REFRGERATION ENGINEERING AUTOMATION IN REFRIGERATION CYCLE Võ Lưu Lan Vi – 1552428 Lại Đỗ Tuấn Hùng – 1552153 Nguyễn Minh Anh – 1552023 Huỳnh Huy Phương Tường – 1552421 CONTENT 1. Fundamentals of Automation in Refrigeration cycle • 1.1. Introduction • 1.2. Classification • 1.3. Introduction to a Typical Automation System for Refrigeration Cycle 2. Automation in Refrigeration cycle • 2.1. Automation in Compressor • 2.2. Automation in Condenser • 2.3. Automation in Evaporator 1. Fundamentals of Automation in Refrigeration cycle 1.1. Introduction FUNDAMENTALS 1.1. Introduction Using additional equipment What is Automation in Refrigeration system?? Programmed settings Safely & Automatically Optimized working condition 1.1. Introduction FUNDAMENTALS Maintain operating parameters within an acceptable limit Protect operators from risks during operation Advantage s Keep the system working stable • • • • • More reliable than manual operation Increase system efficiency Product quality Equipment lifespan Accuracy Energy loss Operating cost 1.1. Introduction FUNDAMENTALS Hardware components “Control loops” Software components Adjust & Measure process variables: temp.,pressure... FUNDAMENTALS 1.1. Introduction “Open-loop control system” • Non-feedback system • Continuous control system: output has no influence on control action of input • Disadvantage: Poor to handle with disturbances Example: FUNDAMENTALS 1.1. Introduction “Closed-loop control system” • Feedback control system • An error signal = reference input – actual output is generated to achieve desired output condition • Advantage: Sensitive to disturbance reduce error Example: error signal = required dryness – actual dryness 1. Fundamentals of Automation in Refrigeration cycle 1.2. Classification FUNDAMENTALS 1.2. Classification Operating parameters Principle • Mechanical • Electrical • Mechanical & Electrical combined • • • • Pressure Temperature Humidity Liquid level Adjustment techniques • Continuous control: P, PI, PID P:Proportional I: Intergrative D: Derivative • 2-point control (ON-OFF) Drive mechanism • Direct: mechanical (valve...) • Indirect: energy (electrical, electronic, compressed air...) Objective • Systematic: refrigerator, heat pump, air con. • Equipment: compressor, condenser, evaporator,.. . 1. Fundamentals of Automation in Refrigeration cycle 1.3. Introduction to a Typical Automation System for Refrigeration Cycle FUNDAMENTALS 1.3. Introduction to a Typical Automation System for Refrigeration Cycle Compressor controls: Oil temp; Suction press; Discharge press; Oil mass flowrate... Condenser controls: - Water cooled condenser controls: condensing pressure, cooling water flowrate. - Air cooled condenser controls: air flowrate, minimum condensing pressure. - Liquid level inside condenser. Evaporator controls: evaporating temperature, evaporating pressure, 2. Automation in Refrigeration cycle 2.1. Automation in Compressor AUTOMATION IN REF. CYCLE 2.1. Automation in Compressor Compressor Controls 1. Compressor Capacity Controls 2. Discharge Temperature Control with Liquid Injection 3. Suction Pressure Control 4. Reverse Flow Control 2.1. Automation in Compressor 2.1.1. Compressor Capacity Controls • Step Control to unload cylinders in a multi-cylinder compressor to open and close the suction ports of a screw compressor to start and stop some compressors in a multicompressor system. 2.1. Automation in Compressor 2.1.1. Compressor Capacity Controls • Variable Speed Control A two-speed electric motor or a frequency converter can be used to vary the speed of the compressor. Compressor capacity can be regulated by running at the high speed when the heat load is high (e.g. cooling down period) and at the low speed when the heat load is low (e.g. storage period). 2.1. Automation in Compressor 2.1.1. Compressor Capacity Controls • Hot Gas Bypass ‐ Is applicable to compressors with fixed capacities. ‐ Part of the hot gas flow on the discharge line is bypassed into the low pressure circuit. ‐ Help decreasing the refrigeration capacity in two ways: by diminishing the supply of liquid refrigerant and releasing some heat into the low pressure circuit 2.1. Automation in Compressor 2.1.2. Discharge Temperature Control with Liquid Injection Liquid refrigerant from the outlet of the condenser or receiver is injected into the suction line, the intermediate cooler, or the side port of the screw compressor. 2.1. Automation in Compressor 2.1.3. Suction Pressure Control 2 ways to overcome overloading in compressor: Start the compressor at part load. The capacity control methods can be used to start compressor at part load Install a back pressure controlled regulating valve in the suction line. 2.1. Automation in Compressor 2.1.4. Reverse Flow Control • For piston compressors, reverse flow can result in liquid hammering. • For screw compressors, reverse flow can cause reversed rotation and damage to the compressor bearings. To avoid this reverse flow, it is necessary to install a check valve on the outlet of the oil separator. 2. Automation in Refrigeration cycle 2.1. Automation in Condenser AUTOMATION IN REF. CYCLE 2.2. Automation in Condenser Why Condenser need automation control? • To control the condenser capacity when the ambient temperature is low Condensing pressure is maintained above the minimum acceptable level • To save cooling water for water cooled condensers AUTOMATION IN REF. CYCLE 2.2. Automation in Condenser Air cooled condenser Water cooled condenser Evaporative condenser 2.2. Automation in Condenser 2.2.1.Air cooled condenser Refrigerant control Air control 2.2. Automation in Condenser 2.2.1.Air cooled condenser Refrigerant control 2.2. Automation in Condenser 2.2.1.Air cooled condenser Air control The sensor of temperature role If the temperature decrease (lower than setting value) First fan will be switched off. The temperature continue to decrease (lower than setting value of the second fan) Second fan will be switched off. 2.2. Automation in Condenser 2.2.1.Air cooled condenser Air control Orientation setting values: • The last fan has the lowest temperature, and the first one is the highest. • Setting temperature range should be divided equally by the number of fans of the condenser. • Condensing temperature usually higher than the ambient temperature about 15oC. 2.2. Automation in Condenser 2.2.2. Water cooled condenser 2.2. Automation in Condenser 2.2.3. Evaporative condensers 2. Automation in Refrigeration cycle 2.3. Automation in Evaporator 2.3. Automation in Evaporator 2.3.1. Direct expansion control Thermostatic expansion control 2.3. Automation in Evaporator 2.3.1. Direct expansion control Electronic expansion control ả 2.3. Automation in Evaporator 2.3.2. Pumped liquid circulation control 2.3. Automation in Evaporator 2.3.3. Defrost • Hot gas defrost for DX evaporator 2.3. Automation in Evaporator 2.3.3. Defrost • Hot Gas Defrost for Pumped Liquid Circulation Air Coolers 2.3. Automation in Evaporator 2.3.4. Multi temperature changeover S2: CVP is preset to 3.6 bar, and P: CVP is preset to 4.4 bar. I: EVM pilot opens. Hence the evaporating pressure is controlled by S2: CVP. II: EVM pilot closes. Hence the evaporating pressure is controlled by P: CVP 2.3. Automation in Evaporator 2.3.5. Media temperature control • Media temperature control using pilot operated valve ICS 2.3. Automation in Evaporator 2.3.5. Media temperature control • Media temperature control using direct operated valve 2.3. Automation in Evaporator SUMMARY 2.3. Automation in Evaporator SUMMARY FOR LISTENING