf4ger.csf, ptrans.csf
tfaw.csf, ptrans.csf -- YTS-Ausgänge
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Communication Error Codes
7CAB Hex
F:
R:
A:
EQ:
EM:
AM:
7CAC Hex
F:
R:
A:
EQ:
EM:
AM:
7CAD Hex
F:
R:
A:
EQ:
EM:
AM:
7CAE Hex
F:
R:
A:
EQ:
EM:
AM:
7CAF Hex
F:
R:
A:
EQ:
EM:
AM:
Parameter zur projektierten Nummer ist ein
Beobachtungsparamter (Ausgang)
Grenzwerte werden nicht in die Parametertabelle eingetragen,
Eintrag in das Fehlerfeld
Parameter an einem Eingang projektieren
ZF4_PLIM_ERR_NO_WRITE
zf4ger.csf
plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang
Parameter zur projektierten Nummer ist nicht vorhanden
Grenzweret können nicht in die Parametertabelle eingetragen
werden, Eintrag in das Fehlerfeld
Vorhandene Parameternummer projektieren
ZF4_PLIM_ERR_NO_PARAM_NR
zf4ger.csf
plim.csf, plim_i.csf , plim_d.csf -- YTS- Ausgang
Datentypen sind nicht identisch
Grenzwerte für Parameternummer werden nicht aktiv, Eintrag in
das Fehlerfeld
Richtigen PLIM-Baustein verwenden
ZF4_PLIM_ERR_NO_DATA_TYPE
plim.csf, plim_i.csf, plim_d.csf
plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das
Fehlerfeld
Fehler bei der Bestimmung der Skalierungsfaktoren der MIN- /
MAX-Eingänge
Grenzwerte werden nicht aktiv
Siemens AG benachrichtigen
ZF4_PLIM_ERR_MINMAX
plim.csf
plim.csf -- YTS- Ausgang
Eintrag in das Fehlerfeld, Zusatz: Funktionsrückgabewert der
Funktion sda_func_afpi_suche_fbk_nr oder
sda_func_afpi_fbk_kbs
Minimum ist größer als Maximum
Grenzwerte werden nicht aktiv
Eingänge MIN, MAX korrigieren
ZF4_PLIM_ERR_MINMAX
plim.csf, plim_i.csf, plim_d.csf
plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das
Fehlerfeld
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
3-113
Communication Error Codes
7CB0 Hex
F:
R:
A:
EQ:
EM:
AM:
R:
A:
EQ:
EM:
AM:
Funktionsbaustein kann wg. Hardwarekonfiguration nicht
verwendet werden
Funktionsbaustein schaltet sich ab.
Baustein nur projektieren, wenn Konfiguration dies zulässt
ZF4_GER_ERR_FB_FE_KOPPZUS
cbconf.csf, tfaw.csf, rfaw.csf
cbconf.csf, tfaw.csf, rfaw.csf -- YTx-Ausgänge
7CB4 Hex
F:
R:
A:
EQ:
EM:
AM:
Initialisierung des Funktionsbausteins läuft
(temporärer Zustand)
warten
ZF4_GER_ERR_FB_INI
cbconf.csf, tfaw.csf, rfaw.csf
cbconf.csf, tfaw.csf, rfaw.csf - YTx-Ausgänge
7CB5 Hex
F:
R:
A:
keine Kommunikation mit Kommunikationspartner
Es findet keine Übertragung der Fehler und Warnungen statt.
Kommunikationspartner überprüfen, Siemens AG
benachrichtigen
ZF4_GER_ERR_FAW_N_COM
tfaw.csf, rfaw.csf
tfaw.csf, rfaw - YTx-Konnektoren
7CB3 Hex
F:
T400 ist nicht als Techboard projektiert
Abschaltung des Bausteins und Eintrag in das
Kommunikationsfehlerfeld
T400 am FB @DRIVE als Techboard projektieren (Eingang
BBF=0)
ZF4_PTRANS_ERR_NO_T400
ptrans.csf
ptrans.csf- YTx-Konnektoren
EQ:
EM:
AM:
7CB6 Hex
F:
R:
A:
EQ:
EM:
AM:
3-114
kein Zugriff auf Kanal möglich
Es findet keine Übertragung der Fehler und Warnungen statt.
Kommunikationspartner überprüfen, Siemens AG
benachrichtigen
ZF4_GER_ERR_FAW_N_CHANNEL_ACCESS
tfaw.csf, rfaw
tfaw.csf, rfaw.csf - YTx-Konnektoren
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
4
Error Supplementary Codes
This chapter describes the error supplementary codes to the individual
error codes. Which supplementary codes exist for which error codes is
indicated in the description of the corresponding error codes. An error
supplementary code does not automatically exist for each error code.
4.1
01 Hex
Supplementary code "bsspvw_geme"
F:
R:
A:
EQ:
EM:
AM:
AA:
R:
A:
EQ:
EM:
AM:
AA:
Memory object ID points to a memory object that does not exist
in the rack.
Required memory was not set.
Contact Siemens AG .
SDB_FRW_BSSPVW_GEME_SOK_NEXIST
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
03 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
The free memory space on the memory object is not sufficient.
Required memory was not set.
Free up memory space on the memory object by reconfiguring.
SDB_FRW_BSSPVW_GEME_SP_ZUKLEIN
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
04 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
The memory object is currently blocked by another user.
Required memory was not set.
Wait state.
SDB_FRW_BSSPVW_GEME_SO_KZUGR
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
02 Hex
F:
Memory object ID impermissible.
(permissible memory object ID’s are PN local RAM, slots 1...24,
PN local SAVE area, L bus coupling memory and C bus coupling
memory).
Required memory was not set.
Contact Siemens AG .
SDB_FRW_BSSPVW_GEME_SOK_UNZ
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
Fehler! Datei kann nicht geöffnet werden.- Fehler! Datei kann nicht geöffnet werden.- Fehler! Datei kann nicht geöffnet
werden.
Fehler! Datei kann nicht geöffnet werden. Fehler! Datei kann nicht geöffnet werden.
4-1
Error Supplementary Codes
R:
A:
EQ:
EM:
AM:
AA:
Required memory distribution is impermissible.
(permissible memory distribution is either word wise or paragraph
wise).
Required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_GEME_SOM_UNZ
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
06 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
System bus access error
Required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_GEME_BUS
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
07 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
RAM drive access error.
Required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_GEME_RAM
BSSPVW.CSF
Block that invokes the function bsspvw_geme.
Block dependent.
05 Hex
4.2
01 Hex
F:
Supplementary code "bsspvw_info"
F:
R:
A:
EQ:
EM:
AM:
AA:
02 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
4-2
Memory object ID impermissible.
(permissible memory object ID’s are PN local RAM, slots 1...24,
PN local SAVE area, L bus coupling memory and C bus coupling
memory.)
The address of the required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_INFO_SOK_UNZ
BSSPVW.CSF
Block that invokes the function bsspvw_info.
Block dependent.
Memory object ID points to a memory object that does not exist
in the rack.
Required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_INFO_SOK_NEXIST
BSSPVW.CSF
Block that invokes the function bsspvw_info.
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Error Supplementary Codes
03 Hex
04 Hex
4.3
31 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
The required list does not exist.
The address of the required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_INFO_SON_NEXIST
BSSPVW.CSF
Block that invokes the function bsspvw_info.
Block dependent.
F:
R:
A:
EQ:
EM:
AM:
AA:
System bus access error
The address of the required memory was not set.
Contact Siemens AG.
SDB_FRW_BSSPVW_INFO_BUS
BSSPVW.CSF
Block that invokes the function bsspvw_info.
Block dependent.
Supplementary code "zbin_komdat"
F:
R:
A:
EQ:
EM:
AM:
AA:
32 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
33 Hex
F:
R:
A:
type
EQ:
EM:
AM:
AA:
Memory assigning for KOMDAT structure temporarily not
possible. Exact cause of error see section Error supplementary
code bsspvw_geme.
KOMDAT area is not set.
Repeat the function invocation
Z_FRW_ZBIN_N_ANM
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
Memory assigning for KOMDAT structure not possible
exact cause of error see section Error supplementary code
bsspvw_geme.
KOMDAT area is not set.
Reduce the RAM requirement in the application
Z_FRW_ZBIN_GEME_AUFRUF_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
Transmit/receive ID in transfer structure of the function incorrect.
KOMDAT area is not set.
The value in transmit / receive ID must correspond to the ENUM
z_kenn_val
Z_ZBIN_DIR_KENN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
4-3
Error Supplementary Codes
34 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
EQ:
EM:
AM:
AA:
The configuring specifications consist of more than 3
components but is not identifiable as a destination specification.
KOMDAT area is not set.
When no destination is configured at AT / AR /US connector,
then the specification may consist of a maximum of three
components (channel name, address stage 1, address stage 2;
when a destination is configured at AT / AR / US connector, then
the specification of the destination rack name must start with an
"@").
Z_ZBIN_ZIEL_N_KENN
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
36 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
Configured destination specification is incorrect.
KOMDAT area is not set.
Only configure a "@" at AT / AR / US connector.
Z_ZBIN_ZIEL_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
37 Hex
F:
R:
A:
Configured channel name is too long.
KOMDAT area is not set.
Channel name first sub?specification at AT / AR / US connector)
may be a maximum of 8 characters long.
Z_ZBIN_KAN_NAM_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
35 Hex
F:
The number of components (separated by a dot) of the
configuring specification is larger than 6.
KOMDAT area is not set.
The specification at AT / AR / US connector may only have a
maximum of 6 components.
Z_ZBIN_TEIL_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
R:
A:
EQ:
EM:
AM:
AA:
38 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
4-4
Configured address stage 1 is too long.
KOMDAT area is not set.
Address stage 1 (second sub?specification at AT / AR / US
connector) may be a maximum of 14 characters long.
Z_ZBIN_ADR_STUF1_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
Error Supplementary Codes
39 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
3A Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
3B Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
3C Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
3D Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
3E Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
Configured address stage 2 is too long.
KOMDAT area is not set.
Address stage 2 (third sub?specification at AT / AR / US
connector) may be a maximum of 20 characters long.
Z_ZBIN_ADR_STUF2_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
The configured destination specification is located in the
incorrect section of the string.
KOMDAT area is not set.
The "@" is only permitted to be at start of the second or third last
sub?specification at the AT / AR / US connector.
Z_ZBIN_STRING_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat
Block dependent.
Configured destination rack is too long.
KOMDAT area is not set.
Destination rack name (first sub?specification after the "@" at
the AT / AR / US connector) must be up to 6 characters long.
Z_ZBIN_ZBGT_NAM_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
Configured destination board name length is incorrect.
KOMDAT area is not set.
Destination board name (second sub?specification after the "@"
at the AT / AR / US connector) must be exactly 6 characters
long.
Z_ZBIN_ZBG_NAM_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
Configured destination interface length is incorrect.
KOMDAT area is not set.
Destination board name (third sub?specification after the "@" at
the AT / AR / US connector) must be exactly 3 characters long.
Z_ZBIN_ZSS_LEN_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat
Block dependent.
Configured destination interface is incorrect.
KOMDAT area is not set.
Only the following interface specifications are permitted: "X01",
"X02", "X03".
Z_ZBIN_ZSS_NAM_ERR
ZBIN.CSF
Block that invokes the function zbin_komdat.
Block dependent.
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
4-5
Error Supplementary Codes
4.4
Supplementary code "zgsd_zini_nachtrag"
02 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
ZINI list is already full
Data interface cannot be initialized.
Reduce the number of data interfaces
SDZ_FRW_ZG_ZINI_ZU_KURZ
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
03 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
Incorrect bus access
Data interface cannot be initialized.
Check hardware or inform Siemens AG.
SDZ_FRW_ZG_BUS_ACC_ERR
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
04 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
ZINI list is already full
Data interface cannot be initialized.
Reduce the number of data interfaces
SDZ_FRW_ZG_ZINI_VOLL
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
05 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
Impermissible board name
Data interface cannot be initialized.
Check CTS connector
SDZ_FRW_ZG_BG_NAM_ERR
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
07 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
ZINI list not found
Data interface cannot be initialized.
Inform Siemens AG.
SDZ_FRW_ZG_ZINI_N_FOUND
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
08 Hex
F:
R:
A:
EQ:
EM:
AM:
AA:
Slot cannot be found
Data interface cannot be initialized.
Inform Siemens AG.
SDZ_FRW_ZG_NO_STPL_NR
ZGSD.CSF
Block that invokes the function zgsd_zini_nachtrag
Block dependent
4-6
General diagnostics - SIMADYN D - Reference Manual
6DD1987-1BA0 Edition 10.97
To
Siemens AG
A&D LD R
Frauenauracher Straße 80
91056 Erlangen
From
Your
Name:
Your
Function
Your
Company:
Street:
City:
Telephone:
Please indicate your particular industrial sector:
o
o
o
o
o
o
o
Automobile industry
Chemical industry
Electrical industry
Foodstuff industry
Process control
Machine construction
o
o
o
o
o
o
Pharmaceutical industry
Plastic processing
Paper industry
Textile industry
Transport
Others _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Petrochemical
"
Basissoftware for D7-SYS - SIMADYN D - Manual
6DD1987-1BA2 Edition 01.99
1
Recommendations and comments on the User Documentation
Your comments and recommendations help us to improve the quality and
usefulness of our documentation. Please complete this form at the next
convenient opportunity and return it to Siemens.
Please give us your own personal opinion to the following questions, values
from
1 = good to 5 = poor.
1.
Do the contents of the documentation fulfill your requirements?
2.
Can you easily find the information you require?
3.
Is the text easy to understand?
4.
Do we go into enough technical details for your requirements?
5.
How do you evaluate the quality of the diagrams and tables?
6.
7.
8.
If you come across any problems, please let us know in the space below: