Foreword, Contents General description SIMADYN D Function Description and User Information General Diagnostics Communication Error Codes Reference Manual Error Supplementary Codes 6DD1987-1AB0 Safety Guidelines This Manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the Manual by a warning triangle and are marked as follows according to the level of danger: _________________________________________________________________________ Danger ! indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. _________________________________________________________________________ _________________________________________________________________________ ! Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. _________________________________________________________________________ _________________________________________________________________________ ! Caution indicates that minor personal injury or property damage can result if proper precautions are not taken. _________________________________________________________________________ _________________________________________________________________________ Note draws your attention to particularly important information on the product, handling the product, or to a particular part of the documentation. _________________________________________________________________________ Correct usage Note the following: _________________________________________________________________________ Warning ! Trademarks This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. _________________________________________________________________________ SIMATIC and SIMADYN D are registered trademarks of SIEMENS AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners. Copyright SIEMENS AG 1997 All rights reserved Disclaimer of liability The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration or a utility model or design, are reserved. We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. Siemens AG Drives and Standard Products Group ASI 1 Variable-Speed Drives Division Frauenauracher Straße 80 91056 Erlangen Siemens Aktiengesellschaft Siemens AG 1997 Technical data subject to change. Order No. 6DD1987-1AB0 Foreword NOTES • This Reference Manual is provided solely as a additional information source and is not necessarily up-to-date. • Purpose of this Manual No guarantee can be made for the technical correctness of this manual. This Reference Manual will help you • when troubleshooting the SIMADYN D control system, and • serve as Reference Manual. The individual diagnostic capabilities will be explained. Target group This manual is intended for engineers commissioning SIMADYN D programs. It is assumed that these persons are knowledgeable about instrumentation and control. Validity of this Manual This manual is valid for SIMADYN D Version 3.1 of D7-SYS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 06.97 iii Foreword Comprehensive user documentation which is intended for selective use, is available to support personnel when configuring and programming a SIMADYN D control task. The following information together with Fig. 01 will help you select the user documentation which you actually require. Overview of the SIMADYN D documentation, Version V5.0 Significance Symbol ? This subject is documented in an online help Reference Manual for selective use The documentation introduces you to the methodology used. The documentation is supplemented by an online help. Online help Manuals can be individually ordered. 1 Introduction SIMADYN D Simple to assemble and configure 1 Manual SIMADYN D Hardware 1 Manual SIMADYN D System software and D7-SYS configuring D7-SYS communication configuring Complete Index SIMADYN D Glossary and complete index Online help Manual SIMADYN D SIMADYN D Basis software for D7-SYS ? Help on events Online help Manual SIMADYN D CFC for SIMADYN D Continuous Function Chart Online help Reference Manual 1 SIMADYN D Function block library Online help Fig. 0-1 Overview of SIMADYN D documentation, Version V5.0 iv General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 06.97 Foreword Introduction Simply to assemble and configure The Introduction provides an extremely simple entry into the methodology when assembling and programming the SIMADYN D control system. It is especially conceived for first-time users of a control system. System software and configuring D7-SYS This Manual provides basic knowhow about the structure of the operating system and an application program of a SIMADYN D CPU. It should be used to obtain an overview of the programming methodology, and as basis for a user program design and configuration . D7-SYS communication configuring This Manual provides you with basic knowhow about the SIMADYN D communications capability and how to configure links to communication partners Function block library This Reference Manual provides you with an overview of SIMADYN D function blocks, such as closed-loop control-, communication blocks etc . Basis software for D7-SYS This Manual explains the essential use and the functions of the STEP 7 automation software with a main focus on the SIMADYN D control system. For first users of SIMADYN D, the Manual provides an overview on configuring, programming and commissioning a SIMADYN D subrack. When working with the basis software, you can access the contextsensitive online help which provides support when it comes to detailed questions regarding software use. CFC for SIMADYN D Continuous Function Chart The CFC language (Continuous Function Chart) allows you to graphically interconnect blocks. The following manuals are available: "CFC for S7, Continuous Function Chart" and "CFC for SIMADYN D, Continuous Function Chart". Further, when using the software, you can access the online help which can answer detailed questions regarding the use of the editors/compilers. Hardware The complete SIMADYN D hardware spectrum is described as reference in this Manual. Table 0-1 Information overview of the SIMADYN D Manuals, Version V5.0 Guide This reference Manual is sub-divided as follows: • resources for troubleshooting • various error classes • error codes The "General diagnostics" Reference Manual consists of the following documents: Document Edition 1 General description 06.97 2 Function Description and User Information 06.97 3 Communication Error Codes 06.97 4 Error Supplementary Codes 06.97 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 06.97 v Foreword Special information The user section of this Manual does not contain any detailed instructions with individual steps, but instead is intended to explain the basic procedure. More detailed information on the software dialogs and their handling, are provided in the online help. Additional support Please contact your local Siemens partner if you have questions regarding the software which are neither addressed in the paper documentation nor in the online help. You can use a Hotline: • Tel.: +49(9131) 98-5000 • Fax: +49(9131) 98-1603 • e-mail: simadyn.hotline@erlf.siemens.de If you have any questions or comments regarding this Manual, please complete the questionnaire at the end of the Manual and send it to the address below. Please let us know your personal opinion about the Manual We offer appropriate courses to make it easier for you to get to know the SIMADYN D automation system. Please contact the Central Training Center in Erlangen: • Tel.: +49(9131) 7-27689, -27972 • Fax: +49(9131) 7-28172 • Internet: http://www.atd.siemens.de/it-dl/training • Intranet: http://training.erlm.siemens.de vi General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 06.97 Inhaltsverzeichnis 1 General description............................................................................................................. 1-1 1.1 The various resources for troubleshooting................................................................. 1-1 1.2 System error fields.................................................................................................... 1-3 2 Function description and user instructions ...................................................................... 2-1 2.1 Acknowledging errors................................................................................................ 2-1 2.2 The various SIMADYN D error classes ..................................................................... 2-1 2.2.1 Error in the INIT operating mode, 7-segment display "0" ................................ 2-1 2.2.2 Error in the RUN operating mode, 7-segment display "E", "C", "A" ................. 2-8 2.2.2.1 Error, task administrator "E" ......................................................... 2-8 2.2.2.2 Error communications "C" ............................................................ 2-9 2.2.2.3 User error "A"............................................................................. 2-10 2.2.2.4 Fatal system error "H" ................................................................ 2-10 2.3 Background processing........................................................................................... 2-14 2.3.1 Online test mode.......................................................................................... 2-14 2.3.2 Monitoring error, 7-segment display "b"........................................................ 2-14 3 Communication Error Codes .............................................................................................. 3-1 3.1 Overview .................................................................................................................. 3-1 3.2 Error Codes .............................................................................................................. 3-2 3.2.1 Data Interface Access Mechanisms ............................................................... 3-2 3.2.2 Data Interface Initialization Errors (IB Errors) ............................................... 3-18 3.2.3 Network ....................................................................................................... 3-18 3.2.4 Service ........................................................................................................ 3-31 3.2.4.1 Display ....................................................................................... 3-32 3.2.4.2 Specific SS52 ............................................................................ 3-37 3.2.5 Process Data ............................................................................................... 3-38 3.2.6 Message System ......................................................................................... 3-41 3.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace)................................ 3-46 3.2.8 Time ............................................................................................................ 3-53 3.2.8.1 Device........................................................................................ 3-55 3.2.8.2 Download................................................................................... 3-58 3.2.9 Central Blocks for Links ............................................................................... 3-60 3.2.9.1 Coupling Memory Link................................................................ 3-60 3.2.9.2 Rack Link ................................................................................... 3-63 3.2.9.3 PN Local Link............................................................................. 3-68 3.2.9.4 Link DUST1................................................................................ 3-71 3.2.9.5 Link SINEC H1........................................................................... 3-71 3.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung ............... 3-75 3.2.9.7 EP Link ...................................................................................... 3-81 3.2.9.8 Link DUST7................................................................................ 3-84 3.2.9.9 Link DUST2................................................................................ 3-89 3.2.9.10 Link DUST3.............................................................................. 3-93 3.2.9.11 USS Link.................................................................................. 3-97 3.2.9.12 Rack Link Fiber Optic Cable................................................... 3-101 3.2.10 Gerätekopplung und Parameterbearbeitung auf T400.............................. 3-108 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 vii Inhaltsverzeichnis 4 Error Supplementary Codes ............................................................................................... 4-1 4.1 Supplementary code "bsspvw_geme"....................................................................... 4-1 4.2 Supplementary code "bsspvw_info" .......................................................................... 4-2 4.3 Supplementary code "zbin_komdat" ......................................................................... 4-3 4.4 Supplementary code "zgsd_zini_nachtrag" ............................................................... 4-6 viii General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 1 General description 1.1 The various resources for troubleshooting The following resources are available in the system for troubleshooting: NOTE The 7-segment display on the CPU module is the first resource which permits rough troubleshooting. Depending on the error type, instead of the configured CPU number, a symbol is displayed which classifies the error. The first error which was identified, is displayed, flashing. After being acknowledged with the red button on the CPU module, the error code of the next error which was identified, is then displayed. The sequence in which these error codes are displayed depends on the priority of the error. The following can be displayed on the 7-segment display: At initialization or in the off status, operating mode INIT In cyclic operation RUN operation mode Initialization running (short numbers can also appear here) <OFF> or <.> Processor crashed, no further diagnostics possible. Replace the memory module or CPU module CPU number, cyclic operation without system error .. Monitoring error, cyclic operation; service possible; refer to the Chapter "Monitoring errors Communication errors, cyclic operation, service possible; refer to the Chapter "Communication errors" Task administration error, cyclic operation; service possible; refer to Chapter "Task administration errors" User error, generated by the USF function block, cyclic operation; service possible; refer to the Chapter "User errors" General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 1-1 General description In non-cyclic operation, STOP operation mode Initialization error, no cyclic operation; service possible; refer to Chapter "Initialization errors" Non-maskable interrupt, no cyclic operation; service possible; refer to the Chapter "Fatal system errors" (as running light). Error when loading the system software, no further diagnostics possible. The memory module could be defective or data incorrectly loaded into it. Stop mode, initiated by the user. Fast download NOTE System error fields and exception buffers are memory areas in which detailed information on the errors which have occurred, can be saved. Non-critical errors from the various software components (operating system, communications,...) are saved in the system error fields. The current system status is saved in the exception buffer when a fatal error occurs, which results in standard processing being stopped. These error fields are read-out, e. g. using CFC in the test mode. 1-2 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 General description 1.2 System error fields In addition to the displayed symbols in the CPU 7-segment display, detailed error information is saved in the central RAM area of the CPU module. These data areas are designated system error fields. The system error fields, described here are called INIT_ERR and SYS_ERR. Hardware-related error information is coded in the system error field INIT_ERR. The various software components (operating system, communications, monitor, user, ...) enter their error information in the SYS_ERR system error field. The first error field is used to identify which of the software components was the first to flag an error. It is possible to identify the first one from a series of saved errors (which may subsequently initiate other errors). The first error field is a bit field in which each software component has an assigned bit. This is set to ’1’, if this component is the first to enter an error. First error field SYS_ERR_ERST The assignment of the bits can be seen from the following table: First error field Byte 1 Byte 0 15 14 13 12 11 10 Always 0 Usergenerated error code 1) -> 0400H 9 8 Always 0 7 6 5 4 3 2 1 0 Always 0 Communications error Hardware failure (monitoring error) Task administration error Al Fatal w system a error y s 0 0040H 0020H 0008H 0001H Table 1.2-1 Assignment of the bits 1) These hexadecimal values are valid for the appropriate software components, as a maximum of one bit can be set in the first error field General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 1-3 General description 1-4 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2 Function description and user instructions 2.1 Acknowledging errors If an error occurs, then this is indicated on the CPU 7-segment display. With the exception of fatal system errors (NMI) and communication errors, these errors can be acknowledged by depressing the acknowledge key. The highest-priority error message is always displayed first. After depressing the acknowledge button, the next highest priority error message is displayed. The appropriate symbol is displayed, flashing, to identify that the displayed error was the first one to occur. If there are no more errors, the logical CPU module number is displayed. 2.2 The various SIMADYN D error classes 2.2.1 Error in the INIT operating mode, 7-segment display "0" The errors of the INIT operating mode are saved in the FLAGH, FPNIB, PNINKO, KO_CBUS and KO_LBU elements of the SYS_ERR error field and in the INIT_ERR error field. For errors, which occur when the system is initialized, the user program doesn’t run-up. However, the service utility can be used and can be used for diagnostics. Error diagnostics should start at that CPU module, which was the first to display an error message . If there is no CPU module which can be identified as having been the first, then that CPU should be selected, which displays a , and which is to the furthest left in the subrack. The significance of the error field contents is listed in the following pages: However, if fatal system errors occur at initialization (e. g. non-maskable interrupt NMI), initialization is aborted, and an appears in the 7-segment display. NOTE Fatal system errors can occur following an initialization error, for example, if a function block addresses hardware, which wasn’t previously correctly initialized. Thus, when fatal system errors occur during the initialization phase, the error field should first be investigated for initialization errors! General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-1 Function description and user instructions Initialization error FLAGH Set bit Significance 0 Error when initializing the DRAM memory object 1 Error when initializing the SRAM memory object 2 Error at C BUS upload 3 Error at C BUS download 4 Error when creating the C BUS buffer system 5 Error when initializing the C bus buffer system 6 Error at L BUS upload 7 Error at L BUS download 8 Error when creating the C BUS buffer system 9 Error when creating the L bus buffer system 10 Error when initializing the task manager 11 RAM change is inhibited in the change memory 12 Änderungsspeicherinhalt kann nicht geladen werden; Speicherplatzmangel beim Service 13 Fehler bei der Initialisierung der Dollarsignale 14 15 CPU hat kein Anwenderprogramm Bits 0-10, subsequent errors or system errors; the user cannot resolve these errors Bit 11 can be an error due to an erroneous change memory, especially for test operation, can be resolved, if, in the change memory the correct test byte ID AA (hexa) is entered in byte 0, and a 0 is entered in byte 2. ! ATTENTION The change memory entries are then lost! Bit 13: siehe Diagnose der Dollarsignal Initialisierungsfehler Bit15: Anwenderprogramm laden 2-2 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions PN initialization- and PN-IB error FBNIB Set bit Significance 8 Group display from the initialization blocks. (also refer to system error field INIT_ERR, ) 9 When requesting a mirror register area in a KS, the slot number or location ID are inconsistent, or the memory object ID illegal 10 The requested mirror register area has already been set-up in the local RAM or in the communications buffer module 11 Number of CPU modules in the C/L bus directory > 1 with the ID, no C/L bus buffer module 15 Group display when communications is initialized Subsequent errors or system errors; they cannot be resolved by the user Error flags from the coordination associated with initializing a multiprocessor system, is entered in the PNINKO element. Coordination error at PN Initialization PNINKO Bits are set for the various error statuses, if the delay time, defined in the operating system, is not adequate for synchronization, i. e. the appropriate initialization stage must be aborted. Even bits (0,2,..) designate the bus master, uneven bits, the bus slaves. Bits 0-7 are used for the C-bus coordination, bits 8-15, for L-bus coordination. Set bits for Synchronizing is canceled for the defined operation Master Slave C bus L bus C bus L bus 0 8 1 9 2 10 3 11 3 11 Loading the mirror register into the communications buffer 4 12 5 13 Re-loading the KS information into the local RAM 6 14 7 15 Initialization- or final synchronization 6 14 6 14 FP initialization, possibly due to erroneous user function blocks. Also refer to KO_CBUS and KO_LBUS Copying local information into the KS Before re-loading the KS lists into the local RAM Subsequent errors or system errors-CPU, which caused the error, can be identified from KO_CBUS and KO_LBUS General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-3 Function description and user instructions Missing checkback signal from the C bus or L bus KO_CBUS and KO_LBUS The CPU modules are marked in these error fields, which hadn’t synchronized with the CPU being investigated. The type of synchronizing error is defined in the PNINKO component. The non-synchronized CPU modules are logged using a bit pattern in the components " " " KO_CBUS for the C bus KO_LBUS " " L bus and the appropriate bits ("PN No." - 1) set to 1, whereby the PN No. is the logical CPU number (CPU No. = Bit No. + 1). Example: SIMADYN D CPU 7 does not checkback via the C bus => KO_CBUS = 0040. Diagnosing initialization errors with the system error field INIT_ERR If errors are identified in the initialization blocks during the initialization phase, then this is indicated in the group display of the SYS_ERR_FPNIB components of the system error field SYS_ERR, and, detailed information regarding the error is also saved in the system error field INIT_ERR. Only module errors are registered in the error field INIT_ERR, for those modules which are located from the CPU module, being investigated, up to the next CPU module, inserted to the right in the subrack. Monitoring errors, i. e., errors, which were first identified during normal operation, are also logged in INIT_ERR. The INIT_ERR system error field is 25 words long (50 bytes). A word is reserved for each module, whereby word- and slot number are clearly assigned to one another (word 1 to word 24 correspond to slots 1 to 24). Each SIMADYN D CPU saves its own error information in word 0. An error is displayed, if in one or several words of this field, a value is not equal to 0. The following messages are possible in word 0: Error number (hexadecimal) 2-4 Significance 1XXX L bus interrupt is not received from the slave CPU 2XXX C bus interrupt was not received from the slave CPU 4XXX L bus KS cannot be accessed for slave CPU 8XXX C bus KS cannot be accessed for slave CPU FXXX The length of the interrupt vector table in a CPU initialization block is inconsistent General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions Measures: Check the daisy chain jumpers and insert as configured System error or subsequent error, cannot be resolved by the user The error numbers, listed here, can be located in words 1-24 of error field INIT_ERR. System errors or subsequent errors, cannot be resolved by the user General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-5 Function description and user instructions Error number (hexadecimal) 01XX 011X 0111 Significance PAD initialization CPU module error Incorrect module code Incorrect module, incorrect type or development status Measure: Insert the right CPU module type 012X Periphery initialization error Measure: Insert the correct module into the correct slot 0121 Invalid slot number transferred 0122 Incorrect module code 0124 No access to the module 0128 Invalid memory range size 014X Chip select error 0141 Address limits for chip select B interchanged 0142 Address limits for chip select C interchanged 0144 Invalid slot basis address 018X Warnings 0181 All chip select inhibited 0182 Chip select address exceeded 0184 Illegal mask for chip select A 02XX 0200 Memory initialization L-bus communications buffer cannot be accessed from KS-IB Measure: Test the communications buffer module 0201 Not possible to access the C-bus communications buffer from KS-IB Measure: Check the communications buffer 0202 Error during memory object initialization 0204 Communication resource list not available 04XX 0401 Illegal memory object ID 0402 Non-configured memory used 0404 Not sufficient memory available 0408 Memory object inhibited 0410 Distribution mode illegal 08XX 2-6 Requesting the mirror register Special periphery, IB errors 0801 C-bus connection not available 0802 Synchronizing error (is signaled as monitoring error) 0804 Incorrect slot number Measure: Insert the module into the correct slot 0808 Incorrect configured special periphery 0810 Dual port RAM unable to be accessed 0820 L-bus connection not available 0840 Configuring error General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions Error number (hexadecimal) 0FXX 0F1X Significance Monitoring error Memory test error, can be signaled both as initialization error as well as monitoring error 0F10 User memory error Measure: Progam a new memory module 0F11 RAM error: Defective address line Measure: Change the module 0F12 Memory module error Measure: Program a new memory module 0F14 RAM error: Data line defective Measure: Change the module 0F18 Special periphery test error 0F1F Incorrect transfer parameter 0F2X Error when testing 0F20 Incorrect slot number Measure: Insert the module into the correct slot 0F21 Battery failure Measure: Insert a battery or replace the battery 0F22 Module does not respond Measure: Insert the correct module type 0F24 Fatal system error on another CPU module Measure: Search for errors on other CPU modules 0F4X Overload, area X5 Short-circuit or excessive current (not a brief overload condition). Measure: Check the periphery 0F41 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 0F42 Overlaod, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 0F8X 0F84 0F88 0FCX Overload, area X6 Short-circuit or excessive current (not a brief overload condition). Measure: Check the periphery Overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8 Overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18 Overload, areas X5 and X6 simultaneously Short-circuit or excessive current (not a brief overload condition). Measure: Check the periphery 0FC5 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 and overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8 0FC9 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 and overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18 0FC6 Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 and overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8 0FCA Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 and overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-7 Function description and user instructions 2.2.2 Error in the RUN operating mode, 7-segment display "E", "C", "A" Errors, occurring in normal operation, are saved in the DAT, COM_PM, COM_EXC, and ANW elements of the SYS_ERR error field. 2.2.2.1 Error, task administrator "E" If a task administrator error occurs, the user program continues to run as well as it can. For cycle errors, or inhibited tasks, low-priority tasks are either not processed, or not on a regular basis. Errors of the task administrator are recorded in the SYS_ERR_DAT components of the SYS_ERR system error field. This field is 5 bytes long, which are assigned to the existing tasks (bytes 0 - 4 for cyclic tasks T1 - T5). A task, which was processed error-free, has the value 0 in "its" byte. Bits which have been set, have the following significance (several bits can be simultaneously set): Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Cycle error which cannot be resolved (endless loop) Internal error Software watchdog (only for T1) No free buffer in the C bus communications buffer Not used No free buffer in the L-bus communications buffer No free local buffer Cycle error or task back-up System errors or subsequent errors, cannot be resolved by the user Cycle errors Before a task is started, it is checked as to whether the task to be started can be completely executed within the task sampling time, or if it is always in the ’continuous’ status. This means, it is flagged as the highestpriority task. If this is the case, the task start is bypassed, i. e. the task is not processed for one cycle. However, a cycle error is only flagged, when several task starts fail, i. e. not at the first failure. Thus, seldom failures, which do not negatively influence program execution, are simply bypassed. 2-8 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions If several cycle errors occur one after the other then you can assume that a task has a significant problem. The cause can be an endless loop within this task, or that practically no computation time is made available for this task over a longer time period (this computation time is completely used by higher-priority tasks), and can therefore not be fully computed. in the 7-segment Thus, in this case, processing is stopped (with an display) and the diagnostics mode (communications utility service) is started. The user can resolve a cycle error, e. g. by increasing the sampling time of the task involved or by reducing the configured function blocks in the particular task. Task "bottleneck" Task "bottleneck" for a particular task is only registered, if the task is not flagged as being the highest-priority task; however it should be started again. Generally, the cause is a cycle error of a higher-priority task. The task start is evaluated just as for cycle errors, and generates the same display bit. The same task-specific error information is used. For a task "bottleneck", using the PSL function block, the utilization of the individual tasks should be determined, and, if required, reduced by re-configuring the software (as for cycle errors). No free local buffer This error is the result that the data sink no longer enables the data buffer. The task start is skipped. Software watchdog A software watchdog occurs if the basic sampling time is not processed four times consecutively (one after another). The basic cycle timer is reinitialized with the configured basic sampling time, and processing continued. If two software watchdogs occur one after the other, then instead of the in basic cycle timer being re-initialized, processing is aborted (with an the 7-segment display) and diagnostics operation (service communications utility) started. 2.2.2.2 Error communications "C" Communication errors are entered in the SYS_ERR_COM_PM components of the SYS_ERR error field. Several entries are possible. The SYS_ERR_COM_EXC components specify which communication errors have been entered. A communications error consists of an error number, a supplementary ID as well as the configured chart- and block name and an address to localize the function block to be entered. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-9 Function description and user instructions 2.2.2.3 User error "A" The user himself specifies the entries in the SYS_ERR_ANW components of the SYS_ERR system error field. The USF function block makes the entry. 2.2.2.4 Fatal system error "H" If a fatal system error occurs, processing (initialization or normal operation) is interrupted, and the system goes into the stop mode. The error cause is available for diagnostic purposes. NOTE Before investigating a fatal system error, the INIT_ERR and SYS_ERR system error fields should first be investigated. If errors are entered there (especially hardware (monitoring) errors), then this could be the cause of a fatal system error. A SAVE area is set-up in the upper area, in the local RAM of each CPU module. This area is not erased at re-initialization, if the status of the RAM copy is appropriate. An error buffer is set-up in this SAVE area, which includes the error protocol (error report) consisting of several messages. The error buffer consists of an administration part and a ring buffer, in which the error messages are saved. The ring buffer is implemented as buffer which can be overwritten, i. e. if the buffer is full with error messages, then the new messages overwrite the oldest messages. There are 2 different types of error messages. A long message is output in the case of a non-maskable interrupt NMI. A short message for a power OFF. The service communications utility is available, (even if it has not been configured) to troubleshoot fatal system errors. It can be accessed via the local diagnostics interface, after pressing the acknowledge button. Using the service utility, the error causes can be output in plain text. What is especially important is the error cause, specified under an ID code and supplementary ID. If a function block is being calculated at the instant that the system error occurs, then this is output. In addition, the results of the last bus accesses are displayed; these are important, if a bus access is the error cause. Further, all of the process registers are displayed for the system specialists to allow them to make a precise error analyses. 2-10 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions NMI handling When a non-maskable interrupt occurs, this is considered as fatal error and causes initialization or normal operation to be interrupted. All of the modules, inserted in the subracks, are no longer processed. is displayed on the CPU module display of the A large flashing is displayed as faulted module, which caused this fatal error. A large steady display on the other CPU modules which received an NMI as result of the faulted module. The debug monitor can be activated by pressing the acknowledge button or setting the status value. The symbols output on the 7-segment display have the following significance: Steady Flashing : CPU module was shutdown by another module. : Fatal error on this CPU module (error cause). General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-11 Function description and user instructions Example for an error protocol (error report) for fatal system errors Information on the last crash: Time: 01.01.93 04:16:24.9294 h ID: #5 CPU Supplementary ID: 28 (unaligned instruction fetch) EPC: 0x04C4F19A Return jump address: 0x801201f8 Running task: Started levels: Last processed FB: Last L-bus access: - Access type: - BUS address: - Retries: Last C-bus access: - Access type: - BUS address: - Retries: T2 T2(NRM),T5(NRM),BACKGROUND FP-KRUMMS.AY0815 (Typ: ADD8F) (ALE: 0x80107D84 CODE: 0x801201E0) Crash instant } Crash cause Crash adress and adress of the last function call The running and started tasks at the crash instant as well as the processed function block with information on the data- and code areas Data on the system bus accesses. This data is especially interesting, if an erraneous bus access is specified as the cause of the crash in the ID (NMI) and supplementary ID. q_read_2byte 0xB0F25874 0 q_read_2byte 0xB4F400B4 0 The processor status at the crash instant: EPC : 0x04C4F19A BadVAddr: 0x04C4F19A Status : 0xF000FC14 mdlo : 0x04C4F19A fpc_csr : 0x00000F04 Register dump of all process register Especially important: EPC (crash adress, as above) and BadVAddr (bad virtual adress, adress which was erroneously accessed (mainly for ID TLB and CPU)) CAUTION: The value of a0, a1 (and possibly a2) is not valid! r00/0 : r04/a0: r08/t0: r12/t4: r16/s0: r20/s4: r24/t8: r28/gp: 0x00000000 0x80064FC8 0x80064FC4 0x04C4F19A 0x800650CC 0x8006548C 0xFFFFFFFF 0x80088BA0 r01/at: r05/a1: r09/t1: r13/t5: r17/s1: r21/s5: r25/t9: r29/sp: 0x00000000 0x80064F44 0x80065048 0x8007FE90 0x8006511C 0x00000020 0x8007FE90 0x80064EA8 r02/v0: r06/a2: r10/t2: r14/t6: r18/s2: r22/s6: r26/k0: r30/s8: 0x00000001 0x0000000A 0x19999999 0x00000000 0x00000000 0x800812E0 0x00000210 0x04C4F19A r03/v1: r07/a3: r11/t3: r15/t7: r19/s3: r23/s7: r27/k1: r31/ra: 0xB8803000 0x00000000 0x00000000 0x00000000 0x8006548C 0x80400000 0x04C4F19A 0x801201f8 d00: +Denorm d08: +4.687500e+01 d16: +3.000001e+03 d24: -1.818767e-12 d02: +6.400000e+01 d10: +Denorm d18: +4.687500e+01 d26:-1.227518e+306 d04: +Denorm d12: +Denorm d20: QNaN d28:-3.691391e+249 d06: +9.999000e-01 d14:+2.660285e+154 d22:+8.329648e+298 d30:-2.374690e-237 f00: +4.787490e+01 f08: +0.000000e+00 f16: +1.024000e+03 f24: QNaN f02: +0.000000e+00 f10: +Denorm f18: +0.000000e+00 f26: QNaN f04: f12: f20: f28: f06: +4.764729e+05 f14: -1.960343e+37 f22: QNaN f30: -4.550802e-04 +4.687500e+01 +4.787490e+01 -1.693935e+38 -6.835168e-27 ------------------------ End of the diagnostics ----------------------- 2-12 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Function description and user instructions Causes of fatal errors A fatal system error can have the following causes (ID codes). A supplementary ID describes the error cause in more detail. ID Supplementary ID code (precise description) NMI a non-maskable interrupt second bus clear for task-controlled access bus clear for direct access timeout during L/C-bus arbitration/assignment (module missing/defective, daisy chain missing) ready internal from L/C bus (error on another CPU module) ready internal from the local expansion bus (LE bus) system bus controller overrun timeout when accessing the local periphery spurious interrupt (an interrupt source cannot be identified) direct access to the L/C bus (bypassing the driver functions) exceptional status of the CPU internal error reserved Instruction unknown Syscall unaligned instruction fetch (jump to address which cannot be divided by four) user access to kernel space unaligned load/store to coprozessor 0/2/3 unaligned load/store to L-/C-bus address space break 6/7 not in div/mul context unknown break value reserved exception task running in endless loop FPU exception status fpu fault at non-fpu instruction illegal fpu sub opcode operation on NaNs add/sub/division of infinities mul of infinity and 0 exception status of the TLB TLB modified exception TLB read/write miss (access to illegal address) UTLB miss (access to illegal address) basic cycle time failure power down power down/reset in the normal mode power down/reset in the stop mode (after another exception) CPU FPU TLB TIME OFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 2-13 Function description and user instructions 2.3 Background processing If the CPU has no tasks to process during normal operation, it processes the background task. As background task, the following functions are simultaneously available: − the online test mode and − a service utility The online test mode is normally processed in the background after initialization was successfully completed. However, if the acknowledge button is pressed at the end of initialization, then only the service communications utility is activated. Errors in the background processing are saved in the UEB element of the error field SYS_ERR. 2.3.1 Online test mode In the online test mode, for example, a battery test, a memory module checksum test etc. are executed. The memory module checksum routine determines the memory module checksum and compares it with the checksum calculated by the programmer and that saved in the memory module. If a memory module checksum error is identified in the online test mode, the user can remove the error by repeatedly generating the memory module. For battery test errors, he can replace the battery. 2.3.2 Monitoring error, 7-segment display "b" The background processing errors are known as monitoring errors. They are registered during the online test mode, and in the normal mode by an "b" at the 7-segment display. Further, the error information is saved in the system error fields. However, there are also errors, which are identified during initialization, but, due to their low significance, are flagged as monitoring errors and normal mode is still permitted. If a monitor error is identified, then the appropriate bit of the slot number of the associated board is set in the SYS_ERR_UEB component of the SYS_ERR system error. Further, detailed information is saved in the appropriate word of the INIT_ERR system error, in the slot number of the associated module. 2-14 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3 Communication Error Codes 3.1 Overview The distribution with regard to the individual functionalities is as follows: Number Range Total Functionality Already Utilized 6000 - 60DF 6000 - 60BF Data Interface Access Mechanisms 60E0 - 60FF 60E0 - 60E3 Data Interface Initialization Errors 6100 - 61FF 6100 - 61AA Network Management 6200 - 6280 6200 - 6206 Service 6300 - 6380 6300 - 6333 Process Data 6400 - 6480 6400 - 6421 Message System 6500 - 6580 6500 - 654A Trace 6600 - 6680 6600 - 660B Time 6700 - 67FF 6700 - 6718 Devices 6800 - 68FF 6800 - 6810 Down Load 6900 - 6BFF 6900 - 6A6F Central Blocks for Links 6C00 - 6FFF 7C00 - /CFF Unassigned 7C00 - 7CB66 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Gerätekopplung und Parameterbearbeitung auf T400 3-1 Communication Error Codes 3.2 Error Codes The error codes are structured according to the same scheme as with the "Error Diagnostics Communication V3.2’’. The codes consists of: 6100 Hex Error Number in Hex Format F: R: A: EQ: EM: AM: AA: Error Cause System Reaction Resolve By Definition Location and Equate of the Error Codes Module, that determines the Error Module, that displays the Error Display Type of the Error The extended error codes EQ, EM and AM (not printed in bold) are of no significance for the designer. They are only supplementary information for the hotline or the development department of SIMADYN D. 3.2.1 Data Interface Access Mechanisms The error codes designated with ①, have no equates in SDZ.SD, but are converted as follows from the defined acknowledge value: Error Code = SDZ_QUIT_xxx ) 6010 Hex. The error codes designated with ② , have no equates in SDZ.SD, but are converted as follows from the defined acknowledge value: Error Code = SDZ_QUIT_xxx * 20 Hex ) 6060 Hex. 3-2 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6000 Hex 6001 Hex 6002 Hex 6003 Hex 6004 Hex 6005 Hex F: No error detected. R: Error free function. A: Not necessary. EQ: SDZ_FRW_ZC_DATA_OK. EM: ZC.CSF. AM: Block invoking the function zc_start. AA: None. F: (Only receiver) transmitter has not identified itself, i.e. the channel is not yet in operation. R: Receive operation has not yet taken place. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_SEND_N_STARTKLAR. EM: ZCRD.CSF. AM: Block invoking the function zc_start. AA: Warning state. F: (Only transmitter) receiver has not yet identified itself, i.e. channel not yet in operation. R: Transmit operation has not taken place. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_EMPF_N_STARTKLAR EM: ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. F: Transmitter: Handshake / Select: User data length of the data to be transmitted is zero and channel is empty. Refresh / Multiple: User data length is zero and channel is readyfor operation. Receiver: Not Select: User data length of the data to be received is zero and no acknowledge exists from the transmitter. Select: User data length of the data to be received is zero. R: Transmit / Receive operation has not taken place. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_N_ATG EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. F: (Only transmit) Handshake/Select: User data buffer in the channel is still full and no acknowledge exists from the receiver. Refresh: User data buffer is being read in the channel. Multiple: Cannot occur. R: Transmit operation has not taken place. A: Re-invoke function zc_start. EQ: SDZ_FRW_ZC_PUF_VOLL EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. Not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-3 Communication Error Codes 6006 Hex F: 6007 Hex to 600F Hex 6010 Hex utilized. 6011 Hex F: 6012 Hex F: 6013 Hex F: 6014 Hex F: 3-4 F: (Only select transmit): another transmitter has temporarily occupied the channel. R: Transmit operation has not taken place. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_SEND_KAN_BLOCK EM: ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. Defined acknowledge was inserted into the channel. R: Acknowledge operation has taken place. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_QUIT_ABGESETZT EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. The acknowledge ‘‘Remote Link Partner Missing’’ was read from the channel. R: Line to link partner defective; The link partner is missing. A: Check line; Re-invoke the function zc_start EQ: SDZ_QUIT_KOP_PART_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. (Only receiver) the acknowledge "Transmit Pause’’ was read from the channel. R: Transmitter temporarily does not carry out transmit operations. A: Re-invoke the function zc_start. EQ: SDZ_QUIT_SEND_PAUSE _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. (Only transmit) the acknowledge ‘‘Receive Pause’’ was read from the channel. R: Receiver temporarily does not carry out receive operation. A: Re-invoke the function zc_start. EQ: SDZ_QUIT_EMPF_PAUSE _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. The acknowledge ‘‘Break’’ was read from the channel. R: The link partner has temporarily disconnected. A: Re-invoke the function zc_start. EQ: SDZ_QUIT_BREAK _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6015 Hex F: 6016 Hex F: 6017 Hex F: 6018 Hex F: The acknowledge ‘‘NMC Off" was read from the channel. R: The corresponding NMC FB in the link has switched to the ‘‘OFF’’ state. A: Investigate the NMC block that transmitted the acknowledge. EQ: SDZ_QUIT_NMC_AUS _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. (Only SINEC L2 DP) The acknowledge ‘‘Station cannot be Controlled’’ was read from the channel. R: Bit 1 of the station diagnostics (byte 0 of slave station) was set. A: Check station. EQ: SDZ_QUIT_STAT_N_STEUER _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. (Only SINEC L2 DP) The acknowledge ‘‘Station not on the SI NEC L2 DP Bus’’ was read from the channel. R: Bit 0 of the station diagnostics (byte 0 of the slave station) was set. A: Check if station is operational; Check whether bus cable is connected. EQ: SDZ_QUIT_STAT_N_AM_BUS _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. (Only SINEC L2 DP) The acknowledge ‘‘Station Diagnostics Error’’ was read from the channel. R: Two or several bits of the station diagnostics (byte 0 of slave station) were set. A: Two or more of the above described errors (SDZ_QUIT_BG_AUS_PORT_ERR, SDZ_QUIT_ADR_ERR_PARA_ERR, SDZ_QUIT_STAT_N_STEUER, SDZ_QUIT_STAT_N_AM_BUS) have occurred. EQ: SDZ_QUIT_STAT_DIAG_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Warning state. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-5 Communication Error Codes 6019 Hex F: (Only SINEC-L2-DP) The acknowledge "Slave already configured by another Master" was read from the channel. Is "another Master" a PG --> temporary fault Is "another Master" a general DP-Master --> two Masters configure the same slave; hard fault A: Is "another Master" a PG: When the PG releases the slave, then Master can access slave again Is "another Master" a general DP-Master: check bus configuration EQ: SDZ_QUIT_MASTER_LOCK _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status The acknowledge "Transmission error: Parity, Framing or Overrun" was read from the channel. R: The received telegram will be discarded A: Check hardware layout; i.e. terminating resistor, bus cable, bus connector, etc. EQ: SDZ_QUIT_POF_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status The acknowledge "BCC error" was read from the channel. R: The received telegram will be discarded A: Check hardware layout; i.e. terminating resistor, bus cable, bus connector, etc. EQ: SDZ_QUIT_BCC_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status The acknowledge "DUST3: No connect (no DLE)" was read from the channel. R: Connect is repeated A: Start-up link partner; Check hardware layout; i.e. terminating resistance, bus cable, bus connector, etc. EQ: SDZ_QUIT_KOP_NO_ACK _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status The acknowledge "DUST3: receive character delay" was read from the channel. R: The received telegram will be discarded A: Check hardware layout; i.e. terminating resistance, bus cable, bus connector, etc. EQ: SDZ_QUIT_EZVZ_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status R: 601A Hex F: 601B Hex F: 601C Hex F: 601D Hex F: 3-6 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 601E Hex 601F Hex 6020 Hex 6021 Hex to 602E Hex 602F Hex 6030 Hex F: The acknowledge "DUST3: Invalid receive string, receive character during transmission" was read from the channel. R: The received telegram will be discarded A: Check hardware layout; i.e. terminating resistance, bus cable, bus connector, etc. EQ: SDZ_QUIT_CHAR_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status F: The acknowledge "DUST3: Invalid receive telegram type" was read from the channel. R: The received telegram will be discarded A: Check SIMATIC S5 configuring with regard to the transmit telegram type EQ: SDZ_QUIT_TEL_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status F: The acknowledge "DUST3 / USS: Faulty or no reaction telegram" was read from the channel. R: The received telegram will be discarded A: Start-up link partner; Check hardware layout; i.e. terminating resistance, bus cable, bus connector, etc. EQ: SDZ_QUIT_TEL_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Warning status not utilized F: F: The acknowledge index from the user is invalid. R: No transmit / receive acknowledge operation took place. A: Contact Siemens AG. EQ: SDZ_FRW_ZC_USER_QUIT_ERR EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start. AA: Block dependent. Memory assigning for ZCDAT structure temporarily not possible. Exact cause see chapter Error Supplementary Code bsspvw_geme. R: ZCDAT structure has not been set, link initialization cannot be started. A: Re-invoke function zc_start. EQ: SDZ_FRW_ZC_N_ANM EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-7 Communication Error Codes 6031 Hex 6032 Hex 6033 Hex 6034 Hex 6035 Hex 6036 Hex 6037 Hex to 603E Hex 603F Hex 3-8 F: The CIP entry for the link was found. R: ZCDAT structure has been set, link initialization can be started. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_CIP_ETG_OK EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. F: The link in the CIP entry is enabled. R: Initialization of the link has begun. A: Re-invoke function zc_start. EQ: SDZ_FRW_ZC_KOP_FREI_OK EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. F: The link in the CIP entry has not yet been enabled. R: Initialization of the link has not yet been started. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_KOP_N_FREI EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. F: The DEXDO3 area is enabled. R: The DEXDO3 enable is set to ‘‘Free’’ in the interface. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_DEXDO_FREI_OK EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. F: The DEXDO3 area has not yet been enabled. R: The DEXDO3 enable is set to ‘‘Disable’’ in the interface. A: Re-invoke the function zc_start. EQ: SDZ_ZC_FRW_ZC_DEXDO_N_FREI EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. F: Link enabled, channel initialization running. R: Channel registration or channel registration checks are started. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_KAN_INIT_START EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. reserved for debug purposes (within zc_start). F: Channel initialization completed without error. R: Channel registration or channel registration check is completed, channel is switched to transmit / receive operation. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_KAN_INIT_OK EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6040 Hex F: Back plane bus access unsuccessful. R: Exception processing has started, a new initialization is subsequently implemented. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_EXC EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. not utilized. 6042 Hex to 604E Hex 604F Hex F: 6050 Hex F: 6051 Hex F: 6052 Hex F: 6053 Hex F: (Multiple receiver) data inconsistent in intermediate buffer. R: Transmitter has overwritten the data in the channel before the receiver could read it. A: Re-invoke the function zc_start. EQ: SDZ_FRW_ZC_DATA_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Warning state. The buffer status is faulty in the channel. R: The information in the channel management is inconsistent, further processing of the channel is not possible. A: Contact Siemens AG. EQ: SDZ_FRW_ZC_PUF_ZUS_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. The channel status in the channel is faulty. R: The information in the channel management is inconsistent, further processing of the channel is not possible. A: Contact Siemens AG. EQ: SDZ_FRW_ZC_KAN_ZUS_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Refresh receiver) buffer semaphore is blocked. R: The information in the channel management is inconsistent, further processing of the channel is not possible. A: Contact Siemens AG. EQ: SDZ_FRW_ZC_PUF_SEM_SPERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Entry in ZCVWL list not possible, since the ZCVWL list is already full. R: ZCDAT area was not set, link initialization cannot be started. A: Reduce the link partners on the processor board. EQ: SDZ_FRW_ZC_ZCVWL_VOLL EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-9 Communication Error Codes 6058 Hex Memory assigning for ZCDAT structure not possible, exact error cause see section Error Supplementary Code bsspvw_geme. R: ZCDAT area was not set, link initialization cannot be started. A: Reduce the RAM requirement in the application. EQ: SDZ_FRW_ZC_ZCDAT_VOLL EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. F: (Only PN local link) the CIP entry cannot be accessed, since it points to another processor board. R: ZCDAT structure was set, but the link initialization cannot be started. A: Board name at the communications port must correspond to the nameof the processor board. EQ: SDZ_FRW_ZC_CIP_NAM_KENN_N_ADR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. F: The CIP entry for the link does not exist. R: ZCDAT structure was set, but the link initialization cannot be started. A: Check the configured name at the communications port. EQ: SDZ_FRW_ZC_CIP_NAM_N_KENN EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. F: Unknown function return value of the function zbak_cip_suche. R: ZCDAT structure was set, but the link initialization cannot be started. A: Contact Siemens AG. EQ: SDZ_FRW_ZC_CIP_SUCH_FRW_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Not utilized. 6059 Hex F: 6054 Hex 6055 Hex 6056 Hex 6057 Hex 3-10 F: Channel registration not possible since memory location in DEXDO3 interface is too small. R: Channel is not switched to the transmit / receive operation. A: Implement a memory reorganization (using CDV connector at the corresponding central block) in order to remove possible channel corpses; Reduce the link partners in the application. EQ: SDZ_FRW_ZC_MEM_KURZ EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 605A Hex F: 605B Hex F: 605C Hex F: 605D Hex F: 605E Hex F: Channel with the desired channel names found but channel registration check faulty because channel mode of the channel and the user are different. R: Channel is not switched to the transmit / receive operation. A: Check the desired channel modes of the link partner. EQ: SDZ_FRW_ZC_KAN_MOD_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Channel with the desired channel names found but channel registration check faulty because the user data structure of the channel and the user are different. R: Channel is not switched to the transmit / receive operation. A: Check the user data structures (connector types) of the link partner. EQ: SDZ_FRW_ZC_DATA_STR_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Channel with the desired channel names found but channel registration check faulty because the user data length of the channel and the user are different. R: Channel is not switched to the transmit / receive operation. A: Check the desired user data lengths of the link partner. EQ: SDZ_FRW_ZC_DATA_LEN_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Channel with the desired channel names found but channel registration check faulty because the utility type of the channel and the user are different. R: Channel is not switched to the transmit / receive operation. A: Check the user types of the link partner. EQ: SDZ_FRW_ZC_DIENSTTYP_ERR EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. Configuring error in the PROFIBUS DP (SS52) R: Channel is not released in the transmit/receive mode. A: Check the configuring; make sure that: Mode = Refresh or (for receivers) Multiple Utility type = Process data First character in the address stage 2 = "0" or "1" EQ: SDZ_FRW_ZC_CSL2A_ERR EM: ZCIN.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’, KFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-11 Communication Error Codes 605F Hex F: 6060 Hex F: 6061 Hex F: 6062 Hex F: 6063 Hex F: 3-12 Internal error in the PROFIBUS DP (SS52) R: Channel is not released in the transmit/receive mode. A: Inform Siemens AG. EQ: SDZ_FRW_ZC_VARTYP_ERR EM: ZCIN.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’, KFF (Only receiver) the acknowledge ‘‘Incorrect Transmit Address’’ was read from the channel. R: No connection to the link partner, because no remote partner can be accessed under this transmit address. A: Check the transmit address of the link partner. EQ: SDZ_QUIT_SEND_ADR_ERR _ EM: ZCRD.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Only transmit) the acknowledge ‘‘Incorrect Receive Address’’ was read from the channel. R: No connection to the link partner, since no remote partner can be accessed under this receive address. A: Check the receive address of the link partner. EQ: SDZ_QUIT_EMPF_ADR_ERR _ EM: ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Only for networks) The acknowledge ‘‘Data Block False’’ was read from the channel. R: The network could not connect to the last rack. A: Check that the utility types of the transmit and receive blocks concur with one another; Check that the desired data lengths of the transmit and receive blocks concur with one another; Check that the channel modes of the transmit and receive blocks concur with one another; Reduce the number of interface users for an end interface on CSH11 or CS7 boards. EQ: SDZ_QUIT_TRANSIT_NDB_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge "No resources" was read by the channel. R: No connect to link partner, since no resources are available. A: CSH11: Check the buffer dimensioning in the NML configuring and modify if necessary. SS52: No help EQ: SDZ_QUIT_N_RESOURCE _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Block dependant General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6064 Hex F: 6065 Hex F: 6066 Hex F: 6067 Hex F: The acknowledge ‘‘Type Mis-Match’’ was read from the channel. R: No connection to the link partner, since the channel type does not match to the link partner. A: Check the channel type of the utility block: Firmware is not permitted to synchronize itself as a receiver to the channel type multiple or as a transmitter to the channel type select. EQ: SDZ_QUIT_TYP_MISMATCH _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge ‘Impermissible Utility Type’’ was read from the channel. R: No connection to the link partner, since the utility type of the channel was faulty or not permitted by the link partner. A: Utilize a block, whose utility type is permitted by the link partner; for SINEC L2 DP only the utility type process data is permitted. EQ: SDZ_QUIT_ILLEGAL_DIENSTTYP _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge ‘‘CIP User Data Length does not match the Address Stage 2’’ was read from the channel. R: No connection to the link partner, since the required length of the user data and the address stage 2 are incompatible. A: Select another address stage; Adapt the size of the data to be transmitted in the address stage. EQ: SDZ_QUIT_NDL_N_ADR2 _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge "Incorrect address stage 1" was read by the channel. R: No connect to link partner, since the channel’s address stage 1 does not match the link partner. A: Check the address stage 1 value range. EQ: SDZ_QUIT_ADR1_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Block dependant General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-13 Communication Error Codes 6068 Hex F: 6069 Hex F: 606A Hex F: 606B Hex F: 606C Hex F: 3-14 The acknowledge "Incorrect address stage 2" was read by the channel. R: No connect to link partner, since the channel’s address stage 2 does not match the link partner. A: Check the address stage 2 value range. USS: Check whether the station number has been entered into thering buffer or whether a broadcast channel to a device has been registered or whether an address stage 2 is configured EQ: SDZ_QUIT_ADR2_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Block dependant The acknowledge ‘‘CIP User Data Length does not match the User Data length of the VARANM Area’’ was read from the channel. R: SW or HW error. A: Contact Siemens AG. EQ: SDZ_QUIT_NDL_N_VARANM _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge ‘‘Transmitter Already Registered’’ was read from the channel. R: No connection to the link partner, since a transmitter is already registered and a maximum of one is permitted. A: Remove a transmitter. EQ: SDZ_QUIT_SEND_ANM _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge ‘‘Receiver Already Registered’’ was read from the channel. R: No connection to the link partner, since a receiver is already registered and a maximum of one is permitted. A: Remove a receiver. EQ: SDZ_QUIT_EMPF_ANM _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. The acknowledge ‘‘Invalid Data Format in VARANM Area’’ was read from the channel. R: No connection to the link partner, since the data format to be transmitted is not permitted. A: Check permissible data formats according to the table. EQ: SDZ_QUIT_DATA_FORMAT _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 606D Hex F: 606E Hex F: 606F Hex F: 6070 Hex F: The acknowledge ‘‘VARANM Area too Large’’ was read from the channel. R: SW or HW error. A: Contact Siemens AG. EQ: SDZ_QUIT_VARANM_LEN_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Only SINEC L2 DP) ET200U: The acknowledge ‘‘Board Pulled’’ was read from the channel. ET200K: The acknowledge ‘‘Port Faulty’’ was read from the channel. R: Bit 3 of the station diagnostics (byte 0 of the slave station) was set. A: Check allocated station. EQ: SDZ_QUIT_BG_AUS_PORT_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Only SINEC L2 DP) ET200U: The acknowledge ‘‘Incorrect Address ID’’ was read from the channel. ET200K: The acknowledge ‘‘Parameter Fault’’ was read from the channel. R: Bit 2 of the station diagnostics (byte 0 of the slave station) was set. A: Check station parameters. EQ: SDZ_QUIT_ADR_ERR_PARA_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. (Only SINEC-L2-DP) The acknowledge "Configuring error: Station type does not match IM318B" was read from the channel. R: No data exchange takes place via this channel with the corresponding Slave-Station. A: COM ET200: Check configuration of this station. EQ: SDZ_QUIT_PARA_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’ KFF (6070, pointer to configured name, Suppl. info dependent upon message generating block) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-15 Communication Error Codes 6071 Hex F: 6072 Hex F: 6073 Hex F: 6074 Hex F: 3-16 The acknowledge "maximum number of channel connects reached, no further channels possible" was read from the channel. R: No data exchange takes place via this channel with the corresponding link partner. A: Reduce number of transmit / receive function blocks EQ: SDZ_QUIT_MAX_CHANNEL _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’ KFF (6071, pointer to configured name, Suppl. info dependent upon message generating block) The acknowledge "incorrect mode (mode of operation)" was read from the channel. R: No data exchange takes place via this channel with the corresponding link partner. A: Check mode (mode of operation: Refresh, Handshake, Select, Multiple) EQ: SDZ_QUIT_MODE_ERR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’ KFF (6072, pointer to configured name, Suppl. info dependent upon message generating block) (Only SINEC-L2-DP) Channel’s user data length does not match the COM ET200 configuring. R: No data exchange to the corresponding link partner takes place via this channel. A: SIMADYN D : Match the amount of data to be transmitted; COM ET200: modify configuration. EQ: SDZ_QUIT_NDL_N_AWI _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Block dependant (Only SINEC-L2-DP) Channel does not match COM ET200 configuring (Address Stage1, Station Number) R: No data exchange to the corresponding link partner takes place via this channel. A: Match the address stage1 and station number in COM ET200. EQ: SDZ_QUIT_N_STAT_ADR1 _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: Block dependant General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6075 Hex 6076 Hex 6077 Hex 6078 Hex to 60BE Hex 60BE Hex 60BF Hex F: (Only SINEC L2 DP) The acknowledge ‘‘No AWI Data Configured for the Channel’’ was read from the channel. R: No connection to the link partner, since the AWI data area does not exist in the link partner. A: SIMADYN D: Remove transmit / receive FB; COM ET200: Configure input / output bytes for station. EQ: SDZ_QUIT_NO_AWI_DATA _ EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. F: The acknowledge "Receive telegram is larger than the available user data buffer" was read from the channel. R: No data exchange takes place via this channel with the corresponding link partner. A: Check configuring; ensure that the maximum transmit data length does not exceed the receive data length. EQ: SDZ_QUIT_NDL_ZUKL _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’ KFF (6076, pointer to configured name, Suppl. info dependent upon message generating block) F: User data length too large for the link. R: No data exchange to the corresponding link partner takes place via this channel. A: Reduce the amount of user data EQ: SDZ_QUIT_NDL_ZUGR _ EM: ZCRD.CSF, ZCWR.CSF AM: Block that invokes the function zc_start AA: 7-Seg ’C’ KFF (6077, pointer to configured name, Additional information dependant upon message generating block) not utilized. F: F: Unknown acknowledge value detected by the channel management. R: SW or HW error. A: Contact Siemens AG. EQ: SDZ.SD EM: ZCRD.CSF, ZCWR.CSF AM: Block invoking the function zc_start. AA: Block dependent. Unknown status flag in the ZCDAT structure. R: The channel is disabled. A: Contact Siemens AG. EQ: SDZ.SD EM: ZCIN.CSF AM: Block invoking the function zc_start. AA: Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-17 Communication Error Codes 3.2.2 Data Interface Initialization Errors (IB Errors) 60E0 Hex F: 60E1 Hex F: 60E2 Hex F: 60E3 Hex F: The IB could not create the PN local KDR list. Exact cause of error, see section Error Supplementary Code bsspvw_info. R: Processor board is not initialized. A: Contact Siemens AG. EQ: ZG_ERR_NUM_KDR_LIST_N_EIN EM: ZG.CSF AM: ZG.CSF AA: 7-Seg. ‘I’. The IB could not create the PN local ZCVWL list. Exact cause of error, see section Error Supplementary Code bsspvw_info. R: Processor board is not initialized. A: Contact Siemens AG. EQ: ZG_ERR_NUM_ZCVWL_LIST_N_EIN EM: ZG.CSF AM: ZG.CSF AA: 7-Seg. ‘I’. The IB could not create the PN local ZINI list. Exact cause of error, see section Error Supplementary Code bsspvw_info. R: Processor board is not initialized. A: Contact Siemens AG. EQ: ZG_ERR_NUM_ZINI_LIST_N_EIN EM: ZG.CSF AM: ZG.CSF AA: 7-Seg. ‘I’. The IB could not create the PN local list. Exact cause of error, see section Error Supplementary Code bsspvw_info. R: Processor board is not initialized. A: Contact Siemens AG. EQ: ZG_ERR_NUM_CIP16K_LIST_N_EIN EM: ZG.CSF AM: ZG.CSF AA: 7-Seg. ‘I’. 3.2.3 Network 6100 Hex 3-18 F: Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the @NMC initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NMC_ZUGR_KDR EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6101 Hex F: 6102 Hex F: 6103 Hex F: 6104 Hex F: 6105 Hex F: 6106 Hex F: 6107 Hex F: Faulty operating status. R: Abort the @NMC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NMC_BZS_ERR EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. Initialization error. R: Abort the @NMC initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NMC_INI EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. General @NMC group error. R: Abort the @NMC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NMC_INT_ERR EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. Channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: Abort the @NMC normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NMC_DREI_APFEL EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. No longer sufficient RAM memory available . Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @NMC normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NMC_NO_MEM EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. Error in function zbin_komdat. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the @NMC normal mode. A: See section Error Supplementary Code zbin_komdat. EQ: ZF_ERR_NUM_NMC_ZBIN_KOMDAT EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. Invoking the sub-task not successful. R: Abort the @NMC initialization. A: Check the configured sampling time. EQ: ZF_ERR_NUM_NMC_INI_SUB_TASK EM: _NMC.CSF AM: _NMC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-19 Communication Error Codes 6108 Hex to 611E Hex 6120 Hex not utilized. 6121 Hex F: 6122 Hex F: 6123 Hex F: 6124 Hex F: 6125 Hex F: 3-20 F: No @NMC configured or correctly initialized. R: Abort the NRI initialization. A: Correct @NMC configuring. EQ: ZF_ERR_NUM_NRI_N_NMC EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ’C’; YTS Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the NRI initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NRI_N_KDR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ’C’; YTS. Faulty ISA connector. R: Abort the NRI initialization. A: Correctly configured the ISA connector. EQ: ZF_ERR_NUM_NRI_ISA_ERR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. RAM memory assigning for NMC-NRI element not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_ELEM EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. RAM memory assigning for NMC-NRI buffer not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_BUF EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. RAM memory assigning for NRI-NMC buffer not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_MEM_NRI_NMC_BUF EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6126 Hex F: 6127 Hex F: 6128 Hex F: 6129 Hex F: 612A Hex F: 612C Hex F: 612E Hex F: RAM memory assigning for RIL not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_MEM_RIL EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS Unknown operating status. R: Abort the NRI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NRI_BZS_ERR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ’C’; YTS Configured data interface not found. R: Abort the NRI normal mode. A: Correctly configure the CTS connector. EQ: ZF_ERR_NUM_NRI_N_CIP EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ’C’; YTS. Channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: Abort the NRI normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NRI_KAN_ERR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. Error during channel search interface channel Read. R: Abort the NRI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NRI_N_IK1_SUCHE EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS Error during channel search interface channel Write. R: Abort the NRI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NRI_N_IK2_SUCHE EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. RAM memory assigning for VARANM area IKR not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_VARANM_IKR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-21 Communication Error Codes 612F Hex F: 6130 Hex 6131 Hex 6132 Hex 6133 Hex 6134 Hex to 6135 Hex 6136 Hex 3-22 RAM memory assigning for KOMDAT area IKR not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_KOMDAT_IKW EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. not utilized. F: RAM memory assigning for VARANM area IKW not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_VARANM_IKW EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. F: RAM memory assigning for KOMDAT area IKW not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_KOMDAT_IKW EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. F: RAM memory assigning for intermediate buffer IKW not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NRI normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NRI_N_ZW_IKW EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. not utilized. F: The function zbak_kop_typ could not find the ZINI list; or the function zbak_kop_typ could not find the desired CIP entry in the ZINI lists; or the function return value of the function zbak_kop_typ is unknown. R: Abort the NRI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NRI_ZBAK_KOP_TYP_FRW_ERR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6137 Hex F: The link type is not supported. R: Abort the NRI normal mode. A: Configure NRI-FB on a board, that has network capability. EQ: ZF_ERR_NUM_NRI_KOP_TYP_ERR EM: NRI.CSF AM: NRI.CSF AA: 7-Seg. ‘C’; YTS. not utilized. 6138 Hex to 613F Hex 6140 Hex F: 6141 Hex F: 6142 Hex F: 6143 Hex F: 6144 Hex F: 6145 Hex No @NMC initialized. R: Abort the NSI initialization. A: Correctly configure @NMC. EQ: ZF_ERR_NUM_NSI_N_NMC EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. No NTC initialized. R: Abort the NSI initialization. A: Correctly configure NTC. EQ: ZF_ERR_NUM_NSI_N_NTC EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. No NET list exists. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the NSI initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NSI_N_NET EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. Faulty operating state. R: Abort the NSI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NSI_N_DEF EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. Faulty return value of the zc_start function. Exact cause see section Data Interface Access Mechanisms. R: Abort the NSI normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NSI_ZC EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-23 Communication Error Codes 6146 Hex F: 6147 Hex 6148 Hex 6149 Hex 614A Hex 614B Hex to 6161 Hex 6162 Hex 3-24 No global list KDR exists. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the NSI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NSI_N_KDR EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ’C’; YTS not utilized. F: No back-up list exists. R: Abort the NSI initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NSI_BCK_LIST EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. F: RAM memory assigning not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NSI initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NSI_N_RAM EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS. F: Error in function zbin_komdat. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the NSI initialization. A: See section Error Supplementary Code zbin_komdat. EQ: ZF_ERR_NUM_NSI_ZBIN EM: NSI.CSF AM: NSI.CSF AA: 7-Seg. ‘C’; YTS not utilized. F: Faulty return value for the function zc_start. Exact cause see section Data Interface Access Mechanisms. R: Abort the NSL normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NSL_N_DEF EM: NSL.CSF AM: NSL.CSF AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6163 Hex 6164 Hex 6165 Hex to 6166Hex 6167 Hex 6168 Hex 6169 Hex to 617F Hex 6180 Hex 6181 Hex F: Channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: Abort the NSL normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NSL_ZC EM: NSL.CSF AM: NSL.CSF AA: 7-Seg. ‘C’; YTS. F: Faulty operating status. R: Abort the NSL normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NSL_BZS EM: NSL.CSF AM: NSL.CSF AA: 7-Seg. ’C’; YTS not utilized. F: Insufficient RAM memory available. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NSL initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NSL_N_RAM EM: NSL.CSF AM: NSL.CSF AA: 7-Seg. ‘C’; YTS. F: Error in the function zbin_komdat. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the NSL initialization. A: See section Error Supplementary Code zbin_komdat. EQ: ZF_ERR_NUM_NSL_ZBIN EM: NSL.CSF AM: NSL.CSF AA: 7-Seg. ’C’; YTS. not utilized. F: F: No function block NTD correctly initialized. R: Abort the NTC normal mode. A: Correctly configure function block NTD. EQ: ZF_ERR_NUM_NTC_NO_NTD EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. No data interface for processing received from @NMC. R: Abort the NTC normal mode. A: This function block does not need to be configured. EQ: ZF_ERR_NUM_NTC_GOT_NO_CIP EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-25 Communication Error Codes 6182 Hex F: 6183 Hex F: 6184 Hex F: 6185 Hex F: 6186 Hex 6187 Hex F: 6188 Hex F: 6189 Hex F: 3-26 The @NMC is not (no longer) active. R: Abort the NTC normal mode. A: Analyze the @NMC error message. EQ: ZF_ERR_NUM_NTC_NMC_OFF EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Faulty operating status. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_BZS_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Error while accessing the global list KDR. R: Abort the NTC initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZUGR_KDR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS Multiple configuring NTC. R: Abort the NTC initialization. A: The function block NTC does not need to be configured. EQ: ZF_ERR_NUM_NTC_MEHRFACHPROJ EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. not utilized. Insufficient RAM memory available. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NTC normal mode. A: Create available RAM memory. EQ: ZF_ERR_NUM_NTC_NO_MEM EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Insufficient memory available on MM11. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NTC initialization. A: Create available memory. EQ: ZF_ERR_NUM_NTC_NO_NET_MEM EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Unknown channel mode. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_KANALMODUS_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 618A Hex F: 618B Hex F: 618C Hex F: 618D Hex F: 618E Hex F: 618F Hex F: Unknown channel status. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_KAN_STATUS EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. An invalid value is to be written into a status byte. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_KAN_FLAGS_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Invalid transit ID read from the channel. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_TRANSIT_KENNUNG_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Invalid transit direction of the channel determined. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_TRANSIT_RICHTUNG_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. Channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: Abort the NTC normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NTC_DREI_APFEL EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. The function znak_transit_kennung could not find a channel with the desired register number; or the return value of the function znak_transit_kennung is unknown. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KENNUNG_FR W_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-27 Communication Error Codes 6190 Hex F: 6191 Hex F: 6192 Hex F: 6193 Hex F: 6194 Hex F: 3-28 The function znei_transit_kennung could not find a channel with the desired register number; or the function znei_transit_kennung determined that the semaphore for the transit ID in the channel is disabled; or the return value of the function znei_transit_kennung is unknown. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNEI_TRANSIT_KENNUNG_FR W_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. The function znak_prk_aktiv determined that the desired link is not a rack link; or the return value of the function znak_prk_aktiv is unknown. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNAK_PRK_AKTIV_FRW_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. Unknown return value of the function znei_kanal_komdat. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNEI_KANAL_KOMDAT_FRW_E RR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Unknown return value of the function znak_dexdo_zugriff. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNAK_DEXDO_ZUGRIFF_FRW_ ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. The function znak_varanm_laenge could not find a channel with the desired registered number; or the return value of the function znak_varanm_laenge is unknown. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNAK_VARANM_LAENGE_FRW _ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6195 Hex F: 6196 Hex F: 6197 Hex F: 6198 Hex F: 6199 Hex F: 619A Hex F: Unknown return value of the function znak_transit_kanal. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KANAL_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. Faulty return value of the function zc_start. Exact cause see section Data Interface Access Mechanisms. R: Abort the NTC normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NTC_ZC_START_FRW_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Internal error. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_INT_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. Several transmitters / receivers for the same handshake / refresh channel. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_KAN_HR_ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ‘C’; YTS. The function zcei_kan_nam_loesch could not find a channel with the desired registered number; or the return value of the function zcei_kan_nam_loesch is unknown. R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZCEI_KAN_NAM_LOESCH_FRW _ERR EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. The function zcak_kanal_nummer_bestimmen could not find a channel with the desired registered number; or the return zcak_kanal_nr_bestimmen is unknown. value of the function R: Abort the NTC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTC_ZCAK_KAN_NR_BEST_FRW_ER R EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-29 Communication Error Codes 619B Hex to 619F Hex 61A0 Hex 61A1 Hex 61A2 Hex 61A3 Hex 614A Hex to 61A7 Hex 61A8 Hex 61A9 Hex 3-30 not utilized. F: No function block NTC active. R: Abort the NTD initialization. A: Correctly configure the function block NTC. EQ: ZF_ERR_NUM_NTD_NO_NTC EM: NTD.CSF AM: NTD.CSF AA: 7-Seg. ’C’; YTS. F: Faulty return value of the function zc_start. Exact cause see section Data Interface Access Mechanisms. R: Abort the NTD normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_NTD_KAN_ERR EM: NTD.CSF AM: NTD.CSF AA: 7-Seg. ’C’; YTS. F: Too little RAM memory. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the NTD initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_NTD_N_MEM EM: NTD.CSF AM: NTD.CSF AA: 7-Seg. ‘C’; YTS. F: Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the NTD initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTD_N_KDR EM: NTD.CSF AM: NTD.CSF AA: 7-Seg. ‘C’; YTS. not utilized. F: F: Copy relationship failed (whilst reading the source channel). R: Copy relationship is no longer processed. The block remains enabled. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTD_STS_ERR_QUELLE EM: NTD.CSF AM: NTD.CSF AA: YTS. Copy relationship failed (whilst writing to the destination channel). R: Copy relationship is no longer processed. The block remains enabled. A: Contact Siemens AG. EQ: ZF_ERR_NUM_NTD_STS_ERR_ZIEL EM: NTD.CSF AM: NTD.CSF AA: YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 61AA Hex F: 61AB Hex F: Incorrect function return value. R: NTD is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_NTD_N_CIP EM: NTD.CSF AM: NTD.CSF AA: 7-Seg. ’C’ Too many data interfaces (CIP). R: NTC is disabled A: Reduce the number of data interfaces (fewer MM11/MM4 or CS11/CS21) EQ: ZF_ERR_NUM_NTC_CIP_ANZ EM: NTC.CSF AM: NTC.CSF AA: 7-Seg. ’C’ 3.2.4 Service 6200 Hex F: 6201 Hex F: 6202 Hex F: 6203 Hex F: General initialization error. Exact cause see section Error Supplementary Code bsspvw_geme. zbin_komdat and R: Abort the initialization, SER block not operating. A: Contact Siemens AG. EQ: Z_ERR_NUM_SER_INIT_ERR EM: zdsest.csf AM: zdsest.csf AA: 7-Seg. ‘C’; YTS. Initialization errors: insufficient RAM memory available. Exact cause see section Error Supplementary Code bsspvw_geme. zbin_komdat and R: Abort the initialization, SER block not operating. A: Create available RAM memory. EQ: Z_ERR_NUM_SER_INIT_NO_MEM EM: zdsest.csf AM: zdsest.csf AA: 7-Seg. ’C’; YTS. Initialization error: request channel cannot be initialized. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the initialization, SER block not operating. A: Check specifications at the CTS and US connectors. EQ: Z_ERR_NUM_SER_INIT_KOMDAT_RD EM: zdsest.csf AM: zdsest.csf AA: 7-Seg. ’C’; YTS. Initialization error: reply channel cannot be initialized. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the initialization, SER block not operating. A: Check specifications at the CTS and US connectors. EQ: Z_ERR_NUM_SER_INIT_KOMDAT_WR EM: zdsest.csf AM: zdsest.csf AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-31 Communication Error Codes 6204 Hex F: 6205 Hex F: 6206 Hex F: Initialization error: sub-task not created. R: SER block cannot operate. A: Check configured sampling times. EQ: Z_ERR_NUM_SER_INIT_SUB_TASK EM: zdsest.csf AM: zdsest.csf AA: 7-Seg. ’C’; YTS. Request channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: SER block is disabled. A: See section Data Interface Access Mechanisms. EQ: Z_ERR_NUM_SER_KAN_ERR_RD EM: zdsekrd.csf AM: zdsekrd.csf AA: 7-Seg. ‘C’; YTS. Reply channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: SER block is disabled. A: See section Data Interface Access Mechanisms. EQ: Z_ERR_NUM_SER_KAN_ERR_WR EM: zdsekwr.csf AM: zdsekwr.csf AA: 7-Seg. ‘C’; YTS. 3.2.4.1 Display 6281 Hex F: 6282 Hex F: 6283 Hex F: 3-32 Configuring FB type @DIS0R, connector DIS: Multiple configuring of display system with the same name. R: Block is disabled. A: Enter correct specification at connector DIS. EQ: Z_ERR_NUM_DIS_MEHRFACH EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring FB type @DIS0R: Invalid sampling time. R: Block is disabled. A: Configure @DIS0R with valid sampling time (30ms <= t <= 300ms) EQ: Z_ERR_NUM_DIS_ABTASTZEIT EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring FB type @DIS0R or DISxy, connector ST1 and ST2: No display station specified. R: Block is disabled. A: Specification at connector ST1 or ST2 not equal to zero. EQ: Z_ERR_NUM_DIS_NOSTATION EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6284 Hex F: 6285 Hex F: 6286 Hex F: 6287 Hex F: 6288 Hex F: Configuring @DIS0T or DISxy, connector DIS: Associated central block @DIS0R or @DIS0T is not configured. R: Block is disabled. A: Configure block type @DIS0R and @DIS0T with the same specification at connector DIS. EQ: Z_ERR_NUM_DIS_NO_ZB EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring @DIS0T or DISxy, connector DIS: Associated central block @DIS0R is not configured. R: Block is disabled. A: Configure block type @DIS0R with the same specification at connector DIS. EQ: Z_ERR_NUM_DIS_NO_DIS EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring @DIS0T or DISxy: Sampling time does not match the associated @DIS0R. R: Block is disabled. A: Configure block with the same sampling time as @DIS0R. EQ: Z_ERR_NUM_DIS_AKT_AUFGABE EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring DISA4, connector Y or DISS4, connector X: Type switching to V4 is not permitted. R: Block is disabled. A: Set different connector type. EQ: Z_ERR_NUM_DIS_V4 EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Configuring DISxy, connector ST1 and ST2: Configured stations are not all initialized by the central block @DIS0R. R: Block is disabled. A: Only specify those stations at ST1, ST2, that are also specified at @DIS0R. EQ: Z_ERR_NUM_DIS_STA_NOZB EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-33 Communication Error Codes 6289 Hex F: 628A Hex F: 628B Hex F: 6290 Hex F: 6291 Hex F: 3-34 Configuring DISx, connector KEY: Process data number is already defined (for a display station). R: Block is disabled. A: Select other process data number or check specification at ST1, ST2. EQ: Z_ERR_NUM_DIS_PZD_DOP EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address of the display station) Configuring DIS1x, connector KEY: Binary value number is already defined (for a display station). R: Block is disabled. A: Select other binary value number or check specification at ST1, ST2. EQ: Z_ERR_NUM_DIS_BIN_DOP EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address of the display station) Configuring DISxy, connector KEY: Invalid value configured. R: Block is disabled. A: Configure valid value (review block description). EQ: Z_ERR_NUM_DIS_KEY EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Internal: Error during memory create. Precise cause: review section Error suppl. code bsspvw_geme. R: Block is disabled. A: Reduce the RAM requirements in the application. EQ: Z_ERR_NUM_DIS_GEME EM: ZDDI.CSF, function BSSPVW_GEME AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of BSSPVW_GEME) Internal: Error during Save-memory create for setpoint. Precise cause: review section Error suppl. code bsspvw_geme. R: Block is disabled. A: Reduce the SAVE requirements in the application. EQ: Z_ERR_NUM_DIS_GEMESAV EM: ZDDI.CSF, function BSSPVW_GEME AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of BSSPVW_GEME) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6292 Hex F: 6293 Hex F: 6294 Hex F: 6295 Hex F: 6296 Hex F: 6297 Hex F: 6298 Hex F: Internal: Error during SAVE-pointer create for setpoint. R: Block is disabled. A: Reduce the SAVE requirements in the application. EQ: Z_ERR_NUM_DIS_SAVPUF EM: ZDDI.CSF, function BSSAVPUF_GEME AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Internal: KDR list not found R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_KDR EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Internal: Error during sampling time calculation R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_AMPI_TN EM: ZDDI.CSF, function AMPI_TN AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI_TN) Internal: Error during receive channel initialization. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_KOMDAT_EMPF EM: ZDDI.CSF, function ZBIN_KOMDAT AM: ZDDI.CSF AA: YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl. code = FRW of ZBIN_KOMDAT) Internal: Error during transmit channel initialization. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_KOMDAT_SEND EM: ZDDI.CSF, function ZBIN_KOMDAT AM: ZDDI.CSF AA: YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl. code = FRW of ZBIN_KOMDAT) Internal: Implementation error. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_IMPLEM EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Internal: Implementation error R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_FORMAT EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-35 Communication Error Codes 6299 Hex F: 629A Hex F: 629B Hex F: 62A0 Hex F: 62A1 Hex F: 62A2 Hex F: 3-36 Internal: (P32) Error during connector description fetch. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_BESCHR EM: ZDDI.CSF, function AMPI/AFPI AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI/AFPI function) Internal: (P16) Segment pointer fetch unsuccessful. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_BSBI_SEG EM: ZDDI.CSF, function BSBI_SEG AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Internal: (P16) Dimension text fetch unsuccessful. R: Block is disabled. A: Inform Siemens AG. EQ: Z_ERR_NUM_DIS_BSBI_DIM EM: ZDDI.CSF, function BSBI_DIM AM: ZDDI.CSF AA: YTS; 7-Seg. ’C’, KFF Dialog unit: Incorrect request ID in the telegram. R: Transmit an error telegram to the dialog unit. A: Check dialog unit. EQ: Z_ERR_NUM_DIS_AUFKENN EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS, YAC = Station address; Error telegram: Error class, (Error number = Request ID) Dialog unit: Incorrect telegram length. R: Transmit an error telegram to the dialog unit. A: Check dialog unit. EQ: Z_ERR_NUM_DIS_AUFLGE EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS, YAC = Station address; Error telegram: Error class, (Error number = Telegram length) Dialog unit: Incorrect process data number requested. R: Transmit an error telegram to the dialog unit. A: Check dialog unit. EQ: Z_ERR_NUM_DIS_PZDNR EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS, YAC = Station address; Error telegram: Error class, (Error number = PZD number) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes F: Dialog unit: Incorrect binary value number requested. R: Transmit an error telegram to the dialog unit. A: Check dialog unit. EQ: Z_ERR_NUM_DIS_BINNR EM: ZDDI.CSF AM: ZDDI.CSF AA: YTS, YAC = Station address; Error telegram: Error class, (Error number = BIN number) 62A4 Hex F: 62A5 Hex 62A6 Hex F: FB-DIAL2A: Impermissible specification at connector ST1 or ST2. R: Block disables. A: Correct specification: 3<=ST1<=ST2<=123. EQ: Z_ERR_NUM_DPDIAG_ST1_ST8_NZUG EM: DIAL2A.CSF AM: DIAL2A.CSF AA: 7-Seg ’C’, KFF FB-DIAL2A: Too little memory (RAM) available. R: Block disables. A: Reduce configuring. EQ: Z_ERR_NUM_DPDIAG_N_SLAVE_LI Z_ERR_NUM_DPDIAG_N_ZWI_PU Z_ERR_NUM_DPDIAG_N_VARANM_BER EM: DIAL2A.CSF AM: DIAL2A.CSF AA: 7-Seg ’C’, KFF FB-@SYL2A: Impermissible specification at connector SEL. R: Block disables. A: Correct specification at connector SEL: 1<=SEL<=8. EQ: Z_ERR_NUM_DPSYNC_SEL_NZUG EM: @SYL2A.CSF AM: @SYL2A.CSF AA: 7-Seg ’C’, KFF FB-@SYL2A: Impermissible specification at connector CNX. R: Block disables. A: Correct specification at connector CNX: CNX>0. EQ: Z_ERR_NUM_DPSYNC_UNTERS_NZUG EM: @SYL2A.CSF AM: @SYL2A.CSF AA: 7-Seg ’C’, KFF FB-@SYL2A: Impermissible specification at connector CTS: Board does not exist or not a CS7. R: Block disables. A: Correct specification at connector CTS. EQ: Z_ERR_NUM_DPSYNC_CIP3_NVH EM: @SYL2A.CSF AM: @SYL2A.CSF AA: 7-Seg ’C’, KFF 62A3 Hex 3.2.4.2 Specific SS52 62A7 Hex 62A8 Hex F: 62A9 Hex F: 62AA Hex F: General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-37 Communication Error Codes 62AB Hex F: 62AC Hex F: 62AD Hex F: FB-@SYL2A: Impermissible specification at connector CTS: Only CS7/SS52 permitted with FB-@CSL2A. R: Block disables. A: Correct specification at connector CTS. EQ: Z_ERR_NUM_DPSYNC_KOP_NZUG EM: @SYL2A.CSF AM: @SYL2A.CSF AA: 7-Seg ’C’, KFF FB-@SYL2A: Impermissible multiple configuring. R: Block disables. A: Remove block. EQ: Z_ERR_NUM_DPSYNC_FB_MEHRFACH EM: @SYL2A.CSF AM: @SYL2A.CSF AA: 7-Seg ’C’, KFF FB-@SYL2A: Waiting for SS52 firmware. R: Wait. A: SS52 installed? EQ: Z_ERR_NUM_DPSYNC_SS52_WAIT EM: @SYL2A.CSF AM: @SYL2A.CSF AA: Warning 3.2.5 Process Data 6000 Hex to 60BF Hex 6310 Hex see section Data Interface Access Mechanisms. 6311 Hex F: 3-38 F: RAM memory assigning for VARANM area not possible. Exact error cause see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: Z_FRW_ZDPD_N_MEM_VARANM EM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, ZDPD.CSF AM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, CCC4.CSF, CDC4.CSF AA: 7-Seg. ‘C’; YEV. Fehler bei Auswertung der Adreßparameter (Eingang AT, AR). Genaue Fehlerursache siehe Abschnitt Fehlerzusatzcode zbin_kombat. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: Z_FRW_ZDPD_INIT_KOMDAT_ERR EM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, ZDPD.CSF AM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, CCC4.CSF, CDC4.CSF AA: 7-Seg. `C'; YEV. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6312 Hex F: 6313 Hex to 631E Hex 631F Hex F: 6320 Hex 6321 Hex 6322 Hex 6323 Hex 6324 Hex to 631F Hex Specification at the MOD connector faulty. R: Block reverts to the dead status. A: Correct the specification at the MOD connector, only the H, R, S or M letters are permissible. EQ: Z_FRW_ZDPD_INIT_KOMDAT_ERR EM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, ZDPD.CSF AM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, CCC4.CSF, CDC4.CSF AA: 7-Seg. ‘C’; YEV. utilized for internal purposes. Unknown function return value of the function zc_start. R: Block reverts to the dead status. A: Contact Siemens AG. EQ: Z_FRW_ZDPD_UNDEF EM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, CCC4.CSF, CDC4.CSF AM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF, CCC4.CSF, CDC4.CSF AA: 7-Seg. ‘C’; YEV. F: RAM memory assigning for reference list not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CTV_N_MEM_REF_LISTE EM: _CTV.CSF, CTV.CSF AM: _CTV.CSF, CTV.CSF AA: 7-Seg. ‘C’; YEV. F: RAM memory assigning for reference list not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CRV_N_MEM_REF_LISTE EM: _CRV.CSF, CRV.CSF AM: _CRV.CSF, CRV.CSF AA: 7-Seg. ‘C’; YEV. F: Reference list no found; no virtual connection configured. R: Block reverts to the dead status. A: Check the virtual connection at the AT connector. EQ: ZF_ERR_NUM_CTV_N_REF_LISTE EM: _CTV.CSF, CTV.CSF AM: _CTV.CSF, CTV.CSF AA: 7-Seg. ‘C’; YEV. F: Reference list no found; no virtual connection configured. R: Block reverts to the dead status. A: Check the virtual connection at the AR connector. EQ: ZF_ERR_NUM_CRV_N_REF_LISTE EM: _CRV.CSF, CRV.CSF AM: _CRV.CSF, CRV.CSF AA: 7-Seg. ‘C’; YEV. utilized for internal purposes. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-39 Communication Error Codes 6330 Hex F: 6331 Hex F: 6332 Hex F: 6333 Hex F: 6334 Hex F: 3-40 RAM memory assigning for intermediate buffer not possible. Exact error cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CTV_N_MEM_ZW EM: _CTV.CSF, CTV.CSF AM: _CTV.CSF, CTV.CSF AA: 7-Seg. ‘C’; YEV. RAM memory assigning for intermediate buffer not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CRV_N_MEM_ZW EM: _CRV.CSF, CRV.CSF AM: _CRV.CSF, CRV.CSF AA: 7-Seg. ‘C’; YEV. RAM memory assigning for intermediate buffer not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CCC4_N_MEM_ZW EM: CCC4.CSF AM: CCC4.CSF AA: 7-Seg. ‘C’; YEV. RAM memory assigning for intermediate buffer not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Block reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CDC4_N_MEM_ZW EM: CDC4.CSF AM: CDC4.CSF AA: 7-Seg. ‘C’; YEV. unknown connector type during evaluation of the return value from function zbak_kon_typ_wandel R: Block reverts to the neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_CRV_CTV_KON_N_KENN EM: ZBAK.CSF AM: _CRV.CSF, _CTV.CSF, CRV.CSF, CTV.CSF AA: 7-Seg. ’C’; KFF (6334,pointer to configured name,0) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.6 Message System 6400 Hex F: 6401 Hex F: 6402 Hex F: 6403 Hex F: 6404 Hex F: 6405 Hex F: Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the MSI initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSI_N_KDR EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ‘C’; No central block @MSC configured. R: Abort the MSI initialization. A: Configure central block @MSC. EQ: ZF_ERR_NUM_MSI_N_MSC EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ’C’; RAM memory assigning not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the MSI initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_MSI_N_MEM EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ’C’; KOMDAT area cannot be initialized. Exact cause see section Error Supplementary Code zbin_komdat. R: Abort the MSI initialization. A: See section Error Supplementary Code zbin_komdat. EQ: ZF_ERR_NUM_MSI_KOMDAT_INIT EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ’C’; Channel continuously faulty. Exact cause see section Data Interface Access Mechanisms. R: Abort the MSI normal mode. A: See section Data Interface Access Mechanisms. EQ: ZF_ERR_NUM_MSI_KAN_ERR EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ’C’; Faulty operating status. R: Abort the MSI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSI_BZS_ERR EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ‘C’; General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-41 Communication Error Codes 6406 Hex F: 6407 Hex F: 6408 Hex F: 6409 Hex F: 640A Hex F: 640B Hex F: 3-42 Faulty message format. R: Abort the MSI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSI_MF_ERR EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ‘C’; Unknown return value of the function zc_start. R: Abort the MSI normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSI_ZC_START_FRW_ERR EM: MSI.CSF AM: MSI.CSF AA: 7-Seg. ‘C’; @MSC configured in incorrect sampling time. R: Abort the @MSC initialization. A: @MSC must be configured with the correct sampling time. EQ: ZF_ERR_NUM_MSC_TN_ERR EM: _MSC.CSF AM: @MSC AA: 7-Seg. ’C’; Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the @MSC initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSC_N_KDR EM: _MSC.CSF AM: @MSC AA: 7-Seg. ’C’; Multiple configuring of the @MSC. R: Abort the @MSC initialization. A: @MSC may only be configured once per rack. EQ: ZF_ERR_NUM_MSC_MEHR_PROJ EM: _MSC.CSF AM: @MSC AA: 7-Seg. ‘C’; Global list of the SAVE area not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the @MSC initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSC_N_SAVE EM: _MSC.CSF AM: @MSC AA: 7-Seg. ‘C’; General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6410 Hex Too little memory available in the SAVE area. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @MSC initialization. A: Create available SAVE memory. EQ: ZF_ERR_NUM_MSC_N_MEM_SAVE EM: _MSC.CSF AM: @MSC AA: 7-Seg. ‘C’; F: Too little memory for the message sequencing buffer. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @MSC initialization. A: Create available memory. EQ: ZF_ERR_NUM_MSC_N_MEM_MFP EM: _MSC.CSF AM: @MSC AA: 7-Seg. ’C’; F: Connector SAV of the @MSC can’t be changed online. R: Abort the @MSC initialization. A: Set connector SAV to initial value. Changes only in the configuring. EQ: ZF_ERR_NUM_MSC_INV_PROJ EM: _MSC.CSF AM: @MSC AA: 7-Seg. ’C’; F: No memory for the entry description system error. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @MSC initialization. A: Create available SAVE memory. EQ: ZF_ERR_NUM_MSC_N_MEM_EB_C EM: _MSC.CSF AM: _MSC.CSF AA: 7-Seg. ’C’; not utilized. 6411 Hex F: 6412 Hex F: 640C Hex 640D Hex 640E Hex 640F Hex F: No memory in RAM area for static intermediate buffer. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @MSC initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_MSC_N_KOM_ERROR EM: _MSC.CSF AM: _MSC.CSF AA: 7-Seg. ’C’; No message evaluation blocks configured. R: Abort the @MSC normal mode. A: Configure function blocks MSI. EQ: ZF_ERR_NUM_MSC_N_MA EM: _MSC.CSF AM: _MSC.CSF AA: 7-Seg. ’C’; General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-43 Communication Error Codes 6413 Hex F: 6414 Hex F: 6415 Hex F: 6416 Hex F: 3-44 Faulty operating status communication error evaluation. R: Abort the @MSC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSC_MZC_ERR EM: _MSC.CSF AM: _MSC.CSF AA: 7-Seg. ’C’; Faulty operating status. R: Abort the @MSC normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_MSC_BZS_ERR EM: _MSC.CSF AM: _MSC.CSF AA: 7-Seg. ’C’; Global list KDR not found. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the ME initialization. A: Contact Siemens AG. EQ: ZF_ERR_NUM_ME_N_KDR EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; No central block @MSC available. R: Abort the ME initialization. A: Configure central block @MSC. EQ: ZF_ERR_NUM_ME_N_MSC EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6417 Hex 6418 Hex 6419 Hex 641A Hex to 641F Hex F: Too little SAVE memory area for pointer. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the ME initialization. A: Create available SAVE memory. EQ: ZF_ERR_NUM_ME_N_MEM_SAVE EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; F: Too little SAVE memory for insertion description. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the ME initialization. A: Create available SAVE memory. EQ: ZF_ERR_NUM_ME_N_MEM_FB EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; F: Too little RAM memory for the static intermediate buffer. Exact cause see section Error Supplementary Code bsspvw_info. R: Abort the ME initialization. A: Create available RAM memory. EQ: ZF_ERR_NUM_ME_N_MEM_SP EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-45 Communication Error Codes 6420 Hex F: 6421 Hex F: Faulty operating status. R: Abort the ME normal mode. A: Contact Siemens AG. EQ: ZF_ERR_NUM_ME_BZS_ERR EM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; Faulty return value of a zdms function. R: Abort the block. A: Contact Siemens AG. EQ: ZF_ERR_NUM_ZDMS_FRW_ERR EM: _MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AM: _MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF, MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF, MESV4.CSF, MEDV4.CSF AA: 7-Seg. ’C’; 3.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace) 6500 Hex F: 6501 Hex F: 3-46 RAM memory assigning for reference list not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the block initialization. A: Restrict the memory area to the local RAM; Reduce configured value of the NTV connector. EQ: Z_ERR_NUM_TC_INI_NO_RAM_1 EM: ZDTR.CSF AM: @TCI , @TCP AA: 7-Seg. ’C’; YTS RAM memory assigning for the trace buffer not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the control block initialization. A: Restrict the memory area to the local RAM; Reduce configured value of the TBL connector. EQ: Z_ERR_NUM_TC_INI_NO_RAM_2 EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6502 Hex F: 6503 Hex F: 6504 Hex 6505 Hex 6506 Hex 6507 Hex 6508 Hex SAVE memory assigning for reference list not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the control block initialization. A: Restrict the memory area to the local SAVE area; Reduce configured value of the NTV connector. EQ: Z_ERR_NUM_TC_INI_NO_SAVE_1 EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. SAVE memory assigning for the trace buffer not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the @ control block initialization. A: Restrict the memory area to the local SAVE area; Reduce configured value of the TBL connector. EQ: Z_ERR_NUM_TC_INI_NO_SAVE_2 EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: RAM memory assigning for channel VARANM area not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the control block initialization. A: Restrict the memory area to the local RAM. EQ: Z_ERR_NUM_TC_INI_NO_RAM_3 EM: ZDTR.CSF, _TCI.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: RAM memory assigning for channel buffer area not possible. Exact cause see section Error Supplementary Code bsspvw_geme. R: Abort the control block initialization. A: Restrict the memory area to the local RAM. Reduce configured value of the NTV connector. EQ: Z_ERR_NUM_TC_INI_NO_RAM_4 EM: ZDTR.CSF, _TCI.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. is not utilized. F: Configured value at TBL connector is equal to zero. R: Abort the control block initialization. A: Configure value not equal to zero at the TBL connector. EQ: Z_ERR_NUM_TC_INI_BAD_TBL EM: ZDTR.CSF, TRCC2.CSF AM: @TCI, @TCP, TRCC2 AA: 7-Seg. ’C’; YTS. F: TRC ID at the control block multiply exists. R: Abort the control block initialization. A: Select new unique TRC ID. EQ: Z_ERR_NUM_TC_INI_TC_DUP EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-47 Communication Error Codes 6509 Hex 650A Hex 650B Hex 650C Hex 650D Hex 650E Hex 650F Hex 3-48 F: Global KDR list not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: Abort the control block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_NO_KDR EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: Global KOMM_ERROR list not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: Abort the control block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_NO_KOM EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ‘C’; YTS. F: KOMDAT area of the request channel was not correctly initialized. Exact cause of error see section Error Supplementary Code zbin_komdat. R: Abort the control block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_NO_KDB_1 EM: ZDTR.CSF AM: @TCI.CSF AA: 7-Seg. ‘C’; YTS. F: KOMDAT area of the reply channel was not correctly initialized. Exact cause of error see section Error Supplementary Code zbin_komdat. R: Abort the control block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_NO_KDB_2 EM: TCI.CSF, ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: SAVE area full. R: Abort the control block initialization. A: Restrict the memory area in the local SAVE area. EQ: Z_ERR_NUM_TC_INI_NO_SAVE_3 EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS F: List of the SAVE area not available. Exact cause of error see section Error Supplementary Code bsspvw_info. R: Abort the control block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_NO_SAVE_4 EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. is not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6510 Hex 6511 Hex 6512 Hex 6513 Hex 6514 Hex to 651F Hex 6520 Hex 6521 Hex 6522 Hex F: Error during channel access to request channel. Exact cause of error see section Data Interface Access Mechanisms. R: @TCI reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_ZP_CHA_IN EM: _TCI.CSF AM: @TCI AA: 7-Seg. ’C’; YTS. F: Error during channel access to reply channel. Exact cause of error see section Data Interface Access Mechanisms. R: @TCI reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_ZP_CHA_OUT EM: ZDTR.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: No acquisition block has been initialized. R: Acquisition block reverts to the dead status. A: Configure acquisition block with corresponding TRC ID. EQ: Z_ERR_NUM_TC_ZP_NO_TRI EM: _TCI.CSF, _TCP.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. F: Unknown connector format to be recorded. R: Block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_BAD_FORMAT EM: TRCC2.CSF AM: TRCC2 AA: 7-Seg. ’C’; YTS. are not utilized. F: Global KDR list does not exist. Exact cause of error see section Error Supplementary Code bsspvw_info. R: Abort the acquisition block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TR_INI_NO_KDR EM: ZDTR.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. is not utilized. F: Multiple configuring of the same acquisition block in the same task. R: Abort the acquisition block initialization. A: Re-configure. EQ: Z_ERR_NUM_TR_INI_NO_TCI EM: ZDTR.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ‘C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-49 Communication Error Codes 6523 Hex F: 6524 Hex F: 6525 Hex F: 6526 Hex F: 6527 Hex F: 3-50 List of the SAVE area does not exist. Exact cause of error see section Error Supplementary Code bsspvw_info. R: Abort the acquisition block initialization. A: Contact Siemens AG. EQ: Z_ERR_NUM_TR_INI_NO_SAVE_1 EM: ZDTR.CSF, TRCC2.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. SAVE area full. R: Abort the acquisition block initialization. A: Reduce memory requirements in the local SAVE area. EQ: Z_ERR_NUM_TR_INI_NO_SAVE_2 EM: ZDTR.CSF, TRCC2 AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. SAVE memory assigning for reference list body not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Abort the acquisition block initialization. A: Reduce memory requirements in the local SAVE area. EQ: Z_ERR_NUM_TR_INI_NO_SAVE_3 EM: ZDTR.CSF, TRCC2.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. SAVE memory assigning for trace value list not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Abort the acquisition block initialization. A: Reduce memory requirements in the local SAVE area; Reduce configured value at the NTV connector of the corresponding @TCI. EQ: Z_ERR_NUM_TR_INI_SAVE_4 EM: ZDTR.CSF, TRCC2.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. RAM memory assigning for reference list body not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Abort the acquisition block initialization. A: Reduce memory requirements in the local RAM area. EQ: Z_ERR_NUM_TR_INI_NO_RAM_1 EM: ZDTR.CSF, TRCC.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6528 Hex 6529 Hex 652A Hex 652B Hex to 653F Hex 6540 Hex F: RAM memory assigning for trace value list not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: Abort the acquisition block initialization. A: Reduce memory requirements in the local RAM area; Reduce configured value at the NTV connector of the corresponding @TCI. EQ: Z_ERR_NUM_TR_INI_NO_RAM_2 EM: ZDTR.CSF, TRCC.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. F: No control block with corresponding TRC ID initialized. R: Abort the acquisition block initialization. A: Configure control block with corresponding TRC ID. EQ: Z_ERR_NUM_TR_INI_UNKWN_TRC EM: ZDTR.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. F: Connector ID not uniquely selected. R: Abort the acquisition block initialization. A: Utilize unique connector ID at the acquisition block. EQ: Z_ERR_NUM_TR_INI_DUP_CID EM: TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF AM: TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. are not utilized. F: 6541 Hex F: 6542 Hex F: Unknown block status for control block. R: Control block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_ZP_BAD_BZS EM: _TCI.CSF, _TCP.CSF, TRCC2.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2 AA: 7-Seg. ’C’; YTS. Ring buffer size too small. R: Control block reverts to the dead status. A: Enlarge trace buffer / configure fewer acquisition blocks. EQ: Z_ERR_NUM_TR_ZP_SM_UMPUF EM: _TCP.CSF AM: @TCP AA: 7-Seg. ’C’; YTS. Sampling time for the control block cannot be determined. R: Control block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TC_INI_BAD_TIME EM: _TCI.CSF, _TCP.CSF AM: @TCI, @TCP AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-51 Communication Error Codes 6543 Hex F: 6544 Hex F: 6545 Hex F: Information function of the operating system could not be invoked. R: Acquisition block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TR_INI_BAD_AFPI EM: TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF AM: TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. 6546 Hex F: 6547 Hex F: 6548 Hex F: Invalid value at the HIA of TRHI R: TRHI reverts to the dead status. A: Configure a value between 0 and 10 at the connector HIA of the TRHI. EQ: Z_ERR_NUM_TR_INI_PARAM_ANZ EM: TRHI.CSF AM: TRHI AA: 7-Seg. ’C’; YTS. TRHI block multiply configured. R: TRHI reverts to the dead status. A: Configure only one TRHI per trace system. EQ: Z_ERR_NUM_TR_INI_MEHR EM: TRHI.CSF AM: TRHI AA: 7-Seg. ’C’; YTS. Channel length at the group telegram has been configured too small. R: @TCP reverts to the dead status. A: Select a larger connector CHA of the @TCP. The minimum number is located at the supplement of the communication error message. EQ: Z_ERR_NUM_TC_ZP_CHA EM: _TCP.CSF AM: @TCP AA: 7-Seg. ’C’; YTS. 3-52 Sampling time for the acquisition block cannot be determined. R: Acquisition block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TR_INI_BAD_TIME EM: _TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF AM: @TRI , TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. Unknown block status for acquisition block. R: Acquisition block reverts to the dead status. A: Contact Siemens AG. EQ: Z_ERR_NUM_TR_ZP_BAD_BZS_ EM: _TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSF AM: @TRI, TRP1, TRP2, TRP4, TRPF AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6549 Hex 654A Hex 654B Hex to 657F Hex F: Too many acquisition blocks at the group telegram output. R: @TCP reverts to the dead status. A: Configure fewer than 256 acquisition blocks (TRP1,TRP2,TRP4,TRPF). EQ: Z_ERR_NUM_TC_TRP_ANZ EM: _TCP.CSF AM: @TCP AA: 7-Seg. ’C’; YTS. F: Length of the output channel is less than 200 bytes. R: Block reverts to the dead status. A: Set the output channel size (connector CHA) to at least 200. EQ: Z_ERR_NUM_CHA_OUT_LEN EM: ZDTR.CSF AM: @TCP, @TCI AA: 7-Seg. ’C’; YTS. not utilized. 3.2.8 Time 6600 Hex 6601 Hex 6602 Hex 6603 Hex F: The board name at the TM connector refers to a board that does not exist in the rack or cannot function as a time source. R: RTCM reverts to the dead status. A: Enter the name of a board that can act as a time source: - Master Processor Board, - CSH11, - MM3, - SS5, - CS21. EQ: ZF_ERR_NUM_RTCM_SZQ_N_VALID EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. not utilized. F: Unknown operating status of the RTCM block. R: RTCM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_RTCM_BZS_ERR EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. F: Memory assigning for the local structures not possible. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: RTCM reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_RTCM_N_MEM EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-53 Communication Error Codes 6604 Hex 6605 Hex 6606 Hex 6607 Hex 6608 Hex 6609 Hex 660A Hex 3-54 F: Several RTCM blocks were configured in the same rack. R: RTCM reverts to the dead status. A: Remove one of the configured RTCM blocks. EQ: ZF_ERR_NUM_RTCM_MEHR_PROJ EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. F: A SS5 import board (at the TM connector) and a SS5 export board (at the TTM connector) are simultaneously configured. R: RTCM reverts to the dead status. A: Another clock source must be configured at the TM connector; The name of the SS5 export board at the TTM connector must be removed. EQ: ZF_ERR_NUM_RTCM_CSL2F_PROJ EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. F: PN local KDR list not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: RTCM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_RTCM_N_KDR EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS not utilized. F: The rack has no CBUS connection. R: RTCM reverts to the dead status. A: Utilize rack with CBUS connection (i.e. SR8). EQ: ZF_ERR_NUM_RTCM_N_CBUS EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. F: RTCM block was configured with an impermissible sampling time (not between 128 ms and 512 ms). R: RTCM reverts to the dead status. A: Configure the sampling time between 128 ms and 512 ms. EQ: ZF_ERR_NUM_RTCM_ABTASTZEIT_ERR EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. F: The RTCM block is configured on a board that is not a master. R: RTCM reverts to the dead status. A: Configure RTCM block on a processor board (processor 1) installed to the left. EQ: ZF_ERR_NUM_RTCM_N_MASTER EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 660B Hex F: 660C Hex F: The clock specification at the connectors XYR, XMO, XDA, XHR and / or XMI are invalid. R: RTCM reverts to the dead status. A: Check specifications at the connectors XYR, XMO, XDA, XHR and XMI Permissible values are: 00 v XYR v 99 01 v XMO v 12 01 v XDA v 31 00 v XHR v 23 00 v XMI v 59 EQ: ZF_ERR_NUM_RTCM_STELL_N_VALID EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. Access to link memory unsuccessful. R: RTCM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_RTCM_BUS_ZUGR_ERR EM: RTCM.CSF AM: RTCM.CSF AA: 7-Seg. ’C’; YTS. 3.2.8.1 Device 6700 Hex F: 6701 Hex F: 6702 Hex F: Incorrect assignments UP connector R: @DPH reverts to a neutral state A: Check specification at connector UP. Permissible values: 1-3 EQ: ZF_ERR_NUM_DPH_UP EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF Invalid combination UP and PHL connector R: @DPH reverts to a neutral state A: Check specifications at the UP and PHL connectors. Invalid combination: PHL = 0 ( 3 word PIV interface ) UP = 1 ( SINEC-L2-DP protocol ) EQ: ZF_ERR_NUM_DPH_UP_PHL EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF KDR list not found R: @DPH reverts to a neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_DPH_NO_KDR EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRW of SDB_FUNC_BSSPVW_INFO) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-55 Communication Error Codes 6703 Hex F: 6704 Hex F: 6705 Hex F: 6706 Hex F: 6707 Hex F: 6710 Hex F: 6711 Hex F: 3-56 Multiple configuring of central blocks R: @DPH reverts to a neutral state A: Connector value PHS must differ on local processor for each @DPH block. EQ: ZF_ERR_NUM_DPH_MEHR_PROJ EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF No memory available R: @DPH reverts to a neutral state A: Reduce memory requirement EQ: ZF_ERR_NUM_DPH_NO_MEM EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRW of SDB_FUNC_BSSPVW_GEME) No parameter block DPI configured R: @DPH reverts to a neutral state A: Configure at least one block DPI with the same connector value PHS EQ: ZF_ERR_NUM_DPH_NO_DPI EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF Internal error R: @DPH reverts to a neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_DPH_DPI_AK EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF Internal error R: @DPH reverts to a neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_DPH_INT_ERR EM: _DPH.CSF AM: _DPH.CSF AA: 7-Seg. ’C’; YTS, KFF KDR list not found R: DPI reverts to a neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_DPI_NO_KDR EM: DPI.CSF AM: DPI.CSF AA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRW SBD_FUNC_BSSPVW_INFO) No central block @DPH configured R: DPI reverts to a neutral state A: Configure central block @DPH with the same connector specification PHS EQ: ZF_ERR_NUM_DPI_NO_DPH EM: DPI.CSF AM: DPI.CSF AA: 7-Seg. ’C’; YTS, KFF General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6712 Hex F: 6713 Hex F: 6714 Hex F: 6715 Hex F: 6716 Hex F: 6717 Hex F: Faulty cascade sequencing R: DPI reverts to a neutral state A: A request was transferred from several parameter blocks DPI to the same central block. Check the cascade configuring ! EQ: ZF_ERR_NUM_DPI_IC_ERR EM: DPI.CSF AM: DPI.CSF AA: 7-Seg. ’C’; YTS, KFF Internal error R: DPI reverts to a neutral state A: Inform Siemens AG. EQ: ZF_ERR_NUM_DPI_INT_ERR EM: DPI.CSF AM: DPI.CSF AA: 7-Seg. ’C’; YTS, KFF Incorrect parameter ID at the PR connector R: DPI does not generate request A: Specify correct value at the connector PR. Permissible values: 0-11 EQ: ZF_ERR_NUM_DPI_REQ_PR_ERR EM: DPI.CSF AM: DPI.CSF AA: QS1; YTS Incorrect parameter number at the PN connector R: DPI does not generate request. A: Specify correct value at the connector PN. Permissible values: 0-2047 EQ: ZF_ERR_NUM_DPI_REQ_PN_ERR EM: DPI.CSF AM: DPI.CSF AA: QS1; YTS Incorrect parameter index at the PI connector R: DPI does not generate request A: Specify correct value at the connector PI. Permissible values: 0-254 EQ: ZF_ERR_NUM_DPI_REQ_PI_ERR EM: DPI.CSF AM: DPI.CSF AA: QS1; YTS Double word request with PIV interface length of 3 words at the connector PR R: DPI does not generate request A: Configure correct word request at connector PR EQ: ZF_ERR_NUM_DPI_PR_4_BYTE_ERR EM: DPI.CSF AM: DPI.CSF AA: QS1; YTS General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-57 Communication Error Codes F: No reply from the device within the TIME-OUT period R: DPI has not received reply A: Increase TIME-OUT period (connector RCM) at the central block @DPH, check communication with the device. EQ: ZF_ERR_NUM_DPI_RES_TIME_OUT_ERR EM: DPI.CSF AM: DPI.CSF AA: QS2; YTS 6800 Hex F: 6801 Hex F: 6802 Hex F: 6803 Hex F: 6804 Hex F: 6805 Hex F: Internal status error 1. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_BZS EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Internal status error 2. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ATG_STATE EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Internal status error 3. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ANT_STATE EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Internal status error 4. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_KON_STATE EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Internal status error 5. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_KOP_STATE EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Too little memory. R: Block LPN disables. A: Reduce application’s RAM requirements. EQ: ZF_ERR_NUM_LPN_NO_MEM EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS 6718 Hex 3.2.8.2 Download 3-58 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6806 Hex F: 6807 Hex F: 6808 Hex F: 6809 Hex F: 680A Hex F: 680B Hex F: 680C Hex F: Multiple configuring of the block LPN. R: Block LPN disables. A: Only configure one LPN-FB per processor board. EQ: ZF_ERR_NUM_LPN_MULT EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS KDR list not found R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_NO_KDR EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Job request channel continually faulty. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ATG_KAN EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Job request initialization faulty R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ATG_KOMDAT_INIT EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Job request initialization faulty. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ATG_KAN_INIT EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Reply channel continually faulty. R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ANT_KAN EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Reply channel initialization faulty R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ANT_KOMDAT_INIT EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-59 Communication Error Codes 680D Hex F: 680E Hex F: 680F Hex F: 6810 Hex F: Reply channel initialization faulty R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_ANT_KAN_INIT EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Unknown card type R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_CARD_TYPE_ERR EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Internal card programming error R: Block LPN disables. A: Inform Siemens AG.. EQ: ZF_ERR_NUM_LPN_BSFC_FRW_ERR EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS Sub-task initialization not possible R: Block LPN disables. A: Configure LPN-FB in a different sampling time. EQ: ZF_ERR_NUM_LPN_INI_SUB_TASK EM: LPN.CSF AM: LPN.CSF AA: QTS; YTS 3.2.9 Central Blocks for Links 3.2.9.1 Coupling Memory Link 6900 Hex F: 6901 Hex F: 3-60 Several @CMM blocks were configured with the same coupling memory board names. R: @CMM reverts to the dead status. A: Remove one of the configured @CMM blocks. EQ: ZF_ERR_NUM_CMM_MEHR_PROJ EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_CIP_FREI_FRW_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6902 Hex F: The CIP entry for the @CMM block cannot be accessed. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ 6903 Hex F: 6904 Hex F: 6905 Hex F: 6906 Hex F: 6907 Hex F: 6908 Hex F: The CIP entry for the @CMM block does not exist. R: @CMM reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CMM_NAM_N_KENN EM: ZBAK.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_SUCH_FRW_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_REOR_FRW_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CMM block. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_BZS_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for the warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CMM reverts to the dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CMM_SAVE_ZU_KURZ EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_SAVE_N_KENN EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-61 Communication Error Codes 6909 Hex F: 690A Hex F: 690B Hex F: 690C Hex F: 690D Hex F: 690E Hex F: 3-62 @CMM block was configured in an impermissible sampling time (not between 32 ms and 255 ms). R: @CMM reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CMM_ABTASTZEIT_ERR EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CMM reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CMM_EXC_ZU_KURZ EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the reorganization structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CMM reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CMM_REORG_ZU_KURZ EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_fb_init. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_FB_INIT_FRW_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Link type in CIP entry is not set to ‘‘Coupling Memory Link’’. R: @CMM reverts to the dead status. A: Check the configured name at the CTS connector; Check that the configured block type corresponds to @CMM EQ: ZF_ERR_NUM_CMM_KOP_TYP_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_ANM_FRW_ERR EM: _CMM.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes F: Unknown registered status determined in DEXDO3 management section. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CMM_ANM_STATUS_ERR EM: ZP.CSF AM: _CMM.CSF AA: 7-Seg. ’C’ 6910 Hex F: 6911 Hex F: 6912 Hex F: Several @CS11 blocks were configured with the same CS11 board names. R: @CS11 reverts to the dead status. A: Remove one of the configured @CS11 blocks EQ: ZF_ERR_NUM_CS11_MEHR_PROJ EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_CIP_FREI_FRW_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ The CIP entry for the @CS11 block cannot be accessed. R: @CMM reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ 6913 Hex F: 6914 Hex F: 690F Hex 3.2.9.2 Rack Link The CIP entry for the @CS11 block does not exist. R: @CS11 reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CS11_NAM_N_KENN EM: ZBAK.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_SUCH_FRW_ERR EM: ._CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-63 Communication Error Codes 6915 Hex F: 6916 Hex F: 6917 Hex F: 6918 Hex F: 6919 Hex F: 691A Hex F: 3-64 Unknown function return value of the function zp_dexdo_reorganization. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_REOR_FRW_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CS11 blocks. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_BZS_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for the warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS11 reverts to the dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CS11_SAVE_ZU_KURZ EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_SAVE_N_KENN EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ @CS11 block was configured in a impermissible sampling time (not between 32 ms and 255 ms). R: @CS11 reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CS11_ABTASTZEIT_ERR EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Memory assignment not possible for the exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS11 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CS11_EXC_ZU_KURZ EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 691B Hex F: 691C Hex F: 691D Hex F: 691E Hex F: 691F Hex F: 6920 Hex F: Memory assigning not possible for the reorganization structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS11 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CS11_REORG_ZU_KURZ EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_fb_init. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_FB_INIT_FRW_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Link type or sub-link type is not set to "CS11 rack link". R: @CS11 reverts to the neutral state A: Check the configured name at the CTS connector; The configured name at the CTS connector must correspond to a CS11 board EQ: ZF_ERR_NUM_CS11_KOP_TYP_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_ANM_FRW_ERR EM: _CS11.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ Unknown registered status detected in DEXDO3 management section. R: @CS11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS11_ANM_STATUS_ERR EM: ZP.CSF AM: _CS11.CSF AA: 7-Seg. ’C’ The configured name of the @CS21 block corresponds to another in the link. R: @CS21 reverts to the dead status. A: Check, whether the name at the CTS connector corresponds to another CS21 block; Check, whether the @CS21 block has been multiply configured on the same CS21 board. EQ: ZF_ERR_NUM_CS21_MEHR_PROJ EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-65 Communication Error Codes 6921 Hex F: 6922 Hex F: 6923 Hex 6924 Hex 6925 Hex 6926 Hex 6927 Hex 6928 Hex 3-66 The CIP entry for the @CS21 block cannot be accessed. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ The CIP entry for the @CS21 block does not exist. R: @CS21 reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CS21_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function zbak_cip_suche. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_CIP_SUCH_FRW_ERR EM: ._CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ not utilized. F: There are already three registered @CS21 blocks in the link. R: @CS21 reverts to the dead status. A: Power down rack and power up again after 10 seconds; Check whether more than three CS21 boards exist on the link; Check whether the @CS21 block has been multiply configured on the same CS21 board. EQ: ZF_ERR_NUM_CS21_SCHON_DREI_CS21 EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: The configured CS11 board does not exist. R: @CS21 reverts to the dead status. A: Check the configured CS11 name at the MTS connector. EQ: ZF_ERR_NUM_CS21_CS11_N_KENN EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _cs21_anmeldung. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_ANM_FRW_ERR EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Unknown operating status of the @CS21 block. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_BZS_ERR EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6929 Hex 692A Hex 692B Hex 692C Hex 692D Hex 692E Hex 692F Hex to 6931 Hex F: SAVE memory assigning not possible for the warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme R: @CS21 reverts to the dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CS21_SAVE_ZU_KURZ EM: ZP.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_SAVE_N_KENN EM: ZP.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: @CS21 block was configured in an impermissible sampling time (not between 32 ms and 255 ms). R: @CS21 reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CS21_ABTASTZEIT_ERR EM: ZP.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Memory assigning not possible for exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS21 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CS21_EXC_ZU_KURZ EM: ZP.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Memory assigning not possible for reorganization structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS21 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CS21_REORG_ZU_KURZ EM: ZP.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function zp_fb_init. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_FB_INIT_FRW_ERR EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-67 Communication Error Codes 6932 Hex 6933 Hex 6934 Hex to 693F Hex F: Link type or sub-link type is not set to "CS11 rack link". R: @CS21 reverts to the neutral state A: Check the configured name at the CTS connector; The configured name at the CTS connector must correspond to a CS21 board EQ: ZF_ERR_NUM_CS21_KOP_TYP_ERR EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ F: The software version on the processor board is not compatible with the version in the CS11 rack. R: @CS21 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CS21_VERSION_ERR EM: _CS21.CSF AM: _CS21.CSF AA: 7-Seg. ’C’ not utilized. 3.2.9.3 PN Local Link 6940 Hex F: 6941 Hex F: 6942 Hex F: 6943 Hex F: 3-68 The @CPN block was multiply configured on the same processor board. R: @CPN reverts to the dead status. A: Remove one of the configured @CPN blocks. EQ: ZF_ERR_NUM_CPN_MEHR_PROJ EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_CIP_FREI_FRW_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ The CIP entry for the @CPN block cannot be accessed, since it is pointing to another processor board. R: @CPN reverts to the dead status. A: Board name at the CTS connector must correspond to the name of the processor board. EQ: ZF_ERR_NUM_CPN_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ The CIP entry for the @CPN block does not exist. R: @CPN reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CPN_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6944 Hex F: 6945 Hex F: 6946 Hex F: 6947 Hex F: 6948 Hex F: 6949 Hex F: Unknown function return value of the function zbak_cip_suche. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_CIP_SUCH_FRW_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_REOR_FRW_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CPN block. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_BZS_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CPN reverts to dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CPN_SAVE_ZU_KURZ EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_SAVE_N_KENN EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ @CPN block was configured in an impermissible sampling time (not between 32 ms and 255 ms) R: @CPN reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CPN_ABTASTZEIT_ERR EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-69 Communication Error Codes 694A Hex F: 694B Hex F: 694C Hex F: 694D Hex F: 694E Hex F: 694F Hex F: 3-70 Memory assigning not possible for exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS21 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CPN_EXC_ZU_KURZ EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS21 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CPN_REORG_ZU_KURZ EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_fb_init. R: @CPN reverts to the dead status. A: Contact Siemens AG EQ: ZF_ERR_NUM_CPN_FB_INIT_FRW_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Link type is not set to ‘‘PN Local Link’’. R: @CS21 reverts to the dead status A: Check the configured name at the CTS connector; Check that the configured block type corresponds to @CS21. EQ: ZF_ERR_NUM_CPN_KOP_TYP_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_ANM_FRW_ERR EM: _CPN.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ Unknown register status detected in the DEXDO3 management section. R: @CPN reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CPN_ANM_STATUS_ERR EM: ZP.CSF AM: _CPN.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.9.4 Link DUST1 6965 Hex 6966 Hex 6969 Hex to 6996 Hex F: Specification at the TWU connector faulty. R: @CSD01 reverts to the dead status. A: Set specifications at the TWU connector to only decimal values be tween 0 and 1000. EQ: ZF_ERR_NUM_CSD1_TWU_ERR EM: _CSD01.CSF AM: _CSD01.CSF AA: 7-Seg. ’C’ F: Specification at the BDR connector faulty. R: @CSD01 reverts to the dead status. A: The specification at the BDR connector can only correspond to one of the following baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200 EQ: ZF_ERR_NUM_CSD1_BDR_ERR EM: _CSD01.CSF AM: _CSD01.CSF AA: 7-Seg. ’C’ not utilized. 3.2.9.5 Link SINEC H1 6970 Hex F: 6971 Hex F: 6972 Hex F: 6973 Hex F: Several @CSH11 blocks were configured with the same CSH11 board names. R: @CSH11 reverts to the dead status. A: Remove one of the configured @CSH11 blocks. EQ: ZF_ERR_NUM_CSH1_MEHR_PROJ EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_CIP_FREI_FRW_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSH11 block cannot be accessed. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSH11 block does not exist. R: @CSH11 reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CSH1_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-71 Communication Error Codes 6974 Hex F: 6975 Hex F: 6976 Hex F: 6977 Hex F: 6978 Hex F: 6979 Hex F: 3-72 Unknown function return values of the function zbak_cip_suche. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_CIP_SUCH_FRW_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown function return values of the function zp_dexdo_reorganization. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_REOR_FRW_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CSH11 block. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_BZS_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CSH11 reverts to dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CSH1_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_SAVE_N_KENN EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ @CSH11 block was configured in an impermissible sampling time (not between 32 ms and 255 ms) R: @CSH11 reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CSH1_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 697A Hex F: 697B Hex F: 697C Hex F: 697D Hex F: 697E Hex F: 697F Hex F: Memory assigning not possible for the exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CSH11 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSH1_EXC_ZU_KURZ EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CS21 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSH1_REORG_ZU_KURZ EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_fb_init. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_FB_INIT_FRW_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Link type not set to ‘‘CSH11 Link’’. R: @CSH11 reverts to the dead status. A: Check the configured name at the CTS connector; Check that the block type corresponds to @CSH11. EQ: ZF_ERR_NUM_CSH1_KOP_TYP_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_ANM_FRW_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_ANM_STATUS_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-73 Communication Error Codes 6980 Hex F: 6981 Hex F: 6982 Hex F: 6983 Hex F: 6984 Hex F: 6985 Hex F: 6986 Hex F: 3-74 CSH11 firmware has detected an unrepairable error. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_INI_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ CSH11 firmware has reverted to an error status. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_TOT EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown status of the CSH11 firmware. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_ZUS_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_firmware_zyklisch. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_FIRM_ZYK_FRW_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Length of the specified address at the MAA connector is false. R: @CSH11 reverts to the dead status. A: Specification at the MAA connector must be exactly 12 characters long. EQ: ZF_ERR_NUM_CSH1_STRING_LEN_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Specification at the MMA connector faulty. R: @CSH11 reverts to the dead status. A: The address at the MAA connector must correspond to a hexa decimal number, i.e. only numbers 0, 1, 2, 3, 4, 5, 6, 7, 8, 9 and letters a, b, c, d, e, f are permitted. EQ: ZF_ERR_NUM_CSH1_STRING_ERR EM: _CSH11.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the firmware structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CSH11 reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSH1_N_MEM EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6987 Hex 6988 Hex 6989 Hex to 698F Hex F: Unknown function return value of the function _csh11_init. R: @CSH11 reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSH1_INI_FRW_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _csh11_firmware_init. R: @CSH11 reverts to the dead status. A: Contact Siemens AG EQ: ZF_ERR_NUM_CSH1_FIR_INIT_FRW_ERR EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ not utilized. 3.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung 6990 Hex F: 6991 Hex F: 6992 Hex F: 6993 Hex F: Several communications central blocks were configured with the same CS7 board names or interface name. R: @CSxyz reverts to the dead status. A: Remove one of the configured @CSxyz blocks EQ: ZF_ERR_NUM_CL2F_MEHR_PROJ EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown return function of the function zp_cip_freigabe. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_CIP_FREI_FRW_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSxyz block cannot be accessed. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSxyz block does not exist. R: @CSxyz reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CL2F_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-75 Communication Error Codes 6994 Hex F: 6995 Hex F: 6996 Hex F: 6997 Hex F: 6998 Hex F: 6999 Hex F: 3-76 Unknown function return value of the function zbak_cip_suche. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_CIP_SUCH_FRW_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_REOR_FRW_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CSxyz block. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_BZS_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CSxyz reverts to dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CSH1_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSH11.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error Supplementary Code bsspvw_info R: @CSxyz reverts to the dead status. A: Contact Siemens AG EQ: ZF_ERR_NUM_CL2F_SAVE_N_KENN EM: ZP.CSF AM: _CSxyz.CSF @CSxyz block was configured in an impermissible sampling time (not between 32 ms and 255 ms) R: @CSxyz reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CL2F_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 699A Hex F: 699B Hex F: 699C Hex F: 699D Hex F: 699E Hex F: 699F Hex F: 69A0 Hex F: Memory assigning not possible for the exception structure. R: @CSxyz reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CL2F_EXC_ZU_KURZ EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the reorganization structure. R: @CSxyz reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CL2F_REORG_ZU_KURZ EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown function return value for the function zp_fb_init. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_FB_INIT_FRW_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Link type is not set to ‘‘CSL2x Link’’. R: @CSxyz reverts to the dead status. A: Check the configure name at the CTS connector; Check that the block type corresponds to @CSxyz. EQ: ZF_ERR_NUM_CL2F_KOP_TYP_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown function return value for the function zp_anmelde_ueberwachung. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_ANM_FRW_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_ANM_STATUS_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ CSL2x firmware has detected an unrepairable error. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_INIT_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-77 Communication Error Codes 69A1 Hex F: 69A2 Hex F: 69A3 Hex F: 69A4 Hex 69A5 Hex 69A6 Hex 69A7 Hex 3-78 CSL2x firmware has reverted to an error status or SS5x module insert is missing. R: @CSxyz reverts to the dead status. A: SS5x module in the CS7 board; Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_TOT EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown status of the CSL2x firmware. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_ZUS_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_firmware_zyklisch. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_FIRM_ZYK_FRW_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ F: Station address false at the MAA connector. R: @CSxyz reverts to the dead status. A: The specification at the MAA connector must correspond to a number between 1 and 126. (@CSL2A: between 1 and 123) EQ: ZF_ERR_NUM_CL2F_STAT_ADR_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ not utilized. F: Memory assigning not possible for the firmware structure. Exact cause of error see section Error Supplementary Code bsspvw_geme R: @CSxyz reverts to the dead status. A: Reduce the RAM requirement of the application. EQ: ZF_ERR_NUM_CL2F_N_MEM EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _csl2f_init. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_INIT_FRW_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 69A8 Hex F: 69A9 Hex F: 69AA Hex F: 69AB Hex F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: 69AC Hex 69AD Hex 69AE Hex Unknown function return value of the function _csl2f_firmware_init. R: @CSxyz reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CL2F_FIR_INIT_FRW_ERR EM: ZP.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Specification of the BDR connector faulty. R: @CSxyz reverts to the dead status. A: The coded baud rate at the BDR connector must correspond to a number between 0 and 5 (@CSL2A: between 0 and 8). EQ: ZF_ERR_NUM_CL2F_BDR_ERR EM: _CSxyz.CSF AM: _CSxyz.CSF AA: 7-Seg. ’C’ Specification of the AST connector faulty. R: @CSL2L reverts to the dead status. A: The value at the BDR connector must correspond to a number between 0 and 126. EQ: ZF_ERR_NUM_CL2L_AST_ERR EM: _CSL2L.CSF AM: _CSL2L.CSF AA: 7-Seg. ’C’ Projektierungsfehler Eingang LTT Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Eingang LTT korrigieren ZF_ERR_NUM_STD_KON_LTT _peer.csf _peer.csf Projektierungsfehler Eingang LTR Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Eingang LTR korrigieren ZF_ERR_NUM_STD_KON_LTR _peer.csf _peer.csf Projektierungsfehler Anschluss CTS Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Anschluss CTS korrigieren (X01, X02 beachten) ZF_ERR_NUM_STD_KON_CTS _peer.csf, _uss_s/m _peer.csf, _uss_s/m Fehler bei Kommunikationsinitialisierung („ZINI-Eintrag“) Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Siemens AG benachrichtigen ZF_ERR_NUM_STD_FRW_ZINI diverse diverse Zusatzcode: Rückgabewert der Funktion zg_zini_Nachtrag General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-79 Communication Error Codes 69AF Hex F: R: A: EQ: EM: AM: 69B0 Hex F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: R: A: EQ: EM: AM: F: 69B1 Hex 69B2 Hex 69B3 Hex 69B4 Hex 69B5 Hex 69B6 Hex R: A: EQ: EM: AM: 3-80 Fehler bei Speicherbeschaffung Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Projektierung verkleinern ZF_ERR_NUM_STD_FRW_GEME diverse diverse Zusatzcode: Rückgabewert der Funktion bsspvw_geme Schnitstelle X01/X02 ist belegt Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Nur eine Kopplung pro Schnittstelle projektieren ZF_ERR_NUM_STD_SST_BELEGT _peer.csf, _uss_s/m _peer.csf, _uss_s/m Projektierungsfehler Eingang BDR Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Eingang BDR korrigieren ZF_ERR_NUM_STD_KON_BDR _peer.csf, _uss_s/m _peer.csf, _uss_s/m Projektierungsfehler Eingang MAA Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Eingang MAA korrigieren ZF_ERR_NUM_STD_KON_MAA _uss_s _uss_s Projektierungsfehler Eingang PZD Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Eingang PZD korrigieren ZF_ERR_NUM_STD_KON_PZD _uss_s _uss_s Schnitstelle X01 nicht für USS freigegeben USS wird nicht gestartet, es läuft Service auf X01 Schalter S1/8 auf T400 auf ON stellen ZF_ERR_NUM_STD_SST_SPERR_X01 _uss_s/m _uss_s/m Zwei USS-Kopplungen auf T400 Baustein schaltet sich ab, Eintrag ins Kommunikationsfehlerfeld Nur eine USS-Kopplung auf T400 projektieren ZF_ERR_NUM_STD_USS_DOPPELT _uss_s/m _uss_s/m Empfangene Telegrammlänge passt nicht zur projektierten Länge Telegramm wird verworfen Telegrammlänge des Kommunikationspartners mit projektierter Länge abgleichen (USS-Slave: Eingänge PAR, PZD; USS-Master: Anzahl virtueller Verbindungen) ZF_ERR_NUM_STD_TEL_LEN_EMPF _uss_s/m _uss_s/m General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.9.7 EP Link 69D0 Hex F: 69D1 Hex F: 69D2 Hex F: 69D3 Hex F: 69D4 Hex F: 69D5 Hex F: Several @CEP22 resp. @CEP blocks have been configured with the same EP22 board name. R: @CEP22 resp. @CEP reverts to the dead status. A: Remove one of the configured @CEP22 resp. @CEP blocks. EQ: ZF_ERR_NUM_EP22_MEHR_PROJ EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_CIP_FREI_FRW_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ The CIP entry for the @CEP22 resp. @CEP block cannot be accessed. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ The CIP entry for the @CEP22 resp. @CEP block does not exist. R: @CEP22 resp. @CEP reverts to the dead status. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_EP22_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_CIP_SUCH_FRW_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_REOR_FRW_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-81 Communication Error Codes 69D6 Hex F: 69D7 Hex F: 69D8 Hex F: 69D9 Hex F: 69DA Hex F: 69DB Hex F: 3-82 Unknown operating status of the @CEP22 resp. @CEP block. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_BZS_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for the warm start flag. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CEP22 resp. @CEP reverts to the dead status. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_EP22_SAVE_ZU_KURZ EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ SAVE are not found. Exact cause of error see section Error Supplementary Code bsspvw_info R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_SAVE_N_KENN EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ @CEP22 resp. @CEP block was configured in an impermissible sampling time (not between 32 ms and 255 ms). R: @CEP22 resp. @CEP reverts to the dead status. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_EP22_ABTASTZEIT_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the exception structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CEP22 resp. @CEP reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_EP22_EXC_ZU_KURZ EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Memory assigning not possible for the reorganization structure. Exact cause of error see section Error Supplementary Code sspvw_geme. R: @CEP22 resp. @CEP reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_EP22_REORG_ZU_KURZ EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 69DC Hex F: 69DD Hex F: 69DE Hex F: 69DF Hex F: 69E0 Hex F: 69E1 Hex F: 69E2 Hex F: Unknown function return value of the function zp_fb_init. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_FB_INIT_FRW_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Link type in the CIP entry is not set to ‘‘Coupling Memory Link’’. R: @CEP22 resp. @CEP reverts to the dead status. A: Check the configured name at the CTS connector; Check that the configured block type corresponds to @CEP22 resp. @CEP. EQ: ZF_ERR_NUM_EP22_KOP_TYP_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_ANM_FRW_ERR EM: _CEP22.CSF resp. _CEP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_ANM_STATUS_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ CEP22 firmware has detected an unrepairable error. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_INIT_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ CEP22 firmware has reverted to an error status. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_TOT EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ Unknown status of the CEP22 firmware. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_ZUS_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-83 Communication Error Codes 69E3 Hex F: 69E4 Hex to 69E5 Hex 69E6 Hex F: 69E7 Hex 69E8 Hex 69E9 Hex to 69EF Hex Unknown function return value of the function zp_firmware_zyklisch. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_FIRM_ZYK_FRW_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ not utilized. Memory assigning not possible for the firmware structure. Exact cause of error see section Error Supplementary Code bsspvw_geme. R: @CEP22 resp. @CEP reverts to the dead status. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_EP22_N_MEM EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _CEP22_init resp. _CEP_init. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_INIT_FRW_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _CEP22_firmware_init. R: @CEP22 resp. @CEP reverts to the dead status. A: Contact Siemens AG. EQ: ZF_ERR_NUM_EP22_FIR_INIT_FRW_ERR EM: ZP.CSF AM: _CEP22.CSF resp. _CEP.CSF AA: 7-Seg. ’C’ not utilized. 3.2.9.8 Link DUST7 69F0 Hex 3-84 F: Several communication central blocks were configured with the same CS7 board names or interface names. R: @CSD07 reverts to the dead state. A: Remove one of the configured @CSD07 blocks; Correct the interface specification of one @CSD07 block. EQ: ZF_ERR_NUM_CSD7_MEHR_PROJ EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 69F1 Hex F: 69F2 Hex F: 69F3 Hex F: 69F4 Hex F: 69F5 Hex F: 69F6 Hex F: 69F7 Hex F: Unknown function return value of the function zp_cip_freigabe. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_CIP_FREI_FRW_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD07 block is not accessible. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD07 block does not exist. R: @CSD07 reverts to the dead state. A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CSD7_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_CIP_SUCH_FRW_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_REOR_FRW_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown operating status of the @CSD07 block. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_BZS_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD07 reverts to the dead state. A: Reduce the SAVE requirement in the application EQ: ZF_ERR_NUM_CSD7_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-85 Communication Error Codes 69F8 Hex F: 69F9 Hex F: 69FA Hex F: 69FB Hex F: 69FC Hex F: 69FD Hex F: 3-86 SAVE area not found. Exact cause of error see section Error supplementary code bsspvw_info. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_SAVE_N_KENN EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ @CSD07 block configured in impermissible sampling time (not between 32ms and 255ms) R: @CSD07 reverts to the dead state. A: Configure the sampling time between 32ms and 255ms EQ: ZF_ERR_NUM_CSD7_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Memory assigning not possible for exception structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD07 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD7_EXC_ZU_KURZ EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD07 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD7_REORG_ZU_KURZ EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_fb_init. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_FB_INIT_FRW_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Link type is not set to "DUST1" or "CS7". R: @CSD07 reverts to the dead state. A: Check the configured name at CTS connector; Check that block type corresponds to @CSD07 EQ: ZF_ERR_NUM_CSD7_KOP_TYP_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 69FE Hex F: 69FF Hex F: 6A00 Hex F: 6A01 Hex F: 6A02 Hex F: 6A03 Hex F: Unknown function return value of the function zp_anmelde_ueberwachung. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_ANM_FRW_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_ANM_STATUS_ERR EM: ZP.CSF AM: @CSD07 AA: 7-Seg. ’C’ DUST1 firmware has detected an unrepairable error. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_DUST_INIT_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ DUST1 firmware has reverted to an error status or SS4 adapter module missing. R: @CSD07 reverts to the dead state. A: Install SS4 module in CS7 board; A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_DUST_TOT EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown status of the DUST1 firmware. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_ZUS_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_firmware_zyklisch. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_FIRMWARE_ZYK_FRW_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-87 Communication Error Codes 6A04 Hex 6A05 Hex 6A06 Hex 6A07 Hex 6A08 Hex 6A09 Hex 6A0A Hex to 6A0F Hex 3-88 F: Memory assigning not possible for firmware structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD07 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD7_N_MEM EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ F: Specification at SPB connector faulty. R: @CSD07 reverts to the dead state. A: Specification at TWU connector can only be in range 0, 1 or 2 . EQ: ZF_ERR_NUM_CSD7_SPB_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ F: Specification at PAR connector faulty. R: @CSD07 reverts to the dead state. A: Specification at BDR connector can only be in range 0, 1 or 2 . EQ: ZF_ERR_NUM_CSD7_PAR_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ F: Specification at BDR connector faulty. R: @CSD07 reverts to the dead state. A: Specification at BDR connector can only correspond to one of the following baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200 EQ: ZF_ERR_NUM_CSD7_BDR_ERR EM: _CSD07.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _CSD7_init. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_INIT_FRW_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _CSD7_firmware_init. R: @CSD07 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD7_FIR_INIT_FRW_ERR EM: ZP.CSF AM: _CSD07.CSF AA: 7-Seg. ’C’ not utilized General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.9.9 Link DUST2 6A10 Hex F: 6A11 Hex F: 6A12 Hex F: 6A13 Hex F: 6A14 Hex F: 6A15 Hex F: Several communication central blocks were configured with the same CS7 board names or interface names. R: @CSD02 reverts to the dead state. A: Remove one of the configured @CSD02 blocks; Correct the interface specification of one @CSD02 block EQ: ZF_ERR_NUM_CSD2_MEHR_PROJ EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_CIP_FREI_FRW_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD02 block is not accessible. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD02 block does not exist. R: @CSD02 reverts to the dead state. A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CSD2_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_CIP_SUCH_FRW_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_REOR_FRW_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-89 Communication Error Codes 6A16 Hex F: 6A17 Hex F: 6A18 Hex F: 6A19 Hex F: 6A1A Hex F: 6A1B Hex F: 3-90 Unknown operating status of the @CSD02 block. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_BZS_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD02 reverts to the dead state. A: Reduce the SAVE requirement in the application EQ: ZF_ERR_NUM_CSD2_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error supplementary code bsspvw_info. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_SAVE_N_KENN EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ @CSD02 block configured in impermissible sampling time (not between 32ms and 255ms) R: @CSD02 reverts to the dead state. A: Configure the sampling time between 32ms and 255ms EQ: ZF_ERR_NUM_CSD2_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Memory assigning not possible for exception structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD02 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD2_EXC_ZU_KURZ EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD02 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD2_REORG_ZU_KURZ EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6A1C Hex F: 6A1D Hex F: 6A1E Hex F: 6A1F Hex F: 6A20 Hex F: 6A21 Hex F: 6A22 Hex F: Unknown function return value of the function zp_fb_init. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_FB_INIT_FRW_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Link type is not set to "DUST1" or "CS7". R: @CSD02 reverts to the dead state. A: Check the configured name at CTS connector; Check that block type corresponds to @CSD02 EQ: ZF_ERR_NUM_CSD2_KOP_TYP_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_ANM_FRW_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_ANM_STATUS_ERR EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ DUST1 firmware has detected an unrepairable error. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_DUST_INIT_ERR EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ DUST1 firmware has reverted to an error status or SS4 adapter module missing. R: @CSD02 reverts to the dead state. A: Install SS4 module in CS7 board; A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_DUST_TOT EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ Unknown status of the DUST1 firmware. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_ZUS_ERR EM: ZP.CSF,_CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-91 Communication Error Codes 6A23 Hex 6A24 Hex 6A25 Hex 6A26 Hex 6A27 Hex 6A28 Hex 6A29 Hex to 6A2F Hex 3-92 F: Unknown function return value of the function zp_firmware_zyklisch. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_FIRMWARE_ZYK_FRW_ERR EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ F: Memory assigning not possible for firmware structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD02 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD2_N_MEM EM: ZP.CSF, AM: _CSD02.CSF AA: 7-Seg. ’C’ F: Specification at PAR connector faulty. R: @CSD02 reverts to the dead state. A: Specification at TWU connector can only be in range 0 to 1 . EQ: ZF_ERR_NUM_CSD2_TWU_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ F: Specification at BDR connector faulty. R: @CSD02 reverts to the dead state. A: Specification at BDR connector can only correspond to one of the following baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200 EQ: ZF_ERR_NUM_CSD2_BDR_ERR EM: _CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _csd2_init. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: Z_ERR_NUM_CSD2_INIT_FRW_ERR EM: ZP.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function_csd2_firmware_init. R: @CSD02 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD2_FIR_INIT_FRW_ERR EM: ZP.CSF,_CSD02.CSF AM: _CSD02.CSF AA: 7-Seg. ’C’ not utilized General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.9.10 Link DUST3 6A30 Hex F: 6A31 Hex F: 6A32 Hex F: 6A33 Hex F: 6A34 Hex F: 6A35 Hex F: Several communication central blocks were configured with the same CS7 board names or interface names. R: @CSD03 reverts to the dead state. A: Remove one of the configured @CSD03 blocks; Correct the interface specification of one @CSD03 block EQ: ZF_ERR_NUM_CSD3_MEHR_PROJ EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_CIP_FREI_FRW_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD03 block is not accessible. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSD03 block does not exist. R: @CSD03 reverts to the dead state. A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CSD3_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_CIP_SUCH_FRW_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_REOR_FRW_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-93 Communication Error Codes 6A36 Hex F: 6A37 Hex F: 6A38 Hex F: 6A39 Hex F: 6A3A Hex F: 6A3B Hex F: 3-94 Unknown operating status of the @CSD03 block. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_BZS_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD03 reverts to the dead state. A: Reduce the SAVE requirement in the application EQ: ZF_ERR_NUM_CSD3_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ SAVE area not found. Exact cause of error see section Error supplementary code bsspvw_info. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_SAVE_N_KENN EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ @CSD03 block configured in impermissible sampling time (not between 32ms and 255ms) R: @CSD03 reverts to the dead state. A: Configure the sampling time between 32ms and 255ms EQ: ZF_ERR_NUM_CSD3_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Memory assigning not possible for exception structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD03 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD3_EXC_ZU_KURZ EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD03 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD3_REORG_ZU_KURZ EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6A3C Hex F: 6A3D Hex F: 6A3E Hex F: 6A3F Hex F: 6A40 Hex F: 6A41 Hex F: 6A42 Hex F: Unknown function return value of the function zp_fb_init. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_FB_INIT_FRW_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Link type is not set to "DUST1" or "CS7". R: @CSD03 reverts to the dead state. A: Check the configured name at CTS connector; Check that block type corresponds to @CSD03 EQ: ZF_ERR_NUM_CSD3_KOP_TYP_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_ANM_FRW_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_ANM_STATUS_ERR EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ DUST1 firmware has detected an unrepairable error. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_DUST_INIT_ERR EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ DUST1 firmware has reverted to an error status or SS4 adapter module missing. R: @CSD03 reverts to the dead state. A: Install SS4 module in CS7 board; A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_DUST_TOT EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ UInknown status of the DUST1 firmware. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_ZUS_ERR EM: ZP.CSF,_CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-95 Communication Error Codes 6A43 Hex 6A44 Hex 6A45 Hex 6A46 Hex 6A47 Hex 6A48 Hex 6A49 Hex to 6A4F Hex 3-96 F: Unknown function return value of the function zp_firmware_zyklisch. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_FIRMWARE_ZYK_FRW_ERR EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ F: Memory assigning not possible for firmware structure Exact cause of error see section Error supplementary code bsspvw_geme. R: @CSD03 reverts to the dead state. A: Reduce the RAM requirement in the application EQ: ZF_ERR_NUM_CSD3_N_MEM EM: ZP.CSF, AM: _CSD03.CSF AA: 7-Seg. ’C’ F: Specification at BCC connector faulty. R: @CSD03 reverts to the dead state. A: Specification at BCC connector can only be in range 0 to 1. EQ: ZF_ERR_NUM_CSD3_TWU_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ F: Specification at BDR connector faulty. R: @CSD03 reverts to the dead state. A: Specification at BDR connector can only correspond to one of the following baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200 EQ: ZF_ERR_NUM_CSD3_BDR_ERR EM: _CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _csd3_init. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_INIT_FRW_ERR EM: ZP.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ F: Unknown function return value of the function _csd3_firmware_init. R: @CSD03 reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSD3_FIR_INIT_FRW_ERR EM: ZP.CSF,_CSD03.CSF AM: _CSD03.CSF AA: 7-Seg. ’C’ not utilized. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 3.2.9.11 USS Link 6A50 Hex F: 6A51 Hex F: 6A52 Hex F: 6A53 Hex F: 6A54 Hex F: 6A55 Hex F: Several communication central blocks were configured with the same CS7 board names or interface names. R: @CSU reverts to the dead state A: Remove one of the configured @CSU blocks; correct the interface specification of one @CSU block. EQ: ZF_ERR_NUM_CSU_MEHR_PROJ EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_cip_freigabe. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_CIP_FREI_FRW_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSU block is not accessible. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ The CIP entry for the @CSU block does not exist. R: @CSU reverts to the dead state. A: Check the configured name at the CTS connector. EQ: ZF_ERR_NUM_CSU_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zbak_cip_suche. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_CIP_SUCH_FRW_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_dexdo_reorganization. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_DEX_REOR_FRW_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-97 Communication Error Codes 6A56 Hex F: 6A57 Hex F: 6A58 Hex F: 6A59 Hex F: 6A5A Hex F: 6A5B Hex F: 3-98 Unknown operating status of the @CSU block. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_BZS_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ SAVE memory assigning not possible for warm start flag exact cause of error see section Error supplementary code bsspvw_geme. R: @CSU reverts to the dead state. A: Reduce the SAVE requirement in the application. EQ: ZF_ERR_NUM_CSU_SAVE_ZU_KURZ EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ SAVE area not found. exact cause of error see section Error supplementary code bsspvw_info. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_SAVE_N_KENN EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ @CSU block was configured in impermissible sampling time (not between 32ms and 255ms). R: @CSU reverts to the dead state. A: Configure the sampling time between 32 ms and 255 ms. EQ: ZF_ERR_NUM_CSU_ABTASTZEIT_ERR EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Memory assigning not possible for exception structure exact cause of error see section Error supplementary code bsspvw_geme. R: @CSU reverts to the dead state. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSU_EXC_ZU_KURZ EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Memory assigning not possible for reorganization structure exact cause of error see section Error supplementary code bsspvw_geme. R: @CSU reverts to the dead state. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSU_REORG_ZU_KURZ EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6A5C Hex F: 6A5D Hex F: 6A5E Hex F: 6A5F Hex F: 6A60 Hex F: 6A61 Hex F: 6A62 Hex F: unknown function return value of the function zp_fb_init. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_FB_INIT_FRW_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ lLnk type is not set to "USS" or "CS7". R: @CSU reverts to the dead state. A: Check the configured name at CTS connector; Check that block type corresponds to @CSU. EQ: ZF_ERR_NUM_CSU_KOP_TYP_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown function return value of the function zp_anmelde_ueberwachung. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_ANM_FRW_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown register status detected in DEXDO3 management section. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_ANM_STATUS_ERR EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ USS firmware has detected an unrepairable error. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_DUST_INIT_ERR EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ USS firmware has reverted to an error status or SS4 adapter module missing. R: @CSU reverts to the dead state. A: Install SS4 module in CS7 board; A: Contact Siemens AG EQ: ZF_ERR_NUM_CSU_TOT EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown status of the USS firmware. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_ZUS_ERR EM: ZP.CSF,_CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-99 Communication Error Codes 6A63 Hex F: 6A64 Hex F: 6A65 Hex F: 6A66 Hex F: 6A67 Hex F: 6A68 Hex F: 3-100 Unknown function return value of the function zp_firmware_zyklisch. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_FIRM_ZYK_FRW_ERR EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Memory assigning not possible for firmware structure exact cause of error see section Error supplementary code bsspvw_geme. R: @CSU reverts to the dead state. A: Reduce the RAM requirement in the application. EQ: ZF_ERR_NUM_CSU_N_MEM EM: ZP.CSF, AM: _CSU.CSF AA: 7-Seg. ’C’ Specification at PPT connector faulty. R: @CSU reverts to the dead state A: Specification at PPT connector can only be in range 0 to 32767. EQ: ZF_ERR_NUM_CSU_PPT_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Specification at HCT connector faulty. R: @CSU reverts to the dead state. A: Specification at HCT connector can only be in range 0 to 32767. EQ: ZF_ERR_NUM_CSU_HCT_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Specification at BDR connector faulty. R: @CSU reverts to the dead state. A: Specification at BDR connector can only correspond to one of the following baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200,38400 EQ: ZF_ERR_NUM_CSU_BDR_ERR EM: _CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ Unknown function return value of the function _csu_init. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_INIT_FRW_ERR EM: ZP.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6A69 Hex 6A6A Hex to 6A6F Hex F: Unknown function return value of the function _csu_firmware_init. R: @CSU reverts to the dead state. A: Contact Siemens AG. EQ: ZF_ERR_NUM_CSU_FIR_INIT_FRW_ERR EM: ZP.CSF,_CSU.CSF AM: _CSU.CSF AA: 7-Seg. ’C’ not utilized. 3.2.9.12 Rack Link Fiber Optic Cable 6A90 Hex F: 6A91 Hex F: 6A92 Hex F: 6A93 Hex F: Several @CS1 blocks were configured with the same CS11/12/13/14 board names. R: @CS1 is disabled A: Reconfigure; only one @CS1 central block permitted EQ: ZF_ERR_NUM_CS1_MEHR_PROJ EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A90, pointer to configured name, 0) Unknown function return value from the function zp_cip_freigabe. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_CIP_FREI_FRW_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A91, pointer to configured name, function return value of the function zp_cip_freigabe) The CIP entry for the @CS1 block cannot be accessed. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A92, pointer to configured name, 0) The CIP entry for the @CS1 block does not exist. R: @CS1 is disabled A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CS1_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A93, pointer to configured name, 0) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-101 Communication Error Codes 6A94 Hex F: 6A95 Hex F: 6A96 Hex F: 6A97 Hex F: 6A98 Hex F: 3-102 Unknown function return value from the function zbak_cip_suche. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_CIP_SUCH_FRW_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A94, pointer to configured name, function return value of the function zbak_cip_suche) Unknown function return value from the function zp_dexdo_reorganisation. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_DEX_REOR_FRW_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A95, pointer to configured name, function return value of the function zp_dexdo_reorganisation) Unknown operating status of the @CS1 block. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_BZS_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A96, pointer to configured name, not defined) SAVE-memory create for warm start flag not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS1 is disabled A: Reduce the SAVE requirements in the application EQ: ZF_ERR_NUM_CS1_SAVE_ZU_KURZ EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A97, pointer to configured name, not defined) SAVE area not found. Precise cause of error, review section Error suppl. code bsspvw_info R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_SAVE_N_KENN EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A98, pointer to configured name, not defined) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6A99 Hex F: 6A9A Hex F: 6A9B Hex F: 6A9C Hex F: 6A9D Hex F: @CS1 block was configured in an invalid sampling time (not between 32ms and 255ms). R: @CS1 is disabled A: Configure the sampling time between 32ms and 255ms EQ: ZF_ERR_NUM_CS1_ABTASTZEIT_ERR EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’’ KFF (6A99, pointer to configured name, not defined) Memory create for exception structure not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS1 is disabled A: Reduce the RAM requirements in the application EQ: ZF_ERR_NUM_CS1_EXC_ZU_KURZ EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9A, pointer to configured name, not defined) Memory create for reorganization structure not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS1 is disabled A: Reduce the RAM requirements in the application EQ: ZF_ERR_NUM_CS1_REORG_ZU_KURZ EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9B, pointer to configured name, not defined) Unknown function return value from the function zp_fb_init. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_FB_INIT_FRW_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9C, pointer to configured name, function return value of the function zp_dexdo_reorganisation) Link type not set to "CS11/12/13/14 Rack Link". R: @CS1 is disabled A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CS1_KOP_TYP_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9D, pointer to configured name, 0) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-103 Communication Error Codes 6A9E Hex F: 6A9F Hex F: 6AA0 Hex F: 6AA1 Hex F: 6AA2 Hex F: 6AA3 Hex F: 3-104 Unknown function return value from the function zp_anmelde_ueberwachung. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_ANM_FRW_ERR EM: _CS1.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9E, pointer to configured name, function return value of the function zp_anmelde_ueberwachung) Unknown connect status in DEXDO3 management area. R: @CS1 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS1_ANM_STATUS_ERR EM: ZP.CSF AM: _CS1.CSF AA: 7-Seg. ’C’ KFF (6A9F, pointer to configured name, 0) The configured name of the @CS2 block matches another in the link. R: @CS2 is disabled A: Reconfigure; only one @CS2 central block permitted. EQ: ZF_ERR_NUM_CS2_MEHR_PROJ EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA0, pointer to configured name, 0) The CIP entry for the @CS2 block cannot be accessed. R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_CIP_NAM_KEN_N_AD EM: ZBAK.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA1, pointer to configured name, 0) The CIP entry for the @CS2 block does not exist. R: @CS2 is disabled A: Check the configured name at the CTS connector EQ: ZF_ERR_NUM_CS2_CIP_NAM_N_KENN EM: ZBAK.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA2, pointer to configured name, 0) Unknown function return value from the function zbak_cip_suche. R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_CIP_SUCH_FRW_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA3, pointer to configured name, function return value of the function zbak_cip_suche) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6AA4 Hex 6AA5 Hex 6AA6 Hex 6AA7 Hex 6AA8 Hex 6AA9 Hex not utilized F: Eight @CS2 blocks already connected in the link. R: @CS2 is disabled A: Power down rack and after 10 sec. power up again Check whether more than eight CS2 boards exist in the link or whether the @CS2 block is multiply configured on the same CS21/22 board EQ: ZF_ERR_NUM_CS2_SCHON_ACHT_CS22 EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA5, pointer to configured name, 0) F: The configured CS11/12/13/14 board does not exist. R: @CS2 is disabled A: Check the configured CS11/12/13/14 name at the MTS connector EQ: ZF_ERR_NUM_CS2_CS1_N_KENN EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’’ KFF (6AA6, pointer to configured name, 0) F: Unknown function return value from the function _cs2_anmeldung. R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_ANM_FRW_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA7, pointer to configured name, function return value of the function _cs2_anmeldung) F: Unknown operating status of the @CS2 block. R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_BZS_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA8, pointer to configured name, faulty operating status) F: SAVE-memory create for warm start flag not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS2 is disabled A: Reduce the SAVE requirements in the application EQ: ZF_ERR_NUM_CS2_SAVE_ZU_KURZ EM: ZP.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AA9, pointer to configured name, not defined) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-105 Communication Error Codes 6AAA Hex 6AAB Hex 6AAC Hex 6AAD Hex 6AAE Hex 6AAF Hex to 6AB0 Hex 3-106 F: SAVE area not found. Precise cause of error, review section Error suppl. code bsspvw_info R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_SAVE_N_KENN EM: ZP.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AAA, pointer to configured name, not defined) F: @CS2 block was configured in an invalid sampling time (not between 32ms and 255ms) or the sampling time of the @CS1 does not fit. R: @CS2 is disabled A: Configure the sampling time between 32ms and 255ms or check the sampling time of the @CS1 EQ: ZF_ERR_NUM_CS2_ABTASTZEIT_ERR EM: ZP.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AAB, pointer to configured name, 0) F: Memory create for exception structure not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS2 is disabled A: Reduce the RAM requirements in the application EQ: ZF_ERR_NUM_CS2_EXC_ZU_KURZ EM: ZP.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AAC, pointer to configured name, not defined) F: Memory create for reorganization structure not possible Precise cause of error, review section Error suppl. code bsspvw_geme R: @CS2 is disabled A: Reduce the RAM requirements in the application EQ: ZF_ERR_NUM_CS2_REORG_ZU_KURZ EM: ZP.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AAD, pointer to configured name, not defined) F: Unknown function return value from the function zp_fb_init. R: @CS2 is disabled A: Inform Siemens AG. EQ: ZF_ERR_NUM_CS2_FB_INIT_FRW_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’’ KFF (6AAE, pointer to configured name, function return value of the function zp_fb_init) not utilized General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 6AB1 Hex F: 6AB2 Hex F: 6AB3 Hex F: 6AB4 Hex F: Link type not set to "CS22 Rack Link in the expanded address area" or "CS22 Rack Link in the special peripherals area". R: @CS2 is disabled A: Check the configured name at the CTS connector otherwise inform Siemens AG. EQ: ZF_ERR_NUM_CS2_KOP_TYP_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AB1, pointer to configured name, 0) Three @CS2 blocks already connected in the link. R: @CS2 is disabled A: Power down rack and after 10 sec. power up again Check whether more than three CS21 boards exist in the link or whether the @CS2 block is multiply configured on the same CS21 board EQ: ZF_ERR_NUM_CS2_SCHON_DREI_CS21 EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AB2, pointer to configured name, 0) The software version on the processor board is not compatible with the version in the CS11/12/13/14 rack. R: @CS2 is disabled A: Check the versions in all the connected racks, otherwise inform Siemens AG. EQ: ZF_ERR_NUM_CS2_VERSION_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AB3, pointer to configured name, 0) Memory size of the CS22 and the CS12/13/14 do not match R: @CS2 is disabled A: Check the EMA connectors on the CS12/13/14-IB or CS22-IB, otherwise inform Siemens AG. EQ: ZF_ERR_NUM_CS2_MEM_SIZE_ERR EM: _CS2.CSF AM: _CS2.CSF AA: 7-Seg. ’C’ KFF (6AB4, pointer to configured name, 0) General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-107 Communication Error Codes 3.2.10 Gerätekopplung und Parameterbearbeitung auf T400 7C00 Hex F: R: A: EQ: EM: AM: Parameternummer ist nicht vorhanden Auftrag wird nicht ausgeführt Parameternummer überprüfen ZF4_GER_ERR_PRP_NO_PARA_NR zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 0 7C01 Hex F: R: A: EQ: EM: AM: PEN-Eingang erlaubt keine Änderung der Parameter Parameter wird nicht geändert FB-@DRIVE, Eingang PEN auf 1 setzen ZF4_GER_ERR_PRP_NO_PEN zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 1 7C02 Hex F: R: A: MIN- / MAX-Grenze ueberschritten Parameter wird nicht geändert Wert für Parameterauftrag so ändern, daß er innerhalb der Grenzwerte liegt. Oder Grenzwerte ändern, falls Grenzwerte über PLIM-Bausteine festgelegt wurden, und RESET der T400. ZF4_GER_ERR_PRP_OFF_LIMIT zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 2 EQ: EM: AM: R: A: EQ: EM: AM: Keine gueltiger Parameterauftrag, Auftragsnummer und Parameternummer konnten nicht aus der Parameter ID bestimmt werden. Auftrag wird nicht bearbeitet Parameter ID überprüfen und gültige Parameter ID angeben ZF4_GER_ERR_PRP_NO_PARA_ID zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 3 7C05 Hex F: R: A: EQ: EM: AM: Ungueltiger Datentyp Auftrag wird nicht ausgeführt Gültigen Datentyp für Parameterauftrag verwenden ZF4_GER_ERR_PRP_ILLEGAL_DATA_TYPE zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 5 7C12 Hex F: R: A: EQ: EM: AM: Parameter auf einem Ausgang ist nicht änderbar Auftrag wird nicht ausgeführt Parameter auf einen Eingang projektieren ZF4_GER_ERR_PRP_NO_INPUT zf4ger.csf _drive.csf, YTx, Parameterrückgabewert 18 7C03 Hex 3-108 F: General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 7C66 Hex F: R: A: EQ: EM: AM Schreibschutz der Speicherkarte ist eingelegt Abspeichern in das EEPROM ist nicht möglich. Siemens AG benachrichtigen ZF4_GER_ERR_PRP_SAVE_PROTECT zf4ger.csf _drive.csf, YTx, Fehlernummer wird als zusätzlicher Parameterrückgabewert bei der Auftragsantwort mit zurückgesendet. 7C70 Hex F: R: A: EQ: EM: AM: Kanalzustand ist AUS aufgrund Baugruppen-Konfiguration Keine weitere Bearbeitung Überprüfen, ob die Baugruppen richtig gesteckt sind ZF4_GER_ERR_PRP_KAN_ZUS_OFF zf4ger.csf _drive.csf, YTx 7C72 Hex F: R: Funktionsbaustein ist mehrfach projektiert Eintrag ins Kommunikationsfehlerfeld, Baustein wird abgeschaltet Funktionsbaustein nur einmal projektieren ZF4_GER_ERR_MEHRFACH _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf A: EQ: EM: AM: 7C7A Hex F: R: A: EQ: EM: AM: 7C7B Hex F: R: A: EQ: EM: AM: 7C7E Hex F: R: A: EQ: EM: AM: Abtastzeit nicht 10 .. 200ms Eintrag ins Kommunikationsfehlerfeld, Baustein wird abgeschaltet Abtastzeit ändern, so daß sie zwischen 10 ms und 200 ms liegt. ZF4_GER_ERR_ABTASTZEIT _drive.csf _drive.csf, YT1 Fehler bei der Speicherbeschaffung Eintrag ins Kommunikationsfehlerfeld, Baustein wird abgeschaltet Siemens AG benachrichtigen ZF4_GER_ERR_GEME _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf Zusatzinformation im Kommunikationsfehlerfeld: Rückgabewert der Funktion bsspvw_geme ungueltiges Request-Buffer-Status-Byte Paramterkanal wird nicht bearbeitet. Hardware überprüfen, Siemens AG benachrichtigen ZF4_GER_ERR_PRP_RQU_BUFFER zf4ger.csf _drive.csf, YT1 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-109 Communication Error Codes 7C7F Hex F: R: A: EQ: EM: AM: kein Zugriff auf Reply-Buffer möglich Paramterkanal wird nicht bearbeitet. Hardware überprüfen, Siemens AG benachrichtigen. ZF4_GER_ERR_PRP_RPL_NO_ACC zf4ger.csf _drive.csf, YTx 7C80 Hex F: R: A: EQ: EM: AM: ungueltiges Reply-Buffer-Status-Byte Paramterkanal wird nicht bearbeitet. Hardware überprüfen, Siemens AG benachrichtigen. ZF4_GER_ERR_PRP_RPL_BUFFER zf4ger.csf _drive.csf, YTx 7C81 Hex F: R: A: EQ: EM: AM: Vorheriger Speicherauftrag noch in Arbeit. Auftrag wird nicht ausgeführt. Auftrag wiederholen. ZF4_GER_ERR_PRP_SAVE_BUSY zf4ger.csf _drive.csf, Ytx Fehlernummer wird als zusätzlicher Parameterrückgabewert bei der Auftragsantwort mit zurückgesendet. 7C83 Hex F: R: A: EQ: EM: AM: Kanalkennung fehlerhaft Paramterkanal wird nicht bearbeitet. Hardware überprüfen, Siemens AG benachrichtigen. ZF4_GER_ERR_PRP_NO_KAN_KNG zf4ger.csf _drive.csf, YTx 7C84 Hex F: Parameterfunktion nicht implementiert, Parameter Auftragsnumer ist ungültig oder Parameterauftrag kann auf der T400 nicht bearbeitet werden. Paramterauftrag wird nicht ausgeführt. Gültigen Parameterauftrag projektieren. ZF4_GER_ERR_PRP_NO_PKW zf4ger.csf _drive.csf, YTx, Parameterrückgabewert R: A: EQ: EM: AM: 7C8D Hex F: R: A: EQ: EM: AM: 3-110 Fehler bei der Übertragung neuer Konfigurationsdaten zum Comboard kein Datenaustausch zum Comboard. An Baseboard oder FB CBCONF andere Konfigurationsdaten für Comboard einstellen und diese zum Comboard übertragen. ZF4_GER_ERR_CBCONF _drive.csf _drive.csf, cbconf.csf, YTS General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 7C8F Hex F: R: A: EQ: EM: AM: A: EQ: EM: AM: Parametertabelle ist nicht vorhanden Eintrag ins Kommunikationsfehlerfeld, Baustein wird abgeschaltet Siemens AG benachrichtigen ZF4_GER_ERR_PRP_PTAB _drive.csf _drive.csf, YT1 7C93 Hex F: R: A: EQ: EM: AM: Request-Buffer-Channel-Control is OFF Parameterkanal wird nicht bearbeitet Kommunikationpartner überprüfen. ZF4_GER_ERR_PRP_RQU_CC_OFF zf4ger.csf _drive.csf, YTx 7C94 Hex F: R: A: EQ: EM: AM: kein Zugriff auf Request-Buffer möglich Parameterkanal wird nicht bearbeitet Kommunikationpartner überprüfen. ZF4_GER_ERR_PRP_RQU_NO_ACC zf4ger.csf _drive.csf, YTx 7C95 Hex F: R: A: EQ: EM: AM: Reply-Buffer-Channel-Control is OFF Parameterkanal wird nicht bearbeitet Kommunikationpartner überprüfen. ZF4_GER_ERR_PRP_RPL_CC_OFF zf4ger.csf _drive.csf, YTx 7C97 Hex F: R: A: EQ: EM: AM: Auf Parameterantwort vom anderen Board warten. Auf Parameterantwort vom anderen Board warten. Überprüfen, ob anderes Board korrekt arbeitet. ZF4_GER_ERR_PRP_RPL_WAIT zf4ger.csf _drive.csf, YT5 7C98 Hex F: R: Timeout beim Warten auf Parameterantwort vom anderen Board Parameterantwort „Auftrag konnte nicht ausgeführt werden“ mit Zusatzinformation „Timeout beim Warten auf Quittung vom anderen Board“ wird gesendet Überprüfen, ob anderes Board korrekt arbeitet. ZF4_GER_ERR_PRP_RPL_WAITOUT zf4ger.csf _drive.csf, YT5 7C92 Hex F: R: Falsche Baugruppe rechts Eintrag ins Kommunikationsfehlerfeld, Baustein wird abgeschaltet Anderen Baugruppe rechts verwenden ZF4_GER_ERR_KOPP_R _drive.csf _drive.csf, YT1 A: EQ: EM: AM: General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-111 Communication Error Codes 7C9C Hex F: R: A: EQ: EM: AM: Speicherkarte ist nicht „SIMADYN D konform“ Parameterauftrag wurde nicht ausgeführt Siemens AG benachrichtigen ZF4_GER_ERR_PRP_SAVE_NONCOMP zf4ger.csf _drive.csf, YTx, als Parameterrückgabewert 7C9D Hex F: R: A: EQ: EM: AM: Speicherkarte wurde beim letzten Schreibvorgang defekt. Alle weiteren Versuch zu schreiben sind zwecklos Parameterauftrag wurde nicht ausgeführt Siemens AG benachrichtigen ZF4_GER_ERR_PRP_SAVE_DEFECT zf4ger.csf _drive.csf, YTx, als Parameterrückgabewert 7C9E Hex F: R: A: EQ: EM: AM: Speicherplatz im EEPROM ist nicht ausreichend Parameterauftrag wurde nicht ausgeführt keine ZF4_GER_ERR_PRP_SAVE_NO_SPACE zf4ger.csf _drive.csf, YTx, als Parameterrückgabewert 7CA1 Hex F: Konvertierung von Float auf I4 hat fehlgeschlagen, Float -Zahl war zu groß Parameterauftrag wird nicht ausgeführt. kleinere Float-Zahlen im Parameterauftrag versenden, Parameterkanal verwenden, über den Float-Zahlen versendet werden können (siehe PCF-/PTF-Eingang am FB @Drive) ZF4_GER_ERR_PRP_NO_KONV_NFI4 zf4ger.csf _drive.csf, Ytx Fehlernummer wird als zusätzlicher Parameterrückgabewert bei der Auftragsantwort mit zurückgesendet. R: A: EQ: EM: AM: 7CA6 Hex F: R: A: EQ: EM: AM: 7CA7 Hex 3-112 F: R: A: EQ: EM: AM: Zentralbaustein FB-@Drive fehlt Eintrag ins Kommunikationsfehlerfeld, Abschaltung des suchenden Bausteins FB @Drive projektieren ZF4_GER_ERR_N_DRIVE zf4ger.csf, pname.csf, ptrans.csf, cbconf.csf, tfaw.csf, rfaw.csf pname.csf, plim.csf, plim_i.csf, plim_d.csf, ptrans.csf, cbconf.csf, tfaw.csf, rfaw.csf YTS-Ausgänge Kanal fehlerhaft Kommunikation wird abgebrochen Board überprüfen, Siemens AG benachrichtigen ZF4_GER_ERR_PKZ_BREAK zf4ger.csf, ptrans.csf tfaw.csf, ptrans.csf -- YTS-Ausgänge General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Communication Error Codes 7CAB Hex F: R: A: EQ: EM: AM: 7CAC Hex F: R: A: EQ: EM: AM: 7CAD Hex F: R: A: EQ: EM: AM: 7CAE Hex F: R: A: EQ: EM: AM: 7CAF Hex F: R: A: EQ: EM: AM: Parameter zur projektierten Nummer ist ein Beobachtungsparamter (Ausgang) Grenzwerte werden nicht in die Parametertabelle eingetragen, Eintrag in das Fehlerfeld Parameter an einem Eingang projektieren ZF4_PLIM_ERR_NO_WRITE zf4ger.csf plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang Parameter zur projektierten Nummer ist nicht vorhanden Grenzweret können nicht in die Parametertabelle eingetragen werden, Eintrag in das Fehlerfeld Vorhandene Parameternummer projektieren ZF4_PLIM_ERR_NO_PARAM_NR zf4ger.csf plim.csf, plim_i.csf , plim_d.csf -- YTS- Ausgang Datentypen sind nicht identisch Grenzwerte für Parameternummer werden nicht aktiv, Eintrag in das Fehlerfeld Richtigen PLIM-Baustein verwenden ZF4_PLIM_ERR_NO_DATA_TYPE plim.csf, plim_i.csf, plim_d.csf plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das Fehlerfeld Fehler bei der Bestimmung der Skalierungsfaktoren der MIN- / MAX-Eingänge Grenzwerte werden nicht aktiv Siemens AG benachrichtigen ZF4_PLIM_ERR_MINMAX plim.csf plim.csf -- YTS- Ausgang Eintrag in das Fehlerfeld, Zusatz: Funktionsrückgabewert der Funktion sda_func_afpi_suche_fbk_nr oder sda_func_afpi_fbk_kbs Minimum ist größer als Maximum Grenzwerte werden nicht aktiv Eingänge MIN, MAX korrigieren ZF4_PLIM_ERR_MINMAX plim.csf, plim_i.csf, plim_d.csf plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das Fehlerfeld General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 3-113 Communication Error Codes 7CB0 Hex F: R: A: EQ: EM: AM: R: A: EQ: EM: AM: Funktionsbaustein kann wg. Hardwarekonfiguration nicht verwendet werden Funktionsbaustein schaltet sich ab. Baustein nur projektieren, wenn Konfiguration dies zulässt ZF4_GER_ERR_FB_FE_KOPPZUS cbconf.csf, tfaw.csf, rfaw.csf cbconf.csf, tfaw.csf, rfaw.csf -- YTx-Ausgänge 7CB4 Hex F: R: A: EQ: EM: AM: Initialisierung des Funktionsbausteins läuft (temporärer Zustand) warten ZF4_GER_ERR_FB_INI cbconf.csf, tfaw.csf, rfaw.csf cbconf.csf, tfaw.csf, rfaw.csf - YTx-Ausgänge 7CB5 Hex F: R: A: keine Kommunikation mit Kommunikationspartner Es findet keine Übertragung der Fehler und Warnungen statt. Kommunikationspartner überprüfen, Siemens AG benachrichtigen ZF4_GER_ERR_FAW_N_COM tfaw.csf, rfaw.csf tfaw.csf, rfaw - YTx-Konnektoren 7CB3 Hex F: T400 ist nicht als Techboard projektiert Abschaltung des Bausteins und Eintrag in das Kommunikationsfehlerfeld T400 am FB @DRIVE als Techboard projektieren (Eingang BBF=0) ZF4_PTRANS_ERR_NO_T400 ptrans.csf ptrans.csf- YTx-Konnektoren EQ: EM: AM: 7CB6 Hex F: R: A: EQ: EM: AM: 3-114 kein Zugriff auf Kanal möglich Es findet keine Übertragung der Fehler und Warnungen statt. Kommunikationspartner überprüfen, Siemens AG benachrichtigen ZF4_GER_ERR_FAW_N_CHANNEL_ACCESS tfaw.csf, rfaw tfaw.csf, rfaw.csf - YTx-Konnektoren General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 4 Error Supplementary Codes This chapter describes the error supplementary codes to the individual error codes. Which supplementary codes exist for which error codes is indicated in the description of the corresponding error codes. An error supplementary code does not automatically exist for each error code. 4.1 01 Hex Supplementary code "bsspvw_geme" F: R: A: EQ: EM: AM: AA: R: A: EQ: EM: AM: AA: Memory object ID points to a memory object that does not exist in the rack. Required memory was not set. Contact Siemens AG . SDB_FRW_BSSPVW_GEME_SOK_NEXIST BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 03 Hex F: R: A: EQ: EM: AM: AA: The free memory space on the memory object is not sufficient. Required memory was not set. Free up memory space on the memory object by reconfiguring. SDB_FRW_BSSPVW_GEME_SP_ZUKLEIN BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 04 Hex F: R: A: EQ: EM: AM: AA: The memory object is currently blocked by another user. Required memory was not set. Wait state. SDB_FRW_BSSPVW_GEME_SO_KZUGR BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 02 Hex F: Memory object ID impermissible. (permissible memory object ID’s are PN local RAM, slots 1...24, PN local SAVE area, L bus coupling memory and C bus coupling memory). Required memory was not set. Contact Siemens AG . SDB_FRW_BSSPVW_GEME_SOK_UNZ BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. Fehler! Datei kann nicht geöffnet werden.- Fehler! Datei kann nicht geöffnet werden.- Fehler! Datei kann nicht geöffnet werden. Fehler! Datei kann nicht geöffnet werden. Fehler! Datei kann nicht geöffnet werden. 4-1 Error Supplementary Codes R: A: EQ: EM: AM: AA: Required memory distribution is impermissible. (permissible memory distribution is either word wise or paragraph wise). Required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_GEME_SOM_UNZ BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 06 Hex F: R: A: EQ: EM: AM: AA: System bus access error Required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_GEME_BUS BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 07 Hex F: R: A: EQ: EM: AM: AA: RAM drive access error. Required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_GEME_RAM BSSPVW.CSF Block that invokes the function bsspvw_geme. Block dependent. 05 Hex 4.2 01 Hex F: Supplementary code "bsspvw_info" F: R: A: EQ: EM: AM: AA: 02 Hex F: R: A: EQ: EM: AM: AA: 4-2 Memory object ID impermissible. (permissible memory object ID’s are PN local RAM, slots 1...24, PN local SAVE area, L bus coupling memory and C bus coupling memory.) The address of the required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_INFO_SOK_UNZ BSSPVW.CSF Block that invokes the function bsspvw_info. Block dependent. Memory object ID points to a memory object that does not exist in the rack. Required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_INFO_SOK_NEXIST BSSPVW.CSF Block that invokes the function bsspvw_info. Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Error Supplementary Codes 03 Hex 04 Hex 4.3 31 Hex F: R: A: EQ: EM: AM: AA: The required list does not exist. The address of the required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_INFO_SON_NEXIST BSSPVW.CSF Block that invokes the function bsspvw_info. Block dependent. F: R: A: EQ: EM: AM: AA: System bus access error The address of the required memory was not set. Contact Siemens AG. SDB_FRW_BSSPVW_INFO_BUS BSSPVW.CSF Block that invokes the function bsspvw_info. Block dependent. Supplementary code "zbin_komdat" F: R: A: EQ: EM: AM: AA: 32 Hex F: R: A: EQ: EM: AM: AA: 33 Hex F: R: A: type EQ: EM: AM: AA: Memory assigning for KOMDAT structure temporarily not possible. Exact cause of error see section Error supplementary code bsspvw_geme. KOMDAT area is not set. Repeat the function invocation Z_FRW_ZBIN_N_ANM ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. Memory assigning for KOMDAT structure not possible exact cause of error see section Error supplementary code bsspvw_geme. KOMDAT area is not set. Reduce the RAM requirement in the application Z_FRW_ZBIN_GEME_AUFRUF_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. Transmit/receive ID in transfer structure of the function incorrect. KOMDAT area is not set. The value in transmit / receive ID must correspond to the ENUM z_kenn_val Z_ZBIN_DIR_KENN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 4-3 Error Supplementary Codes 34 Hex F: R: A: EQ: EM: AM: AA: EQ: EM: AM: AA: The configuring specifications consist of more than 3 components but is not identifiable as a destination specification. KOMDAT area is not set. When no destination is configured at AT / AR /US connector, then the specification may consist of a maximum of three components (channel name, address stage 1, address stage 2; when a destination is configured at AT / AR / US connector, then the specification of the destination rack name must start with an "@"). Z_ZBIN_ZIEL_N_KENN ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. 36 Hex F: R: A: EQ: EM: AM: AA: Configured destination specification is incorrect. KOMDAT area is not set. Only configure a "@" at AT / AR / US connector. Z_ZBIN_ZIEL_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. 37 Hex F: R: A: Configured channel name is too long. KOMDAT area is not set. Channel name first sub?specification at AT / AR / US connector) may be a maximum of 8 characters long. Z_ZBIN_KAN_NAM_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. 35 Hex F: The number of components (separated by a dot) of the configuring specification is larger than 6. KOMDAT area is not set. The specification at AT / AR / US connector may only have a maximum of 6 components. Z_ZBIN_TEIL_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. R: A: EQ: EM: AM: AA: 38 Hex F: R: A: EQ: EM: AM: AA: 4-4 Configured address stage 1 is too long. KOMDAT area is not set. Address stage 1 (second sub?specification at AT / AR / US connector) may be a maximum of 14 characters long. Z_ZBIN_ADR_STUF1_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 Error Supplementary Codes 39 Hex F: R: A: EQ: EM: AM: AA: 3A Hex F: R: A: EQ: EM: AM: AA: 3B Hex F: R: A: EQ: EM: AM: AA: 3C Hex F: R: A: EQ: EM: AM: AA: 3D Hex F: R: A: EQ: EM: AM: AA: 3E Hex F: R: A: EQ: EM: AM: AA: Configured address stage 2 is too long. KOMDAT area is not set. Address stage 2 (third sub?specification at AT / AR / US connector) may be a maximum of 20 characters long. Z_ZBIN_ADR_STUF2_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. The configured destination specification is located in the incorrect section of the string. KOMDAT area is not set. The "@" is only permitted to be at start of the second or third last sub?specification at the AT / AR / US connector. Z_ZBIN_STRING_ERR ZBIN.CSF Block that invokes the function zbin_komdat Block dependent. Configured destination rack is too long. KOMDAT area is not set. Destination rack name (first sub?specification after the "@" at the AT / AR / US connector) must be up to 6 characters long. Z_ZBIN_ZBGT_NAM_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. Configured destination board name length is incorrect. KOMDAT area is not set. Destination board name (second sub?specification after the "@" at the AT / AR / US connector) must be exactly 6 characters long. Z_ZBIN_ZBG_NAM_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. Configured destination interface length is incorrect. KOMDAT area is not set. Destination board name (third sub?specification after the "@" at the AT / AR / US connector) must be exactly 3 characters long. Z_ZBIN_ZSS_LEN_ERR ZBIN.CSF Block that invokes the function zbin_komdat Block dependent. Configured destination interface is incorrect. KOMDAT area is not set. Only the following interface specifications are permitted: "X01", "X02", "X03". Z_ZBIN_ZSS_NAM_ERR ZBIN.CSF Block that invokes the function zbin_komdat. Block dependent. General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 4-5 Error Supplementary Codes 4.4 Supplementary code "zgsd_zini_nachtrag" 02 Hex F: R: A: EQ: EM: AM: AA: ZINI list is already full Data interface cannot be initialized. Reduce the number of data interfaces SDZ_FRW_ZG_ZINI_ZU_KURZ ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 03 Hex F: R: A: EQ: EM: AM: AA: Incorrect bus access Data interface cannot be initialized. Check hardware or inform Siemens AG. SDZ_FRW_ZG_BUS_ACC_ERR ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 04 Hex F: R: A: EQ: EM: AM: AA: ZINI list is already full Data interface cannot be initialized. Reduce the number of data interfaces SDZ_FRW_ZG_ZINI_VOLL ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 05 Hex F: R: A: EQ: EM: AM: AA: Impermissible board name Data interface cannot be initialized. Check CTS connector SDZ_FRW_ZG_BG_NAM_ERR ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 07 Hex F: R: A: EQ: EM: AM: AA: ZINI list not found Data interface cannot be initialized. Inform Siemens AG. SDZ_FRW_ZG_ZINI_N_FOUND ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 08 Hex F: R: A: EQ: EM: AM: AA: Slot cannot be found Data interface cannot be initialized. Inform Siemens AG. SDZ_FRW_ZG_NO_STPL_NR ZGSD.CSF Block that invokes the function zgsd_zini_nachtrag Block dependent 4-6 General diagnostics - SIMADYN D - Reference Manual 6DD1987-1BA0 Edition 10.97 To Siemens AG A&D LD R Frauenauracher Straße 80 91056 Erlangen From Your Name: Your Function Your Company: Street: City: Telephone: Please indicate your particular industrial sector: o o o o o o o Automobile industry Chemical industry Electrical industry Foodstuff industry Process control Machine construction o o o o o o Pharmaceutical industry Plastic processing Paper industry Textile industry Transport Others _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Petrochemical " Basissoftware for D7-SYS - SIMADYN D - Manual 6DD1987-1BA2 Edition 01.99 1 Recommendations and comments on the User Documentation Your comments and recommendations help us to improve the quality and usefulness of our documentation. Please complete this form at the next convenient opportunity and return it to Siemens. Please give us your own personal opinion to the following questions, values from 1 = good to 5 = poor. 1. Do the contents of the documentation fulfill your requirements? 2. Can you easily find the information you require? 3. Is the text easy to understand? 4. Do we go into enough technical details for your requirements? 5. How do you evaluate the quality of the diagrams and tables? 6. 7. 8. If you come across any problems, please let us know in the space below: 2 Basissoftware for D7-SYS - SIMADYN D - Manual 6DD1987-1BA2 Edition 01.99