pg46/47-GB 14-07-1999 9:31 Pagina 1 AIR COOLED LIQUID CHILLERS “FREE-COOLING” VERSION WRAT/FC 0502 - 2404 MODELS UNIT DESCRIPTION This series of air cooled liquid chillers is equipped with FC coils, and is for use in civil and industrial plants whenever the need for cooling continues throughout the cold months, or when the ambient air temperature is lower than the return liquid temperature from the plant. During the “free-cooling” operation, the fluid is cooled by means of the external air, thus reducing the load on the compressors or even completely substituting them. The necessary cooling capacity is therefore obtained with almost zero energy expenditure (FREE-COOLING 100 % = EER 25). WRAT/FC VERSIONS STANDARD UNIT COMPOSITION – Base of galvanized hot-painted sheet steel. – Outer casing made of paraluman and frame of aluminium structural sections. – From 2 to 4 semi-hermetic reciprocating compressors. – Silencers on the compressor discharge lines. – Condensing and FREE-COOLING coil with copper tubes and aluminium fins, complete with subcooling circuit. – FREE-COOLING three way valves and related water connections. – Liquid receiver complete with flooding valves for head pressure control. – Axial fans with six-pole motors and die-cast aluminium blades, with IP54 protection ratio. – Thermally insulated evaporator, with asymmetric refrigerant paths. – Thermostatic expansion valves. Dryer filters. Sight glasses. Solenoid valves on the liquid line. – Electrical power and control panel complying with EN 60204-1/IEC 204-1 standards. – Microprocessor control system. – Freeze-proof oil charge and refrigerant charge. – Interlock door mains isolator. – General testing and operational test carried out in the factory in accordance with European Standard EN 12055. This range of units features cooling only. B LN SL Standard unit. Unit with reduced noise. Super low noise units. A 320 CV / 06 - 99 GB pg46/47-GB 14-07-1999 9:31 Pagina 2 GENERAL TECHNICAL DATA MODELS WRAT/FC Cooling capacity ➀ Compressor power input ➀ E.E.R. ➀ WRAT/FC FREE-COOLING “ON” Total Free-cooling capacity ➁ Absorbed power ➁ E.E.R. ➁ Total Free-cooling temperature ➁ OPERATING WEIGHT WRAT/FC - B DIMENSIONS 0502 0602 0702 0802 0822 1002 1202 1402 1602 1604 1804 2004 2204 2404 kW 117 kW 35 2.9 132 43 2.8 160 56 2.7 186 68 2.6 211 69 2.8 232 82 2.6 267 98 2.7 293 96 2.8 343 118 2.7 382 138 2.5 418 150 2.5 447 165 2.5 496 182 2.5 552 202 2.8 kW 117 kW 5.6 21 °C 0 132 5.6 23.6 -1 160 5.6 28.6 -1 186 5.6 33.2 - 2.3 211 8.4 25.1 -2 232 8.4 27.6 -1 267 11.2 23.8 - 1.5 293 11.8 24.8 -1 343 14 24.5 - 1.6 382 16.8 22.7 -1 418 21 20 -1 447 21 21.3 - 1.6 496 21 23.6 - 2.5 552 21 26.3 -4 Kg. 1920 1960 2160 2330 2420 2920 3050 3630 3750 5190 5440 5600 5740 6170 A ➂ mm 4110 4110 4110 4110 4110 5110 5110 6110 6110 6240 6240 6240 6240 6240 B ➂ mm 2220 2220 2220 2220 2220 2220 2220 2220 2220 2310 2310 2310 2310 2310 H mm 1540 1540 1990 1990 1990 1990 1990 1990 1990 2235 2235 2235 2235 2235 H H B A WRAT/FC 0502 - 1602 A B ➀ Data referred to: Chilled water Condensing air Glycol ➁ Data referred to: Chilled water Glycol ➂ Free areas required: Condensing coil side minimum Electrical panel side Opposite side to electrical panel 12/7 °C 35 °C 30 % 12/7 °C 30 % 2000 mm 1500 mm 1500 mm WRAT/FC 1604 - 2404 MAIN FUNCTIONS OF THE CVM CONTROLS Voltage and frequency supply control Missing external consens led signal Remote on/off by external volt-free contact Cumulative fault warning alarm Evaporator inlet/outlet water temperature display Free cooling coils and external air temperature display Compressor/circuit failure signal Unit general-alarm signal Print-out of the temperature and pressure values (if any) Configuration parameters print-out Historical alarms and events memory and print-out Propor. regulating algorithm on the inlet water temp. Proportional+Integral regulating algorithm Compressors start sequence at unit start-up Real-time internal clock Programmable timer function Double-set mode connected to programmable timer Delayed compressor start Compressor start per hour and restarting time control 300 • • Opt. • • • • • • • 200 • Par. Par. – – – • • 3000 • • • • • • • • • • 200 • Par. Par. • Par. Par. • • 3000 • • • • • • • • Par. Par. Opt. Par. • 300 • • • • • • • • Par. – – – • Compressor working-hours control and display Compressor working hours balance system Part-winding compressor start Pump-down when stopped Pump-down on starting Fan speed control Led display of interface board correct operation Auto-diagnostic of the electrical part CVM-Interface connection Supervisoring software connection Landis Staefa comunication gateway Johnson Controls comunication gateway Comunication protocol WRAT/FC 0502 - 1602 with CVM 300 WRAT/FC 1604 - 2404 with CVM 3000 standard •: –: not available Opt: available upon request Par.: available modifying a value of the configuration parameters Fläkt Woods AS tlf. 63 81 14 00 Lillestrøm Stavanger Bergen Trondheim Tromsø