Current Transducer HASS 50..600-SI = 50 .. 600 A

advertisement
Current Transducer HASS 50..600-S
IPN = 50 .. 600 A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
All Data are given with a R L = 10 kΩ
Electrical data
Primary nominal
current rms
IPN (A)
50
100
200
300
400
500
600
VOUT
G
VREF
RL
ROUT
CL
VC
IC
Primary current
measuring range
IPM (A)
±
±
±
±
±
±
±
150
300
600
900
900
900
900
Features
Type
• Hall effect measuring principle
• Galvanic isolation between primary
HASS 50-S
HASS 100-S
HASS 200-S
HASS 300-S
HASS 400-S
HASS 500-S
HASS 600-S
Output voltage (Analog) @ IP
IP = 0
Output voltage (without offset) @ IPN
Reference voltage 1) - Output voltage
VREF Output impedance
VREF Load impedance
Load resistance
Output internal resistance
Capacitive loading
Supply voltage (± 5 %)
Current consumption @ VC = 5 V
and secondary circuit
VREF ± (0.625·IP/IPN) V
VREF ± 0.025
V
± 0.625 ± 1 %
V
2.5 ± 0.025
V
typ. 200
Ω
≥ 200
kΩ
≥2
kΩ
< 10
Ω
<1
µF
5
V
22
mA
• Isolation test voltage 3300V
• Low power consumption
• Single power supply +5V
• Fixed offset & gain
• Isolated plastic case recognized
according to UL 94-V0
Advantages
• Easy installation
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
• Internal and external reference
Accuracy - Dynamic performance data
X
ε
L
TCVOUT
TCVREF
TCVOUT /VREF
TCG
VOM
t ra
tr
di/dt
V no
BW
Accuracy 2) @ IPN , TA = 25°C
Linearity error 0.. IPN
.. IP
Temperature coefficient of VOUT @ IP = 0
Temperature coefficient of VREF
Temperature coefficient of VOUT / VREF @ IP = 0
Temperature coefficient of G
Magnetic offset voltage @ IP = 0,
after an overload of 3 x IPN DC
Reaction time @ 10 % of IPN
Response time to 90 % of IPN step
di/dt accurately followed
Output voltage noise (DC ..10 kHz)
(DC .. 1 MHz)
Frequency bandwidth (- 3 dB) 3)
≤±
≤±
≤±
≤±
≤±
≤±
1
0.5
1
0.3
0.01
0.2
% of IPN
% of IPN
% of IPN
mV/K
%/K
mV/K
≤ ± 0.05% of reading/K
< ± 0.4
<3
<5
> 100
< 20
< 40
DC .. 50
% of IPN
µs
µs
A/µs
mVpp
mVpp
kHz
Applications
• AC variable speed drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application domain
• Industrial
Notes :
1)
It is possible to overdrive VREF with an external reference voltage between
2 - 2.8 V providing its ability to sink or source approximately 2.5 mA.
2)
Excluding offset and hysteresis.
3)
Small signal only to avoid excessive heatings of the magnetic core.
Page 1/3
081007/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer HASS 50..600-S
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standard
- 40 .. + 85
°C
- 40 .. + 85
°C
55
g
EN 50178: 1997
Isolation characteristics
Vb
Vb
Vd
Ve
Vw
dCp
dCl
CTI
Rated isolation voltage rms
with IEC 61010-1 standards and following conditions
- Reinforced isolation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Rated isolation voltage rms
with EN 50178 standards and following conditions
- Reinforced isolation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Rms voltage for AC isolation test, 50 Hz, 1 min
Partial discharge extinction voltage rms @ 10 pC
Impulse withstand voltage 1.2/50 µs
Creepage distance
Clearance distance
Comparative tracking index (Group I )
150
V
300
V
3.3
>1
6
> 5.5
> 5.5
> 600
kV
kV
kV
mm
mm
V
If isolated cable is used for the primary circuit, the
voltage category could be improved with the following table :
Cable isolation (primary)
Category
HAR 03
300V CAT III
HAR 05
400V CAT III
HAR 07
500V CAT III
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
081007/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HASS 50..600-S (in mm. 1 mm = 0.0394 inch)
22.8
16
d4.5
10.4
2.5
20
R5.2
Ip
4.8
Molex
3
1
4
9.8
R0.5
10.4
30 +/-0.5
20.4
5
5
d2.5
5045-04A
20
40 +/-0.5
Terminal Pin
1...Vref(IN/OUT)
2...OUTPUT
3...0V
4...+5V
Required Connection Circuit
HASS
1
Vref(IN/OUT)
2 Output
3
4
Vref(IN/OUT)
Output
RL=10Kohm
0V
0V
+5V
+5V
Mechanical characteristics
•
•
•
•
•
General tolerance
Aperture for primary conductor
Transducer fastening
Recommended fastening torque
Connection of secondary
± 0.5 mm
20.4 x 10.4 ± 0.5 mm
M4
< 1.5 Nm
Molex 5045-04A
Remarks
• Arrow indicates positive current flow direction.
• Temperature of the primary conductor should not exceed
Operation Principle
+Vc
100°C
Vout
Vref.(IN/OUT)
Ip
0V
Page 3/3
081007/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.