Wiring Instructions Infrared Remote Control by Draper Wiring Diagram for Infrared Remote Control with LVC-IV Low Voltage Trigger 3-28 VDC White-Neutral (Common) to screen & 110V-120V AC Red-to screen (directional) Brown-to screen (directional) Yellow-to 110V-120V AC Black-to 110V-120V AC Green-Ground IR Eye FUSE - 3.15 AMP 250 VAC 5x20mm RS232/485 Inputs/Outputs Dashed wiring by electrician LVC-IV IR Transmitter Transmitter range: 26 feet Wire to connect power to LVC-IV should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be sufficient to carry the motor load. Red and Black wires are the “open” and “close” leads from the motor. The LVC-IV comes enclosed in a metal box with appropriate spacing between the wires and any exposed parts of the box. IR Eye is connected to LVC-IV using low voltage modular data or telephone cord (RJ11), which is isolated from the AC power line. InfraRed (IR) Remote Control 1 Plug Optional IR Eye into mini plug input provided on LVC-IV. 2 IR Remote Control transmitter does not need to be "learned" by the LVC-IV. Simply point and operate. 3 Maximum IR Eye cable length is 42". Battery Replacement for IR Remote Control 1 Slide off cover from the back of IR Remote Control. 2 Remove both CR2032 3-volt batteries and replace. ove Rem er Cov 2 203 CR 3V 2 203 CR 3V + Copyright ©2015 Draper Inc. Form IRRemoteControl_Wiring15 Printed in U.S.A. + If you encounter any difficulties installing/wiring your IR Remote Control, call your dealer or Draper, Inc., Spiceland, Ind., (765) 987-7999; or fax (765) 987-7142. Wiring Instructions 230V Infrared Remote Control by Draper Wiring Diagram for Infrared Remote Control with LVC-IV Low Voltage Trigger 3-28 VDC White-Neutral (Common) to screen 230V AC Red-to screen (directional) Brown-to screen (directional) Yellow-to 230V AC Black-to 230V AC Green-Ground IR Eye FUSE - 3.15 AMP 250 VAC 5x20mm RS232/485 Inputs/Outputs Dashed wiring by electrician LVC-IV IR Transmitter Transmitter range: 7.9 meter Wire to connect power to LVC-IV should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be sufficient to carry the motor load. Red and Black wires are the “open” and “close” leads from the motor. The LVC-IV comes enclosed in a metal box with appropriate spacing between the wires and any exposed parts of the box. IR Eye is connected to LVC-IV using low voltage modular data or telephone cord (RJ11), which is isolated from the AC power line. InfraRed (IR) Remote Control 1 Plug Optional IR Eye into mini plug input provided on LVC-IV. 2 IR Remote Control transmitter does not need to be "learned" by the LVC-IV. Simply point and operate. 3 Maximum IR Eye cable length is 106cm. Battery Replacement for IR Remote Control 1 Slide off cover from the back of IR Remote Control. 2 Remove both CR2032 3-volt batteries and replace. ove Rem er Cov 2 203 CR 3V 2 203 CR 3V + Copyright ©2015 Draper Inc. Form IRRemoteControl-230V_Wiring15 Printed in U.S.A. + If you encounter any difficulties installing/wiring your IR Remote Control, call your dealer or Draper, Inc., Spiceland, Ind., (765) 987-7999; or fax (765) 987-7142.