Current Transducer HAS 50 .. 600-S For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit). IPN = 50 .. 600 A VOUT = ± 4 V Electrical data Primary nominal r.m.s. current IPN (A) Primary current measuring range 5) IP (A) ± ± ± ± ± ± ± 50 100 200 300 400 500 600 150 300 600 900 900 900 900 Type HAS HAS HAS HAS HAS HAS HAS Features 50-S 100-S 200-S 300-S 400-S 500-S 600-S • Hall effect measuring principle • Galvanic isolation between primary and secondary circuit Supply voltage (± 5 %) 5) Current consumption Overload capacity R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn R.m.s. rated voltage, safe separation Isolation resistance @ 500 VDC Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance VC IC IOC Vd Vb RIS VOUT ROUT RL ± 15 ± 15 30,000 3 5001) > 1000 ± 4V ± 40 100 >1 V mA At kV V MΩ mV Ω kΩ Accuracy - Dynamic performance data X ε Accuracy @ IPN, TA = 25°C (without offset) Linearity error 2) (0 .. ± IPN) Electrical offset voltage, TA = 25°C Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of VOE HAS 50-S HAS 100..600-S Thermal drift of the gain (% of reading) Response time @ 90% of IP di/dt accurately followed Frequency bandwidth (- 3 dB) 3) L VOE VOH VOT TCε G tr di/dt f Notes : 2) 3) 4) 5) Advantages • Easy mounting • Small size and space saving • Only one design for wide current ratings range • High immunity to external < ± 20 mV <±2 mV/K <±1 mV/K < ± 0.1 %/K <3 µs > 50 A/µs DC .. 50 kHz Applications interference. • AC variable speed drives • Static converters for DC motor drives • Battery supplied applications • Uninterruptible Power Supplies (UPS) • Switched Mode Power Supplies (SMPS) Ambient operating temperature Ambient storage temperature Mass Standards 4) 1) polycarbonate PBT recognized according to UL 94-V0 <±1 % < ± 1 % of IPN < ± 20 mV General data TA TS m • Isolation voltage 3000 V~ • Low power consumption • Extended measuring range (3 x IPN) • Insulated plastic case made of - 10 .. + 80 °C - 25 .. + 80 °C approx. 60 g EN 50178: 1997 Pollution class 2, overvoltage category III. Linearity data exclude the electrical offset. Please refer to derating curves in the technical file to avoid excessive core heating at high frequency. Please consult characterisation report for more technical details and application advice. Operating at ±12V ≤ Vc < ±15V will reduce the measuring range. • Power supplies for welding applications. Application Domain • Industrial LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. LEM Industrial 051007/5 Page 1/2 www.lem.com HAS 50 to 600-S Dimensions (in mm) Dimensions HAS 50..600-S (in mm. 1 mm = 0.0394 inch) 22.8 16 PINS ARRANGEMENT 10.4 4.5 1 ..... +15V 2 ..... -15V 3 ..... OUTPUT 4 ..... 0V 2.5 20.0 r 5.2 432 1 = = 3 MOLEX 5045-04A 4.8 9.8 20.4 x 10.4 30 I 2.5 20 40 PINS A RRANGEMENT 1 = +15V 2 = 15V 3 = OUTPUT 4 = 0V (Max. 8.0) 30 Safety This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions. Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. 051007/5 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. LEM Industrial Page 2/2 www.lem.com