Instruction Sheet

advertisement
IP Series
IP Series
Sealed Flourescent Luminaire Selfpowered Addendum
IMPORTANT SAFEGARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Caution: To prevent electrical shock, DO NOT mate ballast connectors until installation is complete and A.C. power is supplied to the unit.
Caution: This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect
both normal and emergency sources by turning OFF the A.C. branch circuit and by diconnecting the unit connector.
Caution: The fluorescent power supply is a sealed unit. The integral, high temperature NiCad battery is not replaceable.
Replace the entire unit when necesssary and recycle or dispose the nickel-cadnium battery properly.
DO NOT USE OUTDOOR.
WIRING
- The fluorescent Power Supply (FPS) and the ballast must be on the same branch circuit
- The FPS requires an unswitched A.C. power source of either 120 or 277 volts. Select the proper voltage lead and cap the unused lead.
- When the FPS is used with a switched fixtures, the A.C. input to the FPS must be connected ahead of the fixture switch. Refere to following illustrations for switched and unswitched fixture wiring diagrams.
Switched Fixture
BALLAST
DISCONNECT
Connections to be made
Wall Switch
Prewired
BLK
BLK
120 or 277Vac
Unswitched Fixture
Connections to be made
BLK
BALLAST
WHT
120 or 277Vac
Select proper voltage lead.
Cap unused lead
277 Vac
120 Vac
BLK (120)
BLK
BALLAST
WHT
WHT
WHT/BLK
WHT
ORG (277)
Prewired
BALLAST
DISCONNECT
WHT
FPS
277 Vac
WHT/BLK
WHT
ORG (277)
120 Vac
BLK (120)
FPS
BALLAST
Select proper voltage lead. DISCONNECT
Cap unused lead
BALLAST
DISCONNECT
UNIT CONNECTOR
UNIT CONNECTOR
DO NOT CONNECT
UNTIL INSTALLATION
IS COMPLETED
DO NOT CONNECT
UNTIL INSTALLATION
IS COMPLETED
COMPLETING THE INSTALLATION
Switch A.C. power ON and join the FPS Ballast Connector. Both ballast disconnectors must be joined.
Clip the base plate to the fixture body. Install lamps.
RED indicator and both lamps must be ON.
Press the RED indicator. The AC ballast is turned off by the FPS. The emergency lamp is now lit by the FPS. After releasing the RED indicator, the fixtures returns to normal operation.
Install the lens.
OPERATION
Normal Mode : A.C. is present. The ballast operates the fluorescent lamps. The FPS is in standby charging mode. The RED indicator provides a visual indication that the battery is being charged.
Emergency Mode: A.C. power failed. The FPS automatically switches to emergency mode. One or two lamps is illuminated et reduced
output for the duration of the discharge time (90 minutes). When A.C. is restored, the FPS switches back to the Normal Mode and resumes
battery charging.
TESTING
The FPS is a maintenance free unit.
Monthly : Ensure that the charge indicator is illuminated. Conduct a 30 second discharge test be depressing the RED indicator. One or two
lamps should operate at reduce output.
Annually: Ensure that the charge indicator is illuminated. Conduct a 90 minutes discharge test by forcing a "Black Out" with circuit
breaker. The unit shall operate as intended for the duration of the test.
Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.
Thomas & Betts
Tél: (888) 552-6467 ext. 547 or 255
Fax: (888) 867-1565
www.tnb.com
12/07 750.1336 Rev. A