COMMERCIAL RECESSED COMPACT FLUORESCENT
INSTALLATION INSTRUCTIONS - INTERNAL EMERGENCY
IMPORTANT SAFEGUARDS
Vertical Lamp Fixture
Test Switch / Indicator Light
When using electrical equipment, basic safety precautions
should always be followed, including the following:
Read and follow All Safety Instructions
1
This is a recessed ceiling mounted compact fluorescent unit, with
standby battery operation. In the normal mode, lamp will be
illuminated. In the emergency mode, one lamp will provide
emergency illumination for a minimum of 90 minutes in
accordance with UL standard #924.
2
Installing - To prevent electrical shock and unintentional battery
discharge, do not join the unit connector until the installation is
complete. Immediately prior to permanently turning the AC power
on, engage the connector within the single gang switch box.
3
The emergency source requires an unswitched AC power source
of either 120 or 277 volts. Properly cap the unused AC lead. refer
to wiring diagram.
4
This unit is for recessed mounting only. Do not use outdoors, in
hazardous locations, nor near gas or electric heaters. When used
in insulated ceilings, insulation must be kept off the unit and no
closer than 3" from the unit on all sides.
5
Do not use this equipment for other than the intended use.
6
Install only in accordance with National Electrical Code and local
regulatory agencies' requirements
7
Installation and servicing to be performed only by qualified
personnel
8
Servicing - This fixture provides more than one power supply
output source. To reduce the risk of electrical shock, disconnect
both normal and emergency sources by turning off the AC branch
circuit and by disconnecting the connector on the charge
indicator/test switch assembly.
9
To remove the trim push the test switch in, turn anti-clockwise
and pull trim out of the housing.
See View A
View A
Save These Instructions
BLK (120V)
HOT UNSWITCHED LINE
(CAP UNUSED LEAD)
ORG (277V)
BLUE
#2
YELLOW
#1
FLEX B
YELLOW
#1
YELLOW
#2
GRN
#3
RED / WHITE
RED
BLUE
YELLOW
BLK
RED (+)
WHT/RED (-)
BLUE
YELLOW
YELLOW
WHT
RED
BLUE
WHT/RED (-)
COMMON
SWITCHED OR
UNSWITCHED
LINE
BLUE / WHITE
YELLOW
#3
BALLAST
SWITCHED OR
BLK
UNSWITCHED
LINE
GRN
BLUE / WHITE
RED (+)
WHITE / BLACK
#4
BALLAST
#4
WHT
FLEX B
WHITE / BLACK
FLEX A
WHT/BLK
WHT/BLK
DO NOT MATE CONNECTOR
TO BE MATED BY CUSTOMER
AFTER AC POWER IS SUPPLIED
WHT/BLK
WHT/BLK
DO NOT MATE CONNECTOR
TO BE MATED BY CUSTOMER
AFTER AC POWER IS SUPPLIED
FLEX A
VIOLET
TO TEST SWITCH
SEE CHART A
EMERGENCY MODULE
WHITE COMMON
VIOLET
COMMON
VIOLET
ORG (277V)
TO TEST SWITCH
SEE CHART A
BLK (120V)
EMERGENCY MODULE
WHITE COMMON
VIOLET
HOT UNSWITCHED LINE
(CAP UNUSED LEAD)
RED / WHITE
RED
BLUE
BLUE
YELLOW
RED
YELLOW
RED
BALLAST WIRE COLOR TABLE
WIRE #
#1, #2
#3, #4
CHART A
ESI
BALLAST
NON-ESI
BALLAST
LAMP
VIOLET LEADS
BLUE
RED
RED
BLUE
10-32W
42W
CONNECTED
DISCONNECTED
Cooper Lighting • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • 770.486.4800 • FAX 770.486.4801