project manual for Lewiston Library Second Floor Remodel Project City of Lewiston Lewiston, Idaho VOLUME 2 of 2 d a t e : March 9, 2016 s e t n o . ______________ p r o j e c t n o. 15025 SECTION 15010 - GENERAL MECHANICAL REQUIREMENTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 1.03 1.04 SCOPE OF WORK – GENERAL A. This section specifies general requirements for mechanical installations and includes requirements common to more than one section of Division 15. It expands and supplements the requirements specified in sections of Division 1. B. Provide materials, labor, transportation, tools, permits, fees, inspections, utilities and incidentals necessary for the complete installation of mechanical work indicated and described in the Contract Documents. C. It is the intent of the Contract Documents to provide an installation complete in every respect. In the event that additional details or special construction is required for work indicated or specified under this section of work or work specified in other sections, provide material and equipment which is usually furnished with such systems in order to complete the installation, whether mentioned or not. SEQUENCE OF WORK A. Conduct work in sequence to provide least possible interference to the activities of the Owner, and to permit orderly transfer of activities and equipment to completed areas. B. Work shall be substantially complete by the dates listed in Division 1 Section, “Summary”. ALTERNATES A. 1.05 Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this section. Refer to Division 1 Section, “Alternates” for description of alternates. Review Contract Documents for additional information. DEFINITIONS A. Provide: Furnish and install complete and ready for intended use. B. Indicated: Indicated on drawings. C. Noted: Noted on Drawings or in Specifications. D. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. Lewiston Library Second Floor Remodel Project 15010-1 15025 1.06 E. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms. F. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. G. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and in duct shafts. H. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters. CODES AND STANDARDS A. Code Compliance: Comply with most current adopted edition of following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.07 SAFETY OF PERSONS AND PROPERTY A. 1.08 Comply with applicable laws, ordinances, rules and regulations of any public authority for the safety of persons and property, including the Occupational Safety and Health Act (OSHA) and Division 1, General and Supplementary Conditions. PERMITS AND FEES A. 1.09 International Building Code (IBC), Standards and Amendments. International Mechanical Code (IMC), Standards and Amendments. International Fire Code (IFC), Standards and Amendments. Uniform Plumbing Code (UPC),Standards and Amendments. International Energy Conservation Code (IECC). International Fuel Gas Code (IFGC). National Fire Protection Association (NFPA). National Electrical Code (NEC); NFPA 70. Applicable State and local codes, laws and ordinances. Obtain and pay for required permits and fees necessary to fully complete work included in the Contract Documents. INTENT AND INTERPRETATION A. Drawings and Specifications supplement each other and any details contained in one and not the other shall be included as if contained in both. Items not specifically mentioned in the specifications or noted on the drawings, but which are obviously necessary to make a complete working installation shall be included. B. Drawings are partly diagrammatic and do not necessarily show exact location of new piping and existing utilities, unless specifically dimensioned. C. Riser and other diagrams are schematic only and do not necessarily show the physical arrangement of equipment. They shall not be used for obtaining quantities or lineal runs of piping. Lewiston Library Second Floor Remodel Project 15010-2 15025 1.10 D. Grilles, fixtures or other pieces of equipment shall be centered on windows, wall spaces, or other items, unless specifically dimensioned otherwise. E. Location of piping and ductwork shall be checked to determine that it clears openings and structural members; that it may be properly concealed; and that it clears cabinets, lights and equipment having fixed locations. F. Mechanical drawings shall serve as working drawings for Division 15 work. Refer to Architectural, Structural, Civil, Landscape and Electrical drawings for additional detail affecting the installation of work. Architectural drawings shall take precedence over the Mechanical drawings if any dimensional discrepancies exist. G. Approximate location of each item is indicated on the drawings. These drawings are not intended to give complete and exact details in regard to location. Exact locations are to be determined by actual measurements at the building. Not all pipe and duct offsets are indicated on the drawings. SUBMITTAL OF EQUIPMENT FOR APPROVAL A. Refer to Division 1 Section, “Submittal Procedures” for submittal definitions, requirements and procedures. Additional requirements are listed below. B. Shop drawings, catalog information, and material schedules shall be submitted for approval on materials and equipment prior to ordering. C. Submittals not meeting the following requirements will be returned for revision: 1. 2. 3. 1.11 Provide a cover page for each item or group of items (schedule group, single fixture plus trim group, etc.). Cover page shall provide a 3” x 5” space for Engineer’s review stamp Each cover page must be clearly identified with the project name, specification number and paragraph number. Submittal package must be accompanied by an itemized index listing specification section, paragraph number, item and manufacturer; larger projects will be index tabbed by specification section with index for each section. SCHEDULE OF VALUES A. Furnish to the Engineer, a breakdown of the Contract for work in Division 15 within 30 days of Notice to Proceed. B. The breakdown shall list cost for materials and labor as follows: 1. 2. 3. 4. Miscellaneous Overhead Expenses Selective Demolition Plumbing Rough-in: a. Underground Piping b. Aboveground Piping c. Pipe Insulation Plumbing Finish: a. Fixtures b. Plumbing Equipment Lewiston Library Second Floor Remodel Project 15010-3 15025 5. 6. 7. 8. 9. 10. 11. 1.12 c. Final Connection Plumbing Rainwater capture and distribution system. HVAC Ductwork: a. Ductwork b. Insulation HVAC Equipment: a. Air Moving HVAC Finish HVAC Instrumentation and Controls: Testing, Adjusting and Balancing Project Closeout: a. O & M Manuals b. Record Documents c. Owner Training GUARANTEE A. Guarantee satisfactory operation of material and equipment installed under Division 15. Repair or replace any defective materials, equipment, or workmanship which may show itself within one year from date of Substantial Completion. PART 2 - PRODUCTS 2.01 2.02 GENERAL MATERIALS AND EQUIPMENT REQUIREMENTS A. Where more than one manufacturer is listed, provide products of only one manufacturer for each type of product. B. Materials used under this Contract, unless specifically noted otherwise, shall be new and of the latest and most current model line produced by the manufacturer. Outdated “new” equipment is not acceptable. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. D. Fuel-fired equipment shall be listed by a nationally recognized testing agency. EQUIPMENT AND MATERIAL SUBSTITUTIONS A. Throughout these Contract Documents, various materials, equipment, apparatus, etc., are specified by manufacturer, brand name, type or catalog number. Such designation is to establish standards of desired quality and construction and shall be the basis of the bid. B. Where more than one manufacturer is listed, and only one manufacturer's catalog number is indicated, that standard of quality and construction shall be maintained by materials supplied by other manufacturer(s). Lewiston Library Second Floor Remodel Project 15010-4 15025 C. Substitutions of equipment or materials shall be made only with written prior approval. Prior approval requests must be received at least ten (10) days prior to bid date unless otherwise instructed. Refer to Division1 Section, “Product Requirements” for procedures in requesting substitutions. D. Acceptance of substitution request signifies manufacturer recognition only. No attempt has been made to check each item as to special features, capacities, or physical dimensions required by this project. Verify requirements before submitting for approval. Acceptance of exact features, sizes, capacities, etc., all of which must meet or exceed design requirements will be determined when submitted during the construction phase. E. The Contractor shall bear full responsibility for substituted equipment and materials, including, but not limited to: 1. 2. 3. 4. 5. Costs. Available space requirements Effect on other trades Changes in electrical requirements Changes in structural requirements. PART 3 - EXECUTION 3.01 3.02 COORDINATION A. Refer to Division 1 Section “Project Management And Coordination”. B. Coordinate available space for equipment and systems with other trades. Refer to Architectural, Structural and Electrical Drawings for additional building details necessary for coordination. C. Cutting, patching, wiring, finishing or any other work required for relocation of work installed due to interferences between work of the various trades will be at no additional cost to the Owner. MANUFACTURER'S INSTRUCTIONS A. 3.03 Furnish proper equipment and/or materials required for installation as intended by the manufacturer, for all work described under Division 15. If needed for proper installation or operation, request advice and supervisory assistance from the representative of the specific manufacturer. Manufacturer's published instructions shall be followed for preparing, assembling, installing, erecting, and cleaning manufactured materials or equipment. Promptly notify the Architect in writing of any conflict between the requirements of the Contract Documents and the manufacturer's directions and obtain the Architect's instructions before proceeding with the work. EXAMINATION OF SITE A. Visit site of proposed work and become familiar with conditions affecting work. Verify measurements at the building before beginning work. Lewiston Library Second Floor Remodel Project 15010-5 15025 3.04 SITE UTILITY SERVICES A. 3.05 EXISTING UTILITIES AND PIPING A. 3.06 Locations of equipment and devices, as shown on the drawings, are approximate unless dimensioned. Exact locations of such items shall be determined from the Construction Drawings. Verify physical dimensions of each item of mechanical equipment, ductwork system and piping system, to fit available space and promptly notify the Architect prior to roughing-in if conflicts appear. Coordinate equipment to available space and access routes through construction. Offsets or transitions in ductwork or piping systems required for proper system operation and/or installation, whether indicated on drawings or not, shall be provided at no additional cost to Owner. REPLACEMENT OF PAVING AND CONCRETE A. 3.08 Locations of existing concealed lines and connection points have been indicated as closely as possible from available information. Assume that such connection points are with in a 10-foot (10') radius of indicated locations. Where connection points are not within this radius, contact the Architect for a decision before proceeding. LAYING OUT WORK A. 3.07 Where applicable, make connections to existing permanent cold water service immediately so as to provide the use of this service by other trades. Comply with Division 1 requirements. Existing sidewalks, concrete paving, curbs, or asphalt paving removed or damaged during period of installation or as a result thereof, shall be replaced with like material in a manner as directed by and to the satisfaction of the Architect. Comply with Division 2 requirements. DELIVERY, STORAGE, AND HANDLING A. Deliver products to project properly identified with names, model numbers, types, grades, compliance labels, and similar information needed for distinct identifications; adequately packaged and protected to prevent damage during shipment, storage, and handling. B. Store equipment and materials at the site, unless off-site storage is authorized in writing. Protect stored equipment and materials from damage. C. Coordinate deliveries of mechanical materials and equipment to minimize construction site congestion. Limit each shipment of materials and equipment to the items and quantities needed for the smooth and efficient flow of installations. Lewiston Library Second Floor Remodel Project 15010-6 15025 3.09 ACCESSIBILITY A. 3.10 Install equipment and materials to provide required access for servicing and maintenance. Coordinate location of concealed equipment and devices requiring access with location of access panels and doors. Allow ample space for removal of parts that require replacement or servicing. TEMPORARY USE OF NEW EQUIPMENT A. New equipment shall not be used for temporary heating, cooling or ventilation unless authorized in writing by the Owner. END OF SECTION 15010 Lewiston Library Second Floor Remodel Project 15010-7 15025 SECTION 15015 - MECHANICAL PROJECT CLOSEOUT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this section. B. Related Sections include the following: 1. 2. 1.02 SCOPE OF WORK - GENERAL A. This section specifies procedural requirements for mechanical installations project closeout, including but not limited to: 1. 2. 3. 4. 5. 6. 7. 1.03 Project Record Document submittal. Operation and Maintenance Manual submittal. Operation and Maintenance Instruction and Training. Mechanical Equipment and Systems Start-Up. Training Session Agenda. Lubrication. Final Cleaning. PROJECT RECORD DOCUMENTS A. Record differences between mechanical work as installed and as shown in Contract Drawings on a set of prints of mechanical drawings furnished by Architect. Return these prints to Architect at completion of project. Notations made on drawings shall be neat and legible. Comply with Division 1 Section requirements. 1. 1.04 Division 1 Section, “Submittal Procedures”. Division 1 Section, “Closeout Procedures”. In addition, furnish CAD drawing files of as-built record drawings on CD ROM, AutoCad Release 2010 or later version. B. Mark drawings to indicate revisions to piping and ductwork, size and location both exterior and interior; including locations of coils, dampers, and other control devices, filters, motors and similar items requiring periodic maintenance; actual equipment locations; concealed equipment and control devices; mains and branches of piping systems, with valves and control devices located and numbered; actual inverts and locations of underground piping. C. Revise equipment and fixture schedules on the Drawings to indicate actual installed manufacturer and model numbers. D. Mark specifications to indicate change orders; actual equipment and materials used. OPERATION AND MAINTENANCE MANUALS A. Prepare and submit Operation and Maintenance (O&M) Manuals for mechanical systems provided. Comply with Division 1 Section requirements. Lewiston Library Second Floor Remodel Project 15015-1 15025 B. Manual binder shall have permanent lettering of a contrasting color. Information to be included on the binder is as follows: 1. The front cover shall be lettered as follows: MECHANICAL OPERATION AND MAINTENANCE MANUAL (PROJECT NAME) (CITY AND STATE) (YEAR) OWNER: (NAME) ARCHITECT: (NAME MECHANICAL ENGINEER: L&S ENGINEERING ASSOCIATES, INC. GENERAL CONTRACTOR: (NAME) MECHANICAL CONTRACTOR: (NAME) 2. The spine shall be lettered as follows: MECHANICAL O & M MANUAL (Year) (Project Name) C. Provide master index at beginning of Manual showing sections and items included. Use plastic tab indexes for sections of Manual. D. Cover section: List name, address, and phone number of Project Architect, General Contractor, Mechanical Engineer, Mechanical Contractor and all Mechanical Sub-Contractors. Provide a list of equipment suppliers with address and phone number. E. Provide a separate section for each Section of the Specifications. Provide index for each section listing equipment included. Include all items specified. F. Include descriptive literature (manufacturer's catalog data) of each manufactured item. Literature shall show capacities and size of equipment used and be marked indicating each specific item with applicable data underlined. Data sheets shall be originals or clean copies of originals. Copies of faxes are not acceptable. G. One copy of the manual shall be submitted for review and approval by the Engineer. After approval, submit 3 copies of manual to Architect for approval unless otherwise directed by Division 1 Section requirements. Information to be included in manual: 1. Description of function, normal operating characteristics and limitations, performance curves, engineering data and tests, and complete nomenclature and commercial numbers of all replaceable parts. Lewiston Library Second Floor Remodel Project 15015-2 15025 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. H. 1.05 Manufacturer's printed operating procedures to include start-up, break-in, routine and normal operating instructions; regulation, control, stopping shut-down, and emergency instructions; and summer and winter operating instructions. Maintenance procedures for routine preventative maintenance and troubleshooting; disassembly, repair, and reassembly; aligning and adjusting instructions. Servicing instructions and lubrication charts and schedules. Schematic control diagrams for each automatic control system. Mark correct operating setting for each control instrument on these diagrams. Valve schedule indicating the valve symbol (tag number), valve location by room number and description, valve purpose and system served, and valve size. Provide 1 corresponding set of full size mechanical prints showing these valve locations for cross-reference. A second complete set of valve schedules (8 1/2 in. x 11 in.) encased in clear plastic laminate and fitted in an aluminum holding frame shall be furnished to the Owner. Testing, Adjusting and Balancing Report. Test records and certifications. Equipment start-up reports. Warranty information and letters of guarantee. Instruction period checklist for each equipment item. Complete O&M Manual shall be available for use by Owner's representatives during instruction and training sessions. OPERATION AND MAINTENANCE INSTRUCTION AND TRAINING A. Instruct Owner's Representative(s) in the Operation and Maintenance procedures described in Operation and Maintenance Manual. Comply with Division 1 Section requirements. B. Enlist services of qualified personnel, including each sub-trade and factory trained specialists for each major piece of equipment, to attend training sessions and provide operation and maintenance instructions. C. Submit training agenda, schedule and list of representatives to Design Engineer for review 30 days prior to training sessions. Confirm attendance by written notification to all participants. D. Prepare checklist of all equipment and systems requiring instruction and maintenance for verification and agreement by the Owner's Representative of satisfactory start-up and instruction. Checklist shall include a statement of completion by the Contractor, date and topic(s) covered in each training session, and an attendance list of all participants at each training session. Submit a copy of checklist to Design Engineer for review 30 days prior to training sessions. Include copy of the completed checklist in Operation and Maintenance Manual. E. Minimum instruction time shall be 16 hours, unless otherwise specifically noted. Refer to individual Division 15 Sections for additional instruction/training requirements. F. All mechanical systems shall be properly functioning prior to instruction period. Lewiston Library Second Floor Remodel Project 15015-3 15025 G. Instruction/training sessions shall be video recorded using a video camera with audio capability. Furnish copy of all training sessions in DVD format to Owner. PART 2 - PRODUCTS (Not Applicable) PART 3 - EXECUTION 3.01 3.02 MECHANICAL EQUIPMENT AND SYSTEMS START-UP A. Provide the services of a factory-authorized service representative to test and inspect unit installation, provide start-up service and demonstrate and train Owner's maintenance personnel. B. Include certification of factory-authorized representative status as part of equipment submittal from manufacturer. C. Include written start-up reports with test data for equipment in Maintenance Manual. D. Required Equipment items shall include the following: LUBRICATION A. 3.03 Operation and Lubricate all pieces of equipment in accordance with Manufacturer's written instructions prior to project closeout. Include a listing of all equipment with the date of final lubrication in Operation and Maintenance manual. FINAL CLEANING A. Refer to Division 1 Section general requirements for final cleaning. B. At time of final cleanup, clean all fixtures and equipment and leave in condition for use intended. Vacuum cabinet interiors of control panels, air handling units, etc. to remove all construction debris including electrical wiring debris. PART 4 - APPENDIX TO SECTION 15015 4.01 GOALS OF THE TRAINING SESSION A. Inform maintenance staff of minimum requirements for maintaining equipment installed on this project. Minimum training required to satisfy this goal is listed in Suggested Training Agenda. Additional requirements may apply as appropriate to equipment installed. B. In addition to the general goal stated above, the Owner has the following specific goals which the training session must satisfy: 1. 2. 3. Train janitorial staff how to replace filters. Train janitorial staff how to respond to alarms generated by the controls system. Train maintenance staff regarding standard operating parameters of equipment. Lewiston Library Second Floor Remodel Project 15015-4 15025 4. 5. 6. C. Personnel who will be attending the training session are varied. Contractor should design the training session as appropriate to audience as listed below: 1. 2. 3. 4.02 Train maintenance staff regarding the potential failure modes of equipment and appropriate actions to take should such failures occur. Train maintenance staff how to test status of water treatment. Train Administrative staff how to adjust temperature settings, where appropriate. Maintenance Staff a. Attending: Head of Maintenance, Assistant Head of Maintenance, Maintenance Mechanic(s). b. These personnel have several years experience in maintaining systems similar to those used in this project. General training session should be provided as a refresher course in system maintenance requirements. c. Beyond the understanding general system requirements, individuals should be able to identify specific maintenance requirements of particular equipment used on this project. d. At end of the training session, the maintenance staff should be able to prepare a maintenance schedule, based on information provided in this training program. Janitorial Staff a. Attending: Lead janitor, assistant lead janitor, line janitor(s). b. These personnel have little experience in maintaining systems of the kind used on this project. c. Training for these individuals should focus on the basic, day to day maintenance required to keep system in normal operating condition. d. At the end of training session, these individuals should be able to respond to comfort complaints and emergencies by taking corrective action or by contacting appropriate maintenance personnel. Administrative Staff a. Attending: School Principal, Assistant Principal, Secretaries, other staff. b. These personnel have little or no experience operating systems of the kind used on this project. c. Training for these individuals should consist of instruction regarding normal operating procedures; what systems should be expected to do; what systems should not be expected to do. d. At the end of training session, these individuals should be able to respond to comfort complaints and emergencies by making minor adjustments or by contacting appropriate maintenance personnel. EQUIPMENT DATA SHEETS A. The following data sheet sample is for reference only. This sample sets the level of completeness required for mechanical equipment records. B. Furnish data sheet for each piece of mechanical equipment requiring operation or maintenance or both. Each data sheet be prepared on a single 8.5 by 11 inch sheet suitable for insertion in a three-ring binder. Data sheets shall be completed to the fullest extent possible by the Contractor prior to submission for Owner's use. Lewiston Library Second Floor Remodel Project 15015-5 15025 C. EQUIPMENT DATA SHEET SAMPLE Equipment Designation Equipment Description Location AHU-1 Air Handling Unit Mechanical Room 226 Manufacturer Date of Manufacture Warranty Term Carrier Corporation September 12, 2005 One year Vendor Company name Street Address City, State, ZIP Phone Fax Start Up By Company Name Company Address City, State, ZIP Phone Fax O&M Instructions In Manual Model Number Start-Up Date Performed by 39MXXXXX Date Technician name On Video Tape Spare Parts Filter Size: Motor: Fan Belt Maintenance Maintenance Items Change filters Clean coils Clean fan wheel Inspect condensate drain Inspect damper actuators Inspect piping for leaks Date Frequency Quarterly Annually Annually Quarterly Quarterly Quarterly Maintenance History Maintenance Performed END OF SECTION 15015 Lewiston Library Second Floor Remodel Project 15015-6 15025 SECTION 15020 - MECHANICAL DEMOLITION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specifications, apply to work of this section. B. Related Sections include the following: 1. 2. 3. 1.02 1.03 Division 1 Section, “Summary” for phasing requirements. Division 1 Section, “Execution”. Division 1 Section, “Selective Structure Demolition” for general demolition requirements and procedures. SUMMARY A. Include all labor, equipment, and materials necessary to complete demolition of existing mechanical systems as shown on the drawings and described herein. B. Reclaim and properly dispose of refrigerant at existing mechanical equipment. C. See architectural demolition sheet A2.0 for mechanical items to be removed. DEFINITIONS A. Remove: Detach items from existing construction and legally dispose of them off-site, unless idicated to be removed and salvaged or removed and reinstalled. B. Remove and Salvage: Detach items from existing construction and deliver them to Owner. C. Remove and Reinstall: Detach items from existing construction, prepare them for reuse, and reinstall them where indicated. D. Existing to Remain: Existing items of construction that are not to be removed and that are not otherwise indicated to be removed, removed and salvaged, or removed and reinstalled. PART 2 - SALVAGE 2.01 MATERIALS OWNERSHIP A. The Owner shall have first salvage rights to all removed fixtures and equipment. Coordinate selection with the Owner's Representative. B. Except for items or materials to be reused, salvaged, reinstalled or otherwise indicated to remain owner’s property, demolished materials shall become Contractor’s property and removed from Project site. Lewiston Library Second Floor Remodel Project 15020-1 15025 C. Transport and legally dispose of off site, all materials resulting from demolition not being salvaged. PART 3 - EXECUTION 3.01 DEMOLITION A. Condition and Premises: The Owner assumes no responsibility for condition of areas to be demolished. General conditions existing at time of inspection for bidding purposes will be maintained by Owner. B. Partial Removal: Items of salvageable value to Contractor indicated to be removed, may be removed from structure as work progresses. Salvaged items must be transported from site as they are removed. Storage or sale of removed items on site will not be permitted. C. Protections: Ensure safe passage of persons around area of demolition. Conduct operations to prevent injury to adjacent buildings, structures, other facilities, and persons. D. Damages: Promptly repair damages caused to adjacent facilities by demolition operations at no cost to Owner. E. Existing Utility Services: Maintain existing utilities indicated to remain, keep in service and protect against damage during demolition operations. F. Cut and/or patch and repair all existing floor, wall and roof penetrations not being re-used. Comply with Division 1 Section requirements. G. Previous demolition work at this building removed ductwork and piping within space back to underside of roof at rooftop units. All remaining mechanical equipment piping and associated ductwork waste, vent and gas, to be removed. Contractor to review site before bidding. H. Existing boiler to remain, disconnect and remove all associated piping, electrical and flue ductwork. I. All roof penetrations that are re-used shall be inspected and made air and water tight. J. Not all piping, ductwork or equipment items are shown on drawings. Other demolition may be required. See A2.0 for mechanical items to be removed. K. Disconnect, demolish, and remove mechanical systems, equipment, and components indicated to be removed. 1. 2. 3. Piping to Be Removed: Remove portion of piping indicated to be removed and cap or plug remaining piping with same or compatible piping material. Piping to Be Abandoned in Place: Drain piping and cap or plug piping with same or compatible piping material. Ducts to Be Removed: Remove portion of ducts indicated to be removed and plug remaining ducts with same or compatible ductwork material. Lewiston Library Second Floor Remodel Project 15020-2 15025 4. 5. 6. 7. 8. L. Ducts to Be Abandoned in Place: Cap or plug ducts with same or compatible ductwork material. Equipment to Be Removed: Disconnect and cap services and remove equipment. Equipment removal shall include removal of all connecting piping, ductwork, etc., either to a point below floor behind wall surface, etc. Equipment to Be Removed and Reinstalled: Disconnect and cap services and remove, clean, and store equipment; when appropriate, reinstall, reconnect, and make equipment operational. Equipment to Be Removed and Salvaged: Disconnect and cap services and remove equipment and deliver to Owner. Capture, reclaim and properly dispose of any refrigerant in existing equipment to be removed. If pipe, insulation, or equipment to remain is damaged in appearance during construction, or is rendered unserviceable, remove damaged or unserviceable portions and replace with new products of equal capacity and quality. END OF SECTION 15020 Lewiston Library Second Floor Remodel Project 15020-3 15025 SECTION 15050 - BASIC MECHANICAL MATERIALS AND METHODS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 1.03 Piping materials and installation instructions common to most piping systems. Transition fittings. Dielectric fittings. Mechanical sleeve seals. Sleeves. Escutcheons. Grout. Equipment installation requirements common to equipment sections. Painting. Concrete bases. Supports and anchorages. Access doors. Drip pans. Through-penetration fire stop systems. Roof pipe supports. Excavation and backfill. Cutting and patching. DEFINITIONS A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms. C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and in duct shafts. E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters. Lewiston Library Second Floor Remodel Project 15050-1 15025 F. The following are industry abbreviations for plastic materials: 1. 2. 3. 1.04 SUBMITTALS A. Product Data: For the following: 1. 2. 3. 4. 5. 6. 7. B. 1.05 QUALITY ASSURANCE A. Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural Welding Code--Steel." B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications." C. 1.07 Transition fittings. Dielectric fittings. Mechanical sleeve seals. Escutcheons. Access Doors. Through-Penetration Fire Stop Systems. Roof Pipe Supports. Welding certificates. 1. 2. 1.06 ABS: Acrylonitrile-butadiene-styrene plastic. PVC: Polyvinyl chloride plastic. EPDM: Ethylene-propylene-diene terpolymer rubber. Comply with provisions in ASME B31 Series, "Code for Pressure Piping." Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. DELIVERY, STORAGE, AND HANDLING A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture. B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending. COORDINATION A. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of construction, to allow for mechanical installations. B. Coordinate installation of required supporting devices and set sleeves in poured-in-place concrete and other structural components as they are constructed. Lewiston Library Second Floor Remodel Project 15050-2 15025 C. Coordinate requirements for access panels and doors for mechanical items requiring access that are concealed behind finished surfaces. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. 2.02 2.03 Manufacturers: Subject to compliance with requirements, provide products by the manufacturers listed. PIPE, TUBE, AND FITTINGS A. Refer to individual Division 15 piping Sections for pipe, tube, and fitting materials and joining methods. B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings. JOINING MATERIALS A. Refer to individual Division 15 piping Sections for special joining materials not listed below. B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents. 1. 2. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch maximum thickness unless thickness or specific material is indicated. a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flanges. b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flanges. AWWA C110, rubber, flat face, 1/8 inch thick, unless otherwise indicated; and full-face or ring type, unless otherwise indicated. C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated. D. Plastic, Pipe-Flange Gasket, Bolts, and Nuts: Type and material recommended by piping system manufacturer, unless otherwise indicated. E. Solder Filler Metals: ASTM B 32, lead-free; 95.6% tin/4% copper/0.4% silver solder; 440-500 deg.F melting range. F. Brazing Filler Metals: AWS A5.8, BCuP-5, copper-phosphorus alloys, 15% silver, 1190-1480 deg.F melting range. G. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded. Lewiston Library Second Floor Remodel Project 15050-3 15025 H. Solvent Cements for Joining Plastic Piping: 1. 2. 3. 2.04 TRANSITION FITTINGS A. Plastic-to-Metal Transition FittingsPVC one-piece fitting with manufacturer's Schedule 80 equivalent dimensions; one end with threaded brass insert, and one solventcement-joint end. B. Flexible Transition Couplings for Underground Nonpressure Drainage Piping: ASTM C 1173 with elastomeric sleeve, ends same size as piping to be joined, and corrosion-resistant metal band on each end. 1. 2.05 ABS Piping: ASTM D 2235. PVC Piping: ASTM D 2564. Include primer according to ASTM F 656. PVC to ABS Piping Transition: ASTM D 3138. Manufacturers: a. Cascade Waterworks Mfg. Co. b. Fernco, Inc. c. Mission Rubber Company. d. Plastic Oddities, Inc. DIELECTRIC FITTINGS A. Description: Combination fitting of copper alloy and ferrous materials with threaded, solder-joint, plain, or weld-neck end connections that match piping system materials. B. Insulating Material: Suitable for system fluid, pressure, and temperature. C. Dielectric Unions: Factory-fabricated, union assembly, for 250-psig minimum working pressure at 180 deg F. 1. D. Manufacturers: a. Capitol Manufacturing Co. b. Central Plastics Company. c. Eclipse, Inc. d. Epco Sales, Inc. e. Hart Industries, International, Inc. f. Watts Industries, Inc.; Water Products Div. g. Zurn Industries, Inc.; Wilkins Div. Dielectric Flanges: Factory-fabricated, companion-flange assembly, for 150- or 300-psig minimum working pressure as required to suit system pressures. 1. Manufacturers: a. Capitol Manufacturing Co. b. Central Plastics Company. c. Epco Sales, Inc. d. Watts Industries, Inc.; Water Products Div. Lewiston Library Second Floor Remodel Project 15050-4 15025 E. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic lining; plain, threaded, or grooved ends; and 300-psig minimum working pressure at 225 deg F. 1. 2.06 MECHANICAL SLEEVE SEALS A. Description: Modular sealing element unit, designed for field assembly, to fill annular space between pipe and sleeve. 1. 2. 3. 4. 2.07 Manufacturers: a. Advance Products & Systems, Inc. b. Calpico, Inc. c. Metraflex Co. d. Pipeline Seal and Insulator, Inc. e. PSI/Thunderline Link-Seal. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe. Pressure Plates: Plastic. Include two for each sealing element. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element. SLEEVES A. Galvanized-Steel Sheet: 22 gage (0.0296-inch) minimum thickness; round tube closed with welded longitudinal joint. B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends. C. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated. D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring and bolts and nuts for membrane flashing. 1. E. 2.08 Manufacturers: a. Perfection Corp. b. Precision Plumbing Products, Inc. c. Sioux Chief Manufacturing Co., Inc. d. Victaulic Co. of America. Underdeck Clamp: Clamping ring with set screws. PVC Pipe: ASTM D 1785, Schedule 40. ESCUTCHEONS A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely fit around pipe, tube, and insulation of insulated piping and an OD that completely covers opening. B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with polished chromeplated finish. Lewiston Library Second Floor Remodel Project 15050-5 15025 C. One-Piece, Cast-Brass Type: With set screw. 1. D. Split-Casting, Cast-Brass Type: With concealed hinge and set screw. 1. 2.09 One-Piece, Stamped-Steel Type: With set screw or spring clips and chrome-plated finish. F. Split-Plate, Stamped-Steel Type: With hinge, set screw or spring clips, and chromeplated finish. G. One-Piece, Floor-Plate Type: Cast-iron floor plate. H. Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set screw. GROUT Description: ASTM C 1107, Grade B, nonshrink and nonmetallic, dry hydraulic-cement grout. 1. 2. 3. Characteristics: Post-hardening, volume-adjusting, nonstaining, noncorrosive, nongaseous, and recommended for interior and exterior applications. Design Mix: 5000-psi, 28-day compressive strength. Packaging: Premixed and factory packaged. DRIP PANS A. Galvanized steel sheet: Lock-forming quality; complying with ASTM A 653/A 653M and having G90 coating designation. 1. 2. 3. 4. 2.11 Finish: Polished chrome-plated. E. A. 2.10 Finish: Polished chrome-plated. Minimum thickness: 18 ga. (0.046 inch) Joints: Sealed water-tight or welded. Construction: Minimum 2-1/2 inch high with hemmed top edges all four sides. Drain connection: 3/4 inch diameter outlet at low point. Stub out a minimum of 2 inches for drain line connection. ACCESS DOORS A. Description: Access doors, non-rated and fire-rated for ceiling and wall surfaces. B. Related sections include the following: 1. C. Division 15 Section “Duct Accessories” for duct-mounting access doors in HVAC systems. Manufacturers: 1. 2. 3. 4. 5. Acudor Products, Inc. Cesco Products. Elmdor/Stoneman; Div. Of Acorn Engineering Co. Karp Associates. Milcor . Lewiston Library Second Floor Remodel Project 15050-6 15025 D. Flush, Insulated, Fire-Rated Access Doors and Trimless Frames: Fabricated from steel sheet. 1. 2. 3. 4. 5. 6. 7. 8. E. Flush Access Doors and Frames with Exposed Trim: Fabricated from steel sheet. 1. 2. 3. 4. 5. F. Locations: Gypsum board wall and ceiling surfaces. Door: Minimum 0.060 inch thick sheet metal, set flush with exposed face flange of frames. Frame: Minimum 0.060 inch thick sheet metal with 1 inch wide surfacemounted trim. Hinges: Continuous piano hinge. Latch: Screwdriver operated cam latch. Flush Access Doors and Trimless Frames: Fabricated from steel sheet. 1. 2. 3. 4. 5. 2.12 Locations: Gypsum board wall and ceiling surfaces. Fire-Resistance Rating: One and a half hours, “B” label. Temperature Rise Rating; 250 degrees at the end of 30 minutes. Door: Flush panel with a core of mineral-fiber insulation enclosed in sheet metal with a minimum thickness of 0.036 inch. Frame: Minimum 0.060 inch thick sheet metal with drywall bead. Hinges: Continuous piano hinge. Automatic Closer: Spring type. Latch: Self-latching bolt with interior release. Locations: Gypsum board wall and ceiling surfaces. Door: Minimum 0.060 inch thick sheet metal, set flush with surrounding finish surfaces. Frame: Minimum 0.060 inch thick sheet metal with drywall bead. Hinges: Continuous piano hinge. Latch: Screwdriver operated cam latch. THROUGH-PENETRATION FIRE STOP SYSTEMS A. General: For the following constructions, provide through-penetration firestop systems that are produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of assembly penetrated. 1. 2. 3. 4. B. Fire-resistance-rated load-bearing walls, including partitions, with fireprotection-rated openings. Fire-resistance-rated non-load-bearing walls, including partitions, with fireprotection-rated openings. Fire-resistance-rated floor assemblies. Fire-resistance-rated roof assemblies. F-Rated Systems: Provide through-penetration firestop systems with F-ratings indicated, as determined per ASTM E 814, but not less than that equaling or exceeding fireresistance rating of constructions penetrated. Lewiston Library Second Floor Remodel Project 15050-7 15025 C. T-Rated Systems: For the following conditions, provide through-penetration firestop systems with T-ratings indicated, as well as F-ratings, as determined per ASTM E 814, where systems protect penetrating items exposed to potential contact with adjacent materials in occupiable floor areas: 1. 2. 3. 4. D. For through-penetration firestop systems exposed to view, traffic, moisture, and physical damage, provide products that after curing do not deteriorate when exposed to these conditions both during and after construction. E. Related sections include the following: 1. 2. F. 2. 3. G. Division 7 sections “Through-Penetration FireStop Systems” or “Firestopping”. Division 15 sections specifying duct and piping penetrations. Submittals: 1. Product Data: For each type of through-penetration firestop system product indicated. Product Certificates: Signed by manufacturers of through-penetration firestop system products certifying that products furnished comply with requirements. Product Test Reports: From a qualified testing agency indicating throughpenetration firestop system complies with requirements, based on comprehensive testing of current products. Manufacturers: 1. 2. 3. 4. 5. 6. 2.13 Penetrations located outside wall cavities. Penetrations located outside fire-resistive shaft enclosures. Penetrations located in construction containing fire-protection-rated openings. Penetrating items larger than 4-inch diameter nominal pipe or 16 sq. in. in overall cross-sectional area. Bio-Fireshield Firestop Systems Inc. Hilti Construction Chemicals, Inc. International Protective Coatings Corp. RectorSeal Corporation . 3M Fire Protection Products. ROOF PIPE SUPPORTS A. Freestanding pipe piers: 1. 2. B. Closed cell polyethylene AUV Resistant Black@ foam with 14 gauge clamp channel insert. Manufacturers: a. Erico/Michigan Hanger. Freestanding Apillow block@ type pipestands: 1. 2. Constructed of polycarbonate resins, UV stabilized. Manufacturers: a. MIRO Industries. b. MAPA Products. Lewiston Library Second Floor Remodel Project 15050-8 15025 2.14 EXCAVATION AND BACKFILL A. Bedding and initial backfill material: Clean, sand-gravel mixture free from organic matter and conforming to the following gradation when tested in accordance with ASTM D 2940. U.S. Standard Sieve Size B. Percent Passing 1 inch 100 No. 200 0-10 Backfill: Satisfactory soil materials complying with ASTM D2487 soil classification groups GW, GP, GM, SM, SW, and SP, free of rock or gravel larger than 2 inches in any dimension, debris, waste, frozen materials, vegetation and other deleterious matter. PART 3 - EXECUTION 3.01 PIPING SYSTEMS - COMMON REQUIREMENTS A. Install piping according to the following requirements and Division 15 Sections specifying piping systems. B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved. C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas. D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. E. Do not run piping directly over electrical panels or switchgear. F. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. G. Install piping to permit valve servicing. H. Install piping at indicated slopes. I. Install piping free of sags and bends. J. Install fittings for changes in direction and branch connections. Lewiston Library Second Floor Remodel Project 15050-9 15025 K. Install piping to allow application of insulation. L. Cap or seal temporary openings in piping during construction. Remove caps or seals for final connections. M. Select system components with pressure rating equal to or greater than system operating pressure. N. Install escutcheons for penetrations of walls, ceilings, and floors according to the following: 1. 2. New Piping: a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deeppattern type. b. Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-plated finish. c. Insulated Piping: One-piece, stamped-steel type with spring clips. d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Onepiece, cast-brass type with polished chrome-plated finish. e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, castbrass type with polished chrome-plated finish.Bare Piping in Unfinished Service Spaces: One-piece, stamped-steel type with concealed or exposed-rivet hinge andset screw or spring clips. f. Bare Piping in Equipment Rooms: One-piece, stamped-steel type with set screw or spring clips. Existing Piping: Use the following: a. Chrome-Plated Piping: Split-casting, cast-brass type with chrome-plated finish. b. Insulated Piping: Split-plate, stamped-steel type with concealed or exposed-rivet hinge and spring clips. c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Splitcasting, cast-brass type with chrome-plated finish. d. Bare Piping at Ceiling Penetrations in Finished Spaces: Split-plate, stamped-steel type with concealed hinge and set screw. e. Bare Piping in Unfinished Service Spaces: Split-plate, stamped-steel type with concealed or exposed-rivet hinge and set screw or spring clips. f. Bare Piping in Equipment Rooms: Split-plate, stamped-steel type with set screw or spring clips. O. Sleeves are not required for core-drilled holes. P. Install sleeves for pipes passing through concrete and masonry walls, gypsum-board partitions where specifically indicated and concrete floor and roof slabs. 1. 2. Cut sleeves to length for mounting flush with both surfaces. a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level. Extend castiron sleeve fittings below floor slab as required to secure clamping ring if ring is specified. Install sleeves in new walls and slabs as new walls and slabs are constructed. Lewiston Library Second Floor Remodel Project 15050-10 15025 3. 4. Q. Aboveground, Exterior-Wall Pipe Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals. 1. 2. 3. R. Mechanical Sleeve Seal Installation: Select type and number of sealing elements required for pipe material and size. Position pipe in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal. Fire-Barrier Penetrations: 1. 2. 3.02 Install steel pipe for sleeves smaller than 6 inches in diameter. Install cast-iron "wall pipes" for sleeves 6 inches and larger in diameter. Mechanical Sleeve Seal Installation: Select type and number of sealing elements required for pipe material and size. Position pipe in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal. Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves. Seal pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for 1inch annular clear space between pipe and sleeve for installing mechanical sleeve seals. 1. S. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation. Use the following sleeve materials: a. PVC or Steel Pipe Sleeves: For pipes smaller than NPS 6. b. Stack Sleeve Fittings: For pipes penetrating floors with membrane waterproofing. Secure flashing between clamping flanges. Install section of cast-iron soil pipe to extend sleeve to 2 inches above finished floor level. 1) Seal space outside of sleeve fittings with grout. Except for underground wall penetrations, seal annular space between sleeve and pipe or pipe insulation, using joint sealants appropriate for size, depth, and location of joint. Use metallic piping only for fire-barrier penetrations.Transition from system pipe material to penetration material as required. Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. T. Verify final equipment locations for roughing-in. U. Refer to equipment specifications in other Sections of these Specifications for roughingin requirements. PIPING JOINT CONSTRUCTION A. Join pipe and fittings according to the following requirements and Division 15 Sections specifying piping systems. B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. Lewiston Library Second Floor Remodel Project 15050-11 15025 C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly. D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead-free solder alloy complying with ASTM B 32. E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and Tube" Chapter. F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. 2. G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes and welding operators according to Part 1 "Quality Assurance" Article. H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads. I. Plastic Piping Solvent-Cement Joints: Clean and dry joining surfaces. Join pipe and fittings according to the following: 1. 2. 3. 4. 5. 3.03 Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds. Comply with ASTM F 402 for safe-handling practice of cleaners, primers, and solvent cements. ABS Piping: Join according to ASTM D 2235 and ASTM D 2661 Appendixes. PVC Pressure Piping: Join schedule number ASTM D 1785, PVC pipe and PVC socket fittings according to ASTM D 2672. Join other-than-schedule-number PVC pipe and socket fittings according to ASTM D 2855. PVC Nonpressure Piping: Join according to ASTM D 2855. PVC to ABS Nonpressure Transition Fittings: Join according to ASTM D 3138 Appendix. J. Plastic Pressure Piping Gasketed Joints: Join according to ASTM D 3139. K. Plastic Nonpressure Piping Gasketed Joints: Join according to ASTM D 3212. PIPING CONNECTIONS A. Make connections according to the following, unless otherwise indicated: 1. 2. 3. Install unions, in piping NPS 2 and smaller, adjacent to each threaded valve and at final connection to each piece of equipment. Install flanges, in piping NPS 2-1/2 and larger, adjacent to flanged valves and at final connection to each piece of equipment. Wet Piping Systems: Install dielectric coupling and nipple fittings to connect galvanized or black steel piping to copper piping and fittings. Lewiston Library Second Floor Remodel Project 15050-12 15025 3.04 3.05 3.06 EQUIPMENT INSTALLATION - COMMON REQUIREMENTS A. Install equipment to allow maximum possible headroom unless specific mounting heights are indicated. B. Install equipment level and plumb, parallel and perpendicular to other building systems and components in exposed interior spaces, unless otherwise indicated. C. Install mechanical equipment to facilitate service, maintenance, and repair or replacement of components. Connect equipment for ease of disconnecting, with minimum interference to other installations. Extend grease fittings to accessible locations. D. Install equipment to allow right of way for piping installed at required slope. PAINTING A. Painting of mechanical systems, equipment, and components is specified in Division 9 Section "Painting." B. Damage and Touchup: Repair marred and damaged factory-painted finishes with materials and procedures to match original factory finish. CONCRETE BASES A. Concrete Bases: Anchor equipment to concrete base according to equipment manufacturer's written instructions and according to seismic codes at Project. 1. 2. 3. 4. 5. 6. 7. 3.07 Construct concrete bases of dimensions where indicated, but not less than 6 inches larger in both directions than supported unit and 4 inches minimum thickness or as recommended by equipment manufacturer. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of the base. Install epoxy-coated anchor bolts for supported equipment that extend through concrete base, and anchor into structural concrete floor. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. Install anchor bolts to elevations required for proper attachment to supported equipment. Install anchor bolts according to anchor-bolt manufacturer's written instructions. Use 3000-psi 28-day compressive-strength concrete and reinforcement . ERECTION OF METAL SUPPORTS AND ANCHORAGES A. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor mechanical materials and equipment. B. Field Welding: Comply with AWS D1.1. Lewiston Library Second Floor Remodel Project 15050-13 15025 3.08 3.09 3.10 3.11 ERECTION OF WOOD SUPPORTS AND ANCHORAGES A. Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and anchor mechanical materials and equipment. B. Select fastener sizes that will not penetrate members if opposite side will be exposed to view or will receive finish materials. Tighten connections between members. Install fasteners without splitting wood members. C. Attach to substrates as required to support applied loads. GROUTING A. Mix and install grout for mechanical equipment base bearing surfaces, pump and other equipment base plates, and anchors. B. Clean surfaces that will come into contact with grout. C. Provide forms as required for placement of grout. D. Avoid air entrapment during placement of grout. E. Place grout, completely filling equipment bases. F. Place grout on concrete bases and provide smooth bearing surface for equipment. G. Place grout around anchors. H. Cure placed grout. DRIP PANS A. Locate drip pans where indicated. B. Suspend from structure with threaded rods and building attachments. C. Brace to prevent sagging or swaying. D. Connect drain line to drain connection, and routed to nearest plumbing drain or elsewhere as indicated. ACCESS DOORS A. Provide access doors wherever required to service valves, dampers, fire dampers, motor or any other items of equipment where concealed, unless specifically indicated on the drawings to be furnished under other Section(s). B. Size and locate access doors for service and maintenance of equipment items to allow adequate access for required service. Lewiston Library Second Floor Remodel Project 15050-14 15025 3.12 C. Advise installers of other work about specific requirements relating to access door and floor door installation, including sizes of openings to receive access door and frame, as well as locations of supports, inserts, and anchoring devices. D. Set frames accurately in position and attach securely to supports with plane of face panels aligned with adjacent finish surfaces. E. Adjust doors and hardware after installation for proper operation. THROUGH-PENETRATION FIRESTOP SYSTEMS A. Examination: 1. 2. B. Preparation: 1. 2. C. Surface Cleaning: Clean out openings immediately before installing throughpenetration firestop systems to comply with written recommendations of firestop system manufacturer: Priming: Prime substrates where recommended in writing by throughpenetration firestop system manufacturer using that manufacturer's recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces. Through-Penetration Firestop System Installation: 1. 2. D. Examine substrates and conditions, with Installer present, for compliance with requirements for opening configurations, penetrating items, substrates, and other conditions affecting performance. Proceed with installation only after unsatisfactory conditions have been corrected. General: Install through-penetration firestop systems in accordance with manufacturer's written installation instructions and published drawings for products and applications indicated. Install forming/damming/backing materials and other accessories of types required to support fill materials during their application and in the position needed to produce cross-sectional shapes and depths required to achieve fire ratings indicated. Cleaning and Protection: 1. 2. Clean off excess fill materials adjacent to openings as Work progresses by methods and with cleaning materials that are approved in writing by throughpenetration firestop system manufacturers and that do not damage materials in which openings occur. Provide final protection and maintain conditions during and after installation that ensure through-penetration firestop systems are without damage or deterioration at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated throughpenetration firestop systems immediately and install new materials to produce through-penetration firestop systems complying with specified requirements. Lewiston Library Second Floor Remodel Project 15050-15 15025 3.13 3.14 ROOF PIPE SUPPORTS A. Install roof pipe supports in accordance with manufacturer’s instructions. B. Verify roofing material and assure compatibility with roofing. C. Install at spacing required for pipe size and material. Refer to individual Division 15 Sections for piping system spacing requirements. EXCAVATION AND BACKFILL A. Provide necessary excavation, shoring, and backfilling required for proper installation of mechanical work. B. During excavation, stockpile material satisfactory for backfilling in an orderly manner at a distance from the banks of the trench equal to half the depth of the excavation, but in no instance closer than 2 feet. Remove excavated material not required or not satisfactory for backfill from the site and dispose of properly. Grading shall be done as necessary to prevent surface water from flowing into the excavation. Remove accumulated water to maintain stability of the bottom and sides of excavation. C. Excavate trenches to depth required to establish indicated slope and invert elevations and to support bottom of piping or conduit on undisturbed soil. Trenches shall be of uniform width, sufficient to provide ample working room and a minimum of 12 inches of clearance on both sides of pipe or conduit. D. Grade bottoms of trenches to provide uniform bearing and support for bottom quadrant of each section of pipe. Excavate bell holes to the necessary size at each joint or coupling to eliminate point bearing. Remove stones of 2 inches or greater in any dimension, or as recommended by pipe manufacturer, whichever is smaller, to avoid point bearing. Where unyielding material is encountered in the bottom of trench, remove such material 6 inches below required grade and replaced with materials described below for bedding. E. Bedding and initial backfill material: Clean, sand-gravel mixture free from organic matter and conforming to the following gradation when tested in accordance with ASTM D 2940. U.S. Standard Sieve Size F. Percent Passing 1 inch 100 No. 200 0-10 Backfill: Satisfactory soil materials complying with ASTM D2487 soil classification groups GW, GP, GM, SM, SW, and SP, free of rock or gravel larger than 2 inches in any dimension, debris, waste, frozen materials, vegetation and other deleterious matter. Lewiston Library Second Floor Remodel Project 15050-16 15025 3.15 G. Place bedding and initial backfill material to a depth of 6 inches over the top of piping. Bring material up evenly on both sides of pipe for full length of pipe. H. Backfill to the required grade in layers not exceeding 4 inches loose thickness for compaction by hand operated machine compactors, and 8 inches loose thickness for other than hand operated machines otherwise specified. Compact top 12 inches below subgrade and each layer of backfill at 95 percent maximum dry density (ASTM D 1557) under structures, building slabs, steps, pavements and walkways. Compact the top 6 inches below subgrade and each layer of backfill at 90 percent maximum dry density (ASTM D 1557) under lawn or unpaved areas. I. Do not cover underground lines until installation has been approved by the inspector having jurisdiction and Owner's Representative. J. Cut trenches within 5 feet of footings or under footings only after approval of the Architect. K. Provide bracing and shoring where depth of excavation or character of ground render it necessary for personnel protection. Comply with local and state safety laws and regulations. L. Remove bracing and shoring materials before backfilling except where necessary to insure against caving. M. Provide securely constructed barricades around excavation. N. Exercise extreme care while excavating in the area of utilities, carefully check for location of possible utilities, whether shown on the drawings or not, and establish location of cutoff valves for ready shut-off of service in case of emergency. Assume complete responsibility for all damage to any utilities caused in excavating as well as damage to personnel and property caused by said damaged utilities whether shown on drawings or not. CUTTING AND PATCHING A. Comply with Division 1 Section, “Execution Requirements” for general requirements for cutting and patching. B. Cutting shall be performed with masonry saws, core drills or similar equipment to provide neat and uniform openings. C. Patching shall match adjacent surfaces in materials and finish. Do not endanger or damage installed work through procedures and processes of cutting and patching. D. Arrange for repairs required to restore other work, because of damage caused as a result of mechanical installations. No extra reimbursement will be authorized for cutting and patching work that is necessitated by ill-timed, defective, or non-conforming installations. Lewiston Library Second Floor Remodel Project 15050-17 15025 E. No additional compensation will be authorized for cutting and patching work that is necessitated by ill-timed, defective, or non-conforming installations. F. Perform cutting, fitting, and patching of mechanical equipment and materials required to: 1. 2. 3. 4. 5. 6. Uncover work to provide for installation of ill-timed work. Remove and replace defective work. Remove and replace work not conforming to requirements of the Contract Documents. Remove samples of installed work as specified for testing. Install equipment and materials in existing structures. Upon written instructions from the Architect, uncover and restore work to provide for observation of concealed work. G. Cut, remove and legally dispose of selected mechanical equipment, components, and materials as indicated, including, but not limited to removal of mechanical piping, heating units, plumbing fixtures and trim, and other mechanical items made obsolete by new work. H. Protect structure, furnishings, finishes, and adjacent materials not indicated or scheduled to be removed. I. Provide and maintain temporary partitions or dust barriers adequate to prevent the spread of dust and dirt to adjacent areas. END OF SECTION 15050 Lewiston Library Second Floor Remodel Project 15050-18 15025 SECTION 15054 – ELECTRICAL PROVISIONS FOR MECHANICAL EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specifications, apply to work of this section. B. Related Sections include the following: 1. 1.02 1.03 Division 15 Section “Motors”. SUMMARY A. This section specifies basic requirements for field-installed accessory electrical components specified as a part of packaged mechanical equipment. These components include, but are not limited to controllers, motors, starters, and disconnect switches furnished as an integral part of packaged mechanical equipment, but not factoryinstalled. B. Specific electrical requirements (i.e. horsepower and electrical characteristics) for mechanical equipment are specified within the individual equipment specifications or scheduled on the drawings. C. Make all required electrical connections from mechanical equipment to accessory electrical components furnished by manufacturer as a part of equipment but intended to be field-installed, including pushbuttons, pilot lights, interlocks, speed controllers, and similar devices. D. Provide all required electrical connections of field-mounted float control switches, flow control switches, and similar mechanical/electrical devices provided for pumps and similar mechanical equipment. E. Provide interconnecting wiring between mechanical equipment shipped in multiple parts and designed by the manufacturer to have field-installed interconnecting wiring. F. All electrical work shall comply with applicable requirements of Division 16. REFERENCES A. NEMA Standard ICS 2: Industrial Control Devices, Controllers and Assemblies. B. NEMA Standard 250: Enclosures for Electrical Equipment. C. NEMA Standard KS 1: Enclosed Switches. Comply with National Electrical Code (NFPA 70). Lewiston Library Second Floor Remodel Project 15054-1 15025 1.04 SUBMITTALS A. 1.05 No separate submittal is required. Submit product data for motors, starters, and other electrical components with submittal data required for the equipment for which it serves as required by the individual equipment specification sections. QUALITY ASSURANCE A. All electrical components and materials shall be labeled by an approved testing agency (UL, ETL, CSA, etc.). PART 2 - PRODUCTS (Not Applicable) PART 3 - EXECUTION 3.01 INSTALLATION A. Comply with applicable requirements of Division 16 and NFPA 70 (National Electrical Code). B. Install equipment and wiring per manufacturer’s instructions. END OF SECTION 15054 Lewiston Library Second Floor Remodel Project 15054-2 15025 SECTION 15055 - MOTORS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. Section includes general requirements for single-phase and polyphase, general-purpose, horizontal, small and medium, squirrel-cage induction motors for use on ac power systems up to 600 V and installed at equipment manufacturer's factory or shipped separately by equipment manufacturer for field installation. B. Related Sections include the following: 1. 2. 1.03 DEFINITIONS A. 1.04 Division 15 Sections for application of motors and reference to specific motor requirements for motor-driven equipment. Division 15 Section, “Electrical Provisions for Mechanical Equipment”. Factory-Installed Motor: A motor installed by motorized-equipment manufacturer as a component of equipment. QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. Comply with NFPA 70, National Electrical Code. PART 2 - PRODUCTS 2.01 GENERAL MOTOR REQUIREMENTS A. 2.02 Comply with NEMA MG 1 unless otherwise indicated. MOTOR CHARACTERISTICS A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet above sea level. B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor. Lewiston Library Second Floor Remodel Project 15055-1 15025 2.03 POLYPHASE MOTORS A. Description: NEMA MG 1, Design B, medium induction motor. B. Efficiency: Energy efficient, as defined in NEMA MG 1. C. Service Factor: 1.15. D. Multispeed Motors: Separate winding for each speed. E. Rotor: Random-wound, squirrel cage. F. Bearings: Greasable, shielded, antifriction ball bearings suitable for radial and thrust loading. G. Temperature Rise: Match insulation rating. H. Insulation: Class F. I. Code Letter Designation: 1. 2. J. 2.04 Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for motor frame sizes smaller than 324T. POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS A. Motors Used with Reduced-Voltage and Multispeed Controllers: Match wiring connection requirements for controller with required motor leads. Provide terminals in motor terminal box, suited to control method. B. Motors Used with Variable Frequency Controllers: 1. 2. 3. 4. 5. 2.05 Motors 15 HP and Larger: NEMA starting Code F or Code G. Motors Smaller than 15 HP: Manufacturer's standard starting characteristic. Windings: Copper magnet wire with moisture-resistant insulation varnish, designed and tested to resist transient spikes, high frequencies, and short time rise pulses produced by pulse-width modulated inverters. Energy- and Premium-Efficient Motors: Class B temperature rise; Class F insulation. Inverter-Duty Motors: Class F temperature rise; Class H insulation. Shaft Grounding Lugs: Factory installed. Thermal Protection: Comply with NEMA MG 1 requirements for thermally protected motors. SINGLE-PHASE MOTORS A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application: 1. Permanent-split capacitor. Lewiston Library Second Floor Remodel Project 15055-2 15025 2. 3. Capacitor start, inductor run. Capacitor start, capacitor run. B. Multispeed Motors: Variable-torque, permanent-split-capacitor type. C. Bearings: Pre-lubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading. D. Motors 1/20 HP and Smaller: Shaded-pole type. E. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range. PART 3 - EXECUTION (Not Applicable) END OF SECTION 15055 Lewiston Library Second Floor Remodel Project 15055-3 15025 SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following hangers and supports for mechanical system piping and equipment: B. Related Sections include the following: 1. 2. 3. 1.03 1.04 Division 15 Section "Mechanical Vibration and Seismic Controls" for vibration isolation devices. Division 15 Section "Pipe Expansion Fittings and Loops" for pipe guides and anchors. Division 15 Section(s) "Metal Ducts" and "Nonmetal Ducts" for duct hangers and supports. DEFINITIONS A. MSS: Manufacturers Standardization Society for the Valve and Fittings Industry Inc. B. Terminology: As defined in MSS SP-90, "Guidelines on Terminology for Pipe Hangers and Supports." SUBMITTALS A. Product Data: For each type of pipe hanger, channel support system component, and thermal-hanger shield insert indicated. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Pipe Hangers: a. Anvil International, Inc b. ERICO/Michigan Hanger Co. c. Globe Pipe Hanger Products, Inc. d. Hubbard Enterprises/Holdrite e. PHD Manufacturing, Inc. f. Thomas & Betts. g. Tolco Inc. h. Unistrut Corp. Lewiston Library Second Floor Remodel Project 15060-1 15025 2. 3. 2.02 Channel Support Systems: a. Erico/Michigan Co.; O-Strut Div. b. Thomas & Betts Corp. c. Tolco, Inc. d. Unistrut Corp. Thermal Hanger Shield Inserts: a. ERICO/Michigan Hanger Co. b. PHS Industries, Inc. c. Pipe Shields, Inc. d. Rilco Manufacturing Company, Inc. e. Value Engineered Products, Inc. MANUFACTURED UNITS A. Pipe hangers, Supports and Components: MSS SP-58, factory fabricated components. Refer to “Hanger and Support Applications” Article in Part 3 for where to use specific hanger and support types. 1. 2. B. Channel Support Systems: MFMA-2, factory-fabricated components for field assembly. 1. 2. C. Coatings: Manufacturer’s standard finish, unless bare metal surfaces are indicated. Nonmetallic Coatings: Plastic Coating, jacket or liner. Thermal Hanger Shield Inserts” 100-psi minimum compressive-strength insulation, encased in sheet metal shield. 1. 2. 3. 4. 5. D. Galvanized, Metallic Coatings: Pregalvanized or hot dipped. Nonmetallic Coatings: Plastic coating, jacket or liner. Material for Cold Piping: ASTM C 552, Type I cellular glass or water-repellent treated, ASTM C 533, Type I calcium silicate with vapor barrier. Material for Hot Piping: ASTM C 552, Type I cellular glass or water-repellent treated, ASTM C 533, Type I calcium silicate. For Trapeze or Clamped Systems: Insert and shield cover entire circumference of pipe. For Clevis or Band Hangers: Insert and shield cover lower 180 degrees of pipe. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient air temperature. Pipe Stands: Shop or field-fabricated assemblies made of manufactured corrosionresistant components to support roof-mounted piping. 1. 2. 3. 4. Compact Pipe Stand: One-piece plastic unit with integral-rod-roller, pipe clamps, or V-shaped cradle to support pipe, for roof installation without membrane penetration. Low-Type, Single-Pipe Stand: One-piece plastic base unit with plastic roller, for roof installation without membrane penetration. High-Type, Single-Pipe Stand: Assembly of plastic base, two or more protective coated steel channel vertical members; protective coated steel horizontal member, galvanized steel, clevis-type pipe hangers, for roof installation without membrane penetration. Curb-Mounting-Type Pipe Stands: Shop- or field-fabricated pipe support made from structural-steel shape, continuous-thread rods, and rollers for mounting on permanent stationary roof curb. Lewiston Library Second Floor Remodel Project 15060-2 15025 2.03 MISCELLANEOUS MATERIALS A. Mechanical-Anchor Fasteners: Insert-wedge type zinc coated steel, for use in hardened Portland cement with pull-out, tension and shear capacities appropriate for supported loads and building materials where used. B. Structural Steel: galvanized. C. Plenum Rated Pipe Clamps: ASTM E-84 25/50 plastic clamps. Hubbard Enterprises/ Holdrite or equal. D. Grout: ASTM C 1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications. 1. 2. ASTM A 36/A 36M, steel plates, shapes, and bars; black and Properties: Nonstaining, noncorrosive, and nongaseous. Design Mix: 5000-psi, 28-day compressive strength. PART 3 - EXECUTION 3.01 HANGER AND SUPPORT APPLICATIONS A. Specific hanger and support requirements are specified in Sections specifying piping systems and equipment. B. Comply with MSS SP-69 for pipe hanger selections and applications that are not specified in piping system Sections. C. Use hangers and supports with galvanized, metallic coatings for piping and equipment that will not have field-applied finish. D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing. E. Use felt, rubber or vinyl padding applied to hangers for piping that is subject to scratching. F. Support of pipe, tubing and equipment shall be accomplished by means of engineered products, specific to each application. G. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. 2. 3. 4. 5. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated stationary pipes, NPS 1/2 to NPS 30. Adjustable Swivel Split- or Solid-Ring Hangers (MSS Type 6): For suspension of noninsulated stationary pipes, NPS 3/4 to NPS 8. Adjustable, Steel Band Hangers (MSS Type 7): For suspension of noninsulated stationary pipes, NPS 1/2 to NPS 8. Adjustable Swivel-Ring Band Hangers (MSS Type 10): For suspension of noninsulated stationary pipes, NPS 1/2 to NPS 2. U-Bolts (MSS Type 24): For support of heavy pipes, NPS 1/2 to NPS 30. Lewiston Library Second Floor Remodel Project 15060-3 15025 6. 7. 8. 9. 10. H. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. 2. 3. I. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers, NPS 3/4 to NPS 20. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers, NPS 3/4 to NPS 20, if longer ends are required for riser clamps. For vertical mid-span supports of piping 4” and under, use Hubbard Enterprises/HOLDRITE Stout Brackets™ with Hubbard Enterprises/Holdrite Stout Clamps or equal, or two hole pipe clamps (MSS Type 26). Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. 2. J. Pipe Stanchion Saddles (MSS Type 37): For support of pipes, NPS 4 to NPS 36, with steel pipe base stanchion support and cast-iron floor flange and with U-bolt to retain pipe. Single Pipe Rolls (MSS Type 41): For suspension of pipes, NPS 1 to NPS 30, from 2 rods if longitudinal movement caused by expansion and contraction might occur. Adjustable Roller Hangers (MSS Type 43): For suspension of pipes, NPS 2-1/2 to NPS 20, from single rod if horizontal movement caused by expansion and contraction might occur. Complete Pipe Rolls (MSS Type 44): For support of pipes, NPS 2 to NPS 42, if longitudinal movement caused by expansion and contraction might occur but vertical adjustment is not necessary. Adjustable Pipe Roll and Base Units (MSS Type 46): For support of pipes, NPS 2 to NPS 30, if vertical and lateral adjustment during installation might be required in addition to expansion and contraction. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads. Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations. Building Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. 2. 3. 4. 5. 6. 7. 8. 9. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling. Top-Beam C-Clamps (MSS Type 19): For use under roof installations with barjoist construction to attach to top flange of structural shape. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams, channels, or angles. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads are considerable and rod sizes are large. C-Clamps (MSS Type 23): For structural shapes. Top-Beam Clamps (MSS Type 25): For top of beams if hanger rod is required tangent to flange edge. Side-Beam Clamps (MSS Type 27): For bottom of steel I-beams. Welded-Steel Brackets: For support of pipes from below, or for suspending from above by using clip and rod. Use one of the following for indicated loads: a. Light (MSS Type 31): 750 lb. Lewiston Library Second Floor Remodel Project 15060-4 15025 10. 11. K. Saddles and Shields: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. 2. 3. L. Support and positioning of piping shall be by means of engineered methods that comply with IAPMO PS 42-96. Hubbard Enterprises/HOLDRITE support systems or equal. Use pipe supports that meet ASTM E-84 25/50 standards. Hubbard Enterprises/HOLDRITE Flame Fighter TM or equal. Suspended Water Heaters and similar equipment 1. 3.02 For equipping Type 41 roll Plenum Installations 1. O. Spring-Cushion Roll Hangers (MSS Type 49): hanger with springs. Secondary Pipe Positioning and Supports: 1. N. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation. Thermal-Hanger Shield Inserts: For supporting insulated pipe. Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. M. b. Medium (MSS Type 32): 1500 lb. c. Heavy (MSS Type 33): 3000 lb. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams. Overhead pipe runs of 1” and less to utilize Hubbard Enterprises/HOLDRITE #125, #125-L or #121 Series or equal brackets. Utilize an engineered and manufactured platform for suspended applications of water heaters and similar equipment. Hubbard Enterprises/HOLDRITE Suspended Water Heater Platform or equal.. Weight loading capability shall include a minimum safety factor of 2. HANGER AND SUPPORT INSTALLATION A. Pipe Hanger and Support Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers, supports, clamps, and attachments as required to properly support piping from building structure. B. Support of pipe, tubing and equipment shall be accomplished by means of engineered products, specific to each application. Field devised methods shall not be allowed. C. Install mechanical-anchor fasteners in concrete after concrete is placed and completely cured. Install fasteners according to manufacturers written instructions. D. Install hangers and supports complete with necessary inserts, bolts, rods, nuts, washers, and other accessories. E. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units. Lewiston Library Second Floor Remodel Project 15060-5 15025 F. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment. G. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so maximum pipe deflections allowed by ASME B31.9, “Building Services Piping,” is not exceeded. H. Pipe Stand Installation: 1. 2. I. Insulated Piping: Comply with the following: 1. 2. 3. 4. 5. 6. 7. 3.03 Pipe Stand Types except Curb-Mounting Type: Assemble components and mount on smooth roof surface. Do not penetrate roof membrane. Curb-Mounting-Type Pipe Stands: Assemble components or fabricate pipe stand and mount on permanent, stationary roof curb. Refer to Division 7 Section "Roof Accessories" for curbs. Attach clamps and spacers to piping. a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation. b. Piping Operating below Ambient Air Temperature: Use thermal-hanger shield insert with clamp sized to match OD of insert. c. Do not exceed pipe stress limits according to ASME B31.1 for power piping and ASME B31.9 for building services piping. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation. a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees. a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. Shield Dimensions for Pipe: Not less than the following: a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick. b. NPS 4: 12 inches long and 0.06 inch thick. c. NPS 5 and NPS 6: 18 inches long and 0.06 inch thick. d. NPS 8 to NPS 14: 24 inches long and 0.075 inch thick. e. NPS 16 to NPS 24: 24 inches long and 0.105 inch thick. Pipes NPS 8 and Larger: Include wood inserts. Insert Material: Length at least as long as protective shield. Thermal-Hanger Shields: Install with insulation same thickness as piping insulation. EQUIPMENT SUPPORTS A. Engineered, factory-fabricated, galvanized steel supports shall be used when suspending equipment from overhead structures or when supporting equipment above the floor. 1. Suspended water heater installations shall include a drain pan with minimum 21/2” high sidewalls and a minimum ¾” drain connection. Lewiston Library Second Floor Remodel Project 15060-6 15025 2. 3. 4. 3.04 B. Grouting: Place grout under supports for equipment and make smooth bearing surface. C. Provide lateral bracing, to prevent swaying, for equipment supports. METAL FABRICATIONS A. Cut, drill, and fit miscellaneous metal fabrications for heavy-duty steel trapezes and equipment supports. B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations. C. Field Welding: Comply with AWS D1.1 procedures for shielded metal arc welding, appearance and quality of welds, and methods used in correcting welding work, and with the following: 1. 2. 3. 4. 3.05 3.06 Water heaters of 50 gallons or less, suspended from the structure above, shall be installed with an engineered and manufactured product. Hubbard Enterprises/HOLDRITE Suspended Water Heater Platform with integral drain body or equal. Water heaters placed on a stand, to elevate them above the floor, shall be installed using a manufactured galvanized steel stand, engineered to meet the intended weight load. Hubbard Enterprises/HOLDRITE QuickStand series or equal. Water heaters installed in seismic zones shall be supported from the adjoining structure by the use of DSA approved safety restrain devices. Hubbard Enterprises/HOLDRITE QuickStrap or equal. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals. Obtain fusion without undercut or overlap. Remove welding flux immediately. Finish welds at exposed connections so no roughness shows after finishing and contours of welded surfaces match adjacent contours. ADJUSTING A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe. B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches. PAINTING A. Touching Up: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint. END OF SECTION 15060 Lewiston Library Second Floor Remodel Project 15060-7 15025 SECTION 15071 - MECHANICAL VIBRATION AND SEISMIC CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. B. Related Sections include the following: 1. 2. 3. 4. 1.02 SUMMARY A. This Section includes the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 1.03 Division 15 Section “Hydronic Piping” for flexible pump connectors and hose kits. Division 15 Section “Pipe Expansion Fittings and Loops” for metal bellows expansion joints. Division 15 Section “General Service Compressed Air Piping” for flexible connectors. Division 15 Section “Duct Accessories” for flexible connectors. Elastomeric isolation pads and mounts. Restrained elastomeric isolation mounts. Freestanding and restrained spring isolators. Housed spring mounts. Elastomeric hangers. Spring hangers. Thrust limits. Restrained vibration isolation roof-curb rails. Seismic snubbers. Restraining cables. Steel and inertia, vibration isolation equipment bases. PERFORMANCE REQUIREMENTS A. Equipment Seismic Restraints shall be designed in accordance with Section 16 of the International Building Code - 2009 (IBC). B. Seismic Design Category: “C” C. Mechanical Component Importance Factor: 1.0, 1.5 for gas piping systems and connected equipment. D. Selection and installation of seismic restraint devices shall be in accordance with the most recent edition of the IBC and ASCE-7 (American Society of Civil Engineers), “Minimum Design Loads for Buildings and Other Structures”. Lewiston Library Second Floor Remodel Project 15071-1 15025 1.04 SUBMITTALS A. Product Data: For the following: 1. 2. B. Delegated-Design Submittal: For vibration isolation and seismic-restraint details indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified Professional Engineer responsible for their preparation. 1. 2. 3. C. 1.05 Include rated load, rated deflection, and overload capacity for each vibration isolation device. Illustrate and indicate style, material, strength, fastening provision, and finish for each type and size of seismic-restraint component used. a. Tabulate types and sizes of seismic restraints, complete with report numbers and rated strength in tension and shear. b. Annotate to indicate application of each product submitted and compliance with requirements. Design Calculations: Calculate static and dynamic loading due to equipment weight and operation, seismic forces required to select vibration isolators, seismic restraints, and for designing vibration isolation bases. Vibration Isolation Base Details: Detail overall dimensions, including anchorages and attachments to structure and to supported equipment. Include base weights, equipment static loads, and cantilever loads. Seismic-Restraint Details: a. Design Analysis: To support selection and arrangement of seismic restraints. Include calculations of combined tensile and shear loads. b. Details: Indicate fabrication and arrangement. Detail attachments of restraints to the restrained items and to the structure. Show attachment locations, methods, and spacing. Identify components, list their strengths, and indicate directions and values of forces transmitted to the structure during seismic events. Indicate association with vibration isolation devices. c. Preapproval and Evaluation Documentation: By an agency acceptable to authorities having jurisdiction, showing maximum ratings of restraint items and the basis for approval (tests or calculations). Qualification Data: For Professional Engineer COORDINATION A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into base. B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. Lewiston Library Second Floor Remodel Project 15071-2 15025 PART 2 - PRODUCTS 2.01 VIBRATION ISOLATION SCHEDULE A. Provide the following vibration isolators and bases for mechanical equipment and systems: 1. 2. 3. 4. 5. 6. 7. Equipment: Rooftop Chiller a. Base: Steel support base, Type B. Unit integral support base acceptable in lieu of Type B base if certified by manufacturer for isolator point loading. b. Isolators: Housed spring isolators with integral seismic snubbers, Type 4. c. Minimum Deflection (in.): 2-inch. Equipment: Base-mounted Hydronic Pumps a. Base: Concrete-filled inertia base, Type C. Anchor bolt and grout support base solid to concrete pad. b. Isolators: Spring isolators with integral seismic restraint, Type 3R. c. Minimum Deflection (in.): 2-inch. Equipment: Base-mounted Hydronic Pumps a. Base: Unit integral support base. Anchor bolt and grout support base solid to concrete pad. b. Isolators: None. c. Minimum Deflection (in.): n/a. Equipment: In-line Pumps a. Base: Unit integral hanger supports or field-installed hanger supports. b. Isolators: Hangers with elastomeric isolators, Type 2. c. Minimum Deflection (in.): 0.35-inch. d. Equipment: Rooftop HVAC Units e. Base: Steel support base, Type B. Unit integral support base acceptable in lieu of Type B base if certified by manufacturer for isolator point loading. f. Isolators: Housed spring isolators with integral seismic snubbers, Type 4. g. Minimum Deflection (in.): 2-inch. Equipment: Air-Handling Units with Internal Fan Isolation (floor-mounted) a. Base: None required. Unit integral support base acceptable. b. Isolators: Isolation pads, Type 1. c. Minimum Deflection (in.): 0.25-inch. Equipment: Indoor Air-Handling Units (suspended) a. Base: Steel support base, Type B. Unit integral support base acceptable in lieu of Type B base if certified by manufacturer for isolator point loading. b. Isolators: Hangers with spring isolators, Type 3. c. Minimum Deflection (in.): 1.0-inch. Equipment: Indoor Air-Handling Units without Internal Fan Isolation (floormounted) a. Base: Steel support base, Type B. Unit integral support base acceptable in lieu of Type B base if certified by manufacturer for isolator point loading. b. Isolators: Restrained spring isolator, Type 3R. c. Minimum Deflection (in.): 2.0-inch. Lewiston Library Second Floor Remodel Project 15071-3 15025 8. 9. 10. 11. 12. 2.02 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. 2.03 Equipment: Fan-Coil Units; Fan-Powered, VAV Terminal Units, In-line Exhaust Fans; Unit Heaters, up to 1500 CFM a. Base: Unit integral hanger supports or field-installed hanger supports. b. Isolators: Hangers with elastomeric isolators, Type 2. c. Minimum Deflection (in.): 0.35-inch. Equipment: Fan-Coil Units; Fan-Powered, VAV Terminal Units, In-line Exhaust Fans; Unit Heaters, over 1500 CFM a. Base: Unit integral hanger supports or field-installed hanger supports. b. Isolators: Hangers with spring isolators, Type 3. c. Minimum Deflection (in.): 0.5-inch. Equipment: Air-Cooled Condensing Unit a. Base: Unit integral support base. b. Isolators: Isolation pads, Type 1. c. Minimum Deflection (in.): 0.25-inch. Equipment: Packaged Air Compressors a. Base: None required. Unit integral support base acceptable. b. Isolators: Isolation pads, Type 1. c. Minimum Deflection (in.): 0.25-inch. Equipment: Water Heaters; Tanks, and similar equipment 400 lbs. and greater. a. Isolators: None. b. Minimum Deflection (in.): n/a. c. Seismic Restraints: Anchor bolt to structure if furnished with anchoring provisions, otherwise strap to structure at points within the upper onethird and lower one-third of its vertical dimension to resist lateral displacement. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers listed. VIBRATION ISOLATORS A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. B. Amber/Booth Company, Inc. Kinetics Noise Control, Inc. Mason Industries, Inc. MW Sausse. Vibro-Acoustics. Vibration Eliminator Co., Inc. Vibration Mountings & Controls/Korfund. Elastomeric Isolator Pads (Isolator Type 1): Oil- and water-resistant elastomer; crossed, double ribbed pads, molded with a nonslip pattern; and factory cut to sizes that match requirements of supported equipment. 1. 2. 3. 4. Material: Standard neoprene. Thickness: 3/8-inch minimum. Maximum Deflection: 0.09-inches. Durometer Rating: 45 to 65. Lewiston Library Second Floor Remodel Project 15071-4 15025 5. C. Elastomeric Mounts (Isolator Type 2: Double-deflection type, with molded, oil-resistant rubber or neoprene isolator elements with factory-drilled, encapsulated top plate for bolting to equipment and with baseplate for bolting to structure. Color-code or otherwise identify to indicate capacity range. 1. D. 2. 2. 3. 4. 5. 6. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. Minimum Additional Travel: 50 percent of the required deflection at rated load. Lateral Stiffness: More than 80 percent of the rated vertical stiffness. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. Baseplates: Factory drilled for bolting to structure and bonded to 1/4-inch- thick, rubber isolator pad attached to baseplate underside. Baseplates shall limit floor load to 100 psig. Top Plate and Adjustment Bolt: Threaded top plate with adjustment bolt and cap screw to fasten and level equipment. Restrained Spring Isolators (Isolator Type 3R): Freestanding, steel, open-spring isolators with seismic restraint. 1. 2. 3. 4. 5. G. Materials: Cast-ductile-iron housing containing two separate and opposing, molded, bridge-bearing neoprene elements that prevent central threaded sleeve and attachment bolt from contacting the casting during normal operation. Neoprene: Shock-absorbing materials compounded according to the standard for bridge-bearing neoprene as defined by AASHTO. Spring Isolators (Isolator Type 3): Freestanding, laterally stable, open-spring isolators. 1. F. Durometer Rating: 50 Maximum. Restrained Elastomeric Mounts (Isolator Type 2R): All-directional elastomeric mountings with seismic restraint. 1. E. Number of Layers: 1 unless otherwise noted. Housing: Steel with resilient vertical-limit stops to prevent spring extension due to wind loads or if weight is removed; factory-drilled baseplate bonded to 1/4inch- thick, elastomeric isolator pad attached to baseplate underside; and adjustable equipment mounting and leveling bolt that acts as blocking during installation. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. Minimum Additional Travel: 50 percent of the required deflection at rated load. Lateral Stiffness: More than 80 percent of the rated vertical stiffness. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. Housed Spring Mounts (Isolator Type 4): Housed spring isolator with integral seismic snubbers. 1. 2. 3. Housing: Ductile-iron or steel housing to provide all-directional seismic restraint. Base: Factory drilled for bolting to structure. Snubbers: Vertically adjustable to allow a maximum of 1/4-inch travel before contacting a resilient collar. Lewiston Library Second Floor Remodel Project 15071-5 15025 H. Elastomeric Hangers (Isolator Type 2): Double-deflection type, with molded, oilresistant rubber or neoprene isolator elements bonded to steel housings with threaded connections for hanger rods. Color-code or otherwise identify to indicate capacity range. I. Spring Hangers (Isolator Type 3): Combination coil-spring and elastomeric-insert hanger with spring and insert in compression. 1. 2. 3. 4. 5. 6. J. Thrust Limits (Isolator Type 5): Combination coil spring and elastomeric insert with spring and insert in compression and with a load stop. Include rod and angle-iron brackets for attaching to equipment. 1. 2. 3. 4. 5. 6. 7. 2.04 Frame: Steel, fabricated for connection to threaded hanger rods and to allow for a maximum of 30 degrees of angular hanger-rod misalignment without binding or reducing isolation efficiency. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. Minimum Additional Travel: 50 percent of the required deflection at rated load. Lateral Stiffness: More than 80 percent of the rated vertical stiffness. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. Elastomeric Element: Molded, oil-resistant rubber or neoprene. Steel-washerreinforced cup to support spring and bushing projecting through bottom of frame. Frame: Steel, fabricated for connection to threaded rods and to allow for a maximum of 30 degrees of angular rod misalignment without binding or reducing isolation efficiency. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. Minimum Additional Travel: 50 percent of the required deflection at rated load. Lateral Stiffness: More than 80 percent of the rated vertical stiffness. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. Elastomeric Element: Molded, oil-resistant rubber or neoprene. Coil Spring: Factory set and field adjustable for a maximum of 1/4-inch movement at start and stop. RESTRAINED VIBRATION ISOLATION ROOF-CURB RAILS (Base Type D with 3R Isolators) A. Manufacturers: 1. 2. 3. 4. 5. B. Amber/Booth Company, Inc. Kinetics Noise Control, Inc. Mason Industries, Inc. Vibration Eliminator Co., Inc. Vibration Mountings & Controls/Korfund. Description: Factory-assembled, fully enclosed, insulated, air- and watertight curb rail designed to resiliently support equipment and to withstand 125-mph wind impinging laterally against side of equipment. Lewiston Library Second Floor Remodel Project 15071-6 15025 C. Lower Support Assembly: Sheet-metal "Z" section containing adjustable and removable steel springs that support upper floating frame. Upper frame shall provide continuous support for equipment and shall be captive to resiliently resist wind and seismic forces. Lower support assembly shall have a means for attaching to building structure and a wood nailer for attaching roof materials, and shall be insulated with a minimum of 2 inches of rigid, glass-fiber insulation on inside of assembly. D. Spring Isolators: Adjustable, restrained spring isolators shall be mounted on 1/4-inchthick, elastomeric vibration isolation pads and shall have access ports, for level adjustment, with removable waterproof covers at all isolator locations. Isolators shall be located so they are accessible for adjustment at any time during the life of the installation without interfering with the integrity of the roof. 1. 2. 2.05 Restrained Spring Isolators: Freestanding, steel, open-spring isolators with seismic restraint. a. Housing: Steel with resilient vertical-limit stops and adjustable equipment mounting and leveling bolt. b. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. c. Minimum Additional Travel: 50 percent of the required deflection at rated load. d. Lateral Stiffness: More than 80 percent of the rated vertical stiffness. e. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. Elastomeric Isolator Pads: Oil- and water-resistant elastomer or natural rubber, arranged in single or multiple layers, molded with a nonslip pattern and galvanized steel baseplates of sufficient stiffness for uniform loading over pad area, and factory cut to sizes that match requirements of supported equipment. a. Material: Standard neoprene b. Durometer Rating: 50 Maximum. c. Number of Layers: 1 E. Snubber Bushings: All-directional, elastomeric snubber bushings at least 1/4 inch thick. F. Water Seal: Galvanized sheet metal with EPDM seals at corners, attached to upper support frame, extending down past wood nailer of lower support assembly, and counterflashed over roof materials. VIBRATION ISOLATION EQUIPMENT BASES A. Steel Base (Base Type B): Factory-fabricated, welded, structural-steel bases and rails. 1. 2. 3. Design Requirements: Lowest possible mounting height with not less than 1inch clearance above the floor. Include equipment anchor bolts and auxiliary motor slide bases or rails. Include supports for suction and discharge elbows for pumps. Structural Steel: Steel shapes, plates, and bars complying with ASTM A 36/A 36M. Bases shall have shape to accommodate supported equipment. Support Brackets: Factory-welded steel angles on frame for outrigger isolation mountings and to provide for anchor bolts and equipment support. Lewiston Library Second Floor Remodel Project 15071-7 15025 B. Inertia Base (Base Type C): Factory-fabricated, welded, structural-steel bases and rails ready for field-applied, cast-in-place concrete. 1. 2. 3. 4. 2.06 Design Requirements: Lowest possible mounting height with not less than 1inch clearance above the floor. Include equipment anchor bolts and auxiliary motor slide bases or rails. Include supports for suction and discharge elbows for pumps. Structural Steel: Steel shapes, plates, and bars complying with ASTM A 36/A 36M. Bases shall have shape to accommodate supported equipment. Support Brackets: Factory-welded steel angles on frame for outrigger isolation mountings and to provide for anchor bolts and equipment support. Fabrication: Fabricate steel templates to hold equipment anchor-bolt sleeves and anchors in place during placement of concrete. Obtain anchor-bolt templates from supported equipment manufacturer. SEISMIC-RESTRAINT DEVICES A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. 9. Amber/Booth Company, Inc. Kinetics Noise Control, Inc. Loos & Co., Inc.; Cableware Technology Division. Mason Industries, Inc. TOLCO Incorporated. Unistrut Diversified Products Co.; Wayne Manufacturing Division. Vibro-Acoustics. Vibration Eliminator Co., Inc. Vibration Mountings & Controls/Korfund. B. Resilient Isolation Washers and Bushings: 1-piece, molded, bridge-bearing neoprene complying with AASHTO M 251 and having a durometer of 50, plus or minus 5, with a flat washer face. C. Seismic Snubbers (Restraint Type R): Factory fabricated using welded structural-steel shapes and plates, anchor bolts, and replaceable resilient isolation washers and bushings. 1. 2. Anchor bolts for attaching to concrete shall be seismic-rated, drill-in, and studwedge or female-wedge type. Resilient Isolation Washers and Bushings: 1-piece, molded, bridge-bearing neoprene complying with AASHTO M 251 and having a durometer of 50, plus or minus 5. D. Restraining Cables (Restraint Type C): Galvanized steel aircraft cables with end connections made of steel assemblies that swivel to final installation angle and utilize two clamping bolts for cable engagement. E. Anchor Bolts (Restraint Type C): Seismic-rated, drill-in. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488/E 488M. Lewiston Library Second Floor Remodel Project 15071-8 15025 2.07 FACTORY FINISHES A. Finish: Manufacturer's standard paint applied to factory-assembled and tested equipment before shipping. 1. 2. 3. 4. Powder coating on springs and housings. All hardware shall be electrogalvanized. Hot-dip galvanize metal components for exterior use. Baked enamel for metal components on isolators for interior use. Color-code or otherwise mark vibration isolation and seismic-control devices to indicate capacity range. PART 3 - EXECUTION 3.01 3.02 EXAMINATION A. Examine areas and equipment to receive vibration isolation and seismic-control devices for compliance with requirements, installation tolerances, and other conditions affecting performance. B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. INSTALLATION A. 3.03 EQUIPMENT BASES A. 3.04 Install vibration-isolation and seismic-restraint devices using methods approved by an evaluation service member of ICC-ES providing required submittals for components. Fill concrete inertia bases, after installing base frame, with 3000-psi concrete; trowel to a smooth finish. DUCT AND PIPE PENETRATION METHODS A. Isolate all ductwork and piping at walls and ceiling penetrations of mechanical rooms as follows: 1. 2. 3. 4. 5. Provide a sheet metal (22 gauge) sleeve to cover the entire perimeter of a 1 inch to 1-1/2 inch (1/2 inch to 3/4 inch on each side) oversized penetration cut. Plaster or caulk sleeve to the wall, ceiling, or floor, to ensure an airtight seal. If ductwork or piping penetrates a double wall, use a separate sleeve at each side of the wall (allow no sleeve connection between walls). Pack the gap between the penetrating duct or pipe and the sleeve with acoustical insulation and seal airtight on both sides of the wall, floor, or ceiling with an outer layer of acoustical sealant. Do not use wall, floor, or ceiling penetrations to support ductwork or piping. Support pipe or duct just prior to and just after the penetration, so that the pipe or duct is centered in penetration Lewiston Library Second Floor Remodel Project 15071-9 15025 B. 3.05 3.06 Use the above penetration treatment regardless of the existence of external duct or pipe insulation. Size penetration large enough to pack additional acoustical insulation and apply acoustical sealant between the external insulation and the sheet metal sleeve. ADJUSTING A. Adjust isolators after piping systems have been filled and equipment is at operating weight. B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating height. After equipment installation is complete, adjust limit stops so they are out of contact during normal operation. C. Attach thrust limits at centerline of thrust and adjust to a maximum of 1/4-inch movement during start and stop. D. Adjust active height of spring isolators. E. Adjust snubbers according to manufacturer's written recommendations. F. Adjust seismic restraints to permit free movement of equipment within normal mode of operation. G. Torque anchor bolts according to equipment manufacturer's written recommendations to resist seismic forces. CLEANING A. After completing equipment installation, inspect vibration isolation and seismic-control devices. Remove paint splatters and other spots, dirt, and debris. END OF SECTION 15071 Lewiston Library Second Floor Remodel Project 15071-10 15025 SECTION 15075 – MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This section includes the following mechanical identification materials and their installation: 1. 2. 3. 4. 5. 6. 7. 8. 1.03 1.04 SUBMITTALS A. Product Data: For each type of product indicated. B. Samples: For color, letter style, and graphic representation required for each identification material and device. C. Valve numbering scheme. D. Valve Schedules: For each piping system. Furnish extra copies (in addition to mounted copies) to include in maintenance manuals. QUALITY ASSURANCE A. 1.05 Equipment markers. Access panel and door markers. Pipe markers. Duct markers. Valve tags. Valve schedules. Ceiling tack markers. Ceiling grid markers. ASME Compliance: Comply with ASME A13.1, “Scheme for the Identification of Piping Systems,” for letter size, length of color field, colors, and viewing angles of identification devices for piping. COORDINATION A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. B. Coordinate installation of identifying devices with location of access panels and doors. C. Install identifying devices before installing acoustical ceilings and similar concealment. PART 2 - PRODUCTS 2.01 EQUIPMENT IDENTIFICATION DEVICES A. Equipment Markers: Engraved, color-coded laminated plastic. Include contact-type, permanent adhesive. 1. 2. Terminology: Match schedules as closely as possible. Data: a. Name and Plan number. b. Equipment service. Lewiston Library Second Floor Remodel Project 15075-1 15025 3. B. Access Panel and Door Markers: 1/16-inch thick, engraved laminated plastic, with abbreviated terms and numbers corresponding to identification. Provide two, 1/8-inch holes for attachment. 1. 2.02 3. 4. 5. Colors: Comply with ASME A13.1, unless otherwise indicated. Lettering: Use piping system terms indicated and abbreviate only as necessary for each application length. Pipes with OD, Including Insulation, Less Than 6 Inches: Either full-band pipe markers extending 360 degrees around pipe at each location or strip-type pipe markers. Pipes with OD, Including Insulation, 6 Inches or Larger: Either full-band or strip-type pipe markers at least three times letter height and of length required for label. Arrows: Integral with piping system service lettering to accommodate both directions; or as separate unit on each pipe marker to indicate direction of flow. B. Pretensioned Pipe Markers: Precoiled semi rigid plastic formed to cover full circumference of pipe and to attach to pipe without adhesive. C. Self-Adhesive Pipe Markers: adhesive back. Plastic with pressure-sensitive, permanent-type, self- DUCT IDENTIFICATION DEVICES A. Duct Markers: Engraved, color-coded laminated plastic. Include direction and quantity of airflow and duct service (such as supply, return, and exhaust). Include contact-type, permanent adhesive. VALVE TAGS A. Valve Tags: Stamped or engraved with ¼-inch letters for piping system abbreviation and ½-inch numbers, with approved numbering scheme. Provide 5/32-inch hole for fastener. 1. 2. 3. 4. 2.05 Self-tapping, stainless-steel screws or contact-type, permanent Manufactured Pipe Markers, General: Preprinted, color-coded, with lettering indicating service, and showing direction of flow. 1. 2. 2.04 Fasteners: adhesive. PIPING IDENTIFICATION DEVICES A. 2.03 Size: 2-1/2 by 4 inches for equipment. Material: 0.032-inch –thick brass. Material: 3/32-inch-thick laminated plastic with 2 black surfaces and white inner layer. Valve-Tag Fasteners: Brass wire-link or beaded chain. Size: 1-1/2 inch diameter (minimum). VALVE SCHEDULES A. Valve Schedules: For each piping system, on standard-size bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses. 1. Valve-Schedule Frames: Glazed display frame for removable mounting on masonry walls for each page of valve schedule. Include mounting screws. Lewiston Library Second Floor Remodel Project 15075-2 15025 2. 3. 2.06 CEILING TACK MARKERS A. 2.07 Frame: Extruded aluminum Glazing: Single-thickness glass. Description: Steel with ¾-inch diameter color coded head. CEILING GRID MARKERS A. Description: ¾-inch diameter, removable labels. PART 3 - EXECUTION 3.01 GENERAL A. 3.02 All identification shall use the room numbers assigned by the Owner. Obtain a list of room numbers from the Owner’s Representative prior to preparing identification. EQUIPMENT IDENTIFICATION A. Install equipment markers with permanent adhesive on or near each major item of mechanical equipment. 1. 2. B. 3.03 Letter Size: Minimum ½ inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Locate markers where accessible and visible. Include markers for the following general categories of equipment. a. Meters, and similar units. b. Fuel-burning units, including boilers, furnaces, heaters. c. Pumps, compressors, chillers, condensers, and similar motor-driven units. d. Heat exchangers, coils, evaporators, cooling towers, heat recovery units, and similar equipment. e. Fans, blowers, mixing boxes, and terminal units. f. Packaged HVAC central-station and zone-type units. g. Tanks and pressure vessels. h. Water-treatment systems, and similar equipment. Install access panel markers with screws on equipment access panels. PIPING IDENTIFICATION A. Install manufactured pipe markers indicating service on each piping system. Install with flow indication arrows showing direction of flow. 1. 2. 3. Pipes with OD, Including Insulation, Less Than 6 Inches: Pre-tensioned pipe markers. Use size to ensure a tight fit. Pipes with OD, Including Insulation, Less Than 6 Inches: Self-adhesive pipe markers. Use color-coded, self-adhesive plastic tape, at least ¾ inch wide, lapped at least 1-1/2 inches at both ends of pipe marker, and covering full circumference of pipe for strip-type pipe markers. Pipes with OD, Including Insulation, 6 Inches and Larger: Self-adhesive pipe markers. Use color-coded, self-adhesive plastic tape, at least 1-1/2 inches wide, lapped at least 3 inches at both ends of pipe marker and covering full circumference of pipe. Lewiston Library Second Floor Remodel Project 15075-3 15025 B. Locate pipe markers and color bands where piping is exposed in finished spaces; mechanical rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior non-concealed locations as follows: 1. 2. 3. 4. 5. 6. 7. C. 3.04 Non-potable water: Piping shall be designated with colored bands (Purple or as specified by the authority having jurisdiction), and solid color continuous label "NON-POTABLERAINWATER," with adhesive bands wrapping the entire circumference every 5 feet. DUCT IDENTIFICATON A. Install duct markers with permanent adhesive on air ducts in the following color codes: 1. 2. 3. 4. B. 3.05 Letter size: Minimum ½ inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Locate markers near points where ducts enter into concealed spaces and at maximum intervals of 50 feet in each space where ducts are exposed or concealed by removable ceiling system. Install tags on valves and control devices in piping systems, except check valves; valves within factory-fabricated equipment units; plumbing fixture supply stops; shutoff valves; faucets; convenience and lawn-watering hose connections; and HVAC terminal devices and similar roughing-in connections of end-use fixtures and units. List tagged valves in a valve schedule. VALVE-SCHEDULE INSTALLATION A. 3.07 Green: For cold-air supply ducts. Yellow: For hot-air supply ducts. Blue: For exhaust-, outside-, relief-, and mixed-air ducts. ASME A13.1 colors and Designs: For hazardous material exhaust. VALVE-TAG INSTALLATION A. 3.06 Near each valve and control device. Near each branch connection, excluding sort takeoffs for fixtures and terminal units. Where flow pattern is not obvious, mark each pipe at branch. Near penetrations through walls, floors, ceilings, and nonaccessible enclosures. At access doors, manholes, and similar access points that permit view of concealed piping. Near major equipment items and other points of origination and termination. Spaced at maximum intervals of 25 feet along each run. Reduce intervals in areas of congested piping and equipment. Piping above removable acoustical ceilings. Mount valve schedule on wall in accessible location in each major equipment room. CEILING TACK MARKERS A. Install ceiling tack markers directly below the location of equipment to be identified. Coordinate with Owner’s maintenance staff. B. Install ceiling tack markers at all locations of the following equipment and valves above accessible ceilings: 1. 2. 3. 4. HVAC equipment with filters: Yellow Fire dampers/smoke dampers: Red Plumbing valves: Green Heating/cooling valves: Blue Lewiston Library Second Floor Remodel Project 15075-4 15025 3.08 CEILING GRID MARKERS A. Install ceiling grid markers directly below the location of equipment and valves to be identified. Coordinate with Owner’s maintenance staff. B. Install ceiling grid markers at all locations of the following equipment and valves above accessible ceilings: 1. 2. 3. 4. 3.09 ADJUSTING A. 3.10 HVAC equipment with filters: Yellow Fire dampers/smoke dampers: Red Plumbing valves: Green Heating/cooling valves: Blue Relocate mechanical identification materials and devices that have become visually blocked by other work. CLEANING A. Clean faces of mechanical identification devices and glass frames of valve schedules. END OF SECTION 15075 Lewiston Library Second Floor Remodel Project 15075-5 15025 SECTION 15080 - MECHANICAL INSULATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes mechanical insulation systems for ductwork, , equipment, and piping. B. Related Sections include the following: 1. 1.03 1.04 1.05 Division 15 Section "Metal Ducts" for duct liners. DEFINITIONS A. ASJ: All-service jacket. B. FSK: Foil, scrim, kraft paper. C. PVC: Polyvinyl chloride. D. SSL: Self-sealing lap. E. Conditioned Space: A cooled, heated, or indirectly conditioned space within the insulated building envelope. F. Unconditioned Space: A space that is not a Conditioned Space. SUBMITTALS A. Product Data: For each type of product indicated, identify thermal conductivity, thickness, and jackets (both factory and field applied, if any). B. For adhesives, sealants and mastics: Documentation including printed statement of VOC content. QUALITY ASSURANCE A. Fire-Test-Response Characteristics: Insulation and related materials shall have fire-testresponse characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, and cement material containers, with appropriate markings of applicable testing and inspecting agency. 1. Insulation Installed Indoors: Flame-spread index of 25 or less, and smokedeveloped index of 50 or less. Lewiston Library Second Floor Remodel Project 15080-1 15025 2. 1.06 DELIVERY, STORAGE, AND HANDLING A. 1.07 1.08 Insulation Installed Outdoors: Flame-spread index of 75 or less, and smokedeveloped index of 150 or less. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature. COORDINATION A. Coordinate size and location of supports, hangers, and insulation shields specified in Division 15 Section "Hangers and Supports." B. Coordinate clearance requirements with piping Installer for piping insulation application, duct Installer for duct insulation application, and equipment Installer for equipment insulation application. SCHEDULING A. Schedule insulation application after pressure testing systems. Insulation application may begin on segments that have satisfactory test results. B. Complete installation and concealment of plastic materials as rapidly as possible in each area of construction. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. 2.02 Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. INSULATION MATERIALS A. Refer to Part 3 schedule articles for requirements about where insulating materials shall be applied. B. Products shall not contain asbestos, lead, mercury, or mercury compounds. C. Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm when tested according to ASTM C 871. D. Insulation materials for use on austenitic stainless steel shall be qualified as acceptable according to ASTM C 795. E. Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process. Lewiston Library Second Floor Remodel Project 15080-2 15025 F. Flexible Elastomeric: Closed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials. Thermal conductivity (k-value) not greater than 0.27 at 75 deg F mean temperature. 1. G. Mineral-Fiber Blanket Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 553, Type II and ASTM C 1290, Type III with factoryapplied FSK jacket. Factory-applied jacket requirements are specified in Part 2 "FactoryApplied Jackets" Article. 1. H. Products: a. CertainTeed Corp.; Duct Wrap. b. Johns Manville; Microlite. c. Knauf Insulation; Duct Wrap. d. Manson Insulation Inc.; Alley Wrap. e. Owens Corning; All-Service Duct Wrap. Mineral-Fiber Board Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 612, Type IA or Type IB. For duct and plenum applications, provide insulation with factory-applied FSK jacket. For equipment applications, provide insulation without jacket or with factory-applied ASJ. Factoryapplied jacket requirements are specified in Part 2 "Factory-Applied Jackets" Article. 1. I. Products: a. Aeroflex USA Inc. b. Armacell LLC c. K-Flex USA. Products: a. CertainTeed Corp.; Commercial Board. b. Fibrex Insulations Inc.; FBX. c. Johns Manville; 800 Series Spin-Glas. d. Knauf Insulation; Insulation Board. e. Manson Insulation Inc.; AK Board. f. Owens Corning; Fiberglas 700 Series. Mineral-Fiber, Preformed Pipe Insulation: 1. 2. Products: a. E-Insulation. b. Fibrex Insulations Inc.; Coreplus 1200. c. Johns Manville; Micro-Lok. d. Knauf Insulation; 1000 deg. Pipe Insulation. e. Manson Insulation Inc.; Alley-K. f. Owens Corning; Fiberglas Pipe Insulation. Type I, 850 deg F Materials: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 547, Type I, Grade A, with factory-applied ASJSSL. Thermal conductivity (k-value) not greater than 0.23 at 75 deg F mean temperature. Factory-applied jacket requirements are specified in Part 2 "Factory-Applied Jackets" Article. Lewiston Library Second Floor Remodel Project 15080-3 15025 J. Mineral-Fiber, Pipe and Tank Insulation: Mineral or glass fibers bonded with a thermosetting resin. Semirigid board material with factory-applied ASJ complying with ASTM C 1393, Type II or Type IIIA Category 2, or with properties similar to ASTM C 612, Type IB. Nominal density is 2.5 lb/cu. ft. or more. Thermal conductivity (k-value) not greater than 0.27 at 75 deg F mean temperature. Factory-applied jacket requirements are specified in Part 2 "Factory-Applied Jackets" Article. 1. 2.03 FIRE-RATED INSULATION SYSTEMS A. Fire-Rated Board: Structural-grade, press-molded, xonolite calcium silicate, fireproofing board suitable for operating temperatures up to 1700 deg F. Comply with ASTM C 656, Type II, Grade 6. UL tested and certified to provide a 2-hour fire rating. 1. B. 2.05 Products: a. Johns Manville; Super Firetemp M. Fire-Rated Blanket: High-temperature, flexible, blanket insulation with FSK jacket that is UL tested and certified to provide a 2-hour fire rating. 1. 2.04 Products: a. CertainTeed Corp.; CrimpWrap. b. Johns Manville; MicroFlex. c. Knauf Insulation; Pipe and Tank Insulation. d. Manson Insulation Inc.; AK Flex. e. Owens Corning; Fiberglas Pipe and Tank Insulation. Products: a. CertainTeed Corp.; FlameChek. b. Johns Manville; Firetemp Wrap. c. Nelson Firestop Products; Nelson FSB Flameshield Blanket. d. Thermal Ceramics; FireMaster Duct Wrap. e. 3M; Fire Barrier Wrap Products. f. Unifrax Corporation; FyreWrap. g. Vesuvius; PYROSCAT FP FASTR Duct Wrap. ADHESIVES A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated. B. VOC content of 100 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). MASTICS A. Materials shall be compatible with insulation materials, jackets, and substrates. B. VOC content of 100 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Lewiston Library Second Floor Remodel Project 15080-4 15025 C. Vapor-Barrier Mastic: ambient services. 1. 2. 3. 4. D. 2. 3. 4. Joint Sealants: 1. 2. 3. 4. B. Materials shall be compatible with insulation materials, jackets, and substrates. Fire and water resistant, flexible, elastomeric sealant. Service Temperature Range: Minus 40 to plus 250 deg F. Color: a. White for ASJ and PVC. b. Aluminum for FSK and metal jackets. VOC content of 100 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). FACTORY-APPLIED JACKETS A. Insulation system schedules indicate factory-applied jackets on various applications. When factory-applied jackets are indicated, comply with the following: 1. 2. 3. 2.08 Water-Vapor Permeance: ASTM F 1249, 3 perms at 0.0625-inch dry film thickness. Service Temperature Range: Minus 20 to plus 200 deg F. Solids Content: 63 percent by volume and 73 percent by weight. Color: White. SEALANTS A. 2.07 Water-Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm at 43-mil dry film thickness. Service Temperature Range: Minus 20 to plus 180 deg F. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight. Color: White. Breather Mastic: Water based; suitable for indoor and outdoor use on above ambient services. 1. 2.06 Water based; suitable for indoor and outdoor use on below ASJ: White, kraft-paper, fiberglass-reinforced scrim with aluminum-foil backing; complying with ASTM C 1136, Type I. ASJ-SSL: ASJ with self-sealing, pressure-sensitive, acrylic-based adhesive covered by a removable protective strip; complying with ASTM C 1136, Type I. FSK Jacket: Aluminum-foil, fiberglass-reinforced scrim with kraft-paper backing; complying with ASTM C 1136, Type II. FIELD-APPLIED JACKETS A. Field-applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated. B. FSK Jacket: Aluminum-foil-face, fiberglass-reinforced scrim with kraft-paper backing. C. PVC Jacket: High-impact-resistant, UV-resistant PVC complying with ASTM D 1784, Class 16354-C; 20 mils thick; roll stock ready for shop or field cutting and forming. 1. 2. Adhesive: As recommended by jacket material manufacturer. Color: White. Lewiston Library Second Floor Remodel Project 15080-5 15025 3. 4. D. Metal Jacket: 1. 2.09 2.10 Factory-fabricated fitting covers to match jacket if available; otherwise, field fabricate. a. Shapes: 45- and 90-degree, short- and long-radius elbows, tees, valves, flanges, unions, reducers, end caps, soil-pipe hubs, traps and mechanical joints. Factory-fabricated tank heads and tank side panels. Aluminum Jacket: Comply with ASTM B 209, Alloy 3003, Temper H-14; sheet and roll stock ready for shop or field sizing. a. Finish and thickness: Stucco embossed; .016-inch thick minimum. b. Moisture Barrier for Indoor Applications: 1-mil- thick, heat-bonded polyethylene and kraft paper. c. Moisture Barrier for Outdoor Applications: 3-mil- thick, heat-bonded polyethylene and kraft paper. d. Factory-Fabricated Fitting Covers: 1) Same material, finish, and thickness as jacket. 2) Field fabricate fitting covers only if factory-fabricated fitting covers are not available. TAPES A. ASJ Tape: White vapor-barrier tape matching factory-applied jacket with acrylic adhesive, complying with ASTM C 1136 and UL listed. B. FSK Tape: Foil-face, vapor-barrier tape matching factory-applied jacket with acrylic adhesive; complying with ASTM C 1136 and UL listed. C. PVC Tape: White vapor-barrier tape matching field-applied PVC jacket with acrylic adhesive. Suitable for indoor and outdoor applications. D. Aluminum-Foil Tape: Vapor-barrier tape with acrylic adhesive and UL listed. SECUREMENTS A. Insulation Pins and Hangers: 1. 2. 3. Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully annealed for capacitor-discharge welding, length to suit depth of insulation indicated, with self-locking speed washer. Cupped-Head, Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully annealed for capacitor-discharge welding, length to suit depth of insulation indicated with integral galvanized carbon-steel washer. Metal, Adhesively Attached, Perforated-Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements: a. Baseplate: Perforated, galvanized carbon-steel sheet, 0.030 inch thick by 2 inches square. b. Spindle: Copper- or zinc-coated, low carbon steel, fully annealed, 0.106inch- diameter shank, length to suit depth of insulation indicated. Lewiston Library Second Floor Remodel Project 15080-6 15025 c. 4. Adhesive: Recommended by hanger manufacturer. Product with demonstrated capability to bond insulation hanger securely to substrates indicated without damaging insulation, hangers, and substrates. Self-Sticking-Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements: a. Baseplate: Galvanized carbon-steel sheet, 0.030 inch thick by 2 inches square. b. Spindle: Copper- or zinc-coated, low carbon steel, fully annealed, 0.106inch- diameter shank, length to suit depth of insulation indicated. c. Adhesive-backed base with a peel-off protective cover. B. Staples: Outward-clinching insulation staples, nominal 3/4-inch- wide, stainless steel or Monel. C. Wire: 0.062-inch soft-annealed, stainless steel. D. Bands: Stainless-steel or aluminum with wing seals. PART 3 - EXECUTION 3.01 EXAMINATION A. Examine substrates and conditions for compliance with requirements for installation and other conditions affecting performance of insulation application. 1. 2. 3. 3.02 3.03 Verify that systems and equipment to be insulated have been tested and are free of defects. Verify that surfaces to be insulated are clean and dry. Proceed with installation only after unsatisfactory conditions have been corrected. PREPARATION A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will adversely affect insulation application. B. Coordinate insulation installation with the trade installing heat tracing. Comply with requirements for heat tracing that apply to insulation. COMMON INSTALLATION REQUIREMENTS A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of equipment, ducts and fittings, and piping including fittings, valves, and specialties. B. Install insulation materials, forms, vapor barriers or barriers, jackets, and thicknesses required for each item of equipment, duct system, and pipe system as specified in insulation system schedules. Lewiston Library Second Floor Remodel Project 15080-7 15025 C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state. D. Install insulation with longitudinal seams at top and bottom of horizontal runs. E. Install multiple layers of insulation with longitudinal and end seams staggered. F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties. G. Keep insulation materials dry during application and finishing. H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer. I. Install insulation with least number of joints practical. J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor-barrier mastic. 1. 2. 3. 4. Install insulation continuously through hangers, at supports and around anchor attachments. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor-barrier mastic. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield. K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses. L. Install insulation with factory-applied jackets as follows: 1. 2. 3. 4. 5. Draw jacket tight and smooth. Cover circumferential joints with 3-inch- wide strips, of same material as insulation jacket. Secure strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches o.c. Overlap jacket longitudinal seams at least 1-1/2 inches. Install insulation with longitudinal seams at bottom of pipe. Clean and dry surface to receive selfsealing lap. Staple laps with outward clinching staples along edge at 4 to 6 inches o.c. a. For below ambient services, apply vapor-barrier mastic over staples. Cover joints and seams with tape as recommended by insulation material manufacturer to maintain vapor seal. Where vapor barriers are indicated, apply vapor-barrier mastic on seams and joints and at ends adjacent to duct and pipe flanges and fittings. Lewiston Library Second Floor Remodel Project 15080-8 15025 M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness. N. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement. O. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints. P. Do not install insulation for the following: 1. 2. 3. 4. 5. 6. 7. 3.04 Vibration-control devices. Testing agency labels and stamps. Nameplates and data plates. Manholes. Handholes. Cleanouts. Flexible connector hoses for hydronic coils. PENETRATIONS A. Insulation Installation at Roof Penetrations: Install insulation continuously through roof penetrations. 1. 2. 3. 4. Seal penetrations with flashing sealant. For applications requiring only indoor insulation, terminate insulation above roof surface and seal with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant. Extend jacket of outdoor insulation outside roof flashing at least 2 inches below top of roof flashing. Seal jacket to roof flashing with flashing sealant. B. Insulation Installation at Below-Grade Exterior Wall Penetrations: Terminate insulation flush with sleeve seal. Seal terminations with flashing sealant. C. Insulation Installation at Aboveground Exterior Wall Penetrations: continuously through wall penetrations. 1. 2. 3. 4. D. Install insulation Seal penetrations with flashing sealant. For applications requiring only indoor insulation, terminate insulation inside wall surface and seal with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant. Extend jacket of outdoor insulation outside wall flashing and overlap wall flashing at least 2 inches. Seal jacket to wall flashing with flashing sealant. Insulation Installation at Non-Rated Interior Wall and Partition Penetrations: Install insulation continuously through walls and partitions. Lewiston Library Second Floor Remodel Project 15080-9 15025 E. Insulation Installation at Fire-Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire-rated walls and partitions. Terminate insulation at fire damper sleeves for fire-rated wall and partition penetrations. Externally insulate damper sleeves to match adjacent insulation and overlap duct insulation at least 2 inches. 1. F. Insulation Installation at Floor Penetrations: 1. 2. 3. 3.05 Firestopping and fire-resistive joint sealers are specified in Division 7 Section "Through-Penetration Firestop Systems" and Division 15 Section “Basic Mechanical Materials and Methods”. Duct: Install insulation continuously through floor penetrations that are not fire rated. For penetrations through fire-rated assemblies, terminate insulation at fire damper sleeves and externally insulate damper sleeve beyond floor to match adjacent duct insulation. Overlap damper sleeve and duct insulation at least 2 inches. Pipe: Install insulation continuously through floor penetrations. Seal penetrations through fire-rated assemblies according to Division 7 Section "Through-Penetration Firestop Systems" and Division 15 Section “Basic Mechanical Materials and Methods”. FLEXIBLE ELASTOMERIC INSULATION INSTALLATION A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. B. Insulation Installation on Pipe Flanges: 1. 2. 3. 4. C. Insulation Installation on Pipe Fittings and Elbows: 1. 2. D. Install pipe insulation to outer diameter of pipe flange. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of sheet insulation of same thickness as pipe insulation. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. Install mitered sections of pipe insulation. Secure insulation materials and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. Insulation Installation on Valves and Pipe Specialties: 1. 2. 3. Install reusable valve wrap or preformed valve covers manufactured of same material as pipe insulation when available. Install insulation to flanges as specified for flange insulation application. Secure insulation to valves and specialties and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. Lewiston Library Second Floor Remodel Project 15080-10 15025 3.06 MINERAL-FIBER INSULATION INSTALLATION A. Insulation Installation on Straight Pipes and Tubes: 1. 2. 3. B. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor-barrier mastic and joint sealant. For insulation with factory-applied jackets on above ambient surfaces, secure laps with outward clinched staples at 4 to 6 inches o.c. For insulation with factory-applied jackets on below ambient surfaces, do not staple longitudinal tabs but secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor-barrier mastic and flashing sealant. Insulation Installation on Fittings, Valves, Strainers, Flanges, and Unions: 1. 2. 3. 4. 5. 6. 7. 8. Install insulation over fittings, valves, strainers, flanges, unions, and other specialties with continuous thermal and vapor-barrier integrity, unless otherwise indicated. Insulate pipe elbows using preformed fitting insulation. Where preformed fitting insulation is not commercially available, use mitered fittings made from same material and density as adjacent pipe insulation. Each piece shall be butted tightly against adjoining piece and bonded with adhesive. Insulate tee fittings with preformed fitting insulation. Where preformed fitting insulation is not commercially available, use sectional pipe insulation of same material and thickness as used for adjacent pipe. Cut sectional pipe insulation to fit. Butt each section closely to the next and hold in place with tie wire. Bond pieces with adhesive. Insulate valves using reusable valve wrap or preformed fitting insulation. Where preformed fitting insulation is not commercially available, use sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For valves, insulate up to and including the bonnets, valve stuffing-box studs, bolts, and nuts. Insulate strainers using reusable valve wrap or preformed fitting insulation. Where preformed fitting insulation is not commercially available, use sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. Insulate strainers so strainer basket flange or plug can be easily removed and replaced without damaging the insulation and jacket. For below ambient services, provide a design that maintains vapor barrier. Insulate flanges and unions using a section of oversized preformed pipe insulation. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For services not specified to receive a field-applied jacket except for flexible elastomeric, install fitted PVC cover over elbows, tees, strainers, valves, flanges, and unions. Terminate ends with PVC end caps. Tape PVC covers to adjoining insulation facing using PVC tape. Install reusable valve wrap or removable insulating fabric fitting covers on valves, elbows, tees, and flanges, strainers or other irregularly-shaped fittings or components where fitted PVC covers are not practical or available. Lewiston Library Second Floor Remodel Project 15080-11 15025 C. Blanket Insulation Installation on Ducts and Plenums: insulation pins. 1. 2. 3. 4. 5. D. Secure with adhesive and Where required or recommended by manufacturer, apply adhesives according to recommended coverage rates per unit area for duct and plenum surfaces. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. Install either capacitor-discharge-weld pins and speed washers or cupped-head, capacitor-discharge-weld pins on bottom of rectangular or square ducts as follows: a. On duct bottoms with dimensions 18-inches and larger, place pins spaced 3 inches maximum from insulation end joints, and 18-inches o.c. Install additional pins to hold insulation tightly against surface at cross bracing. Apply insulation with edges tightly secured with staples at 6-inch maximum spacing. Tape secured seam with 3-inch wide pressure-sensitive aluminum foil tape or seal joints with two coats of vapor barrier mastic reinforced with one layer of open weave glass fabric as recommended by manufacturer. Do not overcompress insulation during installation. Cut excess portion of pins extending beyond speed washers. Cover exposed pins and washers with tape matching insulation facing to maintain vapor barrier seal. Insulation Installation on Equipment, Tank and Vessels: Secure insulation with adhesive and insulation pins. 1. 2. 3. 4. 5. 6. 7. 8. Where required or recommended by manufacturer, apply adhesives according to recommended coverage rates per unit area of tank and vessel surfaces. Groove and score insulation materials to fit as closely as possible to equipment, including contours. Bevel insulation edges for cylindrical surfaces for tight joints. Stagger end joints. Protect exposed corners with secured corner angles. Install adhesively attached or self-sticking insulation hangers and speed washers on sides of tanks and vessels as follows: a. Do not weld anchor pins to ASME-labeled pressure vessels. b. Select insulation hangers and adhesive that are compatible with service temperature and with substrate. c. On tanks and vessels, maximum anchor-pin spacing is 3 inches from insulation end joints, and 16 inches o.c. in both directions. d. Do not overcompress insulation during installation. e. Cut and miter insulation segments to fit curved sides and domed heads of tanks and vessels. f. Impale insulation over anchor pins and attach speed washers. g. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing. Secure each layer of insulation with stainless-steel or aluminum bands. Select band material compatible with insulation materials. Stagger joints between insulation layers at least 3 inches. Install insulation in removable segments on equipment access doors, manholes, handholes, and other elements that require frequent removal for service and inspection. Bevel and seal insulation ends around manholes, handholes, ASME stamps, and nameplates. Lewiston Library Second Floor Remodel Project 15080-12 15025 9. 10. 3.07 3.08 FIRE-RATED INSULATION SYSTEM INSTALLATION A. Where fire-rated insulation system is indicated or scheduled, secure system to ducts and duct hangers and supports to maintain a continuous UL-listed fire rating. B. Insulate duct access panels and doors to achieve same fire rating as duct. C. Install firestopping at penetrations through fire-rated assemblies. Fire-stop systems are specified in Division 7 Section "Through-Penetration Firestop Systems" and Division 15 Section “Basic Mechanical Materials and Methods”. FINISHES A. Duct, Equipment, and Pipe Insulation with ASJ, Glass-Cloth, or Other Paintable Jacket Material: Paint jacket with paint system identified below and as specified in Division 9 painting Sections. 1. 3.09 For equipment with surface temperatures below ambient, apply mastic to open ends, joints, seams, breaks, and punctures in insulation. Install removable insulating fitting covers on equipment, tanks and vessels where scheduled. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket material and finish coat paint. Add fungicidal agent to render fabric mildew proof. a. Finish Coat Material: Interior, flat, latex-emulsion size. B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating. C. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work. D. Do not field paint aluminum or stainless-steel jackets. DUCT INSULATION SCHEDULE, GENERAL A. Plenums and Ducts Requiring Insulation: 1. 2. 3. 4. B. Indoor, supply and outdoor air. Indoor, conditioned ventilation supply air from energy recovery units. Indoor, exhaust/relief air from energy recovery units to discharge louver or termination. Outdoor, supply and return. Items Not Insulated: 1. 2. 3. 4. 5. 6. Fibrous-glass ducts. Metal ducts with duct liner of sufficient thickness to comply with energy code and ASHRAE/IESNA 90.1. Indoor, exposed ducts specifically indicated not to be insulated. Factory-insulated flexible ducts. Factory-insulated plenums and casings. Flexible connectors. Lewiston Library Second Floor Remodel Project 15080-13 15025 7. 8. 3.10 Vibration-control devices. Factory-insulated access panels and doors. INDOOR DUCT AND PLENUM APPLICATION SCHEDULE A. If more than one material is listed, selection from materials listed is Contractor’s option. B. Service: Supply-air ducts, within conditioned space. 1. 2. 3. 4. C. Service: Conditioned Ventilation Supply-air from energy recovery units, within conditioned space. 1. 2. 3. 4. D. Material: Mineral-Fiber Board or Mineral-Fiber Blanket. Minimum R-value: R-7. Field-Applied Jacket: None. Vapor Barrier Required: Yes. Service: Boiler Combustion Air Intake Ducts. 1. 2. 3. 4. H. Material: Mineral-Fiber Board or Mineral-Fiber Blanket. Minimum R-value: R-7. Field-Applied Jacket: None. Vapor Barrier Required: Yes. Service: Supply-air, Return-air, Conditioned Ventilation Supply-air ducts from energy recovery units, and Exhaust/Relief-air ducts from energy recovery units, not in conditioned space. 1. 2. 3. 4. G. Material: Mineral-Fiber Board or Mineral-Fiber Blanket. Minimum R-value: R-3.3. Field-Applied Jacket: None. Vapor Barrier Required: Yes Service: Outside-air ducts, within conditioned space from penetration of building exterior to automatic shut-off damper in duct or at HVAC unit. 1. 2. 3. 4. F. Material: Mineral-Fiber Board or Mineral-Fiber Blanket. Minimum R-value: R-3.3. Field-Applied Jacket: None. Vapor Barrier Required: Yes. Service: Exhaust/Relief-air from energy recovery units to discharge louver or termination, within conditioned space. 1. 2. 3. 4. E. Material: Mineral-Fiber Board or Mineral-Fiber Blanket. Minimum R-value: R-3.3. Field-Applied Jacket: None. Vapor Barrier Required: Yes. Material: Mineral-Fiber Blanket. Minimum R-value: R-3.3. Field-Applied Jacket: Aluminum. Vapor Barrier Required: Yes. Service: Type I Grease Hood ducts. 1. 2. Material: Fire-Rated Insulation System (2-hour rating). Minimum R-value: N/A. Lewiston Library Second Floor Remodel Project 15080-14 15025 3. 4. 3.11 EQUIPMENT INSULATION SCHEDULE A. Insulate indoor equipment in paragraphs below that is not factory insulated. If more than one material is listed, selection from materials listed is Contractor’s option. B. Domestic hot-water storage tank: 1. 2. 3. 4. 5. 3.12 Operating Temperature: 55 to 180 deg. F Mineral-Fiber Board: 2 inches thick and 3-lb/cu. ft. nominal density. Mineral-Fiber Pipe and Tank: 2 inches thick. Field-Applied Jacket: Aluminum. Vapor Barrier Required: None. PIPING INSULATION SCHEDULE, GENERAL A. Items Not Insulated: following: 1. 2. 3. 4. 3.13 Field-Applied Jacket: None. Vapor Barrier Required: None. Unless otherwise indicated, do not install insulation on the Fire-suppression piping. Drainage piping located in crawl spaces. Below-grade piping. Chrome-plated pipes and fittings unless there is a potential for personnel injury. INDOOR PIPING INSULATION SCHEDULE A. If more than one material is listed for a piping system, selection from materials listed is Contractor’s option. B. Pipe insulation to be in accordance with the 2009 IECC, or the following schedule, whichever is more stringent. C. Service: Domestic Hot and Recirculated Hot Water. 1. 2. 3. 4. 5. D. Operating Temperature: 60 to 140 deg F. Insulation Material: Mineral-Fiber. Insulation Thickness: Apply the following insulation thicknesses: a. Pipe, 1-1/4 inch and less: 1.0 inch b. Pipe, 1-1/2 inch and larger: 1.5 inch Field-Applied Jacket: PVC for piping exposed in public spaces to 9 feet above floor level. Vapor Barrier Required: None. Service: Domestic Cold Water. 1. 2. 3. 4. 5. Operating Temperature: 35 to 60 deg F. Insulation Material: Mineral-Fiber. Insulation Thickness: Apply the following insulation thicknesses: a. Pipe, 1-1/4 inch and less: 1.0 inch b. Pipe, 1-1/2 inch and larger: 1.5 inch Field-Applied Jacket: PVC for piping exposed in public spaces to 9 feet above floor level. Vapor Barrier Required: Yes. Lewiston Library Second Floor Remodel Project 15080-15 15025 E. Service: Non-Potable Rainwater. 1. 2. 3. 4. 5. F. Service: Storm Drainage (Rainwater) and Overflow Conductors. 1. 2. 3. 4. 5. G. Operating Temperature: 32 to 100 deg F. Insulation Material: Mineral-Fiber. Insulation Thickness: 1.0 inch Vapor Barrier Required: Yes. Service: Refrigerant Suction, liquid. 1. 2. 3. 4. 3.14 Operating Temperature: 32 to 100 deg F. Insulation Material: Mineral-Fiber. Insulation Thickness: Apply the following insulation thicknesses: a. All pipe sizes: 1.0 inch Field-Applied Jacket: PVC for piping exposed in public spaces to 9 feet above floor level. Vapor Barrier Required: Yes. Service: Roof Drain Bodies. 1. 2. 3. 4. H. Operating Temperature: 35 to 75 deg F. Insulation Material: Mineral-Fiber. Insulation Thickness: Apply the following insulation thicknesses: a. Pipe, 1-1/2 inch and less: 0.5 inch b. Pipe, 1-1/2 inch and larger: 1.0 inch Field-Applied Jacket: PVC for piping exposed in public spaces to 9 feet above floor level. Vapor Barrier Required: Yes. Operating Temperature: 35 to 50 deg F. Insulation Material: Flexible Elastomeric. Insulation Thickness: Apply the following insulation thicknesses: a. All pipe sizes: 0.5 inch Field-Applied Jacket: None. OUTDOOR, ABOVEGROUND PIPING INSULATION SCHEDULE A. If more than one material is listed for a piping system, selection from materials listed is Contractor’s option. B. Service: Domestic Cold Water. 1. 2. 3. 4. 5. Operating Temperature: 105 deg F or greater. Insulation Material: Mineral-Fiber or Flexible Elastomeric. Insulation Thickness: Apply the following insulation thicknesses: a. Pipe, 1-1/4 inch and less: 1.0 inch b. Pipe, 1-1/2 inch and larger: 1.5 inch Field-Applied Jacket: Aluminum. Vapor Barrier Required: Yes. Lewiston Library Second Floor Remodel Project 15080-16 15025 C. Service: Refrigerant Suction, Liquid. 1. 2. 3. Operating Temperature: 35 to 50 deg F. Insulation Material: Flexible Elastomeric. Insulation Thickness: Apply the following insulation thicknesses: a. All pipe sizes: 0.5 inch b. Field-Applied Jacket: Aluminum. c. Vapor Barrier Required: None. END OF SECTION 15080 Lewiston Library Second Floor Remodel Project 15080-17 15025 SECTION 15110 - VALVES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following general-duty valves: 1. 2. 3. 4. 5. 6. B. Related Sections include the following: 1. 2. 3. 1.03 Division 15 Section "Mechanical Identification" for valve tags and charts. Division 15 Section "HVAC Instrumentation and Controls" for control valves and actuators. Division 15 piping Sections for specialty valves applicable to those Sections only. DEFINITIONS A. The following are standard abbreviations for valves: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 1.04 Ball valves. Butterfly valves. Swing check valves. Spring-loaded, lift-disc check valves. Gate valves. Globe valves. WOG: Non-shock Water-Oil-Gas working pressure rating, psig. SWP: Steam working pressure rating, psig. EPDM: Ethylene-propylene-diene terpolymer rubber. PTFE: Polytetrafluoroethylene plastic. TFE: Tetrafluoroethylene plastic. NRS: Non-rising stem. RS: Rising stem. OS&Y: Outside stem and yoke. MSS: Manufacturer’s Standardization Society of the Valve and Fittings Industry. PPS: Polyphenylene sulfide. SUBMITTALS A. Product Data: For each type of valve indicated. Include body, seating, and trim materials; valve design; pressure and temperature classifications; end connections; arrangement; dimensions; and required clearances. B. Maintenance Data: For each type of valve indicated to include in operation and maintenance manuals. Lewiston Library Second Floor Remodel Project 15110-1 15025 1.05 QUALITY ASSURANCE A. ASME Compliance: ASME B31.9 for building services piping valves. B. ASME Compliance for Ferrous Valves: ASME B16.10. C. ASME Compliance for Bronze Valves: ASME B16.24. D. MSS Compliance: 1. 2. 3. 4. 5. 6. SP-67: Butterfly Valves. SP-70: Cast Iron Gate Valves, Flanged and Threaded Ends. SP-71: Gray Iron Swing Check Valves, Flanged and Threaded Ends. SP-80: Bronze Gate, Globe, Angle and Check Valves. SP-85: Cast Iron Globe and Angle Valves, Flanged and Threaded Ends. SP-110: Ball Valves, Threaded and Solder Joint Ends. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products of one of the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 2.02 Anvil International. Conbraco/Apollo Industries Hammond Valve Milwaukee Valve Company NIBCO, Inc. Stockham Tyco/Grinnell Victaulic Company of America Viega VALVES, GENERAL A. Valve Type/Manufacturer: Valves of same type shall be of same manufacturer. B. Refer to Part 3 "Valve Applications" Article for applications of valves. C. Bronze or Brass Valves: NPS 2 and smaller with threaded or solder-joint ends, unless otherwise indicated. D. Iron Valves: NPS 2-1/2 and larger with flanged ends or grooved ends, unless otherwise indicated. E. Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures. F. Valve Sizes: Same as upstream pipe, unless otherwise indicated. Lewiston Library Second Floor Remodel Project 15110-2 15025 G. Valve Actuators: 1. 2. 3. 4. 2.03 H. Extended Valve Stems: On insulated valves. I. Valve Flanges: ASME B16.10 for iron valves; ASME B16.24 for bronze valves. J. Valve Grooved Ends: ASME/AWWA C606. BRONZE BALL VALVES A. Bronze Ball Valves, General: MSS SP-110. B. Two-Piece Ball Valves: Bronze body with full port, hard chrome-plated solid brass or bronze ball, reinforced TFE seats and PTFE packing, adjustable packing nut, blowoutproof brass stem, threaded or solder ends; 150 SWP/600 WOG. 1. C. A. Brass Ball Valves, General: MSS SP-110. B. Two-Piece Ball Valves: Forged brass body with full port, hard chrome-plated solid brass or bronze ball, reinforced TFE seats and PTFE packing, adjustable packing nut, blowout-proof brass stem, threaded or solder ends; 150 SWP/600 WOG. Milwaukee BA-475B/BA-485B, or equal. PRESSURE-SEAL BRONZE BALL VALVES A. Two-Piece Ball Valves: Bronze body with full port, chrome-plated brass ball and stem, PFTE seats, blowout-proof stem, pressure-seal ends; 600 WOG for sizes NPS 2 and smaller. 1. 2.06 Milwaukee BA-400S, or equal. BRASS BALL VALVES 1. 2.05 Milwaukee BA-400/BA-450, or equal. Two-Piece Ball Valves: Bronze body with full port, 316 stainless steel solid ball, reinforced TFE seats (15% glass filled) and PTFE packing, adjustable packing nut, blowout-proof 316 stainless steel stem, threaded ends; 150 SWP/600 WOG. 1. 2.04 Chainwheel: For attachment to valves, of size and mounting height, as indicated in the "Valve Installation" Article in Part 3. Gear Drive: For quarter-turn valves NPS 8 and larger. Handwheel: For valves other than quarter-turn types. Lever Handle: For quarter-turn valves NPS 6 and smaller. Viega Pro-Press Series. DUCTILE IRON BODY BUTTERFLY VALVES A. Iron Body Butterfly Valves, General: MSS SP-67, bubble tight seal with lug (flanged) body type. Lewiston Library Second Floor Remodel Project 15110-3 15025 B. Butterfly Valves: Cast iron body, aluminum bronze disc, 416 stainless steel two-piece stem design, field replaceable hard phenolic backed EPDM liner, non-metallic stem journal, blowout-proof stem, extended neck for 2 inch insulation, 10-position lever-lock handle with memory position plate for sizes NPS 6 and Smaller, lug body type; 200 WOG. 1. C. Grooved-End, Butterfly Valves: ASTM A 536 ductile iron body, electroless nickel coated or EPDM encapsulated ductile iron disc, EPDM seat with full continuous contact, EPDM stem seals, stainless-steel stem, 10-position lever-lock handle or gear operator; 230 deg F. maximum service temperature, 300 WOG. 1. 2. 3. 2.07 Grooved-End, Non-Ferrous Butterfly Valve: 300 CWP rating, cast bronze body, elastomer encapsulated ductile iron disc, with grooved ends manufactured to copper-tube dimensions. 1. 2. Anvil “Gruvlok” 7721 Series. Victaulic Series 608. BRONZE CHECK VALVES A. Bronze Check Valves, General: MSS SP-80. B. Horizontal Swing Check Valves: Bronze body, threaded cap, bronze or TFE disc, integral bronze seats, threaded or solder ends; 125 SWP/200 WOG. 1. C. D. Milwaukee 509/1509, or equal. Horizontal Swing Check Valves: Bronze body, threaded cap, TFE disc, integral bronze seats, threaded or solder ends; 150 SWP/300 WOG. 1. Milwaukee 510-T/1510-T, or equal. Horizontal Swing Check Valves: “Y” pattern swing, bronze body, threaded cap, regrindable bronze disc, stainless steel hinge pins, integral bronze seats, threaded ends; 200 SWP. 1. 2.09 Anvil “Gruvlok” 7700 Series Tyco/Grinnell B302 Series Victaulic 761 Series, VIC-300 “Master-Seal” GROOVED NON-FERROUS ALLOY BUTTERFLY VALVES A. 2.08 Milwaukee ML Series, or equal. Milwaukee 508, or equal. IRON BODY SWING CHECK VALVES A. Iron Body Swing Check Valves, General: MSS SP-71. B. Horizontal Swing Check Valves: Cast iron body, bronze trim, bolted bonnet, bronze or cast iron disc, bronze seat ring, flanged ends; 125 SWP/200 WOG. 1. Milwaukee F2974, or equal. Lewiston Library Second Floor Remodel Project 15110-4 15025 C. Horizontal Swing Check Valves: ASTM A216 Grade WCB cast carbon steel body, bolted cover, 13% chrome disc, flanged ends, API 598; 150 SWP. 1. 2.10 SPRING-LOADED, LIFT-DISC CHECK VALVES A. Bronze Spring-Loaded Lift-Disc Check Valves: Bronze body, non-slam, in-line spring lift check, TFE disc, bronze or TFE seat, bronze or stainless steel spring, threaded or solder ends; 250 WOG. 1. B. C. Milwaukee 1400, or equal. Ductile Iron Spring-Assisted, Check Valves: Grooved style, non-slam, ductile iron body, aluminum bronze or elastomer encapsulated ductile iron disc, stainless steel spring and shaft; 300 CWP. 1. Victaulic Series 716. BRONZE GATE VALVES A. Bronze Gate Valves, General: MSS SP-80. B. Gate Valves: Bronze body, threaded bonnet, rising stem, malleable iron handwheel, solid bronze wedge, non-asbestos packing, gland follower, threaded or solder ends; 125 SWP/200 WOG. 1. C. D. Milwaukee 148/149, or equal. Gate Valves: Bronze body, union bonnet, rising stem, malleable iron handwheel, solid bronze wedge, non-asbestos packing, gland follower, threaded or solder ends; 150 SWP/300 WOG. 1. Milwaukee 1151/1169, or equal. Gate Valves: Bronze body, union bonnet, rising stem, malleable iron handwheel, solid bronze wedge, stainless steel seat rings, non-asbestos packing, gland follower, threaded ends; 200 SWP. 1. 2.12 Milwaukee 548T/1548T, or equal. Iron Body Compact-Wafer, Lift-Disc Check Valves: Wafer (flangeless) style, non-slam, cast iron body, bronze trim and disc, center guided, stainless steel springs and screws; 125 SWP/200 WOG. 1. 2.11 Milwaukee 1570, or equal. Milwaukee 1174, or equal BRONZE GLOBE VALVES A. Bronze Globe Valves, General: MSS SP-80. B. Globe Valves: Bronze body, threaded bonnet, rising stem, malleable iron handwheel, bronze disc and seat, non-asbestos packing, gland follower, threaded or solder ends; 125 SWP/200 WOG. 1. Milwaukee 502/1502, or equal. Lewiston Library Second Floor Remodel Project 15110-5 15025 C. Globe Valves: Bronze body, union bonnet, rising stem, malleable iron handwheel, TFE disc, integral bronze seat, non-asbestos packing, gland follower, threaded or solder ends; 150 SWP/300 WOG. 1. D. Milwaukee 590-T/1590-T, or equal. Globe Valves: Bronze body, union bonnet, rising stem, malleable iron handwheel, stainless steel plug disc and seat, non-asbestos packing, threaded ends; 200 SWP. 1. Milwaukee 592A, or equal. PART 3 - EXECUTION 3.01 EXAMINATION A. Examine piping system for compliance with requirements for installation tolerances and other conditions affecting performance. 1. 3.02 Proceed with installation only after unsatisfactory conditions have been corrected. B. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling. C. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations. D. Examine threads on valve and mating pipe for form and cleanliness. E. Examine grooved ends for conditions that might cause leakage. Ends should be free from indentations or projections in the area from valve end to groove. F. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage. G. Do not attempt to repair defective valves; replace with new valves. VALVE APPLICATIONS A. Refer to piping Sections for specific valve applications. If valve applications are not indicated, use the following: 1. 2. 3. Shutoff Service: Ball, butterfly or gate valves. Throttling Service: Ball, globe valves. Pump Discharge: Spring-loaded, lift-disc check valves. B. If valves with specified SWP or WOG ratings are not available, the same types of valves with higher SWP or WOG ratings may be substituted. C. CHILLED-WATER, CONDENSER WATER, AND HOT WATER HEATING PIPING: Use the following types of valves: 1. 2. Bronze Ball Valves, NPS 2 and Smaller: 600 WOG. Brass Ball Valves, NPS 3 and Smaller: 600 WOG. Lewiston Library Second Floor Remodel Project 15110-6 15025 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. D. COMPRESSED-AIR PIPING: Use the following types of valves: 1. 2. 3. E. Bronze Ball Valves, NPS 2 and Smaller: 600 WOG. Equipment-Isolation Ball Valves, NPS 2 and Smaller: Safety-exhaust. Swing Check Valves, NPS 2 and Smaller: 150 SWP/300 WOG, bronze body, TFE disc. DOMESTIC WATER PIPING: Use the following types of valves: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 3.03 Butterfly Valves, NPS 2-1/2 to NPS 12: 200 WOG, ductile iron body. Butterfly Valves, NPS 2-1/2 to NPS 12: 300 WOG, ductile iron body, groovedends. Swing Check Valves, NPS 2 and Smaller: 150 SWP/300 WOG, bronze body. Swing Check Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, bronze trim, iron body. Spring-Loaded, Lift-Disc Check Valves, NPS 2 and Smaller: 250 WOG, bronze body. Spring-Loaded, Lift-Disc Check Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, wafer style, bronze trim, iron body. Spring-Assisted, Check Valves, NPS 2-1/2 and Larger: 300 CWP, grooved end style, stainless steel trim, ductile iron body. Gate Valves, NPS 2 and Smaller: 150 SWP/300 WOG, bronze body. Gate Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, bronze trim, iron body. Globe Valves, NPS 2 and Smaller: 150 SWP/300 WOG, bronze body. Globe Valves, NPS 2-1/2 and Larger: 125 SWP/300 WOG, bronze trim, iron body. Bronze Ball Valves, NPS 2 and Smaller: 600 WOG. Brass Ball Valves, NPS 3 and Smaller: 600 WOG. Butterfly Valves, NPS 2-1/2 to NPS 6: 300 WOG, cast bronze body. Swing Check Valves, NPS 2 and Smaller: 125 SWP/200 WOG, bronze body. Swing Check Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, bronze trim, iron body. Spring-Loaded, Lift-Disc Check Valves, NPS 2 and Smaller: 250 WOG, bronze body. Spring-Loaded, Lift-Disc Check Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, wafer style, bronze trim, iron body. Spring-Assisted, Check Valves, NPS 2-1/2 and Larger: 300 CWP, grooved end style, stainless steel trim, ductile iron body. Gate Valves, NPS 2 and Smaller: 125 SWP/200 WOG, bronze body. Gate Valves, NPS 2-1/2 and Larger: 125 SWP/200 WOG, bronze trim, iron body. VALVE INSTALLATION A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Locate valves for easy access and provide separate support where necessary. C. Install valves in horizontal piping with stem at or above center of pipe. Lewiston Library Second Floor Remodel Project 15110-7 15025 D. Install valves in position to allow full stem movement. E. Install check valves for proper direction of flow and as follows: 1. 2. 3.04 3.05 Swing Check Valves: In horizontal position with hinge pin level. Compact-Wafer Lift-Disc Check Valves: In horizontal or vertical position, between flanges. F. Install union adjacent to each threaded end valve on the downstream side, and at final connection to each piece of equipment. G. Install flanges adjacent to flanged valves and at final connections to each piece of equipment. JOINT CONSTRUCTION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping joint construction. B. Pressure-Seal Joints: Use manufacturer-recommended tool and procedure. insertion marks on pipe after assembly. C. Grooved Joints: Assemble joints with keyed coupling housing, gasket, lubricant, and bolts according to coupling and fitting manufacturer's written instructions. . All grooved couplings, fittings, valves, and specialties shall be of the same manufacturer. Grooving tools shall be of the same manufacturer as the grooved components. Grooved ends shall be clean and free from indentations, projections, and roll marks in the area from pipe end to groove. Grooved coupling manufacturer’s factory trained field representative shall provide on-site training for contractor’s field personnel in the proper use of grooving tools, application of groove, and installation of grooved piping products. Factory trained representative shall periodically inspect the product installation. Contractor shall remove and replace any improperly installed products. Leave ADJUSTING A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs. END OF SECTION 15110 Lewiston Library Second Floor Remodel Project 15110-8 15025 SECTION 15122 - METERS AND GAGES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following meters and gages for mechanical systems: 1. 2. 3. B. Related Sections include the following: 1. 2. 3. 4. 5. 6. 1.03 Division 2 Section "Water Distribution" for domestic and fire-protection water service meters outside the building. Division 2 Section "Natural Gas Distribution" for gas meters outside the building. Division 15 Section "Domestic Water Piping" for domestic and fire-protection water service meters inside the building. Division 15 Section “Hydronic Piping” for calibrated balancing valves, flowmeters and automatic flow-control valves. Division 15 Section "Steam and Condensate Piping" for steam and condensate meters. Division 15 Section "Fuel Gas Piping" for gas meters inside the building. DEFINITIONS A. 1.04 Thermometers. Gages. Test plugs. EPDM: Ethylene-propylene-diene terpolymer rubber. SUBMITTALS A. Product Data: For each type of product indicated. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. 2.02 Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers listed. LIQUID-IN-GLASS THERMOMETERS A. Manufacturers: 1. Marsh Bellofram. Lewiston Library Second Floor Remodel Project 15122-1 15025 2. 3. 4. 5. 6. 7. 2.03 B. Case: Plastic or die-cast aluminum, 9 inches long. C. Tube: Red or blue reading, organic-liquid filled, with magnifying lens. D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings. E. Window: Glass or plastic. F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device. G. Stem: Metal, for thermowell installation and of length to suit installation. H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of 1.5 percent of range. THERMOWELLS A. Manufacturers: Same as manufacturer of thermometer being used. B. Description: Fitting with protective socket for installation in threaded pipe fitting to hold fixed thermometer stem. 1. 2. 3. 4. 2.04 MILJOCO Corporation. Tel-Tru. Trerice, H. O. Co. Weiss Instruments, Inc. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. Winters Instruments. Material: Brass, for use in copper piping. Material: Steel, for use in steel piping. Extension-Neck Length: Nominal thickness of 2 inches, but not less than thickness of insulation. Omit extension neck for sockets for piping not insulated. Insertion Length: To extend to center of pipe, minimum insertion length 2-1/2 inches. PRESSURE GAGES A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. AMETEK, Inc.; U.S. Gauge Div. Ashcroft Commercial Instrument Operations; Dresser Industries; Instrument Div. Marsh Bellofram. MILJOCO Corporation. Tel-Tru. Trerice, H. O. Co. Weiss Instruments, Inc. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. WIKA Instrument Corporation. Winters Instruments. Lewiston Library Second Floor Remodel Project 15122-2 15025 B. Direct-Mounting, Dial-Type Pressure Gages: ASME B40.100. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. C. Case: Dry type, cast aluminum, 4-1/2-inch diameter. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated. Pressure Connection: Brass, NPS 1/4, bottom-outlet type unless back-outlet type is indicated. Movement: Mechanical, with link to pressure element and connection to pointer. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings. Pointer: Red or other dark-color metal. Window: Glass. Ring: Stainless steel. Accuracy: Grade A, plus or minus 1 percent of middle half scale. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure. Range for Fluids under Pressure: Two times operating pressure. Pressure-Gage Fittings: 1. 2. 3. 2.05 Indicating-dial type complying with Valves: NPS 1/4 brass or stainless-steel needle type. Syphons: NPS 1/4 coil of brass tubing with threaded ends. Snubbers: ASME B40.5, NPS 1/4 brass bushing with corrosion-resistant, porous-metal disc of material suitable for system fluid and working pressure. TEST PLUGS A. Manufacturers: 1. 2. 3. 4. 5. Flow Design, Inc. MG Piping Products Co. Peterson Equipment Co., Inc. Sisco Manufacturing Co. Trerice, H. O. Co. B. Description: Corrosion-resistant brass or stainless-steel body with core inserts and gasketed and threaded cap, with extended stem for units to be installed in insulated piping. C. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F. D. Core Inserts: Two self-sealing rubber valves. 1. 2. E. Insert material for air, water, oil, or gas service at 20 to 200 deg F shall be chlorosulfonated synthetic rubber. Insert material for air or water service at minus 30 to plus 275 deg F shall be EPDM. Test Kit: Furnish one test kit containing one pressure gage and adaptor, two thermometers, and carrying case. Pressure gage, adapter probes, and thermometer sensing elements shall be of diameter to fit test plugs and of length to project into piping. Lewiston Library Second Floor Remodel Project 15122-3 15025 PART 3 - EXECUTION 3.01 THERMOMETER APPLICATIONS A. Install liquid-in-glass thermometers in the following locations: 1. 2. 3. 4. 5. 6. 7. B. Provide the following temperature ranges for thermometers: 1. 2. 3. 4. 5. 6. 3.02 Domestic Hot Water: 30 to 180 deg F, with 2-degree scale divisions. Domestic Cold Water: 0 to 100 deg F, with 2-degree scale divisions. Heating Hot Water: 30 to 240 deg F, with 2-degree scale divisions. Condenser Water: 0 to 160 deg F, with 2-degree scale divisions. Chilled Water: 0 to 100 deg F, with 2-degree scale divisions. Steam and Condensate: 30 to 300 deg F, with 5-degree scale divisions. GAGE APPLICATIONS A. Install dry-case-type pressure gages in the following locations: 1. 2. 3. 4. 3.03 Inlet and outlet of each hydronic boiler and chiller. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems. Inlet and outlet of each hydronic heat exchanger. Inlet and outlet of each hydronic heat-recovery unit. Inlet and outlet of each thermal storage tank. Outlet of each water heater. Where indicated on Drawings. Discharge of each pressure-reducing valve. Chilled- and condenser-water inlets and outlets of chillers. Building water-service entrance. Suction and discharge of each hydronic pump. INSTALLATIONS A. Install direct-mounting thermometers and adjust vertical and tilted positions. B. Install thermowells with socket extending a minimum of 2 inches into fluid or to center of pipe and in vertical position in piping tees where thermometers are indicated. Install utilizing thermal conductive paste or other approved material. C. Install direct-mounting pressure gages in piping tees with pressure gage located on pipe at most readable position. D. Install needle-valve and snubber fitting in piping for each pressure gage for fluids (except steam). E. Install needle-valve and syphon fitting in piping for each pressure gage for steam. F. Provide test plugs at the following locations whether indicated on plans or not: 1. Adjacent to all gauges, temperature or pressure sensors, and thermometers. If instruments/ sensors are grouped, one test plug will suffice if provided in a common location. Lewiston Library Second Floor Remodel Project 15122-4 15025 2. 3. 4. G. 3.04 Install flow indicators, in accessible positions for easy viewing, in piping systems. CONNECTIONS A. 3.05 Adjacent to the supply and discharge of all pumps and manual flow control devices. At the inlet and outlet sides of all hydronic coils. Test plugs supplied with combination-duty type valves or as an integral component are acceptable substitutes for applications. Adjacent to each temperature control sensor thermowell. Install meters and gages adjacent to machines and equipment to allow service and maintenance for meters, gages, machines, and equipment. ADJUSTING A. Adjust faces of meters and gages to proper angle for best visibility. END OF SECTION 15122 Lewiston Library Second Floor Remodel Project 15122-5 15025 SECTION 15140 - DOMESTIC WATER PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes domestic water piping inside the building. B. Water meters will be furnished and installed by utility company. C. Water meters will be furnished by utility company for installation by Contractor. D. Related Sections include the following: 1. 2. 1.03 PERFORMANCE REQUIREMENTS A. Provide components and installation capable of producing domestic water piping systems with the following minimum working-pressure ratings, unless otherwise indicated: 1. 2. 1.04 1.05 Division 15 Section "Meters and Gages" for thermometers, pressure gages, and fittings. Division 15 Section "Domestic Water Piping Specialties" for water distribution piping specialties. Domestic Water Service Piping: 160 psig. Domestic Water Distribution Piping: 125 psig. SUBMITTALS A. Product Data: For pipe, tube, fittings, and couplings. B. Water Samples: Specified in "Cleaning" Article in Part 3. QUALITY ASSURANCE A. Piping materials shall bear label, stamp, or other markings of specified testing agency. B. Comply with NSF 61, "Drinking Water System Components-Health Effects; Sections 1 through 9," for potable domestic water piping and components. PART 2 - PRODUCTS 2.01 PIPING MATERIALS A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials. Lewiston Library Second Floor Remodel Project 15140-1 15025 2.02 B. Transition Couplings for Aboveground Pressure Piping: Coupling or other manufactured fitting the same size as, with pressure rating at least equal to and ends compatible with, piping to be joined. C. Transition Couplings for Underground Pressure Piping: AWWA C219, metal, sleevetype coupling or other manufactured fitting the same size as, with pressure rating at least equal to and ends compatible with, piping to be joined. COPPER TUBE AND FITTINGS A. Soft Copper Tube: ASTM B 88, Types K and L, water tube, annealed temper. 1. 2. 3. B. Hard Copper Tube: ASTM B 88, Type L, water tube, drawn temper. 1. 2. 3. 4. 5. 2.03 Copper Pressure Fittings: ASME B16.18, cast-copper-alloy or ASME B16.22, wrought-copper, solder-joint fittings. Furnish wrought-copper fittings if indicated. Bronze Flanges: ASME B16.24, Class 150, with solder-joint end. Furnish Class 300 flanges if required to match piping. Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body, with ball-and-socket, metal-to-metal seating surfaces and solder-joint or threaded ends. Copper Pressure Fittings: ASME B16.18, cast-copper-alloy or ASME B16.22, wrought- copper, solder-joint fittings. Copper Pressure-Seal Fittings and Ball Valves: ASME B16.18, cast-copperalloy or ASME B16.22, wrought- copper fittings with EPDM O-rings, inboard bead design, compression crimp on both sides of the seal bead, minimum 200psig working-pressure rating at 250 deg F; 600 WOG bronze body, two-piece, full-port ball valves with pressure-seal ends. a. Manufacturers: 1) Nibco 2) Viega Bronze Flanges: ASME B16.24, Class 150, with solder-joint end. Furnish Class 300 flanges if required to match piping. Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body, with ball-and-socket, metal-to-metal seating surfaces and solder-joint or threaded ends. Copper, Grooved-End Fittings: ASTM B 75 copper tube or ASTM B 584 bronze castings. VALVES A. Refer to Division 15 Section "Valves" for bronze and cast-iron, general-duty valves. B. Refer to Division 15 Section "Domestic Water Piping Specialties" for balancing and drain valves. Lewiston Library Second Floor Remodel Project 15140-2 15025 PART 3 - EXECUTION 3.01 EXCAVATION A. 3.02 Refer to Division 15 Section "Basic Mechanical Materials and Methods" for excavating, trenching, and backfilling. PIPING APPLICATIONS A. Transition and special fittings with pressure ratings at least equal to piping rating may be used in applications below, unless otherwise indicated. B. Flanges may be used on aboveground piping, unless otherwise indicated. C. Grooved joints may be used on aboveground grooved-end piping. D. Fitting Option: Mechanically formed tee-branch outlets and brazed joints may be used on aboveground copper tubing. E. Pipe Bending Option: Pipe bending of Types K and L copper tube permitted when bends are made with no kinks, ripples, distortions or reductions in diameter or any noticeable deviations from round. Minimum radius shall be 6 pipe diameters for pipe NPS 2 and smaller, and 5 pipe diameters for pipe NPS 2-1/2 and larger. F. Underground Domestic Water Service Piping: Use the following piping materials for each size range: 1. 2. G. Aboveground Domestic Water Piping: Use any of the following piping materials for each size range: 1. 2. 3. 3.03 NPS 2 and Smaller: Soft copper tube, Type K; copper pressure fittings; and brazed joints. NPS 3 and NPS 4: Hard copper tube, Type K; copper pressure fittings; and brazed joints. NPS 4 and Smaller: Hard copper tube,Type L; copper pressure-seal joints and ball valves. NPS 4 and Smaller: Hard copper tube, Type L; copper pressure fittings; and soldered joints. NPS 2-1/2 to NPS 6: Hard copper tube, Type L; with grooved ends; copper grooved-end fittings. VALVE APPLICATIONS A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply: 1. 2. 3. 4. B. Shutoff Duty: Use ball, butterfly or gate valves. Throttling Duty: Use ball, butterfly or globe valves. Hot-Water-Piping, Balancing Duty: Calibrated balancing valves. Drain Duty: Hose-end drain valves. Cast-bronze, grooved-end valves may be used with grooved-end piping. Lewiston Library Second Floor Remodel Project 15140-3 15025 C. 3.04 Bronze, pressure-seal end valves may be used with pressure-seal piping. PIPING INSTALLATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping installation. B. Extend domestic water service piping to exterior water distribution piping in sizes and locations indicated. C. Install copper tubing according to CDA's "Copper Tube Handbook." D. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for wall penetration systems. E. Install shutoff valve, hose-end drain valve, strainer, pressure gage, and test tee with valve, inside building at each domestic water service. Refer to Division 15 Section "Meters and Gages" for pressure gages, and to Division 15 Section "Domestic Water Piping Specialties" for drain valves and strainers. F. Install water-pressure regulators downstream from shutoff valves. Refer to Division 15 Section "Domestic Water Piping Specialties" for water-pressure regulators. G. Rough-in domestic water piping for water-meter installation according to utility company's requirements. H. Install aboveground domestic water piping level without pitch and plumb. I. Fill water piping. Check components to determine that they are not air bound and that piping is full of water. J. Perform the following steps before operation: 1. 2. 3. 4. 5. Close drain valves, hydrants, and hose bibbs. Open shutoff valves to fully open position. Open throttling valves to proper setting. Remove plugs used during testing of piping and plugs used for temporary sealing of piping during installation. Remove and clean strainer screens. Close drain valves and replace drain plugs. K. Check plumbing equipment and verify proper settings, adjustments, and operation. Do not operate water heaters before filling with water. L. Check Domestic Water Piping Specialties and verify proper settings, adjustments, and operation. 1. M. Water-Pressure Regulators: Set outlet pressure at 80 psig maximum, unless otherwise indicated. Energize pumps and verify proper operation. Lewiston Library Second Floor Remodel Project 15140-4 15025 3.05 3.06 JOINT CONSTRUCTION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping joint construction. B. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, 95-5 tin antimony solder; and ASTM B 828 procedure, unless otherwise indicated. C. Pressure-Seal Joints: Use manufacturer-recommended tool and procedure. insertion marks on pipe after assembly. D. Grooved Joints: Assemble joints with keyed-coupling housing, gasket, lubricant, and bolts according to coupling and fitting manufacturer's written instructions. E. Mechanically Formed Outlets: Form tee in copper tube according to equipment manufacturer's written instructions. Use tool designed for copper tube; drill pilot hole, form collar for outlet, dimple tube to form seating stop, and braze branch tube into collar. F. PEX Piping Joints: Join according to ASTM F 1807. VALVE INSTALLATION A. Install sectional valve close to water main on each branch and riser serving plumbing fixtures or equipment. B. Install shutoff valve on each water supply to equipment and on each water supply to plumbing fixtures without supply stops. C. Install drain valves for equipment, at base of each water riser, at low points in horizontal piping, and where required to drain water piping. 1. 2. D. 3.07 Leave Install hose-end drain valves at low points in water mains, risers, and branches. Install stop-and-waste drain valves where indicated. Install calibrated balancing valves in each hot-water circulation return branch and discharge side of each pump and circulator. Set calibrated balancing valves partly open to restrict but not stop flow. Refer to Division 15 Section "Domestic Water Piping Specialties" for calibrated balancing valves. HANGER AND SUPPORT INSTALLATION A. Refer to Division 15 Section "Hangers and Supports" for pipe hanger and support devices. B. Install supports according to Division 15 Section "Hangers and Supports." C. Support vertical piping and tubing at base and at each floor. D. Rod diameter may be reduced 1 size for double-rod hangers, to a minimum of 3/8 inch. Lewiston Library Second Floor Remodel Project 15140-5 15025 E. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. 6. 3.08 F. Install supports for vertical copper tubing every 10 feet. G. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions. CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to equipment and machines to allow service and maintenance. C. Connect domestic water piping to exterior water service piping. Use transition fitting to join dissimilar piping materials. D. Connect domestic water piping to service piping with shutoff valve, and extend and connect to the following: 1. 2. 3. 3.09 NPS 3/4 and Smaller: 60 inches with 3/8-inch rod. NPS 1 and NPS 1-1/4: 72 inches with 3/8-inch rod. NPS 1-1/2 and NPS 2: 96 inches with 3/8-inch rod. NPS 2-1/2: 108 inches with 1/2-inch rod. NPS 3 to NPS 5: 10 feet with 1/2-inch rod. NPS 6: 10 feet with 5/8-inch rod. Water Heaters: Cold-water supply and hot-water outlet piping in sizes indicated, but not smaller than sizes of water heater connections. Plumbing Fixtures: Cold- and hot-water supply piping in sizes indicated, but not smaller than required by plumbing code. Refer to Division 15 Section "Plumbing Fixtures." Equipment: Cold- and hot-water supply piping as indicated, but not smaller than equipment connections. Provide shutoff valve and union or flange for each connection. FIELD QUALITY CONTROL A. Inspect domestic water piping as follows: 1. 2. 3. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction: a. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures. b. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection. Lewiston Library Second Floor Remodel Project 15140-6 15025 B. Test domestic water piping as follows: 1. 2. 3. 4. 3.10 ADJUSTING A. 3.11 Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested. Leave uncovered and unconcealed new, altered, extended, or replaced domestic water piping until it has been tested and approved. Expose work that was covered or concealed before it was tested. Cap and subject piping to static water pressure of 50 psig above operating pressure, without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired. Repair leaks and defects with new materials and retest piping or portion thereof until satisfactory results are obtained. Adjust balancing valves in hot-water-circulation return piping to provide adequate flow. CLEANING A. Clean and disinfect potable domestic water piping as follows: 1. 2. Purge new piping and parts of existing domestic water piping that have been altered, extended, or repaired before using. Use purging and disinfecting procedures prescribed by authorities having jurisdiction or, if methods are not prescribed, procedures described in either AWWA C651 or AWWA C652 or as described below: a. Flush piping system with clean, potable water until dirty water does not appear at outlets. b. Fill and isolate system according to the following: 1) Fill system or part thereof with water/chlorine solution with at least 50 ppm of chlorine. Isolate with valves and allow to stand for 24 hours. c. Flush system with clean, potable water until no chlorine is in water coming from system after the standing time. d. Submit water samples in sterile bottles to authorities having jurisdiction. Repeat procedures if biological examination shows contamination. B. Prepare and submit reports of purging and disinfecting activities. C. Clean interior of domestic water piping system. progresses. Remove dirt and debris as work END OF SECTION 15140 Lewiston Library Second Floor Remodel Project 15140-7 15025 SECTION 15145- DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following domestic water piping specialties: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. B. Related Sections include the following: 1. 1.03 Provide components and installation capable of producing piping systems with following minimum working-pressure ratings, unless otherwise indicated: 1. 1.05 Division 15 Section "Meters and Gages" for thermometers, and pressure gages. PERFORMANCE REQUIREMENTS A. 1.04 Backflow preventers Water regulators Balancing valves Compact Circulators Thermostatic water mixing valves Water tempering equipment for emergency plumbing fixtures Strainers Outlet boxes Key-operation hydrants Trap seal primer valves Drain valves Miscellaneous piping specialties Domestic Water Piping: 125 psig. SUBMITTALS A. Product Data: For each type of product indicated. B. Maintenance Data: For domestic water piping specialties to include in operation and maintenance manuals. QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. NSF Compliance: 1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic domestic water piping components. Lewiston Library Second Floor Remodel Project 15145-1 15025 2. 1.06 Comply with NSF 61, "Drinking Water System Components--Health Effects, Sections 1 through 9," for potable domestic water piping specialties. EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Operating Key Handles: Equal to 100 percent of amount installed for each keyoperated hose bibb and hydrant installed. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. 2.02 Manufacturers: Subject to compliance with requirements, provide products by the manufacturers listed. BACKFLOW PREVENTERS A. Manufacturers: 1. 2. 3. 4. 5. B. Ames Co., Inc. Conbraco Industries, Inc. Febco Backflow Preventers. Watts Industries, Inc. Zurn Industries, Inc.; Wilkins Div. General: ASSE standard, backflow preventers. 1. 2. 3. 4. NPS 2 and Smaller: Bronze body with threaded ends. NPS 2-1/2 and Larger: Bronze, cast-iron, or stainless-steel body with flanged ends. Interior Components: Corrosion-resistant materials. Strainer: On inlet. C. Hose-Connection Vacuum Breakers: ASSE 1011, nickel plated, with nonremovable and manual drain features, and ASME B1.20.7, garden-hose threads on outlet. Units attached to rough-bronze-finish hose connections may be rough bronze. D. Reduced-Pressure-Principle Backflow Preventers: ASSE 1013, suitable for continuous pressure application. Include shutoff valves on inlet and outlet, and strainer on inlet; test cocks; and pressure-differential relief valve with ASME A112.1.2 air-gap fitting located between two positive-seating check valves. Stainless steel construction for water supply serving carbonated water beverage systems. 1. 2. 3. NPS 2 and Smaller: Quarter-turn, full-port ball valves. NPS 2-1/2 and Larger: Outside screw and yoke (OS&Y) gate valves. Pressure Loss: 12 psig maximum, through middle 1/3 of flow range. Lewiston Library Second Floor Remodel Project 15145-2 15025 E. Double-Check Backflow Prevention Assemblies: ASSE 1015, suitable for continuous pressure application. Include shutoff valves on inlet and outlet, and strainer on inlet; test cocks; and two positive-seating check valves. 1. 2. 3. 2.03 WATER REGULATORS A. Manufacturers: 1. 2. 3. B. Conbraco Industries, Inc. Watts Industries, Inc. Zurn Industries, Inc.; Wilkins Div. General: ASSE 1003, water regulators, rated for initial working pressure of 150 psig minimum. Include integral factory-installed or separate field-installed, Y-pattern strainer. 1. 2. 3. 2.04 NPS 2 and Smaller: Quarter-turn, full-port ball valves. NPS 2-1/2 and Larger: Outside screw and yoke (OS&Y) gate valves. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range. NPS 2 and Smaller: Bronze body with threaded ends. a. General-Duty Service: Single-seated, direct operated, unless otherwise indicated. b. Booster Heater Water Supply: Single-seated, direct operated with integral bypass. NPS 2-1/2 and Larger: Bronze or cast-iron body with flanged ends. Include AWWA C550 or FDA-approved, interior epoxy coating for regulators with castiron body. a. Type: Single-seated, direct operated. Interior Components: Corrosion-resistant materials. BALANCING VALVES A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. B. Armstrong Pumps, Inc. Conbraco Industries, Inc. Flow Design, Inc. Bell & Gossett Hays Fluid Control Div. Taco, Inc. Tour & Andersson, Inc. Watts Industries, Inc. Calibrated Balancing Valves: Adjustable, with two readout ports and memory setting indicator. 1. 2. 3. NPS 2 and Smaller: Bronze body with brass ball, adjustment knob, calibrated nameplate, and threaded or solder-joint ends. For recirculation system applications with water flows 1.5 GPM or less: Use NPS ½ valve. For recirculation system applications with water flows 0.5 GPM or less: Use NPS ½ valve specifically designed for accurate low flow control. Lewiston Library Second Floor Remodel Project 15145-3 15025 2.05 COMPACT CIRCULATORS A. Manufacturers: 1. 2. 3. 4. 5. B. Description: Horizontal, in-line, replaceable-cartridge-design circulator; rated for 125psig minimum working pressure and minimum continuous water temperature of 225 deg F. Bronze or stainless steel body. 1. 2. 3. 4. 2.06 Pump and Motor Assembly: On common shaft in hermetically sealed unit without stuffing box or mechanical seal, and with manufacturer's standard cooling and lubrication system. Impeller: Corrosion-resistant material. End Connections for NPS 2 and Smaller: Threaded. Pumps available only with flanged ends may be furnished with threaded companion flanges. Motor: Single speed, unless otherwise indicated. STRAINERS A. Manufacturers: 1. 2. 3. 4. 5. 6. B. Conbraco Industries, Inc. Mueller Steam Specialty Nibco. Spirax Sarco, Inc. Victaulic Company of America. Watts Industries, Inc. Strainers: Y-pattern, unless otherwise indicated, and full size of connecting piping. Include ASTM A 666, Type 304, stainless-steel screens . 1. 2. 3. 4. 2.07 Armstrong Pumps, Inc. Grundfos Pumps Corp. Bell & Gossett Taco, Inc. WILO-USA. Pressure Rating: 125-psig minimum steam working pressure, unless otherwise indicated. NPS 2 and Smaller: Bronze body, with female threaded ends; 20 mesh, 0.033inch openings. NPS 2-1/2 and Larger: Cast-iron body, ANSI 125 flanged ends; 20 mesh, 0.033inch openings for steam and water service to NPS 3; 0.045-inch perforations for steam service NPS 4 to NPS 6; 0.062-inch perforations for steam service NPS 8 and larger; 0.125-inch perforations for water service NPS 4 and larger. Y-Pattern Strainers: Screwed screen retainer with centered blowdown. a. Drain: Factory- or field-installed, hose-end drain valve. OUTLET BOXES A. Manufacturers: 1. 2. 3. 4. Acorn Engineering Company. Guy GrayManufacturing Co., Inc. IPS Corporation. LSP Products Group. Lewiston Library Second Floor Remodel Project 15145-4 15025 5. 6. 7. 8. 9. B. General: Recessed-mounting outlet boxes with supply fittings complying with ASME A112.18.1M. Include box with faceplate, services indicated for equipment connections. C. Clothes Washer Outlet Boxes: With hot- and cold-water hose connections, drain, and the following: 1. 2. 3. D. Box and Faceplate: [Stainless steel] [Enameled or epoxy-painted steel]. Shutoff Fitting[s]: [Two hose bibbs] [Combination, single lever]. Drain: NPS 2 standpipe, P-trap, and direct waste connection to drainage piping. Icemaker Outlet Boxes: With hose connection and the following: 1. 2. 2.08 Oatey. Plastic Oddities, Inc. Sioux Chief Mfg. Co. Symmons Industries, Inc. Zurn Industries, Inc. Box and Faceplate: [Stainless steel] [Enameled or epoxy-painted steel]. Shutoff Fitting: 1/2 inch FIP inlet compression angle valve. KEY-OPERATION HYDRANTS A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. 9. B. General: ASME A112.21.3M, key-operation hydrant with pressure rating of 125 psig. 1. 2. C. Inlet: NPS 3/4 threaded or solder joint. Outlet: ASME B1.20.7, garden-hose threads. Non-freeze Exposed-Outlet Wall Hydrants: ASSE 1019, self-drainable with integral nonremovable hose-connection vacuum breaker or backflow preventer, casing and operating rod to match wall thickness, projecting outlet, wall plate and wall clamp. 1. 2. D. Acorn Engineering. Josam Co. MIFAB Prier Brass Smith, Jay R. Mfg. Co. Tyler Pipe; Wade Div. Watts Industries, Inc. Woodford Manufacturing Co. Zurn Industries, Inc. Nozzle Finish:Polished nickel bronze. Wall Plate Finish: Polished nickel bronze or stainless steel. Non-freeze Concealed-Outlet Wall Hydrants: ASSE 1019, self-drainable with flushmounting box with locking cover, integral non-removable hose-connection vacuum breaker , casing and operating rod to match wall thickness, concealed outlet, wall clamp, “Water” stamped on cover. 1. Box and Cover Finish: Polished nickel bronze or stainless steel. Lewiston Library Second Floor Remodel Project 15145-5 15025 E. Hot and Cold, Non-freeze Concealed-Outlet Wall Hydrants: With deep flush-mounting box with locking cover; hot- and cold-water casings and operating rods to match wall thickness; concealed outlet; wall clamps; factory- or field-installed, non-removable and manual drain-type, hose-connection vacuum breaker complying with ASSE 1011, “Water” stamped on cover. 1. F. Single Temperature, Recessed Hose Box: Recessed hose box with wall flange; 18 gauge stainless steel box, 16 gauge stainless steel hinged removable door with cylinder lock; cartridge operated cold valve with 3/4-inch NPT female supply connection; loose-key vandal-resistant wheel handle; screwdriver stop; atmospheric type vacuum breaker complying with ASSE 1011. Provide engraved plastic nameplate “Water” affixed to cover. 1. G. Box and Cover Finish: Satin finish. Hot and Cold, Recessed Hose Box: Recessed hose box with wall flange; 18 gauge stainless steel box, 16 gauge stainless steel hinged removable door with cylinder lock; cartridge operated hot and cold water valves with 3/4-inch NPT female supply connections; loose-key vandal-resistant wheel handles; screwdriver stops; atmospheric type vacuum breaker complying with ASSE 1011. Provide engraved plastic nameplate “Water” affixed to cover. 1. 2.09 Box and Cover Finish: Polished nickel bronze or stainless steel. Box and Cover Finish: Satin finish. TRAP SEAL PRIMER VALVES A. Supply-Type Trap Seal Primer Valves: ASSE 1018, water-supply-fed type, with the following characteristics: 1. 2. 3. 4. 5. 6. 7. B. Manufacturers: a. Josam Co. b. MIFAB c. Precision Plumbing Products, Inc. d. Smith, Jay R. Mfg. Co. e. Sioux Chief Mfg. Co. f. Watts Industries, Inc. 125-psig minimum working pressure. Field serviceable. Bronze body with atmospheric-vented drain chamber. Inlet and Outlet Connections: NPS 1/2 threaded, union, or solder joint. Gravity Drain Outlet Connection: NPS 1/2 threaded or solder joint. Finish: Chrome plated, or rough bronze for units used with pipe or tube that is not chrome finished. Vacuum Breaker Type Trap Seal Primer Valves: ASSE 1044, Chrome-plated, cast-brass, NPS 1-1/2, flushometer valve vacuum breaker with NPS 3/8 outlet tubing. 1. Manufacturers: a. Smith, Jay R. Mfg. Co. b. Zurn Industries, Inc. Lewiston Library Second Floor Remodel Project 15145-6 15025 2.10 DRAIN VALVES A. Hose-End Drain Valves: MSS SP-110, NPS 3/4 ball valve, rated for 400-psig minimum CWP. Include two-piece, copper-alloy body with standard port, chrome-plated brass ball, replaceable seats and seals, blowout-proof stem, and vinyl-covered steel handle. 1. 2. B. 2.11 Inlet: Threaded or solder joint. Outlet: Short-threaded nipple with ASME B1.20.7, garden-hose threads and cap. Stop-and-Waste Drain Valves: MSS SP-110, ball valve, rated for 200-psig minimum CWP or MSS SP-80, Class 125, gate valve; ASTM B 62 bronze body, with NPS 1/8 side drain outlet and cap. MISCELLANEOUS PIPING SPECIALTIES A. Water Hammer Arresters: ASSE 1010 or PDI-WH 201, piston type with pressurized metal-tube cushioning chamber. Sizes indicated are based on ASSE 1010, Sizes AA and A through F or PDI-WH 201, Sizes A through F. 1. B. Manufacturers: a. Amtrol, Inc. b. Smith, Jay R. Mfg. Co. c. Josam Co. d. MIFAB e. Precision Plumbing Products, Inc. f. Sioux Chief Mfg. Co. g. Watts Industries, Inc. h. Zurn Industries, Inc.; Wilkins Div. Hose Bibbs: Bronze body with replaceable seat disc complying with ASME A112.18.1M for compression-type faucets. Include NPS 1/2 or NPS 3/4 threaded or solder-joint inlet, of design suitable for pressure of at least 125 psig; integral or field-installed, nonremovable, drainable hose-connection vacuum breaker; and garden-hose threads complying with ASME B1.20.7 on outlet. 1. 2. 3. 4. 5. 6. 7. 8. Finish for Equipment Rooms: Rough bronze, chrome or nickel plated. Finish for Service Areas: Rough bronze, Chrome or nickel plated. Finish for Finished Rooms: Chrome or nickel plated. Operation for Equipment Rooms: Wheel handle or operating key. Operation for Service Areas: Wheel handle. Operation for Finished Rooms: Wheel handle. Include operating key with each operating-key hose bibb. Include integral wall flange with each chrome- or nickel-plated hose bibb. PART 3 - EXECUTION 3.01 INSTALLATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for piping joining materials, joint construction, and basic installation requirements. Lewiston Library Second Floor Remodel Project 15145-7 15025 B. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment and water systems that may be sources of contamination. Comply with authorities having jurisdiction. 1. 2. 3. 4. 5. Locate backflow preventers where indicated; in same room as connected equipment or system where possible if not specifically indicated. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap fitting, fixed air-gap fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to floor drain. Locate air-gap device attached to or under backflow preventer. Simple air breaks are not acceptable for this application. Backflow preventers installed more than 5 feet above floor or ground level shall have a permanent platform under for maintenance personnel to stand on. Do not install bypass piping around backflow preventers. Test each backflow prevention assembly by City of Lewiston certified tester at the time of installation. Furnish written report of test to Owner and authority having jurisdiction. C. Install pressure regulators with inlet and outlet shutoff valves and balance valve bypass. Install pressure gages on inlet and outlet. D. Install calibrated balancing valves of size specified at indicated locations. Transition from system piping size to balancing valve as required. E. Install strainers on supply side of each control valve, pressure regulator, and solenoid valve. F. Install plumbing pumps according to manufacturer's written instructions and with access for periodic maintenance, including removing motors, impellers, couplings, and accessories. G. Install thermostatic water mixing valves and required specialties in accordance with manufacturer’s instructions. Provide heat trap of recommended depth in hot water inlet piping where required by mixing valve location, check valves and adjusting valves as required. Adjust mixing valves in accordance with manufacturer’s instructions. Furnish written report to include in Operation and Maintenance Manual. H. Trap seal primers are not indicated on the Drawings. Trap seal primers shall be drainagetype used with flushometer valves. At locations remote from a flushometer valve fixture, trap seal primers shall be supply-type trap seal primer valves Locate trap seal primers in accessible locations. Where located in finished area, conceal in wall and provide access door. Install supply-type trap seal primer valves with outlet piping pitched down toward drain trap a minimum of 1 percent and connect to floor-drain, floor-sink, or open-hub drain or other drain body, trap, or inlet fitting. Adjust valve for proper flow. 1. Outlet Piping: Soft copper tube, Type K; CPVC “Gold” Schedule 40 with socket type fittings; or crosslinked polyethylene (PEX) tubing and barbed or compression adapter fittings Lewiston Library Second Floor Remodel Project 15145-8 15025 3.02 3.03 I. Size and install water hammer arresters in accordance with manufacturer’s recommendations and instructions. Install arresters at quick-closing valves, solenoid valves, and at each plumbing fixture or battery of fixtures in domestic water systems. Arrestors shall be accessible for servicing or replacement. J. Install individual shutoff valve in each water supply to water piping specialties. Use ball valve if specific valve is not indicated. Install shutoff valves in accessible locations. Refer to Division 15 Section "Valves" for general-duty ball, butterfly, check, gate, and globe valves. CONNECTIONS A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to equipment to allow service and maintenance. C. Install shutoff valve and strainer on suction side of circulator pumps, and check valve and balancing valve on discharge side of pumps. Install valves same size as connected piping. LABELING AND IDENTIFYING A. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each thermostatic water mixing valve and backflow preventer. 1. 3.04 Refer to Division 15 Section "Mechanical Identification" for nameplates and signs. FIELD QUALITY CONTROL A. Perform the following tests and prepare test reports: 1. Test each backflow preventer according to authorities having jurisdiction and the device’s reference standard. END OF SECTION 15145 Lewiston Library Second Floor Remodel Project 15145-9 15025 SECTION 15150 – SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes soil and waste, sanitary drainage and vent piping inside the building and to locations indicated. B. Related Sections include the following: 1. 2. 3. 1.03 DEFINITIONS A. The following are industry abbreviations for plastic piping materials: 1. 2. 1.04 Provide components and installation capable of producing piping systems with the following minimum working-pressure ratings, unless otherwise indicated: 1. Soil, Waste, and Vent Piping: 10-foot head of water SUBMITTALS A. 1.06 ABS: Acrylonitrile-butadiene-styrene plastic. PVC: Polyvinyl chloride plastic. PERFORMANCE REQUIREMENTS A. 1.05 Division 15 Section "Chemical-Waste Piping" for chemical-waste and vent piping systems. Division 15 Section "Drainage Piping Specialties" for soil, waste, and vent piping systems specialties. Division 15 Section "Sewage Pumps". Product Data: For pipe, tube, fittings, and couplings. QUALITY ASSURANCE A. Piping materials shall bear label, stamp, or other markings of specified testing agency. PART 2 - PRODUCTS 2.01 PIPING MATERIALS A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials. Lewiston Library Second Floor Remodel Project 15150-1 15025 2.02 2.03 HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS A. Pipe and Fittings: CISPI 301, ASTM A 888 or ASTM A 74, Service class. Pipe and fittings shall be marked with the collective trademark of the Cast Iron Soil Pipe Institute and be of domestic manufacturer. B. Gaskets: ASTM C 564, rubber. HUBLESS CAST-IRON SOIL PIPE AND FITTINGS A. Pipe and Fittings: CISPI 301, ASTM A 888 or ASTM A 74, Service class. Pipe and fittings shall be marked with the collective trademark of the Cast Iron Soil Pipe Institute and be of domestic manufacturer. B. Shielded Couplings: ASTM C 1540 / C 1277 assembly of metal shield or housing, corrosion-resistant fasteners, and ASTM C 564 rubber sleeve with integral, center pipe stop. 1. 2.04 COPPER TUBE AND FITTINGS A. Copper DWV Tube: ASTM B 306, drainage tube, drawn temper. 1. 2.05 2.06 Heavy-Duty, Type 304, Stainless-Steel Couplings: ASTM A 666, Type 304, stainless-steel shield (min. thickness 0.010 in.); stainless-steel bands; and sleeve. a. NPS 1-1/2 to NPS 4: 3-inch- wide shield with 4 bands. b. NPS 5 to NPS 10: 4-inch- wide shield with 6 bands. c. ANACO Husky SD 2000, Mission Rubber Co. Heavyweight (HW), or approved equal. Copper Drainage Fittings: ASME B16.23, cast copper or ASME B16.29, wrought copper, solder-joint fittings. ABS PIPE AND FITTINGS A. Cellular-Core, ABS Pipe: ASTM F 628, Schedule 40, drain, waste, and vent. B. ABS Socket Fittings: ASTM D 2661, made to ASTM D 3311, drain, waste, and vent patterns. PVC PIPE AND FITTINGS A. Cellular-Core PVC Pipe: ASTM F 891, Schedule 40, drain, waste, and vent. B. PVC Socket Fittings: ASTM D 2665, socket type, made to ASTM D 3311, drain, waste, and vent patterns. PART 3 - EXECUTION 3.01 EXCAVATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for excavating, trenching, and backfilling. Lewiston Library Second Floor Remodel Project 15150-2 15025 3.02 PIPING APPLICATIONS A. Transition and special fittings with pressure ratings at least equal to piping pressure ratings may be used in applications below, unless otherwise indicated. B. Aboveground, Soil, Waste, and Vent Piping: Use any of the following piping materials for each size range: 1. 2. 3. 4. 5. 6. C. Underground, Soil, Waste, and Vent Piping: Use any of the following piping materials for each size range: 1. 2. 3. 4. 5. 6. 7. 3.03 NPS 1-1/2 to NPS 6: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 1-1/2 to NPS 6: Copper DWV tube, copper drainage fittings, and soldered joints. NPS 1-1/2 to NPS 6: Cellular-core, ABS pipe; ABS socket fittings; and solventcemented joints. Not allowed in return air plenums. NPS 1-1/2 to NPS 6: PVC pipe, PVC socket fittings, and solvent-cemented joints. Not allowed in return air plenums. NPS 8: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 8: PVC pipe, PVC socket fittings, and solvent-cemented joints. Not allowed in return air plenums. NPS 2 to NPS 6: Service class, hub-and–spigot cast-iron soil pipe and fittings, gasketed joints. NPS 2 to NPS 6: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 2 to NPS 6: Cellular-core, ABS pipe; ABS socket fittings; and solventcemented joints. NPS 2 to NPS 6: PVC pipe, PVC socket fittings, and solvent-cemented joints. NPS 8 to NPS 12: Service class, hub-and–spigot cast-iron soil pipe and fittings, gasketed joints. NPS 8 to NPS 12: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 8 to NPS 12: PVC pipe, PVC socket fittings, and solvent-cemented joints. PIPING INSTALLATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping installation. B. Do not use ABS or PVC plastic piping in return air plenums. C. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary sewers. D. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for wall penetration systems. E. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings." Lewiston Library Second Floor Remodel Project 15150-3 15025 F. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long-sweep bends. Sanitary tees and short-sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. Use long-turn, double Y-branch and 1/8-bend fittings if 2 fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited. G. Install vent piping free from drops or sags, graded and connected as to drip back by gravity to the drainage pipe it serves. H. Lay buried building drainage piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed. I. Install soil and waste drainage and vent piping at the following minimum slopes, unless otherwise indicated: 1. 2. 3.04 Horizontal Sanitary Drainage Piping: 2 percent downward in direction of flow for piping NPS 3 and smaller; 1 percent downward in direction of flow for piping NPS 4 and larger. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack. J. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing. K. Install ABS soil and waste drainage and vent piping according to ASTM D 2661. L. Install PVC soil and waste drainage and vent piping according to ASTM D 2665. M. Prime and paint (chrome or silver finish) all exposed waste drainage piping in Food Service fixture applications. N. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. JOINT CONSTRUCTION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping joint construction. B. Cast-Iron, Soil-Piping Joints: Make joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings." 1. 2. C. Gasketed Joints: Make with rubber gasket matching class of pipe and fittings. Hubless Joints: Make with rubber gasket and sleeve or clamp. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, leadfree-alloy solder; and ASTM B 828 procedure, unless otherwise indicated. Lewiston Library Second Floor Remodel Project 15150-4 15025 D. 3.05 PVC Nonpressure Piping Joints: Join piping according to ASTM D 2665. HANGER AND SUPPORT INSTALLATION A. Refer to Division 15 Section "Hangers and Supports" for pipe hanger and support devices. B. Install supports according to Division 15 Section "Hangers and Supports." C. Support vertical piping and tubing at base and at each floor. D. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch minimum rods. E. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. 6. NPS 1-1/2 and NPS 2: 60 inches with 3/8-inch rod. NPS 3: 60 inches with 1/2-inch rod. NPS 4 and NPS 5: 60 inches with 5/8-inch rod. NPS 6: 60 inches with 3/4-inch rod. NPS 8 to NPS 12: 60 inches with 7/8-inch rod. Spacing for 10-foot lengths may be increased to 10 feet. Spacing for fittings is limited to 60 inches. F. Install supports for vertical cast-iron soil piping every 15 feet. G. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. NPS 1-1/4: 72 inches with 3/8-inch rod. NPS 1-1/2 and NPS 2: 96 inches with 3/8-inch rod. NPS 2-1/2: 108 inches with 1/2-inch rod. NPS 3 to NPS 5: 10 feet with 1/2-inch rod. NPS 6: 10 feet with 5/8-inch rod. H. Install supports for vertical copper tubing every 10 feet. I. Install hangers for ABS and PVC piping with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. NPS 1-1/2 and NPS 2: 48 inches with 3/8-inch rod. NPS 3: 48 inches with 1/2-inch rod. NPS 4 and NPS 5: 48 inches with 5/8-inch rod. NPS 6: 48 inches with 3/4-inch rod. NPS 8 to NPS 12: 48 inches with 7/8-inch rod. J. Install supports for vertical ABS and PVC piping every 48 inches. K. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions. Lewiston Library Second Floor Remodel Project 15150-5 15025 3.06 CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting to join dissimilar piping materials. C. Connect drainage and vent piping to the following: 1. 2. 3. 4. 3.07 FIELD QUALITY CONTROL A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction. 1. 2. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements. B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection. C. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows: 1. 2. 3. 4. 3.08 Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required by plumbing code. Refer to Division 15 Section "Plumbing Fixtures." Plumbing Fixtures and Equipment: Connect atmospheric vent piping in sizes indicated, but not smaller than required by authorities having jurisdiction. Plumbing Specialties: Connect drainage and vent piping in sizes indicated, but not smaller than required by plumbing code. Refer to Division 15 Section "Drainage Piping Specialties." Equipment: Connect drainage piping as indicated. Provide shutoff valve, if indicated, and union or flange for each connection. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested. Leave uncovered and unconcealed new, altered, extended, or replaced drainage and vent piping until it has been tested and approved. Expose work that was covered or concealed before it was tested. Roughing-in Plumbing Test Procedure: Test drainage and vent piping, except outside leaders, on completion of roughing-in. Close openings in piping system and fill with water to point of overflow, but not less than 10-foot head of water. From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained. CLEANING A. Clean interior of piping. Remove dirt and debris as work progresses. Lewiston Library Second Floor Remodel Project 15150-6 15025 B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. C. Place plugs in ends of uncompleted piping at end of day and when work stops. END OF SECTION 15150 Lewiston Library Second Floor Remodel Project 15150-7 15025 SECTION 15155- DRAINAGE PIPING SPECIALTIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following drainage piping specialties: 1. 2. 3. 4. 5. B. Related Sections include the following: 1. 1.03 The following are industry abbreviations for plastic piping materials: 1. 2. Provide components and installation capable of producing piping systems with following minimum working-pressure ratings, unless otherwise indicated: 1. 2. Sanitary Waste and Vent Piping: 10-foot head of water. Storm Drainage Piping: 10-foot head of water. SUBMITTALS A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, and accessories for the following: 1. B. 1.06 ABS: Acrylonitrile-butadiene-styrene plastic. PVC: Polyvinyl chloride plastic. PERFORMANCE REQUIREMENTS A. 1.05 Division 15 Section "Meters and Gages" for thermometers, and pressure gages. DEFINITIONS A. 1.04 Miscellaneous piping specialties Sleeve penetration systems Flashing materials Cleanouts Roof drains Solids interceptors. Maintenance Data: For drainage piping specialties to include in operation and maintenance manuals. QUALITY ASSURANCE A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing agency. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. Lewiston Library Second Floor Remodel Project 15155-1 15025 C. NSF Compliance: 1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic piping components. Include marking "NSF-DWV" on plastic drain, waste, and vent piping. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. 2.02 Manufacturers: Subject to compliance with requirements, provide products by the manufacturers listed. MISCELLANEOUS DRAINAGE PIPING SPECIALTIES A. Air-Admittance Valves: Plastic housing with mechanical-operation sealing diaphragm, designed to admit air into drainage and vent piping and to prevent transmission of sewer gas into building. 1. 2. 3. B. Manufacturers: a. Oatey. b. Sioux Chief Mfg. Co. c. Studor, Inc. Stack Vent Valve: ASSE 1050, designed for installation as terminal on soil, waste, and vent stacks, instead of stack vent extending through roof, in NPS 2 to NPS 4. Fixture Vent Valve: ASSE 1051, designed for installation on waste piping, instead of vent connection, for single fixture, in NPS 1-1/4 to NPS 2. Roof Flashing Assemblies: Manufactured assembly made of 4-lb/sq. ft., 0.0625-inchthick, lead flashing collar and skirt extending at least 10 inches from pipe with galvanized steel boot reinforcement, and counter flashing fitting. 1. 2. 3. 4. Manufacturers: a. Acorn Engineering Company; Elmdor/Stoneman Div. Open-Top Vent Cap: Without cap. Low-Silhouette Vent Cap: With vandal-proof vent cap. Extended Vent Cap: With field-installed, vandal-proof vent cap. C. Roof Piping and Conduit Flashings: One-piece, 18” x 18” 24 gage galvanized steel base with friction-seal, elastomeric sealing collar. D. Fixed Air-Gap Fittings: Manufactured cast-iron or bronze drainage fitting with semiopen top with threads or device to secure drainage inlet piping in top and bottom spigot or threaded outlet larger than top inlet. Include design complying with ASME A112.1.2 that will provide fixed air gap between installed inlet and outlet piping. E. Vent Caps: Cast-iron body with threaded or hub inlet and vandal-proof design. Include vented hood and set-screws to secure to vent pipe. F. Mushroom Vent Caps: Molded ABS plastic body with 3 set-screws to secure to vent pipe. Lewiston Library Second Floor Remodel Project 15155-2 15025 G. Expansion Joints: ASME A112.21.2M, assembly with cast-iron body with bronze sleeve, packing gland, and packing; of size and end types corresponding to connected piping. H. Downspout Boots: ASTM A 48, gray-iron casting, with NPS 4 outlet; shop-applied bituminous coating; and inlet size to match downspout. I. Downspout Nozzle: Bronze body with threaded inlet for connected conductor size, bronze wall flange with mounting holes and bird screen. 1. J. Solids Interceptors: 1. 2. 3. 4. 2.03 Manufacturers: 1. 2. B. Hubbard Enterprises. ProSet Systems, Inc. Description: UL 1479, through-penetration firestop assembly consisting of sleeve and stack fitting with firestopping plug. 1. 2. Sleeve: Molded PVC plastic, of length to match slab thickness and with integral nailing flange on one end for installation in cast-in-place concrete slabs. Stack Fitting: ASTM A 48, gray-iron, hubless-pattern, wye-branch stack fitting with neoprene O-ring at base and gray-iron plug in thermal-release harness in branch. Include PVC protective cap for plug. FLASHING MATERIALS A. Lead Sheet: ASTM B 749, Type L51121, copper bearing, with the following minimum weights and thicknesses, unless otherwise indicated: 1. 2.05 Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings: Type: Factory-fabricated interceptor made for removing and retaining sediment, plaster from wastewater. Body Material: Plastic. Mounting: Above floor, inline. SLEEVE PENETRATION SYSTEMS A. 2.04 Downspout Nozzle Schedule (Reference Manufacturer: Smith, Jay R. Mfg. Co): Smith, Jay R.; Fig. 1770-BS. General Use: 4-lb/sq. ft., 0.0625-inch thickness. B. Elastic Membrane Sheet: minimum thickness. ASTM D 4068, flexible, chlorinated polyethylene, 40-mil C. Fasteners: Metal compatible with material and substrate being fastened. CLEANOUTS A. Manufacturers: 1. 2. 3. 4. Josam Co. MIFAB Sioux Chief Mfg. Co. Smith, Jay R. Mfg. Co. Lewiston Library Second Floor Remodel Project 15155-3 15025 5. 6. 7. B. Cleanouts, General: Comply with ASME A112.36.2M. 1. 2. 3. 4. 5. 6. 7. 8. C. Body or Ferrule Material: Cast iron. Clamping Device: Required. Outlet Connection: Spigot or no-hub. Closure: Brass plug with tapered threads. Adjustable Housing Material: Cast iron with threads. Frame and Cover Material and Finish: Nickel-bronze. Frame and Cover Shape: Round. Top Loading Classification: Light Duty for finished interior floor service; Heavy Traffic Duty for exterior service. Cleanout Schedule (Reference Manufacturer: Smith, Jay R. Mfg. Co): 1. 2. 3. 4. 5. 2.06 Tyler Pipe, Wade Div. Watts Industries, Inc., Drainage Products Div. Zurn Industries, Inc., Specification Drainage Operation Finished Floor: Carpeted Floor: Terrazzo Floor: Wall: Exterior: Smith, Jay R.; Fig. 4023S or Fig. 4033L. Smith, Jay R.; Fig. 4023S-X or Fig. 4033L-X. Smith, Jay R.; Fig. 4183S or Fig. 4193L. Smith, Jay R.; Fig. 4422C. Smith, Jay R.; Fig. 4253S or Fig. 4263L. ROOF DRAINS A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. B. Roof Drains, General: Comply with ASME A112.21.1M. 1. 2. 3. 4. 5. 6. 7. C. Josam Co. MIFAB Sioux Chief Mfg. Co. Smith, Jay R. Mfg. Co. Tyler Pipe, Wade Div. Watts Industries, Inc., Drainage Products Div. Zurn Industries, Inc., Specification Drainage Operation Body Material: Cast iron. Combination Flashing Ring and Gravel Stop: Required. Outlet: Bottom. Dome Material: Cast iron. Extension Collars: Required. Underdeck Clamp: Required. Sump Receiver: Required. Roof Drain Schedule (Reference Manufacturer: Smith, Jay R. Mfg. Co): 1. 2. RD-1 (primary roof drain, 16-inch diameter with low profile dome): Smith, Jay R.; Fig. 1010-C-R-E-CID. RD-2 (overflow roof drain, 16-inch diameter with low profile dome and 2-inch high water dam): Smith, Jay R.; Fig. 1080-C-R-E-CID. Lewiston Library Second Floor Remodel Project 15155-4 15025 PART 3 - EXECUTION 3.01 INSTALLATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for piping joining materials, joint construction, and basic installation requirements. B. Install expansion joints on vertical risers, stacks, and conductors if indicated. C. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated: 1. 2. 3. 4. 5. 6. 7. 8. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated. Locate at each change in direction of piping greater than 45 degrees. Locate at minimum intervals of 50 feet for piping NPS 4 and smaller and 100 feet for larger piping. Locate at base of each vertical soil and waste stack. Locate at upper terminal of all horizontal drain lines that exceed 5 feet from drainage mains. Cleanouts not required for horizontal drain lines less than 5 feet from drainage mains, unless serving sinks or urinals. Locate above each urinal. Locate below each sink and mop sink. Locate as required by the applicable Plumbing Code. D. Install cleanouts with top flush with finished floor, for floor cleanouts for piping below floors. E. Install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall, for cleanouts located in concealed piping. F. Install flashing flange and clamping device with each stack and cleanout passing through floors with waterproof membrane. G. Install wall cleanouts with horizontal clearance for access: 1. 2. 2-inch diameter piping or less: 12-inches minimum. Piping larger than 2-inches diameter: 18-inches minimum. H. Install cleanouts for under floor piping with minimum 18-inches vertical clearance and 30-inches horizontal clearance for access. I. Install vent flashing sleeves on stacks passing through roof. Secure over stack flashing according to manufacturer's written instructions. J. Install downspout nozzles at 12-inches above grade or as indicated. K. Install roof drains at low points of roof areas according to roof membrane manufacturer's written installation instructions. 1. 2. Install roof-drain flashing collar or flange so no leakage occurs between drain and adjoining roofing. Maintain integrity of waterproof membranes where penetrated. Position roof drains for easy access and maintenance. Lewiston Library Second Floor Remodel Project 15155-5 15025 3.02 L. Install traps on piping specialty drain outlets. Omit traps on indirect wastes unless trap is indicated. M. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding pipe fittings. CONNECTIONS A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to equipment to allow service and maintenance. C. Connect drainage piping specialties to piping specified in other Division 15 Sections. D. Interceptor Connections: Connect piping, flow-control fittings, and accessories. 1. 3.03 FLASHING INSTALLATION A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes are required. Join flashing according to the following if required: 1. B. Lead Sheets: Solder joints of lead sheets 4-lb/sq. ft., 0.0625-inch thickness or thinner. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in floors with waterproof membrane. 1. 2. 3. 3.04 Solids Interceptors: Connect inlet and outlet. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 10 inches, and skirt or flange extending at least 8 inches around pipe. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 8 inches around sleeve. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least 8 inches around specialty. C. Set flashing on floors in solid coating of bituminous cement. D. Install flashing for piping and conduit passing through roofs with counter flashing or commercially made flashings. LABELING AND IDENTIFYING A. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each grease interceptor, grease recovery unit and oil interceptor. 1. Refer to Division 15 Section "Mechanical Identification" for nameplates and signs. Lewiston Library Second Floor Remodel Project 15155-6 15025 3.05 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled grease recovery units and their installation, including piping and electrical connections. Report results in writing. 1. 2. 3.06 Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. PROTECTION A. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. B. Place plugs in ends of uncompleted piping at end of each day or when work stops. END OF SECTION 15155 Lewiston Library Second Floor Remodel Project 15155-7 15025 SECTION 15160 - STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes storm-drainage (rainwater) piping inside the building and to locations indicated. B. Related Sections include the following: 1. 2. 1.03 DEFINITIONS A. The following are industry abbreviations for plastic piping materials: 1. 2. 1.04 Provide components and installation capable of producing piping systems with the following minimum working-pressure ratings, unless otherwise indicated: 1. Storm Drainage Piping: 10-foot head of water SUBMITTALS A. 1.06 ABS: Acrylonitrile-butadiene-styrene plastic. PVC: Polyvinyl chloride plastic. PERFORMANCE REQUIREMENTS A. 1.05 Division 15 Section "Drainage Piping Specialties" for storm drainage piping system specialties. Division 15 Section "Sump Pumps." Product Data: For pipe, tube, fittings, and couplings. QUALITY ASSURANCE A. Piping materials shall bear label, stamp, or other markings of specified testing agency. PART 2 - PRODUCTS 2.01 PIPING MATERIALS A. 2.02 Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials. HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS A. Pipe and Fittings: CISPI 301, ASTM A 888 or ASTM A 74, Service class. Pipe and fittings shall be marked with the collective trademark of the Cast Iron Soil Pipe Institute and be of domestic manufacturer. Lewiston Library Second Floor Remodel Project 15160-1 15025 B. 2.03 Gaskets: ASTM C 564, rubber. HUBLESS CAST-IRON SOIL PIPE AND FITTINGS A. Pipe and Fittings: CISPI 301, ASTM A 888 or ASTM A 74, Service class. Pipe and fittings shall be marked with the collective trademark of the Cast Iron Soil Pipe Institute and be of domestic manufacturer. B. Shielded Couplings: ASTM C 1540 / C 1277 assembly of metal shield or housing, corrosion-resistant fasteners, and ASTM C 564 rubber sleeve with integral, center pipe stop. 1. 2.04 COPPER TUBE AND FITTINGS A. Copper DWV Tube: ASTM B 306, drainage tube, drawn temper. 1. 2.05 2.06 Heavy-Duty, Type 304, Stainless-Steel Couplings: ASTM A 666, Type 304, stainless-steel shield (min. thickness 0.010 in.); stainless-steel bands; and sleeve. a. NPS 1-1/2 to NPS 4: 3-inch- wide shield with 4 bands. b. NPS 5 to NPS 10: 4-inch- wide shield with 6 bands. c. ANACO Husky SD 2000, Mission Rubber Co. Heavyweight (HW), or approved equal. Copper Drainage Fittings: ASME B16.23, cast copper or ASME B16.29, wrought copper, solder-joint fittings. ABS PIPE AND FITTINGS A. Cellular-Core, ABS Pipe: ASTM F 628, Schedule 40, drain, waste, and vent. B. ABS Socket Fittings: ASTM D 2661, made to ASTM D 3311, drain, waste, and vent patterns. PVC PIPE AND FITTINGS A. Cellular-Core PVC Pipe: ASTM F 891, Schedule 40, drain, waste, and vent. B. PVC Socket Fittings: ASTM D 2665, socket type, made to ASTM D 3311, drain, waste, and vent patterns. PART 3 - EXECUTION 3.01 EXCAVATION A. 3.02 Refer to Division 15 Section "Basic Mechanical Materials and Methods" for excavating, trenching, and backfilling. PIPING APPLICATIONS A. Transition and special fittings with pressure ratings at least equal to piping pressure ratings may be used in applications below, unless otherwise indicated. Lewiston Library Second Floor Remodel Project 15160-2 15025 B. Aboveground Storm Drainage Piping: Use any of the following piping materials for each size range: 1. 2. 3. 4. 5. 6. 3.03 NPS 1-1/2 to NPS 6: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 1-1/2 to NPS 6: Copper DWV tube, copper drainage fittings, and soldered joints. NPS 1-1/2 to NPS 6: Cellular-core, ABS pipe; ABS socket fittings; and solventcemented joints. Not allowed in return air plenums. NPS 1-1/2 to NPS 6: PVC pipe, PVC socket fittings, and solvent-cemented joints. Not allowed in return air plenums. NPS 8: Hubless, cast-iron soil pipe and fittings, heavy-duty stainless steel couplings. NPS 8: PVC pipe, PVC socket fittings, and solvent-cemented joints. Not allowed in return air plenums. PIPING INSTALLATION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping installation. B. Do not use ABS or PVC plastic piping in return air plenums. C. Install cleanouts at grade and extend to where building storm drains connect to building storm sewers. D. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for wall penetration systems. E. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings." F. Make changes in direction for storm piping using appropriate branches, bends, and longsweep bends. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited. G. Lay buried building drain piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed. H. Install storm drainage piping at the following minimum slopes, unless otherwise indicated: 1. I. Horizontal Storm-Drainage Piping: 2 percent downward in direction of flow for piping NPS 3 and smaller; 1 percent downward in direction of flow for piping NPS 4 and larger. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing. Lewiston Library Second Floor Remodel Project 15160-3 15025 3.04 J. Install ABS storm drainage piping according to ASTM D 2661. K. Install PVC storm drainage piping according to ASTM D 2665. L. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. JOINT CONSTRUCTION A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping joint construction. B. Cast-Iron, Soil-Piping Joints: Make joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings." 1. 2. 3.05 Gasketed Joints: Make with rubber gasket matching class of pipe and fittings. Hubless Joints: Make with rubber gasket and sleeve or clamp. C. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, leadfree-alloy solder; and ASTM B 828 procedure, unless otherwise indicated. D. PVC Nonpressure Piping Joints: Join piping according to ASTM D 2665. HANGER AND SUPPORT INSTALLATION A. Refer to Division 15 Section "Hangers and Supports" for pipe hanger and support devices. B. Install supports according to Division 15 Section "Hangers and Supports." C. Support vertical piping and tubing at base and at each floor. D. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch minimum rods. E. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. 6. NPS 2: 60 inches with 3/8-inch rod. NPS 3: 60 inches with 1/2-inch rod. NPS 4 and NPS 5: 60 inches with 5/8-inch rod. NPS 6: 60 inches with 3/4-inch rod. NPS 8 to NPS 12: 60 inches with 7/8-inch rod. Spacing for 10-foot lengths may be increased to 10 feet. Spacing for fittings is limited to 60 inches. F. Install supports for vertical cast-iron soil piping every 15 feet. G. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. NPS 2: 96 inches with 3/8-inch rod. NPS 2-1/2: 108 inches with 1/2-inch rod. NPS 3 to NPS 5: 10 feet with 1/2-inch rod. Lewiston Library Second Floor Remodel Project 15160-4 15025 4. 5. H. Install supports for vertical copper tubing every 10 feet. I. Install hangers for ABS and PVC piping with the following maximum horizontal spacing and minimum rod diameters: 1. 2. 3. 4. 5. 3.06 3.07 NPS 6: 10 feet with 5/8-inch rod. NPS 8: 10 feet with 3/4-inch rod. NPS 2: 48 inches with 3/8-inch rod. NPS 3: 48 inches with 1/2-inch rod. NPS 4 and NPS 5: 48 inches with 5/8-inch rod. NPS 6: 48 inches with 3/4-inch rod. NPS 8 to NPS 12: 48 inches with 7/8-inch rod. J. Install supports for vertical ABS and PVC piping every 48 inches. K. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions. CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect interior storm drainage piping to exterior storm drainage piping. Use transition fitting to join dissimilar piping materials. C. Connect storm drainage piping to roof drains and storm drainage specialties. FIELD QUALITY CONTROL A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction. 1. 2. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements. B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection. C. Test storm drainage piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows: 1. 2. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested. Leave uncovered and unconcealed new, altered, extended, or replaced storm drainage piping until it has been tested and approved. Expose work that was covered or concealed before it was tested. Lewiston Library Second Floor Remodel Project 15160-5 15025 3. 4. 3.08 Test Procedure: Test storm drainage piping on completion of roughing-in. Close openings in piping system and fill with water to point of overflow, but not less than 10-foot head of water. From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained. CLEANING A. Clean interior of piping. Remove dirt and debris as work progresses. B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. C. Place plugs in ends of uncompleted piping at end of day and when work stops. END OF SECTION 15160 Lewiston Library Second Floor Remodel Project 15160-6 15025 SECTION 15194 - GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes natural gas piping, specialties, and accessories within the building and to locations indicated. Products include the following: 1. 2. 3. 4. 5. 6. 1.03 1.04 PROJECT CONDITIONS A. Gas System Pressure: One pressure range. 0.5 psig (14 inches w.c.) or less. B. Gas System Pressures: Two pressure ranges. Primary pressure is at least 2.0 psig but not more than 5.0 psig, and is reduced to secondary pressure of 0.5 psig (14 inches w.c.) or less. SUBMITTALS A. Product Data: For the following: 1. 2. 3. 4. B. 1.05 Pipe, tube, fittings, and joining materials. Protective pipe and fitting coating. Piping specialties. Specialty valves. Service meters. Pressure regulators. Corrugated, stainless-steel tubing systems. Include associated components. Specialty valves. Include pressure rating, capacity, settings, and electrical connection data of selected models. Service meters. Include pressure rating and capacity of selected models. Pressure regulators. Include pressure rating, capacity, and settings of selected models. Operation and Maintenance Data: For natural gas specialties and accessories to include in operation and maintenance manuals. QUALITY ASSURANCE A. Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX. B. Electrical Components and Devices: Listed and labeled as defined in NFPA 70, Article 100, by testing agency acceptable to authorities having jurisdiction, and marked for intended use. C. ANSI Standard: Comply with ANSI Z223.1, "National Natural Gas Code." Lewiston Library Second Floor Remodel Project 15194-1 15025 1.06 D. FM Standard: Provide components listed in FM's "Fire Protection Approval Guide" if specified to be FM approved. E. IAS Standard: Provide components listed in IAS's "Directory of A. G. A. and C. G. A Certified Appliances and Accessories" if specified to be IAS listed. F. UL Standard: Provide components listed in UL's "Gas and Oil Equipment Directory" if specified to be UL listed. CODES AND STANDARDS A. Code Compliance: Comply with most current adopted edition of following: 1. 1.07 International Natural Gas Code (IFGC). COORDINATION A. Existing Utilities: Do not interrupt utilities serving facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary utility services according to requirements indicated: 1. 2. B. Notify Architect not less than two days in advance of proposed utility interruptions. Do not proceed with utility interruptions without Architect's written permission. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. 2. 3. 4. Corrugated, Stainless-Steel Tubing Systems: a. Omega Flex, Inc. b. Titeflex Corp. c. Tru-Flex Metal Hose Corp. d. Ward Industries, Inc. Piping Specialties: a. Dormont Manufacturing Co. b. T&S Brass Appliance Connector Valves: a. American Valve. b. B&K Industries, Inc. c. Brass Craft Manufacturing Co. d. Conbraco Industries, Inc.; Apollo Div. e. Jomar International, Ltd. f. Mueller Co.; Mueller Gas Products Div. g. Watts Industries, Inc.; Water Products Div. Gas Valves, NPS 2 and Smaller: a. Hammond Valve b. Jomar International, Ltd. c. Kitz Corp. of America. Lewiston Library Second Floor Remodel Project 15194-2 15025 5. 6. 7. 8. 2.02 PIPING MATERIALS A. 2.03 Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials. CORRUGATED, STAINLESS-STEEL TUBING SYSTEMS A. Description: Comply with AGA LC 1 and include the following: 1. 2. 3. 4. 2.04 d. Milwaukee Valve Co., Inc. e. Mueller Co.; Mueller Gas Products Div. f. Nibco, Inc. g. Watts Industries, Inc.; Water Products Div. Plug Valves, NPS 2-1/2 and Larger: a. Flow Control Equipment, Inc. b. Milliken Valve Co., Inc. c. Nordstrom Valves, Inc. d. Olson Technologies, Inc.; Homestead Valve Div. e. Walworth Co. Electrically Operated Gas Valves: a. ASCO General Controls. b. Atkomatic Valve Co., Inc. c. Automatic Switch Co. Service Meters: a. American Meter Co. b. Badger Meter, Inc.; Utility Products Div. c. Invensys. d. National Meter Industries, Inc. e. Sensus. Line Pressure Regulators: a. American Meter Co. b. Fisher Controls International, Inc. c. Maxitrol Co. d. National Meter Industries, Inc. e. Sensus. Tubing: Corrugated stainless steel with plastic jacket or coating. Fittings: Copper alloy with ends made to fit corrugated tubing. Include ends with threads according to ASME B1.20.1 if connection to threaded pipe or fittings is required. Striker Plates: Steel, designed to protect tubing from penetrations. Manifolds: Malleable iron or steel with protective coating. Include threaded connections according to ASME B1.20.1 for pipe inlet and corrugated tubing outlets. PIPES, TUBES, FITTINGS, AND JOINING MATERIALS A. Steel Pipe: ASTM A 53, Schedule 40, black. 1. 2. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern, with threaded ends according to ASME B1.20.1. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and threaded ends according to ASME B1.20.1. Lewiston Library Second Floor Remodel Project 15194-3 15025 3. 4. 5. 6. 7. 8. B. 2.05 Transition Fittings: Type, material, and end connections to match piping being joined. PROTECTIVE COATING A. 2.06 Furnish pipe and fittings with factory-applied, corrosion-resistant polyethylene coating for use with underground piping. PIPING SPECIALTIES A. Flexible Connectors: ANSI Z21.24, copper alloy. B. Quick-Disconnect Devices: connector. C. Appliance Gas Connectors for Moveable Equipment: ANSI Z21.69, ANSI Z21.41, ANSI Z21.24, installation kit complete with flexible gas connector, “push-to-connect” quickdisconnect with integral thermal shut-off, flared design end fittings, and coiled restraining device with mounting hardware. 1. 2. 3. 4. 5. 6. 7. 2.07 Cast-Iron Flanges and Flanged Fittings: ASME B16.1, Class 125. Steel Welding Fittings: ASME B16.9, wrought steel or ASME B16.11, forged steel. Steel Threaded Fittings: ASME B16.11, forged steel with threaded ends according to ASME B1.20.1. Joint Compound and Tape: Suitable for natural gas. Steel Flanges and Flanged Fittings: ASME B16.5. Gasket Material: Thickness, material, and type suitable for natural gas. ANSI Z21.41, convenience outlets and matching plug Connector Tubing: Annealed Type 304 stainless steel. Connector Braiding: Multi-strand Type 304 stainless steel. Connector Coating: PVC dipped coating, NSF certified. Quick Disconnect: Brass body, carbon steel threaded end fittings, aluminum collar. Thermal Shut-off: Polymer insert in quick-disconnect melts when temperatures exceed 350 deg.F, to shut off gas flow. End Fittings: Carbon steel with zinc and yellow dichromate coating; flared design. Restraining Cable: PVC coated, carbon steel multi-stand cable. SPECIALTY VALVES A. Valves, NPS 2 and Smaller: Threaded ends according to ASME B1.20.1 for pipe threads. B. Butterfly Valves, NPS 2 and Smaller: Bronze body, stainless steel disc, stem and nut, viton disc seal, AGA certified, UL Listed, threaded ends according to ASME B1.20.1 for pipe threads. 1. Milwaukee “Butterball” BB2-100, or equal. C. Valves, NPS 2-1/2 and Larger: Flanged ends according to ASME B16.5 for steel flanges and according to ASME B16.24 for copper and copper-alloy flanges. D. Appliance Connector Valves: ANSI Z21.15 and CSA International-listed. Lewiston Library Second Floor Remodel Project 15194-4 15025 E. Gas Stops: Bronze body with AGA stamp, plug type with bronze plug and flat or square head, ball type with chrome-plated brass ball and lever handle, or butterfly valve with stainless-steel disc and fluorocarbon elastomer seal and lever handle; 2-psig minimum pressure rating. F. Gas Valves, NPS 2 and Smaller: ASME B16.33 and CSA International-listed bronze body and 125-psig pressure rating. G. Plug Valves, NPS 2-1/2 and Larger: ASME B16.38 and MSS SP-78 cast-iron, lubricated plug valves, with 125-psig pressure rating. H. General-Duty Valves, NPS 2-1/2 and Larger: ASME B16.38, cast-iron body, suitable for natural gas service, with "WOG" indicated on valve body, and 125-psig pressure rating. 1. 2. I. 2.08 Electrically Operated, Gas Safety Shutoff Valves: UL 429, aluminum body solenoid valve; 120-V ac, 60 Hz, Class B, continuous-duty molded coil. Include NEMA ISC 6, Type 4, coil enclosure and electrically opened and closed dual coils. Valve position shall normally be closed. ASCO 8215 Series or equal. SERVICE METERS A. Service Meters: Positive-displacement type suitable for natural gas service. Include metal case, temperature compensation, corrosion-resistant internal components, and flow registered in cubic feet. 1. 2. 3. 2.09 Gate Valves: MSS SP-70, OS&Y type with solid wedge. Butterfly Valves: MSS SP-67, lug type with lever handle. NPS 2 and Smaller: Threaded ends according to ASME B1.20.1 for pipe threads. NPS 2-1/2 and Larger: Flanged ends according to ASME B16.5 for steel flanges and according to ASME B16.24 for copper and copper-alloy flanges. Type: ANSI B109.1, diaphragm. PRESSURE REGULATORS A. Description: Single-stage, lock-up design, suitable for natural gas service. Include steel jacket and corrosion-resistant components, elevation compensator, and atmospheric vent. Regulator seat shall seal the regulator orifice when the connected appliance or equipment is off and there is no demand for gas. 1. 2. 3. B. NPS 2 and Smaller: Threaded ends according to ASME B1.20.1 for pipe threads. NPS 2-1/2 and Larger: Flanged ends according to ASME B16.5 for steel flanges and according to ASME B16.24 for copper and copper-alloy flanges. Line Pressure Regulators: ANSI Z21.80 with 2-psig- minimum inlet pressure rating. Pressure Regulator Vents: Factory- or field-installed, corrosion-resistant screen in opening if not connected to vent piping. Lewiston Library Second Floor Remodel Project 15194-5 15025 PART 3 - EXECUTION 3.01 EXAMINATION A. Examine roughing-in for natural gas piping system to verify actual locations of piping connections before equipment installation. 1. 3.02 PREPARATION A. 3.03 Close equipment shutoff valves before turning off natural gas to premises or section of piping. Perform leakage test as specified in "Field Quality Control" Article to determine that all equipment is turned off in affected piping section. SERVICE ENTRANCE PIPING A. Extend natural gas piping and connect to natural gas distribution for service entrance to building. 1. 3.04 Exterior natural gas distribution system piping, service pressure regulator, and service meter will be provided by gas utility. SERVICE-METER INSTALLATION A. Install service-meter aboveground. 1. Set service-meter assembly on, or supported over, precast concrete bases. Set bases level with top surface projecting 3 inches above finished grade. Concrete bases are specified in Division 15 Section "Basic Mechanical Materials and Methods." B. Include gas valve or plug valve, [strainer,] [service pressure regulator,] [service-meter bar for service meter with connections NPS 1 and smaller,] [and service meter] for each assembly. C. Install gas valve or plug valve and strainer upstream from each service pressure regulator. D. Install service pressure regulators with vent outlet turned down and with corrosionresistant-metal insect screen. E. Install service meters downstream from service pressure regulators. 1. 2. 3.05 Proceed with installation only after unsatisfactory conditions have been corrected. Service meters with connections NPS 1 and smaller on meter bars. Service meters with connections larger than NPS 1 supported from piping or set on concrete bases. PIPING APPLICATIONS A. Flanges, unions, transition, and special fittings with pressure ratings same as or higher than system pressure rating may be used in applications below, unless otherwise indicated. Lewiston Library Second Floor Remodel Project 15194-6 15025 B. Natural Gas Piping: Use any of the following piping materials for each size range: 1. 2. 3. 4. 5. 6. C. 3.06 3.07 NPS 1/2 and Smaller: Steel pipe, malleable-iron threaded fittings, and threaded joints. NPS 1/2 and Smaller: Corrugated, stainless-steel tubing system and threaded joints. NPS 3/4 and NPS 1: Steel pipe, malleable-iron threaded fittings, and threaded joints. NPS 3/4 and NPS 1: Corrugated, stainless-steel tubing system and threaded joints. NPS 1-1/4 to NPS 2: Steel pipe, malleable-iron threaded fittings, and threaded joints. NPS 2-1/2 and Larger: Steel pipe, steel welding fittings, and welded joints. Underground Natural Gas Piping: Steel pipe, steel welding fittings, and welded joints with protective coating. VALVE APPLICATIONS A. Appliance Shutoff Valves for Pressure 0.5 psig or Less: Appliance connector valve or gas stop. B. Appliance Shutoff Valves for Pressure 0.5 to 2 psig: Gas stop or gas valve. C. Appliance Shutoff Valves for Pressure 2 to 5 psig: Gas valve. D. Piping Line Valves, NPS 2 and Smaller: Gas valve. E. Piping Line Valves, NPS 2-1/2 and Larger: Plug valve or general-duty valve. F. Valves at Service Meter, NPS 2 and Smaller: Gas valve. G. Valves at Service Meter, NPS 2-1/2 and Larger: Plug valve. PIPING INSTALLATION A. Basic piping installation requirements are specified in Division 15 Section "Basic Mechanical Materials and Methods". B. Concealed Locations: Except as specified below, install concealed gas piping in airtight conduit constructed of Schedule 40, seamless, black steel pipe with welded joints. Vent conduit to outside and terminate with screened vent cap. 1. Above-Ceiling Locations: Gas piping may be installed in accessible spaces, subject to approval of authorities having jurisdiction, whether or not such spaces are used as plenums. Lewiston Library Second Floor Remodel Project 15194-7 15025 2. 3. 4. 5. 6. C. In Floors: Gas piping with welded joints and protective wrapping specified in "Protective Coating" Article in Part 2 may be installed in floors, subject to approval of authorities having jurisdiction. Surround piping cast in concrete slabs with minimum of 1-1/2 inches of concrete. Piping may not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. Do not embed piping in concrete slabs containing quick-set additives or cinder aggregate. In Floor Channels: Gas piping may be installed in floor channels, subject to approval of authorities having jurisdiction. Channels must have cover and be open to space above cover for ventilation. In Partitions: Do not install concealed piping in solid partitions. Protect tubing from physical damage when installed inside partitions or hollow walls. a. Exception: Tubing passing through partitions or walls. In Walls: Gas piping with welded joints and protective wrapping specified in "Protective Coating" Article in Part 2 may be installed in masonry walls, subject to approval of authorities having jurisdiction. Prohibited Locations: Do not install gas piping in or through circulating air ducts, clothes or trash chutes, chimneys or gas vents (flues), ventilating ducts, or dumbwaiter or elevator shafts. a. Exception: Accessible above-ceiling space specified above. Drips and Sediment Traps: Install drips at points where condensate may collect. Locate where readily accessible for cleaning and emptying. Do not install where condensate would be subject to freezing. 1. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped. Use minimum-length nipple of 3 pipe diameters, but not less than 3 inches long, and same size as connected pipe. Install with space between bottom of drip and floor for removal of plug or cap. D. Conceal pipe installations in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in floor channels, unless indicated to be exposed to view. E. Install natural gas piping at uniform grade of 0.1 percent slope upward toward risers. F. Use bell reducer or eccentric reducer fittings to make reductions in pipe sizes. Install eccentric reducer fittings with level side down. G. Connect branch piping from top or side of horizontal piping. H. Install unions in pipes NPS 2 and smaller, adjacent to each valve, at final connection to each piece of equipment, and elsewhere as indicated. Unions are not required on flanged devices. I. Install corrugated, stainless-steel tubing system according to manufacturer's written instructions. Include striker plates to protect tubing from puncture where tubing is restrained and cannot move. J. Install shutoff valve on inlet of each line pressure regulator and automatic and electrically operated valve. K. Install flanges on valves, specialties, and equipment having NPS 2-1/2 and larger connections. Lewiston Library Second Floor Remodel Project 15194-8 15025 3.08 3.09 L. Install vent piping for gas pressure regulators and gas trains, extend outside building, and vent to atmosphere. Terminate vents with turned-down, reducing-elbow fittings with corrosion-resistant insect screens in large end. M. Install containment conduits for gas piping below slabs, within building, in gastight conduits extending minimum of 4 inches outside building, and vented to atmosphere. Terminate vents with turned-down, reducing-elbow fittings with corrosion-resistant insect screens in large end. Prepare and paint outside of conduits with coal-tar, epoxypolyamide paint according to SSPC-Paint 16. JOINT CONSTRUCTION A. Basic piping joint construction is specified in Division 15 Section "Basic Mechanical Materials and Methods". B. Patch factory-applied protective coating as recommended by manufacturer at field welds and where damage to coating occurs during construction. HANGER AND SUPPORT INSTALLATION A. Refer to Division 15 Section "Hangers and Supports" for pipe hanger and support devices. B. Install hangers for horizontal steel piping with the following maximum spacing and minimum rod sizes: 1. 2. 3. 4. C. Install hangers for horizontal corrugated, stainless-steel tubing with the following maximum spacing and minimum rod sizes: 1. 2. 3. 3.10 NPS 1 and Smaller: Maximum span, 96 inches; minimum rod size, 3/8 inch. NPS 1-1/4 to NPS 2: Maximum span, 108 inches; minimum rod size, 3/8 inch. NPS 2-1/2 to NPS 3-1/2: Maximum span, 10 feet; minimum rod size, 1/2 inch. NPS 4 and Larger: Maximum span, 10 feet; minimum rod size, 5/8 inch. NPS 3/8 and NPS 1/2: Maximum span, 48 inches; minimum rod size, 3/8 inch. NPS 3/4 and NPS 1: Maximum span, 72 inches; minimum rod size, 3/8 inch. Option: Support tubing from structure according to manufacturer's written instructions. CONNECTIONS A. Drawings indicate general arrangement of natural gas piping, fittings, and specialties. B. Install piping adjacent to appliances to allow service and maintenance. C. Connect piping to appliances with shutoff valve, unions and appliance gas connector. Install valve upstream from and within 72 inches of each appliance. Install union downstream from valve. D. Connect piping to moveable appliances or equipment with shutoff valve and appliance gas connector with quick-disconnect fitting and restraining device. Lewiston Library Second Floor Remodel Project 15194-9 15025 E. 3.11 Sediment Traps: Install tee fitting with capped nipple in bottom to form drip, as close as practical to inlet of each appliance using gas. LABELING AND IDENTIFYING A. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each service meter, pressure regulator, and specialty valve. 1. 3.12 PAINTING A. Paint exterior piping exposed to view, service meters, pressure regulators, and specialty valves. 1. 2. 3.13 3.14 Nameplates, pipe identification, and signs are specified in Division 15 Section "Mechanical Identification." Type: Semi-gloss enamel over primer. Color: Gray, 2 coats. FIELD QUALITY CONTROL A. Test, inspect, and purge piping according to NFPA 54 and requirements of authorities having jurisdiction. B. Repair leaks and defects with new materials and retest system until satisfactory results are obtained. C. Verify capacities and pressure ratings of service meters, pressure regulators, valves, and specialties. D. Verify correct pressure settings for pressure regulators. E. Verify that specified piping tests are complete. ADJUSTING A. Adjust controls and safety devices. Replace damaged and malfunctioning controls and safety devices. END OF SECTION 15194 Lewiston Library Second Floor Remodel Project 15194-10 15025 SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this section. SUMMARY A. Provide all materials, labor, equipment design and services necessary to perform the installation of the fire protection system as shown on the drawings and as described herein. B. Related Sections include the following: 1. 2. 3. 1.03 SCOPE OF WORK A. Fire sprinkler systems shall be hydraulically calculated, wet or dry pipe systems protecting areas of the buildings with a zones as required, designed in accordance with NFPA 13 and NFPA 14 for the following conditions: 1. 2. 1.04 Division 15 Section “General Mechanical Requirements”. Division 15 Section “Basic Mechanical Materials and Methods”. Division 16 Section “Fire Alarm and Detection Systems”. Except as listed below, sprinkler systems shall be designed for Light Hazard occupancy, including spaces above ceilings in existing and new construction where construction is combustible. Sprinkler systems protecting the Electrical Rooms, and Storage spaces shall be designed for Ordinary Hazard, Group 1 occupancy. B. Obtain water supply characteristics from the water utility purveyor or authority having jurisdiction where not specifically indicated. C. Pipe sizes and routing on the Drawings are for general information. Actual pipe sizes and routing shall be shown on the Shop Drawings as verified by hydraulic calculations by the Contractor. SUBMITTALS A. Product Data: Furnish a complete list of fire protection equipment and products, and manufacturer's catalog data sheets and maintenance data sheets for each item to be included in the project. B. Shop Drawings: Submit drawings which have been prepared in accordance with NFPA 13 identified as "Working Plans," including hydraulic calculations, and which have been approved by the authority having jurisdiction. Submit evidence of final drawing approval by the authority having jurisdiction prior to the start of fabrication or installation. Lewiston Library Second Floor Remodel Project 15300-1 15025 C. 1.05 QUALITY ASSURANCE A. 1.06 Test Reports and Certificates: Include "Contractor's Material & Test Certificate for Aboveground Piping" and "Contractor's Material & Test Certificate for Underground Piping" as described in NFPA 13, for work provided. Installer Qualifications: All above ground fire sprinkler system work shall be performed by a licensed fire sprinkler contractor in the State of Idaho. CODES AND STANDARDS A. Code Compliance: Comply with most current adopted edition of following: 1. 2. 3. 4. 5. 6. 1.07 International Building Code (IBC), Standards and Amendments. International Mechanical Code (IMC), Standards and Amendments. International Fire Code (IFC), Standards and Amendments. National Fire Protection Association (NFPA). National Electrical Code (NEC); NFPA 70. Applicable State and local codes, laws and ordinances APPROVALS A. For purposes of code compliance, the Authority having jurisdiction will be the City of Lewiston. Where there is a conflict between the Authority having jurisdiction and the referenced codes and standards, the most stringent shall apply. PART 2 - PRODUCTS 2.01 2.02 GENERAL A. Materials and Equipment: All fire protection system materials and equipment shall be new and current products of a manufacturer regularly engaged in the production of such materials and equipment. B. Approval Guides: All fire protection system materials and equipment shall be listed in the latest publication of the Underwriter's Laboratories Fire Protection Directory or the Factory Mutual Approval Guide. PIPE AND TUBING MATERIALS A. 2.03 Pipe or tubing shall be metallic and meet or exceed the standards of NFPA 13. PIPE FITTINGS A. Threaded Fittings: ANSI B16.4, Class 125, rated for 175 psi, standard pattern, for threaded joints. Threads shall conform to ANSI B1.20.1. B. Steel Fittings: ASTM A 234, seamless or welded, for welded joints. C. Grooved Mechanical Fittings: ASTM A 47, malleable-iron fittings with grooves or shoulders designed to accept grooved end couplings. Lewiston Library Second Floor Remodel Project 15300-2 15025 2.04 2.05 D. Grooved Mechanical Couplings: Consist of ductile or malleable iron housing, a synthetic rubber gasket of a central cavity pressure-responsive design; with nuts, bolts, locking pin, locking toggle, or lugs to secure roll-grooved pipe and fittings. E. Grooved mechanical couplings including gaskets used on dry-pipe systems shall be listed for dry-pipe service. F. Flanges: ANSI B16.1, Class 125; raised ground face, bolt holes spot faced. G. Gasket Materials: Thickness, material, and type suitable for fluid to be handled, and design temperatures and pressures. HANGERS AND SUPPORTS A. Provide hangers to support all piping in perfect alignment without sagging or interference, to permit free expansion and contraction, and meet the requirements of NFPA 13. B. Pipe rings shall be zinc-coated. Grinnell figure 69 or approved equal. C. Hanger rods to be electro-galvanized. SEISMIC BRACING A. 2.06 Seismic bracing shall be with a pipe clamp and pipe with swivel type anchor or those similar to illustrations in NFPA 13 Figures A-4-5.4.3.5.1 (e) and (f). Other types of UL listed or FM approved bracing may be used. VALVES A. Gate Valves - 2 Inch and Smaller: Body and bonnet of cast bronze, 175 pound cold water working pressure - non-shock, threaded ends, solid wedge, outside screw and yoke, rising stem, screw-in bonnet, and malleable iron handwheel. Valves shall be capable of being repacked under pressure, with valve wide open. B. Gate Valves – 2-1/2 Inch and Larger: Iron body; bronze mounted, 175 pound cold water working pressure - non-shock. Valves shall have solid taper wedge; outside screw and yoke, rising stem; flanged bonnet, with body and bonnet conforming to ASTM A 126 Class B; replaceable bronze wedge facing rings; flanged ends; and a packing assembly consisting of a cast iron gland flange, brass bland, packing, bonnet, and bronze bonnet bushing. Valves shall be capable of being repacked under pressure, with valve wide open. C. Check Valves: Cast iron body, bronze seat, stainless steel clapper with a replaceable rubber seal and 175 psi rated working pressure. 1. 2. Butterfly Valves: Iron body with lug, wafer or grooved configuration, rated at 175 psi working pressure, resilient seating for bubble tight shut-off, U.L. listed or F.M. approved. Drain Valves: Valves shall be screw-in bonnet bronze globe valves rated for 175 psi non-shock cold water working pressure. Low point drain valves shall have in addition a : inch brass nipple with : inch male hose thread and cap. Lewiston Library Second Floor Remodel Project 15300-3 15025 2.07 SPECIALTY VALVES A. 2.08 DOUBLE-CHECK DETECTOR BACKFLOW PREVENTION ASSEMBLY A. 2.09 2.10 Dry-Pipe Valves: Differential type, 175 psig working pressure, and have cast iron, flanged inlet and outlet, bronze seat with "O" ring seals, single hinge pin and latch design. Provide trim sets for air supply, drain, priming level, alarm connections, ball drip valves, pressure gauges, priming chamber attachment, and fill line attachment. Double Check Backflow Preventer Assembly: Assembly shall comply with all local water district requirements for bypass detection, etc. SYSTEM ACCESSORIES A. Sight Drain: Provide single piece sight drain on each main drain on the system riser. Grinnell Model F1321 or approved equal. B. Pressure Gauge: Provide 32 inch diameter bourdon type pressure gauge, range of 0 to 300 pounds, 3 inch soft metal seat globe valve with arrangements for draining piping between gauge and valve. Locate near main control valve assembly. C. Wall Escutcheon: Provide chrome plate split ring type escutcheons at all exposed wall penetrations. D. Signs: Provide all control, drain and test valves with signs identifying type of valve and area affected by valve. Signs shall be three layer etched plastic with red letters on a white background to identify valves. Provide hydraulic design information plates as required by NFPA 13. Signs shall be similar to Grinnell Type A. SPRINKLERS A. Provide automatic sprinklers throughout. Sprinklers in finished ceilings shall be glass bulb type with white finish and white recessed escutcheon unless otherwise noted. Temperature rating of sprinkler shall be as required by application. Extended coverage sprinklers may be used where installed in accordance with NFPA 13 and UL/FM listings. B. Sprinkler finishes: 1. 2. 3. 4. Recessed pendent: White with white escutcheon. Horizontal sidewall: Chrome plate with chrome escutcheon. Upright - concealed: Brass. Dry sidewall: Chrome plate with chrome escutcheon. C. Provide spare sprinklers and escutcheons for each type and style of sprinkler used in accordance with NFPA 13 and proportioned based upon the number, type and style of sprinklers installed on the project. D. Provide a spare sprinkler cabinet to accommodate the required number of spare sprinklers and escutcheons. Include a wrench for each type of sprinkler in the cabinet. Lewiston Library Second Floor Remodel Project 15300-4 15025 E. 2.11 FIRE DEPARTMENT CONNECTIONS A. 2.12 2.13 Provide UL Listed sprinkler headguards for sprinklers subject to mechanical damage or for any sprinkler lower than 7'-0" above the floor. Headguards shall be provided for all sprinklers in the gymnasium and mechanical rooms. Wall Type Siamese Connections: Cast brass with wall escutcheon for horizontal connection. Connection sizes shall be 4-inch outlet and two, 2-inch female inlets, having NH standard threads, for the connection size indicated, as specified in NFPA 1963. Each inlet shall have a clapper valve, and plug and chain. Unit shall have wall escutcheon of aluminum alloy with cast-in raised letters with words "AUTO SPRK - FIRE DEPT. CONNECTION" ("STANDPIPE - FIRE DEPT. CONNECTION") ("AUTO SPRK & STANDPIPE - FIRE DEPT CONNECTION"). POST INDICATOR VALVE ASSEMBLY A. Gate Valve: UL 262, FM-approved NRS gate valve with iron body and bonnet with flange for indicator post, bronze seating material, inside screw, flanged connections, 175 psig minimum working pressure. B. Indicator Post: UL 789, FM-approved, vertical type, cast iron body with operating wrench, extension rod, valve supervisory switch, and adjustable cast iron barrel of length required for valve burial depth. ALARM DEVICES A. General: Types and sizes shall mate and match piping and equipment connections. B. Waterflow Switches: Vane type waterflow detector, rated to 250 psig; designed for horizontal or vertical installation; have 2-SPDT circuit switches to provide isolated alarm and auxiliary contacts, 7 ampere 125 volts AC and 0.25 ampere 24 volts DC; complete with factory-set, field-adjustable retard element to prevent false signals, and tamper-proof cover which sends a signal when cover is removed. C. Supervisory Switches: SPST, normally closed contacts, designed to signal valve in other than full open position. D. Electric Bell: 10" diameter, 24-volt connection. PART 3 - EXECUTION 3.01 PIPING INSTALLATIONS A. Deviations from approved "working plans" for fire sprinkler piping, require approval of the authority having jurisdiction and shall be made only after careful coordination with other Trades on the project and the Architect. B. Piping shall be so arranged to allow space for other equipment and piping. Coordinate all work with other trades on the job, and where necessary to alter work, it shall be done at no extra charge to the Owner. Install piping to provide maximum head height. Lewiston Library Second Floor Remodel Project 15300-5 15025 3.02 3.03 C. Install sprinkler piping to provide for system drainage in accordance with NFPA 13. D. Hangers and Supports: Comply with requirements of NFPA 13 and NFPA 14. Hanger and support spacing and locations for piping joined with grooved mechanical couplings shall be in accordance with the grooved mechanical coupling manufacturer's written instructions, for rigid systems. Provide required seismic bracing in accordance with NFPA 13. E. Install inspector's test valves for each system located in accordance with NFPA 13. Test assemblies shall be piped to discharge outside the building. F. Install pressure gauge on the riser or feed main at or near each test connection. Provide gauge with a connection not less than 1/4 inch and having a soft metal seated globe valve, arranged for draining pipe between gauge and valve. Install gauges to permit removal, and where they will not be subject to freezing. G. Install mechanical sleeve seal at pipe penetrations in below grade foundation walls. VALVE INSTALLATIONS A. General: Install fire protection specialty valves, fittings, and specialties in accordance with the manufacturer's written instructions, NFPA 13, and the authority having jurisdiction. B. Control Valves: Install supervised-open control valves so located to control all sources of water supply except fire department connections. Provide permanently marked identification signs indicating the portion of the system controlled by each valve. C. Install check valves in each water supply connection. D. Backflow Prevention Device: Install in proper direction of flow where indicated with adequate support. Maximum height above floor level not to exceed 5'-0". ELECTRICAL CONNECTIONS A. 3.04 3.05 Electrical Connections: Coordinate all required electrical and fire alarm connections to supervisory switches, waterflow switches, bells, compressed air components, etc. with Division 16 - Electrical. SPRINKLER INSTALLATION A. Use proper tools to prevent damage during installations. Sprinkler head layout in finished ceiling areas shall be symmetrical with all heads in straight lines and evenly spaced with respect to lighting fixtures, etc. B. Sprinkler heads located in 2'x 2' lay-in type ceiling panel shall be centered in tile unless otherwise indicated. Sprinkler heads located in 2'x 4' lay-in type ceiling panel shall be centered in tile or located at quarter points unless otherwise indicated. FIRE DEPARTMENT CONNECTION INSTALLATIONS A. Install automatic drip valves at the check valve on the fire department connection. Check valve and ball drip shall be located in the boiler/mechanical room. Lewiston Library Second Floor Remodel Project 15300-6 15025 3.06 FIELD QUALITY CONTROL A. Flush, test, and inspect sprinkler piping systems in accordance with NFPA 13. Underground piping shall be flushed, tested, inspected and approved prior to connection to sprinkler piping within the building. Replace piping system components which do not pass the test procedures specified, and retest repaired portion of the system. END OF SECTION 15300 Lewiston Library Second Floor Remodel Project 15300-7 15025 SECTION 15410 - PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes plumbing fixtures. B. Related Sections include the following: 1. 2. 1.03 1.04 Division 15 Section "Domestic Water Piping Specialties" for backflow preventers, wall hydrants, thermostatic water mixing valves, water tempering equipment for emergency plumbing fixtures and specialty fixtures not in this Section. Division 15 Section "Drainage Piping Specialties" for floor drains, roof drains, interceptors, and grease removal units. DEFINITIONS A. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people with disabilities. B. Fitting: Device that controls flow of water into or out of plumbing fixture. Fittings specified in this Section include supplies and stops, faucets and spouts, shower heads and tub spouts, drains and tailpieces, and traps and waste pipes. Piping and general-duty valves are included where indicated. SUBMITTALS A. Product Data: Include selected fixture and trim, fittings, accessories, appliances, appurtenances, equipment, and supports and indicate materials and finishes, dimensions, construction details, and flow-control rates for each type of fixture indicated. 1. 2. Include summary table of plumbing fixtures, in order scheduled, listing fixture identification symbol, fixture and all related trim and accessories with manufacturers and model numbers. Include single product data for accessories (p-traps, stops, supplies, ADA protective shielding guards, etc.) common to multiple fixtures. Identify which fixture symbols each accessory applies to. Do not duplicate product data for common accessories. B. Shop Drawings: Diagram power, signal, and control wiring and differentiate between manufacturer-installed and field-installed wiring. C. Maintenance Data: manuals. Lewiston Library Second Floor Remodel Project For plumbing fixtures to include in operation and maintenance 15410-1 15025 1.05 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. Regulatory Requirements: Comply with requirements of the International Building Code (IBC) and Public Law 101-336, "Americans with Disabilities Act"; about plumbing fixtures for people with disabilities. C. NSF Standard: Comply with NSF 61, “Drinking Water System Components- Heath Effects,” for fixture materials that will be in contact with potable water. D. Water Conservation: Comply with requirements of the Uniform Plumbing Code (UPC) as amended by Washington State Building Code Council (Chapter 51-47 WAC) for maximum water usage by plumbing fixtures. E. Comply with the following applicable standards and other requirements specified for plumbing fixtures: 1. F. Comply with the following applicable standards and other requirements specified for lavatory and sink faucets: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. G. Stainless-Steel Fixtures Other Than Service Sinks: ASME A112.19.3M. Backflow Protection Devices for Faucets with Side Spray: ASME A112.18.3M. Backflow Protection Devices for Faucets with Hose-Thread Outlet: ASME A112.18.3M. Diverter Valves for Faucets with Hose Spray: ASSE 1025. Faucet Hose: ASTM D 3901. Faucets: ASME A112.18.1M. Hose-Connection Vacuum Breakers: ASSE 1011. Hose-Coupling Threads: ASME B1.20.7. Integral, Atmospheric Vacuum Breakers: ASSE 1001. NSF Materials: NSF 61. Pipe Threads: ASME B1.20.1. Supply and Drain Fittings: ASME A112.18.1M. Comply with the following applicable standards and other requirements specified for bathtub and shower faucets: 1. 2. 3. 4. 5. 6. 7. 8. Backflow Protection Devices for Hand-Held Showers: ASME A112.18.3M. Combination, Pressure-Equalizing and Thermostatic-Control Antiscald Faucets: ASSE 1016. Faucets: ASME A112.18.1M. High-Temperature-Limit Controls for Thermal-Shock-Preventing Devices: ASTM F 445. Hose-Coupling Threads: ASME B1.20.7. Manual-Control Antiscald Faucets: ASTM F 444. Pipe Threads: ASME B1.20.1. Thermostatic-Control Antiscald Faucets: ASTM F 444 and ASSE 1016. Lewiston Library Second Floor Remodel Project 15410-2 15025 H. Comply with the following applicable standards and other requirements specified for miscellaneous fittings and accessories: 1. 2. 3. I. Comply with the following applicable standards and other requirements specified for miscellaneous components: 1. 2. 3. 1.06 Atmospheric Vacuum Breakers: ASSE 1001. Brass and Copper Supplies: ASME A112.18.1M. a. Stops: Chrome-plated, quarter-turn ball or compression type; 1/2 inch nominal compression or threaded inlet, loose-key. b. Supplies: Chrome-plated; flexible tubing riser with ground joint connection to fixture and wall escutcheon. Tubular Brass Drainage Fittings and Piping: ASME A112.18.2M; 17 gauge minimum; semi-cast p-traps with cleanout, 1-1/2” minimum. Hose-Coupling Threads: ASME B1.20.7. Pipe Threads: ASME B1.20.1. Supply and Drain Piping Protective Shielding Guards: ICC A117.1. a. Manufactured, molded anti-microbial protective pipe covers for covering hot and cold water supplies, stops, p-trap and drain piping; flush, snap-in tamper-resistant fasteners; ADA compliant. COORDINATION A. Coordinate roughing-in and final plumbing fixture locations, and verify that fixtures can be installed to comply with original design and referenced standards. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. 2. Stainless Steel Sinks and Service Sinks: a. Advance Tabco b. Elkay Mfg. Co. c. Just Mfg. Co. Faucets: a. American Standard, Inc. b. Bradley Corporation c. Central Brass d. Chicago Faucet Co. e. Crane Plumbing f. Delta Commercial Faucets g. Elkay Mfg. Co. h. Kohler Co. i. Leonard Valve Company j. Moen Commercial k. Sloan l. Speakman Company m. Symmons Industries, Inc. n. T & S Brass and Bronze Works, Inc. Lewiston Library Second Floor Remodel Project 15410-3 15025 3. 2.02 2.03 2.04 o. Zurn Industries, Inc. Fixture Supports and Carriers: a. Josam Co. b. MIFAB c. J.R. Smith Mfg. Co. d. Tyler Pipe/Wade Div. e. Watts Drainage f. Zurn Industries, Inc. PLUMBING FIXTURE SCHEDULE A. General: Basis-of-Design manufacturers and model numbers listed are for reference only for intended level of quality and required features. Refer to plumbing fixture schedule sheet M0.1. B. Fixture Mounting Heights: Refer to Architectural interior elevations for fixture mounting heights. C. Install protective shielding guards on hot and cold water supplies, stops, p-trap and drain piping for lavatories, sinks and other plumbing fixtures designated as “accessible”. EXAMINATION A. Examine roughing-in for water soil and for waste piping systems and supports to verify actual locations and sizes of piping connections and that locations and types of supports match those indicated, before plumbing fixture installation. Use manufacturer's roughing-in data if roughing-in data are not indicated. B. Examine walls, floors, and cabinets for suitable conditions where fixtures are to be installed. C. Proceed with installation only after unsatisfactory conditions have been corrected. FIXTURE INSTALLATION A. Assemble fixtures, trim, fittings, and other components according to manufacturers' written instructions. B. Install counter-mounting fixtures in and attached to casework. C. Install fixtures level and plumb according to manufacturers' written instructions and roughing-in drawings. D. Install water-supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures. Install stops in locations where they can be easily reached for operation. 1. E. Exception: Use ball, gate, or globe valve if stops are not specified with fixture. Refer to Division 15 Section "Valves" for general-duty valves. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system. Lewiston Library Second Floor Remodel Project 15410-4 15025 F. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system. G. Install protective shielding guards on hot and cold water supplies, stops, p-trap and drain piping for fixtures designated as accessible. H. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required. I. Install water-supply, flow-control fittings with specified flow rates in fixture supplies at stop valves. J. Install faucet, flow-control fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required. K. Install traps on fixture outlets. 1. 2. 2.05 Exception: Omit trap on fixtures with integral traps. Exception: Omit trap on indirect wastes, unless otherwise indicated. L. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for escutcheons. M. Seal joints between fixtures and walls, floors, and counters using sanitary-type, one-part, mildew-resistant, silicone sealant. Match sealant color to fixture color. CONNECTIONS A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect water supplies from water distribution piping to fixtures. C. Connect cold water supply piping to plumbed emergency plumbing fixtures without integral, water-tempering system. D. Connect hot and cold water supply piping to hot and cold tempering equipment. Connect tempered water piping to emergency plumbing fixtures. E. Connect drain piping from fixtures to sanitary drainage and vent piping. F. Supply and Waste Connections to Plumbing Fixtures: Connect fixtures with water supplies, stops, risers, traps, and waste piping. Use size fittings required to match fixtures. Connect to plumbing piping. G. Supply and Waste Connections to Fixtures and Equipment Specified in Other Sections: Connect fixtures and equipment with water supplies, stops, risers, traps, and waste piping specified. Use size fittings required to match fixtures and equipment. Connect to plumbing piping. Lewiston Library Second Floor Remodel Project 15410-5 15025 H. Ground equipment. 1. 2.06 2.07 2.08 FIELD QUALITY CONTROL A. Verify that installed fixtures are categories and types specified for locations where installed. B. Check that fixtures are complete with trim, faucets, fittings, and other specified components. C. Inspect installed fixtures for damage. Replace damaged fixtures and components. D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly. E. Install fresh batteries in sensor-operated mechanisms. ADJUSTING A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures, fittings, and controls. B. Adjust water pressure at faucets, shower valves, and flushometer valves to produce proper flow and stream. C. Replace washers and seals of leaking and dripping faucets and stops. CLEANING A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods and materials. Do the following: 1. 2. 2.09 Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. Remove faucet spouts and strainers, remove sediment and debris, and reinstall strainers and spouts. Remove sediment and debris from drains. PROTECTION A. Provide protective covering for installed fixtures and fittings. B. Do not allow use of fixtures for temporary facilities unless approved in writing by Owner. END OF SECTION 15410 Lewiston Library Second Floor Remodel Project 15410-6 15025 SECTION 15732 – PACKAGED ROOFTOP HEATING/COOLING UNITS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following packaged rooftop heating/cooling units: 1. 2. B. Related Sections include the following: 1. 2. 1.03 Division 15 Section "Direct-Fired, Makeup Air Units" for outside units providing 100 percent tempered outside air without heat exchangers. Division 15 Section "Indirect-Fired, Heating and Ventilating Units" for outside units providing 100 percent tempered outside air with heat exchangers. SUBMITTALS A. Product Data: Include manufacturer's technical data for each model indicated, including rated capacities, operating weights, dimensions, required clearances, characteristics, wiring diagrams, furnished specialties, and accessories. 1. 1.04 Units 7-1/2 tons and smaller. Units 7-1/2 to 20 tons. Wiring Diagrams: Power, signal, and control wiring. B. Operation and Maintenance Data: For packaged rooftop heating/cooling units to include in operation and maintenance manuals. C. Warranties: Special warranties specified in this Section. QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Code for Mechanical Refrigeration." C. Energy-Efficiency Ratio: Equal to or greater than prescribed by ASHRAE 90.1, "Energy Efficient Design of New Buildings except Low-Rise Residential Buildings". D. Comply with NFPA 54 for gas-fired furnace section. E. ARI Certification for Units with Capacities Less Than 240,000 Btuh: Units shall be ARI certified and listed. Lewiston Library Second Floor Remodel Project 15732-1 15025 F. ARI Compliance for Units with Capacities Less Than 135,000 Btuh: Rate rooftop airconditioner capacity according to ARI 210/240, "Unitary Air-Conditioning and AirSource Heat Pump Equipment." 1. G. ARI Compliance for Units with Capacities 135,000 Btuh and More: Rate rooftop airconditioner capacity according to ARI 340/360, "Commercial and Industrial Unitary AirConditioning and Heat Pump Equipment." 1. 1.05 Coordinate installation of roof curbs, equipment supports, and roof penetrations with roof installer. 1. Coordinate installation of restrained vibration isolation roof-curb rails. WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to replace components of packaged rooftop heating/cooling units that fail in materials or workmanship within specified warranty period. 1. 2. 1.07 Sound Power Level Ratings: Comply with ARI 270, "Sound Rating of Outdoor Unitary Equipment." COORDINATION A. 1.06 Sound Power Level Ratings: Comply with ARI 270, "Sound Rating of Outdoor Unitary Equipment." Warranty Period for Compressors: Manufacturer's standard, but not less than five years from date of Substantial Completion. Warranty Period for Heat Exchangers: Manufacturer's standard, but not less than ten years from date of Substantial Completion. EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. 2. Fan Belts: One set for each belt-drive fan. Filters: One set of filters for each unit. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by the manufacturers listed. Lewiston Library Second Floor Remodel Project 15732-2 15025 2.02 PACKAGED ROOFTOP HEATING/COOLING UNITS 7.5 TONS AND SMALLER A. Manufacturers: 1. Carrier Corp. B. Description: Factory assembled and tested; designed for exterior installation; consisting of compressor, indoor and outside refrigerant coils, heating section, indoor fan(s) and outside coil fan, refrigeration and temperature controls, filters, and dampers. C. Casing: Galvanized-steel construction with enamel paint finish, removable panels or access doors with neoprene gaskets for inspection and access to internal parts, minimum 1/2-inch- thick thermal insulation, knockouts for electrical and piping connections, exterior condensate drain connection, and lifting lugs. D. Indoor Fan: 1. 2. Forward curved, centrifugal, directly driven by multi-speed motor. Forward curved, centrifugal, belt driven by single-speed motor. E. Outside Coil Fan: Propeller type, directly driven by motor. F. Refrigerant Coils: Aluminum-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. G. Compressor: Hermetic reciprocating or scroll compressor with integral vibration isolators, internal overcurrent and over temperature protection, internal pressure relief, and crankcase heater where recommended by manufacturer. H. Refrigeration System: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Compressor. Outside coil and fan. Indoor coil and fan. Expansion valve with replaceable thermostatic element or fixed orifice metering system. Refrigerant dryer. High-pressure switch. Low-pressure switch. Low-ambient switch. Brass service valves installed in discharge and liquid lines. Charge of refrigerant. I. Filters: 2-inch-thick, pleated, throwaway filters in filter rack. J. Heat Exchanger: Stainless-steel construction for natural -gas-fired burners with the following controls: 1. 2. 3. 4. 5. Redundant single or dual gas valve with manual shutoff. Direct-spark pilot ignition. Electronic flame sensor. Induced-draft blower. Flame rollout switch. Lewiston Library Second Floor Remodel Project 15732-3 15025 K. Economizer: Return- and outside-air dampers with neoprene seals, outside-air filter, and hood. 1. 2. 3. Damper Motor: Fully modulating spring return with adjustable minimum position. Control: Electronic-control system uses outside-air temperature to adjust mixing dampers. Relief Damper: Gravity actuated with bird screen and hood. L. CO2 sensor (where scheduled): wall mounted CO2 sensor for demand controlled ventilation. Sensor to increase ventilation air/economizer damper above a set minimum when CO2 levels approach a set limit. M. Power Connection: Provide for single connection of power to unit with unit-mounted, non-fused disconnect switch accessible from outside unit and control-circuit transformer with built-in circuit breaker. N. Unit Controls: Solid-state control board and components contain at least the following features: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. O. Indoor fan on/off delay. Default control to ensure proper operation after power interruption. Service relay output. Unit diagnostics and diagnostic code storage. Field-adjustable control parameters. Economizer control. Electric heat staging. Gas valve delay between first- and second-stage firing. Indoor-air quality control with carbon dioxide sensor. Low-ambient control, allowing operation down to 0 deg F. Minimum unit and compressor run time. Night setback mode. Return-air temperature limit. Smoke alarm with smoke detector installed in supply air. Low-refrigerant pressure control. Digital display of outside temperature, supply-air temperature, return-air temperature, economizer damper position, indoor-air quality, and control parameters. Thermostat: Programmable, electronic; with heating setback and cooling setup with seven-day programming; and the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Touch sensitive keyboard. Automatic switching. Deg F readout. LED indicators. Hour/day programming. Manual override capability. Compressor cycle delay. Time and operational mode readout. Status indicator. Battery backup. Lewiston Library Second Floor Remodel Project 15732-4 15025 11. 12. 13. P. Optional Accessories: 1. 2. 3. 4. 5. 6. 7. Q. 2.03 Subbase with manual system switch (on-heat-auto-cool) and fan switch (autoon). Fan-proving switch to lock out unit if fan fails. Dirty-filter switch. Convenience Outlet: 115-V, ground-fault, circuit-interrupter type with factoryinstalled stepdown transformer. Dirty-filter switch. Coil guards of painted, galvanized-steel wire. Thru-the-curb service connections. Indoor-air quality control with carbon dioxide sensor. Smoke detector installed in supply air. (RTU-1, 2, 3 and 4) Vertical vent extension. Roof Curb: Steel with corrosion-protection coating, gasketing, and factory-installed wood nailer; complying with NRCA standards; minimum height of 14 inches. PACKAGED ROOFTOP HEATING/COOLING UNITS 7-1/2 TO 20 TONS A. Manufacturers: 1. Carrier; Div. of United Technologies Corp. B. Description: Factory assembled and tested; designed for exterior installation; consisting of compressor, indoor and outside refrigerant coils, heating section, indoor fan(s) and outside coil fan, refrigeration and temperature controls, filters, and dampers. C. Casing: Galvanized-steel construction with enamel paint finish, removable panels or access doors with neoprene gaskets for inspection and access to internal parts, minimum 1-inch thick thermal insulation, knockouts for electrical and piping connections, exterior condensate drain connection, and lifting lugs. D. Indoor Fan(s): 1. Forward curved, centrifugal, belt driven with adjustable motor sheaves, greaselubricated ball bearings, and motor. E. Outside Coil Fan: Propeller type, directly driven by permanently lubricated motor. F. Refrigerant Coils: Aluminum-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. G. Compressor(s): Two hermetic scroll compressors with integral vibration isolators, internal overcurrent and over temperature protection, internal pressure relief, and crankcase heater(s) where recommended by manufacturer. H. Refrigeration System: 1. 2. 3. 4. 5. Compressor(s). Outside coil and fan. Indoor coil and fan. Check valves. Expansion valves with replaceable thermostatic elements. Lewiston Library Second Floor Remodel Project 15732-5 15025 6. 7. 8. 9. 10. 11. 12. Refrigerant dryers. High-pressure switches. Low-pressure switches. Independent refrigerant circuits. Brass service valves installed in discharge and liquid lines. Charge of refrigerant. Hot-Gas Bypass: Factory-installed valve. I. Filters: 2-inch- thick, fiberglass, pleated, throwaway filters in filter rack. J. Heat Exchanger: Stainless-steel construction for natural -gas-fired burners with the following controls: 1. 2. 3. 4. 5. K. Redundant dual gas valve with manual shutoff. Direct-spark pilot ignition. Electronic flame sensor. Induced-draft blower. Flame rollout switch. Economizer: Return- and outside-air dampers with neoprene seals, outside-air filter, and hood. 1. 2. 3. Damper Motor: Fully modulating spring return with adjustable minimum position. Control: Electronic-control system uses outside-air temperature to adjust mixing dampers. Relief Damper: Gravity actuated with bird screen and hood. L. Power Connection: Provide for single connection of power to unit with unit-mounted disconnect switch accessible from outside unit and control-circuit transformer with builtin circuit breaker. M. Unit Controls: Solid-state control board and components contain at least the following features: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Indoor fan on/off delay. Default control to ensure proper operation after power interruption. Service relay output. Unit diagnostics and diagnostic code storage. Field-adjustable control parameters. Economizer control. Gas valve delay between first- and second-stage firing. Indoor-air quality control with carbon dioxide sensor. Low-ambient control, allowing operation down to 0 deg F. Minimum unit and compressor run time. Night setback mode. Return-air temperature limit. Smoke alarm with smoke detector installed in supply air. Low-refrigerant pressure control. Digital display of outside temperature, supply-air temperature, return-air temperature, economizer damper position, indoor-air quality, and control parameters. Variable-Air-Volume Control: Variable-frequency drive controls supply-air static pressure. Supply-air, static-pressure limit shuts unit down on high pressure. Lewiston Library Second Floor Remodel Project 15732-6 15025 N. DDC Temperature Control: Install stand-alone control module providing link between unit controls and DDC temperature-control system. Control module shall be compatible with temperature-control system specified in Division 15 Section "HVAC Instrumentation and Controls." O. Thermostat: Programmable, electronic; with heating setback and cooling setup with seven-day programming; and the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. P. Optional Accessories: 1. 2. 3. 4. 5. Q. Touch sensitive keyboard. Automatic switching. Deg F readout. LED indicators. Hour/day programming. Manual override capability. Compressor cycle delay. Time and operational mode readout. Status indicator. Battery backup. Subbase with manual system switch (on-heat-auto-cool) and fan switch (autoon). Fan-proving switch to lock out unit if fan fails. Convenience Outlet: 115-V, ground-fault, circuit-interrupter type with factoryinstalled stepdown transformer. Coil guards of painted, galvanized-steel wire. Power exhaust fan centrifugal type. Indoor-air quality control with carbon dioxide sensor. Smoke detector installed in supply air. Roof Curb: Steel with corrosion-protection coating, gasketing, and factory-installed wood nailer; complying with NRCA standards; minimum height of 14 inches. PART 3 - EXECUTION 3.01 3.02 INSTALLATION A. Install units level and plumb, maintaining manufacturer's recommended clearances. B. Curb Support: Install roof curb on roof structure, level and secure, according to NRCA's "Low-Slope Membrane Roofing Construction Details Manual," Illustration "Raised Curb Detail for Rooftop Air Handling Units and Ducts." Install and secure rooftop air conditioners on curbs and coordinate roof penetrations and flashing with roof construction. Secure units to curb support. C. Unit Support: Install unit level on structural curbs. Coordinate wall penetrations and flashing with wall construction. Secure units to structural support with anchor bolts. CONNECTIONS A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. Lewiston Library Second Floor Remodel Project 15732-7 15025 B. Install piping adjacent to units to allow service and maintenance. 1. C. Connect condensate drain pans using Type M copper tubing of same size as drain pan outlet connection. Extend to nearest equipment or floor drain. Construct p-trap of depth and configuration as required for unit static pressure at connection to drain pan. Make unit connection with flexible connector for equipment with external vibration isolators. D. Duct installation requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts. The following are specific connection requirements: 1. 2. 3. 4. 3.03 Install ducts to termination in roof curb. Remove roof decking only as required for passage of ducts. Do not cut out decking under entire roof curb. Connect supply ducts to rooftop unit with flexible duct connectors specified in Division 15 Section "Duct Accessories." Terminate return-air duct through roof structure and insulate space between roof and bottom of unit with 2-inch- thick, acoustic duct liner. E. Electrical System Connections: Comply with applicable requirements in Division 16 Sections for power wiring, switches, and motor controls. F. Ground equipment according to Division 16 Section "Grounding and Bonding." G. Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing. 1. 2. 3. 4. B. 3.04 Gas Piping: Comply with applicable requirements in Division 15 Section "Fuel Gas Piping." Connect gas piping to burner, full size of gas train inlet, and connect with union and shutoff valve with sufficient clearance for burner removal and service. After installing rooftop air conditioners and after electrical circuitry has been energized, test units for compliance with requirements. Inspect for and remove shipping bolts, blocks, and tie-down straps. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. Remove malfunctioning units, replace with new units, and retest as specified above. STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. Lewiston Library Second Floor Remodel Project 15732-8 15025 B. Complete installation and startup checks according to manufacturer's written instructions and do the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. Inspect for visible damage to unit casing. Inspect for visible damage to furnace combustion chamber. Inspect for visible damage to compressor, air-cooled outside coil, and fans. Inspect internal insulation. Verify that labels are clearly visible. Verify that clearances have been provided for servicing. Verify that controls are connected and operable. Verify that filters are installed. Clean outside coil and inspect for construction debris. Clean furnace flue and inspect for construction debris. Connect and purge gas line. Adjust vibration isolators. Inspect operation of barometric dampers. Lubricate bearings on fan. Inspect fan-wheel rotation for movement in correct direction without vibration and binding. Adjust fan belts to proper alignment and tension. Start unit according to manufacturer's written instructions. a. Start refrigeration system in summer only. b. Complete startup sheets and attach copy with Contractor's startup report. Inspect and record performance of interlocks and protective devices; verify sequences. Operate unit for an initial period as recommended or required by manufacturer. Perform the following operations for both minimum and maximum firing and adjust burner for peak efficiency. Adjust pilot to stable flame. a. Measure gas pressure on manifold. b. Measure combustion-air temperature at inlet to combustion chamber. c. Measure flue-gas temperature at furnace discharge. Calibrate thermostats. Adjust and inspect high-temperature limits. Inspect outside-air dampers for proper stroke and interlock with return-air dampers. Start refrigeration system and measure and record the following: a. Coil leaving-air, dry- and wet-bulb temperatures. b. Coil entering-air, dry- and wet-bulb temperatures. c. Outside-air, dry-bulb temperature. d. Outside-air-coil, discharge-air, dry-bulb temperature. Inspect controls for correct sequencing of heating, mixing dampers, refrigeration, and normal and emergency shutdown. Simulate maximum cooling demand and inspect the following: a. Compressor refrigerant suction and hot-gas pressures. b. Short circuiting of air through outside coil or from outside coil to outside-air intake. Verify operation of remote panel, including pilot-light operation and failure modes. Inspect the following: a. High-limit heat exchanger. b. Warm-up for morning cycle. c. Freezestat operation. Lewiston Library Second Floor Remodel Project 15732-9 15025 28. 3.05 3.06 d. Economizer to limited outside-air changeover. e. Alarms. After startup and performance testing, change filters, vacuum heat exchanger and cooling and outside coils, lubricate bearings, adjust belt tension, and inspect operation of power vents. ADJUSTING A. Adjust initial temperature set points. B. Set field-adjustable switches and circuit-breaker trip ranges as indicated. DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain rooftop heating/cooling units. END OF SECTION 15732 Lewiston Library Second Floor Remodel Project 15732-10 15025 SECTION 15738 - SPLIT-SYSTEM AIR-CONDITIONING UNITS PART 1 1.01 RELATED DOCUMENTS A. 1.02 1.04 A. Product Data: Include rated capacities; shipping, installed, and operating weights; furnished specialties; and accessories for each type of product indicated. B. Shop Drawings: Diagram power, signal, and control wiring and differentiate between manufacturer-installed and field-installed wiring. C. Maintenance Data: For split-system air-conditioning units to include in operation and maintenance manuals. D. Warranties: Special warranties specified in this Section. QUALITY ASSURANCE Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. WARRANTY A. Special Warranty: Written warranty, executed by manufacturer agreeing to repair or replace components of split-system air-conditioning units that fail in materials or workmanship within specified warranty period. B. Warranty Period: completion. PART 2 2.01 This Section includes split-system air-conditioning units consisting of separate indoor evaporator-fan and outdoor compressor-condenser components. Units are designed for exposed mounting. SUBMITTALS A. 1.05 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. 1.03 GENERAL One year parts, 5-years compressor from date of substantial PRODUCTS MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. 2. Carrier; Div. of United Technologies Corp. Daikin AC Lewiston Library Second Floor Remodel Project 15738-1 15025 3. 4. 2.02 2.03 WALL-MOUNTING, EVAPORATOR-FAN COMPONENTS A. Cabinet: High-impact polystyrene plastic or enameled steel with removable panels on front and ends, and discharge drain pans with drain connection. Fully insulate cabinet for improved thermal and acoustic performance. B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with thermal-expansion valve or capillary tube metering device. C. Fan: Tangential direct drive, centrifugal fan. D. Air Sweep: Automatic, motor-driven vertical air sweep. E. Fan Motors: Multitapped, multispeed with internal thermal protection and permanent lubrication. F. Filters: Permanent, cleanable. AIR-COOLED, COMPRESSOR-CONDENSER COMPONENTS A. Casing: Steel, finished with baked enamel, with removable panels for access to controls, weep holes for water drainage, and mounting holes in base. Provide brass service valves, fittings, and gage ports on exterior of casing. B. Compressor: Hermetically sealed with crankcase heater and mounted on vibration isolation. Compressor motor shall have thermal- and current-sensitive overload devices, start capacitor, relay, and contactor. 1. 2. 2.04 Fujitsu General America, Inc. Mitsubishi Electronics America, Inc.; HVAC Division. Compressor Type: Scroll. Refrigerant: Non HCFC, R-410A. C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with liquid subcooler. D. Fan: Aluminum-propeller type, directly connected to motor. E. Motor: Permanently lubricated, with integral thermal-overload protection. F. Low Ambient Kit: Permits operation down to 0 deg F. ACCESSORIES A. User Controller: Wired, wall-mounted controller to control compressor and evaporator fan, with the following features: 1. 2. 3. 4. Compressor time delay. 24-hour time control of system stop and start. Liquid-crystal display indicating temperature, set-point temperature, time setting, operating mode, and fan speed. Fan-speed selection, including auto setting. Lewiston Library Second Floor Remodel Project 15738-2 15025 B. Automatic-reset timer to prevent rapid cycling of compressor. C. Condensate Pump: Field-installed, automatic operation with level sensor on drain pan to stop cooling operation if the level in drain pan is unacceptable. D. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends. PART 3 3.01 3.02 3.03 EXECUTION INSTALLATION A. Install units level and plumb. Unless otherwise specified in the manufacturer instructions, always adhere to any recommendations for slope of equipment for condensate pans or other specific requirements. B. Install evaporator-fan components using manufacturer's standard mounting devices securely fastened to building structure. C. Install compressor-condenser components on polyethylene mounting base. D. Connect refrigerant piping to indoor and outdoor sections; maintain required access to unit. Install furnished field-mounted accessories. CONNECTIONS A. Connect condensate drain pump using vinyl tubing of same size as drain pan outlet connection. Extend to nearest equipment or floor drain. B. Install piping adjacent to unit to allow service and maintenance. C. Electrical Connections: Comply with requirements in Division 16 Sections for power wiring, switches, and motor controls. FIELD QUALITY CONTROL A. Perform the following field tests and inspections and prepare test reports: 1. 2. 3. B. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. Remove and replace malfunctioning units and retest as specified above. Lewiston Library Second Floor Remodel Project 15738-3 15025 3.04 STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. 1. 3.05 Complete installation and startup checks according to manufacturer's written instructions. DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain units. END OF SECTION 15738 Lewiston Library Second Floor Remodel Project 15738-4 15025 SECTION 15815 - METAL DUCTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes metal ducts for supply, return, outside, and exhaust air-distribution systems in pressure classes from minus 2-inch to plus 10-inch wg. Metal ducts include the following: 1. 2. 3. 4. B. Related Sections include the following: 1. 2. 1.03 NFPA Compliance: 1. 2. B. 1.05 Division 15 Section "Nonmetal Ducts" for fibrous-glass ducts and thermoset FRP ducts. Division 15 Section "Duct Accessories" for dampers, sound-control devices, duct-mounting access doors, turning vanes, and flexible ducts. QUALITY ASSURANCE A. 1.04 Rectangular ducts and fittings. Single-wall, round, and flat-oval ducts and formed fittings. Double-wall, round, and flat-oval ducts and formed fittings. Duct liner. NFPA 90A, "Installation of Air Conditioning and Ventilating Systems." NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems." Comply with NFPA 96, "Ventilation Control and Fire Protection of Commercial Cooking Operations," Ch. 3, "Duct System," for commercial kitchen hood ducts, unless otherwise indicated. DEFINITIONS A. NAIMA: North American Insulation Manufacturers Association. B. SMACNA: Sheet Metal and Air Conditioning Contractors National Association. SUBMITTALS A. Product Data: For the following: 1. 2. 3. 4. Single-wall, round, and flat-oval spiral-seam ducts and formed fittings. Double-wall, round, and flat-oval spiral-seam ducts and formed fittings. Duct liner. For adhesives, sealants and mastics: Documentation including printed statement of VOC content. Lewiston Library Second Floor Remodel Project 15815-1 15025 B. Shop Drawings: Show fabrication and installation details for metal ducts. 1. 2. 3. 4. 5. Fittings. Reinforcement and spacing. Seam and joint construction. Penetrations through fire-rated and other partitions. Hangers and supports, including methods for duct and building attachment, vibration isolation, and seismic restraints. PART 2 - PRODUCTS 2.01 2.02 SHEET METAL MATERIALS A. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods, unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections. B. Galvanized Sheet Steel: Lock-forming quality; complying with ASTM A 653/A 653M and having G90 coating designation. Where specifically indicated, ducts shall have “galvaneal” (“paint-grip”) finish for surfaces to be painted. C. PVC-Coated Galvanized Steel: Acceptable by authorities having jurisdiction for use in fabricating ducts with UL 181, Class 1 listing. Lock-forming-quality, galvanized sheet steel complying with ASTM A 653/A 653M and having G90 coating designation. Factory-applied PVC coatings shall be 4 mils thick on sheet metal surfaces of ducts and fittings exposed to corrosive conditions and 2 mils thick on opposite surfaces. D. Carbon-Steel Sheets: ASTM A 366/A 366M, cold-rolled sheets; commercial quality; with oiled, matte finish for exposed ducts. E. Stainless Steel: ASTM A 480/A 480M, Type 304 or 316 as indicated, and having a No. 2B finish for concealed ducts and No. 4B polished finish for exposed ducts. F. Aluminum Sheets: ASTM B 209, alloy 3003, temper H14; with mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts. G. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts. H. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch minimum diameter for lengths longer than 36 inches. DUCT LINER A. Fibrous-Glass Liner: Comply with NFPA 90A or NFPA 90B and with NAIMA AH124. 1. Manufacturers: a. CertainTeed Corp.; Insulation Group; “ToughGard2” or “ToughGard R” Duct Liner. b. Johns Manville International, Inc.; “Linacoustic RC” Duct Liner. Lewiston Library Second Floor Remodel Project 15815-2 15025 Johns Manville International, Inc.; “Spiracoustic Plus”, “Spiracoustic” Round Duct Liner. d. Knauf Fiber Glass GmbH.; “Duct Liner E-M”. e. Owens Corning.; “QuietR” Duct Liner. Materials: ASTM C 1071; surfaces exposed to airstream shall be coated with tightly bonded non-woven mat to prevent erosion of glass fibers and to facilitate duct cleaning. a. Thickness: 1 inch unless otherwise indicated. b. Thermal Conductivity (k-Value): 0.26 at 75 deg F mean temperature. c. Anti-Bacterial and Fungal Prevention: EPA-registered anti-microbial agent treatment in airstream surfaces applied to aid in the prevention of fungal and bacterial growth. Comply with ASTM C 1338, ASTM G21, ASTM G22. d. Maximum Emissions Levels: 1) Formaldehyde: 0.05 ppm 2) Total Volatile Organic Compounds (TOVC): 0.50 mg/m3 3) Total Particles: 0.05 mg/m3 e. Fire-Hazard Classification: Maximum flame-spread index of 25 and smoke-developed index of 50 when tested according to ASTM E 84. f. Liner Adhesive: Comply with NFPA 90A or NFPA 90B and with ASTM C 916. 1) VOC content of 100 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). g. Mechanical Fasteners: Galvanized steel suitable for welding attachment to duct without damaging liner when applied as recommended by manufacturer and without causing leakage in duct. 1) Tensile Strength: Indefinitely sustain a 50-lb- tensile, dead-load test perpendicular to duct wall. 2) Fastener Pin Length: As required for thickness of insulation and without projecting more than 1/8 inch into airstream. 3) Adhesive for Attaching Mechanical Fasteners: Comply with fire-hazard classification of duct liner system. c. 2. 2.03 SEALANT MATERIALS A. Joint and Seam Sealants, General: The term "sealant" is not limited to materials of adhesive or mastic nature but includes tapes and combinations of open-weave fabric strips and mastics. B. Tape Sealing System: Woven-fiber tape impregnated with gypsum mineral compound and modified acrylic/silicone activator to react exothermically with tape to form hard, durable, airtight seal. 1. C. VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Water-Based Joint and Seam Sealant: Flexible, adhesive sealant, resistant to UV light when cured, UL 723 listed, and complying with NFPA requirements for Class 1 ducts. 1. VOC content of 100 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Lewiston Library Second Floor Remodel Project 15815-3 15025 D. Solvent-Based Joint and Seam Sealant: One-part, nonsag, solvent-release-curing, polymerized butyl sealant formulated with a minimum of 75 percent solids. 1. E. Flanged Joint Mastic: One-part, acid-curing, silicone, elastomeric joint sealant complying with ASTM C 920, Type S, Grade NS, Class 25, Use O. 1. F. 2.04 VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Flange Gaskets: Butyl rubber or EPDM polymer with polyisobutylene plasticizer. HANGERS AND SUPPORTS A. Building Attachments: Concrete inserts, powder-actuated fasteners, or structural-steel fasteners appropriate for construction materials to which hangers are being attached. 1. 2. B. Use powder-actuated concrete fasteners for standard-weight aggregate concretes or for slabs more than 4 inches thick. Exception: Do not use powder-actuated concrete fasteners for lightweightaggregate concretes or for slabs less than 4 inches thick. Hanger Materials: Galvanized sheet steel or threaded steel rod. 1. 2. 3. Hangers Installed in Corrosive Atmospheres: Electrogalvanized, all-thread rods or galvanized rods with threads painted with zinc-chromate primer after installation. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for steel sheet width and thickness and for steel rod diameters. Galvanized-steel straps attached to aluminum ducts shall have contact surfaces painted with zinc-chromate primer. C. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible with duct materials. D. Trapeze and Riser Supports: Steel shapes complying with ASTM A 36/A 36M. 1. 2. 3. 2.05 VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Supports for Galvanized Steel Ducts: Galvanized steel shapes and plates. Supports for Stainless Steel Ducts: Stainless steel support materials. Supports for Aluminum Ducts: Aluminum support materials unless materials are electrolytically separated from ducts. RECTANGULAR DUCT FABRICATION A. Fabricate ducts, elbows, transitions, offsets, branch connections, and other construction according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" and complying with requirements for metal thickness, reinforcing types and intervals, tie-rod applications, and joint types and intervals. 1. 2. Lengths: Fabricate rectangular ducts in lengths appropriate to reinforcement and rigidity class required for pressure class. Deflection: Duct systems shall not exceed deflection limits according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible." Lewiston Library Second Floor Remodel Project 15815-4 15025 B. Transverse Joints: Prefabricated slide-on joints and components constructed using manufacturer's guidelines for material thickness, reinforcement size and spacing, and joint reinforcement. C. Formed-On Flanges: Construct according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible," using corner, bolt, cleat, and gasket details. D. Cross Breaking or Cross Beading: Cross break or cross bead duct sides 19 inches and larger and 22 gage or less, with more than 10 sq. ft. of nonbraced panel area unless ducts are lined. E. Duct Dimensions: Unless specifically indicated, duct dimensions on the Drawings are net free areas. Increase duct dimensions as necessary to compensate for liner thickness. F. Elbow Configuration: 1. G. Branch Configuration: 1. 2.06 Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 4-2, "Rectangular Elbows." Rectangular duct elbow configuration shall be one of the following types unless specifically indicated otherwise: a. Radius Type RE 1 with minimum 1.5 radius-to-width (R/W) ratio. Square throat radius elbows (R/W ratio of 0.5) are not allowed. b. Radius Type RE 3 with minimum 1.0 radius-to-width (R/W) ratio and two splitter vanes. c. Mitered Type RE 2 with turning vanes complying with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane Runners," and Figure 4-4, "Vane Support in Elbows." 1) Exception: Vanes not required for general purpose exhaust-air, return-air, and relief-air ducts where duct velocity is 1000 fpm or lower AND duct net inside area is 144 sq. in. (1.0 sq. ft.) or less. 2) Exception: Maximum velocity limitation: 1500 fpm. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 4-6, "Branch Connection." Rectangular duct branch configuration shall be one of the following types unless specifically indicated otherwise: a. Rectangular Main to Rectangular Branch: 45-degree entry. b. Rectangular Main to Round Branch: Spin-in or self-sealing fitting. ROUND AND FLAT-OVAL DUCT AND FITTING FABRICATION A. Diameter as applied to flat-oval ducts in this Article is the diameter of a round duct with a circumference equal to the perimeter of a given size of flat-oval duct. B. Duct Dimensions: Unless specifically indicated, duct dimensions on the Drawings are net free areas. Increase duct dimensions as necessary to compensate for liner thickness. C. Round, Spiral Lock-Seam Ducts: Fabricate supply ducts of galvanized steel according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible." Lewiston Library Second Floor Remodel Project 15815-5 15025 D. Flat-Oval, Spiral Lock-Seam Ducts: Fabricate supply ducts according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible." E. Manufacturers: 1. 2. 3. 4. 5. 6. 7. F. Accu Duct Mfg. Ductmate Industries, Inc. Lindlab, Inc. Semco Mfg., Inc. Spiral Pipe of Texas United Sheet Metal Div. United McGill Corp. Ventline, Inc. Duct Joints: 1. 2. 3. 4. 5. Ducts up to 20 Inches in Diameter: Interior, center-beaded slip coupling, sealed before and after fastening, attached with sheet metal screws. Ducts 21 to 72 Inches in Diameter: Three-piece, gasketed, flanged joint consisting of two internal flanges with sealant and one external closure band with gasket. Ducts Larger Than 72 Inches in Diameter: Companion angle flanged joints per SMACNA "HVAC Duct Construction Standards--Metal and Flexible," Figure 32. Round Ducts: Prefabricated connection system consisting of double-lipped, EPDM rubber gasket. Manufacture ducts according to connection system manufacturer's tolerances. Flat-Oval Ducts: Prefabricated connection system consisting of two flanges and one synthetic rubber gasket. G. Tees and Lateral Taps: Fabricate to comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible," with metal thicknesses specified for longitudinal-seam straight ducts. H. Diverging-Flow Fittings: Fabricate with reduced entrance to branch taps and with no excess material projecting from fitting onto branch tap entrance. I. Elbow Configuration: 1. Round Duct: Comply with SMACNA's "HVAC Duct Construction Standards Metal and Flexible," Figure 3-4, "Round Duct Elbows." a. Minimum Radius-to-Diameter Ratio and Elbow Segments: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 3-1, "Mitered Elbows." Elbows with less than 90-degree change of direction have proportionately fewer segments. 1) Radius-to Diameter Ratio: 1.5. b. Round Elbows, 12 Inches and Smaller in Diameter: Stamped or pleated. c. Round Elbows, 14 Inches and Larger in Diameter: Standing seam or welded. d. Segmented, adjustable type elbows are not allowed. Lewiston Library Second Floor Remodel Project 15815-6 15025 J. Branch Configuration: 1. K. PVC-Coated Elbows and fittings: Fabricate elbows and fittings as follows: 1. 2. 3. 4. 5. 2.07 Round and Flat Oval: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-5, "90 Degree Tees and Laterals," and Figure 3-6, "Conical Tees." Saddle taps are permitted in existing duct only. a. Velocity 1000 fpm or lower: 90-degree tap, conical tap, 45-degree tap, or 45-degree lateral. b. Velocity over 1000 fpm: Conical tap, 45-degree tap, or 45-degree lateral. Round Elbows 4 to 8 inches in diameter: Two piece, die stamped, with longitudinal seams spot welded, bonded, and painted with PVC aerosol spray. Round elbows 9 to 26 inches in Diameter: Standing seam construction. Round Elbows 28 to 60 inches Diameter: Standard gored construction, riveted and bonded. Other Fittings: Riveted and bonded joints. Couplings: Slip-joint construction with a minimum 2-inch insertion length. DOUBLE-WALL ROUND AND FLAT-OVAL DUCT AND FITTING FABRICATION A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. B. Accu Duct Mfg. Ductmate Industries, Inc. Lindab Inc. Semco Mfg., Inc. Spiral Pipe of Texas United Sheet Metal Div, United McGill Corp Ventline, Inc. Ducts: Fabricate double-wall (insulated) ducts with an outer shell and an inner duct. Dimensions indicated are for inner ducts. 1. 2. 3. Outer Shell: Base metal thickness on outer-shell dimensions. Fabricate outershell lengths 2 inches longer than inner duct and insulation and in metal thickness specified for single-wall duct. Insulation: 1-inch- thick fibrous glass, unless otherwise indicated. Terminate insulation where double-wall duct connects to single-wall duct or uninsulated components, and reduce outer shell diameter to inner duct diameter. a. Thermal Conductivity (k-Value): 0.26 at 75 deg F mean temperature. Solid Inner Ducts: Use the following sheet metal thicknesses and seam construction: a. Ducts 3 to 8 Inches in Diameter: 28 gage with standard spiral-seam construction. b. Ducts 9 to 42 Inches in Diameter: 28 gage with single-rib spiral-seam construction. c. Ducts 44 to 60 Inches in Diameter: 26 gage with single-rib spiral-seam construction. d. Ducts 62 to 88 Inches in Diameter: 22 gage with standard spiral-seam construction. Lewiston Library Second Floor Remodel Project 15815-7 15025 4. 5. C. Perforated Inner Ducts: Fabricate with 24 gage thick sheet metal having 3/32inch- diameter perforations, with overall open area of 23 percent. Maintain concentricity of inner duct to outer shell by mechanical means. Prevent dislocation of insulation by mechanical means. Fittings: Fabricate double-wall (insulated) fittings with an outer shell and an inner duct. 1. 2. 3. Solid Inner Ducts: Use the following sheet metal thicknesses: a. Ducts 3 to 34 Inches in Diameter: 24 gage. b. Ducts 35 to 58 Inches in Diameter: 22 gage. c. Ducts 60 to 88 Inches in Diameter: 20 gage. Perforated Inner Ducts: Fabricate with 28 gage sheet metal having 3/32-inchdiameter perforations, with overall open area of 23 percent. Field- or shop-installed saddle tap fittings are not acceptable. PART 3 - EXECUTION 3.01 DUCT APPLICATIONS A. Static-Pressure Classes: Unless otherwise indicated, construct ducts according to the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. B. All ducts shall be standard galvanized steel except as follows: 1. 3.02 Supply Ducts: 1-inch wg . Supply Ducts (before Air Terminal Units): 2-inch wg. Supply Ducts (after Air Terminal Units): 1-inch wg. Supply Ducts (in Mechanical Equipment Rooms): 2-inch wg. Return Ducts (Negative Pressure): 1-inch wg. Exhaust Ducts (Negative Pressure): 1-inch wg. Sawdust Collection System Ducts (Negative Pressure): 10-inch wg. Welding Exhaust Ducts (Negative Pressure): 2-inch wg. Vehicle Exhaust Ducts (Negative Pressure): 2-inch wg. Clothes Dryer Exhaust Ducts: 24 gage galvanized steel, 0.04-inch thick aluminum or Type 304, stainless steel. DUCT INSTALLATION A. Construct and install ducts according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible," unless otherwise indicated. B. Install round duct liner products in accordance with the manufacturer's application guidelines. C. Install round and flat-oval ducts in lengths not less than 10 feet unless interrupted by fittings. D. Install ducts with fewest possible joints. E. Install fabricated fittings for changes in directions, size, and shape and for connections. Lewiston Library Second Floor Remodel Project 15815-8 15025 F. Install couplings tight to duct wall surface with a minimum of projections into duct. Secure couplings with sheet metal screws. Install screws at intervals of 12 inches, with a minimum of 3 screws in each coupling. G. Secure ductwork joints and fittings for materials-handling applications such as clothes dryers and sawdust collection systems with fastening devices that do not extend into the duct and airstream. H. Install ducts, unless otherwise indicated, vertically and horizontally and parallel and perpendicular to building lines; avoid diagonal runs. I. Install ducts close to walls, overhead construction, columns, and other structural and permanent enclosure elements of building. J. Install ducts with a clearance of 1 inch, plus allowance for insulation thickness. K. Conceal ducts from view in finished spaces. Do not encase horizontal runs in solid partitions unless specifically indicated. L. Coordinate layout with suspended ceiling, fire- and smoke-control dampers, lighting layouts, and similar finished work. M. Seal all joints and seams. Apply sealant to male end connectors before insertion, and afterward to cover entire joint and sheet metal screws. N. Cap or seal temporary duct openings during construction. Remove caps or seals for final connections. O. Electrical Equipment Spaces: Route ducts to avoid passing through and above transformer vaults and electrical equipment spaces and enclosures. P. Non-Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and exterior walls and are exposed to view, conceal spaces between construction openings and ducts or duct insulation with sheet metal flanges of same metal thickness as ducts. Overlap openings on 4 sides by at least 1-1/2 inches. Q. Fire Rated Partition Penetrations: Where ducts pass through interior partitions and exterior walls, install appropriately rated fire dampers, sleeves, and firestopping sealant. Fire and smoke dampers are specified in Division 15 Section”Duct Accessories.” R. Install ducts with hangers and braces designed to withstand, without damage to equipment, seismic force required by applicable building codes. Refer to SMACNA's "Seismic Restraint Manual: Guidelines for Mechanical Systems." S. Protect duct interiors from the elements and foreign materials until building is enclosed. T. Paint interiors of metal ducts, that do not have duct liner, for 24 inches upstream of registers and grilles where bare sheetmetal is visible from a normal viewer position. Apply one coat of flat, black, latex finish coat over a compatible galvanized-steel primer. Lewiston Library Second Floor Remodel Project 15815-9 15025 3.03 APPLICATION OF LINER IN RECTANGULAR DUCTS A. Adhere a single layer of indicated thickness of duct liner with at least 90 percent adhesive coverage at liner contact surface area. Attaining indicated thickness with multiple layers of duct liner is prohibited. B. Apply adhesive to transverse edges of liner facing upstream that do not receive metal nosing. C. Butt transverse joints without gaps and coat joint with adhesive. D. Fold and compress liner in corners of rectangular ducts or cut and fit to ensure buttededge overlapping. E. Do not apply liner in rectangular ducts with longitudinal joints, except at corners of ducts, unless duct size and standard liner product dimensions make longitudinal joints necessary. F. Apply adhesive coating on longitudinal seams in ducts where air velocities are greater than 2500 fpm. G. Secure liner with mechanical fasteners 4 inches from corners and at intervals not exceeding 12 inches transversely; at 3 inches from transverse joints and at intervals not exceeding 18 inches longitudinally. H. Secure transversely oriented liner edges facing the airstream with metal nosings that have either channel or "Z" profiles or are integrally formed from duct wall. Fabricate edge facings at the following locations: 1. 2. 3. I. For double-wall (insulated) ducts, secure insulation between perforated sheet metal inner duct of same thickness as specified for outer shell. Use mechanical fasteners that maintain inner duct at uniform distance from outer shell without compressing insulation. 1. J. 3.04 Fan discharges. Intervals of lined duct preceding unlined duct. Upstream edges of transverse joints in ducts where air velocities are greater than 2500 fpm or where indicated. Sheet Metal Inner Duct Perforations: 3/32-inch diameter, with an overall open area of 23 percent. Terminate inner ducts with build outs attached to fire-damper sleeves, dampers, turning vane assemblies, or other devices. Fabricated build outs (metal hat sections), or other build out means are optional; when used, secure build outs to duct walls with bolts, screws, rivets, or welds. SEAM AND JOINT SEALING A. Seal duct seams and joints according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for duct pressure class indicated. 1. B. For pressure classes 2-inch wg and lower, seal transverse joints at a minimum. Seal ducts before external insulation is applied. Lewiston Library Second Floor Remodel Project 15815-10 15025 3.05 HANGING AND SUPPORTING A. Support horizontal ducts within 24 inches of each elbow and within 48 inches of each branch intersection. B. Support vertical ducts at maximum intervals of 16 feet and at each floor. C. Install upper attachments to structures with an allowable load not exceeding one-fourth of failure (proof-test) load. D. Install concrete inserts before placing concrete. E. Install powder-actuated concrete fasteners after concrete is placed and completely cured. 1. 3.06 Do not use powder-actuated concrete fasteners for lightweight-aggregate concretes or for slabs less than 4 inches thick. CONNECTIONS A. Make connections to equipment with flexible connectors according to Division 15 Section "Duct Accessories." Locate flexible connectors in sections of ductwork below roof level for roof mounted equipment unless indicated otherwise. B. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for branch, outlet and inlet, and terminal unit connections. END OF SECTION 15815 Lewiston Library Second Floor Remodel Project 15815-11 15025 SECTION 15820 - DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. B. Related Sections include the following: 1. 1.03 Division 15 Section "HVAC Instrumentation and Controls" for control dampers and damper actuators. SUBMITTALS A. Product Data: For the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 1.04 Backdraft dampers. Volume dampers. Turning vanes. Duct-mounting access doors. Flexible connectors. Flexible ducts. Spin-in and self-sealing take-off fittings. Duct accessory hardware. Residential clothes dryer vent wall box. Backdraft dampers. Volume dampers. Fire dampers. Ceiling radiation dampers. Combination fire and smoke dampers. Duct silencers. Duct-mounting access doors. Flexible connectors. Flexible ducts. Spin-in and self-sealing take-off fittings. Residential clothes dryer vent wall box. Air measuring stations and flow transmitters. QUALITY ASSURANCE A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems." B. Comply with AMCA Standard 500 for maximum leakage rates. Lewiston Library Second Floor Remodel Project 15820-1 15025 1.05 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Fusible Links: Furnish quantity equal to 10 percent (1 minimum) of amount installed. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. 2.02 2.03 Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers listed. SHEET METAL MATERIALS A. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods, unless otherwise indicated. B. Galvanized Sheet Steel: Lock-forming quality; complying with ASTM A 653/A 653M and having G90 coating designation; ducts shall have mill-phosphatized finish for surfaces exposed to view. C. Stainless Steel: ASTM A 480/A 480M. D. Aluminum Sheets: ASTM B 209, alloy 3003, temper H14; with mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts. E. Extruded Aluminum: ASTM B 221, alloy 6063, temper T6. F. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts; compatible materials for aluminum and stainless-steel ducts. G. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch minimum diameter for lengths longer than 36 inches. BACKDRAFT DAMPERS A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. Air Balance, Inc. American Warming and Ventilating. CESCO Products. Duro Dyne Corp. Greenheck. Pottorff Ruskin Company. Lewiston Library Second Floor Remodel Project 15820-2 15025 8. B. Description: Multiple-blade, parallel action gravity balanced, with blades of maximum 6-inch width, with sealed edges, assembled in rattle-free manner with 90-degree stop, adjustment device to permit setting for varying differential static pressure. C. Maximum Leakage Rates: 1. 2. 2.04 Vent Products Company, Inc. For dampers 24 inches or smaller in either dimension: 40 cfm/sq.ft. at 1.0 inch w.g. For all other damper dimensions: 20 cfm/sq. ft. at 1.0 inch w.g. D. Frame: 0.090-inch- thick extruded aluminum, with mitered corners. E. Blades: 0.025-inch- thick, roll-formed aluminum. F. Bearings: Non-corrosive synthetic. G. Blade Seals: Vinyl. H. Blade Axles: Nonferrous. I. Linkage Tie Bars and Brackets: Aluminum, concealed in frame. VOLUME DAMPERS A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. 9. B. General Description: Factory fabricated, with required hardware and accessories. Stiffen damper blades for stability. Include locking device to hold single-blade dampers in a fixed position without vibration. Close duct penetrations for damper components to seal duct consistent with pressure class. 1. C. Air Balance, Inc. American Warming and Ventilating. Greenheck. Johnson Controls, Inc. Nailor Industries, Inc. Penn Ventilation Company, Inc. Pottorff Ruskin Company. Vent Products Company, Inc. Pressure Classes of 3-Inch wg or Higher: End bearings or other seals for ducts with axles full length of damper blades and bearings at both ends of operating shaft. Volume Dampers: Multiple- or single-blade, parallel- or opposed-blade design, standard leakage rating, and suitable for horizontal or vertical applications. 1. 2. Steel Frames: Hat-shaped, galvanized sheet steel channels, minimum of 16 gage, with mitered and welded corners; frames with flanges where indicated for attaching to walls and flangeless frames where indicated for installing in ducts. Roll-Formed Steel Blades: 16 gage, galvanized sheet steel; maximum 6-inch width. Lewiston Library Second Floor Remodel Project 15820-3 15025 3. 4. 5. 6. 7. 8. D. Jackshaft: 1-inch- diameter, galvanized-steel pipe rotating within pipe-bearing assembly mounted on supports at each mullion and at each end of multiple-damper assemblies. 1. E. 2.05 Length and Number of Mountings: Appropriate to connect linkage of each damper in multiple-damper assembly. Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 3/32-inchthick zinc-plated steel, and a 3/4-inch hexagon locking nut. Include center hole to suit damper operating-rod size. Include elevated platform for insulated duct mounting. Provide concealed type regulators, utilizing miter gears and universal joints as required, for dampers located above hard ceilings or in non-accessible locations. TURNING VANES A. Manufactured Turning Vanes: Single-wall vanes of galvanized sheet steel set into vane runners with friction insert tabs. 1. 2.06 Aluminum Frames: Hat-shaped, 0.10-inch- thick, aluminum sheet channels; frames with flanges where indicated for attaching to walls; and flangeless frames where indicated for installing in ducts. Roll-Formed Aluminum Blades: 0.10-inch- thick aluminum sheet; maximum 6inch width.. Extruded-Aluminum Blades: 0.050-inch- thick extruded aluminum; maximum 6inch width. Blade Axles: Nonferrous. Bearings: Molded synthetic. Tie Bars and Brackets: Aluminum. Manufacturers: a. Ductmate Industries, Inc. b. Duro Dyne Corp. DUCT-MOUNTING ACCESS DOORS A. General Description: Fabricate doors airtight and suitable for duct pressure class. B. Door: Double wall, duct mounting, and rectangular; fabricated of galvanized sheet metal with insulation fill and thickness as indicated for duct pressure class. Include 1-by-1-inch butt or piano hinge and cam latches. 1. 2. Manufacturers: a. American Warming and Ventilating. b. CESCO Products. c. Ductmate Industries, Inc. d. Greenheck. e. Kees. f. McGill AirFlow Corporation. g. Pottorff h. Nailor Industries, Inc. i. Ruskin Company j. Ventfabrics, Inc. Frame: Minimum 22 gage galvanized sheet steel, with bend-over tabs and foam gaskets. Lewiston Library Second Floor Remodel Project 15820-4 15025 3. 2.07 FLEXIBLE CONNECTORS A. Manufacturers: 1. 2. 3. Ductmate Industries, Inc. Duro Dyne Corp. Ventfabrics, Inc. B. General Description: Flame-retardant or noncombustible fabrics, coatings, and adhesives complying with UL 181, Class 1. C. Metal-Edged Connectors: Factory fabricated with a fabric strip 5-3/4 inches wide attached to two strips of 2-3/4-inch- wide, 24 gage, galvanized sheet steel. D. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene. 1. 2. 3. E. Minimum Weight: 26 oz./sq. yd.. Tensile Strength: 480 lbf/inch in the warp and 360 lbf/inch in the filling. Service Temperature: Minus 20 to plus 200 deg F. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with weatherproof, synthetic rubber resistant to UV rays and ozone. 1. 2. 3. 2.08 Provide number of hinges and locks as follows: a. Less Than 12 Inches Square: Secure with two sash locks. b. Up to 18 Inches Square: Two hinges and two sash locks. c. Up to 24 by 48 Inches: Three hinges and two compression latches. d. Sizes 24 by 48 Inches and Larger: One additional hinge. Minimum Weight: 26 oz./sq. yd.. Tensile Strength: 530 lbf/inch in the warp and 440 lbf/inch in the filling. Service Temperature: Minus 10 to plus 250 deg F. FLEXIBLE DUCTS A. Manufacturers: 1. 2. 3. 4. 5. B. Insulated-Duct: UL 181, Class 1, black polymer film supported by helically wound, spring-steel wire; 1 inch fibrous-glass insulation; polyethylene vapor barrier film. 1. 2. 3. C. Pressure Rating: 4-inch wg positive and 0.5-inch wg negative. Maximum Air Velocity: 4000 fpm. Temperature Range: Minus 20 to plus 175 deg F. Insulated-Duct: UL 181, Class 1, 2-ply vinyl film supported by helically wound, springsteel wire; 1 inch fibrous-glass insulation; polyethylene vapor barrier film. 1. 2. 3. D. Ductmate Industries, Inc. Flexmaster U.S.A., Inc. Hart & Cooley, Inc. McGill AirFlow Corporation. Thermaflex Pressure Rating: 10-inch wg positive and 1.0-inch wg negative. Maximum Air Velocity: 5000 fpm. Temperature Range: Minus 10 to plus 175 deg F. Flexible Duct Clamps: Nylon strap, in sizes 3 through 18 inches to suit duct size. Lewiston Library Second Floor Remodel Project 15820-5 15025 E. 2.09 Flexible Elbow: UL listed for return air plenums, molded composite material, one-piece design to install over outside of flexible duct. SPIN-IN AND SELF-SEALING TAKE-OFF FITTINGS A. Spin-in Fitting: Factory-fabricated assembly for making round take-off connections to rectangular ducts. 1. 2. 3. 4. B. Self-Sealing Fitting: Factory-fabricated assembly for making round take-off connections to rectangular ducts. 1. 2. 3. 2.10 2.11 Galvanized sheet steel construction. Spins into round duct opening. Adjustable damper with locking quadrant. Insulation guard for use with internally lined duct. Galvanized sheet steel construction. Neoprene seal on fitting flange for external attachment to round duct opening. Adjustable damper with locking quadrant. DUCT ACCESSORY HARDWARE A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to suit duct insulation thickness. B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease. RESIDENTIAL CLOTHES DRYER VENT WALL BOX A. Manufacturers: 1. In-O-Vate Technologies, Inc. (www.dryerbox.com) B. Description: Recessed in wall dryer venting box with top outlet for 4-inch round ducting. C. Housing: 22 gage aluminized steel; overall dimensions 21” high x 12.5” wide x 5” deep. D. Schedule: 1. Symbol “DB”: In-O-Vate Technologies, Inc. Model 425 PART 3 - EXECUTION 3.01 APPLICATION AND INSTALLATION A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts. B. Provide duct accessories of materials suited to duct materials; use galvanized-steel accessories in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts, and aluminum accessories in aluminum ducts. Lewiston Library Second Floor Remodel Project 15820-6 15025 C. Install backdraft dampers on exhaust fans or exhaust ducts nearest to outside and where indicated. D. Install volume dampers in ducts with liner; avoid damage to and erosion of duct liner. E. Install automatic control dampers where indicated. Coordinate damper installation requirements with Division 15 Section “HVAC Instrumentation and Controls”. F. Provide balancing dampers at points on supply, return, and exhaust systems where branches lead from larger ducts as required for air balancing. Install at a minimum of two duct widths from branch takeoff. 1. Provide concealed damper regulators for dampers located above hard ceilings and in other non-accessible locations. G. Provide test holes at fan inlets and outlets and elsewhere as indicated. H. Install ceiling radiation dampers, fire dampers, smoke dampers and fire/smoke dampers according to manufacturer's UL-approved written instructions. I. Install duct silencers rigidly to ducts. J. Install duct access doors to allow for inspecting, adjusting, and maintaining accessories and terminal units as follows: 1. 2. 3. K. On both sides of duct-mounted coils. Adjacent to fire or fire/smoke dampers, providing access to reset or reinstall fusible links. Adjacent to duct-mounted motorized dampers. Install the following sizes for duct-mounting, rectangular access doors: 1. 2. 3. 4. 5. One-Hand or Inspection Access: 8 by 5 inches. Two-Hand Access: 12 by 6 inches. Head and Hand Access: 18 by 10 inches. Head and Shoulders Access: 21 by 14 inches. Body Access: 25 by 14 inches. L. Label access doors according to Division 15 Section "Mechanical Identification." M. Install flexible connectors immediately adjacent to equipment in ducts associated with fans and motorized equipment supported by vibration isolators. In general, make final duct connections with flexible connectors for units without fan internal vibration isolation. Locate flexible connectors below roof level for rooftop equipment unless indicated otherwise. N. For fans developing static pressures of 5-inch wg and higher, cover flexible connectors with loaded vinyl sheet held in place with metal straps. O. Connect terminal units to supply ducts with maximum 24-inch lengths of flexible duct. Do not use flexible ducts to change directions. Lewiston Library Second Floor Remodel Project 15820-7 15025 3.02 P. Connect diffusers or light troffer boots to low pressure ducts with maximum 48-inch lengths of flexible duct clamped or strapped in place. Install sheetmetal elbow or flexible elbow at terminal connection to prevent duct crimping. Q. Bends in flexible ducts shall be made with not less than 1 duct diameter centerline radius. Do not compress ducts. R. Connect flexible ducts to metal ducts with nylon draw straps. S. Install duct test holes where indicated and required for testing and balancing purposes. ADJUSTING A. Adjust duct accessories for proper settings. B. Adjust fire and fire/smoke dampers for proper action. C. Final positioning of manual-volume dampers is specified in Division 15 Section "Testing, Adjusting, and Balancing." END OF SECTION 15820 Lewiston Library Second Floor Remodel Project 15820-8 15025 SECTION 15855 - DIFFUSERS, REGISTERS, AND GRILLES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles. Related Sections include the following: 1. 1.03 Division 15 Section "Duct Accessories" for fire and smoke dampers and volumecontrol dampers not integral to diffusers, registers, and grilles. SUBMITTALS A. Product Data: For each product scheduled, include the following: 1. 2. Data Sheet: Indicate materials of construction, finish, and mounting details; and performance data including throw and drop, static-pressure drop, and noise ratings. Diffuser, Register, and Grille Schedule: Indicate Drawing designation, model number, size, and accessories furnished. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. 2. 3. 4. 5. 2.02 SOURCE QUALITY CONTROL A. 2.03 Carnes Krueger. Nailor Industries Price Industries. Titus. Verification of Performance: Rate diffusers, registers, and grilles according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets." EXAMINATION A. Examine areas where diffusers, registers, and grilles are to be installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment. B. Proceed with installation only after unsatisfactory conditions have been corrected. Lewiston Library Second Floor Remodel Project 15855-1 15025 2.04 2.05 INSTALLATION A. Install diffusers, registers, and grilles level and plumb. B. Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practicable. For units installed in lay-in ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Architect for a determination of final location. C. Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and maintenance of dampers, air extractors, and fire dampers. Install ductmounted registers and grilles in accordance with manufacturer’s recommended procedures to assure airflow and sound performance. ADJUSTING A. After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed, before starting air balancing. END OF SECTION 15855 Lewiston Library Second Floor Remodel Project 15855-2 15025 SECTION 15861 - AIR FILTERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 SUMMARY A. 1.03 1.04 1.06 This Section includes factory-fabricated air-filter devices and media used to remove particulate matter from air for HVAC applications. SUBMITTALS A. Product Data: Include dimensions; rated flow capacity, including initial and final pressure drop at rated airflow; efficiency and test method; fire classification; furnished specialties; and accessories for each model indicated. B. Maintenance Data: For each type of filter and device to include in operation and maintenance manuals. Provide master filter schedule, listing quantity, size and type of filter for each air handling unit or terminal unit requiring filters. DEFINITIONS A. 1.05 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. MERV: Minimum efficiency reporting value (ASHRAE 52.2). QUALITY ASSURANCE A. Comply with NFPA 90A and NFPA 90B. B. ASHRAE Compliance: Comply with provisions of ASHRAE 52.1 and ASHRAE 52.2 for methods of testing and rating air-filter units. EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Provide one complete set of filters for each air handling unit or terminal unit requiring filters. If system includes prefilters, provide only prefilters. Obtain signed receipt from Owner’s representative. Lewiston Library Second Floor Remodel Project 15861-1 15025 PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. 2. 2.02 EXTENDED-SURFACE, DISPOSABLE PANEL FILTERS A. Description: Factory-fabricated, dry, extended-surface filters with holding frames; UL Class 2 listed. B. Media: Reinforced, non-woven cotton/synthetic blend media formed into deep-V-shaped pleats and held by self-supporting wire grid. C. Media and Media-Grid Frame: Nonflammable, moisture-resistant beverage board with diagonal and horizontal support members on the upstream and downstream sides. D. Thickness: 2 inch E. Performance: 1. 2. 3. 4. 5. 2.03 Air Filters: a. AAF International. b. Airguard Industries, Inc. c. Camfil/Farr d. Flanders-PrecisionAire e. Glasfloss Industries f. Purolator Products. g. Research Products Corp. Filter Gages: a. Dwyer Instruments Inc. Average efficiency: 25-30% (ASHRAE 52.1) MERV: 8 (ASHRAE 52.2) Average arrestance: 90-92% Initial (clean) resistance: 0.25-0.30 inch wg. at 500 fpm. Recommended final (changeout) resistance: 0.9 inch wg. FILTER GAGES A. Description: Diaphragm type with dial and pointer in metal case, vent valves, black figures on white background, and front recalibration adjustment. 1. 2. 3. B. Diameter: 4-1/2 inches. Range: 0- to 2.0-inch wg. Range: 0- to 4.0-inch wg. Accessories: Static-pressure tips, tubing, gage connections, and mounting bracket as required for application. Lewiston Library Second Floor Remodel Project 15861-2 15025 PART 3 - EXECUTION 3.01 INSTALLATION A. Install filter frames according to manufacturer's written instructions. B. Position each filter unit with clearance for normal service and maintenance. C. Install filters in position to prevent passage of unfiltered air. D. Install filter gage for each air handling unit filter bank where not factory installed. E. Install filter gage static-pressure tips upstream and downstream from filters to measure pressure drop through filter. Mount filter gages on outside of filter housing or filter plenum in an accessible position. F. Coordinate filter installations with duct and air-handling unit installations. G. Clean filter housings after completing system installation and install new filters in all air handling equipment prior to testing, adjusting and balancing. H. Where allowed, install filters in all air handling equipment used for temporary heating or air circulation. Filters shall be disposable type, not less than 25-30% efficiency and shall be inspected frequently during construction to prevent damage to equipment and accumulation of debris in duct systems. Air handling equipment shall not be operated without filters in place. END OF SECTION 15861 Lewiston Library Second Floor Remodel Project 15861-3 15025 SECTION 15900 - AUTOMATIC TEMPERATURE CONTROLS PART 1 - GENERAL 1.01 1.02 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections apply to this Section. B. Division 15 Section “Basic Mechanical Materials and Methods” apply to this Section. MECHANICAL PROJECT CLOSEOUT A. 1.03 1.04 1.05 Comply with requirements of Division 15 Section “Mechanical Project Closeout”, in addition to any specific requirements of this Section. SCOPE OF WORK A. Furnish and install all control equipment, engineering services, job drawings and field supervision for automatic temperature control systems described in this Section and/or indicated on the Drawings. B. Refer to Division 15 Section "Testing, Adjusting and Balancing" scope of work. Provide assistance as required for DDC System adjustments, manipulation of operational sequences, etc. for HVAC systems balancing. SERVICE AND GUARANTEE A. The temperature control system(s) as herein specified shall be free from defects in workmanship and material under normal use and service. If within one (1) year from date of Acceptance by the Owner, any of the equipment herein described is proved to be defective in workmanship or material, it shall be replaced or repaired at no expense to the Owner. B. The Contractor shall, after completion of the original test of the installation and Acceptance by the Owner, provide any service incidental to the proper performance of the temperature control system under guarantees outlined above for the period of one (1) year, after completion of the installation, the Contractor shall regulate and adjust all equipment provided. CODES AND STANDARDS A. Electrical Standards: Provide electrical products which have been tested, listed and labeled by UL and comply with NEMA standards. B. NEMA Compliance: Comply with NEMA standards pertaining to components and devices for electric control systems. C. NFPA Compliance: Comply with NFPA 90A "Standard for the Installation of Air Conditioning and Ventilating Systems" where applicable to controls and control sequences. Lewiston Library Second Floor Remodel Project 15900-1 15025 1.06 SUBMITTALS AND SHOP DRAWINGS A. Shop Drawings: Shop drawings shall be submitted in accordance with the General Conditions and shall consist of a complete list of equipment and materials, including manufacturer's descriptive and technical literature, control sequences, catalog cuts, and installation instructions. Shop drawings shall also contain complete wiring and wiring routing, routing, schematic diagrams, tag number of devices, software descriptions, calculations, and any other details required to demonstrate that the system has been and will function properly. Drawings shall show proposed layout and installation of all equipment and the relationship to other parts of the work. B. Shop drawings shall be approved before any equipment is installed. Therefore, shop drawings must be submitted in time for review so that all installations can be completed per the project's completion schedule. C. All drawings shall be reviewed after the final system checkout and updated or corrected to provide Record Drawings to show exact installation. Furnish three (3) sets of Record Drawings. PART 2 - PRODUCTS 2.01 MATERIALS AND EQUIPMENT A. 2.02 Provide electric control products in sizes and capacities indicated, consisting of dampers, thermostats, sensors and other components as required for complete installation. Except as otherwise indicated, provide manufacturer's standard control system components as indicated by published product information, designed and constructed as recommended by manufacturer as indicated. ROOM THERMOSTAT A. Programmable type with seven day programming for two occupied and two unoccupied periods per day; individual occupied and unoccupied set points; three hour override of unoccupied program with automatic return to programmed schedule; battery back-up with rechargeable nicad battery; fan "auto" cycle available for both occupied and unoccupied cycles; automatic changeover on heating/cooling sequences. Thermostat shall be Honeywell TB7220, or equal. Coordinate with rooftop unit specifications. B. Provide clear heavy duty polycarbonate locking thermostat cover for all thermostats in public areas RTU-8, 10, 11 (Alt. #6), 13, 14, 15, 16, 17, and 18. PART 3 - EXECUTION 3.01 ELECTRICAL A. Install systems and materials in accordance with manufacturer's instructions and roughing-in drawings, and details on drawings. Install electrical components and use electrical products complying with requirements of applicable Division 16 sections of these specifications. All system controllers, junction boxes, etc. shall be mounted at readily accessible and convenient locations and heights. Lewiston Library Second Floor Remodel Project 15900-2 15025 3.02 B. Room Temperature Sensors and Thermostats - Mounting Heights: C. Room temperature sensors and thermostats with occupant adjustment capabilities shall be mounted with the highest operable part at 54 inches above finished floors where the clear floor space allows parallel approach by a person in a wheelchair. D. Room temperature sensors and thermostats with occupant adjustment capabilities shall be mounted with the highest operable part at 48 inches above finished floors where the clear floor space allows only forward approach by a person in a wheelchair. E. Room temperature sensors and thermostats without occupant adjustment capabilities shall be mounted at 60 inches above finished floors. unless otherwise specifically indicated on the Drawings. F. Control Wiring: The term “control wiring” is defined to include providing of wire, conduit and miscellaneous materials as required for mounting and connecting electrical control devices. G. Wiring System: Install complete control wiring system for electric control systems. Conceal wiring, except in mechanical rooms and areas where other conduit and piping are exposed. Provide multi-conductor instrument harness (bundle) in place of single conductors where number of conductors can be run along common path. Fasten flexible conductor's bridging cabinets and doors, neatly along hinge side, and protect against abrasion. Tie and support conductors neatly. ADJUSTMENTS A. After completion of installation, adjust thermostats, dampers, motors and similar equipment provided as work of this section. PART 4 - SEQUENCE OF OPERATION 4.01 ROOFTOP UNIT "RTU-8 THROUGH RTU-19" A. The heating and cooling setpoints shall be individually adjustable for both occupied and unoccupied periods. The thermostat shall be capable of a deadband of 5 deg. F (no mechanical heating or cooling shall operate within this deadband). Space temperature deviation above cooling setpoint or below the heating setpoint shall generate a demand signal to control the system as follows: B. Heating 1. 2. The thermostat shall control the heating output based on the demand signal communicated from the thermostat program, taking into account both space temperature deviation and the duration of that temperature deviation. The outdoor air damper shall be at the set minimum position during the occupied period, and shall be closed during the unoccupied period of the heating mode. Lewiston Library Second Floor Remodel Project 15900-3 15025 C. Cooling 1. The thermostat shall control the cooling outputs based on the demand signal communicated from the thermostat program, taking into account both space temperature deviation and the duration of that temperature deviation. Unit mounted controls shall enable economizer as first stage of cooling whenever OSA temperate is lower than return air temp. D. CO2 control of OSA - During occupied periods, modulate outside-air damper open on rising carbon dioxide concentrations, overriding normal damper operation to maintain maximum carbon dioxide level of 1000 ppm +/- 100 ppm as determined by carbon dioxide sensor. Maintain minimum mixed-air temperature limit of 50 deg F (adj.). Coordinate with Rooftop unit specifications. E. Heating Setback and Cooling Setup: 1. Initiation of heating setback or cooling setup for each of 7 days shall be provided by a programmed time schedule manually entered into the thermostat. When all or a portion of a manually programmed schedule is unavailable, the thermostat shall control the unavailable program functions to occupied mode and default setpoint ranges as follows: Heating Cooling 2. 3. F. Setpoint Recovery from Unoccupied to Occupied The thermostat shall employ "Intelligent Recovery (tm)". This shall select the optimum time to begin building warm-up or cool-down based on setpoints and occupied program. Fan Operation 1. 2. G. TABLE OF DEFAULT SETPOINT RANGES OCCUPIED deg. F UNOCCUPIED deg. F 70 55 76 90 Fan operation shall be constant during the occupied period. Fan operation shall be intermittent during the unoccupied period. Heating and Cooling Operation Minimum On/off Times 1. The thermostat shall incorporate a program to maintain minimum-stage operation times of 2 minutes "on" and 4 minutes "off" for compressor stages, and 2 minutes "on" and 2 minutes "off" for gas heat. END OF SECTION 15900 Lewiston Library Second Floor Remodel Project 15900-4 15025 SECTION 15955 - TESTING, ADJUSTING AND BALANCING PART 1 - GENERAL 1.01 SCOPE A. The air distribution systems shall be balanced by an independent testing, adjusting and balancing (TAB) firm or an Engineering firm with a minimum five years experience in HVAC design and balancing. The TAB firm shall furnish the necessary instruments for making tests, perform balancing work, and issue a certified report of balancing work performed. Balancing reports shall be AABC, NEBB certified or shall be certified by a Registered Professional Mechanical Engineer registered in the State where the project is located. PART 2 - PRODUCTS (Not Applicable) PART 3 - EXECUTION 3.01 PROJECT CONDITIONS A. TAB work shall not be started until such time as the following conditions are completely fulfilled: 1. 2. 3. 3.02 INSTRUMENTS A. 3.03 Systems shall be completely installed and shall have been successfully test run, and fully operational. Outlets, dampers, balancing devices, and accessories shall be completely installed. Filters shall be clean. Instruments used for TAB measurements shall be accurate and calibration histories for each instrument shall be available for examination. PROCEDURES FOR AIR SYSTEMS A. TAB for air systems shall include the following: 1. 2. 3. 4. 5. 6. 7. Set supply fans at design speeds and record average amperage readings on all fan motor phases, static pressures and cfm of air flow in each system. Read air flows at diffusers and grilles with a flow hood or equal air measuring device. Adjust dampers as required. Adjust outside air dampers to scheduled minimum cfm. Adjust fans as required to meet design airflows. Check for drafts, noise and vibration. After balancing is complete, mark final position of balancing dampers. Report any discrepancies. Lewiston Library Second Floor Remodel Project 15955-1 15025 3.04 PROCEDURES FOR HYDRONIC SYSTEMS A. TAB for hydronic systems shall include the following: 1. 2. 3. 4. 3.05 TOLERANCES A. Set HVAC system airflow rates within the following tolerances: 1. 2. 3.06 Determine total flow by the use of flow meters. With full flow, record total pump head and compare with pump curve and record amperage. Pump curves with operating point indicated shall be included in the balancing report. Record and adjust flow to each coil or terminal by adjusting flow control. If manual calibrated balancing type valves are used, record each coil or terminal, indicate valve type and size. Record and adjust flow to each coil or terminal by adjusting valve. If automatic, pre-set type valves are used, record each coil or terminal and valve pressure drop; indicate valve type and size. Make spot checks on flow of approximately 20 percent of the valves and record results. Report any discrepancies. Supply, Return, and Exhaust Fans and Equipment with Fans: +/- 10 percent. Air Outlets and Inlets: +/- 10 percent. REPORTS A. Submit, on neat and legible forms, the full, certified report of systems operation, initial and final readings. B. Upon completion of TAB of air systems prepare a complete and legible preliminary report. Submit 2 copies for review. C. Upon verification and approval of the preliminary report, prepare final certified report. Furnish one copy to the Architect, and the remaining 3 copies are to be included in the Owner's Operation and Maintenance Manuals. END OF SECTION 15955 Lewiston Library Second Floor Remodel Project 15955-2 15025 SECTION 16010 - GENERAL ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 1.03 Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this section. SCOPE OF WORK – GENERAL A. This section specifies general requirements for electrical installations and includes requirements common to more than one section of Division 16. It expands and supplements the requirements specified in sections of Division 1. B. Provide materials, labor, transportation, tools, permits, facilities, fees, inspections, utilities and incidentals necessary for the complete installation of electrical work indicated and described in the Contract Documents. C. It is the intent of the Contract Documents to provide an installation complete in every respect. In the event that additional details or special construction is required for work indicated or specified under this section of work or work specified in other sections, provide material and equipment which is usually furnished with such systems in order to complete the installation, whether mentioned or not. D. All work shown and/or specified shall be completely installed and connected in a first calls and workmanlike, professional manner. Work shall be complete in all details. E. All work shall be performed by trade technicians properly qualified to perform the work required. System-specific sub contractors shall be hired (as required) to furnish and install the system. F. Workmanship shall comply with the National Electrical Installation Standards (NEIS), published by the National Electrical Contractors Association (NECA). G. All work shall be done in accordance with system manufacturer’s instructions, recommendations, and requirements, with the exception where the drawings or specifications indicate other detailed instructions. SEQUENCE OF WORK A. Conduct work in sequence to provide least possible interference to the activities of the Agency, and to permit orderly transfer of activities and equipment to completed areas. B. Work shall be substantially complete by the dates listed in Division 1 Section, “Summary”. Lewiston Library Second Floor Remodel Project 16010-1 15025 C. 1.04 ALTERNATES A. 1.05 1.06 Refer to Division 0 Section, “Instruction to Bidders” for phased construction requirements. The Library will be occupied during the entire construction period; coordinate with the Owner during construction operations to minimize conflicts and facilitate Library usage. Perform work so as not to interfere with Library’s operations. Refer to Division 1 Section, “Alternates” for description of alternates. Review Contract Documents for additional information. DEFINITIONS A. Provide: Furnish and install complete and ready for intended use. B. Indicated: Indicated on drawings. C. Noted: Noted on Drawings or in Specifications. D. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. E. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical and electrical equipment rooms. F. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. G. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants and hidden from sight. Examples include above ceilings, within finished walls and in chases or furred spaces. H. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters and utility vaults. CODES AND STANDARDS A. Code Compliance: Comply with most current adopted edition of following: 1. 2. 3. 4. 5. 6. 7. International Building Code (IBC), Standards and Amendments. International Mechanical Code (IMC), Standards and Amendments. International Fire Code (IFC) Standards and Amendments. National Fire Protection Association (NFPA). National Electrical Code (NEC); NFPA 70. American with Disabilities Act (ADA). Applicable State and local codes, laws and ordinances. Lewiston Library Second Floor Remodel Project 16010-2 15025 B. Standards and Regulations Compliance: Comply with most current adopted edition of following: 1. 2. 3. 4. 5. 6. C. 1.07 1.08 Comply with Contract Document requirements which exceed minimum code and standards requirements. SAFETY OF PERSONS AND PROPERTY A. Comply with applicable laws, ordinances, rules and regulations of any public authority for the safety of persons and property, including requirements of the Idaho Division of Building Safety and/or the Occupational Safety and Health Act (OSHA) and Division 1, General and Supplementary Conditions. B. Comply with any and all safety code, rules, regulations, and standards of the City of Lewiston. PERMITS AND FEES A. 1.09 BICSI Telecommunications Distribution Methods Manual (TDMM), Standards/Practices and Amendments. Institute of Electrical and Electronics Engineers (IEEE), Standards/Practices and Amendments. ANSI/TIA/EIA-568-B, Standards and Amendments. ANSI/TIA/EIA-569-B, Standards and Amendments. ANSI/TIA/EIA-606-A, Standards and Amendments. ANSI J-STD-607-A, Standards and Amendments. Obtain and pay for required permits and fees necessary to fully complete work included in the Contract Documents. INTENT AND INTERPRETATION A. Drawings and Specifications supplement each other and any details contained in one and not the other shall be included as if contained in both. Items not specifically mentioned in the specifications or noted on the drawings, but which are obviously necessary to make a complete working installation shall be provide to make a complete and working installation ready for intended use. B. Drawings are partly diagrammatic and do not necessarily show exact location of new equipment, conduits, and existing utilities, unless specifically dimensioned. Size and location of equipment are drawn to scale where possible, however some graphic symbols may be distorted dimensionally to obtain clarity in representation. C. Approximate location of each item is indicated on the drawings. These drawings are not intended to give complete and exact details in regard to location. Exact locations are to be determined by actual measurements at the building(s). D. Riser and other diagrams are schematic only and do not necessarily show the physical arrangement of equipment. They shall not be used for obtaining quantities or lineal runs of conduit and conductors. Lewiston Library Second Floor Remodel Project 16010-3 15025 1.10 E. Drawings generally indicate required minimum allowable size, quantity and type of conductors and points of termination of conduits. Routing or total number of conduits required for circuits are not indicated. Provide additional conduits as required to complete installation for specific equipment furnished. F. Receptacles, switches, and other devices shall be located symmetrically with Architectural elements and coordinated with equipment or devices furnished in other Sections. Devices shall be centered on windows, wall spaces, or other items, unless specifically dimensioned otherwise. G. Electrical drawings shall serve as working drawings for Division 16 work. Refer to architectural documents for additional information which may effect the installation of electrical work such as mechanical equipment. Architectural drawings shall take precedence over the electrical drawings if any dimensional discrepancies exist. SUBMITTAL OF EQUIPMENT FOR APPROVAL A. Refer to Division 1 Section, “Submittals” for submittal definitions, requirements and procedures. Additional requirements are listed below. B. Shop drawings, catalog information, and material schedules shall be submitted for approval of materials and equipment prior to ordering. The submitter is to provide riser and interconnection wiring diagrams for the following low voltage systems: 1. 2. 3. 4. 5. Fire Alarm Notification and Detection Security and Access Control Sound Systems Audio/Video Telecommunications C. Provide detailed riser and interconnecting wiring diagrams for required systems if not specifically indicated on the drawings. D. Submittal data shall clearly identify electrical components, devices and accessories as listed and labeled by Underwriter’s Laboratory, or other testing agency acceptable to authorities having jurisdiction, and marked for intended use. E. Clearly mark submittals as to which items, options, colors, model, etc are to be furnished. F. Submittals not meeting the following requirements will be returned for revision: 1. 2. 3. Provide a cover page for each item or group of items. Cover page shall provide a 3” x 5” space for Engineer’s review stamp. Each cover page must be clearly identified with the project name, specification number and paragraph number. Submittal package must be accompanied by an itemized index listing specification section, paragraph number, item and manufacturer; larger projects will be index tabbed by specification section with index for each section. Lewiston Library Second Floor Remodel Project 16010-4 15025 1.11 GUARANTEE A. 1.12 Guarantee satisfactory operation of material and equipment installed under Division 16. Repair or replace any defective materials, equipment, or workmanship which may show itself within one year from date of Substantial Completion. SCHEDULE OF VALUES A. Furnish to the Engineer, a breakdown of the Contract work in Divisions 16 within thirty (30) days of the Notice to Proceed. B. The breakdown shall list cost for materials and labor as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. Miscellaneous Overhead Expenses Mobilization Permits Panelboards Panelboard Labor Feeder Conduit and Conductors Material Feeder and Conductors Labor Branch Circuit Conduit and Conductors Material Branch Circuit Conduit and Conductors Labor Device Material Device Labor Lighting Fixtures Lighting Fixture Labor Fire Alarm and Detection System Fire Alarm and Detection System Labor Telecommunication Systems Telecommunication Systems Labor Access Control System Access Control System Labor Sound Systems Sound Systems Labor Equipment Connections Commissioning Activities Project Closeout: a. O&M Manuals b. Record Documents c. Owner Training PART 2 - PRODUCTS 2.01 GENERAL MATERIALS AND EQUIPMENT REQUIREMENTS A. Materials used under this Contract, unless specifically noted otherwise, shall be new and of the latest and most current model line produced by the manufacturer. Outdated “new” equipment is not acceptable. Lewiston Library Second Floor Remodel Project 16010-5 15025 B. 2.02 Electrical components, devices, and accessories to be listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. EQUIPMENT AND MATERIAL SUBSTITUTIONS A. Throughout these Contract Documents, various materials, equipment, apparatus, etc., are specified by manufacturer, brand name, and type or catalog number. Such designation is to establish standards of desired quality and construction and shall be the basis of the bid. B. Where more than one manufacturer is listed, and only one manufacturer's catalog number is indicated, that standard of quality and construction shall be maintained by materials supplied by other manufacturer(s). C. Substitutions of equipment or materials shall be made only with written prior approval. Prior approval requests must be received at least ten (10) days prior to bid date unless otherwise instructed. Refer to Division1 Section, “Product Requirements” for procedures in requesting substitutions. D. Acceptance of substitution request signifies manufacturer recognition only. No attempt has been made to check each item as to special features, capacities, or physical dimensions required by this project. Verify requirements before submitting for approval. Acceptance of exact features, sizes, capacities, etc., all of which must meet or exceed design requirements will be determined when submitted during the construction phase. E. The Contractor shall bear full responsibility for substituted equipment and materials, including, but not limited to: 1. 2. 3. 4. 5. Costs. Available space requirements. Effect on other trades. Changes in electrical requirements Changes in structural requirements. PART 3 - EXECUTION 3.01 COORDINATION A. Refer to Division 1 Section “Coordination”. B. Coordinate available space for equipment and systems with other trades. Refer to Architectural, Structural and Mechanical Drawings for additional building details necessary for coordination. C. Cutting, patching, wiring, finishing or any other work required for relocation of work installed due to interferences between various trades will be at no additional cost to the Owner. Lewiston Library Second Floor Remodel Project 16010-6 15025 3.02 CUTTING AND PATCHING A. Comply with Division 1 Section, “Execution Requirements” for general requirements for cutting and patching. B. All cutting, drilling and patching that must be done in order that work is properly installed. All work of this nature is subject to the following conditions: 1. 2. 3. 4. 3.03 MANAGEMENT OG CONSTRUCTION WASTE A. 3.04 3.05 3.06 All disturbed construction or finish must be made good. Structural work shall not be disturbed, except on approval of the project architect. In general, cutting through floors, walls and partitions is to be avoided and only where absolutely necessary will same be permitted. When necessary, it shall be done in a careful manner and the opening filled about conduits as directed by the architect. Holes through concrete or masonry shall be made only with a core drill. Obtain permission from architect for each individual opening. All masonry or other finish damaged or cut into during the installation of this work must be replaced or repaired with materials of like kind and quality as the original materials by skilled labor, experienced in that particular building trade. Comply with Division 1 waste management and disposal procedures. Separate and segregate recyclable materials by type. CLEANUP A. At the time of final cleanup, all fixtures and equipment, new or existing, shall be thoroughly cleaned and left in condition for use. All debris and unused materials shall be removed from the construction site, leaving the premises in a clean condition. B. Site shall be kept clean on a day-to-day basis. SLEEVES A. Sleeves: EMT conduit with insulated throat bushings for each end. B. Provide sleeves where required, sized as noted on the Contract Documents. Where not noted, sleeve sizing shall be determined by the type and quantity of cable to be routed through the sleeve per TIA/EIA 569A cable capacity standards, plus an additional 100% for future expansion. C. Provide roto-hammering or core drilling where required for installation. D. Seal between sleeve and wall or floor in which the sleeve is installed. penetration to restore wall or floor to pre-penetration fire-rating. Firestop PAINTING A. Paint all exposed conduits, raceways, multi-outlet assemblies and panelboard trim as directed by architect. Lewiston Library Second Floor Remodel Project 16010-7 15025 B. 3.07 Comply with Division 9 Section “Paints and Coatings” requirements for painting. TESTS A. All work shall be complete in every respect and shall be tested and approved satisfactory to the architect and in accordance with the local, state and federal regulations governing the installation. B. Be responsible for making any and all tests necessary to insure against concealment of defective materials and/or workmanship. C. Determine, by test, that all wiring and connections are free from shorts between wires and shorts to ground and that all circuits have proper continuity. D. All defects shall be corrected and retested before installation of fixtures and equipment. E. Installed systems shall be tested for conformity to specifications and for proper operation. Provide certification and/or documentation as described in the following individual Division 16 Sections: 1. 2. 3. F. 3.08 3.09 Typical tests shall include outlet polarity, insulation resistance, large circuit breaker tests, surge suppression systems, phase relationships and load balance. MANUFACTURER'S INSTRUCTIONS A. Furnish proper equipment and/or materials required for installation as intended by the manufacturer, for all work described under Division 16. If needed for proper installation or operation, request advice and supervisory assistance from the representative of the specific manufacturer. Manufacturer's published instructions shall be followed for preparing, assembling, installing, erecting, and cleaning manufactured materials or equipment, unless otherwise indicated. B. Promptly notify the architect in writing of any conflict between the requirements of the Contract Documents and the manufacturer's directions and obtain the architect's instructions before proceeding with the work. SEISMIC RESTRAINTS A. 3.10 Section 16720 Section 16727 Section 16751 Newly installed equipment, devices, conduits, fixtures, raceways, etc shall be installed with seismic restraints in accordance with requirements of the latest edition of the International Building Code. EXAMINATION OF SITE A. Visit site of proposed work and become familiar with conditions affecting work prior to bid. Lewiston Library Second Floor Remodel Project 16010-8 15025 B. 3.11 3.12 CONTINUITY OF SERVICES A. Minimize interruption of existing electrical services and systems (power, fire alarm, telephone, intercom, etc) during construction phase. Prior to shutting off any existing services or systems, obtain permission from the architect and a designated representative of the Library at least one (1) week prior to the shutdown. B. Schedule all work to assure continuity of electrical services or systems. Provide additional temporary feeders, wiring, panels, etc. as required at no additional cost to the Agency and/or Owner to assure continuity during construction. SITE UTILITY SERVICES A. 3.13 Existing sidewalks, concrete paving, curbs, or asphalt paving removed or damaged during period of installation or as a result thereof, shall be replaced with like material in a manner as directed by and to the satisfaction of the Architect. Comply with Division 2 requirements. OPENINGS IN CONDUITS A. 3.16 Locations of equipment and devices, as shown on the drawings, are approximate unless dimensioned. Exact locations of such items shall be determined from the Construction Drawings. Verify physical dimensions of each component of electrical equipment, to fit available space and promptly notify the architect prior to roughing-in if conflicts appear. Coordinate equipment to available space and access routes through construction. Offsets in conduits required for proper system installation shall be provided at no additional cost to Owner. REPLACEMENT OF PAVING AND CONCRETE A. 3.15 Where applicable, make connections to temporary electrical service immediately so as to provide the use of this service by other traces. Comply with Division 01 Section “Temporary Facilities and Controls” requirements. LAYING OUT WORK A. 3.14 Verify measurements at the building before beginning work. Cap or seal temporary openings in conduits or raceways during construction. Remove caps or seals for final connections. DELIVERY, STORAGE, AND HANDLING A. Deliver products to project properly identified with names, model numbers, types, grades, compliance labels, and similar information needed for distinct identifications; adequately packaged and protected to prevent damage during shipment, storage, and handling. B. Store equipment and materials at the site, unless off-site storage is authorized in writing. Protect stored equipment and materials from damage. Lewiston Library Second Floor Remodel Project 16010-9 15025 C. 3.17 3.18 Coordinate deliveries of electrical materials and equipment to minimize construction site congestion. Limit each shipment of materials and equipment to the items and quantities needed for the smooth and efficient flow of installations. ACCESSIBILITY A. Install equipment and materials to provide required access for servicing and maintenance. Coordinate location of concealed equipment and devices requiring access with location of access panels and doors. B. Allow ample space for removal of parts that require replacement or servicing. C. Access Doors: Prime coated 14 gauge steel, and flush, with screwdriver operated cam lock, frame to accommodate construction type. Access doors, shall be manufactured by Acudor, Elmdor or approved equivalent. See Division 08 section “Access Doors and Frames.” FIRESTOPPING A. Material: Conform to both Flame (F) and Temperature (T) ratings as required by local building codes and as tested by nationally accepted test agencies per ASTM E814 or UL 1479 fire test in a configuration that is representative of the actual field conditions. Manufactured by: 1. 2. 3. 4. 5. Specified Tech., Inc. Metacaulk Dow Corning 3M Fire Protection Products Tremco Sealants and Coatings B. Firestopping Materials: Firestopping materials shall emit no toxic or combustible fumes, and shall allow for normal movement of the building structure and the penetrating elements without adversely affecting the adhesion or integrity of the firestopping system. C. Openings in fire-rated walls, ceilings, or floors shall be protected by maintaining an effective barrier against the spread of flame, smoke, and gases. Where the penetrating elements are cables, corrugated plastic ducts, or other combustible items, firestopping materials shall be intumescent type. Firestopping shall consist of UL listed fire-rated assemblies and shall be installed in accordance with UL approved installation details. END OF SECTION 16010 Lewiston Library Second Floor Remodel Project 16010-10 15025 SECTION 16015 – ELECTRICAL PROJECT CLOSEOUT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 General Requirements, apply to work of this section. B. Related Sections include the following: 1. 2. 1.02 SCOPE OF WORK - GENERAL A. This section specifies procedural requirements for electrical installations project closeout, including but not limited to: 1. 2. 3. 4. 5. 1.03 Division 1 Section “Submittal Procedures”. Division 1 Section “Closeout Procedures.” Project Record Document submittal. Operation and Maintenance Manual submittal. Operation and Maintenance Instruction and Training. Electrical Equipment and Systems Start-Up. Final Cleaning. PROJECT RECORD DOCUMENTS A. Record differences between electrical Work as installed and as shown in Contract Drawings on a set of dedicated electrical “as-built” plans. Plans to be obtained from the Architect. Return the finished plans to the Architect at completion of the project. Notations made on drawings shall be neat and legible using red ink only. Mistakes or corrections shall be crossed out and the correction made next to it. Comply with Division 1 Section requirements. B. Mark drawings to indicate the following: 1. 2. 3. 4. 5. 6. Revisions to conduits and conductors; size and location both exterior and interior. Revisions to branch circuiting. Revisions to device and outlet location and/or height. Revisions to lighting fixture locations. Concealed equipment and/or devices. Installed location of all underground site utilities including but not limited power, telecommunication, and future conduit raceways. C. Revise equipment and fixture schedules on the plans to indicate actual installed manufacturer and model numbers. D. Mark specifications to indicate change orders; actual equipment and materials used. E. Record the following information for each connected motor and equipment item: 1. Nameplate data (volts, amps, phase) Lewiston Library Second Floor Remodel Project 16015-1 15025 2. 3. F. 1.04 Actual current drawn by each equipment item and each motor larger than 1/3 horsepower when operating at or near normal load. Rating and catalog number or each thermal overload device finally selected for each motor over 1/3 horsepower. Record the voltage between phases and between each phase and neutral, and the actual current in each phase at each panel with normal load applied. OPERATION AND MAINTENANCE MANUALS A. Prepare and submit Operation and Maintenance (O&M) Manuals for electrical systems provided. Comply with Division 1 Section requirements. B. Manual binder shall have permanent lettering of a contrasting color. C. Information to be included on the binder cover is as follows: ELECTRICAL OPERATION AND MAINTENANCE MANUAL LEWISTON CITY LIBRARY LEWISTON IDAHO 2016 OWNER: (NAME) ARCHITECT: CASTELLAW KOM ARCHITECS ELECTRICAL ENGINEER: L&S ENGINEERING ASSOCIATES, INC. GENERAL CONTRACTOR: (NAME) ELECTRICAL CONTRACTOR: (NAME) 1. 2. Information to be included on the binder spine is as follows: ELECTRICAL O & M MANUAL (Year) (Project Name) D. Provide master index at beginning of Manual showing sections and items included. Use plastic tab indexes for sections of Manual. E. Cover section: List name, address, and phone number of Project Architect, General Contractor, Electrical Engineer, Electrical Contractor and all Electrical Sub-Contractors. Provide a list of equipment suppliers with address and phone number. F. Provide a separate section for each Section of the Specifications. Provide index for each section listing equipment included. Include all items specified. Lewiston Library Second Floor Remodel Project 16015-2 15025 G. Include descriptive literature of each manufactured item (catalog cut sheets, etc). Literature shall show capacities and size of equipment used and be marked indicating each specific item with applicable data underlined. Data sheets shall be originals or clean copies of originals. Copies of faxes are not acceptable. H. Include copies of approved submittals or shop drawings for all items requiring submittal. I. One (1) copy of the O&M Manual shall be submitted for review and approval by the Design Engineer. After approval, submit three (3) copies of the manual to the Architect for approval, unless otherwise directed by Division 1 Section requirements. J. Information to be included in O&M Manual: 1. 2. 3. 4. 5. 6. 7. 8. 1.05 Description of function, normal operating characteristics and limitations, performance curves, engineering data and tests, and complete nomenclature and commercial numbers of all replaceable parts. Manufacturer's printed operating procedures to include start-up, break-in, routine and normal operating instructions; regulation, control, stopping shut-down, and emergency instructions; and summer and winter operating instructions. Maintenance procedures for routine preventative maintenance and troubleshooting; disassembly, repair, and reassembly; aligning and adjusting instructions. Itemized listing of lamp type and source for all installed lighting fixtures. Sequence of operation for each installed system. Test records and certifications. Equipment start-up reports. Warranty information and letters of guarantee. K. Complete O&M Manual shall be available for use by Owner's representatives during instruction and training sessions. L. Provide electronic files of approved O&M Manual. Division 1 Section “Operation and Maintenance Data”. Comply with requirements of OPERATION AND MAINTENANCE INSTRUCTION AND TRAINING A. Instruct Owner's Representative(s) in the Operation and Maintenance procedures described in Operation and Maintenance Manual. Comply with Division 1 Section requirements. B. Enlist services of qualified personnel, including each sub-trade and factory trained specialists for each major piece of equipment, to attend training sessions and provide operation and maintenance instructions. C. Submit training agenda, schedule and list of representatives to Design Engineer for review 30 days prior to training sessions. Confirm attendance by written notification to all participants. Lewiston Library Second Floor Remodel Project 16015-3 15025 D. Prepare checklist of all equipment and systems requiring instruction and maintenance for verification and agreement by the Owner's Representative of satisfactory start-up and instruction. Checklist shall include a statement of completion by the Contractor, date and topic(s) covered in each training session, and an attendance list of all participants at each training session. Submit a copy of checklist to Design Engineer for review 30 days prior to training sessions. Include copy of the completed checklist in Operation and Maintenance Manual. E. Minimum instruction time shall be 8 hours, unless otherwise specifically noted. Refer to individual Division 16 Sections for additional instruction/training requirements. F. All electrical systems shall be properly functioning prior to instruction period. PART 2 - EXECUTION 2.01 2.02 ELECTRICAL EQUIPMENT AND SYSTEMS START-UP A. Provide the services of a factory-authorized service representative to test and inspect unit installation, provide start-up service and demonstrate and train Owner's maintenance personnel. B. Include certification of factory-authorized representative status as part of equipment submittal from manufacturer. C. Include written start-up reports with test data for equipment in Operation and Maintenance Manual.Required Equipment items shall include the following:Section 16561, 16720, 16727, and 16751. FINAL CLEANING A. Refer to Division 1 Section general requirements for final cleaning. B. At time of final cleanup, clean all lighting fixtures, devices and equipment and leave in condition for use intended. Vacuum cabinet interiors of control panels, mechanical units, etc. to remove all electrical construction debris. END OF SECTION 16015 Lewiston Library Second Floor Remodel Project 16015-4 15025 SECTION 16020 – ELECTRICAL DEMOLITION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specifications, apply to work of this section. B. Related Sections include the following: 1. 2. 3. 1.02 1.03 Division 1 Section, “Summary” for phasing requirements. Division 1 Section, “Cutting and Patching”. Division 1 Section, “Selective Demolition” for general demolition requirements and procedures. SUMMARY A. Include all labor, equipment, and materials necessary to complete demolition of existing electrical systems as shown on the drawings and described herein. B. Electrical services to areas occupied by Owner shall be maintained. If interruptionof service is necessary, coordinate and schedule work with owner to minimize interruption. C. Remove and dispose of all transformers and related equipment which contain polychlorinated biphenals (PCB’s) in full compliance with EPA regulations. DEFINITIONS A. Remove: Detach items from existing construction and legally dispose of them off-site, unless idicated to be removed and salvaged or removed and reinstalled. B. Remove and Salvage: Detach items from existing construction and deliver them to Owner. C. Remove and Reinstall: Detach items from existing construction, prepare them for reuse, and reinstall them where indicated. D. Existing to Remain: Existing items of construction that are not to be removed and that are not otherwise indicated to be removed, removed and salvaged, or removed and reinstalled. PART 2 - SALVAGE 2.01 MATERIALS OWNERSHIP A. The Owner shall have first salvage rights to all removed lighting fixtures and equipment. Coordinate selection with the Owner's Representative. Lewiston Library Second Floor Remodel Project 16020-1 15025 B. Except for items or materials to be reused, salvaged, reinstalled or otherwise indicated to remain owner’s property, demolished materials shall become Contractor’s property and removed from Project site. C. Transport and legally dispose of off site, all materials resulting from demolition not being salvaged. PART 3 - EXECUTION 3.01 3.02 CONTINUITY OF SERVICE A. Obtain permission from the Architec and Owner’s Representative prior to interruption of existing electrical systems. Reconnect existing circuit loads were necessary. B. Where live circuits are encountered during demolition, relocate and/or extend the circuits as required to accommodate the construction. C. Protect, brace and support existing active electrical circuits or equipment as required. D. Circuits damaged during work of this contract shall be repaired. Data cables shall be replaced from termination jack to patch panel. E. Schedule work to avoid interruptions to the occupied facilities. The Owner may require work to be performed on nights, weekends, or holidays. Include overtime work as necessary. DEMOLITION A. Condition and Premises: The Owner assumes no responsibility for condition of areas to be demolished. General conditions existing at time of inspection for bidding purposes will be maintained by Owner. B. Not all conduit, devices or equipment are shown on drawings. Other demolition may be required. C. Partial Removal: Items of salvageable value to Contractor indicated to be removed, may be removed from structure as work progresses. Salvaged items must be transported from site as they are removed. Storage or sale of removed items on site will not be permitted. D. Protections: Ensure safe passage of persons around area of demolition. Conduct operations to prevent injury to adjacent buildings, structures, other facilities, and persons. E. Damages: Promptly repair damages caused to adjacent facilities by demolition operations at no cost to Owner. F. Existing Utility Services: Maintain existing utilities indicated to remain, keep in service and protect against damage during demolition operations. Lewiston Library Second Floor Remodel Project 16020-2 15025 G. Cut and/or patch and repair all existing floor, wall and roof penetrations not being re-used. Comply with Division 1 Section requirements. H. All roof penetrations that are re-used shall be inspected and made air and water tight. I. Cut and remove buried raceway and conductors, indicated to be abandoned in place, 2 inches below the surface of adjacent construction. Cap raceways and patch surface to match existing finish. J. Remove, store, clean, reinstall, reconnect and make operational components indicated for relocation. END OF SECTION 16020 Lewiston Library Second Floor Remodel Project 16020-3 15025 SECTION 16110 – RACEWAY SYSTEM PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. All line voltage and low voltage wires and cables shall be enclosed in a raceway unless specifically noted otherwise. B. All raceways shall be concealed in finished spaces unless noted otherwise. C. Separate raceway systems shall be provided for each of the various wiring systems. D. Raceways for telecommunication cabling shall comply with ANSI/TIA/EIA Standards 568 and 569. E. All conduit and electrical power required for special systems shall be furnished and installed by the Electrical Contractor as part of the overall Division 16 work. F. Provide a complete raceway system for all mechanical system low voltage controls. Coordinate with mechanical contractor. Review all related specifications and drawings for extent of work. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16120, 16134, and 16190. SUBMITTALS A. Complete manufacturer's data, including catalog cuts. B. Submit parts replacement/ordering information as part of O & M Manuals. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 PROHIBITED MATERIALS A. “Pot-metal” or cast fittings, couplings, or connectors. B. Aluminum raceways, fittings, couplings, and connectors. C. Electrical Non-Metallic Tubing (ENT). Also known by trade name “smurf tubing”. Lewiston Library Second Floor Remodel Project 16110-1 15025 2.02 2.03 MATERIALS A. Rigid Steel Conduit: Standard iron pipe size with screwed joints for electrical raceway use, in conformance with ANSI C80.1 “Rigid and Steel Conduit.” Raceway shall be zinc coated by hot dip galvanizing or sherardizing. Manufacturer shall be Allied Tube and Conduit or Triangle PWC. B. Electrical Metallic Tubing: Zinc-coated steel in conformance with ANSI C80.3 “Electrical Metallic Tubing,” manufactured by Allied Tube and Conduit, or Triangle PWC. C. Rigid Non-Metallic Conduit: Polyvinyl chloride, Schedule 40, heavy-wall, U.L. labeled, in conformance with U.L. Article 651 and NEMA TC-2 as manufactured by Carlon Electrical Products or P.W. Pipe. D. Rigid Non-Metallic Conduit, Type “EB”: Polyvinyl chloride, designed for encased burial, in conformance with U.L. 651A, U.L. 657A, and NEMA TC-6, as manufactured by Carlon Electrical Products or P.W. Pipe. E. Flexible Conduit: Galvanized steel in conformance with UL-1 “Flexible Metal Conduit”, manufactured by International, American Brass, or All-Flex. F. Flexible Conduit, Liquidtight: Galvanized steel in conformance with UL-360 “Liquid-Tight Flexible Steel Conduit”, manufactured by American Brass Co. “Sealtite” or “Flex-Seal” with copper bonding tape and with weatherproof exterior jacket. G. Surface Metal Raceway: Galvanized steel with snap-on covers, finished with manufacturer’s standard prime coating suitable for painting, in conformance with UL-5 “Surface Metal Raceways and Fittings”, manufactured by Legrand Wiremold of size required for wiring, furnished with all associated hardware. System shall be equal to Legrand Wiremold 700 series (single channel) or 4000 series (dual channel). H. Fittings, Couplings and Connectors: Utilize fittings listed and approved for specific conduit or raceway system used. All fittings, couplings, and connectors shall be steel or malleable iron and shall have insulated bushings molded or locked into the metallic body of the fitting for protection of conductors. Fittings for galvanized rigid steel raceways shall be the threaded type. Fittings for EMT shall be compression type. Fittings for flexible conduit shall be of the wedge and screw or the squeeze and clamp type. Fittings for liquid tight flexible conduit shall have a threaded grounding cone, and a compression ring with gland for tightening. Fittings shall be manufactured by Appleton, Thomas & Betts, OZ/Gedney or same manufacturer as conduit. ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above. B. Substitutions may be considered only when submitted in conformance with Section 16010. Lewiston Library Second Floor Remodel Project 16110-2 15025 PART 3 - EXECUTION 3.01 3.02 3.03 PROHIBITED LOCATIONS AND INSTALLATION METHODS A. Electrical metallic tubing shall not be installed underground, in concrete, or exterior (nongalvanized). B. No raceway shall be secured to the ceiling system, ceiling hangers, HVAC ductwork, or mechanical piping. C. Rigid non-metallic conduit (PVC) shall not be used inside a building unless encased in concrete. REQUIRED LOCATIONS A. Rigid steel conduit shall be used for all exposed exterior raceways, for transition of nonmetallic raceways before rising above floor slabs or grade and in locations specifically noted or required by code. B. Rigid non-metallic conduit shall be used for all conduits installed underground (with rigid steel elbows), in concrete slabs and in locations where specifically noted. C. Flexible conduit shall be used only for connections to recessed lighting fixtures, motors and equipment, and shall be limited to dry locations. Maximum length shall be six (6) feet. D. Liquidtight flexible conduit shall be used in place of flexible conduit in damp or wet locations, including all connections to pumps. E. Surface metal raceways shall be used only in finished areas where surface raceways are required by building conditions or as specifically noted. F. Electrical metallic tubing shall be used in all locations not noted above. INSTALLATION A. Underground raceways (other than single conduits) shall be arranged as shown in NEC Figure B.310-2. Maximum depth to the top of all buried raceways shall be 30 inches. B. Maximum size raceway to be installed in concrete floor slabs shall not be larger in outside diameter than 1/3 the overall thickness of the slab. Raceways shall be installed in middle third of the slab thickness and leave at least 1 inch concrete cover. Raceways shall be secured to reinforcing to prevent sagging or shifting during concrete placement. Raceways shall be spaced no closer than three diameters laterally to prevent voids in the concrete. Curved portions of bends shall not be visible above the finished slab. C. Non-metallic raceways run in concrete slabs shall make a transition to rigid steel conduit before rising above the slab. D. Stub-ups in floor slabs shall be made with an adjustable top or coupling threaded inside for plugs, set flush with the finished floor. For connections to equipment, extend raceway from fitting with rigid steel conduit; flexible metal conduit may be used 6 inches above the floor. Lewiston Library Second Floor Remodel Project 16110-3 15025 E. Maintain 6 inch separation from steam and hot water lines. F. All raceways shall be installed parallel with or at right angles to the building lines, and not installed diagonally. G. The locations of all raceways shall be coordinated with all other trades. If a conflict occurs due to lack of this coordination, then changes in the location of the raceways shall be made without extra charge. H. For conduits one inch and larger, hickey bends are not acceptable. Either manufactured elbows or bends fabricated in a bending machine must be used. I. Where a conduit enters a box or other fitting through a knockout, an approved double locknut and insulating bushing must be provided. All conduits shall be equipped with insulating bushings at all outlets, pull boxes, panels, etc. J. Flexible conduit connections to motors shall include (1) 90 degree bend. K. All conduits shall be cleaned by pulling a swab through the conduit before pulling in wires. L. Branch raceway runs are shown schematically. Except where exact routing is indicated, branch circuit raceways may be grouped, and the actual routing of branch circuit raceways may be altered, providing actual locations are properly entered on the “As-Built” drawings. M. Conduit connections between outlet boxes less than 24 inches apart on opposite sides of a wall shall be made with a loop of flexible conduit (no nipples). N. Provide expansion fittings for all rigidly fastened conduits spanning expansion joints, and for all runs 1-1/2 inch or larger exceeding 150 feet in length. Fittings shall be hot-dipped galvanized malleable iron with a packing ring to exclude water, a pressure ring, and a separate external bonding jumper. O. Seal around all conduits at ceiling, floor, and wall penetrations with an approved fire stop material to provide airtight fireproof seal. P. Provide roof jack at all roof penetrations. Coordinate roof jack type and installation with General Contractor. Equipment must be compatible with required roof guarantee. Q. Install raceway sealing fittings per the manufacturer’s recommendations. Sealing fittings shall be located in approved, accessible locations and filled with U.L. listed sealing compound. For concealed raceways, install fittings in a flush steel box with a blank cover. Sealing fittings shall be installed where raceways enter/leave a hazardous area, a refrigerated area and as otherwise required by the code. R. Where conduit runs are 100 feet or longer contain the equivalent of four (4) 90E bends, pull/junction boxes shall be provided. Pull box locations shall be indicated on the record drawings. Lewiston Library Second Floor Remodel Project 16110-4 15025 S. Minimum size conduit shall be 3/4 inch, except where a single circuit of two #12 or two #14 AWG wires are installed, which requires 1/2 inch conduit minimum. Minimum size conduit to be 3/4 inch below grade. Conduit sizes shown on the drawings shall supersede these requirements. T. All unused raceways shall be provided with a nylon pull string. Raceways larger than 1-1/2 inch shall be provided with a 1/4 inch poly pull line. U. PVC conduit sections shall be installed using primer and glue. END OF SECTION 16110 Lewiston Library Second Floor Remodel Project 16110-5 15025 SECTION 16120 - WIRE AND CABLE PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. A complete system of wires shall be installed in the raceway system. B. No attempt has been made to indicate individual branch circuits and associated homerun lengths. It shall be the responsibility of the contractor to review each building for scope of work. C. All branch circuit wiring shall be copper unless specifically noted otherwise. D. Feeder sizing/quantity indicated on the plans are based upon NEC Article 310, Table 310.16 75C copper (cu) for greater than 100 amp and 60C copper (cu) for less than 100 amps. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16110, and 16700 thru 16790. SUBMITTALS A. Complete manufacturer's data, including catalog cuts. B. Submit parts replacement/ordering information as part of O & M Manuals. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. All wiring shall be copper unless specifically noted otherwise, and shall be rated at 600 volts. B. Wire sizes #12AWG and #10AWG shall be solid, type THHN/THWN. C. Wire sizes #8AWG and larger shall be stranded, type THHN/THWN. Sizes #4AWG and larger may be type XHHW. D. Minimum wire size shall be #12AWG unless noted otherwise. 1. E. Exceptions: a. See Sections 16700 thru 16790 for low voltage wire and cable requirements. All wire shall be marked with gauge and insulation type on 24" centers, and color coded as required by the N.E.C. Lewiston Library Second Floor Remodel Project 16120-1 15025 2.02 F. All wire and cable shall be brought to the job in the original containers bearing the U.L. label. G. Molded connectors with metal thread-on core shall be used for splicing #12AWG and #10AWG wire. Stranded cables shall be connected to lugs using mechanical connectors, and shall be wrapped with electrical tape to a thickness equal to the wire insulation. H. Support vertical conductors in raceways with a screw body and wedging type plug segments made to support cables and relieve strain without damaging conductor insulation. I. Wire pulling lubricants shall be non-toxic, polymer based and compatible with conductor insulation. The dielectric strength of the conductor insulation shall not be reduced. ACCEPTABLE MANUFACTURERS A. Wire and cable shall be as manufactured by Rome, Southwire, General Cable, American Insulated Wire, Superior/Essex or Cerrowire. B. Molded connectors shall be as manufactured by 3M or Buchanan. C. Mechanical connectors shall be manufactured by Burndy, O.Z./Gedney Co., or Thomas & Betts. D. Cable supports shall be manufactured by O.Z./Gedney. E. Wire lubricant shall be manufactured by Thomas & Betts or Ideal. F. Tape shall be manufactured by 3M. G. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Wires shall be pulled in such a manner as to avoid kinking or abrasion to the insulation. Use only approved lubricants which do not deteriorate conductors or insulation. Oil or grease shall not be used to lubricate wires. B. Make sure that all conduit fittings have insulated bushings in place before pulling wires. If it is found that the insulating bushings are not in place before pulling wire, the wire will be removed and replaced with new at the contractor’s expense. C. Where more than three current carrying conductors are installed in a single raceway, the minimum wire size shall be increased to comply with NEC Table 310-16, Note 8. D. Where the distance from the overcurrent device to the first outlet exceeds 100 feet, the minimum wire size shall be #10AWG. E. All receptacle circuits associated with computer outlets shall have separate neutrals. No shared neutrals will be allowed. Neutral conductor shall be considered as "current-carrying" for the purpose of applying NEC Table 310-16, Note 8, above. Lewiston Library Second Floor Remodel Project 16120-2 15025 F. Wiring shall be arranged as shown on the drawings. Combining of homeruns will be allowed up to three circuits. G. Provide separate equipment ground conductor full length of all raceways. This conductor is not shown on the drawings and is in addition to the conductors shown. H. Conductor insulation shall be color coded as follows: CONDUCTOR Phase A Phase B Phase C Neutral Ground 208Y/120 VAC Black Red Blue White * Green 480Y/277 VAC Brown Orange Yellow Grey * Green * Neutral shall have colored stripe where so specified I. Except where conductor sizes are indicated on the drawings, the following schedule, listing minimum conductor size, shall be adhered to: CIRCUIT OVERCURRENT DEVICE RATING CONDUCTOR SIZE 20 amperes or less #12AWG 30 amperes #10AWG 40 amperes #8AWG 50 amperes #6AWG 60 amperes #4AWG 70 amperes #4AWG 80 amperes #3AWG 90 amperes #2AWG 100 amperes #1AWG J. 3.02 For paralleled conductors, lengths of the conductors shall be identical and one conductor for each phase and neutral shall be run in each conduit. TESTING A. Inspect wire and cable for physical damage and proper connection. B. Torque test conductor connections and terminations to manufacturer’s recommended values. C. Perform continuity test on all power conductors. Verify proper phasing connections. END OF SECTION 16120 Lewiston Library Second Floor Remodel Project 16120-3 15025 SECTION 16130 - EQUIPMENT ENCLOSURES PART 1 - GENERAL 1.01 PROVISIONS A. This section of the specification applies to the enclosures for enclosed equipment other than grouped equipment, i.e. motor control centers, switchboards, panelboards, etc. B. Provide weather-tight NEMA-rated enclosures for equipment mounted outdoors or exposed to moisture. C. Items covered includes: 1. 2. 3. 4. 5. 6. 1.02 Switches (fusible and non-fusible; motor starting). Starters (magnetic, manual, combination). Circuit breakers. Pilot devices including push-button stations. Contactors. Control enclosures. SUBMITTALS A. List manufacturer and certify compliance with industry standards. PART 2 - PRODUCTS 2.01 MATERIALS A. Enclosures used indoors in nondesignated areas shall be NEMA 1 unless otherwise noted. B. Enclosures used outdoors in nondesignated areas shall be NEMA 3R. PART 3 - EXECUTION 3.01 INSTALLATION A. Coordinate location of enclosures with other trades. B. Install disconnect switch and similar device enclosures where accessible per code. C. Enclosures for individual units shall be mounted at 4'- 6" above floors to centerline of switch, controls, etc. D. Utilize mounting hardware designed for intended use. E. Provide supports and brackets required to attach the enclosure. F. Enclosures shall be installed parallel and perpendicular to architectural and structural elements. END OF SECTION 16130 Lewiston Library Second Floor Remodel Project 16130-1 15025 SECTION 16131 – PULL AND JUNCTION BOXES PART 1 - GENERAL 1.01 PROVISIONS A. 1.02 Furnish and install pull and junction boxes in all locations shown or required for proper installation of the raceway and wiring systems. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16110, and 16199. PART 2 - PRODUCTS 2.01 MATERIALS A. Provide galvanized sheet steel junction and pull boxes, with screw-on covers, of the type, shape, and size to suit each respective location and installation. 1. 2.02 Type for various locations: a. 100 cubic inches or smaller: Standard outlet box with stamped knockouts. b. 150 cubic inches or larger: Code gauge steel with slides formed and welded, with screw covers unless shown to have hinged doors. Hinged doors shall have locking device same as furnished for panelboards. Knockouts shall be factory stamped, or formed in the field with a cutting tool to provide a clean, symmetrically cut hole. c. Exterior or wet areas: Weatherproofed galvanized steel construction with proper gaskets and corrosion resistant fasteners. d. Ordinary Cast Metal Boxes: Provide cast aluminum or malleable iron with minimum wall thickness of 1/8”. Boxes shall have integral threaded raceway hubs and mounting flanges. Boxes shall be corrosion resistant on the inside and outside and contain gasketed covers held in place with a minimum of four corrosion-resistant screws. APPROVED MANUFACTURERS A. Pull and junction boxes shall be as manufactured by the following: 1. 2. 3. 4. 5. 6. B. Appleton Electric Co. Arrow-Hart, Inc. Keystone Columbia, Inc. O.Z./Gedney Co. T&B Panelboard/Switch board manufacturer as described in Section 16410. Cast Metal Boxes: 1. Appleton, Crouse Hinds, OZ/Gedney Lewiston Library Second Floor Remodel Project 16131-1 15025 C. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 PROHIBITED INSTALLATION METHODS A. 3.02 No box shall be secured to the ceiling system, HVAC ductwork, or mechanical piping. INSTALLATION A. Install electric boxes as indicated, and in compliance with N.E.C. requirements, in accordance with manufacturer’s recommendations and with recognized industry practices to ensure that the boxes serve the intended purpose. B. Provide pull and junction boxes wherever necessary for proper installation of the various electrical systems. C. Provide knockout closures to cap all unused holes where blanks have been removed. D. Coordinate and locate boxes to ensure accessibility of electrical wiring. E. Secure boxes rigidly to the building element on which they are mounted, or solidly embed boxes in concrete or masonry. F. Identify all boxes with label showing the individual feeder or electrical system. See Section 16199. G. Boxes shall have appropriate NEMA rating for the location. H. Ordinary cast metal boxes shall be used in exposed locations in mechanical, electrical and telecommunication rooms. END OF SECTION 16131 Lewiston Library Second Floor Remodel Project 16131-2 15025 SECTION 16132 – FLOOR BOXES PART 1 - GENERAL 1.01 1.02 PROVISIONS A. Furnish and install floor boxes in the locations shown on the drawings. B. Provide floor box system designed for the floor type and device configuration. Review all contract documents for floor type and installation requirements. C. Provide power and telecommunications devices in each floor box as indicated. D. Provide power circuits for each receptacle installed in a floor box. E. Provide telecommunications cabling for each telecommunication jack installed in a floor box. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16140 and 16751. PART 2 - PRODUCTS 2.01 MATERIALS A. General: Floor boxes shall be sized to accommodate the indicated devices, regardless of whether such devices are provided under the Contract. Floor boxes shall be suitable for installation in the type of floor at the location where they are to be installed. Floor box covers shall be designed to accommodate the floor finish material where they are installed. B. Multi-service floor boxes designed for flush mounting, having separate compartments for power and communications. C. Boxes shall accommodate power receptacles and additional signal and communications systems devices as indicated on the Drawings. Include device brackets for duplex receptacles each other type device to accommodate the indicated communications devices. Include connectivity inserts for communication devices. D. Insets for telecommunications outlets shall match devices specified in Section 16751. E. Boxes shall include wiring barriers, device plates, mounting hardware, hinged lid, and cable access port. Boxes shall be fully adjustable before and after the concrete pour. F. Boxes installed in floors above grade shall be equivalent to Legrand Wiremold #RFB6. G. Floor box covers shall be equal to Legrand Wiremold FPBTCBS. Lewiston Library Second Floor Remodel Project 16132-1 15025 2.02 ACCEPTABLE MANUFACTURERS A. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Verify exact location of all floor boxes before roughing-in. B. Where flush floor boxes are shown adjacent to one another, mount boxes 3" apart. C. Install in accordance with manufacturer's recommendations. Flush floor boxes must be exactly flush with finished floor. D. Install power, AV, and communication devices in boxes as indicated on drawings. END OF SECTION 16132 Lewiston Library Second Floor Remodel Project 16132-2 15025 SECTION 16134 - OUTLET BOXES PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Each new switch, wall receptacle, light fixture, telecom work area outlet, A/V wall device, and other miscellaneous devices and equipment shall be provided with an outlet (junction or wiring) box. B. All outlet boxes shall be of the flush type unless specifically noted otherwise. C. Box dimensions shall be selected to meet wiring space requirements. Depth may be limited by building conditions. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16110, 16140, 16147, and 16751. SUBMITTALS A. Complete manufacturer's data, including catalog cuts on standard equipment, and shop drawings for all custom equipment. Submit parts replacement/ordering information as part of O & M Manuals. B. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 PROHIBITED MATERIALS A. 2.02 Sectional outlet boxes shall not be utilized. MATERIALS A. Flush outlet boxes shall be galvanized pressed steel, of the knockout type, not less than 4" square, minimum #14 gauge. B. Provide extension rings for all flush boxes. Boxes which occur in concrete block walls shall be equipped with 1-1/2" square cornered tile extensions. C. Outlet boxes installed in surface metallic raceway systems shall be shallow boxes manufactured as part of the system. D. Surface mounted outlet boxes shall be utilized only in conjunction with exposed conduits, and shall be of the cast metal type with internal hubs and mounting flanges. Lewiston Library Second Floor Remodel Project 16134-1 15025 E. 2.03 Boxes for exterior below grade installation shall be watertight, rated for exterior use, with gasketed covers and watertight connections. Boxes shall be cast steel, fully coated with corrosive protective compound. Boxes in paved areas shall be traffic rated. ACCEPTABLE MANUFACTURERS A. Pressed steel boxes shall be manufactured by Bowers, Raco, or T&B (Steel City). B. Cast metal boxes shall be manufactured by Bell. C. Surface boxes which are part of surface metallic raceway systems shall be manufactured by the same manufacturer as the surface metallic raceway. D. Cast exterior boxes shall be manufactured by OZ. E. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. All outlet boxes shall be flush unless specifically noted otherwise. B. This Contractor shall carefully lay out all outlets and check with the plumbing, heating, ventilating, and other contractors so that the outlets are not blocked, hidden, or rendered inaccessible due to equipment or piping of these trades passing over, under, across, or in close proximity to same, or to cause the devices or fixtures in or on these outlets to be inaccessible for use or maintenance. C. Any minor changes in the location of outlets from those shown on the plans shall be made without extra charge if so directed by the Architect before installation. D. Where two or more of the same type devices occur adjacent to each other, they shall be in a gang type box with a gang type cover. Where different type devices occur adjacent to each other, space outlet boxes so that finish plates will be spaced one inch apart (verify with Architect). E. Contractor shall consult the Architectural drawings for exact height of all outlets not specified herein or shown on the drawings. F. Flush ceiling and wall outlet boxes shall have a 3/8" fixture stud where fixture depends on such for support. G. Each ceiling outlet occurring in a suspended ceiling shall be supported from a bar hanger rigidly attached to ceiling support channels. H. Outlet boxes shall be supported independent from the raceway system. I. All switch outlets shall be located where shown, on strike side of door, and shall be 6" from the door casing, unless it is necessary to center switch between door and other construction for appearance. Lewiston Library Second Floor Remodel Project 16134-2 15025 3.02 J. Where two or more outlets occur on the same wall, unless individually noted otherwise, they shall be mounted at exactly the same height. K. Where outlets are shown side by side but at different heights, they shall be centered one above the other unless otherwise indicated. L. Outlets which are shown immediately opposite one another on two sides of a wall shall have boxes sized to prevent contact between the two. Nipples between boxes are prohibited. M. Outlets shown immediately opposite one another on two sides of a fire rated wall shall have 24" minimum horizontal separation. N. No outlet or group of outlets in a single stud space of a fire rated wall shall have a total opening area larger than 16 square inches. O. All unused openings in outlet boxes must be left sealed or closed with plugs. P. Grout around all outlet boxes to seal space between box and wall or ceiling materials. MOUNTING HEIGHTS A. Outlet boxes shall be mounted at heights as shown on the drawings. Dimensions are measured to the top of the box unless a "B" follows the dimension. In this case, the dimension is to the bottom of the box. 1. Exception: In spaces where existing outlets are installed, new outlets shall be mounted at the same height as existing similar outlets. END OF SECTION 16134 Lewiston Library Second Floor Remodel Project 16134-3 15025 SECTION 16140 - WIRING DEVICES PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Provide wiring devices at all device outlet locations shown on the drawings. B. Replace existing devices with new as indicated on the drawings. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16132, 16134, 16147, and 16199. C. For occupancy sensor switches and low voltage switches part of the lighting control system see Specification Section 16561. SUBMITTALS A. Complete manufacturer's data, including catalog cuts. B. Submit parts replacement/ordering information as part of O & M Manuals. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. Single Pole Switches WALL SWITCHES Hubbell #1221-GY Three-Way Switches Hubbell #1223-GY Four-Way Switches Hubbell #1224-GY Single Pole Switch with Red Pilot Lamp Weatherproof Switch Hubbell 1221-PL (120 volt) Hubbell 1221-PL7 (277 volt) Hubbell #1781-GY Momentary Contact Switch Hubbell #1557-GY Lewiston Library Second Floor Remodel Project 16140-1 15025 B. Single Pole Switches WALL SWITCHES Leviton #1221-GY Three-Way Switches Leviton #1223-GY Four-Way Switches Leviton #1224-GY Single Pole Switch with Red Pilot Lamp Momentary Contact Switch Leviton #1221-PLR (120 volt) Leviton #1221-7PLR (277 volt) Leviton #1256-GY C. Duplex Receptacles WALL RECEPTACLES Hubbell #CR5362GY Safety Receptacles Hubbell #HBL8200SG-GY Clock Receptacles Hubbell #5235 Dryer Receptacle Range Receptacle Hubbell 9350 Hubbell #7962 GFI Receptacle Hubbell #GF5352-GY WeatherProof Receptacles Hubbell #GF5352-GY w/#WP-26 plate D. Duplex Receptacles WALL RECEPTACLES Leviton #5362-GY Safety Receptacles Leviton #5262-SG-GY Clock Receptacles Leviton #5361-CH Dryer Receptacle Range Receptacle Leviton #5207 Leviton #5206 GFI Receptacle Leviton #6599-GY WeatherProof Receptacles Leviton #6599-GY w/#G196-V plate E. Devices shall be gray. F. High-capacity toggle operated switches shall be suitable for controlling motors rated up to 2 hp. 1. 2. 3. 4. G. Double-pole 30 amp switch P&S #7802 Three-pole 30 amp switch P&S #7803 Double-pole 40 amp switch P&S #7842 Three-pole 40 amp switch P&S #7843 Additional devices shall be as noted on the drawings. Lewiston Library Second Floor Remodel Project 16140-2 15025 2.02 ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above. B. A&H, Hubbell, P&S and Leviton devices which are the approved equal of those specified above are considered acceptable. C. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Mount devices securely to outlet boxes. B. Provide ground straps between each wiring device and its associated outlet box. 1. Exception: Ground strap not required with self-grounding devices. C. Orient receptacles so that ground pin is at top. D. Mount weatherproof receptacles vertically, up 18" from finished grade. E. All Toilet Rooms, Kitchen and Food Preparation locations shall have GFI type receptacles. F. All receptacles within 6 feet of a sink shall be GFI type receptacles. G. All interior damp or wet location outlets shall be weather resistant type GFI receptacles. H. All exterior damp or wet location outlets shall be weather-resistant type GFI receptacles. I. Provide device labeling per Specification Section 16199. J. All existing outlets noted on the drawings as being existing and reused shall have devices replaced with new. END OF SECTION 16140 Lewiston Library Second Floor Remodel Project 16140-3 15025 SECTION 16147 - DEVICE PLATES PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Provide each newly installed wiring device with a new wall plate or plate to match existing building standard. B. Outlet devices being replaced with new shall have new plate installed. C. Plate shall be size and type to match device. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16134, 16140, and 16199. SUBMITTALS A. Complete manufacturer's data, including catalog cuts on standard equipment, and shop drawings for all custom equipment. B. Submit parts replacement/ordering information as part of O & M Manuals. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 PROHIBITED MATERIALS A. 2.02 Sectional plates shall not be utilized. MATERIALS A. All devices in public areas shall be equipped with stainless steel plates of type to match device. Devices in Staff areas shall be grey nylon. B. Standard Stainless Steel Faceplates: Type 430 stainless steel with satin finish equivalent to P&S Sierra “SL” series. Type 302 Stainless Steel Faceplates: Type 302 stainless steel with satin finish, equivalent to P&S Sierra “SS” series. C. Nylon plates shall be Leviton Decora style. D. All junction boxes in finished areas shall be provided with plates. E. All outlets for communications devices (television, telephone) shall be provided by the communications contractor with plates to match device. Lewiston Library Second Floor Remodel Project 16147-1 15025 F. 2.03 Plates on exposed pressed steel boxes shall be pressed steel of the same manufacture as the box unless noted otherwise. ACCEPTABLE MANUFACTURERS A. Plates shall be Ortronics plates to match existing building standard for communication outlets. B. Plates shall be Leviton 302 stainless for outlets. C. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Install plate on each device outlet, communications outlets, and junction box. B. All existing outlets noted on the drawings as being reused shall have device plates replaced with new. C. Device plates shall be fitted tight to wall. D. All receptacles other than 15 or 20 amperes, 120 volt, shall be engraved with designation of amperage, voltage, and phase, in 3/16" high letters. See Section 16199. E. All devices shall be identified as to circuit number. See Section 16199. END OF SECTION 16147 Lewiston Library Second Floor Remodel Project 16147-2 15025 SECTION 16150 - MOTOR CONNECTIONS PART 1 - GENERAL 1.01 1.02 PROVISIONS A. Furnish and install all power wiring for all permanently installed motors, starters, equipment and control systems. All circuit protection, disconnect switches, and motor starters shall be furnished by Division 16 – Electrical, except for specifically noted starters, integral to equipment specified in other Sections. Review al contract documents for requirements. B. Motor starters and disconnect switches locations are indicated on the drawings. It shall be understood that the symbol representing "motor connection" shall include disconnect switches at all motors and starters, and starters where required. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16170, and 16720. PART 2 - PRODUCTS 2.01 MATERIALS A. Provide all required relays, wiring, and miscellaneous equipment for Fire Alarm Fan Shutdown if required. Interconnecting controls shall be rated to match starter control voltage. B. Branch circuit protection and disconnect switches shall be provided under Division 16. See Section 16170. PART 3 - EXECUTION 3.01 INSTALLATION A. Make a single (unless otherwise noted) line voltage connection to each motor and equipment item, and "line and load" line voltage connections to motor starters. B. Check the rotational direction of all motors after final service connections have been made, and make all phase corrections required. C. Check all motors for proper lubrication and overload protection before placing in operation. END OF SECTION 16150 Lewiston Library Second Floor Remodel Project 16150-1 15025 SECTION 16160 - GROUNDING PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Provide grounding for the electrical system as required in Article 250 of the N.E.C., and as specified herein. B. Provide grounding and bonding of telecommunications cabling as required by the NEC and as called for in ANSI/TIA/EIA 569 and 607-B, and as specified herein. C. No attempt has been made to show or otherwise indicate grounding equipment on the drawings. It shall be understood that all newly installed devices, equipment, circuits; etc shall be properly grounded to ensure safety and code compliance. Review existing conditions to determine scope of work prior to bid. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16120, and 16420.. SUBMITTALS A. Complete manufacturer's data, including catalog cuts. B. Submit parts replacement/ordering information as part of O & M Manuals. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. Ground Clamps: Burndy Type NT. B. Compression Grounding: Burndy Hyground Irreversible Compression Grounding System, Thomas & Betts EZ Ground Compression Connectors, or approved equal. C. All grounding and bonding conductors shall be copper. D. Ground Bar: 12 inch long, 4 inch wide, ¼ inch thick, extruded copper bar with two insulated supports. 1. 2. Bar shall be drilled to accept standard 2-hole lugs. Bar shall have wire clamp connectors and be capable of connecting a minimum of #6 AWG solid conductors. Lewiston Library Second Floor Remodel Project 16160-1 15025 2.02 ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above. B. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. The following are specifically included as requiring grounding: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. B. All raceways. Branch circuit panelboards. Non-current carrying parts of fixed equipment. Grounding terminal of all receptacles. Motors. Above grade metallic raceways. Surge protection devices. Telecommunication main grounding bus bar. Communication equipment racks and enclosures. Cable shields Provide ground strap between each wiring device and its associated outlet box. 1. Exception: Straps may be omitted if self-grounding devices are utilized. C. Provide separate ground conductor full length of all raceways. Ground conductor is not shown on the drawings, and is in addition to conductors shown. D. Provide a ground bar in each telecommunications space. Provide (1) #2 AWG continuous, insulated ground conductor from each ground bar to the main electrical service ground bar. Provide (1) #6 AWG insulated ground conductor from ground bar to each telecommunications rack in the telecommunication spaces. E. Grounding of shields for shielded audio cables shall occur only at the central equipment inputs or outputs of the audio amplifier. Non-grounded ends shall be terminated with wedgeon collars. Care shall be taken to preserve the continuity of the shields at all connection points. END OF SECTION 16160 Lewiston Library Second Floor Remodel Project 16160-2 15025 SECTION 16170 - DISCONNECT SWITCHES PART 1 - GENERAL 1.01 PROVISIONS A. 1.02 1.03 Provide motor and/or circuit disconnect switches in all locations shown or specified and in all locations required by code. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16150, 16180, 16199, and 16470. SUBMITTALS A. Complete manufacturer's data, including catalog cuts. Submit parts replacement/ordering information as part of O & M Manuals. B. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. Each motor and equipment item shall be equipped with a two or three pole, fused, heavy-duty disconnect switch, sized to match the motor or equipment. 1. 2.02 Disconnect switches for 120 VAC, single phase motors rated ½ HP or less shall be enclosed, toggle-type manual motor starters with integral overload protection and a red neon pilot “run” light. Provide General Electric #CR101. B. Switches shall be externally operable, quick-make, quick-break, with neutral connecting block as required, and lockable operating handle. Mount in code gauge steel cabinet. C. See Section 16470 for fuse requirements. D. Provide Class R rejection kits on fuseholders. ACCEPTABLE MANUFACTURERS A. Disconnect switches shall be manufactured by Cutler-Hammer, General Electric, Siemens, or Square D. B. Substitutions may be considered only when submitted in conformance with Section 16010. Lewiston Library Second Floor Remodel Project 16170-1 15025 PART 3 - EXECUTION 3.01 INSTALLATION A. Install disconnect switch at the controller location and wire to disconnect both motor (or equipment) and controller. If the motor (or equipment) is not in sight from the controller location, provide a second disconnect switch at the motor (or equipment), whether shown on the drawings or not. B. Install disconnects where accessible and within reach of personnel, as required by code. END OF SECTION 16170 Lewiston Library Second Floor Remodel Project 16170-2 15025 SECTION 16180 - EQUIPMENT CONNECTIONS PART 1 - GENERAL 1.01 PROVISIONS A. 1.02 Make all required connections to equipment furnished by the Owner, or under Division 1 through 16. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16134, 16140, and 16170. PART 2 - EXECUTION 2.01 INSTALLATION A. Provide disconnect switch at all equipment unless cord/cap connected. B. Where equipment has a cord connection, install a new plug on cord if equipment plug does not match the receptacle provided. C. Coordinate all receptacles, plugs, wiring, and locations with the equipment provided PRIOR to rough-in. Make sure code-required clearances are provided. D. Provide connection from fire/smoke dampers to fire alarm system for shut-down of HVAC units. E. Locate receptacle for each electric water cooler so that cord and plug are concealed inside or behind cooler. F. Serve and Prep Equipment: 1. 2. Verify all rough-in and connection requirements from drawings provided by the equipment supplier. Make final connection to all equipment. Conceal conduit stub-ups for equipment connections in walls behind equipment. Install boxes flush in wall with flush cover plates. Keep exposed conduits, boxes, and flexible conduits to a minimum length and exposure in order to meet health department regulations. END OF SECTION 16180 Lewiston Library Second Floor Remodel Project 16180-1 15025 SECTION 16190 - SUPPORT DEVICES PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Support all raceways, devices, and equipment from the building structure as required by the N.E.C. and as described below. B. Support lighting fixtures as required by the IBC and as described below. C. Support cabling as described below. D. Support electrical equipment to walls or ceilings with concealed backing. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16110, and 16500. SUBMITTALS A. Complete manufacturer's data, including catalog cuts on standard equipment, and shop drawings for all custom equipment. Submit parts replacement/ordering information as part of O & M Manuals. B. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 PROHIBITED MATERIALS A. 2.02 Nails, wires, perforated tape, plumber's tape, duct tape, plastic zip ties, or glue are unacceptable for support or securing of conduits. MATERIALS A. One or two hole pipe straps shall be Kindorf C-144 series or equal. B. Lay-in pipe hangers shall be Kindorf C-149. C. Trapeze or wall surface supports shall be Kindorf "bolt-hole" base galvanized steel channels with C105 and C106 single bolt pipe straps. D. Galvanized steel channels and associated support rods shall be selected to accommodate weight of associated raceway and wire. Lewiston Library Second Floor Remodel Project 16190-1 15025 2.03 E. Lighting fixture supports shall be as recommended by the manufacturer. T-bar type fixtures shall be supported from standard T-bar accessories. Comply with ASTM C636. F. Cable supports: Provide galvanized steel “D” rings or galvanized steel “J” hooks with Velcro wraps to secure cables. Bridle rings are not acceptable. Minimum “J” hook width shall be 3/4”. Size hooks per quantity of communication cables. G. Provide surface mounted wall supports for steel strut channels and electrical attachment accessories. H. Provide adjustable, galvanized steel bar hangers equivalent to RACO #920 or #922. I. Provide adjustable, galvanized steel, box brackets equivalent to Erico “Caddy” #TSGB. J. Provide backing that matches material and is compatible with building components. ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above. B. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Individual conduits shall be secured with steel pipe straps or lay- in pipe hangers. B. Multiple rows of suspended conduit shall be supported from trapeze style hangers. C. Multiple runs of conduit on ceiling or wall surfaces shall be mounted on flush or surface steel channels. D. Ceiling support wires shall not be used for support of conduits. E. Support lighting fixtures as recommended by the manufacturer. See additional requirements in Section 16500. If installed in T-bar ceilings, support as required by N.E.C., and in addition, provide (2) #12 gage slack wire hangers from the fixture housing to the structure above. In addition, see IBC requirements. F. Outlet boxes in framed walls or ceilings shall be supported by horizontal box brackets attached to two studs. Outlet boxes in suspended ceilings shall be supported by bar hangars attached to two ceiling support channels. G. Communication and control cables shall be supported by “J” Hooks and “D” Rings. Supports shall insure that the cable will not kink, sag, or distort. Supports shall be spaced at less than 60 inches apart. Group cables by system in Velcro wraps. H. Connect freestanding equipment to the building structure. Anchor floor-mounted equipment to floor with appropriate fasteners. Lewiston Library Second Floor Remodel Project 16190-2 15025 I. Support suspended electrical equipment from the building structure and provide sway bracing. END OF SECTION 16190 Lewiston Library Second Floor Remodel Project 16190-3 15025 SECTION 16199 – ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 1.02 1.03 1.04 GENERAL A. All identification shall use the room numbers assigned by the Owner. Obtain a list of room numbers from the Owner’s Representative prior to preparing identification. B. Provide revised panelboard circuit directory cards if any panels have been modified or added to. C. Provide arc fault flash hazard labels on all disconnect switches and panels per NEC Section 110.16. PROVISIONS A. Install nameplates on all Main and Distribution Switchboards, starters, panelboards, telephone cabinets, disconnect switches, time clocks, and miscellaneous systems junction boxes and cabinets installed under this contract. B. Provide new nameplates as required for existing equipment. C. Install plates with engraved labels at all control switches noted on the drawings. D. Install printed labels on all device plates, showing circuit number. E. Install bakelite nameplates at each protective device in switchboard and distribution centers, showing circuit service. F. Install typed circuit directory cards in all panelboards, including existing. G. Install printed label on cover of all junction boxes, showing system identification and/or circuit number. H. All wiring in all outlet and junction boxes shall be properly identified as to cable source or circuit number. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16147, 16170, 16411, and 16420. SUBMITTALS A. Detailed shop drawings for all custom nameplates. B. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. Lewiston Library Second Floor Remodel Project 16199-1 15025 PART 2 - PRODUCTS 2.01 PROHIBITED MATERIALS A. 2.02 Dymo (or equivalent) labels shall not be utilized, unless specifically noted. MATERIALS A. Nameplates: 1. 2. 3. B. Nameplates shall be fabricated from black bakelite, with 1/4" or 3/8" engraved white letters. Wherever engraved plates are noted on the drawings, such labels shall be engraved directly into the metal or plastic plate, dead front, or other material. Engraved letters shall be 1/4" or 3/8" high, filled with black enamel, and read as directed. Schedules: 1. Provide typewritten directory for each panel, on heavy card stock, showing all circuit numbers. C. Printed labels shall be matte white polypropylene with adhesive back designed for exterior applications. Label text shall be ¾” high, black and shall be applied to the label by a thermal transfer printer. Printed labels shall be made using a Brady ID PAL printer. D. A warning sign complying with NEC Article 110.16 shall be provided for all panelboards, motor starters, disconnect switches, and lighting control panels. Arc flash signs shall be in accordance with ANSI Standard Z535.4 requirements. Signs shall state “Warning”, “Arc Flash Hazard”, and “Appropriate PPE Required.” PART 3 - EXECUTION 3.01 INSTALLATION A. Nameplates: 1. 2. 3. 4. 5. B. Panelboards: Mount inside door, on dead front, above circuit breakers, unless panelboard is located in an utility-type room, then install nameplate on outside of panelboard above door. Telephone and Miscellaneous Cabinets: Mount nameplate on outside of cabinet above door. Disconnect Switches, Relays, Contactors, Time Clocks: Mount nameplate on outside of cabinet, near top. Omit nameplates from disconnect switches if located adjacent to equipment. Control Switches: Install nameplate in location as directed near switch. Nameplate is required unless engraved labels are specified. Junction Boxes: Install nameplate on exterior of cover. Schedules: 1. Panelboards: Mount in frame under plastic cover, on back side of door. Schedule shall show circuit service for each circuit breaker, using "Owners" room numbers. Spares and spaces shall be written in pencil. Lewiston Library Second Floor Remodel Project 16199-2 15025 2. C. Existing Panelboards: Revise existing schedules to reflect current circuit configuration. Retype on new schedules, showing new and existing circuits. Device Plates: 1. 2. Provide line voltage branch circuit identification labels on all receptacle outlet device plates. Provide network identification labels on all telcom work area outlets. END OF SECTION 16199 Lewiston Library Second Floor Remodel Project 16199-3 15025 SECTION 16411 - EXISTING DISTRIBUTION PANELS, PANELBOARDS PART 1 - GENERAL 1.01 1.02 PROVISIONS A. Modify and connect to existing panelboards and distribution panel as shown on the drawings. B. Modify existing nameplates and circuit directory cards as described below. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16199, and 16490. PART 2 - PRODUCTS 2.01 MATERIALS A. Overcurrent devices shall match existing equipment as to manufacturer, type, and minimum short-circuit rating. PART 3 - EXECUTION 3.01 INSTALLATION A. Install new circuit protective devices in existing panelboards, and distribution panels in available space. Where necessary, relocate existing active devices to make adjacent spaces available. B. Schedules shown for existing panelboards/distribution panels represent the circuit breaker configuration required by the current project. Contractor shall make site investigation and determine the type, number, and arrangement of existing circuit breakers for each existing panelboard/distribution panel to insure inclusion of all required devices. C. Install blank covers over live bus in existing panelboards/distribution panels wherever such exposures are found. D. Reorganize existing panelboards/distribution panels and associated equipment to provide space for new equipment as shown on the drawings. E. Revise existing panel and distribution schedules as required to reflect current circuit configuration. Retype on new schedules showing both new and existing circuits. END OF SECTION 16411 Lewiston Library Second Floor Remodel Project 16411-1 15025 SECTION 16420 - PANELBOARDS PART 1 - GENERAL 1.01 PROVISIONS A. 1.02 1.03 Furnish and install all lighting and power panels shown on the drawings. Panels shall be mounted in steel cabinets arranged for flush or surface mounting as shown on the plans. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010 and 16199. SUBMITTALS A. Complete manufacturer's data, including catalog cuts on standard equipment, and shop drawings for all custom equipment. Submit parts replacement/ordering information as part of O & M Manuals. B. Include drawing showing height, width, and depth of each panel. C. Include schedule showing circuit breaker size and number of poles, keyed to circuit number. Schedule shall be arranged the same as the panel schedules included in the specifications. D. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. Cabinet and trim shall be of code gauge steel (minimum) with 4" (minimum) wiring gutter all around. All panelboards shall be equipped with a hinged, locking door. Two keys shall be furnished with each cabinet, and all locks on all cabinets shall be keyed alike. B. Where panels occur adjacent to one another, cabinets and doors for each panel shall be of the same height. C. All surface mounted panels, unless noted otherwise, shall extend from the floor to the top of the panel, with dividers, blank panels, and miscellaneous hardware as required. Entire cabinet (less front) shall be furnished as one piece, or if not of one piece construction, shall have factory fabricated metal skirts which are designed to provide positive alignment of top and bottom sections. Panelboards which have sections which are not perfectly aligned will not be accepted. D. All panelboards shall be painted with gray lacquer over rust preventative primer. Sides and top of surface mounted panels shall be painted to match fronts. Lewiston Library Second Floor Remodel Project 16420-1 15025 E. Panels shall be of the circuit breaker type, and shall have capacity and arrangement as shown on the panel schedule. F. Branch circuit breakers shall be bolt-on type and shall be of the ambient compensated, thermal magnetic type, which will provide inverse time delay overload, and instantaneous short circuit protection. All branch circuit breakers shall have a minimum interrupting rating of 10,000 amperes RMS symmetrical. Branch circuit breakers shall have one, two or three poles as designated on the panel schedule. No circuit breakers utilizing handle ties for two or three pole operation will be acceptable. 1. 2.02 Voltage and current ratings shall be as indicated on the drawings. G. Provide a typewritten directory for each panel, placed inside the panel door. The directory shall list all rooms served by each breaker, using the "Owner's" room numbers. Directories shall be installed in a metal directory frame and glass. Spares and spaces shall be written in pencil. H. All circuit breakers which serve time clocks and other miscellaneous control devices shall be equipped with mechanical handle locking devices. I. Where panels contain contactors, they shall be mounted behind a hinged, locking door. Contactor section shall be below the circuit breaker section unless otherwise noted. Provide all required barriers. J. All multi-section panels shall be equipped with a "bus rated" main circuit breaker in each section. K. Each panel shall be equipped with a ground lug for feeder ground. L. Each panel and cabinet and the units comprising same shall bear the manufacturer's nameplate and the U.L. label. ACCEPTABLE MANUFACTURERS A. Panelboards shall be Square D Type #NQOD. B. Other Acceptable Manufacturers: G.E., Cutler-Hammer, or Siemens equipment which is the approved equal of the above is considered acceptable. PART 3 - EXECUTION 3.01 INSTALLATION A. Mount panels in locations shown, making sure that code-required clearances exist. B. All panels shall be mounted with top at the same height; approximately 6'-6". C. Where cabinets cannot be set fully flush due to shallowness of all of partition, trim protruding sides with approved metal or hardwood molding, fastened to cabinet so as to conceal intersection of wall and cabinet. Lewiston Library Second Floor Remodel Project 16420-2 15025 D. If paint is damaged during shipping or installation, damaged portion shall be sanded smooth and entire panel repainted. E. Provide (5) 3/4" conduits stubbed into accessible ceiling spaces above and below each flush mounted panel. F. Utilize hydraulic actuated dies to compress the cable connecting lugs. Dies shall compress the full circumference of the cable. END OF SECTION 16420 Lewiston Library Second Floor Remodel Project 16420-3 15025 SECTION 16470 - FUSES PART 1 - GENERAL 1.01 PROVISIONS A. 1.02 1.03 Furnish and install fuses in all fusible equipment, and provide spare fuses as described herein. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16170, and 16500. C. The supplier shall submit a list of fuse manufacturers and types to be used on this project for review. SUBMITTALS A. Complete manufacturer's data, including catalog cuts, time-current curves, and coordination data as required below. Submit parts replacement/ordering information as part of O & M Manuals. B. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. Fuses shall be high interrupting, current-limiting, U.L. approved, and shall be Bussman types listed below: MAIN SWITCHES 250 V 600V 600V CLASS J 0-600A ABOVE 600A FEEDERS LPNRK KRPC LPSRK KRPC LPJ KRPC 0-600A ABOVE 600A GENERAL PURPOSE TRANSFORMERS (LINE SIDE) LPNRK KRPC FRNR LPNRK LPSRK KRPC FRSR LPSRK LPJ KRPC LPJ LPJ K-RATED TRANSFORMERS (LINE SIDE) MOTORS MOTORS (ABOVE 600A) FRNR FRSR LPNRK KRPC LPSRK KRPC LPJ KRPC FLUORESCENT BALLASTS HLR/GLR HLR/GLR HLR/GLR Lewiston Library Second Floor Remodel Project 16470-1 15025 B. 2.02 Class RK5 fuses shall be used for safety switches and combination starters. Class RK5 fuses shall be dual element time delay rejection-type fuse with interrupting capacity rating of 200,000 Amps. Fuses shall have 10 seconds time delay at 500% rate current. Fuses shall clearly indicate that the fuse has blown. RK5 fuses shall be Bussman FRS-R-SPI ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above. B. Fuses have been selected to assure system coordination and compatibility. Submit fuse curves and equivalency charts with all proposed substitutions. C. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Furnish and install fuses in all fusible equipment. Type shall be selected from the above schedule. Ampacity shall be as shown on the drawings, or selected to match equipment rating. B. Provide fuse clips and adaptors as required to match fuse type to fuseholder. C. Install fuses in fuseholder with fuse rating visible. D. Provide (3) spare fuses of each different type and size used on the project. END OF SECTION 16470 Lewiston Library Second Floor Remodel Project 16470-2 15025 SECTION 16490 - CIRCUIT BREAKERS PART 1 - GENERAL 1.01 PROVISIONS A. Provide molded-case, insulated case, or power circuit breaker mounted in grouped equipment. Grouped equipment includes panelboards, distribution panels, etc. B. Provide new power circuit breaker devices in existing Eaton Power R Line panels as required. C. Become familiar with the project conditions and existing equipment prior to bid. Verify brand, type, and AIC rating for each panel. No attempt has been made to show or otherwise indicate existing panel brands and breaker types on the drawings or in the specifications. Only the required amperes, poles, and voltage have been indicated on the drawings. D. The Contractor shall submit the following shop drawings and data for review by the Engineer: 1. 2. 3. 4. Ratings: Voltage, frame size, trip rating, trip settings, interrupting capacity at rated voltage. Dimensions, mounting details and enclosure types. Certification that the breakers conform to the standards required and that they are all listed for the applications on this job. Time-current curves. PART 2 - PRODUCTS 2.01 MATERIALS A. Inspect existing panels for brand, model, and other related information before ordering. B. Molded case breakers shall comply with NEMA Standard AB-1-1986. They shall be thermal magnetic trip free, non-interchangeable trip, non-adjustable trip unless otherwise noted. C. Circuit breakers shall be fully rated for interrupting rating. Series rated breakers are not acceptable. Refer to the power riser diagram and panelboard schedules for required interrupting capacity ratings (AIC) of circuit breaker devices. Where interrupting ratings are shown that do not comply with standard ratings of the manufacturer, the next highest rating shall be provided by the Contractor. D. Circuit breakers shall be ambient-compensated, thermal-magnetic, bolt-on molded-case type, which will provide inverse time delay overload and instantaneous short circuit protection. Branch circuit breakers shall have one, two or three poles as designate on the panelboard schedule. Multi-pole circuit breakers shall have integral trip mechanisms. Circuit breakers utilizing handle ties for two or three pole operation are not acceptable. Interrupting capacity shall match the rating of the panel. E. Circuit breakers serving air-conditioning and refrigeration equipment shall have an “HACR” label. Circuit breakers serving HID lighting shall have an “HID” label. Lewiston Library Second Floor Remodel Project 16490-1 15025 F. All circuits breakers, which serve time clocks and other miscellaneous control devices, and circuits which serve fire smoke dampers, shall be equipped with mechanical handle locking devices. G. Power circuit breakers shall comply with NEMA Standard SG-3-1981 and shall be as follows: 1. 2. 3. 4. Power circuit breakers shall use a "stored energy" mechanism in closing and tripping the breaker. This shall consist of steel springs which shall be fully charged by the operator prior to closing and which, when released, shall provide enough energy to close and latch the breaker under any service conditions within the specified rating of the breaker. When the breaker is tripped it shall be driven open by steel springs which shall be fully charged at all times after closing to permit instantaneous tripping upon closure if necessary. The breakers shall be trip free. Solid state type trips shall be used consisting of current transformers, a solid state unit to interpret the output of the current transformers, and a tripping solenoid acting directly to trip the breaker. The current transformers shall have taps which can be changed simply in the field to permit trip ratings to be changed in any of the manufacturer's standard settings. Trip units shall be capable of being calibrated and tested by a portable test set. The time delay and pickup characteristics shall also be variable in the field. The devices shall be designed such that performance at any setting is repeatable. A ground detection device shall be provided, it shall be an integral part of the trip device and provide field adjustable settings. Power circuit breakers used for motor starting shall have a position switch and auxiliary contacts. The manufacturer shall be capable of furnishing certified test reports for the test required in NEMA Standard SG-3-1981. PART 3 - EXECUTION 3.01 INSTALLATION A. Molded case breakers shall be firmly attached to bus and cable. Connections shall be rechecked after the first load cycle has been applied to the breaker. B. Individual units in enclosure shall be mounted at 4' - 6" above the floor on walls and 3' - 6" above floor, when strut supported at motors, etc. END OF SECTION 16490 Lewiston Library Second Floor Remodel Project 16490-2 15025 SECTION 16500 - LIGHTING PART 1 - GENERAL 1.01 1.02 1.03 PROVISIONS A. Provide lighting fixtures in all locations shown on the drawings. B. Bidders shall acquaint themselves with the conditions and requirements of the building construction, as this work is based on furnishing all materials required to entirely complete each fixtures ready for use. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16190, 16470, and 16561. SUBMITTALS A. Complete manufacturer's data, including catalog cuts on standard equipment, and shop drawings for all custom equipment. Submit parts replacement/ordering information as part of O & M Manuals. B. If lamps are included with the fixture, provide lamp submittal data. C. All submittals shall be made in accordance with requirements of Section 16010 and Division 1. PART 2 - PRODUCTS 2.01 MATERIALS A. See schedule for listing of required lighting fixtures. Fixtures shall be complete with trim, mounting hardware, and lamps. B. All fixtures shall bear the U.L. label associated with the type, location, and usage of the individual fixture. C. Fixtures manufactured with pre-painted metal will not be accepted. D. Each ballasted fixture shall be provided with ballasts of one of the following types. Each ballast shall be protected with a single element fuse, located within the ballast compartment. Ballast voltage rating shall be selected to match circuit voltage. 1. 2. 3. Fluorescent ballasts shall be program rapid start, true electronic (no hybrids) with the following performance requirements: Comply with Federal Efficiency Law #100-357 Comply with Electromagnetic Interference (EMI) and Radio Frequency Interference (RFI) limits set by the Federal Communications Commission (CFR 47, Part 18) Lewiston Library Second Floor Remodel Project 16500-1 15025 4. 5. 6. 7. 8. 9. 10. 11. E. LED Drivers 1. 2. 3. 4. 5. 6. 7. F. Provide transient protection that meets or exceeds IEEE 587 category A and shall provide high frequency ground fault protection, lightning protection, brownout protection and faulty lamp protection. Power factor shall be 95% or greater at full light output. Total harmonic distortion and third harmonic distortion shall be less than 10% Ballast factor shall be greater than 0.85 Lamp current crest factor shall be less than 1.5 Operate at not less than 20kHz frequency and have no audible noise, performing better than sound rating "A" Provide at a minimum, normal rated lamp life as state by the lamp manufacturer Have class P thermal protection and be U.L. listed Certified by Electrical Testing Laboratory (ETL) Minimum Efficiency of 85% Sound “A” rating. Minimum power factor of 90%. Temperature Range: -30 deg. C to 50 deg. C Conform to electromagnetic interference standard FCC Regulation Part 15, Subpart J. Lamp-driver combination shall not reduce normal rated life of lamps. All fixtures shall be complete with lamps of one of the following types: 1. 2. 3. Fluorescent (T8, 265 ma.): Osram/Sylvania Octron "800 XPS" series, 3500K. Fluorescent (Compact): Osram/Sylvania DULUX D/E series, 3500K. All other lamps shall be as required by equipment or as noted on the drawings. G. All plastic lenses shall be K-12 virgin acrylic unless noted otherwise. All flat plastic lenses shall be 0.125" minimum thickness. H. All door frames for fluorescent fixtures shall be equipped with spring-loaded latches. I. All louvered fixtures shall be shipped with dust covers and shall be removed after final building vacuuming has been completed. J. Fixtures mounted to T-bar ceilings shall utilize standard T-bar accessories as manufactured by the A&G Co. or equivalent. K. Spares: Provide spare equipment in the following quantities: 1. 2. 3. L. Fluorescent lamps: (1) cases of each different size and type. Other lamps: (1) cases of each different size and type. Lenses: 10% (or 25 lenses, whichever fewer) of each different type. LED and Fluorescent luminaires noted or indicated as emergency units shall be complete with an automatic battery pack assembly to operate one lamp. Assembly shall be Emergi-Lite, Bodine or approved alternate. Luminaire shall have valid UL label with battery-pack installed. Installation shall be done at the luminaire's manufacturer's factory. Battery pack assemblies shall provide a minimum of 1100 lumens of light output after 1-1/2 hours of operation. Unit may be field installed if installation does not void UL label of battery pack or luminaires. Lewiston Library Second Floor Remodel Project 16500-2 15025 2.02 ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers shall be as listed above and as listed in the fixture schedule on the drawings. B. Substitutions may be considered only when submitted in conformance with Section 16010. PART 3 - EXECUTION 3.01 INSTALLATION A. Mount fixtures securely and adequately to meet the requirements of NFPA 70, Para. 410.16 and UBC Standard 47-18. Mount in locations as indicated on the drawings as follows: B. Surface/Suspended 1. 2. 3. C. Mount stem suspended fixtures on swivel hangers which are a standard catalog item of the same manufacture as the fixture. Provide one more hanger than the number of fixtures in the row. Coordinate degree of swivel with the ceiling slope. Mount cable suspended fixtures with cable and hangers which are a standard catalog item of the same manufacture as the fixture. Cable hangers shall be adjustable for leveling the fixtures. Provide the number of hangers as recommended by the fixture manufacturer. Electrical feeds for cable suspended fixtures shall be with a coiled cord. Mount surface fixtures at two support points. Provide 1-1/2" metal spaces for fixtures which occur on combustible ceilings. Submit spacer for approval. Recessed 1. 2. 3. 4. Coordinate recessed fixture locations with the acoustical tile pattern, concealed ductwork, piping, etc. Check ceiling type (lay-in, gypboard, etc.) before ordering fixtures. Fixtures installed in T-bar ceilings shall be supported as required by N.E.C. All recessed fixtures (in accessible ceilings) shall be connected by means of a flexible conduit which is attached to a 4" square junction box. Box may serve more than one fixture. D. Verify all measurements. Contractor is responsible for fixtures fitting in place in a satisfactory and workman-like manner, to the approval of the Architect. E. Contractor shall verify fixture locations with the Architectural Reflected Ceiling Plans, where such plans are provided. END OF SECTION 16500 Lewiston Library Second Floor Remodel Project 16500-3 15025 SECTION 16561 - LIGHTING CONTROL SYSTEMS PART 1 - GENERAL 1.01 1.02 1.03 1.04 PROVISIONS A. This Section of the Specification applies to low voltage lighting controls for the project. B. Provide complete lighting controls for interior lighting as indicated on the plans and specified herein. Specifications shall take precedence over the plans if discrepancies arise. C. Adjust and test the lighting controls, and demonstrated operation to the Owner’s Representative and Commissioning Agent. D. Instruct the Owner’s staff in operating the controls and recommended maintenance procedures. RELATED REQUIREMENTS A. Drawings and the general provisions of the Contract, including General and Supplementary Conditions and Division 1 specification sections, apply to work in this section B. See Sections 16010, 16120, 16134, and 16131. GENERAL DESCRIPTION A. Interior vestibules, common spaces and corridors shall have time-based controls consisting of automatic relays and low voltage switches. Lighting installed under skylights or within daylight zones shall be provided with daylight harvesting and photocells. B. Interior office area lighting shall be occupancy based with dual technology occupancy sensors, power pack relays and slave relays. C. Classrooms shall be provided with daylight harvesting and individual room controls including dual technology occupancy sensors, photocells, and low voltage wall controls. D. Include low-voltage cabling and all other miscellaneous equipment and devices required for a complete and operable lighting control system. SYSTEM OPERATION A. Time-based controls for interior lighting shall provide automatic on/off control as indicated. 1. Control interior lighting by zone, with each zone incorporating a separate override switch. Lewiston Library Second Floor Remodel Project 16561-1 15025 2. 3. 4. B. Occupancy-based controls for interior lighting shall provide automatic shut-off control as indicated. 1. 2. 3. 4. 5. C. Time-based control zones shall include spaces in the building where no occupancy-based controls are provided, other than areas where lighting must remain in operation 24-hours per day, in mechanical and electrical equipment rooms. Each time-based control zone shall be equipped with means to manually override the automatic lighting controls, which shall enable the lighting in that zone to remain in operation for an adjustable time period set for no longer than 2 hours. The manual override switch shall be located within sight of the controlled lighting. Interior lighting in each time-based control zone shall be enabled during normal business hours by automatic controls which switch on and off automatically at preprogrammed times each day. The controls shall incorporated separate schedules for each day of the week, with automatic pre-programmed schedule changes for holidays and special events. Control interior lighting by room, with automatic controls functioning to turn off the general room lighting after a time delay when no occupant is present in the room. Occupancy sensors shall provide complete and proper volumetric coverage of each room. Occupancy-based controls, except wall switch occupancy sensors, shall include means for automatic self-adjustment. Sensors shall have adjustable sensitivity and time-delay settings, which shall be adjusted in each room to suit the actual room conditions. Dual-technology sensors shall also be equipped with selectable technology logic, initially set to require actuation of both technologies to activate the sensor and either technology to keep it activated. The occupancy sensors shall be aimed and adjusted such that the presence of one occupant anywhere in a room is sufficient to keep the control from automatically shutting off the lighting, without requiring excessive activity or special movement on the part of the occupant. Normal air movement while the room is unoccupied shall not in itself cause the occupancy sensors to remain activated. Wall switch occupancy sensors, shall include means for manual adjustment. Sensors shall have adjustable sensitivity and time-delay settings, which shall be adjusted in each room to suit the actual room conditions. The occupancy sensors shall be adjusted such that the presence of one occupant within sight of the sensor is sufficient to keep the controls from automatically shutting off the lighting, with sufficient time-delay to allow an occupant to conduct any normal functions that may be out of sight from the sensor. Normal air movement while the room is unoccupied shall not in itself cause the occupancy sensor to remain activated. Occupancy based controls, except wall switch occupancy sensors, shall include auxiliary contacts for interface with the energy management system for HVAC system control, in accordance with requirements of Division 15. Dimming daylight harvesting controls for interior lighting shall provide automatic dimming control as indicated. 1. Control interior lighting in daylight zones room by room, with automatic controls to dim the general room lighting in the daylight zone, after a time delay, whenever the ambient illumination in the daylight zone increases or decreases outside of the pre-set deadband beyond the setpoints for the current level. Lewiston Library Second Floor Remodel Project 16561-2 15025 2. 3. 4. 5. 6. D. 1.05 Automatic lighting controls which are programmed or which are time-based shall incorporate back-up capabilities for at least 10 hours upon interruption of power. SUBMITTALS A. Submittals Package: Submit the shop drawings, and the product data specified below at the same time as a package. 1. 2. 3. 1.06 Increase in ambient illumination in the daylight zone shall cause the lamps to dim proportionately, with the row closet to the window dimming more than the row or rows farther away. Decrease in the ambient illumination in the daylight zone shall cause the lamps to increase lumen output proportionately. The controls shall include an automatic shut-off feature, capable of automatically shutting off a channel when the daylight remains adequate to cause the channel to fully dim for a pre-set interval. The controls shall include facilities to disable this feature. The controls shall provide separate adjustable dimming rates and time delays for each lighting channel in each daylight zone. In each room that is equipped with dimming day-light harvesting controls, a manual override dimmer switch shall be provided. The manual override switch shall permit switching between automatic control and manual control of lighting in the daylight zone. When manual override dimmer switch is activated, the controls shall hold the lighting at the user-designated level until the controls are returned to automatic control. Dimming daylight harvesting controls shall be compatible with occupancy sensors which shall function as described above to shut off all lights in the room, including those in the daylight zone, when the room is unoccupied. Occupancy sensors shall shut off the lights in the room regardless of the ambient illumination. Shop Drawings: a. Composite wiring and/or schematic diagram of each control circuit as proposed to be installed (standard diagrams will not be accepted). b. Scale drawing for each area showing exact location of each sensor, room controller, and digital switch. c. Show coverage areas of each sensor. Product Data: Catalog sheets, specifications and installation instructions. Include data for each device which: a. Indicates where sensor is proposed to be installed. b. Prove that the sensor is suitable for the proposed application. B. Test Reports: Record of all field test data. Submit to the Commissioning Authority with a copy to the Architect. C. Training Documentation: session. Sign-off form and attendee sign-in sheet for the training WARRANTY A. Provide a five year complete manufacturer’s warranty on all products to be free of manufacturers’ defects. Lewiston Library Second Floor Remodel Project 16561-3 15025 PART 2 - PRODUCTS 2.01 LIGHTING CONTROLS A. Lightings Controls shall be compatible with the existing Lutron Energi Savr Node (ESN) System with H-series Ballasts and XPS soft switch system. The ESN(s) shall be provided with four (4) dimming circuits 0-10V with (4) relays to control the common area LED lighting. Where only on/off control is required the ESN node with softswitch will be used. Provide a complete and operable system with all necessary components. 1. 2. 3. 4. 5. 6. 7. 8. 9. B. These areas are to be dimmed separately at Office 202 with multiple digital switches: 1. 2. 3. 4. 5. C. 2. 3. F13 window pendant fixtures. After hours the Library likes to have these on to be seen from the street. Note that one F13 fixture is mounted in Conference Room 203A. This fixture needs to be controlled separately when the conference room is being used. This would allow it to be shut-off without shutting off the rest of the F13s. After hours this fixture would need to operate with the other F13 fixtures for a night time setting. F9 casework downlights. F5 fixtures including F3 and F7 fixtures in Casual 201. Conference Room 203A and 203B: 1. 2. E. Teens 206 Center Area 205 Teen Media 207 Tech Center 204 Casual Seating 20 Fixtures and Areas to be Individually Switched at Office 202. 1. D. Energi Savr Node: QSN-4T16-S Digital Switch: QSWS2-5BRLI-WH Wireless Sensor Module: QSM2-4W-C Daylight Sensor: EC-DIR-WH Ceiling Dual Technology Sensor: LOS-CDT-2000-WH Din Rail Power Supply: QSPS-DH-1-75 Raise/Lower/On/Off switch: PX-2BRL-GWH-Io1/CW-1-WH Programming Interface: QSE-CI-AP-D Integration to XPS: QSE-IO These rooms can act as one room or separately depending on when the operable wall is closed. F13 fixture to be shut-off independently from rest of F13 fixtures. Areas where fixtures will be controlled by local room controls. 1. 2. 3. 4. 5. 6. 7. 8. Maker’s Space 208 Wet Storage 208A Dry Storage 208B IT Room 211 Community Board Room 210 Storage 212 Primary AV 216 Elec 216A Lewiston Library Second Floor Remodel Project 16561-4 15025 9. F. Storage 213A Areas needing Special Control 1. 2. Large Meeting Room 213 a. This room will be controlled by a dimming control panel. iLumin SC120-UN-3P-ML-20. See drawing for dimming circuits. Serve and Prep 217 a. Provide local digital switch to control this area for demonstrations. PART 3 - EXECUTION 3.01 INSTALLATION A. Attend a pre-install meeting with the owner, electrical contractor, and lighting controls contractor to discuss the lighting functions of the facility. B. Provide detailed point to point wiring diagrams for every termination. Provide wire specifications and wire colors to simplify contactor termination requirements. Provide shop drawings. C. Install the work of this Section in accordance with manufacturer’s printed instructions unless otherwise indicated. D. Calibrate all sensor time delays and sensitivity to guarantee proper detection of occupants and energy savings. 1. E. Provide written or computer-generated documentation on the commissioning of the system including room by room description including: 1. 2. 3. F. 3.02 Adjust time delay so that controlled area remains lighted for 5 minutes after occupant leaves area. Sensor parameters, time delays, sensitivities, and daylighting setpoints. Sequence of operation, (e.g. manual ON, Auto OFF. etc.) Load Parameters (e.g. blink warning, etc.) Re-commissioning – After 30 days from occupancy re-calibrate all sensor time delays and sensitivities to meet the Owner’s Project Requirements. Provide a detailed report to the Architect / Owner of re-commissioning activity. FACTORY COMMISSIONING A. Upon completion of the installation, the system shall be commissioned by the manufacturer's factory authorized representative who will verify a complete fully functional system. B. The electrical contractor shall provide both the manufacturer and the electrical engineer with ten working days written notice of the system startup and adjustment date. C. Upon completion of the system commissioning the factory-authorized technician shall provide the proper training to the owner's personnel on the adjustment and maintenance of the system. D. Training shall be video recorded if required by end user. Lewiston Library Second Floor Remodel Project 16561-5 15025 PART 4 - EXECUTION 4.01 4.02 INSTALLATION A. Install equipment in accordance with manufacturer’s installation instructions. B. XPS control system cable/wiring to wall stations, sensors, modules, etc must be daisychained. T-taps, star, or other wiring topologies are not allowed. Refer to installation instructions. C. Provide complete installation of system in accordance with Contract Documents. D. Provide equipment at locations and in quantities indicated on Drawings. Provide any additional equipment required to provide control and design intent. SERVICE AND SUPPORT A. Startup and Programming 1. 2. 3. B. Technical Support 1. 2. C. 2. 3. 4. Provide minimum eight (8) hours end-user training upon completion of startup and programming. Arrange training time/date with end user at least two (2) weeks prior to startup and programming. Provide sign up list with names and titles. Training shall be video recorded if required by end user. CLOSEOUT ACTIVITIES A. 4.04 Provide factory direct technical support hotline 24 hours per day, 7 days per week. Provide local support through manufacturer’s representative: a. Ambient Lighting of Spokane, WA. Training 1. 4.03 Provide system start-up and programming upon completion of installation: Contractor must obtain, fill out, and return the Lutron pre-startup checklist documentation prior to startup and programming. Contractor shall obtain from end user required time clock schedule(s), scenes, event schedule(s), and related end-user input information prior to startup. Provide O&M Manual documentation, startup reports, and related information as required by the specifications. MAINTENANCE A. Capable of providing on-site service support within 24 hours anywhere in continental United States and within 72 hours worldwide except where special visas are required. Lewiston Library Second Floor Remodel Project 16561-6 15025 B. Offer renewable service contract on yearly basis, to include parts, factory labor, and annual training visits. Make service contracts available up to ten years after date of system startup. END OF SECTION 15651 Lewiston Library Second Floor Remodel Project 16561-7 15025 SECTION 16720 - FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 1.02 DESCRIPTION A. Provide an extension of the existing Silent Knight Farenhyt IFP-2000 fire alarm control system to include the new devices indicated on the drawing. This section includes the extension and testing of the existing intelligent reporting fire alarm system. B. The contractor shall furnish and install a complete 24 VDC, electrically supervised, analog addressable fire alarm system as specified herein and indicated on the drawings. The system shall include but not be limited to all control panels, power supplies, initiating devices, audible and visual notification appliances, alarm devices, and all accessories required to provide a complete operating fire alarm system. C. The fire alarm system shall comply with requirements of NFPA Standard 72 for Protected Premises Signaling Systems except as modified and supplemented by this specification. The system shall be electrically supervised and monitor the integrity of all conductors. D. The installing company shall employ NICET (minimum Level II Fire Alarm Technology) technicians on site to guide the final checkout and to ensure the systems integrity. SCOPE A. An extension to the intelligent reporting, microprocessor controlled fire detection system shall be installed in accordance to the project specifications and drawings. B. Basic Performance 1. Alarm a. When a device indicates any alarm condition the control panel must respond within 10 seconds. The General Alarm or Supervisory Alarm LED on the annunciator(s) should light and the LCD should prompt the user as to the number of current events. The alarm information must be stored in event memory for later review. Event memory must be available at the main and all remote annunciators. b. When the alarmed device is restored to normal, the control panel shall be required to be manually reset to clear the alarm condition, except that the alarms may be silenced as programmed. c. An alarm shall be silenced by a code at the main or remote annunciators. When silenced, this shall not prevent the resounding of subsequent events if another event should occur (subsequent alarm feature). When alarms are silenced the silenced LED on the control panel, and on any remote annunciators shall remain lit, until the alarmed device is returned to normal Lewiston Library Second Floor Remodel Project 16720-1 15025 2. 3. 1.03 Troubles a. When a device indicates a trouble condition, the control panel System Trouble LED should light and the LCD should prompt the user as to the number of current events. The trouble information must be stored in event memory for later review. Event memory must be available at the main and all remote annunciators. b. When the device in trouble is restored to normal, the control panel shall be automatically reset, The trouble restore information must be stored in event memory for later review. Event memory must be available at the main and all remote annunciators. A trouble shall be silenced by a code or at the main or remote annunciators. When silenced, this shall not prevent the resounding of subsequent events if another event should occur. Supervision methods a. Each SLC loop shall be electrically supervised for opens and ground faults in the circuit wiring, and shall be so arranged that a fault condition on any loop will not cause an alarm to sound. Additionally, every addressable device connected to the SLC will be supervised and individually identified if in a fault condition. The occurrence of any fault will light a trouble LED and sound the system trouble sounder, but will not interfere with the proper operation of any circuit which does not have a fault condition. b. Each indicating appliance circuit shall be electrically supervised for opens, grounds and short circuit faults, on the circuit wiring, and shall be so arranged that a fault condition on any indicating appliance circuit or group of circuits will not cause an alarm to sound. The occurrence of any fault will light the trouble LED and sound the system trouble sounder, but will not interfere with the proper operation of any circuit which does not have a fault condition. SUBMITTALS A. General: 1. B. Shop Drawings: 1. 2. 3. 4. C. Three copies of all submittals shall be submitted to the Architect/Engineer for review. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. Include manufacturer's name(s), model numbers, ratings, power requirements, equipment layout, device arrangement, complete wiring point-to-point diagrams, battery calculations and conduit layouts. Show annunciator layout, configurations, and terminations. Submit shop drawings, cut sheets and calculations to the AHJ for approval. Manuals: 1. 2. Submit simultaneously with the shop drawings, complete operating and maintenance manuals listing the manufacturer's name(s), including technical data sheets. Wiring diagrams shall indicate internal wiring for each device and the interconnections between the items of equipment. Lewiston Library Second Floor Remodel Project 16720-2 15025 3. D. Software Modifications 1. 2. E. 1.05 Provide the services of a factory trained and authorized technician to perform all system software modifications, upgrades or changes. Response time of the technician to the site shall not exceed 4 hours. Provide all hardware, software, programming tools and documentation necessary to modify the fire alarm system on site. Modification includes addition and deletion of devices, circuits, zones and changes to system operation and custom label changes for devices or zones. The system structure and software shall place no limit on the type or extent of software modifications on-site. Certifications: 1. 1.04 Provide a clear and concise description of operation that gives, in detail, the information required to properly operate the equipment and system. Together with the shop drawing submittal, submit a certification from the major equipment manufacturer indicating that the proposed supervisor of the installation and the proposed performer of contract maintenance is an authorized representative of the major equipment manufacturer. Include names and addresses in the certification. GUARANTY A. Warranty all materials, installation and workmanship for a three (3) year period, unless otherwise specified. A copy of the manufacturer warranty shall be provided with the close out documentation. B. The full cost of maintenance, labor and materials required to correct any defect during this warranty period shall be included in the submittal bid. POST CONTRACT MAINTENANCE A. Complete maintenance and repair service for the fire alarm system shall be available from a factory trained authorized representative of the manufacturer of the major equipment for a period of five (5) years after expiration of the guaranty. B. As part of the bid/proposal, include a quote for a maintenance contract to provide all maintenance, tests, and repairs described below. Include also a quote for unscheduled maintenance/repairs, including hourly rates for technicians trained on this equipment, and response travel costs for each year of the maintenance period. Submittals that do not identify all post contract maintenance costs will not be accepted. Rates and costs shall be valid for the period of five (5) years after expiration of the guaranty. C. Maintenance and testing shall be on a semiannual basis or as required by the AHJ. A preventive maintenance schedule shall be provided by the contractor describing the protocol for preventive maintenance. The schedule shall include: 1. 2. 3. Systematic examination, adjustment and cleaning of all detectors, manual fire alarm stations, control panels, power supplies, relays, waterflow switches and all accessories of the fire alarm system. Each circuit in the fire alarm system shall be tested semiannually. Each smoke detector shall be tested in accordance with the requirements of NFPA 72 Chapter 7. Lewiston Library Second Floor Remodel Project 16720-3 15025 1.06 APPLICABLE STANDARDS AND SPECIFICATIONS A. The specifications and standards listed below form a part of this specification. The system shall fully comply with the latest issue of these standards, if applicable. B. National Electric Code, Article 760 C. National Fire Protection Association Standards: 1. 2. 3. National Electrical Code National Fire Alarm Code Life Safety Code D. Local and State Building Codes E. Local Authorities Having Jurisdiction F. Underwriters Laboratories Inc. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. G. All equipment shall be approved by Underwriters Laboratories, Inc. for it’s intended purpose, listed as power limited by Underwriters Laboratories, Inc., for the following standards as applicable: UL 864 UOJZ Control units for Fire Protective Signaling Systems a. Local Signaling Unit b. Central Station Signaling Protected Premises Unit c. Remote Signaling Protected Premises Unit d. Water Deluge Releasing Unit UL 268 Smoke Detectors for Fire Protective Signaling systems. UL 268A Smoke Detectors for duct applications UL 217 Smoke Detectors for Single Stations UL 521 Heat Detectors for Fire Protective Signaling systems. UL 228 Door Holders for Fire Protective Signaling systems. UL 464 Audible Signaling appliances UL 1638 Visual Signaling appliances UL 38 Manually Activated Signaling Boxes UL 346 Waterflow indicators for Fire Protective Signaling systems. UL 1481 Power Supplies for Fire Protective Signaling systems. Americans with Disabilities Act (ADA). 1. 1.07 NFPA 70 NFPA 72 NFPA 101 All visual Notification appliances and manual pull stations shall comply with the requirements of the Americans with Disabilities Act. APPROVALS A. All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. Lewiston Library Second Floor Remodel Project 16720-4 15025 PART 2 - PRODUCTS 2.01 2.02 EQUIPMENT AND MATERIAL, GENERAL: A. All equipment and components shall be new, and the manufacturer's current model. The materials, appliances, equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a protective signaling system, meeting the National Fire Alarm Code. B. All equipment and components shall be installed in strict compliance with manufacturers' recommendations. Consult the manufacturer's installation manuals for all wiring diagrams, schematics, physical equipment sizes, etc., before beginning system installation. C. All equipment shall be attached to walls and ceiling/floor assemblies and shall be held firmly in place (e.g., detectors shall not be supported solely by suspended ceilings). Fasteners and supports shall be adequate to support the required load. MAIN FIRE ALARM CONTROL PANEL OR NETWORK NODE: A. Control Panel 1. The existing fire alarm control panel (FACP) is a Silent Knight IFP-2000 analog addressable control panel. B. The Signaling Line Circuit (SLC) and Data Communication Bus (S-BUS) shall be wired with standard NEC 760 compliant wiring, no twisted, shielded or mid capacitance wiring is required for standard installations. All FACP screw terminals shall be capable of accepting 12-18 AWG wire. All system wiring shall be in accordance with the requirements of NFPA 70, the National Electrical Code (NEC) and also comply with article 760 of the NEC. C. Signaling Line Circuits 1. D. Each SLC shall be capable of a wiring distance of 10,000 feet from the SLC driver module (5815XL) and be capable of supporting 159 detectors and 159 addressable module devices. The communication protocol to SLC devices must be digital. Any SLC loop device, which goes into alarm, must interrupt the polling cycle for priority response from the FACP. The FACP must respond consistently to a device that goes into alarm on an SLC in under 10 seconds. The auxiliary 5815XL SLC loop module must be capable of being located up to 6000 feet from the FACP on an RS-485 bus, which is separate from the SLC bus. The SLC shall be capable of functioning in a class A or class B configuration. SLC loop devices 1. Devices supported must include analog photoelectric, ionization smoke detectors, analog heat detectors, addressable input modules, relay output modules or addressable notification modules. There is to be no limit to the number of any particular device type up to the maximum of 159 detectors and 159 addressable modules that can be connected to the SLC. Lewiston Library Second Floor Remodel Project 16720-5 15025 E. Analog detector functions 1. F. Sensitivity function 1. G. The FACP shall support eight programmable Flexput circuits that are capable of being programmed as supervised reverse polarity notification circuits or supervised auxiliary power circuits that can be programmed as continuous, resettable or door holder power. The circuits shall also be programmable as input circuits in class A or B configurations to support dry contact or compatible two wire smoke detectors. Addressable Notification Module 1. I. The FACP shall have the ability to set three different sensitivity levels. A zone can be programmed to a day and a night sensitivity value. The day/night schedule shall allow for 16 holiday dates that are user programmable to allow the FACP to respond at the night level on those days. Programmable Flexputs 1. H. The products of combustion detectors must communicate analog values using a digital protocol to the control panel for the following functions: a. Automatic compliance with NFPA 72 standards for detector sensitivity testing b. Drift compensation to assure detector is operating correctly c. Maintenance alert when a detector nears the trouble condition d. Trouble alert when a detector is out of tolerance e. Alert control panel of analog values that indicate fire. The contractor shall furnish and install where indicated on the plans, addressable notification modules, Silent Knight model IDP-Control. The modules shall be U.L. listed compatible with Silent Knight’s IFP-2000 fire alarm control panel. The notification module must provide one class A (Style Z) or class B (Style Y) notification output with one auxiliary power input. The notification module must be suitable for mounting in a standard 4 square electrical box and must include a plastic cover plate. The notification module must provide an LED that is visible from the outside of the cover plate. The notification module must be fully programmable for such applications as required by the installation. The IDPControl shall reside on the SLC loop and can be placed up to 10,000ft. from the control or 5815XL SLC loop module. Annunciators 1. The main control must have a built in annunciator with an 160-character LCD display and feature LED’s for General alarm, Supervisory, System trouble, System Silence and Power. When in the normal condition the LCD shall display time and date based on a 200 year clock which is capable of automatic daylight savings time adjustments. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 in.. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a keypad entered code. The annunciators must have twenty levels of user codes that will allow the limitation of operating system programming to authorized individuals. Lewiston Library Second Floor Remodel Project 16720-6 15025 J. Remote Annunciators 1. 2. K. I/O LED Driver Module 1. L. The fire system shall be able to support a minimum of eight I/O modules (SK5880) that shall be used to drive remote LED graphic style displays and accommodate up to eight dry contact type switch inputs. The I/O modules shall each drive up to 40 LEDs without requiring external power connections. The I/O module inputs shall be supervised and be suitable for alarm and trouble circuits as well as reset and silence switches. The system shall also support up to 40 LED drivers that reside on the two-wire SLC loop. These driver boards shall contain 80 LED outputs that are powered by an external power source. Serial/Parallel Interface 1. M. The fire system shall be capable of supporting a minimum of eight remote annunciators. LCD Remote annunciator Model RA-2000 shall have the same control and display layout so that they match identically the built in annunciator. Remote annunciators shall have the same functionality and operation as the built in annunciator. All annunciators must have 160-character LCD displays and must feature five LED’s for general alarm, supervisory, system trouble, system silence, and system power. All controls and programming keys are silicone mechanical type with tactical and audible feedback. Keys shall have a travel of .040 inches. No membrane style buttons will be permitted. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad. The annunciator must have twenty levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple users input simultaneously. Remote annunciators shall be capable of operating at a distance of 6000 feet from the main control panel on unshielded non-twisted cable. The fire system shall be capable of supporting up to two serial / parallel interfaces (SK5824) that are capable of driving standard computer style printers. The interface shall be programmable as to what information is sent to it and shall include the ability to print out Detector Status by point, Event History by point and System Programming. Distributed Power Module 1. The contractor shall supply a power module RPS-1000 compatible with the IFP2000 fire alarm control panel. The power module must have 6 amps of output power, six flexput circuits rated at 3 amps each, and two form C relay circuits rated at 2.5 amps at 24 volts DC. The fire system shall be capable of supporting a minimum of eight (8) RPS-1000 power modules. The six flexput circuits shall have the same functionality as the flexput circuits on the main panel. The Distributed Power Supply shall be capable of being connected via an RS-485 system bus (SBUS) at a maximum distance of 6000ft. from the main control panel. The power module shall contain an additional RS-485 bus that is completely compatible with all IFP-2000 add on modules; including 5815XL SLC expanders, RA-2000, 5865, 5880 annunciators, 5824 serial/parallel module and addressable devices. The power module will also act as a bus repeater so that additional RS-485 (modules) devices can be connected at a maximum distance of 6000ft. from the power module. Lewiston Library Second Floor Remodel Project 16720-7 15025 2. N. Digital Communicator 1. 2. O. A ground fault detection circuit, to detect positive and negative grounds on all field wiring. The ground fault detector shall operate the general trouble devices as specified but shall not cause an alarm to be sounded. Ground fault will not interfere with the normal operation, such as alarm, or other trouble conditions. Over current Protection 1. R. The FACP will have three form “C” dry contacts, one will be dedicated to trouble conditions, the other two will be programmable for alarm, trouble, sprinkler supervisory, notification, pre-alarm, waterflow, manual pull, aux. 1 or aux. 2. The trouble contact shall be normal in an electrically energized state so that any total power loss (AC and Backup) will cause a trouble condition. In the event that the Microprocessor on the FACP fails the trouble contacts shall also indicate a trouble condition. Ground Fault Detection 1. Q. The digital communicator must be an integral part of the control panel and be capable of reporting all zones or points of alarm, supervisory, and trouble as well as all system status information such as loss of AC, low battery, ground fault, loss of supervision to any remote devices with individual and distinct messages to a central station or remote station. The communicator must also be capable of up/downloading of all system programming options, Event history and Sensitivity compliance information to a PC on site or at a remote location. The communicator shall have an answering machine bypass feature that will allow the panel to respond to communication even on phone lines that have other communication equipment present. The communicator must be capable of reporting via SIA and Contact ID formats. The communicator shall have a delayed AC loss report function which will provide a programmable report delay. No controls that use External modems for remote programming and diagnostics shall be accepted. Dry Contacts 1. P. The power module’s RS-485 bus shall be electrically isolated providing ground loop isolation and transient protection. All low voltage circuits will be protected by microprocessor controlled power limiting or have a self restoring polyswitches for the following: smoke detector power, main power supply, indicating appliance circuits, battery standby power and auxiliary output. Test Functions 1. 2. A “Lamp Test” or “Indicator Test” mode shall be a standard feature of the fire alarm control panel and shall test all LED’s and the LCD display on the main panel and remote annunciators. A “Walk Test” mode shall be a standard feature of the fire alarm control panel. The walk test feature shall function so that each alarm input tested will operate the associated notification appliance for two seconds. The FACP will then automatically perform a reset and confirm normal device operation. The event memory shall contain the information on the point tested. the zone tripped, the zone restore and the individual points return to normal. Lewiston Library Second Floor Remodel Project 16720-8 15025 3. 4. S. Remote Input Capabilities 1. T. All notification circuits and modules shall be programmable via a mapping structure that allows for a maximum of 999 output groups. Each of these groups shall have the ability to be triggered by any of the panels 999 Zones. A zone may trigger from groups individually, or may contain a global trigger for manual pull stations, fire drills and two different system alarms. Additionally each Zone will individually control the cadence pattern of each of the Groups that it is “Mapped” to so that sounders can indicate a variety of conditions. The Zone shall be capable of issuing a different cadence pattern for each of the Groups under it’s control. The mapping structure must also allow a group to be designated to “ignore cadence” for use with strobes and other continuous input devices. Zones shall have eight different output categories; Detector alarm, Trouble, Supervisory, Pre-alarm, Waterflow, Manual pull, Zone Auxiliary one and Zone Auxiliary two. The patterns are; March code, ANSI 3.41, Single Stroke Bell Temporal, California code, Zone 1 coded, Zone 2 coded, Zone 3 coded, Zone 4 coded, Zone 5 coded, Zone 6 coded, Zone 7 coded, Zone 8 coded, Custom output pattern 1, Custom output pattern 2, Custom output pattern 3, Custom output pattern 4, and Constant. Each NAC circuit can also be configured to produce one of four synchronization patterns: AMSECO synchronization, Gentex synchronization, System Sensor synchronization, and Wheelock synchronization. This mapping/cadence pattern shall be supported by all system power supplies and Notification Expander Modules. This mapping/cadence pattern shall be supported by all system power supplies and Notification Expander Modules. Downloading Software 1. V. The control panel shall have provisions for supervised switch inputs for the purpose of Alarm reset and Alarm and trouble restore. Notification Appliance Mapping Structure 1. U. A “Fire Drill” mode shall allow the manual testing of the fire alarm system notification circuits. The “Fire Drill” shall be capable of being controlled at the main annunciator, remote annunciators and via a remote contact input. A “Bypass Mode” shall allow for any point or NAC circuit to be bypassed without effecting the operation of the total fire system. The fire alarm control panel must support up/downloading of system programming from a Windows based PC. The FACP must also be able to download the detector sensitivity test results and a 1000 event system event buffer to the PC. Communication shall take place over a direct connection to the PC and/or via the same telephone lines as the built in digital communicator and shall not require an external modem to be connected to the panel. The downloading software shall contain a code that will block unauthorized persons from accessing the panel via direct connection or over the phone lines. English language descriptions 1. The FACP shall provide the ability to have a text description of each system device, input zone and output group on the system. The use of individual lights to provide descriptions will not be acceptable. Lewiston Library Second Floor Remodel Project 16720-9 15025 2.03 SYSTEM COMPONENTS A. Power Supply and Charger: 1. 2. 3. 4. 2.04 2.05 The entire system shall operate on 24 VDC, filtered switch mode power supply with the rated current available of 9 Amps. The FACP must have a battery charging circuit capable of complying with the following requirements: a. Sixty (60) hours of battery standby with five (5) minutes of alarm signaling at the end of this sixty (60) hour period (as required per NFPA 72 remote station signaling requirements) using rechargeable batteries with automatic charger to maintain standby gel-cell batteries in a fully charged condition. The power supply shall comply with U.L. Standard 864 for power limiting. The FACP will indicate a trouble condition if there is a loss of AC power or if the batteries are missing or of insufficient capacity to support proper system operation in the event of AC failure. A “Battery Test” will be performed automatically every minute to check the integrity of the batteries. The test must disconnect the batteries from the charging circuit and place a load on the battery to verify the battery condition. In the event that it is necessary to provide additional power one or more of the model RPS-1000 Distributed Power Modules shall be used to accomplish this purpose. Alternatively, additional IFP-2000 control panels can be networked to provide additional power. Connections and Circuits A. Connections to the light and power service shall be on a dedicated branch circuit in accordance with the National Fire Alarm Code NFPA 72, National Electrical Code (NEC) NFPA 70, and the local authority having jurisdiction (AHJ). B. The circuit and connections shall be mechanically protected. C. A circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly marked “FIRE ALARM CIRCUIT CONTROL”. ACCESSORY COMPONENTS A. The FACP shall support a the following devices on the RS-485 data bus: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 5815XL 5824 RA-2000 5865-3 5865-4 5880 RPS-1000 5495 5496 5499 Lewiston Library Second Floor Remodel Project Signaling Line Circuit Expander (SLC) Module Printer Interface Module LCD Remote Annunciator LED Remote Annunciator LED Remote Annunciator with reset and silence switches LED I/O module Intelligent Distributed Power Module Remote Power Supply 6.0 Remote Addressable Power Supply 6.0 Amp Remote Power Supply 9.0 Amp 16720-10 15025 B. The FACP shall support the operation of 159 detectors and 159 addressable module total devices per SLC loop without regard to device type. The following devices shall be supported: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. C. The FACP shall support these other Silent Knight devices via addressable input, addressable Notification, or Addressable Output Modules. 1. 2. 2.06 IDP-Photo Addressable Photoelectric Smoke Sensor IDP-Photo-T Addressable Photoelectric Smoke Sensor with Thermal IDP-Ion Addressable Ionization Sensor IDP-Heat Addressable Heat Sensor IDP-Heat-ROR Addressable Heat with Rate of Rise IDP-Heat-HT Addressable Heat High Temp 190° IDP-Acclimate Addressable Multi Criteria Smoke Sensor with Thermal SSDNR Addressable Photoelectric Duct Detector Does Not Include Head SSDCOIL required on the DNR (Older Than Date Code 0013) if Remote Test Switch is Used IDP-6AB 6” Detector Base IDP-Relay Addressable Relay Module IDP-Relay-6 Addressable Multi Relay Module IDP-Monitor Addressable Input Module (Class A or B) IDP-Minimon Mini Input Module IDP-Monitor-2 Addressable Dual Input Module IDP-Monitor-10 Addressable Multi Input Module (10) IDP-Control Addressable Notification Module IDP-Control-6 Addressable Notification Multi Module (6) IDP-Zone Two Wire Smoke Detector Module IDP-Zone-6 6 Multi Smoke Detector Module IDP-Iso Isolation Module IDP-Beam Addressable Beam Detector IDP-Beam-T Addressable Beam Detector with Test feature SSB224RB Detector Relay Base SSB501BHT Detector Sounder Base SSRTS151KEY Key Activated Remote Test Switch For Photoelectric Duct Detector SSRTS151 Magnet Remote Test Switch IDP-Pull-SA Addressable Single Action Pull Station IDP-Pull-DA Addressable Dual Action Pull Station PS-SATK PS-DATK Single Action Manual Pull Station – Key Reset Dual action Manual Pull Station – Key Reset Furnish and install, where shown on the drawings, the following devices A. Manual Fire Alarm Stations 1. Manual Fire Alarm Stations shall be non-coded, break glass, single or double action type, with a key operated test-reset lock in order that they may be tested, and so designed that after actual emergency operation, they cannot be restored to normal except by use of a key. The reset key shall be so designed that it will reset manual station and open FACP without use of another key. An operated station shall automatically condition itself so as to be visually detected, as operated, at a Lewiston Library Second Floor Remodel Project 16720-11 15025 minimum distance of fifty feet, front or side. Manual stations shall be constructed of die cast metal with clearly visible operating instructions on the front of the stations in raised letters. Stations shall be suitable for surface mounting on matching backbox, or semi-flush mounting on a standard single-gang box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) dependent on manual station accessibility or per local requirements. Manual stations shall be Model IDP-Pull. If using conventional pull stations they must be installed in conjunction with an Addressable Input Module (IDPMonitor) or Mini Input Module (IDP-Minimon) used with the manual stations. Shall be Silent Knight Model PS-DATK, PS-SATK, PS-DA or PS-SA and Underwriters Laboratories listed when used with addressable modules. B. Remote Power Supplies 1. 2. C. Notification Devices 1. D. The Remote Power Supplies for Notification appliances shall be the Silent Knight Model RPS-1000. The Model RPS-1000 Intelligent Power Supply shall hang on the main S-Bus and be programmed through the IFP-2000 control. It will support 6 amps of 24 volt DC power, with 6 Flexput circuits, rated at 3 amps each. Two additional 5815XL SLC loop expanders shall be capable to be installed in the cabinet. The power supply will also regenerate the S-Bus for an additional 6000’. The remote power supply model 5499 or 5495 may also be used on the system. These power supplies are activated by the IDP-Control module and support 24VDC power, with 4 notification circuits, rated at 3 amps each. The total power on a 5495 is 6 amps. The total power on a 5499 is 9 amps. These power boosters may also be activated from another notification circuit from either the fire alarm control, a distributed power supply (RPS-1000). The visual and audio/visual signaling devices shall be compatible with the IFP2000, RPS-2000, 5495, 5496, 5499, or RPS-1000 as stated in the installation manuals and be Listed with Underwriters Laboratories Inc. per UL 1971 and/or 1638. Each indicating appliance circuit shall be electrically supervised for opens, grounds and short circuit faults, on the circuit wiring, and shall be so arranged that a fault condition on any indicating appliance circuit or group of circuits will not cause an alarm to sound. The occurrence of any fault will light the trouble LED and sound the system trouble sounder, but will not interfere with the proper operation of any circuit which does not have a fault condition. The notification appliance (combination audio/visual units only) shall produce a peak sound output of 90dba or greater as measured in an anechoic chamber. The appliance shall be capable of meeting the candela requirements of the blueprints presented by the Engineer and ADA. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with terminals with barriers for input/output wiring and be able to mount a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 19-30 volts. Smoke Detectors 1. Smoke detectors shall be Silent Knight model IDP-Photo ceiling mounted, Analog/Addressable photoelectric smoke detectors. The combination detector head and twist lock base shall be U.L. listed compatible with the Silent Knight IFP-2000 fire alarm control panel. Lewiston Library Second Floor Remodel Project 16720-12 15025 2. 3. 4. 5. E. Heat Detectors 1. 2. 3. F. Furnish and install analog/addressable heat detectors, Silent Knight model IDPHeat. The combination heat detector and twist lock base shall be U.L. listed compatible with the Silent Knight IFP-2000 fire alarm control panel. The base shall permit direct interchange with the Silent Knight IDP- Ionization smoke detector and the IDP-Photo photoelectric smoke detector. The base shall be appropriate twist lock base IDP-6AB. The heat detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel’s reset switch. The vandal security-locking feature shall be used in those areas as indicated on the drawings. Electronics of the unit shall be shielded to protect against false alarms from E.M.I. and R.F.I. Duct Detectors 1. 2.07 The base shall permit direct interchange with Silent Knight’s IDP-Ion ionization smoke detector or the IDP-Heat detector. The base shall be the appropriate twist lock base IDP-6AB The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel’s reset switch. The sensitivity of the detector shall be capable of being selected and measured by the control panel without the need for external test equipment. The vandal security-locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable when required. It shall be possible to perform a sensitivity test of the detector without the need of generating smoke. The test method shall simulate the effects of products of combustion in the chamber to ensure testing of the detector circuits. Detectors shall have completely closed back to restrict entry of dust and air turbulence and have a 30 mesh insect screen. Electronics of the unit shall be shielded to protect against false alarms from E.M.I. and R.F.I. Duct Detector shall be Silent Knight SSDNR with an IDP-Photo smoke head. WIRING A. Installer’s Responsibilities 1. 2. 3. B. The installer shall coordinate the installation of the fire alarm equipment. All conductors and wiring shall be installed according to the manufacturer’s recommendations. It shall be the installer’s responsibility to coordinate with the supplier, regarding the correct wiring procedures before installing any conduits or conductors. Installation of System Components 1. 2. System components shall be installed in accordance with the latest revisions of the appropriate NFPA pamphlets, the requirements contained herein, National Electrical Code, local and state regulations, the requirements of the fire department and other applicable authorities having jurisdiction (AHJ). All wire used on the fire alarm system shall be U.L. Listed as fire alarm protection signaling circuit cable per National Electrical Code, Articles 760. Lewiston Library Second Floor Remodel Project 16720-13 15025 2.08 WARRANTY AND FINAL TEST A. General 1. B. Final Test 1. 2. 3. 4. 5. 6. 7. 8. C. The contractor shall warrant all equipment and wiring free from inherent mechanical and electrical defects for one year (365 days) from the date of final acceptance. Before the installation shall be considered completed and acceptable by the awarding authority, a test of the system shall be performed as follows: The contractor’s job foreman, a representative of the owner, and the fire department shall operate every building fire alarm device to ensure proper operation and correct annunciation at the control panel. At least one half of all tests shall be performed on battery standby power. Where application of heat would destroy any detector, it may be manually activated. The communication loops and the indicating appliance circuits shall be opened in at least two (2) locations per circuit to check for the presence of correct supervision circuitry. When the testing has been completed to the satisfaction of both the contractor’s job foreman and owner, a notarized letter cosigned by each attesting to the satisfactory completion of said testing shall be forwarded to the owner and the fire department. The contractor shall leave the fire alarm system in proper working order, and, without additional expense to the owner, shall replace any defective materials or equipment provided by him under this contract within one year (365 days) from the date of final acceptance by the awarding authority. Prior to final test the fire department must be notified in accordance with local requirements. As Built Drawings, Testing, and Maintenance Instructions 1. 2. As Built Drawings a. A complete set of reproducible “as-built” drawings showing installed wiring, color coding, and wire tag notations for exact locations of all installed equipment, specific interconnections between all equipment, and internal wiring of the equipment shall be delivered to the owner upon completion of system. Operating and Instruction Manuals a. Operating and instruction manuals shall be submitted prior to testing of the system. Three (3) complete sets of operating and instruction manuals shall be delivered to the owner upon completion. User operating instructions shall be provided prominently displayed on a separate sheet located next to the control unit in accordance with U.L. Standard 864. PART 3 - EXECUTION 3.01 INSTALLATION A. Installation shall be in accordance with the NEC, NFPA 72, local and state codes, as shown on the drawings, and as recommended by the major equipment manufacturer. Lewiston Library Second Floor Remodel Project 16720-14 15025 3.02 B. All conduit, junction boxes, conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas. Smoke detectors shall not be installed prior to the system programming and test period. If construction is ongoing during this period, measures shall be taken to protect smoke detectors from contamination and physical damage. C. All fire detection and alarm system devices, control panels and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas. D. Manual fire alarm boxes shall be suitable for surface mounting or semi-flush mounting as shown on the plans, and shall be installed not less than 42 inches (1067 mm), nor more than 48 inches (122 mm) above the finished floor. TEST A. The service of a competent, factory-trained engineer or technician authorized by the manufacturer of the fire alarm equipment shall be provided to technically supervise and participate during all of the adjustments and tests for the system. All testing shall be in accordance with NFPA 72, Chapter 7. B. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation. C. Close each sprinkler system flow valve and verify proper supervisory alarm at the FACP. D. Verify activation of all waterflow switches. E. Open initiating device circuits and verify that the trouble signal actuates. F. Open and short signaling line circuits and verify that the trouble signal actuates. G. Open and short notification appliance circuits and verify that trouble signal actuates. H. Ground all circuits and verify response of trouble signals. I. Check presence and audibility of tone at all alarm notification devices. J. Check installation, supervision, and operation of all intelligent smoke detectors using the walk test. K. Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points. L. When the system is equipped with optional features, the manufacturer's manual shall be consulted to determine the proper testing procedures. This is intended to address such items as verifying controls performed by individually addressed or grouped devices, sensitivity monitoring, verification functionality and similar. Lewiston Library Second Floor Remodel Project 16720-15 15025 3.03 FINAL INSPECTION A. 3.04 At the final inspection, a factory-trained representative of the manufacturer of the major equipment shall demonstrate that the system functions properly in every respect. INSTRUCTION A. Instruction shall be provided as required for operating the system. Hands-on demonstrations of the operation of all system components and the entire system including program changes and functions shall be provided. B. The contractor and/or the systems manufacturer's representatives shall provide a typewritten "Sequence of Operation." END OF SECTION 16720 Lewiston Library Second Floor Remodel Project 16720-16 15025 SECTION 16727 – DOOR SECURITY SYSTEM PART 1 - GENERAL 1.01 1.02 1.03 1.04 GENERAL REQUIREMENTS A. Provide an extension to the existing DMP XR500 security detection and alerting system as indicated. System shall provide digital alarm and trouble transmission to a central reporting agency of the Owner’s choice. The unit shall be UL listed for Commercial Burglary applications. B. System shall support the future addition and expansion. RELATED REQUIREMENTS A. All provisions of the contract including Division 1 apply to work specified in each section of this Division 16. B. See Sections 16010, 16110, 16120, 16134, 16199 and 16751. SUBMITTALS A. Product Data: Provide vendor information for each type of security device installed on the project. B. Shop Drawings: Provide floor plan wiring diagrams indicating equipment locations and wiring configuration. Include riser diagrams, rough-in diagrams, instructions for installation, and operation and maintenance instructions. All drawings shall be machine produced on AUTOCAD 2010 or later release. SYSTEM DESCRIPTION A. The system areas and zones shall be programmable, and the system shall store, log, display, and transmit specific custom designations for system areas, zones, and user names. B. To ensure continued, one-call support, the system shall be constructed of sensing components provided directly by the system manufacturer, such as power supplies, motion detectors, door and window position switches, glass break detectors, or other sensing devices that the manufacturer offers. C. The system controller, user interfaces, zone input devices, relay output devices, and the system signal receiving equipment shall be engineered, manufactured, assembled, and must be distributed from a location within the United States of America. D. The system shall support user interaction by way of a keypad, web browser, system software, key switch, or radio frequency wireless control, using integrated or auxiliary devices provided by the system manufacturer. E. The system shall support controller zone input connections, system keypads, system zone expansion modules, and wireless zone input modules, and must support zone input connections by way of at least two competitive products. The system shall offer a seamless integrated compatibility with hard-wire and/ or wireless zone expansion equipment for at least 200 wireless zones and/ or a maximum of 574 hardwired zones. F. The system shall be capable of offering at least five zone expansion buses, each of which can support the connection of up to 15,000 feet of four-wire cable. Zone expansion and keypad data buses that exceed 2,500 feet of cable must include splitter/repeater modules to boost data voltage and maintain data integrity. Lewiston Library Second Floor Remodel Project 16727-1 15025 1.05 1.06 G. The system shall provide a seamless capability to provide a minimum of 500 addressable relays, which can be located at any connection location upon a zone expansion bus. H. System relay outputs shall have the capability of being triggered as a result of a command from the user interface, changes in system status, changes in zone status, or by a programmable schedule. I. System relay output states shall be programmable for momentary, maintained, pulsed, or must follow the state of an associated system zone input. J. The system shall be completely programmable either locally from a keypad or remotely through a standard dial-up, and network connections by way of a LAN, WAN, and/or by way of the Internet. K. The control unit shall be completely programmable remotely using remote annunciators, and/ or using upload/ download software that communicates using SDLC 300 baud, 2400 baud, or IP Addressed data network. On-site programming from a personal computer shall also be permitted. L. The control unit shall be equipped with an anti-reversing circuit breaker to prevent damage due to accidental reversal of battery leads. SYSTEM OPERATION A. This system shall be capable of monitoring a maximum of 574 individual zones and controlling a maximum of 502 output relays. B. The control panel shall have, as an integral part of the assembly, 2 SPDT Form C relays rated at 1 Amp at 30 VDC and four open collector 12 VDC outputs rated at 50mA each. It shall also have the capacity of a maximum of 125 output expander modules with 500 switched ground, open collector outputs, 50mA maximum and 502 auxiliary relays (Form C rated at 1.0 Amp at 30 VDC). C. The panel shall also provide 100 programmable output schedules, and include an integral bell alarm circuit providing at least 1.5 Amps of steady, pulsed, or temporal bell output. Output type shall be programmable by zone type. Relays and voltage outputs shall be capable of being independently programmed to turn on and/or off at selected times each day. SYSTEM FEATURES A. Control Panel Capability 1. The basic control panel shall provide: a. Expansion to a total of at least 10,000 user codes with 99 user profile definitions. b. Sixteen (16) independent door/keypad addresses, each with four zones. c. Twenty (20) Holiday Dates for custom holiday scheduling by area. d. A total door access granted event buffer of at least 10,000 events. e. Anti-passback access control selectable by area and user. f. Four (4) shift schedules per area. g. A total of at least 100 programmable output relay schedules. h. Thirty-two (32) individual reporting areas. i. Built-in bell and telephone line supervision. Lewiston Library Second Floor Remodel Project 16727-2 15025 PART 2 - EQUIPMENT 2.01 2.02 MATERIALS A. Control Panel: Existing DMP XR500 Series Access/Burglary/Fire 574-Zone Command Processor Panel B. Keypads: DMP Thinline LCD Keypads LT7073 C. Proximity Card Reader: Assa Abloy HID ProxPro Reader Hu5355 D. Zone Expansion Module: DMP LT714-16 E. PIR Motion Sensors: Optex RX-40 PI Wall Mount F. 360 Degree PIR Motion Sensor: Optex FX-360 G. Hinged Door Contacts: Equivalent to Sentrol #1378 Series magnetic flush-mounted contacts and magnets. Each contact shall be hermetically sealed for long term 10,000,000 cycle operation. Switch contacts shall be of the reed blade type with rhodium plating eliminating cold-welding; sticking and resistance build-up. All switches shall be 100% factory tested prior to installation. H. Overhead Door Contacts: Same features as specified for Hinged Door Contacts, except designed to monitor vertically moving doors. I. Power Supplies: DMP LT 505 Series COMPILED DETECTION EQUIPMENT LISTING A. Hard-wired 1. Hard-wired detection equipment shall communicate to the system by way of the control panel loop expansion bus. The equipment shall have a three (3) year warranty as stated in the current DMP Product Catalog and meet or exceed features offered in the following products: a. Motion Detector – DMP Model 6155LX (wall mount with built-in zone expander) b. Motion Detector – DMP Model AP669 (ceiling mount 360’ – requires DMP zone expander) c. Glass Break Detector – DMP Model 5845LX (includes built-in zone expander) d. Door Contact – DMP Model SD70 (concealed applications – requires DMP zone expander) e. Bus Splitter/Repeater Module – DMP Model 710 f. Door Contact – DMP Model SM20WG (surface applications – requires DMP zone expander) g. Output Expansion Module - DMP Model 716 h. Graphic Annunciator Module - DMP Model 717 i. Other product types shall connect directly to zone expansion modules such as: 1) Manual Fire Alarms – DMP Models 850S, 850D 2) Smoke/Smoke Heat Detectors – NS6-100 and SLR-835 or SLR835H 3) Smoke/Smoke Heat Detectors – SLR-835B, SLR-835BH 4) Addressable - DMP Model 711 5) Addressable - DMP Models 714, 714-8, 714-16 6) Addressable - DMP Models 712-8 Lewiston Library Second Floor Remodel Project 16727-3 15025 7) 8) 9) B. Wireless 1. C. Wireless detection equipment shall communicate to the system by way of a compatible 900MHz receiver utilizing two way communications, capable of receiving up to 500 wireless zones. The wireless system shall be programmed directly from the control panel, and shall not require a separate device programmer. The wireless detection equipment shall have a one (1) year warranty. It shall be capable of sending transmitter and battery status to the control panel’s compatible receiver up to once every 60 seconds and must meet or exceed the following products: a. Input transmitter – DMP Model 1101, 1102 b. Pendant Panic Transmitter – DMP Model 1147, 1146, 1145 c. Smoke Detector Transmitter – DMP Model 1161, 1162 d. Motion Detector – DMP Model 1121 or DMP Model 1125 e. Glass Break Detector – DMP Model 1129 f. Bill Trap – DMP Model 1139 g. Panic Transmitter – DMP Model 1142 h. Wireless Receiver – DMP Model 1100X, 1100XI, 1100XH i. Recessed Contact – DMP Model 1131-W Notification Devices 1. D. Addressable - DMP Models 715, 715-8, 715-16 Addressable - DMP Models 521LX, 521LXT, 850S/711, 850D/711 Non-Addressable - DMP Models 521B, 850S, 850D Notification equipment shall be control panel activated by way of the supervised bell output module. The equipment shall have a three (3) year warranty as stated in the current DMP Product Catalog and meet or exceed features offered in the following products: a. Bells – Wheelock Model MB-G6-12, MB-G10-12, MB-G6-24, MBG10-24 b. Horns – Wheelock Model MT-12/24, NH-12/24, MIZ-24, AH-24, AH24WP c. Strobe – Wheelock Model RSS-121575W, RSS-24MCW d. Horn Strobe – Wheelock Model MTWP=2475W, NS-121575W, NS24MCW, AS-24MCW e. Notification Modules – DMP Models 865, 866, 867, f. Notification/Synchronization Modules – DMP Models 831, 832 Power Supplies and Transformers 1. Power supply, transformer, and battery devices shall maintain system operation. The batteries shall be checked and replaced every three to five years. The equipment shall have a three (3) year warranty as stated in the current DMP Product Catalog and meet or exceed features offered in the following products: a. Power Supply – DMP Model 505-12, 115 VAC, 12 VDC b. Power Supply – DMP Model 505-12LX, 115 VAC, 12 VDC c. Transformer - DMP Model 327, 16.5 VAC 50 VA, Plug-in d. Transformer - DMP Model 322, 16.5 VAC 56 VA, Wire-in e. Transformer - DMP Model 323, 16.5 VAC 56 VA, Wire-in Lewiston Library Second Floor Remodel Project 16727-4 15025 E. Access Control Equipment 1. Access control equipment shall provide access control functions between the panel and controller door access points. The equipment shall have a three (3) year warranty as stated in the current DMP Product Catalog and meet or exceed features offered in the following products: a. Interface Module – DMP Model 734, Wiegand b. Egress Module – DMP Model PB-2 REX Button c. Reader – DMP Model PP-6005B Proxpoint Plus© d. Reader – DMP Model MP-5365 Miniprox© e. Reader – DMP Model MX-5375 Maxi-Prox™ f. Reader – DMP Model TL-5395 Thinkline II™ g. Door Controller – DMP Model 1306P Prox Patch™ h. Door Controller – DMP Model 1306PW Prox Patch™ i. Access Card – DMP Model 1351 ProxPass© Card j. Access Card – DMP Model 1326 Proxcard II© Card k. Access Device – DMP Model 1346 Proxkey II™ Keyfob, 1386 Isoprox PART 3 - INSTALLATION 3.01 3.02 3.03 MANUFACTURERS A. Installers shall be qualified with at least 5 years of successful installation experience on projects with low-voltage electronic systems installation work similar to that required for the project. B. Any person installing this equipment and wiring must hold valid State of Idaho electrical licenses. Installers shall also possess any licenses required by local jurisdictions. C. Substitutions may be considered only when submitted in conformance with Section 16010. INSTALLERS A. System shall be installed under the direct-supervision of a qualified installer B. Substitutions may be considered only when submitted in conformance with Section 16010. INSTALLATION A. Wiring shall be installed in raceway and shall be arranged as indicated on the Drawings and the shop drawings. B. Any wiring and conduit arrangement shown on the drawings for the security alarm/access system is illustrative only in nature and shall not be construed as “an installation design” to be rigidly followed. The installing contractor is responsible to arrange conduit and wiring in accordance with the equipment manufacturer’s requirements, the general requirements of the building’s construction, and comply with all applicable electrical codes. All wire installed must be approved for burglar alarm and access control use under Article 760, of the National Electrical Code. C. Final connections between system equipment and the wiring system shall be made under the direct supervision of a representative of the Installer. No power shall be applied to the alarm equipment until all connections between the equipment and the wiring system have been approved and checked for grounds, shorts, opens or other wiring defects, by a representative of the equipment supplier. Lewiston Library Second Floor Remodel Project 16727-5 15025 3.04 D. The equipment subcontractor must provide a complete installation. They must perform final trim of all devices, test and program the entire system, and provide proper training on the system to the owner’s representatives. This shall include programming of the dialer to report to a UL listed Remote Station. E. Door contacts shall be flush mounted in doors and door frames. F. Motion detectors shall be installed on stainless steel device plates covering flush mounted outlet boxes. G. Keypads shall be surface mounted over flush mounted outlet boxes. OPERATION AND TESTING A. The installing contractor and equipment supplier shall be jointly responsible to assure that a complete functional test of all equipment is performed prior to the system operation being demonstrated to the Owner’s representative. B. Program control panel using building area descriptions provided by the Owner. C. Program digital communicator after installation and programming is complete. Demonstrate the operation of each alarm device and the digital communicator to the Owner. D. Two weeks after initial operation, reprogram control panel and digital communicator as directed by the Owner. END OF SECTION 16727 Lewiston Library Second Floor Remodel Project 16727-6 15025 SECTION 16751 – COMMUNICATIONS STRUCTURED CABLING PART 1 - GENERAL 1.01 1.02 1.03 RELATED DOCUMENTS A. All provisions of the contract including Division 01 apply to work specified in each section of this Division 16. B. See Sections: 16010, 16110, 16120, 16160, 16131, 16132, 16134, and 16147. DESCRIPTION OF WORK A. Furnish, install, test and place into satisfactory and successful operation all equipment, materials, devices, and necessary appurtenances to provide a complete ANSI/TIA/EIA, NECA/NEIS and ISO/IEC compliant communications CAT-6 Structured Cabling System (SCS) as hereinafter specified and/or shown on the Contract Documents. The system is intended to be capable of integrating voice, data, and video signals onto a common media, and shall be tested for and capable of Gigabit Ethernet operation as specified in IEEE 802.3z. B. Work shall include all materials, equipment and apparatus not specifically mentioned herein or noted on the plans but which are necessary to make a complete working ANSI/TIA/EIA and ISO/IEC compliant SCS. C. Provide all telecom racks, patch panels, patch cords, punch-down blocks, cabling, fiber optic cable, outlet boxes, pull boxes, plates and jacks. D. Provide testing of all terminated cables. E. Provide a fiber optic patch panel in basement MDF room and in the new IT closet on the second floor. Route a 12 strand fiber with SC connectors on each end. F. Provide all data outlet boxes, pull boxes, plates and jacks. Jacks shall be RJ-45 Category 6. G. Route a 25 pair Telecom Cable from the basement MDF room to the new IT closet on the second floor. Terminate on both ends on patch panels. H. Route a communications cable to each camera location. PREMISE WIRING CONTRACTOR QUALIFICATIONS A. Contractor shall be trained and certified by the Manufacturers to install, test, and maintain the SCS and be certified by the SCS Manufacturers to provide the SCS Manufacturers Warranties. B. Contractor shall employ a minimum of one Registered Communications Distribution Designer (RCDD) certified by and in current good standing with BICSI. The RCDD shall be a direct full time employee of the Contractor (i.e. an RCDD consultant/sub-contractor to the Contractor is not acceptable). Contractor shall continue to employ a minimum of one RCDD throughout the duration of the project. Lewiston Library Second Floor Remodel Project 16751-1 15025 1.04 C. Contractor shall have successfully completed no less than five similar projects (in terms of size and construction cost) under the Contractor’s current business name within the past three years. D. The Contractor shall be thoroughly knowledgeable in TIA/EIA 568 standards of Category 3, 5, and 6 installations. The requirements of these standards shall be met whether a particular item is specified or not. The specifications assume that the contractor shall provide all miscellaneous components, hardware, etc., in a manner compliant with these standards. REFERENCES A. General: 1. 2. 3. 4. B. Communications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 1.05 National Electrical Code (NEC) National Electrical Safety Code (NESC) Washington Industrial Safety and Health Act (WISHA) Occupational Safety and Health Act (OSHA) ANSI/TIA/EIA – 455: Fiber Optic Test Standards ANSI/TIA/EIA – 526: Optical Fiber Systems Test Procedures ANSI/TIA/EIA – 568-B Commercial Building Telecommunications Cabling Standard ANSI/EIA/TIA – 569:Commercial Building Standard for Telecommunication Pathways and Spaces ANSI/TIA/EIA – 606: The Administration Standard for the Telecommunications Infrastructure of Commercial Buildings ANSI/TIA/EIA – 607: Commercial Building Grounding and Bonding Requirements for Telecommunications ANSI/TIA/EIA – TSB67: Transmission Performance Specifications for Field Testing of Unshielded Twisted Pair Cabling Systems ANSI/TIA/EIA – TSB75: Additional Horizontal Cabling Practices for Open Offices NECA/FOA 301-1997: Standard for Installing Commercial Building Telecommunications Systems IEEE 802.3 (series): Local Area Network Ethernet Standard, including the IEEE 802.3z Gigabit Ethernet Standard ISO/IEC IS 11801: Generic Cabling for Customer Premises BICSI: BICSI Telecommunications Cabling Installation Manual BICSI: BICSI Telecommunications Distribution Methods Manual (TDMM) DEFINITIONS A. “SCS” shall mean Structured Cabling System. The SCS is defined as all required equipment and materials including (but not limited to) ANSI/TIA/EIA 568-B and ISO/IEC 11801 compliant copper station cable (Category 3, Category 5E, Category 6, etc.) and fiber optic cable (multimode and singlemode), patch cables, stations and staion connectors, termination blocks, patch panels, racks/enclosures (such as EIA standard equipment racks, enclosures, and vertical and horizontal cable management hardware), pathway/raceway materials (such as conduit, sleeves, D-rings, surface raceway, ladder rack, cable tray, etc.), and other incidental and miscellaneous equipment and materials as required for a fully operational, tested, certified, and warranted system, compliant with all applicable codes and standards. Lewiston Library Second Floor Remodel Project 16751-2 15025 1.06 B. “TMGB” shall mean Telecommunications Main Grounding Busbar. There is typically one TMGB per building, located in the main telecommunications room. This busbar is directly bonded to the electrical service ground. C. “TGB” shall mean Telecommunications Grounding Busbar. There is typically on TGB per telecommunications room. The TGB is connected both to the TMGB and to building structural steel or other permanent metallic systems. D. “TBB” shall mean Telecommunications Bonding Backbone. The TBB is a conductor used to connect TMGBs to TGBs. E. “UTP” shall mean Unshielded Twisted Pair Cable. SUBMITTAL INFORMATION A. Submit the following: 1. 2. 3. 4. 5. 6. B. 1.07 Product Detailed Specifications Product Data Sheets Manufacturer’s Instructions Product Catalog Literature Product (Shop) Drawings Third party performance verification certificates (upon request where applicable) Provide submittals on all Category 6 Cabling, Indoor/Outdoor Fiber Optic Cabling, copper patch panels, fiber patch panels, jacks, D-rings and J-hooks. WARRANTY A. Contractor Warranty 1. B. Provide a Contractor-endorsed two-year service warranty against defects in materials and workmanship. a. Provide al labor attributable to the fulfillment of this warranty at no additional cost to the Owner. 1) The Contractor warranty period shall commence upon Owner acceptance of the work. SCS Manufacturer Warranties: 1. 2. The SCS Manufacturer Warranties shall be provided by the selected SCS Manufacturers and shall be: a. 16-year System Warranty. 1) Provide a copy of the warranty registration document to the Owner at the time of submittal. b. 16-year System Warranty. 1) Provide a copy of the warranty registration document to the Owner at the time of submittal. The SCS Manufacturer Warranty period shall commence upon a Warranty Certificate being issued by the manufacturer. The Warranty Certificates shall be issued no later than three months after Owner acceptance of the work. Lewiston Library Second Floor Remodel Project 16751-3 15025 PART 2 - PRODUCTS 2.01 MATERIALS A. Provide CommScope, AVAYA, Systimax for copper-related products and fiber optic related products. Components shall not be intermixed between different manufacturers unless the manufacturer of the SCS has listed (in writing) another manufacturer’s component as an “Approved Alternative Product” and will warrant the “Approved Alternative Product” as part of the SCS Manufacturer Warranty (see PART 1 – WARRANTY). B. All copper-related components shall be part of the copper SCS product line and all fiber optic-related components shall be part of the fiber optic SCS product line – components shall not be intermixed between manufacturers’ SCS product lines. The SCS product lines shall be engineered “end-to-end” – the system and all components shall be engineered to function together as a single, continuous transmission path. 1. C. Racks, rack cable distribution hardware, and other rack and distribution components shall be manufactured by a single manufacturer unless stated otherwise in this Specification or in the Contract Documents. Do not intermix equipment and components between different manufacturers. 1. 2. D. 2.02 The SCS Product Line shall be the following, per manufacturer. a. For Category 6 Copper Distribution : CommScope, AVAYA, Systimax Racks/Distribution Equipment: Chatsworth Products, INC. (CPI) B-line Provide all incidental and/or miscellaneous hardware not explicitly specified or shown on the Contract Documents that is required for a fully operational, tested, certified, and warranted system. PATHWAYS AND CABLE SUPPORTS A. Raceways, boxes, etc., shall be provided under this contract. Conduits shall be metallic, and shall be of the size shown on the drawings. If not indicated, minimum 3/4”. See Sections 16110, 16134, and 16132, B. Sleeves: Provide sleeves where required for cable pass-thru. Provide core drilling where required for sleeve installation. Sleeves shall be EMT conduit and shall be provided with insulated throat bushings for each end. Sleeve sizing shall be as noted on the Drawings. Where not noted, sleeve sizing shall be determined by the type and quantity of cable to be routed through the sleeve per TIA/EIA 569 cable capacity standards, plus an additional 100% for future expansion. C. All backboards in the communications room shall be 3/4 inch A-C non-fire retardant plywood backboards, void free, 8 ft high. All Backboards shall be capable of supporting attached equipment, and painted with a minimum of two coats (over primer) of fire retardant, nonconductive paint, and one coat of white colored semi gloss top coat paint. Mount A-C plywood backboards with the “A” side exposed. D. D-Rings: 1. Metallic: CPI 10941, 10942, 10943 Lewiston Library Second Floor Remodel Project 16751-4 15025 E. Cable Supports (J-Hooks, Straps): Complete with incidental materials and assemblies required for mounting. 1. 2. F. Innerduct: 1. 2. G. 2.03 Pull Strings: Plastic or nylon with a minimum test rating of 200 lb. Firestopping material: Conform to both Flame (F) and Temperature (T) ratings as required by local building codes and as tested by nationally accepted test agencies per ASTM E814 or UL 1479 fire test in a configuration that is representative of the actual field conditions. Manufactured by: 1. Rack– free standing 1. Design and performance requirements a. Free standing communications racks shall be a floor-mounted formed/welded steel construction or aluminum channel construction, with powder coating. Racks shall be suitable for equipment rooms, telecommunications rooms, entrance facilities and data centers. b. Racks shall have a full assortment of vertical and horizontal cable management accessories available. c. Racks shall accommodate expansion of cable capacity and added volume for augmented category 6 cabling. GROUNDING AND BONDING A. 2.06 Specified Tech. Inc. (or approved equal). EQUIPMENT RACKS/ENCLOSURES A. 2.05 Indoor: 1 1/14” Outside Diameter, bright orange in color. Provide innerduct for fiber optic cables from termination points within buildings to outside conduit entrances. Innerduct installed in plenum rated ceilings shall be plenum rated. Outdoor: Innerduct shall be rated for outdoor duct installation. Innerduct shall be corrugated, bright orange, and installed in quantities and sizes as shown on the Drawings. Innerduct shall be provided in the following sizes. a. 1-1/2” Diameter b. 1” Diameter FIRESTOPPING A. 2.04 CADDY CableCat wide Base Cable Supports (J-Hooks): a. CAT12 (up to 16 4-pair/2-strand UTP/fiber cables) b. CAT21 (up to 50 4-pair/2-strand UTP/fiber cables) c. CAT32 (up to 80 4-pair/2-strand UTP/fiber cables) CADDY CableCat Adjustable Cable Supports (Straps): a. CAT425 (up to 425 4-pair/2-strand UTP/fiber cables) As specified under Division 16 Section – 16160 Grounding PATCH PANELS A. Rack Mounted Copper Patch Panel: 1. Category 6 component performance requirements. Lewiston Library Second Floor Remodel Project 16751-5 15025 2. 3. 2.07 CONNECTORS A. Copper Connectors (modular jacks): 8-position/8-conductor, insulation displacement connection (IDC), non-keyed, and shall accept modular 8-position/8-conductor plugs, complete with multicolored identification labels/icons for identification, and with universally color-coded wiring pattern for both T568A and T568B. Copper connectors shall be manufactured by the selected SCS Manufacturer. 1. 2.08 Copper Termination Blocks – For Outside Plant Copper Cabling 1. 2. Copper Termination Blocks: UL listed and exceed ANSI/TIA EIA 568-B Category 5e specifications for performance. Include connecting blocks, designation, strips, and labels for each 25-pair strip. Label colors per ANSI/TIA/EIA standards. Termination blocks shall be manufactured by the selected SCS Manufacturer. a. Cable - CommScope 1) Blocks: 110 Connect 2) IDC Connecting Blocks (5-pair markings) 3) Designation Strips 4) Labels (white) Copper Termination Blocks Cable Management: Vertical and horizontal cable management for jumper/patch cables between termination blocks shall consist of a single unit with separate horizontal and vertical pathways and shall be capable of mounting 110Connect wiring blocks. STATIONS A. Each communications outlet shall consist of the following components: 1. 2. 3. 2.10 Horizontal Distribution: Shall meet or exceed Category 6 transmission requirements for connecting hardware, as specified in ANSI/TIA/EIA 568-B and ISO/IEC 11801, and shall be part of the UL LAN Certification and Follow-up Program: a. Sistemax GIGASPEED XL CATEGORY 6 COPPER TERMINATION BLOCKS A. 2.09 Ports may be individually replaced. Wiring T568B. 4-port outlet Category 6 jacks shall be TIA/EIA, 568 B configuration, eight pin, non-keyed. Provide as indicated per outlet. Identification icons, labels, cable tape/markers, etc. as specified CABLE A. General: Cables shall be manufactured by the selected SCS Manufacturer. Lewiston Library Second Floor Remodel Project 16751-6 15025 B. Copper Cable: 1. 2. 2.11 For the Horizontal Distribution: 4-pair, UTP 24 AWG, with solid copper conductors and shall be part of the UL LAN Certification and Follow-up Program. a. Category 6: Shall exceed Category 6 transmission requirements as specified in ANSI/TIA/EIA 568-B and ISO/IEC 11801: 1) CommScope Plenum rated b. For Termination Block Connections (back-side): Unshielded, non-plenum multi-pair copper cable. c. Multi-pair Copper Cable: 24-AWG, solid copper conductor, and insulated with color coded PVC, UL Verified to ANSI/TIA/EIA 568-B for Category 6 performance. Cable shall be manufactured by the selected SCS Manufacturer: 1) CommScope or approved equal Provide Category 6 plenum rated cable continuous from each communication jack to the communications room and patch panel. When cable termination is made, label within 6" of jacket end using Panduit LS4H Heat Shrink Marking System or other approved heat shrink label products on both ends of each cable. Label jack faceplates using Brother P-Touch or Panduit LS4M or Panduit LS5 marking systems or approved equal for each modular jack port and with same equipment label. Completely label all patch panels with circuit identification numbers. In addition, the modular jacks at both patch panels and workstation shall be labeled with circuit identification numbers as described above. CABLE ASSEMBLIES (PATCH CORDS) AND CROSS-CONNECTS A. Velcro Cable Managers: Reusable (Velcro based) hook and loop style, adjustable tension, roll or spool dispensed. B. Copper Patch Cables: Pre-manufactured (factory-terminated), stranded unshielded twisted pair (UTP), with 8-pin modular plugs and/or termination block-style patch plugs. Patch cables shall be manufactured by the selected SCS Manufacturer. 1. Category 6: Shall exceed Category 6 Transmission as specified in ANSI/TIA/EIA 568-B and ISO/IEC 11801. Modular plugs shall be complete with snagless boots. C. Fiber Patch Cables: Pre-manufactured (factory-terminated) with a UL rating of OFNR. Fiber patch cables shall be manufactured by the selected SCS Manufacturer. D. Copper Jumper Wire: Category 6 (for cross connects): Lewiston Library Second Floor Remodel Project 16751-7 15025 2.12 LABELING AND ADMINISTRATION A. Labels: 1. As recommended in ANSI/TIA/EIA 606. Permanent (i.e. not subject to fading or erasure), permanently affixed, and created by a hand-carried label maker or a computer/software-based label making system. Handwritten labels are not acceptable. Labels for outside plant cables shall be permanently affixed on plastic tags. Labels shall be provided for all components of the cabling system including but not limited to, cables, splice enclosures, BETs, patch panels, and grounding/bonding cables. a. For station Cable: 1) Brady: Bradymaker Wire Marking Labels WML-511-292 (or approved equal) 2) Labels for outside plant cables shall be: a) Panduit Marker Tie (or approved equal). 3) Hand-carried label maker shall be Brady ID Pro Plus (or approved equal) PART 3 - EXECUTION 3.01 3.02 GENERAL A. All work shall comply with the standards, references and codes listed in Part 1 – REFERENCES above. Where questions arise regarding which standards, references, or codes apply, the more stringent shall prevail. B. All work shall comply with the requirements and recommendations of the product manufacturers. Where questions arise regarding which requirements and recommendations apply, the more stringent shall prevail. RACEWAY A. Backboards: Provide backboards as shown on Contract Documents. Backboards shall be capable of supporting attached equipment, and painted with a minimum of two coats (over primer) of fire retardant non-conductive paint, and one coat of white colored semi-gloss top coat paint. Mount A-C plywood backboards with the “a” side exposed. B. Sleeves: Provide sleeves where required for cable pass-thru through building structures and/or fire rated barriers. Provide roto-hammering or core drilling where required for sleeve installation. Seal (and if a fire rated barrier, firestop) between sleeve and building structure and/or barrier. Size sleeves: 1. Where not noted, size sleeves a minimum of 2 inches in diameter or by the type and quantity of cable to be routed through the sleeve per ANSI/TIA/EIA 569 cable capacity standards plus an additional 100% for future expansion – whichever is greater. Lewiston Library Second Floor Remodel Project 16751-8 15025 C. D-Rings: Provide D-Rings as necessary to route exposed cables in telecommunications rooms and on backboards and for raceway for routing cable in non-exposed open access environments. D-Rings may be affixed to wall/ceiling structures or other supports, but not attached to a ceiling support system. In telecommunication rooms, mount D-Rings at 12 inch intervals. Mound D-Rings used for raceway in open access environments at 4 foot intervals. 1. 3.03 D. Cable Supports (J-Hooks, Straps): Provide cable supports for routing cable in non-exposed open access environments. Cable supports may be affixed to wall/ceiling structures or other supports, but not attached to a ceiling support system. Mount cable supports at 4 foot intervals. Do not use cable supports for more cables than they were designed to support. Provide multiple cable supports where the total cable count exceeds the maximum cable count for which the support was designed. Size according to the type and quantity of cable to be routed through the ring per ANSI/TIA/EIA 569 cable capacity standards, plus an additional 50% for future expansion. E. Innerduct: Provide bright orange innerduct as a pathway for Fiber cabling. F. Pull Strings: Provide a pull string in new conduits that have new cable installed under this project. FIRESTOPPING A. Only employees trained/certified by the firestopping manufacturer shall apply firestopping materials. B. Maintain fire rating of penetrated fire barriers. Fire stop and seal penetrations made during construction. 1. 2. 3. 4. 5. 3.04 Size D-Rings according to the type and quantity of cable to be routed through the ring per TIA/EIA 569 cable capacity standards, plus an additional 100% for future expansion, but not less than a minimum of 2 inches in diameter. Provide firestopping material for through and membrane penetrations of fire-rated barriers. Install firestops in strict accordance with manufacturer’s detailed installation procedures. Install firestops in accordance with fire test reports, fire resistance requirements, acceptable sample installations, manufacturer’s recommendations, local fire and building authorities, and applicable codes and standards referenced in PART 1REFERENCES. Apply sealing material in a manner acceptable to the local fire and building authorities. For demolition work, apply firestopping to open penetrations in fire rated barriers where cable is removed. Apply firestopping regardless of whether or not the penetrations are used for new cable or left empty after construction is complete. Fire stopping material used to seal open penetrations through which cable passes shall be re-usable/re-enterable. EQUIPMENT RACKS/ENCLOSURES A. Provide EIA racks/cabinets and all associated hardware according to location, elevations, and plan views as shown in the Contract Documents. Lewiston Library Second Floor Remodel Project 16751-9 15025 3.05 GROUNDING AND BONDING A. Grounding and bonding work shall comply with the International Building Code, International Fire Code, WAC, National Electrical Code, and UL467, ANSI/TIA/EIA standards and references listed in PART 1- REFERENCES above, as well as local codes which may specify additional grounding and/or bonding requirements. 1. 2. 3.06 PATCH PANELS A. Provide patch panels and horizontal wire management according to locations, elevations, and plan views as shown on the Contract Documents and stated in the specifications. 1. 2. 3. 3.07 Fiber: Size and install rack-mountable patch panels as shown on the Contract Documents. Use fiber patch panels to terminate multimode fiber entrance cables. Copper: Size and install rack-mountable patch panels to terminate horizontal data cabling. Horizontal Wire Management: Provide horizontal wire management between patch panels. CONNECTORS A. Copper Connectors (modular jacks): 1. 3.08 Provide a minimum of one wall mountable telecommunications ground bus bar per telecommunications room. Grounding conductor shall be installed to bond all non-current carrying metal telecommunications equipment and materials to the nearest TMGB. a. Ensure that bonding breaks through paint to bare metallic surface of all painted metallic hardware, b. Provide ladder rack grounding kits to bond each section of ladder rack and bond ladder rack to tacks/cabinets where ladder racks are connected. Horizontal Distribution: a. Provide connectors and install using T568B wiring pattern. b. Mount connectors at 90-degrees (i.e. straight, not angled) c. Provide 10% spare blue connectors and 10% spare black connectors to Owner. COPPER TERMINATION BLOCKS A. Provide vertical and horizontal cable management for jumper/patch cables between termination blocks. Provide termination blocks and (jumper troughs) with legs: 1. 2. 3. Mounting on Backboards: Provide termination blocks, jumper troughs, and distribution rings with legs. Use jumper troughs above and below each termination block in a column. Route Entrance cable horizontally along base of backboard until it reaches the termination block column on which it is to terminate and then route vertically to the termination block. Punch down cable using only the selected SCS Manufacturer approved impact tool. Lewiston Library Second Floor Remodel Project 16751-10 15025 3.09 STATIONS A. Faceplates: Provide faceplates for stations in the locations and gang counts shown on the Contract Documents. Faceplates shall completely conceal outlet boxes, reducer plates, etc. Faceplates shall provide a snug and sure fit for connectors – loose connectors are not acceptable. 1. 3.10 Flush-mount connectors on faceplates. a. Unless otherwise noted in the Contract Documents, mount voice connector in top port location (blue jack), middle port location shall be blank, mount data connector in bottom port location (black jack). CABLE A. General: Provide plenum rated cable for all locations. 1. 2. 3. 4. 5. 6. 7. For Horizontal Distribution: Provide station cables in types, sizes, and quantities as defined by the Symbol Schedule and as shown on the Contract Documents. Install cable between station and the telecommunications room. Provide one cable per each connector at the station. Provide cables of the same type in the same color – multiple colors of the same cable type are not acceptable. Install cable in compliance with ANSI/TIA/EIA and ISO/IEC 11801 requirements and BICSI TCIM practices. Adhere to the bending radius and pull strength requirements as detailed in the ANSI/TIA/EIA standards and the manufacturer’s installation recommendations during cable handling and installation. a. Pull all cables simultaneously where more than one cable is being installed in the same raceway. b. Use pulling compound or lubricant where necessary. Use compounds that will not damage conductor or insulation (Polywater, or approved equal). c. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips that will not damage media or raceway. Repair or replace conduit bushings that become damaged during cabling installation. Install cable in a continuous (non-spliced) manner unless otherwise indicated. Install exposed cable parallel to and perpendicular to surfaces on exposed structural members and follow surface contours where possible. Tie or clamp cabling. Attaching cables to pipes, electrical conduit, mechanical items, existing cables, or the ceiling support system (grids, hanger wires, etc – with the exception of ceiling support anchors) is not acceptable. Install tie-wraps in conformance with the SCS manufacturer’s installation recommendations. Do not over-tighten tie wraps or cause cross-sectional deformation of cabling. Cabling at the backboards: a. Lay and dress cables to allow other cables to enter raceway (conduit or otherwise) without difficulty at a later time by maintaining a working distance from these openings. b. Route cable as close as possible to the ceiling floor, sides, or corners to insure that adequate wall or backboard space is available for current and future equipment and for cable terminations. Lewiston Library Second Floor Remodel Project 16751-11 15025 c. 8. 9. B. Copper Cable: Terminate all pairs within a cable. Un-terminated cable pairs are not acceptable. 1. C. 2. 3. 3.12 For horizontal distribution: Provide station cable in the locations shown on the Contract Documents. Provide service loops with a minimum length of 12 inches in outlet boxes and no less than 10 feet in the telecommunication room. a. Route station cable that is exposed (not in conduit) to comply with ANSI/TIA/EIA-569 rules for avoiding potential EMI sources. Fiber Cable: Terminate all fiber strands with a fiber cable. The installation of “dark fiber” is not acceptable. 1. 3.11 Lay cable via the shortest route directly to the nearest edge of the backboard from mounted equipment or blocks. Support cables so as not to create a load on the equipment upon which the cables are terminated. Tie-wrap similarly routed and similar cables together and attach to D-Rings vertically and/or horizontally, then route over a path that will offer minimum obstruction to future installations of equipment, backboards or other cables. Cable in the telecommunications rooms: a. For telecommunications rooms with ladder rack, lay cable neatly in ladder rack in even bundles and loosely secure cabling to the ladder rack at regular intervals with tie-wraps or Velcro straps. Cable terminating on patch panels located on racks: a. Route cables in telecommunications rooms to patch panels on racks by routing across ladder rack across top of rack and then down vertical ladder rack to patch panel. Test fiber optic cable on the reel upon delivery to the job site, and again prior to installation. Permanently affix the test results to the reel and submit a copy to the Owner prior to installation. Do not install cables that fail the on-reel test. Replace any cables that fail the on-reel test at no additional expense to the Owner. For shielded cable, bond both ends of the metallic shield member to the nearest TGB. Provide a 10 foot service loop at each termination point. CABLE ASSEMBLIES (PATCH CORDS) AND CROSS-CONNECTS A. Furnish copper patch cables for modular copper cross-connects. B. Furnish fiber patch cables for fiber cross connects. LABELING AND ADMINISTRATION A. General: Labeling and administration shall comply with AMSI/TIA/EIA 606 and standard industry practices. Lewiston Library Second Floor Remodel Project 16751-12 15025 B. Color Coding: Apply industry standard color coding to cable termination fields. Always apply the same color at both ends of any given cable. Cross-connections are generally made between termination fields of different colors. The color may be applied to the backboard behind the termination equipment, may be the color of a cover on the termination equipment, or may be the actual color of the insert label on the termination equipment Use the following color code: 1. 2. 3. 4. 5. 6. 7. 8. C. Telecommunications Rooms: Affix a permanent label to the door of each telecommunications room. Where telecommunications room names are required in other labels, use the telecommunications room name shown on the Contract Documents. D. Racks: Affix label centered across top cross-member of rack. E. Grounding/Bonding Conductors: Label bonding conductors: “WARNING! TELECOMMUNICATIONS BONDING CONDUCTOR. DO NOT REMOVE OR DISCONNECT!” F. Cables: 1. 2. 3. 3.13 Orange: Identification of the telecommunication service (telephone company) demarcation point. Green: Identification of network connections on the customer side of the demarcation point. White: Identification of first-level backbone in the building containing the main cross-connect, or may be used to identify the second-level backbone in the buildings not containing the main cross-connect. Gray: Identification of the second-level backbone in the building containing the main cross-connect. Blue: Identification of the horizontal distribution (station) cables. A blue color coding is only required at the telecommunications room end of the cable no at the station end of the cable. Brown: Identification of inter-building backbone cables. Yellow: Identification of auxiliary circuits, alarms, maintenance, security, and other miscellaneous circuits. Red: Identification of key telephone systems. Label location: Affix at each end of the cable. Station cables: Label station cables with the same label as the station connector that terminates the cable at the station location. Include a clear vinyl adhesive wrapping applied over the label in order to permanently affix the label to the cable. Using transparent tape to affix labels to cables is not acceptable. Provide labels at each end of each cable within 24” of telecommunications room entrance and again within 24” of termination point. INSTALLATION A. All cables shall be run through walls in conduit stub-ups of 3/4 inch from each outlet location to a 90 degree sweep in suspended ceiling area. Provide bushings on all conduits to protect cables. Cables shall be run in free air through suspended ceiling areas above tile grid routed in bridal D-rings. Lewiston Library Second Floor Remodel Project 16751-13 15025 B. LAN and other system cables above ceilings shall be supported from the building structure. Cables shall be loosely bundled (where grouped) and supported as required to prevent sharp bends or kinking. Support shall be adequate for the cable weight. Utilize wall or ceiling suspended J- hooks and or D-rings. Cable supports shall be as required by standard industry practice and building conditions. C. Communication cables shall be separated from other systems cables to minimize cross talk interference. Communication cables in cable tray are to be installed in one side of the divided cable tray and not mixed in with other systems wiring. D. Systems cables shall not be attached to power conduits. Cables running parallel to power conduits shall have a minimum separation of 6 inches. E. Minimum separation from fluorescent light fixtures is to be 12". Minimum separation from motors or transformers is to be 40". F. Bond all systems stub-ups and raceways per NEC requirements. G. Sleeves are to be provided in fire walls above ceilings to provide paths wherever cables are being routed. At fire walls provide 2" rigid steel conduit threaded nipples with bushings (both sides) or EMT fitted with threaded, nylon throated end connectors. Provide fire seal as necessary wherever passage through any type of fire wall is required. Unused sleeves are to be provided with metal end caps on both sides. H. The data (communication) system CAT5 enhanced shall be installed in a star topology. A dedicated cable shall run between each jack and the patch panel in the communications room. The maximum length of each cable shall not exceed 295' (90 meters). Route cables between jack and patch panel using the shortest distance possible. Each cable shall be terminated on CAT5 enhanced patch panel 568B with 110 punchdowns to RJ45 nonkeyed ports. I. All cables must be terminated using a compression connection tool. An additional eight feet of cable shall be left on or near the network backboards for future cable re-termination. An additional 18" to 24" of each cable shall be left at or near each outlet box/jack for future cable re-termination. No microbends shall be permitted less than 2" bend radius for the entire cable run. Cable runs must be continuous full length - no splices are allowed between patch panel and work station jacks. J. All communication cables shall be installed using Category 5 enhanced standards as follows: Wire pair twists must be maintained to within 1/2" of IDC contacts on each jack, jacketing must be undamaged for the full length of the cable run and must continue to within two inches of IDC contacts on each jack, each end of each cable must be secured to the jack module with a plastic cable tie. All plastic cable ties must be trimmed with a flush-cut tool to ensure that no sharp edges result. Any cables damaged during pulling shall be the responsibility of the cable installer. Any failing tests (see above) shall be re-terminated, rerouted, re-tested, etc., until no further alternatives exist, at which time it will be assumed that a bad cable run (too much twisting of the cable, compression of jacketing and wire pairs, etc.) has resulted (at the discretion of the LAN tester) and the pulling party/parties will have to bear the responsibility of re-pulling new cable to replace it. Lewiston Library Second Floor Remodel Project 16751-14 15025 K. Documentation: The vendor shall provide each of the following to the Owner at the system demonstration: 1. 2. 3. 4. 3.14 Final Record Drawings: Provide As-Built network drawings and/or diagrams indicating the cabling distribution system from outlet faceplate to distribution frame (patch panel), for each and every drop. These drawings and/or diagrams are to be included in the As-Built drawings, or the O&M manuals and hub binders. They shall be draft quality. Markups, hand drawings, etc., will be rejected. Materials and components listing for each item. Manufacture, part number and distributor. Include in O&M manuals. Patching Map: Provide a drafted illustration of each patch panel which shows device and cable identification connected to each port position. Hub Reference Binders: For each hub, provide a three-ring binder which includes the test reports, patching map, network diagrams and/or reduced size drawings for the backbone and portion of the networking system served by that hub. TESTING A. Provide test records on a form approved by the Owner and Engineer/Designer. Include the test results for each cable in the system. Submit the test results for each cable tested with identification as discussed under LABELING and ADMINISTRATION above. Include the cable identifier, outcome of test, indication of errors found, cable length, retest results, and name and signature of technician completing the tests. Provide test results to the Owner and Engineer/Designer for review and acceptance within two weeks of Substantial Completion. 1. B. Print test records for each cable within the system directly from the tester and submit in paper form (in a binder) and in electronic form (on CDROM) to the Owner and Engineer/Designer for review. Handwritten results will not be accepted. Test the SCS after installation for compliance to all applicable standards as follows: 1. Copper: a. For Horizontal Distribution: Test all pairs of each copper station cable, for conformance to ANSI/TIA/EIA 568-B Category 5E, and ANSI/TIA/EIA 568-B standards. To the extent possible, perform tests with building electrical system fully powered on (i.e. Lights, HVAC, etc). 1) Test each end-to-end link (the entire channel from the connector at the station to the connector or termination in the telecommunications room) utilizing sweep tests, for continuity, shorts, polarity, near-end cross talk (NEXT), far-end cross talk (FEXT), attenuation, installed length, transposition (wire map), mutual capacitance, characteristic impedance, resistance, ACR, and presence of AC voltage. Use the Power Sum method to test NEXT and FEXT. Test each cable in both directions. 2) Use a TIA/EIA Level III testing instrument, re-calibrated within the manufacturer’s recommended calibration period, with the most current software revision based upon the most current ANSI/TIA/EIA testing guidelines, capable of storing and printing test records for each cable within the system and equipped with the current Category 5e test adapters. Lewiston Library Second Floor Remodel Project 16751-15 15025 3) In addition to the above, perform tests both recommended and mandated by AMP. Tests shall confirm/guarantee compliance to AMP Ethernet Category 5e applications based on the data contained in the AMP Performance Specifications. Volume 1, May 2001 or latest edition. C. Cables and equipment which do not pass shall be identified to the Owner and Engineer. The source of the non-compliance shall be determined, replaced or corrected and the cable or equipment re-tested at no additional expense to the Owner. Provide new test results to the Owner and Engineer on the same form as above. LABELING D. Identification and labeling shall follow the guidelines of ANSI/TIA/EIA-606-A. Mandatory minimum labeling shall include pathways, TR’s, ER’s, EF’s, cable ends behind panels and wall outlets, wall outlet ports, patch panels and ports, fire stops, and grounding/bonding locations. E. Labels shall be permanent, with machine-generated identification codes according to specification. Tape with hand-written identifiers is prohibited. END OF SECTION 16751 Lewiston Library Second Floor Remodel Project 16751-16 15025