stelmec

advertisement
stelmec®
P RODU
S
PO
ER
boundaries
CT
W
beyond
Pole Mounted Sectionalizer is dedicated to serve
the purpose of disconnecting the faulty section
SSSG12
automatically in conjunction with an upstream
Autorecloser circuit breaker in the substation and
restoring power to the healthy lines/branches with
minimum down time.
OUTDOOR SF6 GAS INSULATED
SECTIONALIZER
Salient Features
Compact in size, light weight design, hence easy
to install and transport
SF6 gas filled hermetically sealed stainless steel tank
Control Unit with logic based programming
Suitable for mounting on a single pole or on
double pole structure
Latest technology of arc quenching & short
arcing time
Local & Remote control options
Manual & automated options
Least maintenance
Application
Sectionalizer is installed in different branch/line in
a power distribution system especially in ring main
type distribution system. It has been observed that
about 70% of faults in power distribution system
are Transient Faults (i.e. short-time faults) which
get cleared within mille-seconds. The upstream
Autorecloser, through a number reclosing operations with a definite interval of times determines
the type of the fault (transient or permanent) and
in case of permanent faults, the faulty section is
isolated by Sectionalizer and power is restored to
the healthy branches of the distribution system
with a minimum time lag.
OUTDOOR SF6 GAS INSULATED SECTIONALIZER
SSSG12
SIPV 12 - 12KV PANELS
Technical Specifications
®
Technical Specifications
Description
SSSG 12-16
Description
SSSG 12-16
Rated voltage
12 kV
Mounting on
Single/Double pole
Rated normal current
630 A
Rated frequency
50Hz
Rated short-time withstand
16 kA, 3s
current & duration
Rated short-circuit making
40 kA
structure
Fault break capacity
630 A
Operating mechanism
Solenoid
Degree of protection of gas tank
IP67
Material of bushing
Cycloaliphatic epoxy
current (peak)
resin
Rated power frequency
28 kV
withstand voltage (one minute)
Rated lightning impulse
75 kVp
voltage (peak)
Number of phase
3
Method of earthing
Solid
Interrupting medium
SF6 Gas
Insulating medium
SF6 Gas
Type
Outdoor
Mechanical endurance class
M2
SF6 rated pressure
0.14 MPa
Leakage rate per year
<0.02%
Weight (without structure)
80 kg (Approx.)
Dimensions (W x D x H)
1260mm x 760mm x
525mm
Reference Standard
IEC 62271-103
Control Unit
Power supply to operate the Sectionalizer
Multifunction meter to monitor – line current, line voltage, PF, fault & its type,
duration of fault and other related data w.r.t. real time and transmit the same
through its RS485 port MODBUS to the PLC on the control unit.
PLC with its sufficient memory stores these data and at the same time sends
these data to the communication protocol
Communication
Every Control Unit is having a communication Modem (leased line / GPRS / 3G/GSM/Fibre Optic); hence they are connected to
each other and also with auto-recloser and with the integrated SCADA (installed at substation) based on standard
communication Protocol IEC-60870-5-104. Moreover, there will be dedicated RS-232C serial port capable of communicating
(over IEC-60870-5-101).
Backup
Every control unit is equipped with rechargeable dry battery of adequate power delivering capacity & along with battery
charger.
There is a continuous effort at Stelmec to keep abreast of latest technology inline with customers’ requirement.
All these activities are followed as per ISO 9001 : 2008.
stelmec
beyond
boundaries
®
SBU – II (Medium Voltage Switchgear Division)
CORPORATE
Plot no. 90/91/92, Virar-Vajreshwari Road,
Usgaon, Vasai (E),
Dist. Palghar – 401 303.
Tel: +91 250 – 6456432 / 33 / 34
Stelmec Limited 'Sea Queen', 43-A, H.K. Bhabha Road,
Bandstand, Bandra (W), Mumbai - 400 050.
E-mail: corporate@stelmec.com
Tel: +91 22 2643 6127 / 28 / 29 | Fax: +91 22 2643 6139
website: www.stelmec.com
Download