Medium and Low Temperature Retrofit from R502 to R404A/R507 Application Bulletin 125 Application Bulletin Number: Release EN: Date: Revision EN: Date: 125 C18810 10/20/95 Z27301 10/2/15 Subject: Medium and Low Temperature Retrofit from R502 to R404A/R507 These are general guidelines only and in no way should they replace, contradict or otherwise take precedence over any local, state or federal law or regulation pertaining to the recovery, reclamation, and recycling of refrigerants. With the phase-out of CFC’s, existing refrigeration equipment will need to be replaced with new equipment or retrofitted with new components (including the compressor) that are approved for use with the new refrigerant and their lubricants. Using the procedures described below, existing R502 systems can be retrofitted for use with R404A or R507, allowing them to continue in service for the remainder of their useful life. Bristol Compressors does not recommend the changeover of CFC refrigerants to HFC’s in systems that are operating and have no leaks. R404A is a near-azeotropic blend of refrigerants of the following composition: R125 R143a R134a 44% 52% 4% R507 is an azeotropic blend of refrigerants of the following composition: R125 R143a 50% 50% New Medium and Low Temperature R404A/R507 Compressors are identified by the number 6 in the second digit of the model number (example: L61B562BBC). These compressors are factory oil charged with polyolester (POE) lubricant and employ an improved lubrication system which are required for the new refrigerant. Bristol’s lubricant approved for use with R404A and R507 is Polyolester Mobil EAL Arctic 22A. The use of any other lubricant may void the compressor warranty. The amount of oil charge for each model is listed in the individual compressor specification. SYSTEM DESIGN 1.0 Refrigerant Metering Devices The performance of each system is very dependent on the proper operation of each metering device. Devices such as solenoid valves, capillary tubes, fixed orifice valves, and expansion valves can perform differently if they are not correctly adjusted or properly sized. For example, the port size of a valve may not be correct for the new refrigerant density. Each valve and metering device manufacturer should be consulted, along with the system’s manufacturer, to ensure all components will work properly in the presence of the new refrigerant and lubricant. 2.0 Filter Driers The proper selection of a system’s filter drier is very important. Some filter driers may not be suitable for R404A/R507 refrigerant and polyolester lubricant. Therefore, the original equipment manufacturer should Revision Z27301 Application Bulletin 125 Page 2 be contacted for the proper filter drier selection. It is important to replace the filter drier any time the refrigerant or lubricant in a system is changed. Specifically, Bristol Compressors requires a new suction line filter drier be installed during any compressor replacement. Maintaining good system performance, reliability and cleanliness is closely linked to proper filter drier operation. 3.0 Controls The proper operation of many types of refrigeration equipment requires that the control systems function correctly. The control system could be pressure controls, temperature controls, timing devices, or sophisticated electronic controls. Changing to R404A/R507 refrigerant and polyolester lubricant in a system could adversely affect these control systems. Each equipment manufacturer should be consulted to ensure each control system will operate correctly with the R404A/R507 refrigerant/polyolester lubricant combination. Changes most likely will have to be made for continued good equipment performance. These changes could involve adjusting temperature or pressure set points to new values or replacing the control system with a newly designed unit. 4.0 Explanation of R404A/R507 vs. R502 Condenser and Evaporator Temperature/Pressure Graphs Pressure versus temperature charts and graphs are included on pages 3 through 5 as a general information guideline. More detailed saturated property tables can be obtained from the chemical manufacturer and should be used when conducting system retrofits. The graphs are intended to represent the pressures that R404A/R507 delivers versus R502 at the equivalent saturated evaporator and condenser temperatures. Revision Z27301 Application Bulletin 125 Page 3 Saturated Properties of R404A, R507 and R502 Pressure vs. Temperature Graph Pressure (Psia) Condenser Pressure vs. Temperature 375 365 355 345 335 325 315 305 295 285 275 265 255 245 235 225 215 205 195 185 175 165 155 145 135 125 R507 R502 R404A SAT VAPOR R404A SAT LIQUID 80 90 100 110 120 130 Condenser Temperature (°F) FIGURE # 1 Revision Z27301 Application Bulletin 125 Page 4 Saturated properties of R404A, R507 and R502 Pressure vs. Temperature Graph Evaporator Pressure vs. Temperature 140 R507 R502 120 R404A SAT VAPOR R404A SAT LIQUID Pressure (Psia) 100 80 60 40 20 0 -20 -10 0 10 20 30 40 50 Evaporator Temperature (°F) FIGURE # 2 Revision Z27301 Application Bulletin 125 Page 5 TABLE 1 Pressure-Temperature Chart Pressure (1) Saturated Vapor Temperature °F Pressure Saturated Vapor Temperature °F (psig) R404A(1) R507 R502 (psig) R404A(1) R507 R502 0 -50 -51 -50 46 12 10 15 2 -45 -47 -45 48 14 11 16 4 -41 -43 -40 50 15 13 18 6 -37 -39 -36 52 17 15 20 8 -33 -35 -32 54 19 16 21 10 -30 -32 -29 56 21 18 23 12 -26 -29 -25 58 22 19 24 14 -23 -26 -22 60 24 21 26 16 -20 -23 -19 62 25 22 28 18 -17 -20 -16 64 26 24 29 20 -15 -17 -13 66 27 25 30 22 -12 -15 -11 68 29 26 32 24 -10 -12 -8 70 30 28 33 26 -8 -10 -6 72 32 29 34 28 -5 -8 -3 74 33 30 36 30 -3 -5 -1 76 34 32 37 32 -1 -3 1 78 35 33 38 34 1 -1 3 80 36 34 40 36 3 1 5 85 40 37 43 38 5 3 7 90 43 40 46 40 7 5 9 95 45 43 49 42 9 6 11 100 48 46 51 44 10 8 13 105 51 48 54 Saturated Vapor Temperature (Dew Point)--The temperature (at a given pressure) at which the last drop of liquid R404A/R507 has boiled. It is also the temperature (at a given pressure) where condensation begins. Above this temperature (at the same pressure), the refrigerant is superheated vapor. NOTE: For R404A/R507 the mean evaporator temperature where a change of state occurs is approximately 1°F below the saturated vapor temperature. For example, at a saturated vapor temperature of 11°F, the mean evaporator temperature is approximately 10°F. Revision Z27301 Application Bulletin 125 Page 6 5.0 Maximum Continuous Current (MCC) Data Extensive testing has been done at maximum continuous current (MCC) test conditions with R404A/R507 and R502 refrigerant on many different displacement compressors. The MCC values of the compressors did not change from the published R502 values when R404A or R507 refrigerant was utilized. 6.0 Retrofit Procedure Summarized below are the recommended procedures for retrofitting an R502 system to R404A or R507: 6.1 Compatibility. Consult the original equipment manufacturer of the system components for their recommendation on the following: - Plastics compatibility Elastomers compatibility Lubricant (viscosity, manufacturer, additives) Solid core driers: Check with drier manufacturer for recommendations 6.2 If compressor has failed: a. Determine reason for system/compressor failure and correct b. Recover refrigerant (see step 6.4) c. Remove compressor (see step 6.5) d. Measure lubricant remaining in compressor - should be greater than 95% of original charge to minimize removal efforts in step (e) e. Assure removal of residual levels of original lubricant (must be less than 5%) - Purge system heat transfer components using high pressure inert gas (e.g., nitrogen) - Disconnect and purge line sets, or any other component that could trap lubricant (e.g., oil separator, valves, etc.) - Large system/long line sets may require up to three (3) oil changes after replacing compressor f. Go to 6.6 6.3 If compressor has not failed: a. Run at reference condition and record on Data Sheet (see Appendix 2) which will be used to confirm R404A or R507 charge requirements b. Run system at a high flow condition (highest suction pressure) for 10 - 15 minutes for optimum lubricant pick-up/return to compressor c. Go back to step 6.2, item (b) through (f) 6.4 Remove R502 charge. Remove refrigerant and collect in a recovery cylinder using a recovery device capable of pulling 10 - 20 in. Hg vacuum. If the correct R502 charge size for the system is not known, weigh the amount of refrigerant removed. The initial quantity of R404A or R507 charged in the system will be determined from this weight. 6.5 Remove compressor. The compressor must be removed from system since it will not be compatible with HFCs/POE lubricant. 6.6 Replace filter drier. Replace filter drier with one approved for use with R404A or R507 refrigerant/ polyolester lubricant. 6.7 Install compressor. Using normal service practices, install one approved for R404A or R507 refrigerant/polyolester lubricant. CAUTION: Do not leave compressor or system open to atmosphere longer than 15 minutes maximum. Polyolester lubricants are at least 100 times more hygroscopic (ability to absorb moisture) than mineral oils. It is almost impossible to remove the moisture absorbed by the lubricant even with heat and vacuum. 6.8 Leak check system. Use normal service practices. If a leak detector is used, consult the leak detector manufacturer for unit’s sensitivity to R404A and R507. 6.9 Evacuate. Use normal service practices to remove air and other non-condensables in the system, evacuate to at least 200 microns. Revision Z27301 Application Bulletin 125 Page 7 6.10 Charge system with R404A or R507. To ensure that the proper refrigerant composition is charged in the system, it is important that liquid only be removed from the charging cylinder using R404A. R507 is an azeotrope and does not require charging in the liquid phase. Once removed from the cylinder, R404A can be charged to the system as vapor as long as all of the refrigerant removed from the cylinder is transferred to the system. Due to the liquid density difference of R404A and R507 versus R502, the refrigeration system will require less weight of R404A and R507 than R502. The optimum charge will vary depending on the operating conditions, size of the evaporator and condenser, size of receiver (if present), and length of pipe or tubing runs in the system. For most systems, the optimum charge will be 90 - 95% by weight of the original R502 charge. It is recommended that the system be initially charged with about 90% by weight of the original R502 charge (refer to section 6.4). Add the initial charge to the liquid line of the system with the compressor not running. When the system and cylinder pressures are equal, start the compressor and meter the remainder of the refrigerant into the suction line of the system. Since some compressors may be damaged if liquid refrigerant enters the suction side of the compressor, it is important to charge the refrigerant slowly into the suction line to allow it to vaporize before it enters the compressor. A throttling valve can be used to ensure that the liquid is converted to vapor prior to entering the system. 6.11 Charge adjustment. Allow the system to run until conditions stabilize. Add additional R404A or R507 in small amounts until the system conditions reach the desired levels (refer to data recorded in step 6.3). Be sure to charge by evaporator/condenser temperatures, since the pressures will be higher at the temperatures equal to R502. Total charge should not exceed original R502 charge levels. 6.12 Label components and system. After completion of retrofit, label the system and the converted components to identify the type of refrigerant and lubricant, so proper service will be performed in the future. Attached is a Retrofit Checklist (Appendix 1) for R404A and R507 to assist you in the retrofit process and a System Data Sheet (Appendix 2) to record the system operating conditions for your records. Revision Z27301 Application Bulletin 125 Page 8 Appendix 1 Checklist for R404A/R507 Retrofit 1. Consult the original equipment manufacturer of the system components for their recommendation concerning compatibility and their retrofit procedures in order to sustain warranty. 2. If compressor is operable, run high flow condition (highest suction pressure) for 10 - 15 minutes to maximize oil return to compressor. 3. Remove R502 charge from system (need 10-20 in. Hg vacuum to remove charge). Use recovery cylinder --Do not vent to atmosphere-4. Replace filter drier with new filter drier approved for use with R404A/R507. - Loose fill driers: Use XH7 or XH9 desiccant or equivalent. - Solid core driers: Check with drier manufacturer for recommendation. 5. Replace compressor with one approved for usage with R404A/R507 - Measure and record oil remaining in old compressor - Residual lubricant should be less than 5% by weight of the total lubricant used in system 6. Leak check system using normal service practices. 7. Evacuate with vacuum pump (200 microns minimum). 8. Charge system with R404A/R507. - Initially charge 90% by weight of original equipment manufacturer specified R502 charge. - Amount of refrigerant charged: _______ 9. Start up equipment and adjust charge until desired operating conditions are achieved. - If low on charge, add in increments of 2 - 3% of original R502 charge. - Amount of refrigerant charged: _______ 10. Total Refrigerant Charged (add 8 and 9) _______ - Should not exceed original R502 charge level 11. Label components and system for type of refrigerant (R404A or R507) and lubricant (polyolester oil). 12. Conversion is complete!! Revision Z27301 Application Bulletin 125 Page 9 Appendix 2 SYSTEM DATA SHEET Type of System/Location: Equipment Mfg.: Compressor Mfg.: Model No.: Model No.: Serial No.: Serial No.: Original Lubricant: Type/Mfg.: Charge Size: New Lubricant: Type/Mfg.: 1st Charge Size: 2nd Charge Size: Additional Charge Size: Drier Mfg.: Drier type (check one): Model No.: Loose Fill: Solid Core: Condenser Cooling Medium (Air/Water): Expansion Device (check one): Capillary Tube: Expansion Valve: If Expansion Valve: Manufacturer: Model No.: Control/Set Point: Location of Sensor: Other System Controls (e.g.: head press control); Describe: (circle units used where applicable) R502 Data R404A or R507 Data Date/Time Refrigerant Charge Size Lb. Ambient Temperature (°F/°C) Relative Humidity Compressor: Suction Temperature (°F/°C) Suction Pressure psig DischargeTemperature (°F/°C) Discharge Pressure psig Indoor Temperature (°F/°C) Evaporator: Refrigerant Inlet Temperature (°F/°C) Refrigerant Outlet Temperature (°F/°C) Coil Air/H 2O In Temperature (°F/°C) Coil Air/H 2O Out Temperature (°F/°C) Refrigerant Temperature @ Superht. Ctl. Pt. (°F/°C) Condenser: Refrigerant Inlet Temperature (°F/°C) Refrigerant Outlet Temperature (°F/°C) Coil Air/H 2O In Temperature (°F/°C) Coil Air/H 2O Out Temperature (°F/°C) Exp. Device Inlet Temperature (°F/°C) Motor Amps Run/Cycle Time Comments: Revision Z27301 Application Bulletin 125 Page 10 Release EN Number C18810 Release Date 10/20/95 Revisions D00905 Revision Z27301 2/9/96 Z27301 10/2/15 Application Bulletin 125 Page 11