VAL-SQ SE… - Onlinecomponents.com

advertisement
VAL-SQ SE…
120, 160 and 200 kA Service Entrance protection
Data Sheet
2460_en_B
2
The VAL-SQ SE… Surge Protective Device (SPD) provides
maximum surge protection for the service entrance. These
units are available with 120, 160 and 200 kA surge current
ratings to protect electronic equipment in industrial, medical
and commercial applications.
–
The VAL-SQ SE… utilizes a hybrid suppression circuit, Sine
Wave Tracking, in a single, replaceable module. It provides
both transient protection and up to -30 dB of noise filtration.
Each surge suppression mode is individually fused.
–
The product is provided in a NEMA Type 1 metal enclosure
and includes a function monitor.
–
120, 160 or 200 kA surge current capacity per phase
(L-N and N-G) protects against high-energy lightning
strikes
LEDs provide continuous feedback on the status of
each phase
Suppression status alarm sounds if protection is not
active due to a fault
Dry contacts allow connection to a remote monitoring
system
Sine Wave Tracking filter for increased equipment
protection
LCD counter displays the number of surges safely
taken to earth-ground
Replaceable modules available in the event of damage
UL/cUL listed; meets UL 1449 2nd edition February
2007 requirements
–
–
–
–
on
lin
e
co
m
po
ne
–
Features
s.
Description
co
© PHOENIX CONTACT - 2/2008
nt
1
m
TRABTECH
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
VAL-SQ SE…
3
Ordering Data
Part No.
Pcs./Pkt
VAL-SQ SE 120-120/208Y/FM
2803917
1
Surge protective device, 160 kA, 3-phase, 4-wire + ground
for 120/208 Wye configuration
VAL-SQ SE 160-120/208Y/FM
2803920
1
Surge protective device, 200 kA, 3-phase, 4-wire + ground
for 120/208 Wye configuration
VAL-SQ SE 200-120/208Y/FM
2803933
1
Surge protective device, 120 kA, 4-wire + ground
for 120/240 High-Leg Delta configuration
VAL-SQ SE 120-120/240HLD/FM
2803969
1
Surge protective device, 160 kA, 4-wire + ground
for 120/240 High-Leg Delta configuration
VAL-SQ SE 160-120/240HLD/FM
2803975
1
Surge protective device, 200 kA, 4-wire + ground
for 120/240 High-Leg Delta configuration
VAL-SQ SE 200-120/240HLD/FM
2803988
1
Surge protective device, 120 kA, 3-wire + ground
for 120/240 split-phase configuration
VAL-SQ SE 120-120/240S/FM
2804021
1
Surge protective device, 160 kA, 3-wire + ground
for 120/240 split-phase configuration
VAL-SQ SE 160-120/240S/FM
2804034
1
Surge protective device, 200 kA, 3-wire + ground
for 120/240 split-phase configuration
VAL-SQ SE 200-120/240S/FM
2804047
1
Surge protective device, 120 kA, 3-phase, 4-wire + ground
for 277/480 Wye configuration
VAL-SQ SE 120-277/480Y/FM
2804076
1
Surge protective device, 160 kA, 3-phase, 4-wire + ground
for 277/480 Wye configuration
VAL-SQ SE 160-277/480Y/FM
2804089
1
VAL-SQ SE 200-277/480Y/FM
2804092
1
VAL-SQ SE 120-347/600Y/FM
2804115
1
VAL-SQ SE 160-347/600Y/FM
2804128
1
VAL-SQ SE 200-347/600Y/FM
2804131
1
Surge protective device, 120 kA, 3-phase, 3-wire + ground
for 480 V Delta configuration
VAL-SQ SE 120-480D/FM
2804144
1
Surge protective device, 160 kA, 3-phase, 3-wire + ground
for 480 V Delta configuration
VAL-SQ SE 160-480D/FM
2804157
1
Surge protective device, 200 kA, 3-phase, 3-wire + ground
for 480 V Delta configuration
VAL-SQ SE 200-480D/FM
2804160
1
Surge protective device, 120 kA, 3-phase, 3-wire + ground
for 600 V Delta configuration
VAL-SQ SE 120-600D/FM
2804513
1
Surge protective device, 160 kA, 3-phase, 3-wire + ground
for 600 V Delta configuration
VAL-SQ SE 160-600D/FM
2804520
1
VAL-SQ SE 200-600D/FM
2804526
1
co
s.
ne
Surge protective device, 120 kA, 3-phase, 4-wire + ground
for 347/600 Wye configuration
Surge protective device, 160 kA, 3-phase, 4-wire + ground
for 347/600 Wye configuration
on
lin
e
co
m
Surge protective device, 200 kA, 3-phase, 4-wire + ground
for 347/600 Wye configuration
po
Surge protective device, 200 kA, 3-phase, 4-wire + ground
for 277/480 Wye configuration
Surge protective device, 200 kA, 3-phase, 3-wire + ground
for 600 V Delta configuration
2460_en_B
m
Type
Surge protective device, 120 kA, 3-phase, 4-wire + ground
for 120/208 Wye configuration
nt
Products
Description
PHOENIX CONTACT
2
VAL-SQ SE…
4
Technical Data
Surge Protection Data
Maximum surge current per phase
VAL-SQ SE 120…
VAL-SQ SE 160…
VAL-SQ SE 200…
200 kA
see list below
SPD circuit type
Parallel hybrid
EMI/RFI noise rejection
-30 dB
Response time
< 1 ns
Internal coordinated fusing
yes
Part No.
Type
MCOV
2803917
VAL-SQ SE 120-120/208Y/FM
150
500
2803920
VAL-SQ SE 160-120/208Y/FM
150
500
2803933
VAL-SQ SE 200-120/208Y/FM
150
500
2803969
VAL-SQ SE 120-120/240HLD/FM
150/320
2803975
VAL-SQ SE 160-120/240HLD/FM
150/320
L-N
Surge Voltage Rating (SVR)
L-G
N-G
L-L
co
Short circuit current rating (SCCR)
Maximum continuous operating voltage (MCOV)
m
120 kA
160 kA
200 kA
500
500
500
800
500
500
800
s.
500
800
500/900
500
800
500/800
500/900
500
800
nt
500/800
VAL-SQ SE 200-120/240HLD/FM
150/320
500/800
500/900
500
800
VAL-SQ SE 120-120/240S/FM
150
500
500
500
800
VAL-SQ SE 160-120/240S/FM
VAL-SQ SE 200-120/240S/FM
2804076
VAL-SQ SE 120-277/480Y/FM
2804089
VAL-SQ SE 160-277/480Y/FM
150
500
500
500
800
150
500
500
500
800
320
po
2804034
2804047
ne
2803988
2804021
320
900
1200
1200
1800
900
1200
1200
1800
VAL-SQ SE 200-277/480Y/FM
VAL-SQ SE 120-347/600Y/FM
2804128
VAL-SQ SE 160-347/600Y/FM
420
1200
1500
1500
2500
2804131
VAL-SQ SE 200-347/600Y/FM
420
1200
1500
1500
2500
VAL-SQ SE 120-480D/FM
VAL-SQ SE 160-480D/FM
co
2804144
2804157
m
2804092
2804115
320
900
1200
1200
1800
420
1200
1500
1500
2500
640
NA
NA
NA
1800
640
NA
NA
NA
1800
VAL-SQ SE 200-480D/FM
640
NA
NA
NA
1800
VAL-SQ SE 120-600D/FM
840
NA
NA
NA
2500
lin
e
2804160
2804513
2804520
VAL-SQ SE 160-600D/FM
840
NA
NA
NA
2500
2804526
VAL-SQ SE 200-600D/FM
840
NA
NA
NA
2500
on
General Data
Dimensions (WxHxD)
Weight
Enclosure material
15 x 14 x 3.9 in.
(381 x 356x 99 mm)
19.25 lb. (8.73 kg).
Metal
Housing rating
NEMA 1
Mounting method
Surface
Connection method – phase
Screw terminal, #2-10 AWG
Connection method – function monitor
Screw terminal, #14-22 AWG
Operating frequency
50-60, 400 Hz
Operating temperature
-40 to 140°F (-40 to 60°C)
Storage temperature
-40 to 160°F (-40 to 70°C)
Operating altitude
0 to 12,000 ft. (3,658 m) above sea level
2460_en_B
PHOENIX CONTACT
3
VAL-SQ SE…
Approvals
UL/cUL
1449 2nd edition, February 2007 requirements
1283
CSA
C22.2 No. 8-M1986
IEEE
C62.41.1-2002
C62.41.2-2002
C62.45-2002
Dimensions
s.
Q
nt
VA
L-S
SE
Seri
es
ØA
BT
EC
H
ØB
ØC
ww
w.ph
oenix
act.c
om
Figure 1
2460_en_B
on
lin
e
co
m
po
cont
12.68 in.
322 mm
ne
TR
A
13.19 in.
335 mm
14.00 in.
356 mm
.
in
8
.9 m
13 m
5
35
.
in
00 m
9. 9 m
22
Surg
e Pr
ote
ctiv
eD
evic
e
co
m
3.
99 89
m in.
m
5
15.
0
381 0 in.
mm
.
5 in
1.9 m
m
50
.
1 in
1.2 m
m
31
Dimensions
PHOENIX CONTACT
4
VAL-SQ SE…
6
Installation
The SPD can be mounted in any orientation.
DANGER:
2.
Turn off all power supplying this equipment
before working on or inside equipment.
Always follow federal and local regulations during
installation. Apply appropriate personnel
protective equipment (PPE) and follow electrical
work practices.
Secure the VAL-SQ SE… to the wall with the
appropriate type of fasteners, 2, (not included) for the
mounting surface, i.e., lag bolts for concrete surface,
metal screws for metal surface, etc. The enclosure
mounting holes are sized for 1/4 in. (6 mm) mounting
hardware.
NOTE:
Only qualified electrical personnel may install and
service this equipment.
3.
Remove the four screws, 3, securing the cover.
Disconnect the connector wire between the keypad in
the cover and the module and set the front cover aside.
s.
This equipment depends upon an effective
ground. Failure to obtain a quality ground
connection may result in explosion or arc flash.
co
WARNING:
m
Always secure the SPD to a mounting surface. Do
not rely on the conduit to hold the VAL-SQ SE….
NOTE:
6.1
Mounting and connection
ne
Position the VAL-SQ SE… as close as possible to the
service entrance being protected so the wires are as
short and straight as possible. LEDs must be visible and
the keypad accessible.
2
Cover or remove components inside any
enclosure before drilling to prevent shavings from
causing short-circuits across terminals and races.
4.
5.
Drill or punch an appropriate size hole(s) in the side of
the SPD for conduit attachment. The hole must match
the size of conduit used. Secure conduit with strain
relief nut.
Connect the VAL-SQ SE… to the power as shown on
the appropriate connection diagram.
Module
Ground
N
A B C
1
on
lin
e
co
m
1.
po
Megger® or hi-potential tests will damage this
surge protective device. Turn off all power
supplying the equipment and isolate the surge
protective device before testing.
nt
NOTE:
C
3
N
1
2
3
SPD
Mounting hardware
Cover screws
Figure 2
2460_en_B
A
Figure 3
3-wire single-phase connections
Mounting the SPD
PHOENIX CONTACT
5
VAL-SQ SE…
Module
Ground
A B C
N
Enclosure
Ground
N
A B C
C
m
A
B
Figure 6
3-wire ungrounded Delta connections
N
A B
C
Enclosure
Ground
N
A B
C
co
m
Module
Ground
po
ne
nt
3- or 4-wire, 3-phase Wye connections
B
s.
A
Figure 4
C
co
N
Figure 5
on
lin
e
N
C
C
B
B
3- or 4-wire High-Leg Delta connections
On a High-Leg Delta installation, the high leg of the
power system must be connected to phase B of the
SPD.
2460_en_B
A
A
Figure 7
3-wire corner ground Delta connections
The SPD must be connected on the load side of the
service entrance breakers as shown. All connections,
as shown in the connections diagram, must be attached
to the appropriate terminal (phase, neutral or ground).
PHOENIX CONTACT
6
VAL-SQ SE…
for the SPD to function correctly. Conductors and circuit
breakers must be sized for the current load, typically
30 A minimum. Use an appropriate breaker, i.e., 2- or 3pole, for the electrical configuration.
The wires between the SPD and protected device
should be twisted 1/2 turn every 12 in. (300 mm).
Do not loop or coil wire. Excess wire must be
removed without applying stress to wires.
7.
In addition to the LEDs, an audible alarm sounds when a
fault is detected and the SPD is not providing full protection.
The audible alarm can be turned on and off by pressing the
alarm button, 3. When a fault occurs, press the alarm button
to turn the audible alarm off. If the alarm is off when a fault
occurs, the alarm is muted until the button is pressed again.
Ensure the ground (green) wire from the SPD is
attached to a solid earth ground.
Torque connection terminals to 35 lbf-in. (3.96 N•m)
and ground terminal to 50 lbf-in. (5.65 N•m).
When a phase LED is not lit, verify the correct voltage is
present on each phase. If power is present, the module must
be replaced.
co
DANGER:
Never apply power to the SPD with the cover
removed.
s.
A counter displays the number of transient voltage surges
detected since the counter was reset. The reset button is
located on the module inside the SPD.
Attach the connector wire to the display in the front
cover and secure the cover to the SPD with the four
fasteners previously removed.
Connecting remote monitoring
Fault condition and loss of power
Common
Normal operation
m
NC
COM
NO
po
Dry contacts can be used to provide alarm status to a
remote monitoring system. Connections are:
nt
6.2
DANGER:
ne
8.
co
Use #22-14 AWG (0.21 - 2 mm²) wire to attach the remote
terminals.
Operation
lin
e
7
When the VAL-SQ SE… is connected in a singleor split-phase configuration, only the ØA and ØC
LEDs and switches are present.
m
6.
If a phase is not operating correctly or a fault occurs, the
corresponding LED to that phase illuminates red.
The counter is battery powered to retain memory in the
event of power loss.
7.1
Testing operation
To test the integrity of the SPD diagnostics, each phase has
a button. With power applied, press the button for the
corresponding phase. If operating correctly, the phase LED
will change from green to red and the alarm will sound, if
enabled. When the button is released, the audible alarm will
stop and the LED will change back to green.
If the system fails the diagnostic test in any way, or one or
more of the phase LEDs illuminates red at power up, the
module must be replaced.
on
Phase LEDs, 1, indicate the operating status of the
individual phases of the VAL-SQ SE… The LEDs illuminate
green when the relevant phase is operating correctly.
Always remove power to the SPD before
removing the cover.
5
4
3
2
1
1
2
Figure 8
2460_en_B
Phase LEDs
Power LED
3
4
5
Alarm button
Phase buttons
Counter
Keypad
PHOENIX CONTACT
7
Download