VAL-SQ SE… 120, 160 and 200 kA Service Entrance protection Data Sheet 2460_en_B 2 The VAL-SQ SE… Surge Protective Device (SPD) provides maximum surge protection for the service entrance. These units are available with 120, 160 and 200 kA surge current ratings to protect electronic equipment in industrial, medical and commercial applications. – The VAL-SQ SE… utilizes a hybrid suppression circuit, Sine Wave Tracking, in a single, replaceable module. It provides both transient protection and up to -30 dB of noise filtration. Each surge suppression mode is individually fused. – The product is provided in a NEMA Type 1 metal enclosure and includes a function monitor. – 120, 160 or 200 kA surge current capacity per phase (L-N and N-G) protects against high-energy lightning strikes LEDs provide continuous feedback on the status of each phase Suppression status alarm sounds if protection is not active due to a fault Dry contacts allow connection to a remote monitoring system Sine Wave Tracking filter for increased equipment protection LCD counter displays the number of surges safely taken to earth-ground Replaceable modules available in the event of damage UL/cUL listed; meets UL 1449 2nd edition February 2007 requirements – – – – on lin e co m po ne – Features s. Description co © PHOENIX CONTACT - 2/2008 nt 1 m TRABTECH Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for all products listed on the following page: VAL-SQ SE… 3 Ordering Data Part No. Pcs./Pkt VAL-SQ SE 120-120/208Y/FM 2803917 1 Surge protective device, 160 kA, 3-phase, 4-wire + ground for 120/208 Wye configuration VAL-SQ SE 160-120/208Y/FM 2803920 1 Surge protective device, 200 kA, 3-phase, 4-wire + ground for 120/208 Wye configuration VAL-SQ SE 200-120/208Y/FM 2803933 1 Surge protective device, 120 kA, 4-wire + ground for 120/240 High-Leg Delta configuration VAL-SQ SE 120-120/240HLD/FM 2803969 1 Surge protective device, 160 kA, 4-wire + ground for 120/240 High-Leg Delta configuration VAL-SQ SE 160-120/240HLD/FM 2803975 1 Surge protective device, 200 kA, 4-wire + ground for 120/240 High-Leg Delta configuration VAL-SQ SE 200-120/240HLD/FM 2803988 1 Surge protective device, 120 kA, 3-wire + ground for 120/240 split-phase configuration VAL-SQ SE 120-120/240S/FM 2804021 1 Surge protective device, 160 kA, 3-wire + ground for 120/240 split-phase configuration VAL-SQ SE 160-120/240S/FM 2804034 1 Surge protective device, 200 kA, 3-wire + ground for 120/240 split-phase configuration VAL-SQ SE 200-120/240S/FM 2804047 1 Surge protective device, 120 kA, 3-phase, 4-wire + ground for 277/480 Wye configuration VAL-SQ SE 120-277/480Y/FM 2804076 1 Surge protective device, 160 kA, 3-phase, 4-wire + ground for 277/480 Wye configuration VAL-SQ SE 160-277/480Y/FM 2804089 1 VAL-SQ SE 200-277/480Y/FM 2804092 1 VAL-SQ SE 120-347/600Y/FM 2804115 1 VAL-SQ SE 160-347/600Y/FM 2804128 1 VAL-SQ SE 200-347/600Y/FM 2804131 1 Surge protective device, 120 kA, 3-phase, 3-wire + ground for 480 V Delta configuration VAL-SQ SE 120-480D/FM 2804144 1 Surge protective device, 160 kA, 3-phase, 3-wire + ground for 480 V Delta configuration VAL-SQ SE 160-480D/FM 2804157 1 Surge protective device, 200 kA, 3-phase, 3-wire + ground for 480 V Delta configuration VAL-SQ SE 200-480D/FM 2804160 1 Surge protective device, 120 kA, 3-phase, 3-wire + ground for 600 V Delta configuration VAL-SQ SE 120-600D/FM 2804513 1 Surge protective device, 160 kA, 3-phase, 3-wire + ground for 600 V Delta configuration VAL-SQ SE 160-600D/FM 2804520 1 VAL-SQ SE 200-600D/FM 2804526 1 co s. ne Surge protective device, 120 kA, 3-phase, 4-wire + ground for 347/600 Wye configuration Surge protective device, 160 kA, 3-phase, 4-wire + ground for 347/600 Wye configuration on lin e co m Surge protective device, 200 kA, 3-phase, 4-wire + ground for 347/600 Wye configuration po Surge protective device, 200 kA, 3-phase, 4-wire + ground for 277/480 Wye configuration Surge protective device, 200 kA, 3-phase, 3-wire + ground for 600 V Delta configuration 2460_en_B m Type Surge protective device, 120 kA, 3-phase, 4-wire + ground for 120/208 Wye configuration nt Products Description PHOENIX CONTACT 2 VAL-SQ SE… 4 Technical Data Surge Protection Data Maximum surge current per phase VAL-SQ SE 120… VAL-SQ SE 160… VAL-SQ SE 200… 200 kA see list below SPD circuit type Parallel hybrid EMI/RFI noise rejection -30 dB Response time < 1 ns Internal coordinated fusing yes Part No. Type MCOV 2803917 VAL-SQ SE 120-120/208Y/FM 150 500 2803920 VAL-SQ SE 160-120/208Y/FM 150 500 2803933 VAL-SQ SE 200-120/208Y/FM 150 500 2803969 VAL-SQ SE 120-120/240HLD/FM 150/320 2803975 VAL-SQ SE 160-120/240HLD/FM 150/320 L-N Surge Voltage Rating (SVR) L-G N-G L-L co Short circuit current rating (SCCR) Maximum continuous operating voltage (MCOV) m 120 kA 160 kA 200 kA 500 500 500 800 500 500 800 s. 500 800 500/900 500 800 500/800 500/900 500 800 nt 500/800 VAL-SQ SE 200-120/240HLD/FM 150/320 500/800 500/900 500 800 VAL-SQ SE 120-120/240S/FM 150 500 500 500 800 VAL-SQ SE 160-120/240S/FM VAL-SQ SE 200-120/240S/FM 2804076 VAL-SQ SE 120-277/480Y/FM 2804089 VAL-SQ SE 160-277/480Y/FM 150 500 500 500 800 150 500 500 500 800 320 po 2804034 2804047 ne 2803988 2804021 320 900 1200 1200 1800 900 1200 1200 1800 VAL-SQ SE 200-277/480Y/FM VAL-SQ SE 120-347/600Y/FM 2804128 VAL-SQ SE 160-347/600Y/FM 420 1200 1500 1500 2500 2804131 VAL-SQ SE 200-347/600Y/FM 420 1200 1500 1500 2500 VAL-SQ SE 120-480D/FM VAL-SQ SE 160-480D/FM co 2804144 2804157 m 2804092 2804115 320 900 1200 1200 1800 420 1200 1500 1500 2500 640 NA NA NA 1800 640 NA NA NA 1800 VAL-SQ SE 200-480D/FM 640 NA NA NA 1800 VAL-SQ SE 120-600D/FM 840 NA NA NA 2500 lin e 2804160 2804513 2804520 VAL-SQ SE 160-600D/FM 840 NA NA NA 2500 2804526 VAL-SQ SE 200-600D/FM 840 NA NA NA 2500 on General Data Dimensions (WxHxD) Weight Enclosure material 15 x 14 x 3.9 in. (381 x 356x 99 mm) 19.25 lb. (8.73 kg). Metal Housing rating NEMA 1 Mounting method Surface Connection method – phase Screw terminal, #2-10 AWG Connection method – function monitor Screw terminal, #14-22 AWG Operating frequency 50-60, 400 Hz Operating temperature -40 to 140°F (-40 to 60°C) Storage temperature -40 to 160°F (-40 to 70°C) Operating altitude 0 to 12,000 ft. (3,658 m) above sea level 2460_en_B PHOENIX CONTACT 3 VAL-SQ SE… Approvals UL/cUL 1449 2nd edition, February 2007 requirements 1283 CSA C22.2 No. 8-M1986 IEEE C62.41.1-2002 C62.41.2-2002 C62.45-2002 Dimensions s. Q nt VA L-S SE Seri es ØA BT EC H ØB ØC ww w.ph oenix act.c om Figure 1 2460_en_B on lin e co m po cont 12.68 in. 322 mm ne TR A 13.19 in. 335 mm 14.00 in. 356 mm . in 8 .9 m 13 m 5 35 . in 00 m 9. 9 m 22 Surg e Pr ote ctiv eD evic e co m 3. 99 89 m in. m 5 15. 0 381 0 in. mm . 5 in 1.9 m m 50 . 1 in 1.2 m m 31 Dimensions PHOENIX CONTACT 4 VAL-SQ SE… 6 Installation The SPD can be mounted in any orientation. DANGER: 2. Turn off all power supplying this equipment before working on or inside equipment. Always follow federal and local regulations during installation. Apply appropriate personnel protective equipment (PPE) and follow electrical work practices. Secure the VAL-SQ SE… to the wall with the appropriate type of fasteners, 2, (not included) for the mounting surface, i.e., lag bolts for concrete surface, metal screws for metal surface, etc. The enclosure mounting holes are sized for 1/4 in. (6 mm) mounting hardware. NOTE: Only qualified electrical personnel may install and service this equipment. 3. Remove the four screws, 3, securing the cover. Disconnect the connector wire between the keypad in the cover and the module and set the front cover aside. s. This equipment depends upon an effective ground. Failure to obtain a quality ground connection may result in explosion or arc flash. co WARNING: m Always secure the SPD to a mounting surface. Do not rely on the conduit to hold the VAL-SQ SE…. NOTE: 6.1 Mounting and connection ne Position the VAL-SQ SE… as close as possible to the service entrance being protected so the wires are as short and straight as possible. LEDs must be visible and the keypad accessible. 2 Cover or remove components inside any enclosure before drilling to prevent shavings from causing short-circuits across terminals and races. 4. 5. Drill or punch an appropriate size hole(s) in the side of the SPD for conduit attachment. The hole must match the size of conduit used. Secure conduit with strain relief nut. Connect the VAL-SQ SE… to the power as shown on the appropriate connection diagram. Module Ground N A B C 1 on lin e co m 1. po Megger® or hi-potential tests will damage this surge protective device. Turn off all power supplying the equipment and isolate the surge protective device before testing. nt NOTE: C 3 N 1 2 3 SPD Mounting hardware Cover screws Figure 2 2460_en_B A Figure 3 3-wire single-phase connections Mounting the SPD PHOENIX CONTACT 5 VAL-SQ SE… Module Ground A B C N Enclosure Ground N A B C C m A B Figure 6 3-wire ungrounded Delta connections N A B C Enclosure Ground N A B C co m Module Ground po ne nt 3- or 4-wire, 3-phase Wye connections B s. A Figure 4 C co N Figure 5 on lin e N C C B B 3- or 4-wire High-Leg Delta connections On a High-Leg Delta installation, the high leg of the power system must be connected to phase B of the SPD. 2460_en_B A A Figure 7 3-wire corner ground Delta connections The SPD must be connected on the load side of the service entrance breakers as shown. All connections, as shown in the connections diagram, must be attached to the appropriate terminal (phase, neutral or ground). PHOENIX CONTACT 6 VAL-SQ SE… for the SPD to function correctly. Conductors and circuit breakers must be sized for the current load, typically 30 A minimum. Use an appropriate breaker, i.e., 2- or 3pole, for the electrical configuration. The wires between the SPD and protected device should be twisted 1/2 turn every 12 in. (300 mm). Do not loop or coil wire. Excess wire must be removed without applying stress to wires. 7. In addition to the LEDs, an audible alarm sounds when a fault is detected and the SPD is not providing full protection. The audible alarm can be turned on and off by pressing the alarm button, 3. When a fault occurs, press the alarm button to turn the audible alarm off. If the alarm is off when a fault occurs, the alarm is muted until the button is pressed again. Ensure the ground (green) wire from the SPD is attached to a solid earth ground. Torque connection terminals to 35 lbf-in. (3.96 N•m) and ground terminal to 50 lbf-in. (5.65 N•m). When a phase LED is not lit, verify the correct voltage is present on each phase. If power is present, the module must be replaced. co DANGER: Never apply power to the SPD with the cover removed. s. A counter displays the number of transient voltage surges detected since the counter was reset. The reset button is located on the module inside the SPD. Attach the connector wire to the display in the front cover and secure the cover to the SPD with the four fasteners previously removed. Connecting remote monitoring Fault condition and loss of power Common Normal operation m NC COM NO po Dry contacts can be used to provide alarm status to a remote monitoring system. Connections are: nt 6.2 DANGER: ne 8. co Use #22-14 AWG (0.21 - 2 mm²) wire to attach the remote terminals. Operation lin e 7 When the VAL-SQ SE… is connected in a singleor split-phase configuration, only the ØA and ØC LEDs and switches are present. m 6. If a phase is not operating correctly or a fault occurs, the corresponding LED to that phase illuminates red. The counter is battery powered to retain memory in the event of power loss. 7.1 Testing operation To test the integrity of the SPD diagnostics, each phase has a button. With power applied, press the button for the corresponding phase. If operating correctly, the phase LED will change from green to red and the alarm will sound, if enabled. When the button is released, the audible alarm will stop and the LED will change back to green. If the system fails the diagnostic test in any way, or one or more of the phase LEDs illuminates red at power up, the module must be replaced. on Phase LEDs, 1, indicate the operating status of the individual phases of the VAL-SQ SE… The LEDs illuminate green when the relevant phase is operating correctly. Always remove power to the SPD before removing the cover. 5 4 3 2 1 1 2 Figure 8 2460_en_B Phase LEDs Power LED 3 4 5 Alarm button Phase buttons Counter Keypad PHOENIX CONTACT 7