Lighting Controls

advertisement
UMC El Paso Far East Clinic and Neighborhood Healthcare Center West
Page Project No. 414018 and 414019
Issue for Construction
April 13, 2015
SECTION 265400 - LIGHTING CONTROLS
PART 1 - GENERAL
RELATED DOCUMENTS
1.1
A.
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this section.
SUMMARY
1.2
A.
This section includes the following lighting controls:
1.
The lighting control system is indicated by the drawings and by the requirements of this
section. It is defined to include:
a.
2.
Wiring devices such as daylight harvesting sensors, occupancy sensors, and
vacancy switches. Dual level power room controllers will be utilized to interconnect
the devices.
System installation includes the following:
a.
b.
c.
d.
Wiring of main and branch circuit conductors.
Installation of external control devices and wiring to the remote controllers per
room.
Installation of communications conductors and associated hardware.
Training of Owner’s personnel in the configuration and use of the system for
normal operating purposes.
SUBMITTALS
1.3
A.
Product Data: For each type of product indicated.
B.
Shop Drawings: Detail assemblies of standard components, custom assembled for specific
application on this Project.
1.
Outline Drawings:
Indicate dimensions, information packages, arrangement of
components, and clearance and access requirements for devices.
2.
Block Diagram: Show interconnections between components specified in this Section
and devices furnished with power distribution system components. Indicate data
communication paths and identify networks, data buses, data gateways, concentrators,
and other devices to be used. Describe characteristics of network and other data
communication lines.
3.
Wiring Diagrams: Power, signal, and control wiring.
presentation with a block diagram.
4.
Coordination Drawings: Submit evidence that lighting controls are compatible with
connected Ethernet system.
Coordinate nomenclature and
LIGHTING CONTROL
265400 - 1
UMC El Paso Far East Clinic and Neighborhood Healthcare Center West
Page Project No. 414018 and 414019
C.
Issue for Construction
April 13, 2015
5.
Show interconnecting signal and control wiring and interfacing devices that prove
compatibility of inputs and outputs.
6.
For networked controls, list network protocols and provide statements from
manufacturers that input and output devices meet interoperability requirements of the
network protocol.
Software and Firmware Operational Documentation:
1.
Software operating and upgrade manuals.
2.
Program Software And System Configuration Backup provided electronically, complete
with data files.
3.
Device address list.
4.
Printout of software application and graphic screens.
D.
Upgrade Kit: For Owner to use in modifying software and firmware to upgrade and to allow
system expansion. Must include full technical information on all installed devices.
E.
Field quality-control test reports.
F.
Operation and Maintenance Data: For lighting controls to include in emergency, operation, and
maintenance manuals.
QUALITY ASSURANCE
1.4
A.
Source Limitations: Obtain lighting control module and power distribution components through
one source from a single manufacturer.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C.
Comply with 47 CFR, Subparts A and B, for Class A digital devices.
D.
Comply with NFPA 70.
1.
Manufacturer shall be engaged in the manufacture of lighting control equipment and
ancillary equipment, of the types indicated, whose products have been in satisfactory use
in similar service for not less than five years. Design is based on Watt Stopper Digital
Lighting Management.
E.
Component Testing: All electronic component board assemblies are to be factory tested and
burned in prior to installation.
F.
System Support: Factory fax/telephone/email support shall be available free of charge during
normal business hours for the duration of the warranty period.
G.
NEMA Compliance: Comply with applicable portions of NEMA standards pertaining to types of
electrical equipment.
LIGHTING CONTROL
265400 - 2
UMC El Paso Far East Clinic and Neighborhood Healthcare Center West
Page Project No. 414018 and 414019
K.
Issue for Construction
April 13, 2015
H.
NEC Compliance: Comply with applicable portions of the NEC including 725.
I.
UL Compliance: Comply with applicable UL standards for energy management equipment.
J.
FCC Emissions: All assemblies are to be in compliance with FCC emissions Standards
specified in Part 15, Subpart J for Class A applications.
COORDINATION
L.
Coordinate lighting control components to form an integrated interconnection of compatible
components.
1.
Match components and interconnections for optimum performance of lighting control
functions.
WARRANTY
1.5
A.
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or
replace components of lighting controls equipment that fail in materials or workmanship within
specified warranty period.
1.
Failures include, but are not limited to, the following:
a.
b.
c.
2.
Software: Failure of input/output to execute switching or dimming commands.
Failure of modular relays to operate under manual or software commands.
Damage of electronic components due to transient voltage surges.
Warranty Period: Cost to repair or replace malfunctioning parts for two years from date
of Substantial Completion.
EXTRA MATERIALS
1.6
A.
Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents. Each label
must also be clearly stated.
1.
Photoelectric devices and sensor components: Equal to 10 percent of amount installed.
Must be delivered to and receipted by the Owner.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Manufacturers subject to compliance with requirements, provide products by the following:
1.
Watt Stopper Digital Lighting Management.
2.
For substitutions see Division 1 submittal requirements.
FUNCTIONAL SYSTEM DESCRIPTION
A.
Material and Components:
LIGHTING CONTROL
265400 - 3
UMC El Paso Far East Clinic and Neighborhood Healthcare Center West
Page Project No. 414018 and 414019
2.3
Issue for Construction
April 13, 2015
1.
The lighting control system shall consist of microprocessor-based control electronics with
integral room controller packs for power.
2.
All lighting control components shall be installed as per plan (as noted on drawings).
Suitable barriers shall be installed to separate Class 2 wiring from power conductors.
MANUAL SWITCHES AND PLATES
A.
2.4
Switches: Modular, momentary push-button, low-voltage type.
1.
Color: Ivory with stainless steel cover plates, unless otherwise indicated.
2.
Lighting override switches shall be conspicuously labeled as “Lighting Override” and also
display in an inconspicuous but clearly visible fashion the unique identifier of the switch
as it appears on the construction drawings.
CONDUCTORS AND CABLES
A.
Power Wiring to Supply Side of Class 2 Power Source: Not smaller than No. 12 AWG,
complying with Division 26 Section "Conductors and Cables."
B.
Classes 2 and 3 Control Cable: Multiconductor cable with copper conductors not smaller than
No. 22 AWG, complying with Division 26 Section "Conductors and Cables."
C.
Class 1 Control Cable: Multiconductor cable with copper conductors not smaller than No. 16
AWG, complying with Division 26 Section "Conductors and Cables."
D.
Digital and Multiplexed Signal Wire: Shielded, twisted-pair cable complying with Division 26
Section "Voice and Data Communication Cabling."
PART 3 - EXECUTION
3.1
WIRING INSTALLATION
A.
Wiring Method: Install wiring in raceways. Comply with Division 26 Section "Conductors and
Cables." Minimum conduit size shall be 1/2 inch (13 mm).
B.
Wiring within Enclosures: Bundle, lace, and train conductors to terminal points. Separate
power-limited and non-power-limited conductors according to conductor manufacturer's written
instructions.
C.
Install field-mounting transient voltage suppressors for lighting control devices in Category A
locations that do not have integral line-voltage surge protection.
D.
Size conductors according to lighting control device manufacturer's written instructions, unless
otherwise indicated.
E.
Splices, Taps, and Terminations: Make connections only on numbered terminal strips in
terminal cabinets, equipment enclosures, and in junction, pull, and outlet boxes.
LIGHTING CONTROL
265400 - 4
UMC El Paso Far East Clinic and Neighborhood Healthcare Center West
Page Project No. 414018 and 414019
F.
3.2
Issue for Construction
April 13, 2015
Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A and UL 486B.
IDENTIFICATION
A.
3.3
Identify components and power and control wiring according to Division 26 Section "Electrical
Identification."
FIELD QUALITY CONTROL
A.
Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect, test, and adjust field-assembled components and equipment installation, including
connections, and assist in field-testing. Report results developed and provided by factoryauthorized service representative in writing.
B.
Perform the following field tests and inspections and prepare test reports:
3.4
1.
Test for circuit continuity.
2.
Verify that the control module features are operational.
3.
Check operation of local override controls.
4.
Test system diagnostics by simulating improper operation of several components
selected by the Owner.
ADJUSTING – The paragraph applies to each building individually.
A.
3.5
When requested within 12 months of date of Substantial Completion, provide quarterly on-site
assistance in reviewing Owner’s lighting panel operating configuration changes and in adjusting
occupancy sensors to suit actual occupied conditions. Provide visits to site outside normal
occupancy hours for this purpose.
TRAINING – This paragraph applies to each building individually.
A.
Engage a factory-authorized service representative to train Owner's maintenance personnel to
configure, adjust, operate, and maintain lighting controls. The training shall consist of 16 hours
onsite, split up into no more than 3 hour sessions.
END OF SECTION
LIGHTING CONTROL
265400 - 5
Download