Journal of Power Electronics, to be published 1 The Control Strategy Design of Grid-Connected and Stand-Alone Single-Phase Inverter for Distributed Generation Fenghuang Cai†***, Dexiang Lu*, Qiongbin Lin*,**, and Wu Wang*,** †* School of Electrical Engineering and Automation, Fuzhou University, Fuzhou, China Research Center for Advanced Process Control, Fuzhou University, Fuzhou, China. *** Fujian Key Laboratory of New Energy Generation and Power Conversion, Fuzhou University, Fuzhou, China ** Abstract A dual-mode photovoltaic power system should be able to operate in grid-connected (GC) and stand-alone (SA) modes for distributed generation. In different working modes, the optimal parameters of the inverter output filter are different. Since the inverter operates more time in the GC mode, a smaller capacitance is beneficial to the GC topology for reasonable compromise. In the GC mode, a predictive current control scheme is proposed to control the grid current to obtain a high-performance power quality. Notice that the filter is not optimal in the SA mode. Then, a compound control strategy, consisting of predictive current control, instantaneous voltage control and repetitive control (RC), is proposed to achieve low total harmonic distortion and thus improve the output voltage spectrum. The detailed process of the seamless transfer between GC and SA is illustrated. Finally, simulation and experimental results of a 4kVA prototype demonstrate the effectiveness of the proposed control strategy. Key words: Distributed generation (DG), Grid-connected, Predictive current control, Repetitive control, Single-phase inverter, Stand-alone power supply I. INTRODUCTION During the two past decades, some renewable energy technologies have been proposed to relieve the environmental pollution problems and to achieve social sustainable development [1], [2]. Renewable energies, including photovoltaic power energy, wind energy, etc., have been widely applied to distributed generation (DG) installations [3]. However, the DG units often cannot directly support the electrical appliances with the same power qualities of the grid in terms of frequency and amplitude. So, DG systems are connected to the utility grid (UG) through power electronic inverters. Due to unexpected power disruption, the grid-connected (GC) inverter should be able to operate in GC and stand-alone (SA) modes in order to provide power to the emergency load during outages. A high-performance inverter with the abilities of both stand-alone operation and utility-grid connection is necessary to ensure efficient utilization of DG units [4]. Grid-connected inverter can be achieved by various circuit topologies [5], but new designed circuit topologies cannot be popularly adopted in commercial products [4]. A single phase inverter with low cost and high efficiency shown in Fig. 1 has a simple circuit topology and low component counts. As the grid-interactive inverter should operate in SA mode, the filter capacitor is necessary [6]. Nevertheless, the filter capacitor can affect the quality of the grid current in the GC mode, especially at low output power. Since the inverter operates more time in the GC mode, a smaller capacitor is beneficial to the GC topology for reasonable compromise. A low-pass filter with the values of Lf = 1.3 mH and Cf = 4.4 μF is selected by considering the switching frequency and the output fundamental frequency in Fig. 1[7]. The value of capacitor is smaller than the capacitor which is designed in [8] (Cf = 14.25 μF) , [9] (Cf = 20 μF ) and [10] (Cf = 75 μF). The control objective of the DG system in this paper is: (1) to supply a 2 Journal of Power Electronics, to be published sinusoidal output voltage at load terminal (vinv) in the SA mode; (2) to transfer a sinusoidal grid current (ig) to the utility grid in GC mode; (3) to obtain smooth transition between the two modes. Up to now, many control approaches have been proposed to control the DC/AC inverter, such as, PI control, sliding-mode control, optimal multi-loop linear resonant control, linear control, backstepping control, and passivity-based control etc. However, some of these control methods are only suitable for SA mode or GC mode, while some control methods are very complex and are difficult to realize and apply to industry. In order to solve these problems, a novel control method is proposed in this paper. In the GC mode, a predictive current control scheme is proposed to control the grid current to obtain a high-performance power quality. Notice that the filter is not optimal in the SA mode. So a compound control strategy, consisting of predictive current control, instantaneous voltage control and repetitive control, is proposed to achieve low total harmonic distortion and thus improve the output voltage spectrum. The paper is organized as follows. The description of the inverter, the control methods for the SA and GC mode, and the detailed process of the seamless transition between the two modes are developed in Section II. In order to show the usefulness of the proposed control strategies, simulation results are presented in Section III. In addition, experimental results are performed to verify the theoretical analysis in Section IV. Finally, some conclusions are drawn in Section V. II. SYSTEM CONFIGURATION AND PROPOSED CONTROL STRATEGY A. Single-Phase Inverter Description Fig. 1 shows the conventional full-bridge inverter scheme. The PWM inverter framework includes four power switches (S1, S2, S3, and S4) and a low-pass filter (L and C). Moreover, critical-load represents an output load in the SA mode. Vbus, vg, vinv are the voltages of the DC bus, the utility grid and the inverter output, respectively. vAB is the voltage between point A and B. iL, ic, iinv, io, ig are the currents of the filter inductor, the filter capacitor, the inverter output, the critical-load and the utility grid, respectively. The grid-connected switch (Tg) is used to disconnect or reconnect the inverter output to the grid. When Tg is closed, the inverter is working in the GC mode to transmit the power of DG units into the utility grid. Under utility interruption or abnormal grid condition, Tg is open, and then the inverter provides power to the emergency load and operates in SA mode. S1 Vbus S3 A C1 iL vAB S2 L B Tg iinv iC C S4 io ig vg vinv Critical-load Fig.1. Single-Phase Full-Bridge Inverter of Dual-Mode The dc-ac converter is a nonlinear system by nature due to the existence of the solid-state switches. A nonlinear system needs be firstly linearized around its operating point before the linear controller can be designed. The performance of the controlled system in the neighborhood of that operating point can be guaranteed if the designed controller is robust enough. The wider the bandwidth of the system is, the larger the neighborhood will be. From Fig. 1, the inverter model is decided by following differential equation: diL dt Vbus D v AB vinv L v AB (1) (2) where D is the PWM duty cycle during one switching period. B. System Control Method The system control block diagram is shown in Fig. 2. Switching between GC and SA is determined by islanding detection. Although the current controllers in both GC mode and SA mode are the same, the current commands are different. When the inverter is operated in the GC mode, the current command iLref is equal to i L GC , which is decided by maximum power point tracking (MPPT) control and digital phase locked loop (PLL) control. Owing to the limited space in this paper, these two control methods are not addressed here, please refer to the references [11], [12]. is When the inverter is operated in the SA mode, the iLref equal to i L SA , which is decided by the inverter output voltage controller. Next, the algorithm will be analyzed in detail. GC Mode vbus ibus vg MPPT PLL Islanding Detection v*inv vinv io i*L-GC Output Voltage Control Mode select i*L-SA SA Mode Fig.2. The system control block diagram i*Lref Inductor Current Control iL Journal of Power Electronics, to be published 3 C. GC mode In the GC mode, inverter behaves as controllable current-sources. The closed-loop control method should manipulate the output current (ig) with a high power factor. With the recently developed high-performance digital signal processor (DSP), realization of digital controllers with higher sampling rate becomes possible and this makes the sampling frequency gradually approaches to the switching frequency of a digital-controlled power converting system. Assume that the inverter is operating with a constant switching frequency, the switching period is a constant value T . During the switching period [k , k 1] , (1) and (2) can be rewritten in a discrete form as v AB [k ] vinv [k ] (iL [k 1] iL [k ]) v AB k Vbus k Dk L T unavoidable control delay. If the digital control delay is considered, the input-to-output transfer function of the current control loop is: 1 I L ( z) L I ref ( z ) z ( z 1) 1 Lm (8) The root locus of the closed-loop system (8) is obtained as shown in Fig. 4(b). It can be observed that the system is unstable when Lm ≥ L. In order to ensure the system stability, Lm need be less than L, which can result in poor stability margin and dynamic performance. (3) (4) Substituting (4) into (3), the D[k ] can be expressed as D[k ] vinv [k ] (iL [k 1] iL [k ]) L T Vbus [k ] (5) a. (Lm < 2L) The target of the controller is that the load current at the sampling point [k+1] is controlled to equal to the reference current value at the point [k+1]. So the control law (5) turns to be (6) [13]. This is the predictive current control. D[k ] vinv [k ] (iref [k 1] iL [k ]) Vbus [k ] L T (6) Fig. 3 illustrates the employment of an inner current loop. z is a control delay. The predictive controller requires full knowledge of the system parameters. If there exists model mismatch in the control system, the mismatch will influence the control accuracy. Lm is the parameters of digital controller. Without considering the digital control delay, the input-to-output transfer function of the current control loop is: -1 I L ( z) 1 L I ref ( z ) ( z 1) 1 Lm b. (Lm < L) (7) c. (Lm < 2L) Fig.4. Root locus plot of Inner Loop Fig.3. Current control block diagram The root locus of the closed-loop system (7) is obtained as shown in Fig. 4(a). It can be observed that the system poles are in the unit circle if Lm is less then L. When Lm is greater than L, it allows a deviation of 50%. No control delay is considered in (7). However, in the actual digital control system, there exists The goal of predictive current control is to make the error of next control period to be zero. However, due to the existence of the sampling error, the model parameter deviation and so on, the error is difficult to be controlled to be zero. Taking this fact into consideration, an improved algorithm is proposed. The current error will converge to 0 automatically, and the stability margin of the system can be improved greatly. The control law is: 4 Journal of Power Electronics, to be published ie [ k ] iref [ k ] i L [ k ] D[k ] vinv [k ] (iref [k 1] iL [k ] 0.5 * ie [k ]) Vbus [k ] (9) Lm T (10) From (10), we can give the input-to-output transfer function of the current control loop as follow: I L ( z) z 0.5 L 3 I ref ( z ) ( z z 2 ) 0.5 z Lm (11) The root locus of the closed-loop system (11) is obtained as shown in Fig.4.c. It can be observed that the permissible range Fig.6. Amplitude frequency response of Vinv / Io In SA mode, the filter capacitor should choose bigger in order to improve the quality of the voltage. The small filter capacitor has a bad effect on the output voltage: First, voltage Fig. 5. Control block diagram of the grid-interactive inverter in off-grid mode of the model parameters is the same as (7). D. SA mode In the SA mode, the output voltage (vinv) should be controlled with a low THD. The control block diagram in SA mode is given in Fig. 5. Three controllers are included in the control loops: a current tracking controller, a voltage tracking controller and a repetitive controller. The current control loop is the same as it is used in GC mode. The output voltage controller is used to regulate the output voltage, where the reference voltage vr(z) is a sine waveform and is given by the DSP. The output of voltage control loop is the reference current of the current control loop. In order to improve the load disturbance rejection performance, load current is taken as the feed-forward compensation in the current loop. kcomp is the compensation coefficient. The input-to-output transfer function of the voltage control loop becomes: Vinv IO L ( z 1) 2 (1 k comp )( z 1) KT LC C ( z 1) 3 ( z 1) 2 K p ( z 1) K i z T KT 2 (12) where Ki and Kp are the integral and proportional coefficients of the output voltage controller, respectively. It can be seen from (12) that the inverter in SA mode is stable according to the conventional control theory. The parameters are as follows: kcomp = 0.96, Kp = 2.5, Ki = 0.03. Fig. 6 is the amplitude frequency response of Vinv / Io. The control system has strong anti-load disturbance performance. harmonics can not be filtered out effectively; Secondly, the dead-time in PWM based inverter will result in output waveform distortion and fundamental voltage loss, especially when the output voltage is low. When the current reaches zero during the deadtime and stays at zero level during the rest of the deadtime, there is no means of controlling the output voltage, the phenomena of zero crossing is difficult to avoid, especially when the filter capacitor is small. Since all repetitive disturbance is repeated for every switching operation, so it can be solve by the techniques of repetitive control (RC). RC, which originates from the internal model principle, provides a solution to eliminate periodic errors. A plug-in type modified repetitive controller is shown in Fig. 5. The result of the integration, denoted as e[k ] , is then processed by the following units to generate Dr [14]. 1) z N : time delay unit. It postpones the control action by one fundamental period so that time advance z k unit as well as the noncausal zero-phase-shift notch filter included in S (z ) can be realized. Let N = fs / f with f =50Hz be the fundamental frequency of the reference signal vr(z) , and let fs=16k be the sampling rate, so N=320 is the order of the RC. 2) S (z ) : compensator. It modifies magnitude characteristic of the open-loop system for better harmonic rejection. 3) z k : time advance unit. It advances the control action by Journal of Power Electronics, to be published 5 sample periods in the next fundamental period, so as to compensate the delay of compensator S (z ) as well as the inverter. 4) k r : gain. It controls the magnitude of Dr. Steady-state analysis shows that if the band-limit filter Q(z ) is unit, no steady-state error occurs. Unfortunately, the capacitor can help to reduce zero-crossing distortion, but the large filter capacitor can affect the grid current control in GC mode and increase the cost of hardware. Fig. 7(d) shows the simulation of the load step of rated power, there is a large and relatively transient drop in voltage, but the drop of RMS value is less than 2V. As can be seen, the proposed control method in the SA mode is less sensitive to load variations. Nyquist criterion reveals that it is not possible to establish a stable system when Q( z ) 1 .With this constraint, set Q( z ) 0.96 . According to [14], the designed parameters are as follows a=0.2, b=0.8, k r =1, k=5. E. Seamless Transfer The detailed process of the seamless transfer between the SA and GC modes are summarized as follows. 1) SA mode to GC mode: a) Detect that the grid is operating in nominal condition. b) Adjust the reference voltage (vr(z)) to match the frequency and phase of the grid voltage by digital PLL. c) After the load voltage is equal to the grid voltage, Tg is turned on at zero crossing of the grid voltage. Then the control model switches to GC mode. d) Increase the reference grid current slowly from load current to the desired value (decided by MPPT). (a) Double loop control (Cf=4.4μF) (b) Double loop control (Cf=40μF) 2) GC mode to SA mode: a) Detect a fault on the utility. b) Change the reference current to load current. c) Tg is turned off at zero crossing of the load voltage. Then the control model switches to SA mode. III. SIMULATION RESULTS (c) Compound control with RC (Cf=4.4μF) To verify the effectiveness of the proposed control strategy, a simulation model is built in power electronic simulation software (PSIM) with the system parameters given in Table I. TABLE I SYSTEM PARAMETERS Parameters Rated output power Grid voltage Grid frequency(fs) DC-link voltage(Vbus) Switching/Sampling frequency(fsample) Output filter inductance(L) Output filter capacitance(C) Values 4kVA 220(rms) 50Hz 370V 16kHz 1.3mH 4.4μF Fig. 7 shows the simulation results of SA mode. Fig. 7(a) and Fig.7(c) show the simulation results of the double controlled and RC + double controlled PWM inverter under rated output power. It is obviously shown that RC can reduce zero-crossing distortion. It can be seen from Fig. 7(b), a larger (d) Output power changes from o to 4kVA Fig. 7. Simulation waveforms of SA mode Fig. 8(a) presents the simulation results for a transfer from GC mode to SA mode. Due to the randomness of the grid fault and the mismatch of the inverter output power and the load power, the load voltage and current have some inrush spikes during the transition period. This process is short and the waveform will resume normal when the system switches to the SA control mode. 6 Journal of Power Electronics, to be published Fig. 8(b) presents the simulation results for a transfer from SA mode to GC mode. There is not any sudden voltage change across the emergency load. The load voltage and the load current, which do not have any inrush spikes during the entire transition period, reveal a smooth transition from SA mode to GC mode. the condition of regular operation or load variations. (a) Without RC (a) GC mode to SA mode (b) With RC (b) SA mode to GC mode Fig. 8. Simulation waveforms of transfer control IV. EXPERIMENTAL RESULTS To further verify the theoretical analysis and simulated results, an experimental system is built in the laboratory. The system parameters used in the experiment are the same as those in the simulation model given in Table I. The proposed control scheme is implemented by using a digital-signal-processor (DSP) TMS320F2808 from Texas Instruments. The 16 kHz PWM modulated driving signals for the full-bridge inverter are generated by the DSP and peripheral logic circuits. The TMS320F2808 is essentially a 32-bit microcontroller with DSP architecture, most of its instructions can be executed in one instruction cycle of 10 ns. Fig. 9(a) and Fig. 9(b) shows the experimental results at 4kW load. With RC compensation, the voltage distortion near the zero-crossing is reduced and the THD of the voltage decreases from 2.9% to 0.7%. Fig. 9(c) shows the experimental results for a rectifier load (2500VA) with power factor (PF) of 0.7. The THD of the voltage is about 2.2%. Fig. 9(d) shows the step response of the load changes from 0 to 4kVA, the settling time of the system is about 600μs. As can be seen from Fig. 9, the performance indexes show that the experimental results agree with the numerical simulations, and the proposed control method can provide favorable control performance either under (c) Rectifying load (d) 4kVA load Fig. 9. Experimental Waveforms of SA mode Fig. 10 presents the experimental results in the GC mode. The THD of the grid voltage is about 3.1%, but the THD of the grid current is just 1.8% (4kVA grid-connected power) and 2.5%(2kVA grid-connected power). The PF of the grid current is 1 (4kVA grid-connected power) and 0.998(2kVA grid-connected power). The waveform quality of the grid current is good with the control method even in polluted Journal of Power Electronics, to be published 7 voltage. (b)SA mode to GC mode Fig. 11. Experimental Waveforms of Transfer Control with 2kVA Load (a) 2kVA load (b) 4kVA load Fig. 10. Experimental voltage and current responses of GC mode Fig. 11(b) shows the experimental results from SA mode to GC mode. When the grid is normal, the voltage of inverter synchronizes with the grid voltage. Tg is turned on at zero-crossing of the grid voltage and then the control system switches to current control mode. The reference current increases from current value. The load voltage and the load current, which do not have any inrush spikes during the entire transition period, reveal a smooth transition from SA mode to GC mode Fig. 11 presents the experimental results of transfer control with 2kVA load. Fig. 11(a) shows the experimental results from GC mode to SA mode. The output power of inverter is 4kVA, iinv is the inverter output current, composed of load current and grid current. The grid is broken off at t1. Because the output power of the inverter is greater than the load power consumption, so the inverter output voltage has inrush spike. The grid fault is detected at t2, and the control system switches the reference current value to the load current. Tg (Bidirectional triode thyristor) is turned off at t3 (zero-crossing of the inverter voltage) and then the control system switches to voltage control mode. (a) GC mode to SA mode (b) SA mode to GC mode Fig. 12. Experimental Waveforms of Transfer Control with 4kVA Load (a) GC mode to SA mode . Fig. 12 presents the experimental results of transfer control with 4kVA load. The output power of inverter is 2kVA in GC mode. Grid and inverter supply power to load at the same time. Because the load power is greater than the output power of the inverter, so the inverter output voltage has inrush spike when the grid is break off at t1. As the same as the analysis of Fig. 11, the value of reference current switches to the value of load current and then the control system switches to voltage control 8 Journal of Power Electronics, to be published mode at zero-crossing of the inverter voltage. As can be seen from Fig. 12(b), the load voltage and the load current do not have any inrush spikes during the entire transition period from SA mode to GC mode. V. CONCLUSIONS This study has successfully developed a single-phase full-bridge inverter with a small filter capacitor. Predictive current control has been applied well to both the SA and GC power-supply modes. A compound control strategy is applied to SA mode. A novel seamless transfer between SA mode and GC mode is proposed. The proposed control method has salient features, including fast response characteristics in transient states, robust control performance, high power-supply quality, and automatic transformation between the SA mode and the GC mode. The proposed control schemes also can be extended easily to other power conversion systems for satisfying high power quality demands. ACKNOWLEDGMENT This work was supported in part by the National Natural Science Foundation of China under Grant No. 51537001. REFERENCES [1] [2] [3] [4] [5] [6] [7] M. N. Arafat, S. Palle, Y. Sozer, and I. Husain, "Transition control strategy between standalone and grid-connected operations of voltage-source inverters," IEEE Transactions on Industry Applications, Vol. 48, No. 5, pp. 1516-1525, Sept. 2012. Y. He, Y. Xu, Y. Pang, H. Tian, and R. Wu, "A regulatory policy to promote renewable energy consumption in China: Review and future evolutionary path," Renewable Energy, Vol. 89, pp.695-705, Apr. 2016. M. F. Akorede, H. Hizam, and E. Pouresmaeil, "Distributed energy resources and benefits to the environment," Renewable and Sustainable Energy Reviews, Vol. 14, No. 2, pp. 724-734, Feb. 2010. R.-J. Wai, C.-Y. Lin, Y.-C. Huang, and Y.-R. Chang, "Design of high-performance stand-alone and grid-connected inverter for distributed generation applications," Industrial Electronics, IEEE Transactions on, Vol. 60, No. 4, pp. 1542-1555, Apr. 2013. Y. Xue, L. Chang, S. B. Kjær, J. Bordonau, and T. Shimizu, "Topologies of single-phase inverters for small distributed power generators: an overview," IEEE Transactions on Power Electronics, Vol. 19, No. 5, pp. 1305-1314, Sept. 2004. Hirase Y, Noro O, Sugimoto K, Sakimoto K, Shindo Y, Ise T, "Effects of suppressing frequency fluctuations by parllel operation of virtual synchronous generator in microgrids," in Proc. 2015 IEEE ECCE, Montreal, pp.3694-3701, Nov. 2015. Sakimoto K, Sugimoto K, Shindo Y, Ise T,"Virtual synchronous generator without phase locked loop based on current controled inverter and its parameter design," IEEJ, Tran. Power and Energy, Vol. 135, No. 7, pp.462-471, Jul. 2015. Y. Zhilei, X. Lan, and Y. Yangguang, "Seamless transfer of single-phase grid-interactive inverters between grid-connected and stand-alone modes," Power Electronics, IEEE Transactions on, Vol. 25, No. 6, pp. 1597-1603, Jun. 2010. [9] R.-J. Wai, C.-Y. Lin, W.-C. Wu, and H.-N. Huang, "Design of backstepping control for high-performance inverter with stand-alone and grid-connected power-supply modes," Power Electronics, IET, Vol. 6, No. 4, pp. 752-762, Apr. 2013. [10] C.-P. Hong, H.-W. Kim, and S.-J. Lee, "Stationary frame voltage controller of single-phase inverter for seamless transition," in Future Energy Electronics Conference (IFEEC), 2015 IEEE 2nd International, pp. 1-6.Dec. 2015. [11] B. Zheng, F. Cai, and W. Wang, "Analysis and research of MPPT algorithm for a single-stage PV grid-connected power generation system," Diangong Jishu Xuebao(Transactions of China Electrotechnical Society), Vol. 26, No.7, pp. 90-96, Jul. 2011. [12] F. Cai, B. Zheng, and W. Wang, "Islanding detection method combined with PLL for photovoltaic grid-connected power system," Diangong Jishu Xuebao(Transactions of China Electrotechnical Society), Vol. 27, No.10, pp. 202-206, Oct. 2012. [13] F. Cai, B. Zheng, and W. Wang, "Comparisons of Two Control Methods for Single-stage Grid Connected Inverter," Dianli Dianzi Jishu/ Power Electronics, Vol. 45, No.4, pp. 4-6,Apr. 2011. [14] K. Zhang, Y. Kang, J. Xiong, and J. Chen, "Direct repetitive control of SPWM inverter for UPS purpose," Power Electronics, IEEE Transactions on, Vol. 18, No.3, pp. 784-792, May.2003. Fenghuang Cai was born in Fujian, China in 1976. He received his B.S in Industrial Automation, M.S in Control Theory and Engineering, Ph.D. in Electrical Engineering from the Fuzhou University, PR China, in 1998, 2002 and 2007, respectively. In 1998, he joined Fuzhou University, as an teaching assistant in the Department of Electrical Engineering, and where he has been an Associate Professor in Control Engineering since 2010. His current research interests include power electronics and control, which include modeling and control of power electronic system, digital-signal-processing-based control applications, distributed generation, and renewable energy. [8] Dexiang Lu was born in Fujian, China, in 1990. He received his B.S. degree in electrical engineering and automation from the Jimei University, Xiamen, China, in 2013. He is currently working toward the M.S. degree in electrical engineering at the School of electrical engineering and automation, Fuzhou University, Fuzhou, China. His current research interests include control techniques of power converter, renewable energy generation system and high-frequency power conversion. Qiongbin Lin was born in Fujian, China in 1976. He received his B.S in Industrial Automation, M.S in Control Theory and Engineering, Ph.D. in Electrical Engineering from the Fuzhou University, PR China, in 2000, 2003and 2010, respectively. In 2000, Journal of Power Electronics, to be published 9 he joined Fuzhou University, as an teaching assistant in the Department of Electrical Engineering, and where he has been an Associate Professor in Control Engineering since 2012. His current research interests include power electronics and control, nonlinear system and fuzzy control, which include modeling and control of power electronic system, digital-signal-processing-based control applications, and DC microgrids.. Wu Wang was born in Fujian, China, in 1973. He received his B.S in Mechanical Design and Manufacturing and M.S in Agricultural Mechanization Engineering from the Fujian Agriculture and Forestry University, PR China, in 1996 and 1999, respectively. He received his PhD in Electrical Engineering from the Fuzhou University, PR China, in 2004. He joined Fuzhou University after obtaining his PhD Degree, where he currently is a Professor in Control Engineering. His research interests include modeling and control of power electronic systems, H-infinity control and filtering, and networked control.