Heat Pump Water Heaters: Controlled Field Research of Impact on Space Conditioning and Demand Response Characteristics Graham Parker,1 Sarah Widder,1 Ken Eklund,2 Joe Petersen,1 and Greg Sullivan3 1 Pacific Northwest National Laboratory Washington State University Energy Program 3 Efficiency Solutions, LLC 2 Abstract A new generation of heat pump water heaters (HPWH) has been introduced into the U.S. market that promises to provide significant energy savings for water heating. Many electric utilities are promoting their widespread adoption as a key technology for meeting energy conservation goals and reducing greenhouse gas emissions. There is, however, considerable uncertainty regarding the space conditioning impact of an HPWH installed in a conditioned space. There is also uncertainty regarding the potential for deployment of HPWHs in demand response (DR) programs to help manage and balance peak utility loads in a similar manner as conventional electric resistance water heaters (ERWH). To help answer these uncertainties, controlled experiments have been undertaken over 30 months in a matched pair of unoccupied Lab Homes located on the campus of the Pacific Northwest National Laboratory (PNNL) in Richland, Washington. The water heater closet in the Lab Homes is in conditioned space; therefore, taking supply air and injecting cool exhaust air from an HPWH will interact with space conditioning within the homes. Initial experiments were conducted with the second-generation General Electric (GE) “Brillion™” heat pump water heater in several configurations: 1) unducted, 2) exhaust-air ducted, and 3) fully ducted to ascertain the impact of the HPWH on space conditioning. Experiments also were conducted under simulated occupancy conditions on the GE units to determine the DR of the units under multiple scenarios. Subsequent DR experiments were conducted in the Lab Homes with Sanden carbon-dioxide (CO2) refrigerant HPWHs as part of a project conducted by Washington State University Energy Program with funding from Bonneville Power Administration. These HPWHs are new to the U.S. market but not yet commercially available. Two units were evaluated: 1) a split system with an outdoor compressor and an 80-gal (303 L) indoor water tank and 2) a 40-gal (151 L) unitary unit installed in the Lab Home water heater closet and fully ducted (supply and exhaust air). 1.0 Introduction In the United States, water heating represents the second largest household energy expense behind space heating, representing approximately 18% of residential energy consumption, or approximately 1.8 Quads annually [1]. Efficient water heater options are necessary to achieve significant energy savings in the residential sector and therefore the U.S. Department of Energy (DOE) recently completed new energy conservation standards for natural gas, oil, and ERWHs between 20 and 80 gal (76 and 303 L) [2]. For storage water heaters with volumes of 55 gal (208 L) and below (representing the majority of new water heaters for dwellings) the new standards will increase the efficiency by approximately 4% [2]. For water heaters larger than 55 gal (208 L), a much bigger jump in efficiency is mandated. The new standards for these larger water heaters can be met using electric heat pump (HPWH) and gas condensing technology. HPWHs save at least 50% and condensing gas units about 25% compared to today’s conventional tank-type ERWHs [3]. Electric HPWHs ranging in size from 40 to 80 gal (151 to 303 L) offer the most efficient option for the 1 41% of homes equipped with ERWHs, with a theoretical energy savings of up to 63%. 1 1 Based on the DOE test procedure [9], and comparison of an ERWH (Energy Factor, EF = 0.90) versus a HPWH (EF = 2.4) However, significant barriers must be overcome before this technology will reach widespread 2 adoption. One barrier noted by the Northwest Energy Efficiency Alliance (NEEA) is that HPWH products are not ideal for northern climates, especially when installed in conditioned spaces. HPWHs exhaust cool air as they heat the water, and there may be complex and detrimental interactions with the homes’ space conditioning system for units installed in a conditioned space [4]. Such complex interactions may decrease the magnitude of whole-house savings available from HPWHs installed in the conditioned space in cold climates and could lead to comfort concerns [4, 5]. Modeling studies indicate that the installation location of HPWHs can significantly impact their performance and the resultant whole-house energy savings [6, 7]. As a result, NEEA’s Northern Climate HPWH Specification, which describes the characteristics a HPWH must have to be incentivized in cold climates in the Pacific Northwest, requires exhaust ducting for a Tier II product and full ducting for a Tier III product (see www.neea.org/northernclimatespec). In addition, if exhaust-air ducting on HPWHs is found to be beneficial in some or all climates, it will be important to understand the source and temperature of supply air (whether it is the home’s conditioned air or outside air brought into the home) and the implications for interior depressurization, particularly for tight homes. Another barrier is the impact of HPWHs on DR programs because DR characteristics currently are unknown for HPWH technology. Many utilities currently employ large storage tank ERWHs to reduce peak load by turning off the water heater during times of peak demand. Some utilities also are demonstrating the potential of using ERWH to increase load for areas with high renewable energy penetration and to provide additional balancing and ancillary services. As HPWHs begin to penetrate the market in the residential sector, utilities will need to better understand the DR capability and characteristics of HPWHs. 2.0 Demand Response DR benefits to utilities include increased system reliability, defrayed cost of new infrastructure investment, reduced fuel consumption, improved system efficiency, and decreased carbon emissions through increased penetration of intermittent renewable resources. When considering grid stability and reliability, several types of DR are considered: • Peak curtailment, or peak load reduction, which drops non-critical loads for a period of 4-6 hours during the time when power use is highest and the strain on the grid is greatest. This can prevent the need to bring on inefficient, fossil fuel-fired “peaking plants” that exist solely to generate electricity during the peak 4-6 hour period and are otherwise turned down or off. • Balancing reserves, or regulation services, responds to hourly or sub-hourly changes in generation capacity either because of inherent variability in the generation resource or large disturbances in the grid (e.g., transmission fault). Balancing reserves can be implemented for either a shortage of generation capacity (commonly referred to as INC) or a surplus of generation capacity (commonly referred to as DEC). • Ancillary services that adapts to sub-minute fluctuations in voltage or frequency to maintain consistent electricity service and distribution. Several studies have previously evaluated the potential of ERWH to provide peak curtailment, balancing reserves, and ancillary services using models and found significant potential and benefit for ERWH to perform these grid functions [8, 10, 11, 12]. However, no extensive field testing has verified these model results. In addition, new HPWH technology has the potential to dramatically decrease the electricity use and peak load of residential water heating. Consequently, use of more efficient heat pump technology may also limit the magnitude of the water heater for DR. 2 2 www.neea.org 3.0 HPWH Experiments Given there is a need to understand both the efficiency and impact of a HPWH installed in a conditioned space in a home and the potential for deploying a HPWH for DR compared to the DR 3 characteristics of ERWHs, a set of experiments were conducted in the PNNL Lab Homes over a 3-year period to better understand the attributes of a HPWHs. Three diverse types of HPWHs were tested: 1) a GE second-generation 50-gal (189 L) GeoSpring Hybrid Water Heater (model GEH50DEEDSR), which is enabled with Brillion™ wireless communication and control technology to 4 test the thermal envelope and HVAC impact and DR characteristics; 2) a Sanden GES-15QTA 40 gal 5 (151 L) integrated heat pump water heater using CO2 as the heat pump refrigerant to test DR; and 3) a Sanden GAU-315EQTA split system heat pump with an 80 gal (303 L) storage tank also using CO2 as the refrigerant to test DR. The Sanden unitary HPWH was fully ducted during all experiments with this unit per manufacturer’s specifications. 3.1 PNNL Lab Homes Testing Platform The matched pair of PNNL Lab Homes (designated Lab Home A and Lab Home B) provide a unique platform in the Pacific Northwest region for conducting experiments on residential-sector technologies. These unoccupied electrically heated and cooled 1500 square-foot homes are sited adjacent to one another on the PNNL campus in Richland, Washington. The homes are fully instrumented with enduse metering (via a 42-circuit panel), indoor and outdoor environmental sensors, and remote data collection. Figure 1 is a floor plan of the Lab Homes noting the location of the water heater and the required ventilation (transfer) grills installed in interior walls of the home to allow air circulation for the integral HPWHs that were tested. Water heater Figure 1. Floor plan of Lab Homes with water heater and transfer grills locations noted. 3.2 Experimental Design The experiments were designed evaluate the HVAC system (space conditioning) impact and DR characteristics of the GE GeoSpring HPWH, and the DR characteristics of the Sanden integrated CO2 heat pump water heater and the Sanden CO2 split-system heat pump water heater. Occupancy and hot water use schedules were simulated to isolate the performance, impact, and DR of the HPWHs from all other variables. Table 1 summarizes the six experiments. Table 1. Summary Description of HPWH Experiments in the PNNL Lab Homes. Experiment 3 4 5 Equipment Experiment Description Time Period A full description of the Lab Homes is found at http://labhomes.pnnl.gov. A full description of the features and controls capability of the GE GeoSpring HPWH is found elsewhere [14]. CO2 has a very low Global Warming Potential of 1. A full description of the features of both Sanden units tested is found elsewhere [15]. 3 1 GE GeoSpring HPWH 2 GE GeoSpring HPWH 3 GE GeoSpring HPWH 4 GE GeoSpring HPWH ERWH 5 Sanden GES-15QTA HPWH Unitary System Sanden GAU-315EQTA HPWH Split System 6 HVAC impact of ducting compared to unducted configuration HVAC impact of ducting compared to unducted configuration Water heating energy use of ducted and unducted configurations DR characteristics of the GeoSpring HPWH in unducted configuration compared to DR of ERWH DR characteristics June-August DR characteristics October Dec-Jan June-August Dec-Jan April-May October As a part of thermal impact experiments 1 and 2, the comfort (i.e., room temperature) was determined; however the results are not reported in this paper but are reported elsewhere [14]. In addition, the COP of the Sanden split system under DR stress is currently being evaluated in the laboratory and will be reported in late CY2015. The baseline efficiency in the laboratory was established in research prior to the Lab Homes testing [15]. Figures 2a and 2b show the GE GeoSpring HPWH installed in the Lab Homes for experiments 1-4. Figures 3a and 3b show the Sanden HPWHs installed in the Lab Homes for experiments 5 and 6. Figure 2a. Installed GE HPWH without ducting in Lab Home B. Figure 2b. GE HPWH with exhaust and supply ducting in Lab Home A. The supply air for the fully ducted configuration of the GE GeoSpring units was supplied from the 6 home crawlspace near the center of the home through a 6-in. flexible duct. The exhaust air was drawn by a small fan through 6-in. flexible duct from the unit and exhausted via a standard dryer-type vent installed at the bottom of the closet door. The exhaust duct fan was needed to provide sufficient airflow across the heat pump, as the GE GeoSpring HPWH was not designed for exhaust or full ducting as purchased. The measured airflow through the ducting during these experiments, with the 3 supplemental exhaust fan running, was 166 CFM (282 m /hour) for the exhaust-only ducting and 3 117 CFM (199 m /hour) for the full ducting, both of which are in accordance with installation recommendations [4]. For the unducted configuration, the master bedroom closet was closed and any air circulation around the HPWH was provided by four transfer grills (two in the closet wall and two in the hallway wall). 6 4 Note that the homes are both completely skirted by ~2 inch insulating vinyl-covered foam panels. Figure 3a. Sanden unitary unit installed in Lab Home A. Figure 3b. Sanden split system installed in Lab Home B. 3.3 Data Capture and Experimental Configuration Following are summary descriptions of the experimental setup for the Lab Homes. These descriptions include how energy (electricity) was measured, how occupancy was simulated, how the HVAC system was operated, and how temperature, humidity, and water flow were measured. A more detailed description can be found elsewhere [14,16]. 3.3.1 Electrical Energy Whole-house electrical power and circuit level (true) power was measured at the 42-circuit breaker panel with current transformers. Data were captured at 1-minute intervals via a Campbell Scientific data logger. 3.3.2 Simulated Occupancy To simulate occupancy, hot water draw profiles were implemented identically in both homes. The hot water draws used a modulating solenoid valve at the kitchen sink hot water supply and were controlled via the Campbell data acquisition system. Controllable breakers were programmed to activate connected loads on schedules to simulate human occupancy. The bases for occupancy simulation were data and analysis developed in previous residential simulation activities [15, 16]. Detailed information on the electrical loads used to simulate occupancy and the relevant schedules was reported previously [18]. 3.3.3 Hot Water Draw and Draw Profile PNNL selected a hot water draw and draw profile that was representative of a typical daily draw pattern for a population of homes, rather than a single home and that was feasible to implement reliably and repeatable using existing equipment in the PNNL Lab Homes. The draw profile was based on the U.S. DOE Building America House Simulation Protocols, which specify typical daily draw volumes for different appliances based on the number of bedrooms and an hourly draw pattern 7 based on fraction of total daily load [17, 20] . 7 The hot water draw profile in the Lab Homes for this experiment is not shown in this paper but can be found elsewhere [16] 5 A high hot water draw volume was chosen to create a worst-case scenario to evaluate the maximum space conditioning interaction for the experiments. Therefore, the hot water flow rate was set to 2.0 gpm (7.6 L/minute), for a total draw volume of 130 to 140 gal/day (492 to 530 L/day) in both lab homes. 3.3.4 HVAC System Operation Throughout testing, the HVAC system in both homes was operated identically. During the cooling season, the 2.5-ton SEER 13 heat pumps maintained an interior set point of 76°F with no setback [17]. During the heating season, the heat pumps were set to “Emergency Heat,” to operate like electric resistance furnaces and maintain an interior set point of 71°F with no setback [17]. 3.3.5 Temperature and Humidity Measurements Identical networks of temperature sensors were deployed in both homes. Each defined area of the home (individual rooms, hallway, and open living areas) had at least one thermocouple; a total of 17 space temperature thermocouples were installed per home. Two type T thermocouples were installed to measure supply and exhaust process air through the heat pump compressor. Three crawlspace temperature sensors were installed to monitor the temperature of the crawlspace, which was be the temperature of the supply air for the GE GeoSpring HPWH tested in the fully ducted arrangement. 3.3.6 Water Flow Measurements The water flow rate was measured using a low-flow, impeller-type flow meter with 375 to 1380 pulses per gallon (0.07–5 gal [0.26–19 L] or 0.2–20 gal [0.76–7.6 L] range, depending on the model) with a 6–24 VDC output. 4.0 Testing Protocol The testing protocol was tailored depending upon the experiment conducted. The GE GeoSpring units were tested over an approximately 2-year period. They were tested for space conditioning (HVAC) during relatively long time periods during the summer (cooling) and winter (heating) in both ducted and unducted configurations. The GE GeoSpring DR experiments were conducted during relatively shorter time periods in the spring and fall. 4.1 Baselining the Homes Prior to initiating the experiments, the homes were extensively baselined. For experiments 1–4, the homes were baselined with the GE GeoSpring water heaters operating in electric resistance (only) and heat pump (only) modes. For experiments 5 and 6, the homes were similarly baselined although the heat pumps were operated only in heat pump mode as the home thermal/HVAC impacts of the units were not part of the experiment. 4.1.1 Air Leakage Blower door measurements were taken on both homes as part of the baseline period for experiments 1 and 2 as these (thermal/HVAC impact) experiments depended upon near-identical building thermal characteristics. Air leakage through the building shell was quantified in both homes using a Minneapolis Blower Door Model 3 and DG-700 digital pressure gauge in accordance with ASTM E779, “Standard Test Method for Determining Air Leakage Rate by Fan Pressurization,” and manufacturer recommendations [21, 22]. 4.1.2 Null Testing Following blower door measurements, the homes went through an active null testing period, with fulloccupancy simulation to verify equivalent performance. Null testing with full occupancy (lighting, human-related, and equipment sensible loads) and simulated hot water draws showed similar energy use between the two homes, within 1.9 ±2.0% over the cooling season baseline testing period for 6 experiments 1 and 2. The differences in whole-house energy use between Lab Home A and Lab Home B were observed to be within 0.7 ±0.5% over the heating season baseline testing period for experiments 1 and 2. 5.0 Experiments and Results The results of each of the six experiments described in Table 1 are summarized below. A discussion of those results and conclusions will follow. Recommendations for further investigations follow the discussions and conclusions. 5.1 Experiment #1: Cooling Season HVAC Impact of Ducting the GE GeoSpring HPWH Fully Ducted Water Heater Unducted Water Heater Exhaust-Only Ducted Water Heater % Difference in HVAC Energy Use 35 14% 30 12% 25 10% 20 8% 15 6% 10 4% 5 2% 0 0% Exhaust-Only Ducted Comparison Fully Ducted Comparison Percent Change in HVAC Energy Use Due to Ducting Configuration Daily HVAC Energy Use [kWh/day] Over a period of several weeks during the cooling season, both exhaust-only and fully ducted configurations were tested and compared to the unducted unit. Figure 4 illustrates the results of this experiment. Both the exhaust-only (green bar) and fully ducted configuration (red bar) led to increased HVAC energy usage as compared to the HVAC energy use in an unducted HPWH configuration (blue bar). This was attributed to the supplemental space cooling from the unducted HPWH exhaust being available for cooling the homes whereas the cool air was not available in either ducted configuration. The unducted HPWH provided a space cooling benefit equivalent to approximately 1.5 kilowatt-hours per day (kWh/day). Because this additional space cooling is not available in the exhaust-only and fully ducted scenarios, these ducting configurations resulted in increased space conditioning energy use of 9.3 ±1.0% for the exhaust-only and 9.3 ±2.2% for the fully ducted scenario during the cooling season. Figure 4. Daily home HVAC energy use and % difference in HVAC energy use for the exhaustonly ducted and the fully ducted GE GeoSpring HPWH experiments in the cooling season. In Figure 4, the duct configuration (exhaust-only and fully ducted) is compared directly to the corresponding unducted control case (blue bar). The average difference in HVAC energy use during each experimental period is represented by the yellow diamonds, where positive values indicate increased energy use resulting from ducting. The difference in the HVAC energy use for the unducted HPWH between the exhaust-only ducted comparison and the fully ducted comparison periods is due to weather differences during the two discreet time periods of the experiments. 5.2 Experiment #2: Heating Season HVAC Impact of Ducting the GE GeoSpring HPWH Over a several week period in the heating season, both exhaust-only and fully ducted configurations of the GE GeoSpring HPWH were tested and compared to the unducted unit. The results are summarized in Figure 5. The HVAC energy use in Lab Home A in the exhaust-only ducted configuration (green bar) increased 3.2 ± 2.5 kWh/day, or 4.0 ± 2.8% as compared to the unducted HPWH in Lab Home B (blue bar). The HVAC energy use in Lab Home A in the fully ducted 7 configuration (red bar), decreased 5.7 ± 1.6 kWh/day or 7.8 ± 2.3% as compared to Lab Home B with the HPWH in an unducted configuration (blue bar). Fully Ducted Water Heater Unducted Water Heater Exhaust-Only Ducted Water Heater % Difference in HVAC Energy Use 120 8% 6% 100 4% 2% 80 0% 60 -2% -4% 40 -6% -8% 20 -10% 0 -12% Exhaust-Only Ducted Comparison Fully Ducted Comparison Percent Change in HVAC Energy Use Due to Ducting Configuration Daily HVAC Energy Use [kWh/day] In Figure 5, the ducting configuration is compared directly to the corresponding unducted control case. The average difference in HVAC system energy use during each experimental period is represented by the yellow diamonds, where positive values indicate increased HVAC system energy use resulting from ducting. Figure 5. Daily home HVAC energy use and % difference in HVAC system energy use for the exhaust-only ducted and the fully ducted GE GeoSpring HPWH experiments in the heating season. 5.3 Experiment #3: Water Heating Energy Use for Ducted and Unducted Configurations Ducting can impact the energy consumed by the HPWH as the efficiency of the HPWH will be affected by the temperature of the inlet air. For example, while the unducted water heater may provide space conditioning benefits in the cooling season, such a configuration may increase water heating energy use because the colder inlet air decreases the efficiency of the HPWH. Table 2 summarizes the annualized water heating energy use difference between an unducted HPWH and an exhaust-only and fully ducted HPWH. The energy use difference is calculated based on data taken during the summer and winter experiments and annualized to the Richland, Washington, climate. The 8 measured temperatures during the winter and summer experiments also are shown in Table 2. Table 2. HPWH energy use for exhaust-only and fully ducted configurations compared to an unducted HPWH. HPWH Configuration Exhaust Only Fully Ducted Energy Use Difference vs. Unducted HPWH −144 ±74 kWh/yr −6.8 ± 3.5% 48 ±49 kWh/year 2.3 ±2.3% Living Space Average Temperature (season) 75.9 ±2.1°F (cooling) 71.6 ±1.6°F (heating) 74.7 ± 0.4°F (cooling) 71.3 ± 1.5°F (heating) Crawlspace Temperature (season) Not applicable to this configuration 73.0 ±1.3°F (cooling) 44.2 ±2.2°F (heating) 5.4 Experiment #4: GE GeoSpring HPWH Demand Response Compared to ERWH This experimental was undertaken to evaluate the DR capability of the GE GeoSpring HPWH as compared to the ERWH under two types of DR events: peak curtailment and balancing reserves (INC 8 Note that the HPWH energy use difference does not include fan energy used for the exhaust-only and fully ducted configurations. 8 and DEC, respectively). Table 3 summarizes the DR experiments that were designed to be a range of typical times during which DR may be required across a broad spectrum of utilities. To implement DR for the GE GeoSpring HPWH, PNNL deployed the built-in capability using the GE ® Nucleus™, GE’s Home Energy Management System, via ZigBee communication protocol. The mode and tank set points can be controlled through the Nucleus either by a homeowner or a utility employing conserve signals or peak pricing. Table 3. DR experiments with the GE GeoSpring HPWH compared to ERWH. DR Experiment Description Time of Day Duration Purpose of Experiment AM Peak Curtailment Turn off heating elements/HP 0700 3 hours PM Peak Curtailment Turn off heating elements/HP 1400 3 hours EVE Peak Curtailment Turn off heating elements/HP 1800 3 hours Balancing INC Turn off heating elements/HP 1 hour Balancing DEC Set tank temp to 135°F 0200 0800 1400 2000 0200 0800 1400 2000 Evaluate HPWH load shedding potential (dispatchable kW and thermal capacity) as compared to ERWH to manage peak load Evaluate HPWH load shedding potential (dispatchable kW and thermal capacity) as compared to ERWH to manage peak load Evaluate HPWH load shedding potential (dispatchable kW and thermal capacity) as compared to ERWH to manage peak load Evaluate HPWH potential to provide balancing reserves for dispatchable kW as compared to ERWH Evaluate thermal capacity of HPWH, as compared to ERWH, when temp set point is increased to 135°F (57°C) 1 hour Table 4 is a summary of the results of the experiments showing the average water heater power use during the DR event, water heater energy use during the DR event, daily energy use, and the ratio of the HPWH/ERWH for peak curtailment, INC experiment, and DEC experiment. Table 4. Data from DR experiments for the GE GeoSpring HPWH and ERWH. Experiment Duration Water Heater Mode Peak 3 hours HP 9 Average Power Draw a Impact (W) −439 Average Energy Use During DR Event (Wh) −1,285 Average Daily Energy Use Impact (Wh/day) −498 Ratio HPWH/ERWH 2.64 b Curtailment Balancing c INC Balancing DEC 1 hour 1 hour ER HP −1,158 −442 −3,320 −442 258 −159 ER HP ER −1,185 220 1,174 −1,185 220 1,174 86 −158 1,543 2.67 d 17.1 a. Positive numbers indicated increased energy use, and negative numbers indicate decreased energy use. b. The 0700 peak curtailment event was not successfully implemented because of a communication failure between the GE Nucleus and the GE server. Therefore, the data shown are the average for the combined PM and EVE events. Disaggregated data for the PM and EVE events are available elsewhere [13]. c. Does not include the 0200 event when both water heaters had zero load per hot water draw schedule. d. Ration range is from 2.12 for the 0200 event to 50.6 for the 0800 event when the HPWH ramping capability in heat pump mode is significantly decreased. 5.5 Experiment #5: Sanden GES-15QTA HPWH Unitary System Demand Response A DR schedule to simulate an oversupply (peak curtailment) condition and a balancing reserves condition was generated to ascertain the performance of the Sanden unitary water heater and demonstrate the peak shift or reduction associated with each experiment. The peak curtailment experiment is of considerable interest to utilities deploying ERWHs in DR to manage peak demand. Only the oversupply experiment shown in Table 5 is reported. The balancing reserves experiment is reported elsewhere [16]. Table 5. Sanden unitary HPWH oversupply experiment. Day 1 2 3 4 5 6 7 Start Time 1800 1700 1600 1500 1400 1300 1200 End Time 2400 2400 2400 2400 2400 2400 2400 Duration (hours) 6 7 8 9 10 11 12 As noted in Table 5, the experiment consists of increasing the time the unit is off in 1-hour increments, beginning at 6 hours on Day 1 to a total of 12 hours by Day 7. This increased daily strain on the system was imposed to determine at which hour the system cannot meet the delivered water temperature during the daily draw schedule. The experiment also was designed to determine the load impact from the shift in the HPWH operation. The unit was baselined for 7 days prior to initiating the DR experiments. Figure 6 shows the water temperature profile for the second DR event (Day 2) where the water heater was off for 7 hours. The corresponding water heater power draw for Day 2 is shown in Figure 7 along with the outdoor air temperature (red dotted line) and crawl space temperature (green solid line). The Day 2 event is shown here as this is the time period during which the hot water temperature drops below the tank set point to about 115°F (46°C) after 6 hours, thus making this demand event resulting in a likely unacceptable water temperature and thus unavailable for residential application. The sawtooth pattern shown in Figure 6 (and Figure 8) is a result of the temperature monitoring via an insertion thermocouple in a thermowell at the outlet of the mixing valve. As water is drawn, the temperature peaks to the set delivery temperature, a nominal 120°F (49°C), followed by the temperature decay after the draw is concluded. This decay approached ambient temperature (i.e., temperature of the water heater closet) until the next draw occurs at which time the cycel begins again 10 Figure 6. Sanden unitary HPWH oversupply experiment delivered water temperature profile: second DR event (7 hours powered-down). Figure 7. Sanden unitary HPWH oversupply experiment power profile: second DR event (7 hours powered-down). 5.6 Experiment #6: Sanden GAU-315EQTA HPWH Split System DR The same peak curtailment DR schedule used for the unitary system (Table 5) was used to ascertain the performance of the Sanden split system water heater. The balancing reserves DR experiment schedule for the split system was identical to the unitary system experimental schedule. These schedules are reported elsewhere [16]. The split system was baselined for 7 days prior to initiating the DR experiments. Figure 8 shows the water temperature profile for Day 7 of the experiment when the water heater was off for 12 hours, the longest duration of power-down. The corresponding water heater power draw for Day 7 is shown in Figure 9 along with the outdoor air temperature (red dotted line). 11 Figure 8. Sanden Split System HPWH Oversupply Experiment Delivered Water Temperature Profile for Last DR Event (12 hours powered-down). The temperature profile in Figure 8 shows that the delivered temperature still maintains the 120°F values across the DR period because of both the elevated set point and the larger tank capacity. This observation was expected given the size of the storage tank. Figure 9. Sanden split system HPWH oversupply experiment power profile for last DR event (12 hours powered-down) Table 6 presents the summary finding for the oversupply experiments. The Dispatchable Power is the peak watts available to be shifted through oversupply implementation. The Recovery Energy Shift is the value of energy (kWh) that is shifted to the post-oversupply period. The oversupply duration indicates the number of hours the protocol was enacted while still delivering hot water at an acceptable temperature to the household. 12 Table 6. Summary of the oversupply DR experiments in the Sanden units: power, energy shift and off-period delivered acceptable hot water temperature. Experimental Results Dispatchable Power (kW) a Recovery Energy Shift (kWh) b Oversupply Duration (hours) Maximum Off-Period while Acceptable Hot Water Temperature Met (hours) Unitary System 1.3 2.65 6 6 dispatchable Split System 1.2 2.95 6 12 a The Oversupply Recovery Energy Shift is the water heater energy use at the conclusion of the oversupply period. b The Oversupply Duration of the split system presented was for the 6-hour interval and provided for comparison to the unitary system. 6.0 Discussion and Conclusions The following is a summary discussion of the experiments and conclusions drawn from the experiment. Experiments 1 and 2 are combined in this discussion because the purpose of those experiments was to determine overall/annual space conditioning (heating/cooling) impact from HPWH ducting. Additional details on the cooling season impact and the heating season impact can be found elsewhere [15]. 6.1 Experiments 1 and 2: Whole-House Space Conditioning Annualized Impact of HPWH Ducting The experimental results were annualized for the climate in Richland, Washington, based on the average number of heating days and cooling days in a year. Specifically, the daily difference in HVAC energy usage for the exhaust-only ducted versus unducted configuration are combined to yield a daily whole-house difference in energy use for that case, assuming all other loads are identical. The annual difference in whole-house energy use for the fully ducted HPWH compared to the unducted HPWH is calculated in a similar manner. The expected annual difference in HVAC and whole-house energy use using this method is shown in Table 7. Table 7. Comparison of HVAC and whole-house energy use for exhaust-only and fully ducted HPWH configurations vs. an unducted HPWH. HPWH Configuration HVAC Energy Use Difference vs. Unducted Whole-House Energy Use Difference vs. Unducted Exhaust Only 858 ±440 kWh/yr 6.2 ±3.2% −1,079 ±408 kWh/yr −7.8 ±3.0% 714 ±446 kWh/yr 2.9 ±1.8% −1,031 ±411 kWh/yr −4.2 ±1.7% Fully Ducted As shown in Table 7, the fully ducted configuration has a significant energy benefit on the HVAC and whole-house energy use (7.8% and 4.2% less energy use, respectively) whereas the exhaust-only configuration has a negative impact on the HVAC and whole-house energy use (6.2% and 2.9% increase in energy use). Also note that the differences for both ducting configurations in HVAC and whole-house energy use is much larger than the difference in water heater energy use (shown in Table 2). The annualized differences in space conditioning energy usage is dominated by space heating, which could be considered a worst-case comparison in this experiment because of the use of an electric resistance furnace for space heating and heat pump for space cooling. These data can be used to ascertain the cost-effectiveness of ducting (exhaust only or fully ducted) a HPWH taking into account the climate (i.e., degree-days), the cost of ducting, and the cost of energy for water heating and space heating and cooling. The theoretical annualized differences for exhaust only and ducted configurations also were determined from modeling. Modeling suggests that HPWHs installed in conditioned space will increase HVAC energy use in the heating season because of the use of air that has been initially 13 heated by the HVAC system to heat water and the introduction of cool exhaust air into the space. Therefore, models assume, any heat that has been extracted from the space must be made up, or reheated, by the HVAC system to maintain interior thermostat set points. These models also indicate that exhaust ducting will mitigate the impact of HPWHs on space conditioning systems by preventing cool exhaust air from being introduced into the conditioned space. However, data collected during this experiment suggest that exhaust-only ducting did not decrease space conditioning energy use, as compared an unducted HPWH. The experimental data may suggest that the reduced HVAC impact is due to buffering of the HPWH space conditioning impacts by the interior walls. For the unducted HPWH, the water heater closet experienced localized cooling while the thermostat, located in the hallway near the kitchen (see Figure 1), was not affected by the HPWH thermal loads. Data taken during the experiments were not sufficient to fully address this observation and further discussions are published elsewhere [14]. 6.2 Experiment 3: GE GeoSpring Water Heater Energy Use in Ducted Configurations. From Table 2, exhaust-only ducting decreased water heater energy use by 144 ±74 kWh/year on an annualized basis. However, this decrease was offset by an increase in whole-house energy use of 714 ±446 kWh/year on an annualized basis (Table 7). Therefore, exhaust ducting in a climate similar to that of Richland, Washington, would not be cost effective. Annualized estimation would be needed for other climate regions to determine overall net energy impacts. Fully ducting the HPWH resulted in a net increase in water heater energy use by 48 ±49 kWh/yr on an annualized basis (Table 7). However, this increase is relatively small compared to the decrease in whole-house energy use of 1,031 ±411 kWh/year on an annualized basis (Table 7). Therefore, from a whole-house perspective, the net energy impacts of HPWHs installed in conditioned space are driven by the HVAC system interaction and not by the impact of the ducting on the water heater performance. The magnitude of these energy impacts, their costs and the costs for ducting were determined and reported elsewhere [15]. This analysis suggests that exhaust-only ducting may not be advisable but that full ducting may be cost effective over the lifetime of the water heater in climates comparable to that of Richland, Washington. However, additional analysis would be needed to take these data and develop recommendations for the variety of energy rates, climates, and installations/configurations where HPWHs may be installed. 6.3 Experiment 4: GE GeoSpring HPWH DR Compared to ERWH Based on the data collected in these DR experiments, both ERWH and HPWH are capable of performing peak curtailment and regulation services. However, their characteristics differ, as can be seen in Table 4 which shows the average impact on power use during the DR event, energy use during the DR event, and daily energy use for ERWH and HPWH for peak curtailment, INC events, and DEC events. The HPWH provides approximately 38% of the peak reduction or INC balancing response of the ERWH, when accounting for differences in power use and use profiles of the water heaters. The ERWH provides more dynamic response with a large amount of power increase or decrease per water heater. However, the HPWH has longer and more frequent operating times, which means the HPWH is able to respond when an INC event or peak curtailment is needed. In addition, the inherent measured efficiency savings of HPWH (61.7 ±1.7%) compared to a standard ERWH will result in some permanent peak savings as well (not quantified here), resulting in overall peak load reduction for a utility with significant penetration of HPWHs. However, the DEC response of the HPWH is limited during some parts of the day when especially high hot water use occurs. During the nighttime when there is little to no hot water draw activity, the HPWH has significant capacity to increase load because it takes much longer for increases in tank temperature to saturate, as compared to an ERWH. And, in experiments reported elsewhere [19], a modification to the HPWH control algorithm can allow the HPWH reach tank temperatures above 135ºF (57°C) using only the heat pump mode for overnight DEC response. 14 With regard to hot water delivery, decreased hot water delivery temperature was measured for all DR events. The most dramatic delivered hot water temperature decrease was ~18ºF (~8°C) for the HPWH during an afternoon peak curtailment event. However, an extremely high hot water draw profile was implemented during these events to provide a “worst-case scenario.” Based on the results of these experiments, decreased hot water delivery temperature is not likely to be an issue for the majority of participants in a DR program providing peak curtailment or INC balancing services even when only the heat pump is used to heat water. A more comprehensive discussion of this experiment can be found elsewhere [19]. 6.4 Experiments 5 and 6: Sanden HPWH DR Peak Curtailment The Sanden split system with the 80 gal (303 L) tank was able to maintain ~120ºF delivered hot water temperature under the relatively extreme DR experiment where the unit was powered off for 12 hours. And, when the DR event was terminated, the ramp up peak power draw was ~1500 W at midnight, thus shifting this peak to a typically off-peak period for most utilities. This is approximately the same peak draw as a standard ERWH (not reported here; see reference [16]). Given the Day 7 experiment profile (Figure 9), it is likely the water heater could provide near 120ºF (49°C) hot water to the home during the initial early morning (0600) hot water draw (~4 gal/hour/~15 L/hr) to later (0700) hot water draw (~11 gal/hr/~43 L/hr) without being powered. This is an advantage of the large tank capacity and flexibility of this unit should a utility wish to avoid an early morning peak. Additional analysis and discussion of the energy impacts of DR compared to ERWH can be found elsewhere [16]. The Sanden integrated system with the 40-gal (151-L) tank was unable to maintain ~120ºF (~49°C) delivered hot water temperature for more than 5 hours after powered off (Figure 6). The delivered water temperature after 5 hours was ~108ºF (42°C) would likely not be acceptable to home occupants. These results were anticipated with a 40 gal tank and were similar to the observation with the GE GeoSpring HPWH DR experiment. However, both the unitary and split systems can effectively recover from peak curtailment up to a minimum of 5 hours in the case of the 40-gal (151-L) unitary system and 12 hours for the 80-gal (303-L) split system. As with the GE GeoSpring HPWH, a utility seeking 3 to 4 hours of peak curtailment and/or peak shifting could successfully deploy the integrated system while simultaneously harvesting the advantage of using less energy to deliver hot water to a home [16]. 7.0 Recommendations Results obtained from the experiments described in this paper answered many questions regarding installation, performance, and DR potential for the current and future generation of HPWHs. Observations made during these experiments also led to questions that could be answered through additional research. These issues and additional research areas include, but are not limited to: • The GE GeoSpring HPWH demonstration found significant differences between the modeled energy impacts of an unducted HPWH compared to the measured impacts. A more thorough measurement and analysis of air infiltration and movement and temperature gradients inside the home with an unducted HPWH installed in conditioned space needs to be undertaken. • As delivered, the GE GeoSpring HPWH was not configured for operating with ducting, so the ducting had to be custom designed. A similar study of an unitary HPWH, and perhaps a HPWH with a larger (60-80 gal) tank that was configured for ducting at the factory, may provide additional data on the overall impact of ducting and the optimal ducting configuration for installation in a conditioned space. • The impact of exterior temperature, water supply temperature, and closet temperature for the Sanden split system on the overall system performance is not well understood. A systematic and controlled evaluation and analysis would be of value given a small number of field research studies have indicated that these variables are not determinative of overall system performance [23]. 15 8.0 References [1] EIA—U.S. Energy Information Administration. 2009. Residential Energy Consumption Survey. U.S. Department of Energy, Washington, D.C. Available at http://www.eia.gov/consumption/residential/. [2] 75 FR 20112. April 16, 2010. “10 CFR Part 430 Energy Conservation Program: Energy Conservation Standards for Residential Water Heaters, Direct Heating Equipment, and Pool Heaters; Final Rule.” Federal Register, U.S. Department of Energy. Available at http://www.regulations.gov/#!documentDetail;D=EERE-2006-STD-0129-0005 [3] American Council for an Energy-Efficient Economy. Water Heating. Available at http://aceee.org/node/3068. [4] Kresta, D. 2012. Heat Pump Water Heater Market Transformation Update. Northwest Energy Efficiency Alliance. Portland, Oregon. [5] Larson, B., M, Logsdon and D. Baylon. 2011. Residential Heat Pump Water Heater Evaluation: Lab Testing & Energy Use Estimates. Available at: http://www.bpa.gov/energy/n/emerging_technology/pdf/HPWH_Lab_Evaluation_Final_Report _20111109.pdf. [6] Larson, B. and M. Logsdon. 2012. NEEA Report: Laboratory Assessment of General TM Electric GeoSpring Hybrid Heat Pump Water Heater. REPORT #09282012, Ecotope, Inc. for the Northwest Energy Efficiency Alliance, Portland, Oregon. [7] Maguire, J., J. Burch, T. Merrigan and S. Ong. 2013. Energy Savings and Breakeven Cost for Residential Heat Pump Water Heaters in the United States. NREL/TP-5500-58594, National Renewable Energy Laboratory, Golden, Colorado. Available at: http://techportal.eere.energy.gov/techpdfs/HPWH_mapping.pdf. [8] Lu, S.; N. Samaan, R. Diao, M. Elizondo, C. Jin, E. Mayhorn, Y. Zhang and H. Kirkham. 2011. Centralized and Decentralized Control for Demand Response. Innovative Smart Grid Technologies (ISGT), 2011 IEEE PES, 1(8):17-19 Jan. 2011. Available a: http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=5759191 [9] 10 CFR 430.23(e). 2012. “Test Procedures for the Measurement of Energy and Water Consumption – Water Heaters.” Code of Federal Regulations, U.S. Department of Energy, Washington, D.C. Available at http://www.ecfr.gov/cgi-bin/textidx?c=ecfr&sid=4244256deb6e3f16076e5cb34c6b93d9&rgn=div8&view=text&node=10:3.0.1. 4.18.2.9.2&idno=10 [10] Sepulveda, A., L. Paull, W. Morsi, H. Li, C. Diduch and L. Chang. 2010. A Novel Demand Side Management Program using Water Heaters and Particle Swarm Optimization. IEEE Electrical Power & Energy Conference (EPEC), IEEE , 1(5):25-27 Aug. 2010. Available at http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=5697187 [11] Diao, R., S. Lu, M. Elizondo, E. Mayhorn, Y. Zhang and N. Samaan. July 2012. Electric Water Heater Modeling and Control Strategies for Demand Response. Power and Energy Society General Meeting, 2012 IEEE , 1(8):22-26. Available at http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=6345632. [12] Mathieu, J., M. Dyson and D. Callaway. 2012. Using Residential Electric Loads for Fast Demand Response: The Potential Resource and Revenues, the Costs, and Policy Recommendations. ACEEE Summer Study on Energy Efficiency in Buildings, Pacific Grove, California. Available at http://www.aceee.org/files/proceedings/2012/data/papers/0193000009.pdf 16 [13] Saker, N.; M. Petit and J Coullon. 2011. Demand Side Management of Electrical Water Heaters and Evaluation of the Cold Load Pick-Up Characteristics (CLPU). 2011 IEEE Trondheim Power Tech, 1(8):19-23 June 2011. Available at http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=6019312. [14] Widder, S., G. Parker, J. Petersen and M. Baechler. 2014. Impact of Ducting on Heat Pump Water Heater Space Conditioning Energy Use and Comfort. PNNL-23526, Pacific Northwest National Laboratory, Richland, Washington. Available at http://labhomes.pnnl.gov/news.stm. [15] Larson, B. 2013. Laboratory Assessment of Sanden GAU Heat Pump Water Heater. WSU Publication WSUEEP14-003, Washington State University, Pullman, Washington. Available at http://www.energy.wsu.edu/documents/Sanden_CO2_split_HWPH_lab_report_Final_Sept%2 02013.pdf. [16] Sullivan, G.P. and J.P. Petersen. 2015. Demand Response Performance of Sanden Unitary/Split System Heat Pump Water Heaters. PNNL-24224, Pacific Northwest National Laboratory, Richland, Washington. [17] Hendron, R. and C. Engebrecht. 2010. Building America House Simulation Protocols. TP-550-49426, National Renewable Energy Laboratory, Golden, Colorado. Accessed August 6, 2013, at http://www.nrel.gov/docs/fy11osti/49246.pdf. [18] Christian, J., T. Gehl, P. Boudreaux, J. New and R. Dockery. 2010. Tennessee Valley Authority's Campbell Creek Energy Efficiency Homes Project: 2010 First Year Performance Report July 1, 2009–August 31, 2010. ORNL/TM-2010/206, Oak Ridge National Laboratory, Oak Ridge, Tennessee. Accessed August 6, 2013, at http://info.ornl.gov/sites/publications/files/pub26374.pdf [19] Widder, S., J. Peterson, G. Parker and M. Baechler. 2013. Demand Response Performance of GE Hybrid Heat Pump Water Heater. PNNL-22642, Pacific Northwest National Laboratory, Richland, Washington. Available at http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-22642.pdf. [20] Lutz, J., A. Renaldi, A. Lekov, Y. Qin and M. Melody. 2011. Hot Water Draw Patterns in Single-Family Houses: Findings from Field Studies. LBNL-4830E, Lawrence Berkeley National Laboratory, Berkeley, California. [21] ASTM International. 2010. ASTM Standard E779-10: Standard Test Method for Determining Air Leakage Rate by Fan Pressurization. ASTM International, West Conshohocken, Pennsylvania. [22] The Energy Conservatory. 2012. Minneapolis Blower Door Operation Manual for Model 3 and Model 4 Systems. The Energy Conservatory, Minneapolis, Minnesota. [23] Eklund, K., A. Banks and B. Larson. 2014. Advanced Heat Pump Water Heater Research First Midterm Field Study Report. WSUEEP15-005, Washington State University, Pullman, Washington. Available at http://www.energy.wsu.edu/documents/First%20Midterm%20Report%20on%20Monitoring%2 0of%20Advanced%20HPWH%20from%20Installation%20thru%20March%202014Corrected.pdf. 17