XEB-26-CFZ - Barron Lighting Group

advertisement
XEB-26-CFZ
SERIES D
QUAD TUBE
FLUORESCENT EMERGENCY BALLAST
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnecting the unit connector.
3. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4. DO NOT USE OUTDOORS. The XEB-26-CFZ is for use with grounded, UL Listed, indoor fixtures. Not for use
in heated air outlets or hazardous locations.
5. The XEB-26-CFZ requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6. Do not mount near gas or electric heaters.
7. The XEB-26-CFZ should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
8. The XEB-26-CFZ is designed to cold strike and operate one 18W–26W, quad tube compact fluorescent lamp,
two-pin base including integral starter, with a single lampholder per lamp.
9. The XEB-26-CFZ is for use in fluorescent downlight fixtures.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this equipment for other than intended use.
12. Install in accordance with the National Electrical Code and local regulations.
13. Installation and servicing should be performed by qualified personnel.
14. Lighting fixture manufacturers, electricians, and end users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
THIS UNIT CONTAINS A
RECHARGEABLE NICKELCADMIUM BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
XEB-26-CFZ unit connector is disconnected.
1. MOUNTING THE XEB-26-CFZ
Mount the XEB-26-CFZ in the ballast channel or enclosed wireway so the wire leads are not exposed, at least 1/2″
away from the A.C. ballast(s). Refer to illustrations 1 and 2.
When battery packs are remote mounted, the remote distance can not exceed 1/2 of the distance from ballast to
lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no
more than 25′ remote distance, then the battery pack should not exceed 121/2′. Under no circumstances should
the battery pack exceed a distance of 50′ from the lamp.
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s), ballast and XEB-26-CFZ.
Install in accordance with the National Electrical Code and local regulations. For additional wiring diagrams not
shown, consult Customer Service.
3. INSTALLING THE CHARGE INDICATOR
Downlight Fixture– Select a convenient location on the fixture so that the Charge Indicator can be seen after installation. Allow for proper clearance and drill or punch a 1/2″ mounting hole. Disconnect the leads from the Charge
Indicator. Push the Charge Indicator into the 1/2″ hole until it is firmly locked into place. Reconnect the leads,
observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Make certain all leads are
enclosed in an appropriate wireway. Refer to Illustrations 1 and 2.
4. INSTALLING THE TEST SWITCH
Downlight Fixture– The test switch should be mounted on the fixture to allow access to authorized personnel. Drill
or punch a 1/2″ mounting hole. Make certain all leads are enclosed in an appropriate wireway. Refer to Illustration 1.
Illustration 1
Illustration 2
Downlight Fixture
Charge Indicator
+R
ED
XEB-26-CFZ
WHITE/RED
LEAD
+ RED
LEAD
OBSERVE PROPER POLARITY
NOTE: Position the Charge Indicator so that
it can be seen after installation.
Page 2
5. LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for
lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.
6. COMPLETING INSTALLATION
A.When the wiring is complete, the A.C. power is to be turned on permanently, join the unit connector.
B. Replace the ballast cover, fixture lens and other fixture hardware.
C. Refer to the “Operation” section below for proper operation.
OPERATION
General­—The XEB-26-CFZ is a compact fluorescent emergency ballast. The XEB-26-CFZ is to be used with U.L.
Listed fluorescent fixtures. When used with fluorescent downlight fixtures, the XEB-26-CFZ will wire in conjunction with
the existing lamp(s) to provide the emergency function.
Normal Mode – A.C. power is present. The A.C. ballast(s) operate the fluorescent lamp(s) as intended. The
XEB-26-CFZ is in the standby charging mode. The Charge Indicator will be lit providing a visual indication that
the battery is being charged.
Emergency Mode – The A.C. power fails. The XEB-26-CFZ senses the A.C. power failure and automatically switches
to the Emergency Mode. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power
is restored, the XEB-26-CFZ switches the system back to the Normal Mode and resumes battery charging. See page 1
of the Instruction Manual.
TESTING & MAINTENANCE
Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour
charge before conducting a one hour test.
The XEB-26-CFZ is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life
Safety Code, outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. One lamp should operate at reduced output.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 11/2 hour discharge test. The unit should
operate as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service for current warranty information.
Page 3
TYPICAL WIRING DIAGRAMS
For use with 2 pin, 26 watt lamps with integral starter only
1. ONE LAMP MAGNETIC BALLAST
�
TEST
SWITCH
COMMON
BLACK
SWITCHED OR
UNSWITCHED
LINE
XEB-26-CFZ
SERIES D
BLUE/WHT
WHT/BLK
YEL/BLK
WHT/BLK
*AC/EMERGENCY LAMP
I
CHARGE
INDICATOR
BLACK
SWITCHED OR
UNSWITCHED
LINE
�
UNIT
CONNECTOR
COMMON
WHITE
BLACK
SWITCHED OR
UNSWITCHED
LINE
RED
BLUE
RED OR
RED/BLK (+)
WHITE
WHT/BLK
BLACK
SWITCHED OR
UNSWITCHED
LINE
�
�
TEST
SWITCH
COMMON
CHARGE
INDICATOR
FIXTURE
GROUND
YEL/BLK
�
�
WHT/RED
WHT/BLK
�
�
YEL/BLK
WHT/BLK
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
A.C.
BALLAST WHITE
BLUE
LAMP
WHT
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
YEL/BLK
WHT/BLK
�
�
�
A.C.
BLACK BALLAST
SWITCHED OR
UNSWITCHED
LINE
XEB-26-CFZ
SERIES D
BLUE
LAMP
BLUE
RED OR
RED/BLK (+)
YEL/BLK
WHT/BLK
RED
�
*AC/EMERGENCY LAMP
�
COMMON
BLUE
A.C.
BLACK BALLAST WHT
LAMP
LAMP
RED OR
RED/BLK (+)
CHARGE
INDICATOR
FIXTURE
GROUND
WHT/BLK
*AC/EMERGENCY LAMP
�
WHT/RED
YEL/BLK
�
�
*AC/EMERGENCY LAMP
OL M S
WHT/BLK
�
�
�
�
*LAMP
SHG
PO E
A
A
�
UNIT
CONNECTOR
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
IC B L A
BLK (120V)
�
UNIT
CONNECTOR
COMMON
WHITE
BLACK
SWITCHED OR
UNSWITCHED
LINE
TEST
SWITCH
�
ORG (277V)
WHITE
A.C.
BALLAST BLUE
BLUE
LAMP
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
YEL/BLK
WHT/BLK
*LAMP
�
�
�
CHARGE
INDICATOR
FIXTURE
GROUND
WHT/BLK
RED
Page 4
RED OR
�
RED/BLK (+)
WHT/RED
YELLOW
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
XEB-26-CFZ
SERIES D
BLUE/WHT
*AC/EMERGENCY LAMP
Rev. 031306
00000-000
CHARGE
INDICATOR
FIXTURE
GROUND
8. TWO LAMP SERIES HIGH POWER FACTOR MAGNETIC BALLAST
YELLOW
*LAMP
WHT/BLK
WHT/BLK
BLUE
�
WHT/RED
YEL/BLK
UNSWITCHED LINE
BLUE/WHT
SWITCHED OR
UNSWITCHED
LINE
RED OR
RED/BLK (+)
YELLOW
BLUE
ORG (277V)
BLUE
XEB-26-CFZ
SERIES D
SWITCHED OR
UNSWITCHED
LINE
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
XEB-26-CFZ
SERIES D
ORG (277V)
BLUE/WHT
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
WHITE
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
WHITE
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
BLK (120V)
�
TEST
SWITCH
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
UNIT
CONNECTOR
7. TWO LAMP SERIES MAGNETIC BALLAST
UNSWITCHED LINE
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
WHITE
A.C.
BLACK BALLAST BLUE
FIXTURE
GROUND
WHT/BLK
�
�
CHARGE
INDICATOR
�
TEST
SWITCH
COMMON
�
WHT/RED
YELLOW
*LAMP
�
UNIT
CONNECTOR
BLK (120V)
UNSWITCHED LINE
BLUE/WHT
FIXTURE
GROUND
WHT/BLK
*LAMP
CHARGE
INDICATOR
6. TWO LAMP PARALLEL HIGH POWER FACTOR MAGNETIC BALLAST
ORG (277V)
WHITE
RED OR
�
RED/BLK (+)
WHT/RED
YELLOW
BLACK
BLK (120V)
TEST
SWITCH
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
XEB-26-CFZ
SERIES D
BLUE/WHT
BLACK
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
LAMP PAR L EL M GNETIC BA AST
5. TWO
LAMP PARALLEL MAGNETIC BALLAST
COMMON
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
WHITE
UNIT
CONNECTOR
W
�
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
ORG (277V)
*AC/EMERGENCY LAMP
UNSWITCHED LINE
�
UNIT
CONNECTOR
BLK (120V)
UNSWITCHED LINE
XEB-26-CFZ
SERIES D
CHARGE
INDICATOR
FIXTURE
GROUND
WHT/BLK
�
�
�
4. TWO LAMP ELECTRONIC BALLAST
YELLOW
*LAMP
BLUE
RED OR
RED/BLK (+)
WHT/RED
YELLOW
�
ORG (277V)
BLUE/WHT
A.C.
BALLAST BLUE
A.C.
BLUE
BALLAST
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
WHITE
XEB-26-CFZ
SERIES D
BLUE/WHT
*LAMP
BLK (120V)
�
WHITE
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
BAL A T
TEST
SWITCH
ORG (277V)
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
3. ONE LAMP ELECTRONIC BALLAST
UNSWITCHED LINE
�
TEST
SWITCH
COMMON
WHITE
FIXTURE
GROUND
BLUE
�
�
�
WHT/RED
YELLOW
�
E
RED OR
RED/BLK (+)
WHITE
A.C.
BLUE
BALLAST
BLK (120V)
UNSWITCHED LINE
ORG (277V)
*LAMP
LA
2. ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST
BLK (120V)
UNSWITCHED LINE
�
UNIT
CONNECTOR
SELECT PROPER VOLTAGE LEAD CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A C POWER IS SUPPLIED
TEST ACCESSORY LEADS REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING
TYPICAL WIRING DIAGRAMS
For use with 2 pin, 18 through 26 watt lamps with integral starter only.
9. TWO NORMAL POWER FACTOR MAGNETIC BALLASTS
BLK (120V)
UNSWITCHED LINE
COMMON
SWITCHED OR
UNSWITCHED
LINE
�
TEST
SWITCH
ORG (277V)
XEB-26-CFZ
SERIES D
WHITE
BLUE/WHT
A.C.
BLACK BALLAST BLUE
A.C.
BALLAST BLUE
#2
LAMP
�
�
*LAMP
�
CHARGE
INDICATOR
FIXTURE
GROUND
WHT/BLK
YELLOW
YEL/BLK
BLACK
WHT/RED
WHT/BLK
BLUE
#1
RED OR
�
RED/BLK (+)
�
UNIT
CONNECTOR
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
10. TWO HIGH POWER FACTOR MAGNETIC BALLASTS
BLK (120V)
UNSWITCHED LINE
TEST
SWITCH
COMMON
SWITCHED OR
UNSWITCHED
LINE
WHITE
�
ORG (277V)
WHITE
XEB-26-CFZ
SERIES D
BLUE/WHT
A.C.
BLACK BALLAST BLUE
BLACK
A.C.
BALLAST BLUE
#2
LAMP
*LAMP
�
�
�
Rev. 031306
00000-000
CHARGE
INDICATOR
FIXTURE
GROUND
WHT/BLK
YELLOW
YEL/BLK
WHITE
WHT/RED
WHT/BLK
BLUE
#1
RED OR
�
RED/BLK (+)
�
UNIT
CONNECTOR
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.