HCP FireFinder™ XLS Control Point Module • Intelligent Device for use with FireFinder XLS Control Panel • Used as a Telephone Zone, Speaker Zone or Notification Appliance Circuit • Provides either a 25V (35 Watts) or 70.7V (25 Watts) Single Channel Speaker Zone • Provides 24 VDC Notification Appliance Circuits • Used with Siemens Fire Safety Notification Appliances • Firefighters Telephone Circuits • Polarity Insensitive with SureWire™ Technology • Internally Power Limited Using Self Restoring Solid State Thermal Devices • Supervised DC Input • Mounts on Standard Electrical Box (Double Gang or 4" Square) • No Mechanical Address Programming Required • Listed and ULC Listed; City of Chicago, CSFM, NYMEA (Pending) Description The HCP provides an intelligent control point for the FireFinder XLS Control Panel. The HCP can be programmed as an independent, remotely located telephone zone, speaker zone or notification appliance circuit. The HCP is designed to be used with the Siemens Fire Safety notification appliance product line. The HCP can be programmed for any of the usages mentioned above using the ZEUS programming software and controlled by the systems’ output logic. It can be addressed and tested using the DPU device, eliminating the need for any mechanical addressing. The output of the HCP is inherently power limited using solid state, self-restoring thermal devices. This 24VDC input to the HCP is supervised by the HCP itself so that power wiring may include branch circuits. When programmed as a speaker zone, the high power audio risers are supervised using the ZAC40 or ZAM-80/180 zone amplifiers. When programmed as a telephone zone, the telephone riser is supervised by the TZC-8 module. The HCP mounts in a standard double gang or 4" square electrical box. This equipment is approved for operation over the temperature range of 0°C to 50°C and relative humidity range of 93% RH +/- 2% RH at 40°C +/-2°C. The HCP communicates through the DLC analog loop and can be wired either Class A (Style Z) or Class B (Style Y). The 24 VDC power input comes from either the control panel or from any UL listed power limited, auxiliary power supply. CATALOG NUMBER 6311 Mounting Data 4 INCH SQUARE ELECTRICAL BOX, 2 ½ INCHES DEEP 3 ½ INCH DEEP, DOUBLE GANG SWITCHBOX 1 ½ INCH DEEP EXTENSION OR 1¼ INCH DEEP PLASTER RING EXTENSION HCP HCP DOUBLE GANG BLANK SWITCHPLATE (USER SUPPLIED) 1. Use a standard 31/2" deep, double gang electrical switchbox or a 4" square electrical box that is 21/2" deep with either a 1½" deep extension or a 11/4" deep plaster ring extension. 2. Connect the field wiring. Insert the HCP into the box and fasten the module plate to the box. 4 INCH SQUARE BLANK PLATE (USER SUPPLIED) OR DOUBLE GANG BLANK SWITCHPLATE (USER SUPPLIED) Note: When using the double gang switchbox or the plaster ring extension, use the same four screws to fasten both the module and the blank plate (user supplied). 3. Cover the module front plate with a 4" blank plate (user supplied) and fasten with two plate screws. Please see installation instructions or check the web site (password protected section), www.cerbpyro.com, for the current listing of Compatible Notification Appliances. NOTICE: The use of other than Siemens Fire Safety detectors and bases with Siemens Fire Safety equipment will be considered a misapplication of Siemens Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Siemens Building Technologies Fire Safety Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (973) 593-6670 Website: www.cerbpyro.com 12/01 5M SFS-IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 December 2001 New Issue