SCADA connectivity

advertisement
Siemens Remote Control Unit™
Monitor and control your rural network
www.siemens.com/Fusesaver
Answers for infrastructure and cities.
An intelligent solution
for rural networks
ƒƒImproving network
reliability in a cost
effective way is one of
the most challenging
tasks for power utilities
today.
2
ƒƒReducing the number
and duration of power
outages and limiting the
number of affected
customers are important
steps toward this goal.
ƒƒRemotely monitoring
and controlling the
network is key to
achieving this.
Siemens Fusesaver
Ever increasing regulatory demands means medium
voltage, rural electricity network operators are under
pressure to gather accurate data about network
performance.
The Siemens Fusesaver is a self-powered, electronically
controlled, single-phase fault interrupting device that is
installed in series with a fuse to protect that fuse from
transient faults. A short-range wireless communication
module is fitted to Fusesaver allowing you to:
ƒƒ manually operate using the Connect PC application
ƒƒ configure protection modes
ƒƒ download event log files from Fusesaver memory
ƒƒ view live data on status of each device including time,
type and magnitude of the most recent fault.
ƒƒ connect with Siemens Remote Control Unit
Control Fusesaver
Add the Siemens Remote Control Unit (RCU) and interface
Fusesaver with a SCADA system to provide remote access
to Fusesavers throughout your rural network.
Mounted beneath the Fusesaver, the RCU uses short-range
radio to communicate with Fusesaver, and long-range
backhaul radio or modem to remotely monitor and control
Fusesavers via the utility SCADA system to:
ƒƒ receive fault alerts
ƒƒ remotely operate Fusesaver sites
ƒƒ change protection modes from afar
ƒƒ saving line crew cost and effort, and improving
response time.
3
Bushfire
mitigation
Remote control of Fusesavers allows utilities in high-risk
bushfire areas or on high-risk days to change protection
by applying a different protection mode:
ƒƒ Normal protection
ƒƒ ‘Single shot’ using standard Fusesaver protection
ƒƒ ‘Single shot’ with instantaneous trip (half cycle) for
Code Red or extreme risk days
ƒƒ Protection off
Single shot modes allow supply to continue until any fault
occurs then the Fusesaver trips and stays open. Supply
can be reconnected remotely when required.
Local/remote lockout capability enables line crews to
disable Remote Control whilst they are working on the
downstream line, ensuring supply is not reinstated
unawares from afar.
4
Function
ƒƒ connects wirelessly to Fusesavers fitted with
Communications Modules via short range radio
ƒƒ simple installation, requiring only mounting and
connection of power and ground
ƒƒ powered from 115/230VAC low voltage supply or solar
panel (suitable locations only), eliminating the need for
an additional VT (option available)
ƒƒ power backup from 7AH 12V standard lead/acid battery
ƒƒ provides sheltered accommodation for the backhaul
radio/modem
ƒƒ DNP3 over serial link communications protocol suits
most SCADA systems / others available upon request
ƒƒ variety of settings, including protocol configuration and
radio interface. Configurable using the supplied PC
configuration/maintenance tool.
ƒƒ troubleshooting is simplified by an LED display showing
status of processor, power supply, communications and
Fusesavers. Additional fault finding can be performed
with the PC configuration/maintenance tool
ƒƒ purposely designed for outdoor use, not an adaptation
of a general purpose RTU
ƒƒ optional operator panel for local operator controls
ƒƒ use almost any radio/modem, with a user-settable DC
power supply, plus various signal interfaces, including
serial data and ethernet
5
Specifications
Value
Power supply
115/230 VAC mains
12V/7.2Ah Battery backup
Solar power option
6
Radio power supply
User set variable 3-9V 2A
or 12V battery supply 5A
Radio data interface
Serial asynchronous RS232
or user set logic levels variable 3-9V
or 10/100 Base T Ethernet
Radio compartment size
170 x 215 x 100mm
Standard protocol
DNP3 or others available upon request
Weight
18 kgs
Siemens Fusesaver with RCU
– a well thought out system
Fusesaver and RCU were developed as a part of an integrated system of tools and accessories.
All components permit easy installation, fast commissioning and reliable operation.
Solar panel
Solar ratings
Value
Power rating
65W
Nominal voltage
12V
Cell type
Polycrystalline
Additional VT
VT ratings
Value
Value
Where solar power is not practical,
the RCU can be powered with a
voltage transformer. Optional surge
arrestors fitted.
Primary voltage
11kV p-p
22kV p-p
Secondary voltage
115V
230V
VA
300
300
In suitable locations, the RCU can be
powered by an optional solar panel,
mounted above.
According to IEC 60044-2
7
Siemens Ltd.
www.siemens.com.au
Australia Nationwide
Telephone +61 3 9721 2000
Facsimile +61 3 9721 2001
Head Office Australia
885 Mountain Highway
Bayswater VIC 3153
ABN: 98 004 347 880
Manufacturing Facility
Siemens Ltd.
37 Chetwynd St
Loganholme
Queensland
Australia 4129
Siemens (N.Z.) Limited
www.siemens.co.nz
Head Office New Zealand
55 Hugo Johnston Drive
Penrose Auckland
Telephone +64 9 580 5500
Facsimile +64 9 580 5501
© 2013 Siemens Ltd.
Produced by
Siemens Communications
Australia and New Zealand
www.siemens.com.au/Fusesaver
Download