Chapter 5 Transformer Part 2 Prepared by Dr. Mohd Azrik Bin Roslan What you should know at the end of this chapter What is transformer Mutual inductance Ideal transformer Non-ideal transformer Open circuit test Short circuit test Per unit system Autotransformer 3-phase transformer Application of transformer Transformer model parameters It is possible to experimentally determine the values of the inductances and resistances in the transformer model An adequate approximation of these values can be obtained with only two tests the open-circuit test the short-circuit test Open circuit test Conducted to determine Rc and XM Obtained components are connected in parallel One transformer winding is open-circuited, and the other winding is connected to full rated line voltage The input voltage, input current, and input power to the transformer are measured. (This measurement is normally done on the low~voltage side of the transformer, since lower voltages are easier to work with.) Open circuit test All the input current must be flowing through the excitation branch of the transformer. The series elements , Rp and Xp are too small in comparison to Rc and XM to cause a significant voltage drop, so essentially all the input voltage is dropped across the excitation branch. From this information, it is possible to determine the power factor of the input current and therefore both the magnitude and the angle of the excitation impedance. Open circuit test Admittance Yo c I oc Vo c Open circuit Power Factor Poc PF cos Voc I oc R Resistance X Reactance Z Impedance 1 Y G jB Admittance Z G Conductance B Susceptance Open circuit Power Factor Angle cos 1 Poc Voc I oc I oc 1 1 Yoc GC jBM j Voc RC XM Short circuit test Conducted to determine combined leakage reactance and winding resistance Obtained components are connected in series Low-voltage terminals of the transformer are short-circuited, and the high-voltage terminals are connected to a variable voltage source (This measurement is normally done on the high-voltage side of the transformer, since currents will be lower on that side, and lower currents are easier to work with.) Short circuit test The input voltage is adjusted until the current in the short circuited windings is equal to its rated value The input voltage, current, and power are measured. Since the input voltage is so low during the short-circuit test, negligible current flows through the excitation branch If the excitation current is ignored, then all the voltage drop in the transformer can be attributed to the series elements in the circuit. Short circuit test Impedances referred to the primary side Psc PF cos Vsc I sc Power Factor of the current Angle Power Factor Therefore Z sc Vsc I sc Psc cos Vsc I sc 1 Vsc 00 Vsc 0 Z sc 0 I sc I sc Z sc Req jX eq R p a 2 Rs j X p a 2 X s Voltage regulation (VR) Because a real transformer has series impedances within it, the output voltage of a transformer varies with the load even if the input voltage remains constant. The voltage regulation of a transformer is defined as the change in the magnitude of the secondary voltage as the current changes from full load to no load with the primary held fixed. VR Vs ,nl Vs , fl Vs , fl Vs At no load, Vp VR a X 100% Req s jX eq s Is Vp a Vp Vs , fl Vs , fl aI p a X 100% Vs Voltage regulation (VR) Lagging PF Vp Vs a so VR 0 Unity PF Vp Vs a so VR 0 Leading PF Vp Vs a so VR 0 Transformer Efficiency Transformers are also compared and judged on their efficiencies. The efficiency of a device is defined by the equation Pout 100% Pin Pout Pout P losses X 100% Transformer Efficiency There are three types of losses present in transformers Copper (I2R) losses. These losses are accounted for by the series resistance (Rp and Rs) in the equivalent circuit. Hysteresis losses. These losses are included in resistor Rc. Eddy current losses. These losses are also included in resistor Rc. Output power is given by Pout Vs I s cos so Vs I s cos X 100% Vs I s cos Pcu Pcore Pcu Pcopper losses Pcore Peddy current Physterisis Example 5 The equivalent circuit impedances of a 20-kVA, 8000/240 V, 60Hz transformer are to be determined. The open-circuit test was performed on the secondary side of the transformer (to reduce the maximum voltage to be measured) and the short circuit test were performed on the primary side of the transformer (to reduce the maximum (current to be measured). The following data were taken: POC Find the impedances of the approximate equivalent circuit referred to the primary side, and sketch that circuit. Example 5 Example 5 Example 5 Example 6 Example 6 S S Example 6 Example 6 Example 6 Per unit system The per unit value of any quantity is defined as Actual Quantity Per Unit, pu Base value of quantity Quantity – may be power, voltage, current or impedance Per unit system In normal practice Sbase and Vbase are defined Then the other base value can be determined Sbase I base Vbase Pbase ,Qbase , Sbase VbaseI base Zbase Vbase Vbase 2 I base Sbase Ybase I base Vbase Example 7 : Per Unit System Example 7 : Per Unit System Example 7 : Per Unit System Example 7 : Per Unit System Example 7 : Per Unit System Example 7 : Per Unit System Autotransformer On some occasions it is desirable to change voltage levels by only a small amount. 110 V 120 V 13.2 kV 13.8 kV These small rises may be made necessary by voltage drops that occur in power systems a long way from the generators. In such case, it is wasteful and excessively expensive to wind a transformer with two full windings, each rated at about the same voltage. A special-purpose transformer, called an autotransformer is used instead. Both the primary and the secondary are in a single winding. Autotransformer Conventional transformer Autotransformer Autotransformer Step-up autotransformer the first winding is shown connected in an additive manner to the second winding. the voltage at the output of the whole transformer is the sum of the voltage on the first winding and the voltage on the second winding. The first winding here is called the common winding. The smaller winding is called the series winding Autotransformer Step-down autotransformer the voltage at the input is the sum of the voltages on the series winding and the common winding. the voltage at the output is just the voltage on the common winding. Autotransformer Because the transformer coils are physically connected, a different terminology is used for the autotransformer than for other types of transformers. The voltage on the common coil is called the common voltage Vc and the current in that coil is called the common current Ic. The voltage on the series coil is called the series voltage VSE and the current in that coil is called the series current ISE. Voltage and current on the low-voltage side of the transformer are called VL and IL respectively Voltage and current on the high-voltage side of the transformer are called VH and IH respectively Autotransformer Voltage and current relationship VC NC VSE N SE VL VC I L IC I SE I SE NC I C N SE VH VC VSE I H I SE NC VL I H VH I L NC N SE Autotransformer Input apparent power is equal to output apparent power for an ideal autotransformer: Sin VL I L Sout VH I H Sin Sout SIO The apparent power in transformer winding: Sw VC IC VSE I SE The ratio of apparent power in the primary and secondary of the autotransformer to the apparent power actually travelling through Its winding is S IO NC N SE SW N SE Apparent power rating advantage of an autotransformer over a conventional transformer. The apparent power that actually travelling through the transformer’s winding is less than the apparent power entering the primary and leaving the secondary of the transformer. Three phase transformer 3-phase transformer connections Wye-wye (Y-Y) Wye-delta (Y-∆) Delta-wye (∆-Y) Delta-delta (∆ -∆) N p1 Vp1 I s1 a N s1 Vs1 I p1 N p2 Ns2 N p3 Vp 2 Is2 a Vs 2 I p 2 Vp 3 I s3 a N s 3 Vs 3 I p 3 Phase 1 2 3 Primary phase voltage Vp1 Vp2 Vp3 Secondary phase voltage Vs1 Vs2 Vs3 Primary phase current Ip1 Ip2 Ip3 Secondary phase current Is1 Is2 Is3 Primary turns Np1 Ns1 Np2 Np3 Ns2 Ns3 Secondary turns Three phase transformer Wye-wye (Y-Y) Three phase transformer Wye-delta (Y-∆) Three phase transformer Delta-wye (∆-Y) Three phase transformer Delta-delta (∆ -∆)