Scalable N+1 Inverter

advertisement
www.mgeups.com
MGE UPS SYSTEMS, INC.
S4
3.5kVA-21kVA
Scalable N+1 Inverter
Advanced Features
◗ Constructed to NEBS /Telecom
industry standards
◗ True Modular Scalability: 3.5 kVA-21 kVA
(3.5 kVA modules) – add modules as
your system grows
◗ Parallel for N+1 redundancy or capacity
◗ Safe hot swap technology
◗ Unparalleled reliability: no single points
of failure
◗ Full front accessibility
◗ Ultra low profile: 21 kVA in 24 U
with static switch
The Next Generation in AC Telecom Power
MGE’s Power-Invert™ S4 N+1 scalable DC to AC inverter is the latest addition to the
◗ Clean DC input < 30 dBrnc
Power-Invert™ line recognized as the industry standard for critical AC power by many
◗ Precision output voltage regulation:
+ 1% THD
of the world’s leading telecom companies. The S4’s scalable 3.5 kVA inverter power
modules can be stacked in a N+1 redundant configuration for optimum reliability up
to 21 kVA. This modular scalability makes the Power-Invert™ S4 ideal for overlay
◗ Integrated static bypass for
added reliability
applications where future power growth is anticipated. All modules are packaged into
a “hot swap” receiver cabinet allowing rapid and safe exchange of any component
without interruption to the critical load.
◗ Universal voltage and frequencies
(user selectable)
S4 “Fortress” Topology ~ High Reliability Features
Redundant Microcontroller Modules
If the primary micro controller module is
ever compromised, the secondary module
continues to provide uninterrupted performance.
Digital Calibration & Self Diagnostics
Any drift in settings is immediately self
corrected, eliminating maintenance and
calibration requirements.
Redundant 3.5 kVA
“hot swappable” Inverter Modules
Permits power modules to go off line and be
quickly replaced while keeping the load
on inverter power.
Integrated Electronic Static
T H E
Transfer Switch
Provides six sigma reliability by adding
a third layer of protection by rapidly and
seamlessly transferring to bypass power
if required.
Rack mount receiver cabinet with
rapid change connector system
Swap components on-line safely and
rapidly with no wiring connections and
without risking system perfomance.
U N I N T E R R U P T I B L E
P O W E R
◗ LCD status display module
P R O V I D E R
◗ Customers supported by
MGE’s Trained and Certified
Field Engineer force
◗ International agency certifications
(UL, CE, TUV)
Power-Invert™ S4 Inverter Plant Accessories
Options
to meet
specific
requirements
Why is the
S4 theyour
most
reliable
critical power protection solution?
System Operation:
Tri-Layer Redundancy:
The Inverter plant receives 48 VDC from a
DC power plant/battery bank and converts
the output to precision regulated AC power
(user selectable voltage and frequency). In
the event that the DC is not available or out
of tolerance due to a discharged battery, or
the inverters are not able to maintain the
critical load, the system will automatically
transfer via the static transfer switch and
disconnect from the DC source. The static
transfer switch (standard) will make a seamless, uninterrupted transfer from the critical
load to an alternate AC power source where
the inverter power was synchronized to
utility power or another protected AC
source. The MTBF of the S4 N+1 on-line
mode with a backup source present is
greater than 99.9999%.
Three independent layers of redundancy
contribute to the S4’s reliability
starting with the N+1 inverter assemblies,
dual independent microcontrollers
and integrated static transfer switch for a
final layer of protection.
CONTROLLER(S)
INVERTER
INVERTER
DC INPUT
INVERTER
AC INPUT
STATIC SWITCH
Telecom Grade Filtering:
Since the S4 is connected to large telecom
battery plants and shared by other critical
equipment, it is equipped with a high grade
noise filter system, limiting ripple current
on the battery to well under required levels,
as well as ensuring that radiated and
conducted EMI are kept to safe levels.
AC OUTPUT
DC POWER
N+1 REDUNDANT INVERTER ASSEMBLIES
REDUNDANT AC BYPASS SOURCE
Tri Layer Redundancy
DUAL REDUNDANT MICROCONTROLLERS
N+1 REDUNDANT INVERTER ASSEMBLIES
REDUNDANT AC BYPASS SOURCE (Static Switch)
Regulatory Compliance ~ built to meet industry standards
The S4 inverter is designed to meet the
stringent regulatory qualifications demanded by telecommunications facilities. As
well as meeting all major safety standards,
the S4 inverter is one of the only inverters
designed to meet Network Equipment
Building System (NEBS) standards~
the industry benchmark
for product quality and reliability.
◗
◗
◗
◗
NEBS
CE
UL
TUV
S4 Power Center: The six 9s solution for ultra critical IT installations
The S4 Power Center provides up to a 21 kVA N+1 power system
S4 Power Center Components
complete with maintenance bypass and distribution in one 70"
The S4 Power Center can also integrate a DC power source (rectifier
high rack enclosure. The scalability, redundancy and rack mounted
and battery bank) transforming the system into a complete double
configuration of the S4 makes it an ideal solution for mid range
conversion UPS system.
IT applications that require a very high level of reliability.
Receiver Cabinets
Part Number*
64074-94
MGE 7 kVA receiver assembly w/STS (no inverters)
64144-94
MGE 14 kVA receiver assembly w/STS (no inverters)
64214-94
MGE 21 kVA receiver assembly w/STS (no inverters)
64144-94J
MGE 14 kVA receiver assembly w/STS (no inverters) with Junction Box
64214-94J
MGE 21 kVA receiver assembly w/STS (no inverters) with Junction Box
* NOTE: For Line to Line (208/240V) version, add an “H” on the end of the part number.
Power-Invert™ S4 Inverter Plant Accessories
Options to meet your specific requirements
The S4 is available with the following optional accessories, all of which can be factory
installed on an open frame relay rack, providing a ready to install inverter system.
Maintenance Bypass:
AC Distribution Panel
Safely and seamlessly transfers the output to an alternate AC source (utility power
or protected AC power from another inverter or UPS system) allowing the inverter
to be shutdown or removed without interrupting power to the critical loads. The
Maintenance Bypass assembly is factory wired to the inverter module when
ordered as a system.
AC Distribution Panel:
The AC distribution panel accommodates 20 single pole breakers and is available
in 120 and 240 VAC versions. 10 x two pole breakers can be used if distribution
alarm monitoring is required.
Maintenance Bypass Cabinet
Web Based Monitoring:
The Falcon monitoring system (1.75” high rack mounted) provides inverter, maintenance bypass and AC distribution status and alarms over a closed network or via the
Internet serving up web pages that can be viewed with a standard browser or via
SNMP or dial up access. Accessories include environmental monitoring modules and
auxiliary inputs to monitor other devices such as leak detection systems, room
security or any other dry contact status points.
S4 Fortress Inverters
Open Frame Relay Rack:
All components can be mounted on an industry standard open frame relay rack with
the entire inverter plant certified for zone 4 seismic installations.
Conduit Junction Boxes: (optional when maintenance bypass is not used)
Larger inverter modules such as the 14 kVA through 21 kVA require substantial
cable gauges. The conduit junction box is factory mounted to the back of the inverter
module, easing conduit landing requirements and simplifying installation of rear
mounted cable entry systems.
Rack
Inverter Systems
Inverter systems include inverter(s), receiver cabinet, static switch and single controller module (redundant controller module optional).
N+1 redundant power rating indicates that a single inverter module can go off-line with existing inverters maintaining the critical load.
(Rack mount bracket kit is optional.)
Part
Number *
With
Junction Box
System Output
Power (kVA)
3.5
Qty. Inverters
Supplied
(x 3.5 kVA)
1
Total #
of Bays
(x 3.5 kVA)
2
Receiver Cabinet
Capacity
(kVA)
7.0
64074-9401
N/A
64074-9402
N/A
7.0
2
2
7.0
64144-9402
64144-9403
64144-94J2
7.0
2
4
14.0
64144-94J3
10.5
3
4
14.0
64214-9403
64214-94J3
10.5
3
6
21.0
64144-9404
64144-94J4
14.0
4
4
14.0
64214-9404
64214-94J4
14.0
4
6
21.0
64214-9405
64214-94J5
17.5
5
6
21.0
64214-9406
64214-94J6
21.0
6
6
21.0
Junction Box - Suggested on 14 kVA (6414J) & 21 kVA (6421J) Receivers when Maintenance Bypass Not Used - Adder
* NOTE: For Line to Line (208/240V) version, add an “H” on the end of the part number.
Power-Invert™ S4 Technical Specifications
The Power-Invert™ S4
Input Voltage
-48VDC (40-57 VDC)
Output/Bypass Voltage
line to neutral
110, 115, 120, 220, 230, 240 (user selectable)
Output/Bypass Voltage
line to line
208, 220, 230, 240 (user selectable)
Output Frequency User-selectable
50Hz or 60Hz (+/-0.02%)
Output Waveform
High resolution PWM sine wave
Inverter Technology
IGBT PWM
Load/Line Voltage Regulation
< +/- 1%
Static Switch Transfer Time
< than 3 ms
Efficiency
88% typical (on-line mode) to 97% typical (off-line eco mode)
Transient Response
5% deviation with 1millisecond recovery from zero to full load
Overload Capability
106% of continuous rated VA/watts at 20°C.
Short Circuit Current (SCC)
300% for more than 4 cycles
Audible Noise
Less than 60 dBA
EMI Emission (DC Ripple)
<30 dBrnc.
Total Harmonic Distortion < 1% for linear loads, <3% for crest factor loads up to 3:1.
Monitoring
LCD with true RMS metering and LED status display,
dry contacts
Calibration
Digitally controlled / automatic
Operating Temperature
Operating Humidity
Operating Altitude
Agency Approvals
Design Mandate
Before designing the S4,
MGE’s team of engineers
was given the following
non-compromising instructions:
Reliability: Eliminate single points
of failure and allow component
changes without interrupting
the load.
Scalability: Allow users to add
extra power for increased capacity
as well as redundancy.
Maintainability: Ensure that
all components can be exchanged
safely and rapidly by any technician.
Installability: Minimize the mechanical profile of the system while eliminating any
requirement for rear access.
Operability: Provide clean, comprehensive operating
status information with robust communication interfaces.
0 to +55° C (-40° C to +75° C shipping)
0 to 90% relative, without condensation.
<10,000 without de-rating
UL/CSA 60950 (listed) and European Standard EN60950,
CE, TUV, FCC class A certified
19, 23, 25" rack or floor mounted
RAL 902 off white
I year
Installation
Finish
Warranty
Power-Invert™ S4 Selection Guide
[1] Select line to neutral or line to line voltage model
[2] Select a receiver cabinet (7, 14 or 21 kVA); determines
minimum and maximum kVA of the system.
[3] Select the quantity of 3.5 kVA inverter modules. Ensure
that the total inverter output is at least 3.5 kVA greater
than the load for N+1 redundancy
Maintenance Bypass (optional)
[4] For 14 kVA or 21 kVA receiver cabinets without a
maintenance bypass, select a rear mounted conduit
option box for sufficient cable landing space.
AC
Bypass input
DC input
[5] Inverter systems ordered with optional Maintenance
Bypass Module and/or AC Distribution Panel and
Telecom Rack are pre-wired to inverter.
AC Distribution
Panel (optional)
Static Transfer
Switch
Inverter Modules
(1-6 modules)
3.5 kVA Inverter
[6] Rack mounting bracket options are available
for 19", 23", 25" and 26" racks.
EMI Filter
Static Transfer Switch Assembly
Power-Invert™ S4 Options
3.5 kVA Inverter
◗
◗
◗
◗
◗
◗
◗
Dry Contact Alarms
3.5 kVA Inverter
RS232 Comm. Port *
requires external hardware *
3.5 kVA Inverter
Power-Invert™ S4
3.5 kVA Inverter
System Schematic
3.5 kVA Inverter
System Height
17.0” W x 18.5” D
Receiver Cabinet
Capacity kVA
21.0”
7.0
(min/max inverter qty 1-2)
31.5”
14.0
(min/max inverter qty 2-4)
42.0”
21.0
kVA
Qty.
Inverters
Power
kVA / kW
3.5
7.0
1
2
3.5/3.0
7.0/6.0
88
176
26
52
10.5
3
10.5/9.0
265
14.0
4
14.0/12.0
17.5
5
6
Inverter Capacity
23" Open Frame Relay Rack
Web Enabled Status Monitor
AC Distribution Panel w/ Alarm Indication - 20 pole/24 pole
Maintenance Bypass (rack mounted)
Rack Mount Kits (19", 23", 25", 26" versions)
On Site Start-Up and Commissioning
On Site Service Plans & Extended Warranty
Max
BTU
(A) suggested
135
182
1807
3614
200
200
80
80
40
40
78
252
5421
400
150
80
353
104
299
7227
400
150
80
17.5/15.0
441
130
371
9034
600
225
125
21.0/18.0
529
157
418
10,841
600
225
125
DC Input Output (A) Approx. System
(A) Max. @120VAC* Weight(lbs) *
DC Breaker AC Input Breaker AC Input Breaker
(A) @ 120 VAC
(A) @ 240VAC
(min/max inverter qty 3-6)
21.0
* Inverters and receiver cabinet shipped separately. Each inverter is approx. 47 lbs.
MGE UPS SYSTEMS, INC.
USA (headquarters)
1660 Scenic Avenue
Costa Mesa, CA 92626
tel
(800) 523-0142
(714) 557-1636
fax
(714) 557-9788
T H E
CANADA
#9, 2798 Thamesgate Dr.
Mississauga, ON L4T 4E8
tel (905) 672-0990
(877) 672-0990
fax (905) 672-7667
ARGENTINA
Avenida Uzal 3556
(1636) Olivos, Pcia. de
Buenos Aires, Rep. Argentina
tel (54) 11-4766-8777
fax (54) 11-4766-6008
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.
U N I N T E R R U P T I B L E
BRAZIL • Sao Paulo Office:
Avenida Guido Caloi 1985
(Galpao 23), Guarapiranga
Sao Paulo –SP, 05802-140Brazil
tel (55) 11-5515-9255
fax (55) 11-5515-9250
P O W E R
MEXICO
Ave. Congreso de la Union
#524 Colonia Santa Anita
Mexico D.F 08300
tel 525 538 9687
fax 525 530 7625
P R O V I D E R
www.mgeups.com
info@mgeups.com
Pwrinvrt S4
Revision 100
Effective: October 2005
Download